Discovery 1-4 Loop 40 Character Application Guide

image

Contents

1. 130 Additional loop cards Insertable type display overlay with English printed inserts Cabinet size 480h x 670w x 144d Space for printer and 2 x 12V 12Ah battery set 2604023 96 Zone 40 Character Discovery 6 loop analogue addressable control panel with 96 zone LEDs c w 6 loop cards expandable to 8 loops with two 2500 130 Additional loop cards Insertable type display overlay with English printed inserts Cabinet size 480h x 670w x 144d Space for printer and 2 x 12V 12Ah battery set 2604024 96 Zone 40 Character Discovery 7 loop analogue addressable control panel with 96 zone LEDs c w 7 loop cards expandable to 8 loops with one 2500 130 Additional loop card Insertable type display overlay with English printed inserts Cabinet size 480h x 670w x 144d Space for printer and 2 x 12V 12Ah battery set 2604025 96 Zone 40 Character Discovery 8 loop analogue addressable control panel with 96 zone LEDs c w 8 loop card Insertable type display overlay with English printed inserts Cabinet size 480h x 670w x 144d Space for printer and 2 x 12V 12Ah battery set 2500 107 Printer 2500 130 Additional loop cards for Discovery panels Document Ref DVAOAPP Rev 2 09 02 2010 Page 5 of 23 Raised by GG Checked JBI 2 2 Semi Flush Bezels The semi flush bezel locates to the rear of the bevelled edge of the back box leaving the bevelled edge and door raised out from the wall Finished in
2. Raised by GG Checked _ JBI INPUT CIRCUIT INPUT CIRCUIT SWITCH SWITCH END OFLINE 3k9 680R Figure 1 Input circuit configuration 3 6 Alarm circuits The 96 Zone 40 Character Discovery panel has two alarm circuits each rated at 1A The circuits are reverse polarity monitored for open and short circuit faults To allow monitoring all devices must be polarised To prevent damage to the control panel bells must also be suppressed a bell fit diodes as shown in Figure 2 The circuit must be terminated with a 3k9 end of line resistor ALARM CIRCUIT POLARISING DIODE E G 1440025 SUPPRESSION DIODE E G 11440025 ALARM CIRCUIT END OFLINE 3k9 SOUNDER Figure 2 Alarm circuit configuration 3 7 Mechanical and Environmental Specification Size Height Width Depth Weight excluding batteries Operating temperature Operating humidity Electrical Mains voltage Document Ref DV4OAPP Rev 2 09 02 2010 480mm 410mm 2 loop and network repeater 160mm including lock and indented holes 15kg 5 C to 40 C 5 to 95 230V AC 10 15 Page 13 of 23 Raised by GG Checked__JBJ Mains failed fault battery current Adjustable 27 5V float charger 1 Loop 145mA 2 Loop 170mA 3 Loop 195mA 4 Loop 220mA Mains failed alarm battery current 1 Loop 260mA 2 Loop 285mA 3 Loop 310mA 4 Loop 335mA Battery charger type Maximu
3. Zone 40 Character Discovery 4 loop analogue addressable control panel with 96 zone LEDs c w 4 loop cards English printed display overlay Cabinet size 480h x 410w x 144d Space for printer and 2 x 12V 12Ah battery set Document Ref DVAOAPP Rev 2 09 02 2010 Page 4 of 23 Raised by GG Checked JBI Part No Description 2604014 96 Zone 40 Character Discovery 5 loop analogue addressable control panel with 96 zone LEDs c w 5 loop cards expandable to 8 loops with three 2500 130 Additional loop cards English printed display overlay Cabinet size 480h x 670w x 144d Space for printer and 2 x 12V 12Ah battery set 2604015 96 Zone 40 Character Discovery 6 loop analogue addressable control panel with 96 zone LEDs c w 6 loop cards expandable to 8 loops with two 2500 130 Additional loop cards English printed display overlay Cabinet size 480h x 670w x 144d Space for printer and 2 x 12V 12Ah battery set 2604016 96 Zone 40 Character Discovery 7 loop analogue addressable control panel with 96 zone LEDs c w 7 loop cards expandable to 8 loops with one 2500 130 Additional loop card English printed display overlay Cabinet size 480h x 670w x 144d Space for printer and 2 x 12V 12Ah battery set 2604017 96 Zone 40 Character Discovery 8 loop analogue addressable control panel with 96 zone LEDs c w 8 loop card English printed display overlay Cabinet size 480h x 670w x 144d Space for p
4. amp 2500 842 painted to customer s specification Fully flush stainless steel bezel for 96 Zone 40 Character Discovery 1 4 loop repeater panel 2500 830 amp 2500 842 brushed or polished 2501 129 Fully flush brass bezel for 96 Zone 40 Character Discovery 1 4 loop repeater panel 2501 155 Fully flush brass bezel for 96 Zone 40 Character Discovery 1 4 loop panel amp large repeater 2500 844 brushed or polished 2500 830 amp 2500 842 brushed or polished Note Fully flush bezels for 5 8 loop enclosures contact Sales Department Document Ref DVAOAPP Rev 2 09 02 2010 Page 7 of 23 Raised by GG Checked 87 3 0 Hardware Specifications 3 1 Mechanical Assembly Illustration Document Ref DVAOAPP Rev 2 09 02 2010 Page 8 of 23 Raised by GG Checked JBI 3 2 20 character by 4 line LCD display Back lit when event present or Access controls switch ON User indications Document Ref DVAOAPP Rev 2 09 02 2010 User Controls amp Indications OVERRIDE EVACUATE DELAY SCROLL SILENCE MESSAGES BUZZER SILENCE TEST ALARMS RESOUND ALARMS POWER SUPPLY ON TEST DISPLAY DELAY ON RESET FIRE MAINTENANCE ACCESS MENU MENU UP ESCAPE GENERAL DISABLEMENT BUZZER SILENCED MENU DOWN ENTER ACCESS CONTROLS GENERAL 01 FAULT N ALARM FAULT MORE DISABLEMENT MESSAGES TEST 000000 ee Se eS dh eS 10 11
5. manufacture 2601 076 55000 001 APO Open area SONOS sounder Apollo manufacture 2601 078 55000 005 APO Open area SONOS sounder beacon Apollo manufacture 2601 082 58000 005 Discovery open area sounder beacon Apollo manufacture 2608 001 XPA CB 1 2034 Optical smoke detector and address module Apollo manufacture 2608 002 2608 003 2608 004 XPA CB 1 2032 Multisensor smoke detector and address module Apollo manufacture XPA CB 1 1170 AIR heat detector and address module Apollo manufacture XPA CB 1 1171 CS heat detector and address module Apollo manufacture 2608 010 XPA IN 1 4007 XPander interface module with isolator Apollo manufacture 2608 005 XPA MC 1 4006 XPander manual call point Apollo manufacture Document Ref DV40APP Rev2 09 02 2010 Page 22 of 23 Raised byGG Checked by 787__ Part No Description 2608 006 XPA CB 1 4001 XPander sounder and sounder base Apollo manufacture 2608 008 XPA CB 1 4003 XPander sounder beacon and sounder base Apollo manufacture 6 2 General Accessories Order Codes amp Descriptions PartNo Description o Squashni Sounder and Base 2501 0468 Squashni Sounder and Base 2501 049 Cover Plate for Squashni Sounder Appendices i Other Relevant Documentation Sales Literature Discovery 1 4 Loop 96 Zone 40 Character Installation and Commissioning Manual Discovery 1 4 Loop 96 Zone 40 Chara
6. 00w x 210d 2500 223 Enclosure c w 5A p s e amp space for five outstation boards amp 6 2Ah batteries Size 600h x 600w x 210d 2500 226 Remote square indicator 2500 227 Remote round indicator 55000 780 XP95 RDM Interface Apollo manufacture 55000 580 XP95 RDM Ionisation smoke detector Apollo manufacture 55000 680 XP95 RDM Optical smoke detector Apollo manufacture 55000 480 XP95 RDM Heat detector Apollo manufacture 45681 280 XP95 RDM Base Apollo manufacture 2501 251 55000 265 XP95 Loop powered beam detector Apollo manufacture 4568 1 242 XP95 Low power relay base Apollo manufacture 2501 584 55000 855 XP95 Protocol translator single channel Apollo manufacture 2501 585 55000 856 XP95 Protocol translator dual channel Apollo manufacture 2501 580 55000 540 XP95 I S Ionisation smoke detector Apollo manufacture 2501 581 55000 640 XP95 I S Optical smoke detector Apollo manufacture 2501 582 55000 440 XP95 L S Temperature detector standard Apollo manufacture 2501 479 2501 583 55000 940 XP95 I S Manual call point Apollo manufacture 45681 215 XP95 L S Base Apollo manufacture 2601 036 CEL platform sounder XP95 Discovery detector base 2601 035 CEL platform sounder Xplorer detector base 2501 254 Document Ref DV40APP Rev2 55000 261 100dB Loop sounder Apollo manufacture 09 02 2
7. 010 Page 21 of 23 Raised byGG Checked by 787__ Part No Description 2501 255 45681 262 Loop sounder with isolating base Apollo manufacture 2501 105 55000 280 XP95 flame detector Apollo manufacture 2501 381 55000 852 XP95 sounder controller unit with isolator Apollo manufacture 2501 285 55000 812 Din rail zone monitor unit with isolator Apollo manufacture 2501 375 55000 843 XP95 switch monitor with isolator Apollo manufacture 2501 377 55000 841 XP95 switch monitor plus with isolator Apollo manufacture 2501 373 55000 847 XP95 1 unit with isolator Apollo manufacture 2501 371 55000 849 XP95 output unit with isolator Apollo manufacture 2501 382 55000 589 XP95 3 channel I O unit Apollo manufacture 2501 383 55000 588 XP95 3 channel I O unit with isolator Apollo manufacture 2501 253 55000 885 XP95 Multi Sensor Apollo manufacture 2501 219 55000 875 XP95 Mains Switching I O Unit Apollo manufacture 2501 378 55000 845 XP95 Zone Monitor with Isolator Apollo manufacture 2501 109 58000 300 Discovery CO Detector Apollo manufacture 2501 438 55000 268 Reflective beam detector 5 50m 2501 439 55000 273 Reflective beam detector 50 100m 2601 046 55000 877 Loop Powered Beacon Apollo manufacture 2601 031 45681 265 Intelligent Base Sounder Apollo manufacture 2601 063 45681 2
8. 12 13 14 15 16 17 18 19 20 21 22 23 24 eS SS Se Se eee eS ee OOOOOoOoOoOoOooOoooooooooooooo OoOoOoOOoOOOOOOOOOOooooooo 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 OOOOOOOOOOOOOOOOoOooooooco OcOOOOoOOOOOOOOoOOooooooooooo 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 OO OOOOOOOOOOOOOOoOoooooooco C I E Production Period 1 Page 9 of 23 Raised by GG Checked JBI User controls Only override delay is available without operating the access controls keyswitch Switch to 1 to enable controls enter level 2 Override delay operates with Zonal fire red and fault yellow indications Pulse to indicate a non Silenced event continuous to indicate an event has been silenced Displays the next message at the 3 2 1 User Controls and Indications in Detail Operates all sounder circuits continuously current event level Activates all alarm outputs when pressed Alarms silenced when released Tests all indications and internal buzzer Enters the user menu system for access to further level 2 and level 3 OVERRIDE EVACUATE DELAY SCROLL SILENCE MESSAGES BUZZER TEST SILENCE RESOUND ALARMS ALARMS TEST DISPLAY ACCESS MENU MENU UP ESCAPE MENU DOWN Increments digits in user m
9. 2501 274 58000 900 Discovery Manual call point Apollo manufacture 2501 022 55000 500 XP95 Ionisation smoke detector Apollo manufacture 25017023 55000 600 XP95 Optical smoke detector Apollo manufacture 2501 024 55000 400 XP95 Temperature detector standard Apollo manufacture 2501 020 45681 210 XP95 Base complete with address card Apollo manufacture 2501 019 55000 900 XP95 Manual call point Apollo manufacture 2501 027 55000 700 XP95 Isolator Apollo manufacture 2501 026 45681 211 XP95 Isolator base Apollo manufacture 2501 218 45681 321 XP95 Isolating base 20 devices Apollo manufacture 2501 021 55000 401 XP95 Temperature detector high temperature Apollo manufacture 2501 2775 55000 818 XP95 Input Output unit Apollo manufacture Document Ref DV40APP Rev2 09 02 2010 Page 20 of 23 Raised byGG Checked by JBI__ Part No Description 2501 217 55000 819 XP95 Output unit Apollo manufacture 2501 276 55000 810 XP95 Switch monitor Apollo manufacture 2501 277 55000 809 XP95 Switch monitor plus Apollo manufacture 2501 278 55000 813 XP95 Zone monitor Apollo manufacture 2501 279 55000 823 XP95 Sounder control unit Apollo manufacture 2501 280 55000 833 XP95 Mini switch monitor Apollo manufacture 2501 216 55000 832 XP95 Mini switch monitor interrupt Apollo manufacture 2501 281 55000 803 X
10. 78 Integrated Base Sounder Apollo manufacture Vesda Aspirating Smoke Detector 2601 084 46581 393 Discovery Sounder Beacon Base Apollo manufacture 2501 229 55000 950 XP95 Weatherproof call point Apollo manufacture 2501 376 55000 809 XP95 Switch Monitor Plus Flush Apollo manufacture 2501 590 55100 908APO Call point with isolator Apollo manufacture 2501 622 55000 760 XP95 Mini DIN Rail Switch Monitor Apollo manufacture 2601 034 45681 276 Anciliary base sounder Apollo manufacture 2601 041 55000 278 High output loop sounder Apollo manufacture 2601 064 45681 277 Integrated base sounder with isolator Apollo manufacture 2601 065 45681 331 Integrated base sounder beacon Apollo manufacture 2601 066 45681 330 Integrated base sounder beacon with isolator Apollo manufacture 2601 069 55000 274 Stand alone high output sounder beacon Apollo manufacture 2601 070 55000 291 Multi tone open area sounder beacon Apollo manufacture 2601 071 55000 293 Multi tone open area sounder beacon with isolator Apollo manufacture 2601 072 55000 296 Multi tone open area sounder beacon weatherproof Apollo manufacture 2601 073 55000 291 Multi tone open area sounder beacon with isolator weatherproof Apollo manufacture 2601 074 45681 333 Beacon base with isolator Apollo manufacture 2601 075 45681 335 Beacon base Apollo
11. BI Page 3 of 23 Document Ref DVAOAPP Rev 2 09 02 2010 2 0 Cabinet Specifications 2 1 Surface Cabinets All cabinets are manufactured from 18SWG sheet steel and finished in satin texture epoxy powder stove paint Top entry grommets and rear entry knockouts are provided Cabinet colour RAL 7035 Light Grey C b _ js le La 480mm 37mm Eb 10 325mm Part No Description 2604010 96 Zone 40 Character Discovery 1 loop analogue addressable control panel with 96 zone LEDs c w 1 loop card expandable to 4 loops with three 2500 130 Additional loop card English printed display overlay Cabinet size 480h x 410w x 144d Space for printer and 2 x 12V 12Ah battery set 2604011 96 Zone 40 Character Discovery 2 loop analogue addressable control panel with 96 zone LEDs c w 2 loop cards expandable to 4 loops with two 2500 130 Additional loop cards English printed display overlay Cabinet size 480h x 410w x 144d Space for printer and 2 x 12V 12Ah battery set 2604012 96 Zone 40 Character Discovery 3 loop analogue addressable control panel with 96 zone LEDs c w 3 loop cards expandable to 4 loops with one 2500 130 Additional loop card English printed display overlay Cabinet size 480h x 410w x 144d Space for printer and 2 x 12V 12Ah battery set 2604013 96
12. Discovery 1 4 Loop 96 Zone 40 Character Analogue Addressable Control Panel Application Guide Contents Page 1 0 Introduction and Typical System Illustration 2 2 0 Cabinet Specifications 4 3 0 Hardware Specifications 7 4 0 Software Specifications 14 5 0 Panel Enhancements 18 6 0 Compatible Field Devices 20 Appendices i Other Relevant Documentation 23 Document Ref DV4QAPP Rev 2 09 02 2010 Page 1 of 23 Raised by GG Checked by 7 87____ Approved by IBJ 1 0 Introduction and Typical System Illustration The 96 Zone 40 Character Discovery analogue addressable panel is available as a 1 4 loop panel using plug in loop driver cards Each loop is rated at 500mA and will control up to 126 Apollo XP95 or Discovery devices All addresses may be configured as cause effect outputs with up to 255 different programmable groups and 3 independently programmable output bits per address Discovery mode changes are configured by the panel s internal clock and may differentiate between weekday and weekend functions Loop inputs may also be configured to change selected loop devices between modes where temporary mode changes are required Panels are housed in well designed enclosures and are finished in hardwearing epoxy paint The motherboard electronics are fixed to a detachable chassis thus facilitating a completely empty enclosure for first fix installation Top entry plastic grommets bottom rear entry knockouts for mains and rear entry knockout
13. IT COMPANY NAME EDIT POINT TEXTS EDIT INPUT TEXTS 3 NETWORK IDENTIFY PANEL EDIT NETWORK RESPONSES 1 DISPLAY 2 PRINTER 3 MEMORY 4 CONTROLS 5 SPECIAL 3 PRINT NETWORK RESPONSES Raised by GG Checked by 387 a 5 0 Panel Enhancements The 96 Zone 40 Character Discovery 1 4 loop panel may be enhanced to provide additional facilities Other relevant documentation is available providing more details Note This is an illustration only and not wiring schematic A secondary cabinet is usually required for all PCBs 5 1 Panel Enhancement Order Codes amp Descriptions 2500 157 A1535 programmable expansion board 8 open inputs amp 8 relay outputs 2500 158 A 1536 programmable expansion board 8 open inputs amp 8 alarm outputs 2500 221 Enclosure c w 3A psu amp space for 6 2AH battery set amp 2 or 4 panel programmable E n Rm nn 2500 223 Enclosure c w 5A psu amp space for 6 2AH battery set amp 2 or 4 panel programmable NE onec gt 2500 107 Printer Po jSize 300hx350wx75d 0000000000000 E Size 300 x350wx75d Size355hx370wx900 TP Size300hx360wx1904d S O Size600nx380wx 2104 PP Document Ref DV40APP Rev2 09 02 2010 Page 19 of 23 Raised byGG Checked by JBI__ 5 1 2 A1535 A1536 8 Way Expansion Boards Up to 31 1535 amp 1536 8 way programmable expansion
14. NT e 2 3 4 CLEAR PRINT QUEUE PRINT EVENT LOG PRINT DISABLEMENTS PRINT TEXTS VALUES Document Ref DV40APP Rev 2 09 02 2010 2 8 2 TEXTE pma 3 1 g Page 18 of 23 1 PANEL SETUP LOOP SETUP 1 LOOP CONFIGURATION 1 LOOP CONTENTS 1 VIEW LOOP CONTENTS 2 PRINT LOOP CONTENTS L 3 RECONFIGURE LOOP 2 POINT SENSITIVITY L 1 FIRE L 2 ALERT L 3 DISCOVERY 1 PRINT DRIFT 2 PRINT DATE 8 LED 4 RAPID COMPENSATION 5 BEACON SETUP 6 BEACON AUTO 2 ZONE ALLOCATION 1 EDIT POINT ZONES _ 2 PRINT POINT ZONES L 3 VIEW POINT ZONES 3 LOOP CAUSE EFFECT 1 POINT GROUP ALLOCATION 1 EDIT POINT GROUPS 2 PRINT POINT GROUPS L 8 VIEW POINT GROUPS 2 LOOP OUTPUT CAUSE EFFECT L 8 PRINT LOOP O P C E INPUT OUTPUT SETUP 1 I O BOARD TYPES 2 PANEL OUTPUT C E 1 INPUT GROUP ALLOCATION 1 EDIT INPUT GROUPS 2 PRINT INPUT GROUPS 3 VIEW INPUT GROUPS 2 REMOTE OUTPUT C E __ 3 PRINT REMOTE O P C E L 3 INPUT ZONES 1 EDIT INPUT GROUPS _ 2 PRINT INPUT GROUPS L 3 VIEW INPUT GROUPS GENERAL CONFIGURATION 1 REMOTE EVACUATE MODE 2 POWER FAULT MODE 3 NUMBER OF REPEATERS 4 CLASS CHANGE MODE 5 SHARED ZONE MODE L 6 NUMBER OF ZONES DIT ED
15. P95 DIN rail mounted input output unit Apollo manufacture 2501 282 55000 804 XP95 DIN rail mounted Output unit Apollo manufacture 2501 283 55000 822 XP95 DIN rail mounted switch monitor Apollo manufacture 2501 284 55000 821 XP95 DIN rail mounted switch monitor plus Apollo manufacture 2501 285 55000 812 XP95 DIN rail mounted zone monitor Apollo manufacture 2501 286 55000 826 XP95 DIN rail mounted sounder control unit Apollo manufacture 2501 287 55000 802 XP95 DIN rail mounted isolator Apollo manufacture 2501 221 45681 261 XP95 Loop sounder requires XP95 base Apollo manufacture 2501 222 55000 260 XP95 Loop sounder with red cap Apollo manufacture 2501 223 55000 259 XP95 Loop sounder with white cap Apollo manufacture 2500 235 CEL Addressable break glass unit no back box 2500 236 A1444 basic outstation board 3 inputs 2500 237 A1445 relay outstation board 3 inputs 3 relays 2500 238 A1446 sounder outstation board 3 inputs 1 sounder circuit 1 relay 2500 240 A1447 add on zone monitor board for above outstation boards 2501 149 Enclosure to fit 1 outstation board Size 150h x 225w x 75d 2500 197 Enclosure c w 14A p s e space for one outstation board amp 3 2Ah batteries Size 300h x 350w x 75d 2500 221 Enclosure c w p s e space for four outstation boards amp 6 2Ah batteries Size 380h x 6
16. and off for the remainder of the time This period is user definable and would typically be during working hours The delay is not operated if the alarm condition is initiated by a call point or the evacuate function The delay may be overridden by a user function on the panel The engineer can set the delay start and end times set the delay duration and enable or disable the delay 4 1 3 Enabling Site Specific Data Changes site specific data is held in non volatile memory To protect this from errors the memory is protected by a write enable switch on the motherboard This switch has to be set to the write enable position to allow any changes If the switch is inadvertently left in the enable position when the changes are complete the panel indicates a fault condition 4 1 4 Point Configuration The panel loop devices can be automatically reconfigured through an engineers menu command The panel stores each device address and type on configuration Any changes to the loop devices are then indicated as a fault The system configuration can also be printed out This shows all devices on a loop with their current status The sensitivity of each point can also be changed to allow for ambient conditions XP95 detectors can have the trip level for fire and alert configured Discovery devices have the sensitivity code changed for fire sensitivity and the analogue threshold for alert can be changed Note For compliance with ENS4 the fire sensit
17. boards may be connected to each 1 4 loop panel A special 2 door cabinet is available to house up to 4 enhancement boards details on request Up to 31 boards in total may be connected via an RS485 comms for local expansion only Local power is required for each board in addition to the RS485 comms link WARNING In order to conform to the requirements of BS5839 EN54 the 1536 8 way alarm board must be used adjacent to the main panel The inputs and outputs are fully programmable within the panel s cause effect facility The output type eg relays or alarm circuits are determined by the board type chosen The inputs may be monitored or non monitored or indication only Please refer to A1535 8 Way Relay Board amp A1536 8 Way Alarm Board documentation for further details 52 Battery Sizes YUASA 15Ah battery 12V 181mm long x 98mm wide x 167mm high 38Ah battery 12V 166mm long x 175mm wide x 125mm high 65Ah battery 12V 350mm long x 166mm wide x 174mm high 6 0 Compatible Field Devices The 96 Zone 40 Character Discovery is compatible with the devices listed in this section Field Device Order Codes amp Descriptions Part No Description 2501 270 58000 500 Discovery Ionisation smoke detector Apollo manufacture 2501 271 58000 600 Discovery Optical smoke detector Apollo manufacture 2501 272 58000 400 Discovery Heat detector Apollo manufacture 2501 273 58000 700 Discovery Multisensor Apollo manufacture
18. cter User Instructions Wiring Recommendations PC based Software Programming Guide Battery Calculation spreadsheet Document Ref DV40APP Rev2 09 02 2010 Page 23 of 23 Raised byGG Checked by JBI__
19. enu number entry Decrements digits in user menu number entry Indicates power supply active mains or battery Pulses when a new fire is active continuous when all fires have been Pre alarm active Indicates internal fault Pulses if new fault detected continuous if all active faults have been silenced Pulses if fault detected with either alarm circuit or any loop alarm controller Continuous for a silenced fault and alarm circuit disabled conditions Document Ref DVAOAPP Rev 2 09 02 2010 POWER SUPPLY ON DELON FIRE MAINTENANCE GENERAL ALERT DISABLEMENT SYSTEM BUZZER FAULT SILENCED GENERAL FAULT ALARM FAULT MORE DISABLEMENT MESSAGES TEST Page 10 of 23 Overrides the delay to outputs function and immediately actions the outputs Silences the internal buzzer for any condition Silence fire events If already silenced re activates the previous alarm condition Resets all fire and fault indications Fire conditions must be silenced first Used within access menu to delete items and escape from menus Enters text in the access menus Constant to indicate delay is active pulsing when delay running Indicates Discovery device drift compensation limit reached Indicates some part of the system has been disabled Continuous when the buzzer has been silenced Continuous to indicate some part of the system is in test mode Pulses to indicate another
20. f a fire or a fault on a device will cause operation of the fire or fault indicator associated with the zone The panel alphanumeric display will also indicate the zone number The panel has an insert fitted to the front door suitable for text descriptions of each zone location The engineer can also print out all the zones with the devices allocated to the zones 4 1 7 Programmable Cause Effect Any loop device output can be individually programmed to operate in response to a common event or a zone or group entering a specific condition The common events are e Common fire output cleared on reset e Common fire output cleared on silence alarms e Common alert output cleared on reset e Common fault output cleared on reset e Common indication output cleared on reset e Alarms silenced e Panel reset e Evacuate including remote evacuate Document Ref DVAOAPP Rev2 09 02 2010 Page 16 of 23 Raised by GG Checked JBI The zone and group based events can occur on any device or devices within the specified zone or group Fire in a group or zone output cleared on silence alarms Fire in a group or zone output cleared on reset Any two fires in a group or zone output cleared on silence alarms Any two fires in a group or zone output cleared on reset Alert in a group or zone output cleared on reset Fault in a group or zone output cleared on reset Indication in a group or zone output cleared on reset A group con
21. ivity level must be set to 55 The pre alarm value can be set to any value Note Do not adjust the fire sensitivity level of the XP95 high temperature heat detector This device has an analogue count of 55 at 90 C Document Ref DVAOAPP Rev 2 09 02 2010 Page 15 of 23 Raised by GG Checked JBI Note The default levels are XP95 sensor Discovery sensor Default Alert level 45 45 Default Fire level 55 55 Valid Alert Levels 35 40 45 50 35 40 45 50 Valid fire levels 55 60 65 70 55 Default sensitivity levels N A 3 Valid sensitivity levels N A 1 2 3 4 5 ancillary devices have fixed responses except the Apollo Input Output module and the Discovery Sounder Beacon devices The input for the Apollo Input Output module device can be configured for response as a fire fault alert or indication only The tone pair and volume for the Discovery Sounder Beacon can be configured 4 1 5 Discovery Device Functions The following functions are available with Apollo Discovery devices e Print drift compensation level by loop e Print device date of manufacture e Enable or disable LED pulsing mode e Configure Discovery Sounder Beacon volume setting using magnetic wand e Configure Discovery Sounder Beacon auto stop function 4 1 6 Zone Allocation The 96 Zone 40 Character Discovery has 96 programmable zones All loop devices can be programmed into one of these zones through the engineers menu Activation o
22. m battery charging 1 5A current Battery type Battery size Panel inputs Remote Fault Remote Evacuate Remote Silence Remote Reset Panel outputs For each loop Alarm circuits Auxiliary supply Document Ref DVAOAPP Rev 2 09 02 2010 2 off 12V 12AH sealed lead acid standby battery 151mm x 98mm x 97 5mm Fully monitored circuit 3 9 EOL 680R active Fully monitored circuit 3k9 EOL 680R active Fully monitored circuit 3k9 EOL 680R active Fully monitored circuit 3k9 EOL 680R active LO LO LI LI 2atlA Loop out ve Loop out ve Loop return Loop return ve per circuit 18 8V 28V 500mA Page 14 of 23 Raised by GG Checked__ 187 4 0 Software Specifications 4 1 Overview of Engineers Functions This section describes an overview of the functions available to the end user 4 1 1 Changing Time and Date The user can manually set the time and date although this should not normally be required The current time is maintained by a dedicated battery when all power removed from the system How to set the time and date is described in the user manual 4 1 2 Delay of Operation of Outputs The activation of panel outputs alarm circuit and cause effect can be delayed upon detection of an automatic alarm condition to allow for the cause of the alarm to be investigated The delay can be programmed for a period of between 1 and 10 minutes The delay is active for one period every day
23. message is available for viewing with the scroll events button Raised by GG Checked__ 187 3 3 Engineer s Facilities ue LINK LK2 TO ENABLE Loops 1 loop 2 loop 3 loop 4 loop nb Do not fit link CONFIGURATION mE LINKTO DISABLE DISPLAY MONITOR Lithium battery OFF ON OFF ON Fit link to enable earth fault monitoring Remove link to enable earth fault monitoring Move switch to right to enable changes to site specific data Move switch to left to disable when changes complete Set switches 1 and 2 for number for loops 2 OFF OFF ON ON Auxiliary supply fuse 500mA PC port Cherry keyboard port Alarm 1 fuse 1A Alarm 2 fuse 1A 9ecccccccceceeeeseeeesscen 9060eseeece2000000902905 System fault reset Processor reset Loop card 1 position Loop card 2 position Loop card 3 position Loop card 4 position Document Ref DV40APP Rev 2 09 02 2010 Page 11 of 23 Raised by GG Checked__ 187 3 4 Power Supply Power supply status indicators OUTPUT OK Output healthy BATT CHARGE FAULT Battery or charger fault EARTH FAULT Short circuit between earth and field cabling 5 8V FAULT 5 8V supply fault MAINS FAULT Mains failed B3 End outer insulation close to PSE OUTPUT OK and r
24. oute earth connection back Power output connector exTTICHARGE to primary earth connection point to motherboard EARTH FAULT 5 8V FAULT Fit cable tie here to secure Link fitted to select incoming mains cable 5V output MAINS FAULT Terminals not used Battery fuse 6 3A MIESTLAMPS BADZ E Battery terminals Fix thermistor to battery lead D t fit links f with cable tie D ROETIEMIRS TOF EARTH CAP or EARTH Fit battery terminals towards FLT outside of enclosure Incoming mains supply Connect mains in earth to primary Fix to side of power supply with cable enclosure earth stud here ties Connect chassis to enclosure secondary earth stud here 3 5 Use of Auxiliary Inputs Auxiliary inputs are provided to allow remote operation of the following functions e Fault e Evacuate e Silence e Reset Each input circuit is fully monitored for open and short circuit faults To activate an input a 680 ohm resistor should be connected across the input circuit by a normally open switch contact Two switches are shown in Figure 1 although there is no limit to the number of switches Document Ref DV40APP Rev 2 09 02 2010 Page 12 of 23
25. rinter and 2 x 12V 12Ah battery set 2604018 96 Zone 40 Character Discovery 1 loop analogue addressable control panel with 96 zone LEDs c w 1 loop card expandable to 4 loops with three 2500 130 Additional loop card Insertable type display overlay with English printed inserts Cabinet size 480h x 410w x 144d Space for printer and 2 x 12V 12Ah battery set 2604019 96 Zone 40 Character Discovery 2 loop analogue addressable control panel with 96 zone LEDs c w 2 loop cards expandable to 4 loops with two 2500 130 Additional loop cards Insertable type display overlay with English printed inserts Cabinet size 480h x 410w x 144d Space for printer and 2 x 12V 12Ah battery set 2604020 96 Zone 40 Character Discovery 3 loop analogue addressable control panel with 96 zone LEDs c w 3 loop cards expandable to 4 loops with one 2500 130 Additional loop card Insertable type display overlay with English printed inserts Cabinet size 480h x 410w x 144d Space for printer and 2 x 12V 12Ah battery set 2604021 96 Zone 40 Character Discovery 4 loop analogue addressable control panel with 96 zone LEDs c w 4 loop cards Insertable type display overlay with English printed inserts Cabinet size 480h x 410w x 144d Space for printer and 2 x 12V 12Ah battery set 2604022 96 Zone 40 Character Discovery 5 loop analogue addressable control panel with 96 zone LEDs c w 5 loop cards expandable to 8 loops with three 2500
26. s are designed to assist with cable installation The panel has a 4 line x 20 character backlit LCD display showing device address zone type status and location text The LCD display provides capacity for 40 characters of user programmable device text It is also used as a menu driven engineers configuration display User controls are accessed by means of keyswitch enabled membrane controls with password protection for engineer purposes 96 zonal LEDs are provided as standard and plug in printer is available as an option The panel provides 2 common fire changeover relays and 1 common fault changeover relay each rated at 1A 30V DC Four fully monitored panel inputs are provided for remote silence remote reset remote evacuate and remote fault The evacuate input will operate the general alarms and may be programmed to operate the fire relay The panel may control up to 14 repeaters with full user capability via RS485 data comms Extensive panel and network cause effect programming is achieved via the PC programming package Full networking with other 96 Zone 40 Character Discovery panels network repeaters and graphics package may be achieved with an additional plug in network driver card Network cause effect may be programmed between 96 Zone 40 Character Discovery panels and active network repeaters Document Ref DV40APP Rev 2 09 02 2010 Page 2 of 23 Raised by GG Checked__ 187 Raised by GG Checked__ J
27. tains device points in the same way as a zone but the group is used solely for cause effect programming Document Ref DV4OAPP Rev 2 09 02 2010 Page 17 of 23 Raised by GG Checked JBI Overview of Engineer s Menu Options Operate Access Controls Key Switch followed by the following NEERS FUNCTION S ACCESS CODE 8812 1 USER FUNCTIONS 2 ENG 1 TIME DATE 2 MODES 1 PANEL DELAY 1 DELAY ENABLE _ 2 DELAY TIMES 3 DELAY DURATION 2 DAY NIGHT MODE 1 DAY MODE 2 NIGHT MODE 3 TIMER MODE 4 OFF 8 BAUD RATE _ 3 ENABLE DISABLE 1 POINTS 1 SINGLE POINT 2 RANGE OF POINTS 3 VIEW DISABLED POINTS 4 ENABLE ALL POINTS 1 LOCAL 2 GLOBAL 3 SPECIFY PANEL 2 ZONES 1 SINGLE ZONE 2 RANGE OF ZONES 3 VIEW DISABLED ZONES PRINTER 4 SOUNDERS 5 INPUTS 1 SINGLE INPUT 2 RANGE OF INPUTS 3 VIEW DISABLED INPUTS OUTPUTS 4 VIEW e VIEW EVENT LOG VIEW SUPPRESSED EVENTS 1 ALERTS 2 FAULTS 3 INDICATIONS 4 DISABLEMENTS 5 TEST VIEW POINT STATUS 1 POINT DISABLED 2 POINT ENABLED ONE PERSON TESTS 1 POINT WALK TEST 2 ALARM WALK TEST 3 BEACON TEST 6 PRI
28. the same colour as the cabinet back box and fitted by means of pinch bolts thus avoiding the need to drill the cabinet 1 Q 00 000 00 0 0000000 I n le b HoleHeight a 487mm 377mm L HoleWidth b 47mm 332mm Bezel Depth g 30mm 30mm 2501 124 Semi flush bezel for 96 Zone 40 Character Discovery 1 4 loop panel and repeater panels 2500 844 2501 121 Semi flush bezel for LCD repeater panels 2500 830 amp 2500 842 Document Ref DVAOAPP Rev 2 09 02 2010 Page 6 of 23 Raised by GG Checked JBI 2 3 Fully Flush Bezel Fixed to the standard cabinet back box in place of the door and sized larger than the back box Available in polished or brushed brass stainless steel and painted finishes e F a SS eo M N a d ee ee 9 E ul un n uu fc o a op t L 2 1 lO 0 0 0 0 0 0 0I 00000000 I IER 485mm 375mm L HoleWidth 435mm 350mm Hole Depth Bezel Height EY Bezel Width Hinge Protrusion 20mm large repeater panel 2500 844 painted to customer s specification amp large repeater panel 2500 844 brushed or polished panel 2500 830