Home

InduSoft Web Studio Getting Started Guide

image

Contents

1. Creating the Synoptic Screen synoptic scr Explains how to create a synoptic screen for your application Configuring the I O Communication Driver Explains how to configure an I O communication driver for your application Creating a New Application Use the following procedure to create a new IWS application 1 Select File gt New from the InduSoft Web Studio main menu bar 2 When the New dialog opens click on the Project tab File Project Application name APPL Location c Program Files Indusoft Web Studio v6 0 Projects Browse Configuration file c Program Files Indusoft Web Studio v6 0 Projects4PPLYAPPL APP Target platform CEView Lite Local Interface Operator Workstation Control Room Advanced Server 1 500 tags Runtime for WinCE Select the Project Tab on the New Dialog InduSoft Web Studio Page 37 Getting Started Guide Creating an IWS Application 3 Type the name of your application into the Application name text box for this example type GetStart IWS automatically creates a new directory of the same name and assigns your application file to that directory notice the Configuration file text box in the previous figure To put your application file somewhere other than in the Projects subfolder of InduSoft Web Studio click Browse and navigate to the preferred directory location 4 Select a platform from the Target Platform list for this example select CEVi
2. Loceeb our 2706 2002 16 45 35 me CC On SEH Relay 21001 Closed Error Relay 21001 Main bus powered E Turbine Tei Turbine Temp Standard Failur BUZZ RINGING 2 indusoft Tools for Automation Microsoft Internet Explorer LUS GO EOrATATAN DANA VA Ve jl i0 xj ftodule zl ch ifo 100000 Iva zlkha eie 1 zl E SEH ES SE 100 0000 10 z homie 2 SIE E 200 000 200 0000 1 REH Module 2 wji InduSoft Web Studio Getting Started Guide Web Ready induSoft gt Tools for Automation _ www nduSoft com 877 INDUSOFT InduSoft Web Studio IT Locee our 27m6 2092 16 45 35 Seen Relay 21001 Closed i Error Relay 21001 1 Main bus powered E Si TUS Failures um Standard Turbine Standard Turbine Alarms RED3 Trip Level Su REDI Trip Temp Sum High TARU e indusoft ools for Automation Microsoft Int tnet Explorer InduSoft Web Studio Getting Started Guide Web Ready induSoft gt Tools for Automation www InduSoft com 877 INDUSOFT Getting Started Guide Copyright Windows Windows XP Windows 2000 and Windows NT are registered trademarks of Microsoft Corp in the United States and other countries Other brand or product names are trademarks or registered
3. e lf Tag gt AlrStatus 0 there are no active alarms For Boolean tags only 1 bit 1 4 bit 2 or 16 bit 4 values are returned Getting Started Guide Working with Tags Tag Field Name Description of Value Tag Type Associated with Field R Read Only Associated with Each Field Boolean Real RW Read Write lf 0 Lo alarm is inactive lf 1 the Lo alarm is active LoLo If 0 LoLo alarm is inactive If 1 the LoLo alarm IS active GE H 1 the Rate alarm i IS active pe ss LEE If 1 the Dev alarm is active Sam If 0 Dev alarm is inactive an ae P l 1 Dev alarm is active v k HiHiLimit Limit value for HiHi aam kk at Lmt va for alam fee ww Mgeekiegeg 5 K e 5 unt Limit va for ate alam KE EK ere point value for Deviation alarms o krk RW DevpLimit Limit value for Deviation alarm sz kr RWO DevmLimit Limit value for Deviation alarm 4 vk RW SISIS Au TECT SIS RW 8 va Note If the application tries writing a value outside the range specified in the Min and Max fields the Tags Database will not accept the new value and writes a warning message in the LogWin If you configure both Min and Max properties with the value 0 zero any value applied to the tag type can be written to the tag Caution You cannot use tag fields such as Bit fields to configure Alarm or Trend worksheets Working with Tag Folders You can use tags as communication points with field equipment
4. OK to apply this color to the screen Creating a Screen Title To create a screen title Text object use the following steps Click the Text icon D click on the screen and type Synoptic Screen 2 Double click on the Text object to open the Object Properties dialog 3 When the dialog displays check the transparent check box and set the Text object s background color to transparent 4 Click the Fonts button and modify the font settings for example Type Arial Size 20 Color Blue 5 Move the object to the top of the screen Finished Screen Title InduSoft Web Studio Page 45 Getting Started Guide Creating an IWS Application Page 46 Creating Date Time Text Objects x Note Date and Time are internal tags that hold the current date and current time respectively from the local station The Date and Time tags are available for any application To create Date and Time Text objects use the following steps i 10 Click on the Text icon ER then click on the screen and type Date H HFEEETEE Double click on the Text object to open the Object Properties dialog When the dialog opens enable the Transparent check box and set the Text object s background color to transparent Object Properties __ __ P E Replace Hint Text 10 ad Tag E spressioni Date al Mmmm value l Input Enabled Eet Decimal sl m Password in Copbmm Security Maximum Value l Disable o Select the Text
5. Sample Header Section 10 Type the following information into the spreadsheet provided at the body section of the Modbu001 drvu window Tag Name Type the I O tag name Address Type the PLC Address offset 11 Associate the application tags to the PLC addresses according to the following table Application Tag rasa e e PLC Address Level 1 An 1 4X1 Holding Register 1 Level 2 A0 2 X 2 Holding Register 2 Level 3 A0 3 4X3 Holding Register 3 InduSoft Web Studio Page 59 Getting Started Guide Creating an IWS Application E MODBUO01 DR t Sje x Description Example Modbus J Increase priority Read Trigger Enable Read when Idle Read Completed Read Status em B B Write Trigger Enable Write on Tag Change Write Completed Write Status Station Header a Ce Minf May Address Tag Name Level 1 1 Level 2 2 Level 3 Completed Body Section 12 Save the communication driver sheet File gt Save When prompted to choose the driver sheet number type 1 and click OK to save the MODBUOO1 DRV driver sheet Lee d Sheet number il Cancel Save the Driver Sheet To test the communication driver use the following steps 1 Click the Run application icon Ei on the IWS toolbar to execute the application 2 Right click in the Output window bottom of IWS development environment and select Settings from the pop up menu x
6. Specifying the Device Connection Method va Note InduSoft recommends using TCP IP for performance reasons InduSoft Web Studio Page 67 Getting Started Guide Running Applications from a Remote Station 4 Click OK and leave the Remote Agent running on the remote station 5 Select Project Execution Environment from the main menubar to open the Execution Environment dialog 6 Specify a link type for the Target Station Network IP or Serial Port If you select Network IP type the remote station IP Address into the text box Execution Environment l x Target Application Import CE License Target Station Connect Local Status Network IP 192 168 1 1 C Serial Port co Mi Infrared EE Platform Install system files Jk Only newer files Specifying the Target Station Link Type 7 Click the Connect button to connect to the remote station x Note If the remote station is a CE device click the Install system files button to download the CEView runtime files to the remote station 8 Return to the Execution Environment dialog and select the Application tab Click Send to Target to download the application to the remote station Execution Environment i x Target Application Import CE License Application Path Local C Program Files SInduS oft Web Studio51 Projects GetStart s Target ON Pal Send To Target v Only newer files Send F
7. Uninstalling InduSoft Web Gud 16 Chapter A Working with the IWS Interface snansnnnnsnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnn nnmnnn 19 O02 61 2 ee 19 Using the TU E 21 Reading the Stat s Bal eisrsoessereen orina me eee ee eee aain ee eee 21 Using the Menu Bar assisia eiiiai aa aaeeea riai aaide ainas 22 Using Buerg ele 24 Using the eler 26 Chapter 5 Working with TagS ccccccsseeceseeeeeeeeeeeneeeaeeeseeeeeeeneesaaeesaaeeseaseeeeneeeaneesaneesons 29 Naming Tags and Tag Fields E 29 Ee Rn e a a eee eee eee ee aes 29 Tag WE KEE 30 Workmg with Tag ee 32 Understanding the Tag Tvpoes ENNER 34 Using Array Tags E 34 SING Dare Ee EE 35 Chapter 6 Creating an IWS Application ieee ceeceeeeeeeeceeeeeeeeeeeeeeeeeeeseneeeaneeeeeeesees 37 Creating a New Application cccccccccceccceeececeecececeseueeeseeeeseeceseucessueeeseeeessecesseeesgeeesaes 37 Specifying Project Settings A 39 SAU WA E 40 Creating the Start up Screen Main cr 41 InduSoft Web Studio Page iii Getting Started Guide Contents Creating the Synoptic Screen synoptic ScCrl 45 Creating a Screen Title fax ch2s tics ato teeth al da tol co eg 45 Creating Date Time Text Objects ccecccccsececceeeeecceeeeeceeeeecseeeesseeseeseeeeesseneeenas 46 Creating IM XI ee EEN 47 RESTING ANG AD DIC ATION EE 48 Creating sa Tank OD 6G EE 49 Creating a Level Slider Obert 52 ee ln Le EE EE 54 M STNG LVS PA CARLO ssa sss Fe
8. File names messages and screen text are indicated using bold monospaced text for example D Setup exe Variables and information you must provide are indicated using bold italicized monospaced text enclosed in lt and gt brackets for example Run the lt driver name gt exe file indicates you must provide a driver name Buttons menu options and keyboard keys are indicated in bold Text requiring special emphasis is in bold italic Some information is segregated into Tip Note and Caution boxes as follows Tips provide useful information to save development time or to improve application performance Notes provide supplemental information related to the surrounding text usually the text just preceding the note Cautions provide information necessary to prevent damage or problems when running the application InduSoft Web Studio Page 7 Getting Started Guide About this Publication Mouse and Selection Conventions Because most PCs used for application development run a version of Windows with a mouse this publication assumes you are using a mouse This publication also assumes that your mouse is configured so that the left button is the primary button and the right button is the secondary button This publication uses the following mouse and selection conventions Double click means to quickly click twice on an object with the left mouse button Right click means to click once on an object
9. Getting Started Guide Tag Field Name Description of Value Tag Type Associated with Field R Read Only Associated with Each Field gt Associated with Each Field Boolean Integer Real String RW Read Write _ RW Read Write AlrStatus Specifies whether alarms associated ith the tag require acknowledgement This field has only two possible values e 0 Alarms do not require acknowledgment e 1 Atleast one alarm requires acknowledgment AlrDisable Specifies whether alarms associated ith a tag will become active This field has only two possible values e 0 Enables alarm and when an alarm condition occurs the alarm becomes active 1 Disables alarm so that even if an alarm condition occurs the alarm will not become active HiHi lf 0 HiHi alarm is inactive If 1 HiHi alarm is active lf 0 Hi alarm is inactive wi s v x lf 1 Hi alarm is active Page 31 InduSoftWeb Studio Page3t Web Studio Status integer value of any currently active alarms associated with a tag Each bit of the integer value indicates a Specific status e Bit 0 LSB HiHi Alarm active e Bit 1 Hi Alarm active e Bit 2 Lo Alarm active e Bit 3 LoLo Alarm active e Bit 4 Rate Alarm active e Bit 5 Deviation Alarm active e Bit 6 Deviation Alarm active For example e If Tag gt AlrStatus 2 Hi alarm is active e If Tag gt AlrStatus 3 HiHi and Hi alarms are active simultaneously
10. Overview InduSoft Web Studio uses standard Windows like tools and interfaces to make the product user friendly IWS also provides an integrated unique development environment see figure for easy access to tools and information LI LA o File Edit Yiew Insert Project Tools Window Help Menu Bar Toolbars oy aciAa s hex Siinzme als El e0 Ae lex OT zele glgamglagslwzlcmtoleelses ax RE EN Project NTDemo app zl Screens Group Screen zl Web Pages BG Library LC Symbols Workspace El K HEITE DI x e Name Value ualit Continuous Database Spy Window Output Window aN 2na 1 Status Line Dese gess x 200 0 InduSoft Web Studio Development Environment InduSoft Web Studio Page 19 Getting Started Guide Working with the IWS Interface The development environment consists of the following basic areas Title Bar Indicates the active screen or worksheet Status Bar Provides quick access to actual information Menu Bar Contains the main product options and controls which you can easily access using the cursor or your keyboard keys Auxiliary Toolbars Provide shortcuts to the main commands used in the development environment Displays Building Toolbars Contain features and tools used to create or edit objects and dynamics in the application screens Workspace Provides tree view control from which you can access project worksh
11. PM Fa Viewing Web Files 4 Select Project Settings from main menubar and select the Web tab You must specify the Server station IP address for the station on which you are running IWS or CEView the Data Server IP Address field during runtime The Web Thin Client station exchanges on line data tag values with the station specified in this field 6 You also must specify the URL path to the Web files files saved in the Web subfolder in the URL field The URL depends on the Home directory configured for your server station Web Server If the application s Web subfolder is the home directory you can configure the Web settings as shown in the following figure to test the Web Thin Client locally Project Settings x Identification Options Runtime Desktop Web Preferences Data Server IP Address Send Period ms 127 0 0 1 1000 URL http A7 27 0 0 17 Tl Disable Remote Client Commands Auto Screen Scaling IV Enable ToolTips Enable File Compression ples Security os Log T Enable File ame Cancel Specifying the Project Settings Page 64 InduSoft Web Studio Running the Web Based Application Getting Started Guide va Note Microsoft provides Web servers for any Microsoft operating system Consult your Microsoft documentation for information about installing and configuring a Web Server 7 After configuring the Web settings click OK to close the Project Settings dialog 8
12. Read When Idle text box Boolean values 1 yes and 0 no Type 1 so IWS will continue reading these values from the PLC addresses configured in the body of this driver worksheet Enable Write on Tag Change text box Boolean values 1 yes and 0 no Type 1 so IWS will write the value from the tags configured in this driver worksheet whenever the tags change value Station text box indicates the I O device number to be accessed by this driver Typically the PLC is specified as Device 1 Type 1 Header text box Type a reference value from the following table x Note You must use a driver specific format in the Header text box The format for a ModBus protocol is lt reference for the type of register gt lt initial offset for the first stored value gt The following table provides a list of acceptable register types for the MODBU driver Register Type Description InduSoft Web Studio Creating an IWS Application Getting Started Guide ox Coll Status AX input Status 3X input Register AX Holding Register ID Slave ID Number For example 4X 0 signifies a Holding Register with an offset of zero EC MODBUO01 DR Description Example Modbus I Increase priority Read Trigger Enable Read when Idle Read Completed Read Status ee elm ke mT Write Trigger Enable Write on Tag Change Write Completed Write Status Station Header DR E E Mir hi el Tag Name Address Div 1 bs 4 e
13. ac aa hte leila ee atlas 55 Configuring the I O Communication Driver 56 Chapter 7 Running the Web Based Application ccccscccsseeeesseeeseeeeeeeeeeeeeeseeeeseaees 63 Chapter 8 Running Applications from a Remote Station cc ceccccseeeeseeeeeeeeeeeeeeeeeees 67 Page iv InduSoft Web Studio induSoft gt Chapter 1 Welcome to InduSoft Web Studio InduSoft Web Studio or IWS is a powerful integrated tool that exploits key features of Microsoft Windows NT 2000 XP and Windows CE and enables you to build full featured SCADA Supervisory Control And Data Acquisition or HMI Human Machine Interface applications for your Industrial Automation business Overview This InduSoft Web Studio Getting Started Guide is intended for individuals using InduSoft Web Studio for the first time This publication will help you quickly familiarize yourself with the basic functions of InduSoft Web Studio va Note InduSoft assumes you are familiar with the Windows NT 2000 XP operating system However if you need assistance as you work we suggest using the Help feature on the Windows desktop Start menu This Getting Started guide is divided into the following chapters This chapter provides a brief overview of the InduSoft Web Studio product including its main features and system requirements Chapter 2 About this Publication Provides information about this publication such as conventions used and rela
14. button to accept the default settings 4 Right click on the new screen and select Background color from the pop up menu Select the gray color and click OK to apply that color to the screen ive Paste Ctrl V Select All gt Test display Background Fi xi Color Grid Settings OK Wi Screen Attributes eem TTT Uelech CT Background color OBB BBE Imi E mim Close Ctrl F4 More Colors Fill Effects Disable Drag Ctrl D Open the Background Color Dialog and Select a Gray Color 5 Create a Text object by clicking on the Text icon D 6 Click on the screen and type the following text Welcome to the InduSoft Sample Application Page 42 InduSoft Web Studio Creating an IWS Application Getting Started Guide 7 10 11 Double click on the Text object to open the Object Properties dialog Click here to openthe Object Properties dialog Object Properties sal Replace Hirt Caption welcome to the InduSott Sanple Application Use this dialog to aton Let El Border UE W Transparent set properties for Background O M Eten translation the text object Click on the Text Object za Notes Double clicking on any object opens an Object Properties dialog containing parameters related to that object The features on the dialog change depending on the item selected from the combo box The combo box list changes depending on which properties you applied to the object The Object P
15. can also operate the application through a standard Web browser Internet Explorer or Netscape The product consists of two parts The development system software which runs on a desktop laptop or industrial PC running Windows NT 2000 XP The run time system software which runs on any operator interface workstation running Windows NT 2000 XP or Windows CE Note The run time system software for the Windows CE operating system CEView is usually pre loaded on the HMI If necessary you can update the CEView version of the development system software by downloading the current version to the HMI or PDA You can run IWS applications on your development workstation or download it to a run time station through a serial or TCP IP connection and run the application using the IWS or CEView run time software The workstation processes scan data from connected devices according to parameters defined in the application and then react to display store and upload the data InduSoft Web Studio Welcome to InduSoft Web Studio Getting Started Guide Main Features The InduSoft Web Studio product offers the following features and functions Integrated Windows development environment with toolbars dialogs and menus Shortcut menus which can be accessed by right clicking on any area of the development environment options vary according to context Customizable fly over toolbars Tasks objects and controls org
16. object and click on the Text UO icon BA to apply this dynamic to the object Double click on the Text object to open the Object Properties dialog again Type Date into the Tag Expression field as shown in the following figure to configure the Text I O dynamic During the runtime IWS replaces the chars you configured for the Text object with the value of the Date tag Click on the Text icon a again to create a time Text object Click on the screen and type Time Double click on the Text object to open the Object Properties dialog Enable the Transparent check box and set the background color to transparent InduSoft Web Studio Creating an IWS Application Getting Started Guide 11 Select the Text object and click on the Text I O icon BA to apply this dynamic to the object 12 Double click on the Text object to reopen the Object Properties dialog and type Time into the Tag Expression field see figure to specify the internal tag for the Text I O dynamic Object Properties Ss 8 Replace Hint Text 0 sl Tag Espression Time ba Mmmm value Input Enabled Frat Decimal r Password 7 Confirm Security Mssomum Yale Digable 0 During runtime IWS replaces the chars with the Time tag value This figure illustrates how your screen should look after creating the Date and Time text objects Finished Date and Time Objects Creating an Exit Icon To create an Ex
17. the Index tag to set the array position of the Level tag and show the level for any of the three tanks in the same object For example When Index 1 the object shows the level of Tank 1 Level 1 Index 2 the object shows the level of Tank 2 Level 2 Index 3 the object shows the level of Tank 3 Level 3 6 Click OK to confirm the tag replacement Because you have not previously created an Index tag in the Application Tags database IWS displays the following message Cs 6 hls eh Tag Index does not exist VI J Would you like to create this tag Page 50 InduSoft Web Studio Creating an IWS Application Getting Started Guide 7 Click Yes to create the Index tag from the screen editor Note that you do not have to open the application Tags database again to create tags as you configure the application xi Name Index Array Size NEE Type Integer Description Tank index number Web Data local sl Cancel New Tag Dialog 8 You must configure the Index tag Type as Integer Array Size as O and Web Data as Local Because the tag is Local it can have different values for the Server station and the Web Thin Client station at same time Consequently the local user Server station can be monitoring the level of one tank for example Index 1 Tank 1 while the remote user Web Thin Client station is monitoring the level of another tank for example Index 2 Tank 2 Th
18. trademarks of their respective owners Copyright 2003 InduSoft Ltd All rights reserved worldwide This document shall not be reproduced or copied in any manner without expressed written authorization from InduSoft The information contained within this document is subject to change without notice InduSoft Ltd does not guarantee the accuracy of the information PN IND GSG WD002 Page ii InduSoft Web Studio induSoft gt Contents Chapter 1 Welcome to InduSoft Web Studio cc ccecccsceeeeeeeeeeeeeeeeeeeeeeeeaeessaeeeseeeeseanes 1 KEE ge EE 1 AD GUI IMGU SON VV Cy e lO E 2 Mam EE 3 System Heourements rreren 5 Chapter 2 About this Publication 0c cccceccececeeeeeeeeeeeeeeeeeeceneeeeaeeseaeeseeseesenessaseeseeesoones 7 T COR VSN EE 7 Mouse and Selection CONVENTIONS ccccceccccseeeeeceeeeeeseeeeeeeeeeeeeeeeeeeseeeesaaeeeeseeeeesaeeessaees 8 Windows CONVENTIONS ccccceecccseeccceececececaueeeceeeeceueeceaeesseeeeseeessaeessueeeseueessaeesseeeseeesaas 8 Related Publications ccccceccseccceeeceeccueeseeccaeeceeeceueceuceseecuesaueecseesuessueeseeesseessuseseeess 10 Chapters Installing the Software sissien 11 Installing InduSoft Web Studio 20 0 0 ceecccccseeeeeeeeeeeeeeeeeeseeeeeeseeeeeseeeeeeseaeeeeseeeeeesaeeeesaees 11 Starting InduSoft Web Gud 13 Installing CEView Software ceccccceecccecseeeeeseeeeeeseeeeeeeeeeeeseeeeeesaeeeeseaeeeesaaeeeeseeeeesaeeeesaees 13
19. up connection with the RAS Server of remote stations Functions to send e mail from IWS or CEView Real time project documentation Screen resolution converter Note IWS provides different product types for each level of application responsibility However IWS does not support some features in certain product types such as CEView You can review the TargetVersions pdf document on the InduSoft Web Studio CD ROM for detailed information about the limitations of each product type limitations InduSoft Web Studio Welcome to InduSoft Web Studio Getting Started Guide System Requirements To develop and run applications with IWS you must install the following hardware and software IBM compatible computer with an Intel Pentium II compatible processor or higher Windows NT 2000 XP operating system for development Windows NT 2000 XP or Windows CEv3 00 or Windows CE NET operating system for runtime Minimum of 128MB random access memory RAM 256MB or higher recommended MS Internet Explorer 6 0 or higher Minimum of 150MB free hard disk space required for the program without any application files 300MB is recommended CD ROM drive can be on a different computer Standard keyboard with function keys F1 through F12 Parallel printer port optional 100 IBM compatible VGA or SVGA display adapter with 32MB Video RAM VRAM optional for runtime when running Web based applications Microsoft compatible pointing d
20. with the right mouse button Click and Select both mean to click once on an object with the left mouse button In general you click on buttons and select from lists Select also means to use your pointing device to highlight or specify an item on the computer screen Selecting an object with a touch screen is usually the same as selecting with a mouse except that you use your finger to touch select a screen object or section You can also use keys on your keyboard to select objects options For example you can use the Tab key to move between options the Enter key to open menus and the Ctrl or Alt keys in combination with a letter key for example Ctrl S to select a menu option having an underlined letter Save Drag means using your mouse cursor to move an object to a new location on your computer screen Position your cursor over the object and press the mouse button As you move the mouse you move the object Usually an outline of the object will move along with the cursor When you have the object positioned where you want it release the mouse button Windows Conventions Page 8 This publication uses the following Windows conventions Dialog boxes or dialogs are windows that allow you to enter information Textboxes or fields are areas in dialogs where you can type in text Radio buttons are white circles in which a black dor 2 appears or disappears when you click on the button Typically the bl
21. Click the button to toggle between the two options Resize tiles the IWS window Maximize maximizes the IWS window to fill your computer screen Exit or Close button Click this button to automatically save the database then close IWS If you modified any screens or worksheets IWS prompts you to save your work This button function is similar to the Exit command on the File menu va Note Closing the development environment does not close the IWS run time tasks To close your run time tasks click the Stop icon E on the Execution toolbar or select Project Stop Application option from the main menu bar Reading the Status Bar The status bar located along the bottom of the IWS window contains fields used to identify toolbar buttons and provide information about the active screen if any Create a new document or project CAP NUM SCAL ID 0 52 7 64 W 205 H 114 No DAAG 4 Sample Status Bar The fields are as follows from left to right Hint field Provides a short description of any toolbar button or display object touched by the cursor Caps Lock field Indicates whether the keyboard Caps Lock key is on CAP or off empty Num Lock field Indicates whether the keyboard Num Lock key is on NUM or off empty InduSoft Web Studio Page 21 Getting Started Guide Working with the IWS Interface Scroll Lock field Indicates whether the keyboard Scroll Lock key is on SCRL or off empty ID f
22. Close all screens in the screen editor Window Close All and then select Tools Verify Application to update the Web Settings for the Web pages gt Caution You must execute Tools Verify Application after changing any settings in the Project Settings menu To test your Web based application use the following steps 1 Click on Run application icon EI on the IWS toolbar to execute the application locally on the Server station 2 Open an Internet Browser Microsoft Internet Explorer or Netscape and type the URL address to open the synoptic htm1 screen from the Server station for example hittp 7127 0 0 1 svnoptic html 3 When the Log On dialog displays in the Browser see the following figure type guest in the User Name field then click OK to open the synoptic html screen in the Browser CC x User Name guest Password Cancel Logging On as Guest InduSoft Web Studio Page 65 Getting Started Guide Running the Web Based Application Notice that you can modify the level of any tank locally Server Station using the Viewer run time module or remotely Web Thin Client using the Browser Synoptic Screen Date 11 15 2002 Time 10 41 33 D 100 Tank 2 L SPRDDR Modifying the Tank Level x Note A Web Thin Client requires an ActiveX component ISSymbol ocx to handle screens on the Browser If you connect the Web Thin Client to the Internet this component is downloaded an
23. For example if the size of TagA is 3 the tag positions could be TagA 0 TagA 1 TagA 2 and TagA 3 InduSoft Web Studio Working with Tags Getting Started Guide In many cases using array tags will simplify the configuration task For example if you want a display to monitor each tank you could use array tags to configure a single display containing tags linked to any tank using the tk tag as an index containing the tank number For example pressure tk temperature tk and temperature tk 1 An array index can be a tag a numeric value or an expression with the arithmetic operator x Note When referring to an array having an index with the arithmetic operation you must use the following syntax lt ArrayTagName gt lt NumValuel gt lt NumValue2 gt Where lt NumValuel gt and lt NumValue2 gt can be integer tags or numerical constants For example temperature tk 2 temperature tk 6 or temperature TagA TagB Using array tags in an IWS task can save a significant amount of application development time For example if you wanted tag points related to the temperature of four tanks the conventional configuration method is temperaturel high temperature on tank 1 temperature2 high temperature on tank 2 temperature3 high temperature on tank 3 temperature4 high temperature on tank 4 Using array tags simplifies this task as follows temperature j high temperature on tank j
24. LAML Display Lami NT 2000 9x v1 04 LAUER LAUER GMBH Lauer Standard Protocol PCS Light NT 2 MATSU MATSUSHITA FP1 Cxx NT 2000 9s v1 02 MBLAU MICROBLAU TD3000 NT 2000 1 20 MISTC OPTO22 MISTIC Protocol OPTO22 Controller NT 2000 ai MITSA MITSUBISHI Protocol Melsec 4 NT 2000 9x CE x86 5h U MODBUS Protocol RTU ASCII NT 2000 9 CE x86 Sh3 MODPL MOTCP MODBUS Protocol RTU ASCI via TCP IP NT 2000 9x C sl Select gt gt Selected drivers DLL Description oo O Communication Drivers Dialog 3 Select a driver from the Available drivers list for this example use the MODBU Modbus Protocol RTU ASCII driver then click the Select button or double click on the driver The program moves the selected driver to the Selected drivers list 4 Click OK to close the window and save your changes x Note To remove a driver from Selected drivers select it and click Remove 5 A boxed plus sign displays beside the Drivers folder Click the plus sign or double click on Drivers the word or folder to display the subfolders Page 56 InduSoft Web Studio Creating an IWS Application Getting Started Guide for any drivers you added For this example a MODBU subfolder displays 6 Right click on the MODBU folder and select Settings from the pop up menu ER Project GetStart APP Fy Drivers 30 a OPC Insert Select Settings from the Pop Up Menu 7 When the Commun
25. Name Value ualt Continuous Cut Copy Delete Select All E Pause e KA E A Hide window d KIDLAT i Change log settings x 33 Y 4 ds Select Settings from the Popup Menu Page 60 InduSoft Web Studio Creating an IWS Application Getting Started Guide 3 Enable the Field Read Commands Field Write Commands and Serial Communication options on the Log Settings dialog see the following figure then click OK x Log Options Log Tags IV Field Read Commands J Recipe Report V Insert date time Je Field write Commands Display Open Close DDE Messages Logon Logout OPC Messages Trace Messages TCP IP Messages IV Serial Communication Cancel Specifying the Log Options 4 Now you can start the application and monitor the communication messages from the Output window x Note You can also monitor communication messages from the Log Win window Project Settings gt LogWin InduSoft Web Studio Page 61 Getting Started Guide Creating an IWS Application Page 62 InduSoft Web Studio KEE Tools for Automation ab Chapter 7 Running the Web Based Application This chapter explains how to prepare your application to run on the Web x Note IWS stores all application screens in the Screens folder located on the Graphics tab in the Workspace To open your application screen use the following steps 1 Expand the Screens folder and double click on synoptic scr Wor ksp
26. View Installing InduSoft Web Studio InduSoft Web Studio IWS provides development tools for all InduSoft applications and it runs on the Microsoft Windows NT 2000 XP operating systems You can install IWS from the InduSoft Web Studio installation CD ROM or download the installation files from the InduSoft Web site at http www indusoft com For Windows CE applications you use IWS to download CEView run time software to the Windows CE HMI using a serial or TCP IP link The IWS installation program automatically creates necessary directories copies files to your hard drive and creates the IWS icons in your desktop folder za Notes e You must have Administrator privileges on a Windows NT 2000 XP workstation to install InduSoft Web Studio You must uninstall all previous versions of InduSoft Web Studio or install the newer version in a different directory Also you cannot install the same version of IWS in two different paths of the same computer InduSoft Web Studio Page 11 Getting Started Guide Installing the Software Use the following procedure to install IWS from the CD ROM 1 Turn on the power to your development computer Windows NT 2000 or XP and be sure that no other programs are running 2 Insert the installation CD ROM into the CD ROM driver x Notes A CD Browser window should display automatically If not you can start the program manually from Windows Explorer Navigate to the D Installati
27. WS be sure to back up any files you might need later into the InduSoft Web Studio Projects folder Also be sure you have the current or newest version of the IWS installation CD ROM or diskettes so you can re install the software again You will lose the product softkey license when you uninstall IWS 1 From the Windows taskbar select Start Settings Control Panel to open the Control Panel A Taskbar amp Steet Menu A Folder Optio 7 Active Dasktop Opening the Control Panel idF 2 Double click on the Add Remove Programs icon Podane in the Control Panel window 3 When the Add Remove Programs Properties dialog displays see figure select InduSoft Web Studio from the list and click the Add Remove button 4 When the Confirm File Deletion dialog displays click the Yes button Page 16 InduSoft Web Studio Installing the Software Getting Started Guide The Uninstall Shield Wizard and the Remove Programs from Your Computer dialogs display Remove Programs From Your Computer unlnstallShield will remove the software InduS oft Web Studio from your computer Please wait while each of the following components is removed Shared program files Standard program files Folder items Program folders Program directories A A AS h ONS Program registry entries Uninstall completed Some elements could not be removed You should manually remove items
28. ace Es gi Project GetStart APP CH Screens Kl main scr synoptic scr Group Screen Web Pages G Library Symbols eat Database hn Graphics Ee Tasks Comm Select scynoptic scr 2 Select File Save All as HTML to save all screens in HTML format SE New Chrl ty E Open Project G Open File ChLo Close Ctrl F4 Close All Ki gave Chris Save Os Gl Save All E Save As HTML Save Screen Group as HTML Save ll As HTML Import Wizard Print Setup Print Preview InduSoft Web Studio Exit Saving Screens in HTML Format InduSoft Web Studio Page 63 Getting Started Guide Running the Web Based Application 3 After executing this command the Web files are stored in the Web subfolder of the application directory lol x See C Program Files InduSoft Web Studio51 Projects GetStart Web Edit View Favorites Tools Help Ei File Q Back v gt wi a Search Ki Folders Hab Address e C Program Files InduSoft Web Studio5S1 Projects GetStart web D Go Date Modified fs class Ist 1KB LST File 6 16 2002 11 32 PM E synoptic html 2KB WNetscapeH 6 16 2002 11 32 PM File and Folder Tasks Z CH Make a new folder ae E synoptic scc 6KB SCC File 6 16 2002 11 32 PM a frags ene E synoptic taal 1KB TAGL File 6 16 2002 11 32 PM E3 Share this Folder E tagi bin 3KB BIN File 6 16 2002 11 32
29. ack dot indicates that the option or function is enabled active The absence of a black dot indicates the option or function is disabled inactive Check boxes are white squares in which a check V appears or disappears when you click on it with the cursor Typically the check indicates that the option or function is enabled active The absence of a check indicates the option or function is disabled inactive InduSoft Web Studio About this Publication Getting Started Guide Buttons are icons in boxes that appear pressed when you click on them Lists are panes white boxes in windows or dialog boxes containing two or more selectable options Combo boxes have arrows that when clicked show part or all of an otherwise concealed list Combo Bo Si Click arrow button to display list Using a Combo Box Interface or Development Environment refers to the entire InduSoft Web Studio window Dockable windows are windows that you can drag to an edge of the interface and merge with that edge Toolbars are dockable windows that contain only buttons and text boxes va Note The dialogs and procedures described in this publication are valid for Windows 2000 Some terms may vary according to the operating system type language and version you are using InduSoft Web Studio Page 9 Getting Started Guide About this Publication Related Publications You may want to review the following publications for ad
30. and network diagnostics InduSoft Web Studio Page 3 Getting Started Guide Welcome to InduSoft Web Studio Page 4 Powerful and flexible Tags Database Boolean Integer Real and String tags array tags classes and indirect tag pointers Open architecture with API exchanges and tag values with external software Translation editor which enables you to translate an application into several different languages and switch between them while the runtime system is online TCP IP client and server modules to exchange tag values and configure redundancy systems More than 200 drivers for different devices such as PLC from several manufacturers such as Allen Bradley Siemens GE Fanuc as well as standard protocols such as MODBUS RTU ASCII DeviceNet Profibus Interbus and so forth OPC Server and OPC Client with integrated OPC Browser Screen and object password protected runtime security 256 levels Logical expressions and a scripting language with more than 200 functions Recipe and Report ASCII UNICODE and RTF formats builders integrated into the product Event scheduler based on date time or data condition 100ms resolution Multi layer application which means modular worksheets and screens can be merged easily to other applications Full integration with PC based control programs imports tag databases such as ISaGRAF SteepleChase Think amp Do and ASAP Dial Up functions to trigger monitor and hang up a dial
31. anized in a tree view explorer Full featured objects and dynamics the ability to modify object properties execute commands or inset values to tags used to build screens on the fly at runtime Configurable objects such as buttons rectangles ellipse polygons lines and text Dynamic properties such as bar graphs color resizing position hide unhide rotation command hyperlink and text input output Online and historical alarm list displays Online and historical trending Alignment and distribution tools Background bitmap layer creation and editing Graphics importation Active X object containers Online remote management and configuration Microsoft DNA architecture compliance with full OPC and XML support Web interface enabled which exports application screens to a thin client through the Internet intranet and by exchanging data online through the TCP IP protocol Symbol library with more than 100 symbols and dynamic objects such as pushbuttons meters sliders switches text and numeric displays LED style indicators pipes bumps icons vehicles valves frames motors gauges and common controls Debugging tools Database Spy window to monitor force tag values and execute functions LogWin module to record OPC DDE and TCP IP transactions modules activation trace tags and so forth Cross referencing to locate tags throughout the project Online system
32. ct GetStart APP lication Tags Datasheet View fo he Tag List 0 1 Classes 4 23 Shared database 4 23 Internal Tags E E Security ed H Event Settings Application Tags Folder Use the following procedure to create a new tag 1 Double click on the Datasheet View icon to open the Application Tags worksheet 2 When creating a new tag you must set the following main properties Name Specify a unique tag name All tags must have a unique name Array Size Specify the number of elements for an array tag For simple tags you must specify zero Type Specify the data type to be supported by the tag Boolean Integer Real String or Class Description optional Type a description of the tag for documentation purposes only Web Data Specify the communication behavior of the tag between the Server and the Web Thin Client stations LI Specify Local if you want the tag to have independent values in the Server and Web Thin Client stations LI Specify Server if you want the tag to share the same value in the Server and Web Thin Client stations Page 40 InduSoft Web Studio Creating an IWS Application Getting Started Guide 3 Use the following parameters to create a tag for the sample application es Application Tags ioj x Description web Data Level E Integer Level ofthe tank Sewer DT Notice that Array Size 3 was specified for each tag Each array element relates to o
33. ctions within the program This section describes the function and default location of each toolbar Notes All toolbars are dockable screen objects You can move a toolbar to a different screen location by clicking on its title bar and dragging it toa new location For more information about the toolbars discussed in this section see the InduSoft Web Studio Users Guide and Technical Reference Manual The following toolbars contain general purpose tools and they are located across the top of the workspace just below the menu bar by default Standard toolbar Allows you to perform general actions such as file management and printing functions Standard Standard E A Er E EER A Standard Toolbar Tag Properties toolbar Allows you to create locate and access different tags and their properties amp E th Tag Properties Toolbar Execution Control toolbar Allows you to execute and manage an application locally or from a remote location E a Execution Control Toolbar InduSoft Web Studio Working with the IWS Interface Getting Started Guide Web toolbar Allows you to open HTML files che e ek 621 sl 2 Web Toolbar Align and Distribute toolbar Allows you to edit screen objects lt SO bam dhl west O oa aCe d Align and Distribute Toolbar The following toolbars contain screen editing tools These toolbars are located along the right side of th
34. d registered automatically Otherwise you must copy the ISSymbol cab from IWS s BIN subfolder and paste it into the lt OSPath gt System32 directory on the Web Thin Client station Use the WinZip utility to unzip extract the files from TSSymbol cab into the lt OSPath gt System32 directory and register the TSSymbol ocx using the regsvr32 ISSymbol ocx command Page 66 InduSoft Web Studio induSoft gt Tools for Automation ab Chapter 8 Running Applications from a Remote Station This chapter explains how to run your application from a remote location After configuring an application and testing it locally on the development station you can download it to a remote run time station that is running IWS on Windows NT 2000 XP or CEView on Windows CE 1 From the remote target station select Start gt InduSoft Web Studio InduSoft Remote Agent to verify that the Remote Agent CEServer exe is running 2 When the Remote Agent dialog displays click the Setup button x Connection status Not connected to remote client Log AA Device connection via Get Chart Network TCP IP _ Setup Local IP 192 168 23 42 Exit Verifying the Remote Agent 3 When the Setup dialog displays click Serial or TCP IP to specify how the device is connected to the development station Setup eee Device Connection Serial Port come Advanced Ge TCPAR E C Inira Red Users Cancel
35. ditional information about InduSoft Web Studio InduSoft Web Studio Users Guide and Technical Reference Manual Provides detailed information about using InduSoft Web Studio and explains all its features and functions InduSoft Web Studio Training Manual Describes how to build an application step by step with the main product features You can use this document as a self training manual Drivers User Guides Explain how to configure individual InduSoft drivers according to their unique protocol characteristics One customized user guide is included with each InduSoft driver va Note These publications are located in the Documentation folder on the InduSoft Web Studio CD ROM IWS installs the Driver User Guides in the DRV subdirectory of the InduSoft Web Studio folder Technical information also is available from the Help menu on the IWS menu bar Page 10 InduSoft Web Studio induSoft gt db Chapter 3 Installing the Software This chapter provides instructions for installing starting and uninstalling InduSoft Web Studio and CEView The information is organized as follows Installing InduSoft Web Studio Explains how to install InduSoft Web Studio on your computer Starting InduSoft Web Studio Explains how to run InduSoft Web Studio Installing CEView Software Explains how to install CEView on your computer Uninstalling InduSoft Web Studio Explains how to uninstall InduSoft Web Studio and CE
36. e Current Tag The following figure illustrates how your screen should look after creating the slider object bottom right a Screen with the New Slider InduSoft Web Studio Page 53 Getting Started Guide Creating an IWS Application Selecting a Tank To select a tank use the following steps l 2 3 A Page 54 Click on the Text icon a to create a Text object Click on the screen and type Tank Double click on the Text object to open the Object Properties dialog Enable the Transparent check box and set the background color of the Text object to transparent Select the Text object and click on the Text UO icon BA to apply this dynamic to the object xi Replace Hint Text 1 0 sl Tag Expressiory Index ES Mmimum value H I Input Enabled Get Decimal sl IT Password IT Confirm Ser Maximum Value 3 Security Disable fo Double click on the Text object to reopen the Object Properties dialog and type Index in the Tag Expression field to specify this internal tag for the Text I O dynamic Enable the Input Enabled check box to permit entering a new value for the Index tag during runtime Type 1 in Minimum Value field and 3 in the Maximum Value field During runtime IWS will replace the characters configured in the Text object with the Index tag value Finally select File gt Save from the main menu bar and save the screen as Synoptic Scr InduSoft Web Studio Creatin
37. e WinCE device 3 Click the Setup button in the Remote Agent dialog and configure the link serial or TCP IP to connect the WinCE device to the Windows NT 2000 XP computer va Note For better performance InduSoft recommends using a TCP IP link between the WinCE device and the Windows NT 2000 XP computer to download and upload files 4 Start IWS on the Windows NT 2000 XP computer 5 Select Project Execution Environment from the main menu bar Page 14 InduSoft Web Studio Installing the Software Getting Started Guide 6 When the Execution Environment dialog displays select a connection type Network IP or Serial Port and configure its settings for example COM Port or IP Address Execution Environment x Target Application Import CE License M Target Station Connect Local Network IP 192 168 1 0 Status Serial Port com Advanced E nftared Install system files IR Oniy newer files Close Execution Environment Dialog 7 Click the Connect button to connect IWS to the WinCE device 8 Click the Install System Files button from the Execution Environment window Target tab to download the CEView files to the WinCE device InduSoft Web Studio Page 15 Getting Started Guide Installing the Software Uninstalling InduSoft Web Studio If you must remove IWS from your system follow these instructions Caution Before uninstalling I
38. e following figure illustrates how your screen should look after creating the tank object bottom center Screen with New Tank Object InduSoft Web Studio Page 51 Getting Started Guide Creating an IWS Application Creating a Level Slider Object To create a level slider object for your application use the following steps 1 Click the Library icon to open the symbols library 2 Select sliders from the list then double click on any slider object in the display see following figure to add it to the screen amp Library Sarows 5 SS E Le E i common controls conveyors date time filebrowser frames icons links for nt meter motors ul a a 8 DC D pid Selecting a Slider Object 3 Double click on the slider to open its Object Properties dialog A slider is a group of different objects and dynamics from IWS rectangle position and so forth You can modify the properties of this object by selecting the object or dynamic from the Group of Symbols combo box For this example you will modify just the tag associated to the object 4 Click the Replace button to associate a tag to the object Page 52 InduSoft Web Studio Creating an IWS Application Getting Started Guide 5 When the Replace dialog displays type Level Index in the topmost New Tag field then click OK to confirm the tag replacement Replace ai W Analogyalue_ Lal Level Index Replacing th
39. e interface window by default and they are enabled only while you are editing graphic screens Mode toolbar Allows you to edit your screens Made EB Ip oe 7 le Mode Toolbar Bitmap toolbar Allows you to access the bitmap screen editor tools This toolbar is available only when the Background Picture layer is active You enable the Background Picture layer in the Screen Attributes dialog Bitmap Toolbar va Note The Bitmap toolbar is hidden by default Static Objects toolbar Allows you to create polygons rectangles lines and other objects for your screen Static Objects e t e e H Li a Static Objects Toolbar InduSoft Web Studio Page 25 Getting Started Guide Working with the IWS Interface Dynamic Properties toolbar Allows you to apply dynamics to objects or a group of objects Dynamics enable you to modify object properties on the fly during runtime according to tag values Some dynamics also enable you to execute commands or insert values set points to the tags Dynamic Properties x 2 a iat Th gt 6 T Dynamic Properties Toolbar Active Objects toolbar Allows you to create dynamic objects Active objects typically require more parameters than static objects and provide embedded dynamics xl i a l m Be oe ER E E Active Objects Toolbar Using the Workspace The IWS Workspace window is a user friendly interface that enables you to quickly find and or create an
40. eets InduSoft Web Studio Working with the IWS Interface Getting Started Guide View Contains options that enable you to manage which tools and toolbars are visible in the development environment This menu also provides shortcuts to the dialogs you open most frequently enables you to customize your toolbars restore defaults open the libraries zoom unzoom and set screen attributes Insert Contains options that enable you to create and configure a variety of application tags tag classes documents drivers users security settings screens and ActiveX objects Project Contains options to execute applications locally and remotely and provides links used to configure general application settings Tools Contains options that provide links to auxiliary tools Window Contains options that enable you to manage open displays and worksheets Help Contains options that link to information about IWS and InduSoft x Note e The menu bar is dockable e If you right click on the menu bar a pop up menu displays From this pop up you can restore the default location of the menu bar and toolbars You also can use this pop up to hide toolbars and windows and to customize the development environment InduSoft Web Studio Page 23 Getting Started Guide Working with the IWS Interface Using the Toolbars Page 24 IWS provides several toolbars containing icons shortcuts that enable you to perform different a
41. eets and screens Database Spy Window Provides a debugging tool which you can use to monitor and force tags and to execute functions Output Window Displays debugging messages Displays Worksheets Provides an area where you can edit screens and worksheets Note The preceding figure shows the development environment areas and windows in their default position You can customize this environment as needed by changing the position of the areas You can right click the mouse almost anywhere inside the development environment to display a pop up menu similar to the following figure relating to the context of where you clicked E Standard EX Tag Properties iv Execution Control EX Web Bitmap EX Dynamic Properties iv Mode v Static Objects E Active Objects EX Align and Distribute hel Workspace Alk 0 Fa Output Alk 1 E Database Spy Alk 2 Customize Restore Default Sample IWS Pop Up Menu Page 20 InduSoft Web Studio Working with the IWS Interface Getting Started Guide Using the Title Bar The title bar located along the top of the IWS window displays the InduSoft Web Studio icon the product name and the name of the active open screen or worksheet if any InduSoft Web Studio Display Mi x Typical IWS Title Bar The title bar also contains the following three buttons from left to right Minimize button Click this button to minimize the IWS window Resize Maximize button Q
42. evice such as a mouse trackball or touch screen One or two COM ports and adapters for downloading applications optional Ethernet connection for downloading applications optional Note IWS is UNICODE compliant and will not run on a non UNICODE compliant operating system such as Windows 9x ME You can however run the Web Thin Clients of IWS applications on non UNICODE operating systems InduSoft Web Studio Page 5 Getting Started Guide Welcome to InduSoft Web Studio Page 6 InduSoft Web Studio induSoft gt Chapter 2 About this Publication This chapter provides the following information about this InduSoft Web Studio Getting Started Guide and other InduSoft publications Text Conventions Describes the text formatting conventions used in this publication to help you read and assimilate information quickly Mouse and Selection Conventions Describes the conventions used in this publication for using a mouse and selecting objects in a Windows environment Windows Conventions Describes conventions used in this publication for working in a Windows environment Related Publications Lists other InduSoft publications available on the IWS installation CD ROM you can read for more information about the InduSoft Web Studio product Text Conventions This publication uses special formatting to help you quickly identify certain items as follows Titles labels and new terms are indicated using italic text
43. ew Standard then click OK to proceed x Note You use CEView Lite and CEView Standard target platforms for WindowsCE compliant run time applications 5 When the Project Wizard dialog displays select Empty Application from the Template list click the 640 X 480 radio button to specify the application resolution and then click OK x Template ge Resolution C 240 x 320 320 x 240 C 640x240 640x 480 800x600 1024x768 1280 x 1024 m Shared Tags Name lt None gt s Cancel Specifying an Empty Application with 640X480 Resolution The new application file name displays in the Workspace window For this example the file name is Project GetStart APP Page 38 InduSoft Web Studio Creating an IWS Application Getting Started Guide Specifying Project Settings You can use tabs on the Project Settings dialog to apply certain parameters to the entire project For example Use the Identification tab to provide information that identifies the project application such as project description revision number Company name Author s name field equipment and general notes Use the Options tab to specify automatic translations alarm history pc based controls target systems communication drivers OPCs and TCP ports Use the Runtime Desktop tab to enable disable the run time desktop parameters Use the Web tab to specify data server IP addresses send periods in mi
44. g an IWS Application Getting Started Guide The following figure illustrates how your screen should look when you are finished creating your application Synoptic Screen Date 11 15 2002 Time 10 41 33 b Tank 3 Finished Application Screen 10 Right click on the screen and select Close from the pop up menu to close the main screen Testing the Application To test your application use the following steps 1 Click on the Run application icon Bi execute the application 2 Type the tank number 1 2 or 3 in the Tank label and modify the level of each tank using the slider Note that you can monitor set the level of each tank independently 3 Click the Exit icon upper right corner or switch back to the IWS development environment AIt TAB and click the Stop application icon E to close the application InduSoft Web Studio Page 55 Getting Started Guide Creating an IWS Application Configuring the I O Communication Driver The IWS run time software uses I O drivers to acquire necessary data values from PLCs and other I O devices This section explains how to select install and configure an I O driver 1 Inthe Workspace select the Comm tab and right click the Drivers folder 2 When the pop up menu displays select the Add Remove drivers option e Project GetStart APP Add Remove Drivers The Communication Drivers dialog displays Communication Drivers Ed Available drivers Help LAM
45. ication Parameters dialog displays configure the settings to match the communication parameters configured for the PLC E MODBU Communication Parameters COM com z S Baud Rate 3600 z i i Data Bits amp D me ere Advanced Parity None Station Signed Value Protocol ASCil or ATU oti Je Long 2 Custom Command ERO xxs Reg Communications Parameters Dialog for MODBU Driver Tip Select Help gt Communication Drivers and MODBU Driver User Manual for detailed information about configuring these communication parameters 8 Right click the MODBU folder again and select Insert from the menu InduSoft Web Studio Page 57 Getting Started Guide Creating an IWS Application Page 58 A Modbu001 drv dialog displays in the Workspace Notice that the dialog is divided into two sections fil Modbu001 drv Cer Description IT Increase priority Read Trigger Enable Read when Idle Read Completed Read Status E EEN WEN B Write Trigger Enable Write on Tag Change write Completed Write Status eee Station Header a mmm Tag Name Address Modbu001 drv Dialog Header A gray header with several fields Body Form of the worksheet In the header section configure these parameters as follows Description text box Type Example Modbus This parameter is just for documentation and it does not affect the communication in any way Enable
46. ield Displays the ID number of a selected screen object Screen Coordinate field Displays the current location of the cursor or pointer on the active screen When you select a screen object this field displays the object s coordinates in the top left corner Where X is the number of pixels from the left edge of the screen and Yis the number of pixels from the top of the screen Object Size field Displays the size in pixels of a selected object where W is the width and His the height No DRAG field Indicates whether dragging is disabled No DRAG or enabled empty in the active screen You might want to disable dragging to change the object properties of an object without moving it from its current location gt Tip You can enable disable dragging by pressing Ctrl D Also you can click on any object and use the arrow keys on the keyboard to move objects on the screen pixel by pixel Using the Menu Bar Page 22 The menu bar contains the following menus File Edit View Insert Project Tools Window Help Main Menu Bar File Contains options that enable you to create open close save and print application projects and files and allows you to close the IWS development environment Edit Contains options that enable you to edit your displays and worksheets by cutting copying pasting formatting and setting security levels You can also undo edits delete search and replace elements in these displays worksh
47. ile Status Application was started Close Downloading the Application 9 After all of the application files are downloaded click Run to execute the application on the remote target station Page 68 InduSoft Web Studio Revision History Revision Author Date Comments B Fabio Terezinho une 17 2002 Overall changes in the layout and content of the document C KC Francis uly 10 2002 Overall changes in the layout and content of the document D KC Francis November 13 2002 Overall changes in the layout of the document E SWamke November 17 2003
48. it icon for the screen use the following steps 1 Click the Library icon to open the symbols library 2 Select icons from the list then double click on the open door icon to open the object on your screen amp Library arrows bargraphs buttons common controls conveyors date amp time filebrowser Select the Open Door Icon InduSoft Web Studio Page 47 Getting Started Guide Creating an IWS Application 3 Double click on the Bitmap object to open its Object Properties dialog xj E Replace Hint Bitmap z M Transparent Color ES Select the Bitmap object and click on the Command icon to apply this dynamic to the object Double click on the Bitmap object to reopen the Object Properties dialog and type Shutdown into the Expression field to configure this function for the Command dynamic and apply it to the bitmap The following figure illustrates how your screen should look after creating the Exit icon right side of screen Now when a user clicks on this icon during runtime IWS will Shutdown the application runtime modules Synoptic Screen Date 07 09 2002 Time 13 11 52 j Exit Icon Testing the Application Use the following procedure to test your application l Page 48 Click the Run application icon Ei located on the IWS toolbar to execute the application Click the Exit icon open door bitmap or switch back to the development environment of IWS AIt TAB and click the St
49. lliseconds URL addresses tooltips and file compression logging and IP security Use the Preferences tab to enable disable warning messages before downloading screens to the target system Specify the following settings for your new GetStart APP application L Select Project Settings from the main menu bar 2 When the Project Settings dialog displays see the following figure click the Runtime Desktop tab and type main in the Startup screen field Project Settings Ki Identification Options Runtime Desktop Web Preferences F Titlebar F Minimize Box Active area indication 4 E Mavimize Box Show D bject Edge ia chose tar Change Mouse Cursor IV Start Maximized IV Stylus M Menu Options Je Virtual Keyboard Resize Border Default Keypad il Status Line z Scale 100 ll Startup screen main Show when quality is not GOOD F Enable Tooltips IT Hide Taskbar Auto Screen Scaling Specifying the main Screen When you execute the application IWS will open the main screen or whatever screen you specify automatically InduSoft Web Studio Page 39 Getting Started Guide Creating an IWS Application Creating Tags A tag is any variable that holds a value You can create tags at any time during the development of an application All tags created in an application are stored in the Application Tags folder located on the Database tab in the Workspace zi Ef Proje
50. ne of the three tanks Level 1 Level of the Tank 1 Level 2 Level of the Tank 2 Level 3 Level of the Tank 3 Do not use the 0 element Level fol in this example although it is a valid tag va Note You will create additional tags as you configure the application Creating the Start up Screen main scr To create a new screen for your application 1 In the Workspace window click the Graphics tab then right click on the Screens folder Wor k Pace H mae Screens oJ Group Screen oof 9 Web Pages el Database hr Graphics CS Tasks Comm Right Click the Screens Folder IWS stores all screens created for an application in this Screens folder InduSoft Web Studio Page 41 Getting Started Guide Creating an IWS Application 2 When the pop up menu displays select the Insert option to open the Screen Attributes dialog Screen Attributes K EA Description Location Tog jo Size Width E40 Height DS Security GH Background Picture T Enable Background EMP D T Shared image Runtime Properties TP Titleber M Sustem Menu Gegen Style Replace Partial NM BS F Minimize Box Border None sl Don t redraw Cancel Screen Logic Gn Oper while Dipen O On Eose Screen Attributes Dialog 3 Use this dialog to set screen properties such as size and type For this example just click the OK
51. older or component InduSoft Web Studio Page 27 Getting Started Guide Working with the IWS Interface Page 28 InduSoft Web Studio induSoft gt Chapter 5 Working with Tags This chapter provides information needed to create and edit tags including Naming Tags and Tag Fields Explains the required syntax for naming tags and tag fields Working with Tag Folders Explains the purpose of tag folders Understanding the Tag Types Describes the different tag types Using Array Tags Explains how to use array tags Using Indirect Tags Explains how to use indirect tags Naming Tags and Tag Fields This section provides guidelines for naming tags database location identifiers and tag fields a set of parameters inherent to each tag in the database Applications use tag fields during runtime Tag Syntax You must observe the following syntax guidelines when naming a tag Use letters numbers and the underscore _ character Do notuse the following characters tSt amp FVNANTI LC lt gt Tag names must begin with a letter Maximum tag length is 32 characters Maximum class member length is 16 characters Tag names must be unique do not specify the same name for two different tags unless you are creating an array tag and specify a unique index see Using Array Tags Tag names are not case sensitive for readability however we recommend using uppercase and lowercase cha
52. on directory where Dis your CD ROM drive and run the Setup exe file 3 Double click on the Installation folder and then double click on the InduSoft Web Studio icon to launch the InstallShield Wizard 4 Follow the instructions provided by the InstallShield Wizard to proceed with the installation 5 When prompted to restart Windows click the Yes want to restart my computer now radio button then click OK Notes Refer to the Product Licensing User Guide manual available on you IWS CD ROM for instructions about licensing IWS and or CEView Page 12 InduSoft Web Studio Installing the Software Getting Started Guide Starting InduSoft Web Studio To run IWS double click the InduSoft Web Studio shortcut on the desktop or select Start gt Programs InduSoft Web Studio InduSoft Web Studio J E Database Merge A InduSalt Remote Agent InduSioft Web Studio amp Fegste AL StoetLip Starting IWS gt Tip You can run the IWS development environment under any video setting however InduSoft recommends using a resolution of 800x600 or higher with more than 256 colors for a more pleasing environment Application resolution screen size is independent of the operating system resolution Installing CEView Software When installing IWS under Windows NT 2000 XP the CEView runtime files are stored in the following folder lt InduSoft Web Studio Folder gt Redist lt WinCE version g
53. op application icon EI on the IWS toolbar to close the application InduSoft Web Studio Creating an IWS Application Getting Started Guide Creating a Tank Object To add a Tank object to your screen use the following steps l Click the Library icon located on the IWS toolbar to open the symbols library Select tanks from the list and double click on any tank to include it on the screen amp Library Select a Tank Object Double click on the tank to open its Object Properties dialog A tank is a combination of different objects and dynamics from IWS for example a rectangle a bar graph and so forth You can modify the properties of this object by selecting the object or dynamic from the Group of Symbols combo box For this example however you will modify just the tag associated with the tank object 4 Click on the Replace button to associate a tag with the tank object InduSoft Web Studio Page 49 Getting Started Guide Creating an IWS Application 5 When the Replace dialog displays see following figure you are going to replace the Current Tag AnalogValue_ an internal tag used to simulate level by typing Level Index in the topmost New Tag field Method Show Jh Custom Properties Label lw Tags e Replace whole tag name Replace tag name by parts String value Whole Tag Name Max 100 100 Min U KO Analog alue_ LA Level Index en Replace Dialog You can use
54. r any class depends on the product specification InduSoft Web Studio Page 33 Getting Started Guide Working with Tags Understanding the Tag Types A tag can be one of the following types fe Lt E pn Boolean Boolean or digital variable O or 1 Integer Integer number positive negative or zero equivalent to C type long integer 4 bytes For example 0 5 200 Real Real number float internally stored as a double word equivalent to C type double 8 bytes for example 2 12 10 5 String Character string up to 256 characters that contains letters numbers or special characters For example Recipe product X123 01 01 90 On Class User defined compound tag The preceding icons and their respective tag types are located in folders on the Database tab Using Array Tags IWS tags can consist of a single value or an array of values An array tag is a set of tags that all have the same name but use unique indexes to differentiate between each tag a matrix of n lines and 1 column The maximum array size permitted will depend on the product specification You can use the following syntax to access an array tag lt ArrayTagName gt ArrayIndex For example tank 1 tank 2 tank 3 and tank 500 gt Caution You can specify the maximum index for each array tag in the Size column of any datasheet Specify size n to indicate that the array tag has Page 34 positions from 0 to n
55. racters For example use TankLevel instead of tanklevel Tag names must be different from internal tag names and math functions Some valid tag names include Temperature pressure l count Xx InduSoft Web Studio Page 29 Getting Started Guide Working with Tags Tag Field Syntax You can use the Tag Properties dialog click the Tag Properties icon located on the Tag Properties toolbar to specify tag field parameters To access a tag field you must use the following syntax lt TagName gt gt lt TagField gt for example second gt Max You can access the following tag fields during runtime Tag Field Name Description of Value Tag Type Associated with Field R Read Only Associated with Each Field Boolean Integer Real String RW Read Write database N fo PP the tag at runtime e ia CR tag at runtime Tag quality 192 GOOD 0 BAD Updates every time tag receives the result of an expression or a value from a communication task Driver or OPC Invalid expressions such as division by 0 or reading communication errors associated with tag sets quality to BAD Peery Fe returns the value 0 TimeStamp Records time and date when a tag changes value Brief description up to 9 characters of v an engineering unit such as Kg for a tag value alue 0 or 1 of any of the 32 bits b0 b1 b2 b31 of an integer tag BO LSB B31 MSB Page 30 InduSoft Web Studio Working with Tags
56. related to the application Details i Removing the Program D When the Uninstall successfully completed message displays and the OK button becomes active click OK Verify that IWS is no longer listed in the Add Remove Programs Properties dialog 6 Click the Cancel button or the close button S to close the Add Remove Programs Properties dialog and then close the Control Panel 7 Open the Windows Explorer and browse to the directory containing the InduSoft Web Studio directory 8 Verify that all of the IWS files and folders were deleted You can manually delete any that remain x Note The uninstall tool should not delete any files that you created or modified in the InduSoft Web Studio Projects folder InduSoft Web Studio Page 17 Getting Started Guide Installing the Software Page 18 InduSoft Web Studio KSE Tools for Automation ab Chapter 4 Working with the IWS Interface This chapter describes the InduSoft Web Studio development environment interface The information in this chapter is organized as follows Overview Provides a brief description of the tools and interfaces that make up the IWS development environment Title Bar Describes the title bar Status Bar Describes the status bar Menu Bar Describes the different menu options that you can access from the IWS main menu bar Toolbars Describes the IWS toolbars Workspace Describes the IWS Workspace
57. results of calculations alarm points and so forth In IWS all tags are organized into folders on the Database tab according to their origin application internal or shared IWS also provides a folder for compound tags named classes The following is a description of the different IWS tag folders Application Tags User defined tags created for screens to read from and write to field equipment for control auxiliary tags to perform mathematical calculations and so forth Page 32 InduSoft Web Studio Working with Tags Getting Started Guide Internal Tags Tags predefined by IWS Internal tags have predetermined functions such as time date acknowledge alarms storage of the logged on user name and so forth You cannot delete or modify these tags but you can access their values from any IWS task Shared Tags Tags created in PC based control software and imported into the IWS environment You cannot edit shared tags in the IWS environment but you can modify these tags using PC based control software and then re import the modified tags to update the IWS database Consequently you can configure shared tags for any IWS task just as any other tag Classes Structures that allow for high level encapsulation in the application database When you create a class type tag the tag contains a whole set of values rather than a single value You create classes by grouping elements called members The maximum number of members fo
58. roperties dialog contains a button that controls whether this dialog remains open The button changes state and function each time you click on it as follows e Click to close the dialog when you click anywhere in the display except on an object e Click to keep the dialog open regardless of where you click Also you can click to close the Object Properties dialog Check enable the Transparent check box to set the background color of the Text object to transparent Click the Fonts button to specify font settings for example Type Arial ize 20 Color Blue Click the Button icon led to create a Button object Click on the screen press the mouse button and drag the cursor to define the object size InduSoft Web Studio Page 43 Getting Started Guide Creating an IWS Application 12 Double click on the new Button object to open the Object Properties dialog and type the following text into the Caption field Click here to open the synoptic screen Welcome to the InduSoftt Sample Application ck bere od pen die Spd screen Adding a Caption to the Button 13 Select the Button object and click on the Command icon Si to apply this dynamic to the object 14 Double click on the Button object to reopen the Object Properties dialog 15 Type Open synoptic into the Expression field to apply this Command dynamic to the button x ECO Replace Hint Command sl Ces anban Open synop
59. t lt Processor Type gt where lt InduSoft Web Studio Folder gt is the installation directory chosen during installation C Program Files InduSoft Web Studio is the default installation directory lt Processor Type gt is the processor platform InduSoft provides a CEView runtime for all processor platforms supported by the WinCE operating system Arm Mips MipsFP Pocket Arm Pocket Mips Pocket SH3 PPC SH3 SH4 Thumb and x86 lt WinCE version gt is the Windows CE version for example WinCE300 WinCE400 and so forth InduSoft Web Studio Page 13 Getting Started Guide Installing the Software To install CEView use the following steps 1 Power on the Windows CE device and the Remote Agent dialog should launch automatically If not copy the CESERVER EXE file from the lt InduSoft Web Studio Folder gt Redist lt WinCE version gt lt Processor Type gt BIN directory of the Windows NT 2000 XP computer where you installed IWS 2 Paste the file into the lt non volatile gt folder of your WinCE device and run it x Note There are different ways to copy a file into a WinCE device for example you can map a shared folder from the Windows NT 2000 XP computer in the WinCE device or using ActiveSync If you need assistance copying this file into the WinCE device contact InduSoft technical support or the hardware manufacturer After executing the CESERVER EXE file the Remote Agent dialog launches in th
60. ted publications Chapter 3 Installing the Software Explains how to install InduSoft Web Studio and CEView on your system Chapter 4 Working with the IWS Interface Describes all the elements of the IWS development environment including menubars toolbars dialogs buttons menus and so forth Chapter 5 Working with Tags Describes the procedures for creating and editing tags for the tags database including a description of the proper syntax and tag types Chapter 6 Creating an IWS Application Explains how to create and edit applications objects screens and drivers Also explains the procedure for testing your applications Chapter 7 Running the Web Based Application Explains how to start and run your Web based applications Chapter 8 Running Applications from a Remote Station Explains how to run and manage applications remotely InduSoft Web Studio Page 1 Getting Started Guide Welcome to InduSoft Web Studio About InduSoft Web Studio Page 2 InduSoft Web Studio applications consist of animated operator interface screens communication drivers for PLCs and I O protocols such as Modbus DFS Profibus and so forth tags database and additional modules such as alarm monitors logic trend charts recipes schedulers and security system IWS applications interface with industrial I O systems and other Windows applications in the run time environment using ODBC DDE NetDDE OPC or TCP IP protocols You
61. tic Fate 250 7 Confirm Ey TC Shift Disable Force Securty sl TC Chl Alt EE jo Applying the Open synoptic Command Dynamic Tag Expression When a user clicks on this button during runtime IWS will open the synoptic screen 16 Finally select File gt Save from the main menu bar and save the screen as main scr 17 To close the main screen right click on the screen and select the Close option from the pop up menu Page 44 InduSoft Web Studio Creating an IWS Application Getting Started Guide Creating the Synoptic Screen synoptic scr To create a new synoptic screen use the following steps 1 Select the Graphics tab then right click on the Screens folder 2 Select the Insert option from the pop up menu and the Screen Attributes dialog displays automatically 3 Use the parameters on this dialog to set the main properties of the screen size type and so forth For this example just click OK to accept the default settings and open the screen in the screen editor window 4 Right click on the screen and select Background color Ga Paste Select All gt Test display OF Bii Setii E EEES EE miming OBR E Imi E Iming iff Screen Attributes P Background color Close Ckrl F4 More Colors Fill Effects Disable Drag Chri D Selecting a Background Color 5 When the Background Fill dialog displays select the gray color and click
62. va Note When you create an n position array tag the system creates nt 1 positions from 0 to n For example tag_example 15 with Array Size 4 has five elements start position 0 end position 4 Using Indirect Tags IWS supports indirect access to tags in the database For example consider a tag X of the string type This tag can hold the name of any other tag in the InduSoft Web Studio Page 35 Getting Started Guide Working with Tags Page 36 database in other words this tag can provide a pointer to any other tag type including the class type The syntax for an indirect tag is straightforward lt IndirectTagName gt For example assume that the X tag holds the TEMP string Reading and or writing to X provides access to the value of the TEMP tag va Note Any tag created as a string type is a potential indirect tag pointer InduSoft Web Studio induSoft gt Tools for Automation ab Chapter 6 Creating an IWS Application This chapter explains using a step by step tutorial how to create a working IWS application and how to install and configure an I O driver Creating a New Application Explains how to create IWS applications Specifying Project Settings Explains how to specify various settings for your application Creating Tags Explains how to create new tags and add them to the IWS Tags database Creating the Start up Screen main scr Explains how to create the main start up screen
63. y application component tags screens worksheets and so forth Application components are organized in a tree view with each one having its own icon and customized description You can move resize or hide the Workspace window Vd or ke D fon ea AE H E Screens Sg Group Screen ig Web Pages el Datab hh Graphics The IWS Workspace Page 26 InduSoft Web Studio Working with the IWS Interface Getting Started Guide The Workspace window is divided into four tabs as follows Database tab Provides access to all tags in the application and security system components This tab includes the following folders Application Tags Classes Shared Database Internal Tags Security Graphics tab Provides access to all screens and symbols in the application This tab includes the following folders and icons Screens Group Screen Web Pages Library Symbols Tasks tab Provides access to all task worksheets in the application This tab includes the following folders Alarms Trend Recipes Report ODBC Math Scheduler Comm tab Provides access to all worksheets configured to establish communication with another device or software using available protocols This tab includes the following folders Drivers OPC TCP IP DDE x Note You can right click on all folders and components to open a menu relating to that f

Download Pdf Manuals

image

Related Search

Related Contents

MANUAL DE INSTALAÇÃO E DO USUÁRIO  Who is the migration portal suitable  Label Egalité Diversité - Service public fédéral Emploi, Travail et  Philips DVD972C User's Manual  Mini-Lavastoviglie 4 Coperti  Seagate Savvio 300GB  QuickGene SP kit RNA tissue  Sony Ericsson J108I User's Manual    Philips GC7240 Iron User Manual  