1. ERERSO PRODUCTS CO Tower Battery BankInstallation User s Manual 003 2301 Rev A 12 20 2007 Chapter 1 Chapter 2 2 1 Chapter 3 3 4 Chapter 4 4 1 4 2 Table of Contents Important Safety Instructions i 2 Introduction to the Rear Panel sse 4 Rear Panel Descriptions i 4 Installation and Operation i 5 Unpacking Em 5 Selecting Installation Position 6 Installation Instructions enn 7 Storage Instruction i 9 Optional Battery Bank Connections 10 Types of Chargers Installed i 10 Explanation of the connection among the internal UPS UPS to Battery Bank 1 and Battery Bank 1 to Battery Bank 2 10 Chapter 1 Important Safety Instructions SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation and maintenance of the battery bank and batteries An Important Notice The battery bank which is supplied with a factory input plug can be safely connected to the wall receptacle by the user This battery bank is connected to an UPS There will be voltage at the output terminals if the UPS is turned on even if the input AC mains is not available Make sure that the AC utility outlet is correctly grounded Do not try to repair the unit yourself c
2. m L a Wire 1990 amp 2777 Red and Wire 1991 amp 2778 Black ou TO Wire 0469 Brown Wire 0431 Blue Board P N B CHCC2X CN10 CN11 CHACO X CN2 HAS C2xx CN404 CN6 CN5 12
3. Battery Bank UPS 3 4 Storage Instruction For extended storage through moderate climate 15 to 30 C 5 to 86 F the batteries should be charged for 12 hours every 6 months by plugging the UPS power cord into the wall receptacle Repeat this every 3 months under high temperature 30 to 45 86 to 113 F environment Chapter 4 Optional Battery Bank Connections 4 1 Types of Chargers Installed Charger Wire connection lication Appicatg Position F Position G Position H Position I SC1000 16AWG Brown 16AWG Blue 12AWG Red 12AWG Black 200W CHCC2xx SC2000 Wires Wires Wires Wires SC3000 P No 0469 P No 0431 P No 0302 P No 1869 CHACOxx SC2000 16AWG Brown 16AWG Blue 12AWG Red 12AWG Black 500W or SC3000 Wires Wires Wires Wires CHR500 x P No 0469 P No 0431 P No 0302 P No 1869 4 2 Explanation of the connection among the internal UPS UPS to Battery Bank 1 and Battery Bank 1 to Battery Bank 2 2 MS Series in Tower types SC1000 n nU 12AWG Red Black em 51 Installation is done Installation is done Wires P No 1892 SC2000 m pali 12AWG Red Black Reso 3 Installation is done Installation is done Wires P No 1892 SC3000 7 12AWG Red Black p n Installation is done Not Necessary Wires P No 1892 10 CONNECTOR TO THE REAR PANEL OF THE UPS Rear Panel TO EXT BAT TO UPS BAT Battery Bank 1 Internal Terminal Block 3P 11 Wire 1892 RED
4. When replacing batteries replace with the same quantity type amp capacity CAUTION Do not dispose of battery or batteries in an open fire The battery may explode CAUTION Do not open or mutilate the batteries The electrolyte from the batteries is toxic and harmful to the skin and eyes CAUTION Risk of electric shock battery circuit is not isolated from AC hazardous Voltage may exist between battery terminals and ground Test before touching with bare hands CAUTION A battery can present a risk of electrical shock and high short circuit current The following precaution should be observed when working on batteries Remove watches rings or other metal objects Use tools with insulated handles Wear rubber gloves and boots Do not lay tools or metal parts on top of batteries Disconnect charging source prior to connecting or disconnecting battery terminals Chapter 2 Introduction to the Rear Panel 2 1 Rear Panel Descriptions SC BP1000 SC BP2000 SC BP3000 d e TOURS tp TE 1 DC Breaker 1 Battery Over current Protection Breaker 2 To easy swappable battery please put the position of the breaker in O position In case there is 2 or next battery bank connected with the battery bank the DC voltage from the UPS
5. Bat will flow through without any interruption to the 2 Battery Bank 2 EXT BAT To the DC terminal of the 2 or next battery bank connected 3 UPS BAT To the UPS DC terminal 5 Charger Switch The inlet of the charger built in the Battery 4 Charger Inlet Bank Optional To control the On Off switch of the charger Optional 6 Utility Indicator To show the Utility is flown through the charger Optional 4 Chapter 3 Installation and Operation 3 1 Unpacking 1 Take the battery bank out of the PE foam 2 Remove the packing materials Note The battery bank module is approx 12 5 50 kgs be cautious when unpacking and lifting the unit to avoid injury 3 Standard Package includes a User s Manual b DC connect cable c AC Input Power Cord for charger only 4 Accessories for Tower and Rack Mount CONNECTION SC1000 115V 230V SC2000 115V 230V SC3000 115V 230V Note The packing condition and the external outlook of the unit should be inspected carefully before installation Retain the packing material for future use 3 2 Selecting Installation Position It is necessary to select a proper environment to install the unit in order to minimize the possibility of damage to the battery bank and extend the life of the batteries Please follow the instructions below 1 Keep at least 20cm 8 inches clearance from the rear panel of the
6. battery bank from the wall or other obstructions 2 Do not block the air flow to the ventilation openings of the unit 3 Please ensure the installation site environmental conditions are in accordance with the battery bank working specifications to avoid overheat and excessive moisture 4 Do not place the battery bank in a dusty or corrosive environment or near any flammable objects 5 This battery bank is not designed for outdoor use Relative humidity non condensation 30 90 3 3 Installation Instructions 1 ForUPS SC1000 115V 230V SC2000 115V 230V SC3000 115V 230V D amp BE l q ON o fu mu I gt aS Pie dedil OFF ON Connect to Utility Connect to Utility Charger Included Charger Included Second Batterv Bank First
7. ontact your local supplier or your warranty will be void Use a certified input power cable with the correct plugs and sockets for the appropriate voltage system To eliminate any overheating of the battery bank keep all ventilation openings free from obstruction and do not place any foreign objects on top of the battery bank Keep the battery bank 20 cm away from the wall Make sure the battery bank is installed within the proper environment as specified 0 40 C and 30 90 non condensing humidity Do not install the battery bank under direct sunlight Your warranty will be void if the batteries fail due to overheating This battery bank is designed for indoor use only This battery bank is not designed for use in dusty corrosive and salty environment The warranty for this battery bank will be void if water or other liquid is spilt or poured directly onto the battery bank Similarly we do not warrant any damage to the battery bank if foreign objects are deliberately or accidentally inserted into the battery bank enclosure The battery will discharge naturally if the system is unused for a period of time It should be recharged every 2 3 months if unused If this is not done then the warranty will be null and void During normal operation the batteries will be automatically remained in charged condition Servicing of batteries should be performed or supervised by trained personnel with knowledge of batteries and the required precautions

Download Pdf Manuals

image

Related Search

Related Contents

User's Manual  ALPHASENSE USER MANUAL 4-20mA Transmitter for Toxic  Samsung CLP-350N Uporabniški priročnik    Fixapart EL-CONN044S  Manuel d`utilisation  TVR II Unidades exteriores (Bomba de Calor) - IOM  Hunter 83001 Use and Care Manual  The pinnacle of scan tool technology The pinnacle of scan tool  