1. General Notes TFM TPM units are supplied with no configuration Commissioning by competent commissioning personnel is necessary for proper operation TROX cannot guarantee proper functioning if commissioning is carried out improperly The specifications of the laboratory equipment manufacturers the laboratory owner and the relevant standards and regulations must be taken into account Great care was taken when selecting the graphics and composing the text TROX assumes no responsibility or liability for a faulty configuration of the units based on incorrect or misinterpreted information in this user manual TROX GmbH reserves the right to modify or supplement this user manual without prior notice Copyrights Copyright 2006 TROX GmbH Heinrich Trox Platz 47504 Neukirchen Vluyn Germany www trox de All rights reserved Subject to change Microsoft and Windows are registered trademarks of Microsoft Corporation These and other trademarks are used in the text but are not specially identified so as to preserve the readability of the text Visit us on the Internet and stay informed about LABCONTROL system at www trox de TROX GmbH Heinrich Trox Platz 47504 Neukirchen Vluyn Germany Tel 49 0 2845 202 0 Fax 49 0 2845 202 265 LABCONTROL TEM TPM http www trox de User Manual E mail trox trox de TroxMConnect Operating Software 2 Software Installation M TrosdiConnect Select Installation Folder The req
2. DI 1 The volume flow in the ventilation system required for the fume cupboard must now be set This may be checked by taking measurements manually if necessary You can now read the pressure value at the measuring grid under actual value on the tab actual value This pressure serves as the initial value for setting the alarm limits Now the monitoring limits must be set depending on the measured pressure value These limits should be approx 10 20 above or below the measured pressure value Value selection is incumbent on the judgement of the competent commissioning personnel If a second value is to be monitored the procedure is to be repeated for this value in the same way 14 LABCONTROL TFM TPM User Manual TroxMConnect Operating Software 4 1 4 Alarm Setting Alarm handling can be set up individually on the tab alarm depending on the monitoring situation For this purpose refer to section 3 2 5 Tab alarm on page 9 TROX GmbH Heinrich Trox Platz 47504 Neukirchen Vluyn Germany Tel 49 0 2845 202 0 Fax 49 0 2845 202 265 LABCONTROL TEM TPM http www trox de User Manual E mail trox trox de TroxMConnect Operating Software 4 2 Example Configuration of TFM 2 4 2 2 Analogue Input Setting Connection to Volume flow Controller The analogue input must be set to the actual volume flow With the TFM 2 the volume flow at the fume cupboard is signal of the connected controller The voltage range and moni
3. Please note that the monitoring limits must be entered here Please refer to the documentation of the Fa Tihi er Baiki vi G jG eii m B a a 4 2 4 Alarm Setting fume cupboard for the monitoring limits Alarm handling can be set up individually on the tab alarm depending on the monitoring situation For this purpose refer to section 3 2 5 Tab alarm on page 9 maniT aep Tien eg U Tape miam riein ao o rar a mo samiem seein ome E steamers nae min ghar Tag ben 01 peered alr lal mo cane is w a O arated an aii E mip r i Tria TP F can cata rere cco AG T 2 Sl tig F cortect ceed cS SRC man metre fl cowie wi cecal weer ee 1h mmia am 2 ee gs OP cial j E chase ates sag mmi aay tbe be 0 7 eel dre diy TH Boii i AL E map r re O am g a aa 42 Pe a ioma a mga 4 cored amad aie i i h memi j om hz j m Bemi bss gemi 16 TROA tecunik Automation and Systems Technology TROX GmbH Heinrich Trox Platz 47504 Neukirchen Vluyn Germany Tel 49 0 2845 202 0 Fax 49 0 2845 202 265 http www trox de E mail trox trox de 4 3 Example Configuration of TPM Room Pressure Monitoring The pressure of a pressure controlled room is monitored with a TPM The actual pressure is switched by a room pressure sensor on the TPM The actual pressure signal of the sensor is to be connected to the analogue input 4 3 1 Function Selecti
4. Tel 49 0 2845 202 0 Fax 49 0 2845 202 265 http www trox de E mail trox trox de 3 2 1 Description of Tabs In the following sections the individual tabs and their functions will be described in detail 3 2 2 Tab main Basic configurations for the TFM TPM can be made on the tab main In the state of supply the indicator on the user terminal flashes back and forth between red and green and it is not possible to change the tab Field 1 device description General specifications or designations for the respective monitoring unit can be entered under device description There are three fields available for this each with a maximum of 16 characters The installation location can be entered here for example Field 2 monitor function selection The activated monitoring type is specified under monitor function selection TFM 1 or TFM 2 is selected for monitoring fume cupboards and TPM is selected for room pressure monitoring Fd TroxMConnect Y1 0 File Options diagnostic schema device description project subsystem monitor function selection volume flow 1 7 Ka pressure 2 La valume flowy 2 volume flow E velocity Oom Pressure user terminal selection standard AF1 additional functions TFM TEM LABCONTROL TFM TPM User Manual TroxMConnect Operating Software e TFM 1 volume flow internal dp transmitter Monitoring of the volume flow at the fume cupboard Measure
5. 00 mm active if contact is opened monitoring off if contact is opened gt 500 mm active if contact is closed monitoring off if contact is closed acoustic alarm 15 C unlimited acoustic alarm TEM j TPM TROX GmbH Heinrich Trox Platz 47504 Neukirchen Vluyn Germany Tel 49 0 2845 202 0 Fax 49 0 2845 202 265 http www trox de E mail trox trox de Field 1 Monitor value 1 too high DI 1 open e alarm delay The alarm delay specifies how long the actual value must exceed the alarm limit in order to trigger an alarm An alarm is not activated at this time Setting range 0 to 3600 s e acoustic alarm The duration of the acoustic alarm is set in the acoustic alarm field The acoustic alarm is cleared after the set time or by pressing the Quit button on the user terminal Setting range O no acoustic alarm 3 to 3600 s e unlimited acoustic alarm An unlimited acoustic alarm can be selected The acoustic alarm can only be deactivated by pressing the Quit button on the user terminal e activate alarm relay If the alarm relay is activated the alarm relay drops off during an alarm or power failure The alarm relay is used to pass on the alarm status to higher order equipment e g building control systems Field 5 TFM TPM e use sash window contact DI 2 The sash window contact function pursuant to DIN EN 14175 can be activated The contact comes from the fume cupboard and is wired to DI 2 V
6. 2 0 Fax 49 0 2845 202 265 http www trox de E mail trox trox de Field 2 Tabs Clicking on individual tabs opens them Field 3 Value Area Configuration The current parameters of the TFM TPM are displayed in these areas The configurations e g actual and set values can be read or set If a tab contains different function areas they are separated from one another with a frame Field 4 Buttons The cancel and apply buttons are activated when a parameter is changed FA TroxMConnect 1 0 File Options OO device description project monitor function selection O TFM TFM TFM TFM 3 TFM TPM user terminal selection standard AF1 additional functions TFM TPM diagnostic schema _ subsystem volume How pressure volume Hor volume flow velocity room PressUre LABCONTROL TFM TPM User Manual TroxMConnect Operating Software e apply After making a change you must click apply to send the change to the controller e cancel If the changed parameter is not to be saved you must cancel the procedure with cancel You cannot switch between tabs until a change has been applied or cancelled device Internal dp transmitter Internal dp transmitter external volume flow signal external dp transmitter external velocity transmitter external dp tranerntter TROX GmbH Heinrich Trox Platz 47504 Neukirchen Vluyn Germany
7. MConnect Operating Software 2 3 Connection to the PC A connection must be made between a laptop PC and the TFM TPM unit For this purpose the laptop PC must have a serial interface You can connect a cable directly to the connection jack of the user terminal and thus make the connection to the monitoring unit in this way The terminal cable for monitoring units can be ordered from TROX The order code for the cable is M546EW5 The cable is not included in the scope of supply of the TFM TPM units The user terminal is connected to the Con1 jack on the PCB via the RJ plug PC TFM TPM connection p g m E a E a E bnar mn ets J z i NEE Le TROX recom TFM TPM TROX GmbH Heinrich Trox Platz 47504 Neukirchen Vluyn Germany Tel 49 0 2845 202 0 Fax 49 0 2845 202 265 http www trox de E mail trox trox de 3 TroxMConnect Description The program for monitoring fume cupboards and rooms is implemented in the TFM TPM If the computer is connected to a TFM TPM and the TroxMConnect software is started the set parameters are displayed automatically The software has six tabs You can find a detailed description of the individual tabs in section 3 2 1 3 1 Starting the Software The operating software is started via the TroxMConnect icon on the desktop or via the Start menu If no hardware is connected the dialog box shown below appears 3 2 Layout The following see figure on page 5 i
8. TROX GmbH Heinrich Trox Platz 47504 Neukirchen Vluyn Germany E LABCONTROL TFM TPM http www trox de User Manual E mail trox trox de TroxMConnect Operating Software 1 introduction 1 2 Software Installation 2 1 System Requirements 2 2 TroxMConnect Installation 2 3 Connection to the PC oO NNN 3 TroxMConnect Description 3 1 Starting the Software 3 2 Layout 3 2 1 Description of Tabs 3 2 2 Tab main 3 2 3 Tab actual value 3 2 4 Tab config Al 3 2 5 Tab alarm 3 2 6 Tab diagnostic 3 2 17 Tab schema N OONOOoOA A A ok 4 Example Configurations 13 4 1 Example Configuration of TFM 1 with Measuring Grid 13 4 1 1 Function Selection 13 4 1 2 Zeroing 13 4 1 3 Monitor Value Recording 14 4 1 4 Alarm Setting 14 4 2 Example Configuration of TFM 2 Connection to Volume flow Controller 15 4 2 1 Function Selection 15 4 2 2 Analogue Input Setting 15 4 2 3 Monitor Value Setting 16 4 2 4 Alarm Setting 16 4 3 Example Configuration of TPM Room Pressure Monitoring 17 4 3 1 Function Selection 17 4 3 2 Analogue Input Setting 17 4 3 3 Monitor Value Setting 17 4 3 4 Alarm Setting 18 TROX GmbH Heinrich Trox Platz 47504 Neukirchen Vluyn Germany Tel 49 0 2845 202 0 Fax 49 0 2845 202 265 http www trox de E mail trox trox de 1 Introduction LABCONTROL Air Management In highly sensitive areas like laboratories and hospitals the top priority is protection of personnel The complex requ
9. appears during installation nerang aoea fe TroxMConnect Welcome to the TroxM Connect Setup Wizard Cancel The inctalien eal gunia pou thiqugh the shepe required bo etal Taah Conrad on pout Computer WARMING This computer pogam lm protected by copynght levy and inbemeational treaties Unauthorized duplication on detinuhor of this pogam or ary Gorton of it nay iesu in Sanne cii A cirenal penals and val be proseculed Io Fe mamum avert pscsble under the lee Please click the Next gt button after reading the warning TROX GmbH Heinrich Trox Platz 47504 Neukirchen Vluyn Germany Tel 49 0 2845 202 0 Fax 49 0 2845 202 265 http www trox de E mail trox trox de The following window appears once the installation is complete io TroxdConnect Installation Complete Tie Correct hat beer succeeehully meakai Chek Whee bo al Pleere ve Wirda Updates bo check for ary ocal updstes bo the HET Fremeseck The TroxMConnect program can now be started via Start Programs TROX GmbH TroxMConnect The serial interface must be selected the first time the program is started If a USB adapter is used to provide the serial interface this adapter must be inserted Otherwise a serial interface is not available on the computer TroxMConnect 1 0 Please select one of the available comports and press ok to continue available comports Co COM3 cancel LABCONTROL TFM TPM User Manual Trox
10. d monitoring off if contact is closed You specify whether a normally closed or normally open contact is connected as the contact The following fields are only active with the TPM e no monitoring if door is opened for x s With the TPM you can specify the amount of time that is to pass until monitoring is switched on again This is used to notify you in case a door has been left open too long Setting range 0 to 3600 s e monitoring inactive if door is opened Monitoring is switched off as long as the door is opened the contact is active After the door is closed the monitoring is been activated Once monitoring is reactivated the state of the system is determined and indicated visually If an alarm is active an acoustic alarm is emitted after the alarm delay expires TROX GmbH Heinrich Trox Platz 47504 Neukirchen Vluyn Germany Tel 49 0 2845 202 0 http www trox de User Manual E mail trox trox de TroxMConnect Operating Software 3 2 6 Tab diagnostic This tab contains status and fault messages as well as voltage signals used for diagnosing the monitoring function e DO 3 open sash window Indicates the state of the open sash window relay for operating the sash window closer Function is only available with AF1 user terminal Field 1 Digital inputs e DI 1 monitorvalue contact Indicates the selected monitor value e DO 4 close sash window Indicates the state of the close sash window relay fo
11. e pressure to a volume flow the alarms are handled is documented in the following C value of the measuring station is entered The volume example monitor value 1 too high The same rules apply flow is calculated using the formula for the other monitor values t Cx VAp When dealing with alarms the mathematical quantity is e TFM 2 velocity external velocity transmitter evaluated to decide whether the monitor value is too The voltage range and value range of the connected large or small velocity sensor must be entered Example 40 Pa is less than 30 Pa This has to be made allowance for when making settings e TPM room pressure external dp transmitter for alarm handling The voltage range and value range of the connected room pressure sensor must be entered Fd TroxMConnect 1 0 File Options hanes ee ies abel 1 i main diagnostic schema monitor value 1 too high DI 1 opened monitor value 2 too high DI 1 closed alarm delay 15 alarm delay 15 Q acoustic alarm 10 acoustic alarm 10 C unlimited acoustic alarm C unlimited acoustic alarm activate alarm relay activate alarm relay monitor value 1 too low D7 opened monitor value 2 too low Dl 1 closed alarm delay 1 5 alarm delay 15 2 acoustic alarm 10 acoustic alarm 5 C unlimited acoustic alarm C unlimited acoustic alarm activate alarm relay activate alarm relay TFM TPM use sash window contact DI 2 use monitoring off contact DI 3 O gt 5
12. e user who made the most recent changes Possible users TROX and customer 3 2 7 Tab schema The wiring schematic is displayed on the tab schema depending on the selected configuration WZ jadhi wndow contact EII ii ee be pond ac ll eden hareri TROX recunix 12 TROX GmbH Heinrich Trox Platz 47504 Neukirchen Vluyn Germany Tel 49 0 2845 202 0 http www trox de User Manual E mail trox trox de TroxMConnect Operating Software 4 Example Configurations 4 1 2 Zeroing General Information The TFM 1 must be zeroed before the correct measured The TFM TPM units are supplied with no configuration value is displayed on the tab This is performed by Commissioning by competent commissioning personnel pressing the zeroing button on the tab diagnostic see is absolutely necessary page 12 Zeroing TROX cannot guarantee proper functioning if commissioning is carried out improperly The following window appears when the button is The specifications of the laboratory equipment pressed manufacturers the laboratory owner and the relevant standards and regulations must be taken into account irodiConnect V1 0 4 1 Example Configuration of TFM 1 with Measuring Grid With the TFM 1 the volume flow is monitored at the fume Please remove the pressu re cupboard with the differential pressure grid supplied The measuring grid is mounted in accordance with the tubes from the controller installation instructi
13. irements of these areas are fulfilled by room air conditioning systems The monitoring and display of system parameters are indispensable here TROX offers with the TFM TPM a range of monitoring devices covering the monitoring function for fume cupboards and room pressure control in new buildings and those being renovated Proper aerodynamic functioning of a fume cupboard must be monitored in accordance with EN 14175 by a fume cupboard function indicator If a malfunction occurs visual and acoustic alarms must be emitted The TFM 1 and TFM 2 units are required for this application The TFM 1 has an inbuilt pressure transmitter with which the volume flow is monitored with the differential pressure grid The TFM 2 is connected to an external measuring point e g a volume flow controller or a velocity sensor The physical quantity to be monitored is specified and monitored by the connected unit Room pressure control is used in laboratory buildings with more extensive safety requirements The TPM is used to monitor pressure controlled rooms Manual TroxMConnect This manual contains important information on the TroxMConnect operating software for the TFM TPM unit types The TFM monitoring units for fume cupboards and the TPM monitoring units for room pressure can be configured through the MConnect software Installation and operation are documented in detail LABCONTROL TFM TPM User Manual TroxMConnect Operating Software
14. isual and acoustic alarms are emitted at the user terminal when the contact is actuated The following setting options are not active until the function is selected Using the selection boxes gt 500 mm active if contact is opened gt 500 mm active if contact is closed You specify whether a normally closed or normally open contact is connected as the sash window contact e acoustic alarm The duration of the acoustic alarm is set in the acoustic alarm field The acoustic alarm is cleared after the set time or by pressing the Quit button on the user terminal Setting range 0 no acoustic alarm 3 to 3600 s e unlimited acoustic alarm An unlimited acoustic alarm can be selected The acoustic alarm can only be deactivated by pressing the Quit button on the user terminal 10 LABCONTROL TFM TPM User Manual TroxMConnect Operating Software e use monitoring off contact DI 3 The monitoring off function switches the monitoring function off To visually indicate that switching off has occurred the red alarm indicator on the user terminal is switched on and the green operating LED on the user terminal flashes The alarm relay remains active because an alarm is not in effect This can be used as a standby circuit with the TFM and as a tie in for the door contact with the TPM The following setting options are not active until the function is selected Using the selection boxes monitoring off if contact is opene
15. larm red alarm TROX GmbH Heinrich Trox Platz 47504 Neukirchen Vluyn Germany Tel 49 0 2845 202 0 Fax 49 0 2845 202 265 http www trox de E mail trox trox de Field 2 monitor value 2 DI 1 closed The alarm limits for the value to be monitored are entered here This pair of values is valid for monitor value 2 i e digital input 1 DI 1 closed Upper and lower thresholds must be entered this defines a permissible range in which an alarm is not been triggered The units depend on the monitor function selection on the tab main Field 3 actual value The current measured value is displayed 3 2 4 Tab config Al The analogue input is configured on the tab config Al The parameters are dependent on the monitor function selection and the connected sensor Field 1 config Al e min max Voltage The analogue input is set to the output voltage range of the connected sensor or volume flow controller FA TroxMConnect 1 0 File Options LABCONTROL TFM TPM User Manual TroxMConnect Operating Software STEPS TTT Ta Tee a main diagnostic schema TFM TPM e min max wanted signal type The analogue input is set to the output value range of the connected sensor or volume flow controller Setting values for monitor function selection e TFM 1 volume flow internal dp transmitter Since the internal pressure sensor is used only the C value based on l s needs to be entered for the conversion The v
16. m depending on the monitoring situation For this purpose refer to section 3 2 5 Tab alarm on page 9 When dealing with alarms the mathematical quantity is evaluated to decide whether the monitor value is too large or small Example 40 Pa is less than 30 Pa This has to be made allowance for when making settings for alarm handling 18
17. ment of the volume flow with a measuring station e g VMR Sensors are connected directly with the 0 300 Pa internal pressure sensor The volume flow is calculated using the formula t C x VAp where C unit constant and Ap measured differential pressure e TFM 1 pressure internal dp transmitter Monitoring of the pressure value at the differential pressure grid The pressure value is a gauge of the volume flow at the fume cupboard The differential pressure grid is connected to the 0 300 Pa internal pressure sensor e TFM 2 volume flow external volume flow signal Monitoring of the volume flow at the fume cupboard Measurement of the volume flow with volume flow controller with an actual value output for example The signal is wired to the analogue input device internal dp transmitter Internal dp transmitter external volume flow signal external dp transmitter external velocity transmitter external dp transmitter TROX GmbH Heinrich Trox Platz 47504 Neukirchen Vluyn Germany Tel 49 0 2845 202 0 Fax 49 0 2845 202 265 http www trox de E mail trox trox de LABCONTROL TFM TPM User Manual TroxMConnect Operating Software e TFM 2 volume flow external dp transmitter Monitoring of the volume flow at the fume cupboard Measurement of the volume flow with measuring station with pressure sensor for example The signal is wired on the analogue input The volume flow is calculated using the formula C x
18. olume flow is calculated using the formula C x VAp Zeroing is to be carried out at the beginning of commissioning and maintenance for purposes of zero adjustment See page 12 Zeroing e TFM 1 pressure internal dp transmitter Since the internal pressure sensor is used no configuration of the pressure adapter is required Zeroing is to be carried out during commissioning and maintenance for purposes of zero adjustment See page 12 Zeroing volume flow mit 0 00 voltage max 10 00 i TROX GmbH Heinrich Trox Platz 47504 Neukirchen Vluyn Germany Tel 49 0 2845 202 0 Fax 49 0 2845 202 265 LABCONTROL TEM TPM http www trox de User Manual E mail trox trox de TroxMConnect Operating Software 3 2 5 Tab alarm The way alarms are dealt with when alarm limits are exceeded or fall below a set value are defined on the tab alarm The alarm limits are set on the tab actual values a description is found on page 7 In case of an e TFM 2 volume flow external volume flow signal The voltage range and value range of the connected volume flow controller must be entered e TFM 2 volume flow external dp transmitter alarm visual and acoustic alarms are emitted at the user The voltage range and value range of the connected terminal The way alarms are dealt with can be specified volume flow measuring station with pressure sensor must depending on which monitor value is exceeded The way be entered To convert th
19. on The indicator at the user terminal alternates between red and green TFM TPM not configured the first time the TFM TPM is started The following selection must be made on the tab main monitor function selection e TPM room pressure external dp transmitter user terminal selection e The TPM can only be operated with the standard user terminal Only the standard user terminal can be selected rag ic 2 ee coke al ede eo eal maer apis eure feipr ef opps 8 are bral op 6 ere 4 3 2 Analogue Input Setting The analogue input must be set to the actual pressure signal of the connected pressure sensor The voltage range and pressure range of the connected pressure sensor are entered on the tab config Al 17 LABCONTROL TFM TPM User Manual TroxMConnect Operating Software 4 3 3 Monitor Value Setting The pressures to be monitored are entered on the tab actual value Please note that the monitoring limits must be entered here Please refer to the requirements of the system owner for the monitoring limits Since the way alarms are handled depends on whether a room is monitored with underpressure or with overpressure this must be specified with the monitoring limits The diagrams shown here change accordingly depending on the values entered TROX TECHNIK Automation and Systems Technology 4 3 4 Alarm Setting Alarm handling can be set up individually on the tab alar
20. ons and is connected to the 0 300 Pa internal pressure sensor The pressure value measured during commissioning is used to determine the alarm limits When you are ready please press ok 4 1 1 Function Selection The indicator at the user terminal alternates between red and green TFM TPM not configured the first time the a ne TFM TPM is started coco The following selection must be made on the tab main Please click ok after removing the pressure tubes The current zero point of the internal pressure sensor is monitor function selection determined This zeroing is to be repeated during annual e TFM 1 pressure internal dp transmitter maintenance to correct any zero point drift of the pressure sensor that may have occurred user terminal selection No further settings for measuring value recording are e Your choice the example uses the standard user necessary e g on the tab config Al since the internal terminal analogue input is configured in the program coke al ede En eral ST E S eee ppr opie 8 are mer al T S grea 13 TROX GmbH Heinrich Trox Platz 47504 Neukirchen Vluyn Germany Tel 49 0 2845 202 0 Fax 49 0 2845 202 265 http www trox de E mail trox trox de 4 1 3 Monitor Value Recording Before the monitor value can be recorded you should check to see which monitor value is activated on the tab diagnostic Switching between monitor values occurs via digital input
21. ox trox de Field 4 Analogue inputs e external Al Al 1 Measured voltage at analogue input 1 offset Al 1 Voltage measured at analogue input 1 when zeroing e internal pressure transducer Al 0 Voltage measured at the internal pressure transducer offset Al 0 Voltage measured at the internal pressure transducer when zeroing e zeroing button Zeroing determines the zero point of the internal or connected external pressure transducer When executing this function the pressure tubes must be detached from the pressure transmitter Another window appears This function must be executed each time commissioning or maintenance is performed roxhMiConmmect 1 0 ey nan actual value conbg Al dsm disgnosko Poems LABCONTROL TFM TPM User Manual TroxMConnect Operating Software Field 5 Service This function can only be used with the TFM in conjunction with the AF1 user terminal since this user terminal has a service LED You can enter a service interval here setting range 0 to 3 600 days Maintenance is to be performed once this interval has passed The next maintenance date is indicated via an LED on the user terminal e service time button The service time is reset to O with the service time button This function must be executed each time maintenance is performed in order to start a new maintenance interval Field 6 e version Indicates the TFM TPM program version e last user Indicates th
22. r operating the sash window closer Function is only e DI 2 sash window contact available with AF1 user terminal Indicates whether the fume cupboard sash window is open more than 500 mm e DO 5 alarm Indicates the state of the alarm relay with changeover contact The relay is not active drops off in case of an e DI 3 monitor contact alarm Indicates whether monitoring has been switched on or off Field 2 Digital outputs Field 3 Alarm e DO 1 light alll E Indicates state of light relay The light relay can be ndicates the alarm state switched on and off with the light button on the user red or yellow field alarm terminal green field no alarm DO 2 n a e fault pressure transmitter a ma fault indication red field fault if a fault occurs at the pressure transmitter FA TroxMConnect 1 0 f File Options This digital output is not used mar digital inputs analog Inputs O11 monitorvalue contact monitorvalue 1 external l Al DI 2 sash window contact 500 mm DIS monitor contact monitoring on Internal pressure transmitter digital outputs service DO 5 alarm active service time 0 days service interval 365 days service time alarm alarm 3 fault pressure transmitter veon 1 D last user customer TFM TPM TROX GmbH Heinrich Trox Platz 47504 Neukirchen Vluyn Germany Tel 49 0 2845 202 0 Fax 49 0 2845 202 265 http www trox de E mail tr
23. s an explanation of the layout of the user interface and the functions of each area LABCONTROL TFM TPM User Manual TroxMConnect Operating Software Field 1 Menu bar File File Options Save Parameters Load Parameters End e Save Parameters Save Parameters allows you to save an entire data record of the current configuration of the TFM TPM You can select any desired name to construct your own database from the various monitoring types e g fume cupboards of specific sizes The data can be saved for proof of commissioning e Load Parameters The saved data records can be loaded in the operating software via Load Parameters Once the file has been opened the configurations must be sent to the controller by pressing the apply button e End Exit the software Options _ Options german english volume Flow unit l s volume Flow unit mih Change Comport You can choose German or English as the language of the TroxMConnect operating software in the Options menu You can choose between l s and m h for the display of volume flow values The volume flow values are saved in l s in the TFM TPM so minor rounding differences may occur when displaying the values in m h e Change Comport The communication interface can be set via Change Comport This must occur the first time the program is started TROX GmbH Heinrich Trox Platz 47504 Neukirchen Vluyn Germany Tel 49 0 2845 20
24. tored via the measurement at a volume flow volume flow range of the connected controller are entered controller The actual volume flow signal of the volume on the tab config Al flow controller is to be connected to the analogue input 4 2 1 Function Selection The indicator at the user terminal alternates between red and green TFM TPM not configured the first time the TFM TPM is started The following selection must be made on the tab main monitor function selection e TFM 2 volume flow external volume flow signal user terminal selection e Your choice the example uses the standard user terminal Please refer to the documentation of the connected controller for the values to be set Zeroing is not carried out because an external volume flow linear measured value is recorded The setting values of the most important controllers from TROX are listed in the following table range actual value TVLK 250 110 BB3 2 10 V 0 340 I s Belimo VRP VFP TVLK 250 140 BB3 2 10 V 0 280 I s Belimo VRP VFP VLK 250 180 BB3 2 10 V 0 210 I s Belimo VRP VFP TVLK 250 0 BB3 2 10 V 0 615 I s Baimoveenme o e TVRK 315 BB3 2 10 V 0 1025 l s Belimo VRP VFP TVRK 250 BB3 2 10 V 0 615 l s Belimo VRP VFP TVRK 200 BB3 2 10 V 0 405 l s Belimo VRP VFP TVRK 160 BB3 2 10 V 0 250 l s Belimo VRP VFP 15 4 2 3 Monitor Value Setting The volume flows to be monitored are entered on the tab actual value
25. uirements and steps for installation are explained in the following The maake yall imal Trek Connect to te folloenn older 2 1 System Requirements Before you install the TroxMConnect software on your To insta m hee foder cikk hee To metal bo a dienst fodder een it below or cik Brier PC please review the following system requirements Fokje fr pgi ttc agektLionnect Browne e PC recommended Pentium III 1 GHz or faster Disk Con Operating system Microsoft Windows 2000 Inet To Gonrect for pouseF or lo spona who uses Bis compute Microsoft Windows XP P Even e RAM min 256 MB eee e hard disc min 30 MB e Screen Super VGA 1024 x 768 You can select whether TroxMConnect is only to be Ea installed for the user currently logged on to the computer e Serial interface USB to serial adapter may or if it is to be installed for all users The installation path also be used should not be changed 2 2 TroxMConnect Installation The installation begins with another prompt after clicking Next gt If the NET framework 2 0 is not yet installed on your computer it is now installed automatically In this To install the software start the setup program case the following window appears Setup exe Then follow the instructions provided The setup program automatically installs the required data on your PC TroxMConnect Setup i ing i 4 Installing NET F k 2 0 The following menu
26. vAp e TFM 2 velocity external velocity transmitter Monitoring of the entrance velocity at the fume cupboard Measurement of the entrance velocity with velocity sensor The velocity sensor is not included in the scope of supply The signal is wired to the analogue input e TPM room pressure external dp transmitter Monitoring of the pressure of pressure controlled rooms Measurement of the room pressure with a suitable static pressure sensor The pressure sensor is not included in the scope of supply The signal is wired to the analogue input FA TroxMConnect 1 0 File Options diagnostic schema monitor value 1 DON open Volume flow limita monitor value 2 O11 closed volume flow limita actual value TEM TPM 3 User terminal selection Various user terminals can be selected In the scope of supply is the standardterminal included Standard standard monitoring functions AF 1 additional functions operation of sash window closer service LED light switch 3 2 3 Tab actual value Field 1 monitor value 1 DI 1 open The alarm limits for the value to be monitored are entered here This pair of values is valid for monitor value 1 i e digital input 1 DI 1 open Upper and lower thresholds must be entered this defines a permissible range in which an alarm is not been triggered The units depend on the monitoring function selection on the tab main yellow alarm red alarm vellow a