SmartLoop Analogue fire alarm control panel User`s manual
Contents
1. Description of the Control panel User s manual SMARTLOOP M EARTH Indicates voltage dispersion to earth Indicates a short circuit on one or more system devices e g detectors Call your installer for immediate assistance N O Indicates electrical mains failure primary power source failure P BELLS ACTIVE Indicates that the bell output is active Q BELLS FAULT Indicates that an alarm signaling device is not operating properly e g bell out ot order R BELLS Indicates that one or more signaling DISABLED outputs have been disabled Indicates that the SmartLoop PSTN board is sending an Alarm or Fault related report call E Mm S DIALLER ACTIVE Indicates a dialler fault T DIALLER FAULT U DIALLER Indicates that one or more of the dialler DISABLED functions have been bypassed V Programmable The cause of activation of this LED can be LEDs defined during the programming phase Description of the Control panel ON Blinking Indicates that the dialler fault has been cleared The event details can be viewed on the display via the main menu level 1 Indicates that the dialler fault has been cleared The event details can be viewed on the display via the main menu level 1 Indicates that the mains failure has been cleared The event details can be viewed on the display via the main menu level 1 Indicates that the dialler f
2. 7 Description of the Control panel 5 SMARTLOOP User s manua 8 INVESTIGATE If this button active at level 2 only this level requires key in keyswitch or code entry is pressed during active pre alarm conditions the system will add the preset investigation time to the running pre alarm time this operation can be done once only 9 SILENCE This button active at level 2 only silences switches Off any active outputs with the silenceable attribute The silenceable outputs will hold silenced status until a new event occurs that releases the outputs automatically The SILENCE button operates as a toggle switch therefore silenced outputs can be unsilenced by pushing the button again 10 RESET This button active at level 2 only clears any active events deletes the memory and restores standby conditions 11 EVACUATE If this button is pressed during active pre alarm conditions level 1 the system will generate an alarm If this key is pressed during standby status when the key is in the keyswitch level 2 the system will generate an instant alarm 1 5 2 The LEDs ON Blinking A INVESTIGATE Indicates that investigation time has been requested B SILENCE Indicates that the system has been silenced C RESET In the event of pre alarm alarm indicates that reset commands are not allowed Reset will be allowed when all outputs have been silenced and this LED goes Off D ALARM Indicates an
3. ho m t gt S mo oO lt D Dv D e p ar U mela gt 3 gt gt a D QMa AM Mm WN a OJ RO TCO WO lt lt oO D w wv a NUNS unu mi 10 Using the control panel User s manual num SMARTLOOP 2 7 Operating on the control panel network From panel lt key gt Remote Console Or lt key gt 9 This command will allow you to access temporarily one of the control panels in the network from the console you are working on During this operating mode the screens on the display will allow you to monitor and command the remote control panel Press 4 and W to view the control panels in gt 001 Control panel 01 002 Control panel 02 EE 003 NOT In Configuration Press in correspondence to the remote 004 NOT In Configuration control panel you wish to connect to The screen of the remote control panel will appear after a few seconds ALARM UO o OLO FIRE ALARM H l SMARTLoop nnn lt Zone Description gt The icon H on the bottom right of the display lt Device Type gt 01 01 11 17H 4 confirms that you are communicating with the Last Alarm Zone yyy Panel zzz Bl selected remote panel and that any commands entered at the panel you are working on will be implemented on the remote panel you are communicating with Press TEST to go back to the local control panel Note If the local control panel goes into alarm status while you are working on the remote console the remote connection will
4. alarm condition that is an input point detector callpoint input module etc set to generate alarms has detected alarm conditions E PRE ALARM Indicates a pre alarm condition that is an input point detector callpoint input module etc set with a pre alarm time has activated F DISABLED Indicates that one or more of the system components loop point zone or output have been bypassed G TEST Indicates that one or more components points or zones are undergoing tests H NIGHT MODE Indicates that the panel is operating in night mode I Indicates the control panel is working J FAULT Indicates an active system fault condition Indicates memory of a cleared fault event The display will provide the fault details To view the restored fault condition details consult the events log using the main menu level 1 m K LOGIC UNIT Indicates trouble with the panel CPU the Indicates that the CPU has re initialized panel must be sent back immediately to due to control panel shutdown or fault the manufacturer for repair condition If this occurs it will be necessary to check the functionality of the entire system L BATTERY Indicates that a battery fault has been Indicates that the battery fault has been detected the display will provide the fault cleared The event details can be viewed details low battery battery disconnected on the display via the main menu level 1
5. 1 TEST BUZZER INVESTIGATE SILENCE RESET EVACUATE S e ELECTRONICS Figure 1 Control panel frontplate 000 jo NIGHT MODE FUSE ON ES 1 5 1 Commands Note For further details refer to the programming manual Chapter 3 The SmartLoop control panel 1 40 character x 4 line alphanumeric display Indicates the system status signals critical events priority given to the most serious events and allows you to navigate through of the main menu and screens These keys allow you to navigate through menu screens and change the values in the programming fields 2 This key allows you to quit an operation and exit the screen without saving or step back to higher level menu options 3 This key allows you to confirm an operation and exit a screen or go to the options of a lower level menu 4 Alphanumeric keypad for data entries Key 1 allows you to view the specifics of events which provide detailed information info If an event relating to a loop device is shown on the display key 2 will allow you to access the bypass unbypass loop device menu 5 Keyswitch allows level 2 users Users Authorized Users to access the system Can be used instead of code entry 6 TEST This button active at level 1 no key or code entry required activates all the console LEDs in order to allow the operator to check functionality This button active at level 1 silences the panel beeper
6. Ad a 0051 CPD 0225 0051 CPD 0226 0051 CPD 0227 0051 CPD 0228 0051 CPD 0231 0051 CPD 0232 III LLLI SmartLoop Analogue fire alarm control panel Users manual GameOver ELECTRONICS SMARTLOOP nin User s manual Copyright The information contained in this document is the sole property of INIM Electronics s r l No part may be copied without written authorization from INIM Electronics s r l All rights reserved European directive compliance This Control panel has been designed and developed to the highest standards of quality and performance implemented by Inim Electronics This control panel must be installed in accordance with the instructions described in this manual and in compliance with the laws in force All control panels from the SmartLoop series are EN54 2 and EN54 4 compliant AII control panels from the SmartLoop series and all accessory items and special functions have IMQ Security Systems certification unless otherwise stated 2 Copyright User s manual num SMARTLOOP Table of contents CODY IGG sci i 2 European directive compliance ccc cceceeseusueueeueneeeeeenererensees 2 Table of contents serata io 3 Description of the Control panel 4 Manufacturer s name and address 4 Device identification details 4 Documentation supplied 4 Manual details 4 Control panel user interface 5 Using the control panel iaccastssanenencsesaceanteaniawices donsennenennenananes 8 Note to Se
7. UATE button and ensure that all building On occupants evacuate the building immediately Inform the person s in charge of the safety of the building and its occupants immediately To silence the beeper press BUZZER 2 2 2 Note to Security Personnel To force the panel into alarm status regardless of its status press EVACUATE ALARM PRE At least one zone is alarm pre alarm status ALARM RESET If there is no intervention during a pre alarm the panel will generate an alarm LEDs On when the pre set pre alarm time expires To request INVESTIGATION time press INVESTIGATE and check the building The INVESTIGATION time cannot be refreshed In the event of a false alarm press SILENCE The panel beeper and the silenceable outputs will be silenced until a new event occurs If the panel is operating in Night mode the panel beeper and the silenceable outputs will be unsilenced automatically after the pre set time and the panel will generate pre alarm status If you wish to re activate pre alarm alarm status after pressing the SILENCE button press it again pre alarm alarm signaling and the outputs will re activate To clear all alarm fault signaling active and in memory press RESET If the conditions persist the panel will generate another alarm SILENCE LED On Indicates that the control panel has been silenced RESET LED On The control panel is in alarm or pre alarm status To reset the control panel you must press SILENCE before pressi
8. ates that the respective fault was detected and has since cleared In this case view the fault details on the display via the log in the main menu 2 4 Informative signaling Signaling that does not require specific action DISABLED LED On A zone point or output has been bypassed View specifics on display TEST LED On A zone or point is undergoing testing View specifics on display NIGHT MODE LED On Control panel in Night mode Attention The panel may have been programmed to generate instant alarms During Night mode SILENCE will be held for the pre set silence time only ON LED On The control panel is working BELLS ACTIVE LED The alarm signaling devices are In Service i e monitoring the protected area On BELLS DISABLED Indicates that one or more alarm signaling devices have been bypassed LED On DIALLER ACTIVE Indicates that the dialler is sending a control panel generated call LED On DIALLER DISABLED Indicates that one or more of the dialler functions have been bypassed LED On Using the control panel 9 SMARTLOOP nin User s manual 2 5 View Events The events represent the various conditions signaled by the panel and have the following order of importance alarm pre alarm Supervision early warning fault monitor test disablement The events that appear on the control panel and repeater displays may have been generated by other control panels in the network Ss re If several events of the same
9. ault has been cleared The event details can be viewed on the display via the main menu level 1 Indicates that the SmartLoop PSTN board is sending a technical communication monitoring communication etc Indicates that the dialler fault has been cleared The event details can be viewed on the display via the main menu level 1 SMARTLOOP nin User s manual Chapter 2 Using the control panel 2 1 Note to Security Personnel Persons responsible for the safety of the building and its occupants security personnel etc can put the control panel in day night bypass zones devices and NAC outputs clear the call queue disable alarm and fault report calls request system event printouts refer to the programming manual Chapter 10 Maintenance operations Attention Insert and turn the key The panel will enable access level 2 The panel will hold level 2 status until the keyswitch is turned Off key in vertical position 2 2 Danger signaling In the event of fire hazard always follow the fire department approved fire drill 2 2 1 Note to building occupants All building occupants may view the events log refer to paragraph 2 5 2 View Events Log and the status of the detectors refer to paragraph 2 8 View detector status and operate remote Repeater refer to paragraph 2 7 Operating on the control panel network ALARM LED On Evacuate the building immediately PRE ALARM LED In the event of real danger press the EVAC
10. be interrupted and the screen of the local control panel will be reinstated 2 8 View detector status From panel lt key gt Check Detectors state x Loop x yyy Device or lt key gt 2 Xx yyy This option will allow you to view the detector status and some parameter values Note You must wait several seconds for the control panel to retrieve the detector data Refer to the detector instructions for details Press keys A and W to view the previous and Point x yyy lt Point Description gt lt Device Type gt Smoke 0 dB m i i ce 0 08dB m Contamination 01 Using the control panel 11 ELECTRONICS via Fosso Antico Loc Centobuchi 63076 Monteprandone AP ITALY Tel 39 0735 705007 _ Fax 39 0735 704912 info inim biz _ www inim biz ISO 9001 FM 530352 DCMUINEOSLOOP R301 20120209
11. curity Personnel 8 Danger signaling 8 Fault signaling 9 Informative signaling 9 View Events 10 Dialler calls 10 Operating on the control panel network 11 View detector status 11 Chapte ONDUAWNHEN OAWNHE NNNNNNNNO Table of contents 3 SMARTLOOP nin User s manual Chapter 1 Description of the Control panel 1 1 Manufacturer s name and address INIM Electronics s r l Via Fosso Antico Centobuchi 63076 Grottammare AP Italy Tel 39 0735 70 50 07 Fax 39 0735 70 49 12 info inim biz www inim biz 1 2 Device identification details e Denomination Fire alarm control panel e Model SmartLoop 1 3 Documentation supplied e User s Manual this manual e Installation Manual e Programming Manual 1 4 Manual details e Title SmartLoop user s manual e Version 3 01 e Month and year February 2012 e Code DCMUINEOSLOOP 4 Description of the Control panel User s manual SMARTLOOF 1 5 Control panel user interface The SmartLoop control panel manages up 15 consoles the main console is located on the control panel frontplate G and P models only and up to 14 optional consoles SmartLetUSee LCD repeaters connectable to RS485 BUS STATUS N FAULTS S BELLS Q DIALLER Esc pa FAULT active o gt ACTIVE CPU Fu FAULT FAULT BATTERY DISABLED DISABLED PRE ALARN 1 9 3 info abe def 4 5 6 ghi jkl mno DISABLED TEST EARTH 7 g 9 Lev pqrs tuv WXYZ f Ca 0 LEV
12. ng RESET 8 Using the control panel User s manual num SMARTLOOP 2 3 Fault signaling 2 3 1 Note to building occupants FAULT LED On or Inform the person s in charge of the safety of the building and its occupants blinking immediately 2 3 2 Note to Security Personnel You must always ensure that faults are dealt with and cleared as soon as possible However if you wish to stop the fault signaling you can bypass the zone point output concerned FAULT LED On Indicates that at least one system fault has been detected View the fault details on the display and ensure that it is dealt with and cleared On LED Off Primary and secondary power failure no mains or battery power The system is not working ensure that power is restored as soon as possible CPU LED On The control panel must be sent back to the manufacturer for repair BATTERY LED On Indicates that the panel batteries are low or inefficient and must be either charged or changed EARTH LED On Indicates voltage dispersion to earth You must find the part of the system concerned and that cleared the fault as soon as possible FUSE LED On Indicates short circuit on one of the AUX or AUX R terminals MAINS LED On Indicates Mains failure BELLS FAULT LED On Indicates an alarm signaling device connection fault e g bell fault has been detected DIALLER FAULT LED Indicates a dialler fault or telephone line down condition On Blinking on any of the above mentioned LEDs indic
13. type occur e g three faults only the first event will be shown on the display The system displays different real time events in the order of importance e g if the system is dealing with three fault events when a pre alarm event occurs the pre alarm will take priority Control panel reset operations clear all the events from the display however all events are will be saved to the log and can be viewed on the control panel 2 5 1 Active events These are the events that occurred after the last control panel RESET operation This is the first of three events Event 00lof 003 01 01 07 14 34 PM Fri PRE ALARM WAREHOUSE Press keys A and W to view other active NORTH EAST SECTOR CORRI DOR events Loop n 4 Point 147 Panel 22 J Press Esc to view the Events menu Li 31 Main Menu Press to select the menu option 2 View Log Menu options from 3 onwards show all the 3 View Pre al arms events related to the active event type 4 View Disablements 2 5 2 View Events Log From panel lt key gt View Log Read Log lt 7 or lt key gt 2 1 The events are recorded in chronological order Once the log is full old events will be overwritten by new ones The navigation method is the same as that used for the active events 2 6 Dialler calls From panel lt key gt Dialler Settings or lt key gt 5 This command will allow you to clear the call queue and enable disable Alarm and Fault associated calls Select the required option