Home
Installation And User Manual - inverter
Contents
1. o mm Do D gt VACON 37 APPENDIX ADDITIONAL INFORMATION 9 APPENDIX ADDITIONAL INFORMATION 9 1 Max master This parameter represents the value of the Max_Master property of the node s Device object The value of Max_Master specifies the highest allowed address for the master nodes The val ue of Max_Master shall be less than or equal to 127 If Max_Master is not writable in a node its value shall be 127 The drive has a readable only value thus 127 Example of use We have 4 devices on the bus given addresses from 1 to 4 A token is passed in the MS TP allowing each device to send in turns Device no 1 passes the token to device no 2 no 2 to device no 3 no 3 to no 4 and no 4 to no 1 Max master is set to 127 Having received the token and sent its data the device with the highest address on the bus in this case 4 will check the bus for new devices by sending a Poll for master message After the first token passing round the Poll for master message is sent to address 5 after the second round time to address 6 and so forth until address 127 is reached Because there are no de vices at addresses 5 to 127 the sender of the message must wait for a reply to each Poll for master message after each token passing round If there is on the bus another manufacturer s device that supports Max master property it can be used to prevent the Po for master messages by giving it the highest addre
2. 1 management device IP address BACnet IP broadcast P5 8 3 1 5 BBMD UDP Port 1 65535 47808 management device UDP port The Time to Live value is the number of sec onds within which a for eign device must re register with a BBMD P5 8 3 1 6 Time to Live 0 255 S 0 The value also applies as the interval for trans mitting the Register For eign Device message to BBMD device 0 means not in use MONITORING VALUES P5 8 3 1 3 Protocol in use 0 1 0 1 Stopped P5 8 3 2 1 Fieldbus protocol 1 3 2 Operational status 3 Faulted 0 99 Number of mes Communication sta sages With errors P5 8 3 2 2 tus 0 0 99 999 0 0 0 999 Number of mes sages without communi cation errors Honeywell 19 Programming Code Parameter Min Max Unit Default ID Description Actual instance Serial num Shows actual Device P5 8 3 2 3 0 65535 Object s instance num number ber ber P5 8 3 2 4 Control word hex Ge chapters 6 2 and P5 8 32 5 Status word hex 2 chapters 6 2 and Table 7 Parameters related with BACnet used through Ethernet Programming Honeywell 20 5 3 BACnet MS TP parameter descriptions 5 3 1 BACnet MS TP Parameters P5 7 3 1 1 BAUD RATE Select the communication speed for the network The default value is 9600 baud If value Auto is chosen this parameter is not editable P5 7 3 1 2 AUTOBAUDING NOTE Th
3. 2 1 Fieldbus protocol 1 3 2 Operational status 3 Faulted 0 99 Number of mes Communication sta sages with errors P5 7 3 2 2 t s 0 0 99 999 0 0 0 999 Number of mes sages without communi cation errors Actual instance Serial Shows actual Device P5 7 3 2 3 0 65535 Object s instance num number number ber 0 None 1 Sole Master 2 Duplicate MAC ID 3 Baud rate fault P5 7 3 2 4 Fault code 0 3 0 See chapters 6 2 and P5 7 3 2 5 Control word hex 63 P5 7 3 2 6 Status word hex Ges chapters 6 2 an Table 5 Parameters related with BACnet used through MS TP Programming Honeywell 18 5 2 BACnet IP parameters and monitoring values 5 2 1 Ethernet common settings M5 8 1 Code Parameter Min Max Unit Default ID Description P5 8 1 1 IP address mode See page 23 P5 8 1 2 IP address See page 23 P5 8 1 3 Subnet mask See page 23 P5 8 1 4 Default gateway See page 23 P5 8 1 5 MAC address See page 23 Table 6 Common settings for BACnet IP 5 2 2 BACnet IP settings Code Parameter Min Max Unit Default ID Description PARAMETERS Device Object s instance P5 8 3 1 1 Instance number 0 4194304 0 number 0 Serial number P5 8 3 12 Communication 0 65535 s 10 0 Not used time out 0 Not used 1 Used BACnet IP broadcast P5 8 3 1 4 BBMD IP address 192 168 0
4. MAC address of the control board MAC address Media Access Control is a unique address given to each network host Programming Honeywell 24 5 4 2 BACnet IP settings P5 8 3 1 1 INSTANCE NUMBER Similar to BACnet MS TP device object instance number see page 20 P5 8 3 1 2 COMMUNICATION TIME OUT BACnet board initiates a communication error if the Ethernet connection is lost Communica tion time out parameters define the minimum delay between UDP packages received from the master The timer is reset and started after each received UDP package This parameter can be used if the master is periodically polling the slaves P5 8 3 1 3 PROTOCOL IN USE BACnet IP protocol can be enabled and disabled with this parameter When the parameter val ue is set to 1 the BACnet IP protocol is enabled and disabled when set to 0 P5 8 3 1 4 BBMD IP ADDRESS BACnet IP broadcast management device IP address P5 8 3 1 5 BBMD UDP PoRT BACnet IP broadcast management device UDP port P5 8 3 1 6 TIME TO LIVE The Time to Live value is the number of seconds within which a foreign device must re register with a BBMD The value also applies as the interval for transmitting the Register Foreign De vice message to BBMD device 0 means not in use 5 4 3 BACnet IP monitoring values P5 8 3 2 1 FIELDBUS PROTOCOL STATUS Fieldbus Protocol Status tells the status of the protocol P5 8 3 2 2 COMMUNICATION STATUS The Communication status shows how
5. Motor Voltage Motor Voltage V R AV8 Unit Temperature Heatsink Temperature eC R AV9 Motor Torque ns metornemnal R AV10 Operating Days GEN ting Days reset Day R AV11 Operating Hours Hours reser Hour R AV12 Kilowatt Hours dee Hours pesetta kWh R AV13 Torque Reference Torque Reference 96 R Calculated motor tem AV14 Temperature Rise N m m 96 R motor AV15 fb ProcessdataOut 01 Application specific 16 bit Resolution 1 R AV16 fb ProcessdataOut 02 Application specific 16 bit Resolution 1 R AV17 fb ProcessdataOut 03 Application specific 16 bit Resolution 1 R AV18 fb ProcessdataOut 04 Application specific 16 bit Resolution 1 R AV19 fb ProcessdataOut 05 Application specific 16 bit Resolution 1 R AV20 fb ProcessdataOut 06 Application specific 16 bit Resolution 1 R AV21 fb ProcessdataOut 07 Application specific 16 bit Resolution 1 R AV22 fb ProcessdataOut 08 Application specific 16 bit Resolution 1 R AV23 Active Fault Code Active Fault Code R Speed Reference per AV24 Speed Reference centage of nominal 96 C speed AV25 Current Limit Current Limit A W AV26 Min Frequency Minimum Frequency Hz W Communications Honeywell 30 AV27 Maximum Frequency Maximum Frequency Hz Ww AV28 Accel Time Acceleration Time S W AV29 Decel Time Deceleration Time s W AV30 fb Processdataln 01 Application specific 16 bits Resolution 1 C AV31 fb_Processdataln_02 Application specific 16 bits Resolution 1 C AV
6. S eA 428u3 g Jajdeyo aas sed ejqe yoayug cp saydeyo aas sa qe u m q So2uejsip 42949 Bulges 5285 Sc nu ulul SJojouleJed sngpiey Jadlo 49949 IL Cell 1020104d papayas 4298uj3 SJajouie ed sndqple Y994D yO Jajunog 0 1 s6ulyo2olJelul euJajxe y2 uo pedAay uo pa 84 Y99YD 9181s AQV3yd U eiep eui S SaseaJoul g slqel ees s uueuJ peq Joj J91uno3 und JOU seop J9juno cCcegs Vegeta Jed snjejs uonjeoiunululoo 428453 UO EIIUNWIWWOD Jood uoneoiunuJuloo ON eng ay Woy Jels JOU saop aAU0 Figure 9 Fault tracing diagram for BACnet IP Honeywell 35 Fault tracing Quick setup Honeywell 36 8 Quick setup Following these instructions you can easily and fast set up your BACnet bus for use Choose control place 4 A Press LOC REM button on keypad to select Remote Control Place B Select Fieldbus as remote control place Main Menu gt Quick Setup M1 gt Rem Ctrl Place P1 15 FieldbusCTRL Make these settings in the master software Set Control Word to 0 AV36 Fb Control Word Lo16 Set Control Word to 1 AV36 Fb Control Word Lo16 Frequency converter status is RUN Set Reference value to 50 50 0096 AV24 Speed Reference Frequency setpoint is 25 00 Hz if MinFreq is 0 00 Hz and MaxFreq is 50 00 Hz Set Control Word to 0 AV36 Fb Control Word Lo16 Frequency converter status is STOP
7. many error and how many good messages the frequen cy converter has received The Communication status includes a common error counter that counts CRC and parity errors and a counter for good messages Bad Frames Good messages Number of messages received Number of messages received 0 99 0 999 with errors without errors Table 11 Communication status P5 8 3 2 3 ACTUAL INSTANCE NUMBER The Device Object s actual instance number This monitoring value is needed when value 0 is written to parameter P5 8 3 1 1 Honeywell 25 P5 8 3 2 3 CONTROL WORD Shows the Control Word received from the bus P5 8 3 2 4 STATUS WORD Shows the current Status Word that is sent to the bus Programming Communications 6 6 1 Communications Object types and properties supported Honeywell 26 Property Object Type Device Binary Value Analog Value Object Identifier Object Name gt X X X X Object Type System Status X X Vendor Name Vendor Identifier Model Name Firmware Revision Application Software Version Protocol Version Protocol Revision Protocol Services Supported Protocol Object Types supported Object List Max APDU Length Accepted Segmentation Supported APDU Timeout Number of ADPU Retries Max Master Max Info Frames Device Address Binding Database Revision X X X X X X
8. the last device on the bus the bus termination must be set Locate the DIP switches to the right of the control keypad of the drive and turn the switch for the RS485 bus termination resistor to position ON Biasing is built in the termination resistor See also step 9 on page 15 m ON diese 5 gt OFF 14 E iN Bus termination resistor Honeywell 15 BACnet installation Unless already done for the other control cables cut free the opening on the VFD cover for the RS485 cable protection class IP21 Remount the VFD cover and run the RS485 cables as shown in picture NOTE When planning the cable runs remem ber to keep the distance between the fieldbus cable and the motor cable at a minimum of 30 cm Fieldbus cables The bus termination must be set for the first and the last device of the fieldbus line See picture below See also step 6 on page 14 We recommend that the first device on the bus and thus terminated was the Master device ew Termination activated BACnet MS TP Termination activated with DIP switch A Termination 2 Bus termination deactivated Programming Honeywell 16 5 Programming Basic information on how to use the control keypad you will find in the Application Manual The navigation path to the fieldbus parameters may differ from ap
9. uoneululI9 42903 8 SN nu ui ui sJojeugeJed snqpietj Jadlo 42949 I SAN 1020104d pajyoajas 429u3 T SadiAap snq JaU10 Burges 28u Loi JENY NENEA 195 I GOEL GW aqeIDeA Jolluou ol ped a asp SJ0 SIs2J uolnjeuluLI9 Y29049 SJojeuieJed sJalselN 429u2 0 1 s6up2olbelul jeusa xa 42949 LOEW 40 SULIN JeleuleJed yoayg ped ax uo pa a4 42949 i pueuiuio2 NAY auf JalseIN s oq 2e1d 1013005 se pal52alas snqp lJ S LelelS AQV3yd u aoIAap at S si l ulieuied snqplay 49949 e 40 Jeluno0 SaseaJ2ul g elqel ees sawey peq Jol Jeluno0 E DEEN una jou s op J9juno ccegs Veera ued smeis uoneoiunululoo 2au2 uonje iunuluJ02 Jood uoneoiunudul02 ON snq ay Woy Jels 1ou s op seALQ Figure 8 Fault tracing diagram for BACnet MS TP Honeywell 34 Fault tracing seu21ws D al So2IMop fJesso eu Jadlo 42803 saolAap Sng Jann Loi 98AV OI0EUEA 18S GEL Gn alqelIJeA Jolluouu ol pedAay esf cpuewWuwoo NAH 9ND Je1se u seoq sleuluuJal ul sJolonpuoD jo 1ueuj eoejd pao Dat Sjno JO 9 qe 42949 Burges eu V d 40 G LIN J9jeujeed 29u3 La2pId 1oJ1uoD se pal5alas snqpjal s SJajnoJ JaU 10 Jo NV1M ra 42849 pJodeu aas sJojonpuoo pue sa qed jo Duddus 42949 suoll52auuoo 2 49 oa Aemayeb SseJppe dl 42949 ssajawesed S J9
10. 0 5 1 one or more of the following conditions for the associated protective circuit shall be satisfied A fixed connection and a the protective earthing conductor shall have a cross sectional area of at least 10 mm Cu or 16 mm Al Safety Honeywell 4 or b an automatic disconnection of the supply in case of discontinuity of the protective earthing conductor or C provision of an additional terminal for a second protective earthing conductor of the same cross sectional area as the original protective earthing conductor Minimum cross sectional area of the corre Cross sectional area of phase conductors S 2 sponding protective earthing conductor De mm S 16 S 16453535 16 35 lt 5S S 2 The values above are valid only if the protective earthing conductor is made of the same metal as the phase conductors If this is not so the cross sectional area of the protective earthing conductor shall be determined in a manner which produces a conductance equivalent to that which results from the application of this table Table 2 Protective earthing conductor cross section The cross sectional area of every protective grounding conductor which does not form part of the supply cable or cable enclosure shall in any case be not less than 2 5mm if mechanical protection is provided or 4mm if mechanical protection is not provided For cord connected equipment provi sions shall be
11. 1 Binary Value EE 27 6 1 2 Analog Value Object Ne 29 6 2 Control word DIES EE 31 6 3 Status word bits ise e be e ER RE e a RC RR EX Cea de d e be d des 31 MEE V card Pr E 32 Gel EE Tee T E 32 7 2 Other fault conditions eee 33 E CT ET NEE 36 9 Appendix additional information pe 37 91 Max in 37 10 Annex Protocol implementation conformance statement 38 Honeywell 1 Safety 1 Honeywell 2 Safety This manual contains clearly marked cautions and warnings which are intended for your per sonal safety and to avoid any unintentional damage to the product or connected appliances Please read the information included in cautions and warnings carefully The cautions and warnings are marked as follows DANGEROUS VOLTAGE A WARNING or CAUTION Table 1 Warning signs 1 1 Danger The components of the power unit of the SmartDrive are live when the VFD is connected to mains potential Coming into contact with this voltage is extremely dangerous and may cause death or severe injury The motor terminals U V W and the brake resistor terminals are live when the drive is connected to mains even if the motor is not running After disconnecting the VFD from the mains wait until the indicators on the keypad go out if no keypad is attached see the indicators on the cover Wait 5 more minutes before doing any work on the connecti
12. 32 fb Processdataln 03 Application specific 16 bits Resolution 1 C AV33 fb Processdataln 04 Application specific 16 bits Resolution 1 C ID number that is used 0 to 65535 AVR Anykaram ID in AV35 resolution 1 Lii AV35 AnyParam Value Value onl Denied by 32 bits Value Ww AV34 AV36 Fb Control Word Lo16 Xed Control Word First 46 bits Resolution 1 C 16 bits 0 15 AV37 Fb Control Word Hite Xed Control Word Last Ae bits Resolution 1 C 16 bits 16 31 AV38 Fb Status Word Lote Xed Status Word First Ae bits Resolution 1 R 16 bits 0 15 AV39 Fb Status Word Hite Xed Status Word Last 46 bits Resolution 4 R Ke 16 bits 16 31 ANSI IEEE 754 floating point Binary coding can be done only if the value has no decimals Table 14 NOTE Present Value Access Types R Read only W Writeable C Commandable Commandable values support priority arrays amp relinquish defaults High and Low limits for the objects are defined in the application See corresponding applica tion for exact limits Honeywell 31 Communications 6 2 Control word bits Bit Name Value 1 Value 0 Description BO Start Stop Start request Stop request SEHR application B2 Fault reset Reset faults No action Command to reset fault B3 B15 Not used Table 15 Control Word bits 6 3 Status word bits Bit Name Value 1 Value 0 Description BO Ready Ready Not ready Indicates whether the
13. D cover opening for the Ethernet cable protection class IP21 Figure 5 Remount the VFD cover NOTE When planning the cable runs remember to 5 keep the distance between the Ethernet cable and the motor cable at a mini mum of 30 cm Ethernet Figure 6 Honeywell 13 BACnet installation 4 2 Prepare for use through MS TP Strip about 15 mm of the RS485 cable see specification on page 8 and cut off the grey cable shield Remember to do this for both bus cables Leave no more than 10 mm of the cable outside the terminal block and strip the cables at about 5 mm to fit in the terminals See picture below 10 9 3 Also strip the cable now at such a distance from the terminal that you can fix it to the frame with the grounding clamp Strip the cable at a maximum length of 15 mm Do not strip the aluminum cable shield Then connect the cable to its appropriate terminals on Honeywell SmartDrive 4 standard terminal block terminals A and B A negative B positive See Figure 7 RS485 terminals A and B U xcci messe Si Fe Se Im ERB BHH 2 P75 16 77319 EECH I Figure 7 BACnet installation Honeywell 14 Using the cable clamp included in the delivery of the drive ground the shield of the RS485 cable to the frame of the VFD 5 7 NS Cable clamp If the drive is
14. Honeywell Installation and User Manual BacNet protocol for Variable Frequency Drives Honeywell 0 INDEX Document DPD00546B Version release date 6 9 11 TJ Safety saiae ana u aussi c eae i Eee 2 UMP UE E I M PT 2 1 2 WARNINGS 3 1 3 Grounding and ground fault protection pp 3 1 4 Electro magnetic compatibility EM 4 2 BACnet general info E 6 3 BACnet technical data eei riter etin enbne sos 8 3 1 BACnet MS TP protocol memes 8 3 2 BAGCnetIP protocol ny m um e tee re eed ley dee Rd deed eae 8 4 BACnetinstallation 1 11eeeeeeee esee rennen NEEN RKEN ERR KENREEEN NEEN RK KEN KREENRKEEN En 10 4 1 Prepare for use through Ethernet eee 11 4 2 Prepare for use through MS TP pp 13 5 Programming E 16 5 1 BACnet MS TP parameters and monitoring values M5 7 3 16 5 2 BACnet IP parameters and monitoring values pp 18 5 2 1 Ethernet common settings M5 8 1 seen enne 18 5 2 2 BACMOt IP Settings E 18 5 3 BACnet MS TP parameter descriptions RN 20 5 3 1 BACnet MS TP Parameters mener rns 20 5 9 2 BACnet MS TP monitoring UE 21 5 4 BACnet IP parameter descriptions Ne 23 5 4 1 Ethernet common El Le E 23 5 4 2 BACnet IP settings i ep ade rtu br eon utei tad uve ebd ee den tus 24 5 4 3 BACnet IP monitoring EE 24 6 el NU Un E 26 6 1 Object types and properties supported Ne 26 6 1
15. X OK X zl zl X X X X X OK zi x x x Preset Value Status Flags Event State Out of Service x x x x Units x X X x gt x Priority Array Relinquish Default x Xx Polarity Active Text X Inactive Text X Only with commandable values Table 12 Object types and properties supported Honeywell 27 Communications 6 1 1 Binary Value Object Present iei Object Name Description aere 1 SC Type avo rentre ere a k R BV1 Run Stop State E ed arive Stop Run R BV2 _ Fwd Rev State ee direc Fwd Rev R BV3 Fault State Indicates if a fault is active OK Fault R BV4 Alarm State os SS EE OK Alarm R BV5 At Setpoint Ref Frequency reached False True R BV6 At Zero Speed iaa Running at zero False True R BV7 fb ProcessdataOut 01 Bit 0 ProcessDataOut1 bit 0 0 1 R BV8 fb ProcessdataOut 01 Bit 1 ProcessDataOut1 bit 1 0 1 R BV9 fb ProcessdataOut 01 Bit 2 ProcessDataOut1 bit 2 0 1 R BV10 fb ProcessdataOut 01 Bit 3 ProcessDataOut1 bit 3 0 1 R BV11 fb ProcessdataOut 01 Bit 4 ProcessDataOut1 bit 4 0 1 R BV12 fb ProcessdataOut 01 Bit 5 ProcessDataOut1 bit 5 0 1 R BV13 fb ProcessdataOut 01 Bit 6 ProcessDataOut1 bit 6 0 1 R BV14 fb ProcessdataOut 01 Bit 7 ProcessDataOut1 bit 7 0 1 R BV15 Run Stop CMD COMUNE drive FB stop Run C BV16 F
16. an PADO dards 135 2004 Default IP Selectable Fixed or DHCP AutolP Table 4 Honeywell 9 BACnet technical data BACnet installation Honeywell 10 4 BACnet installation 1 Open the cover of the VFD The relay outputs and other l O terminals may have a dangerous control voltage present even when the drive is disconnected from mains Figure 2 2 Locate the components that you will need on the VFD to connect and run the BACnet cables Be sure not to plug the Ethernet BACnet IP cable to the terminal under the key pad This might harm your personal computer Honeywell 11 BACnet installation RS485 terminals Ei 21 22 23 24 25 26 32 33 thernet 12 13 14 15 16 17 18 19 3 BY Ethernet cable run OOOOOOOOQ SE 1 2 3 4 5 6 7 8 9 10 TH OOOOOOOOOCOl 1 0 terminal see larger picture Grounding bar Figure 3 You can use the BACnet communication protocol through Ethernet and RS485 4 1 Prepare for use through Ethernet Connect the Ethernet cable see specification on page 8 to its terminal and run 3 the cable through the conduit as shown in Figure 4 NOTE Pay attention that the non bending part of the connector does not exceed 40 mm in length Ethernet cable Figure 4 BACnet installation Honeywell 12 4 Cut the VF
17. ationally accepted protocol for building automation e g lightning control air conditioning and heating automation and control over a communications network BACnet provides a method by which computer based control equipment from different manu facturers can work together or interoperate For this to be achieved components must be able to exchange and understand BACnet data messages Your Honeywell SmartDrive is equipped with BACnet support as standard BACnet IP Switch Ethernet to MS TP i i i Router Figure 1 Principal example diagram of BACnet Honeywell 7 BACnet general info BACnet technical data Honeywell 8 3 BACnet technical data 3 1 BACnet MS TP protocol nterface 40 Data transfer method RS 485 MS TP half duplex STP Shielded Twisted Pair type Belden 9841 or similar Connections and Connector 2 5 mm Transfer cable communications Electrical isolation Functional As described in ANSI ASHRAE Stan BACNET MONTE dards 135 2004 Baud rat j 38400 and 6800 EE baud supports autobaud detection Table 3 3 2 BACnet IP protocol nterface DOBaseTX 802 3 compatible Data transfer method thernet half full duplex Data transfer speed 10 100 MBit s autosensing Protocol BACnet over UDP IP Connections and Shielded RJ45 connector NOTE Max Connector communications length of the non bending part 40 mm able type AT5e STP As described in ANSI ASHRA t
18. drive is ready or not B1 Run Running stop Indicates whether the drive is running or stopped Indicates the rotation direc B2 Direction Counterclockwise Clockwise tion of the motor B3 Fault Faulted Not faulted Indicates if a fault is active BA Alarm Alarm No alarm Indicates if an alarm is active B5 AtReference True False Reference frequency reached B6 ZeroSpeed True False Motor running at zero speed B7 B15 Not used Table 16 Status Word bits Fault tracing Honeywell 32 T Fault tracing When an unusual operating condition is detected by the VFD control diagnostics the drive ini tiates a notification visible for example on the keypad The keypad will show the ordinal num ber of the fault the fault code and a short fault description The fault can be reset with the Reset button on the control keypad or via the I O terminal The faults are stored in the Fault history menu which can be browsed The different fault codes you will find in the table below This fault table presents only the faults related to the fieldbus in use 7 1 Typical fault conditions Fault condition Possible cause Remedy Termination Install termination resistors resistor Missing or excessive termination resistor at both ends of the fieldbus line Supply or motor cables are located too close to the fieldbus cable Cabling Wrong type of fieldbus cable Too long cabling Ensu
19. ell products visit us online at http ecc emea honeywell com Automation and Control Solutions Honeywell GmbH B blinger Str 17 71101 Sch naich Germany Telephone 49 7031 637 01 EN2B 0371GE51 R1210 Telefax 49 7073 637 493 December 2010 www ecc emea honeywell com 2010 Honeywell International Inc Honeywell
20. is function is only used at start up This function is set off by default If the parameter is given value 1 the automatic baud rate de tection is used The automatically detected baud rate is then shown as value of parameter P5 7 3 1 1 Baud rate P5 7 3 1 3 MAC ADDRESS The parameters of every device must be set before connecting to the bus Especially the pa rameters MAC adaress and Baud rate must be the same as in the master s configuration The first parameter MAC Medium Access Control address must be unique on the network to which it is connected The same MAC address may be used on a device on another network within the internetwork Addresses 128 254 are reserved for slaves Addresses 1 127 are valid for both masters and slaves The portion of the address space that is actually used for masters in a particular instal lation is determined by the value of the Max Master property of the Device object It is recommended that MAC address 0 be reserved for use by the MS TP router 255 is re served for broadcasts P5 7 3 1 4 INSTANCE NUMBER The Device Objects Instance number must be unique across the entire BACnet internetwork because it is used to uniquely identify the BACnet devices It may be used to conveniently iden tify the BACnet device from other devices during installation If O default is selected the Device Instance number is read from the VFD This unique number is then shown in the Monitor menu If any other value
21. made so that the protective earthing conductor in the cord shall in the case of failure of the strain relief mechanism be the last conductor to be interrupted NOTE Due to the high capacitive currents present in the VFD fault current protective switches may not function properly Do not perform any voltage withstand tests on any part of the drive There is a A certain procedure according to which the tests shall be performed Ignoring this procedure may result in damaged product 1 4 Electro magnetic compatibility EMC This equipment complies with IEC 61000 3 12 provided that the short circuit power Ssc is greater than or equal to 120 at the interface point between the user s supply and the public sys tem It is the responsibility of the installer or user of the equipment to ensure by consultation with the distribution network operator if necessary that the equipment is connected only to a supply with a short circuit power Ssc greater than or equal to 120 Honeywell 5 Safety BACnet general info Honeywell 6 2 BACnet general info BACnet stands for Building Automation and Control Networks It is the common name for the communication standard ISO 16484 5 which defines the methods and the protocol for cooper ating building automation devices to communicate Devices can be designed to operate using BACnet communication protocol as well as utilising BACnet protocol to communicate between systems BACnet is an intern
22. ons of the drive Do not open the cover before this time has expired After expiration of this time use a measur ing equipment to absolutely ensure that no voltage is present Always ensure absence of voltage before starting any electrical work The control l O terminals are isolated from the mains potential However the relay outputs and other I O terminals may have a dangerous control voltage present even when the drive is disconnected from mains Before connecting the VFD to mains make sure that the front and cable covers of the drive are closed P PP bbb During a ramp stop see the Application Manual the motor is still generating voltage to the drive Therefore do not touch the components of the VFD before the motor has completely stopped Wait until the indicators on the keypad go out if no keypad is attached see the indicators on the cover Wait additional 5 min utes before starting any work on the drive Honeywell 3 Safety 1 2 Warnings The Honeywell SmartDrive is meant for fixed installations only Do not perform any measurements when the VFD is connected to the mains The ground leakage current of the Honeywell SmartDrive exceeds 3 5mA AC According to standard EN61800 5 1 a reinforced protective ground connec tion must be ensured See chapter 1 3 Corner grounding is allowed for the drive types with the ratings from 72 A to 310 A at 380 480 V supply and from 75 A to 310 A at 208 240 V suppl
23. plication to application The exemplary paths below apply to the Honeywell SmartDrive 1 First ensure that the right fieldbus protocol is selected Navigate Main Menu I O and Hardware M5 RS 485 M5 7 OR Ethernet M5 8 gt Common settings M5 7 1 gt Protocol P5 7 1 1 gt Edit gt Choose protocol 2 Select Fieldbus control as the Remote Control Place Navigate Main Menu Quick Setup M1 Rem Ctrl Place P1 15 OR Navigate Main Menu Parameters M3 Start Stop Setup M3 2 Rem Ctrl Place P3 2 1 3 Choose source of reference Navigate Main Menu Parameters M3 References M3 3 4 Set fieldbus parameters M5 7 and M5 8 See below 5 1 BACnet MS TP parameters and monitoring values M5 7 3 Code Parameter Min Max Unit Default ID Description PARAMETERS Communication speed 1 9600 P5 7 3 1 1 Baud rate 1 4 bd 1 2 19200 3 38400 4 76800 Automatic baudrate detection 0 Off P5 7 3 1 2 Autobauding 0 1 1 1 On The automati cally detected baud rate is then shown as value of parameter P5 7 3 1 1 P5 7 3 1 3 MAC address 1 127 1 Device Object s instance P5 7 3 1 4 Instance number 0 65535 0 DUMPEN ss 0 Automatically gegerated P5 7 3 15 Communication 0 65535 s 10 0 Not used time out Honeywell 17 Programming Code Parameter Min Max Unit Default ID Description MONITORING VALUES 1 Stopped P5 7 3
24. re grounding in all Grounding Inadequate grounding points on the net Faulty connections Excessive stripping of cables Connections e Conductors in wrong terminals Too loose connections of conduc tors Faulty address Overlapping slave addresses Wrong baud rate Wrong control place selected Parameter Table 17 Typical fault conditions Fault tracing Honeywell 33 tions Other fault cond 7 2 f the most usual prob IX some o I help you to locate and f lagram WI The following fault tracing d tributor IS lems If the problem persists contact your local d Suon2euuoo soo Joy sleuluuJal Y29049 Jaydeyo ees s10 2npuoo pue sejqe jo Buiddi uns 42949 iaolAap yoea Joy 6ulpunoJ6 exeuu 0 J qw w y Jeldeu5 aas 6ulpunoJ6 y2 49 Je1deuo ees sadh ejqe you ty 4aydeyo aas sayqeo u m q So2uejsIp Ou sJalauUleJed au zy 491deu sJo1sise1 uoneu IUl19 SAeu eur snqplalj eui jo spue u1oq ledl 42949 suoloauuoo x29u2 JalnoJ Dei SesolAep iesse eu J9ujo 499849 sleuluuel ul SJojinpuoo jo zuad j eu100 3293 Buipunoub yoay9 S n2 JO 9 qe2 42949 zy 481deu SJ0 sISaJ uorjeurulJ9 9 eu aul snqp1ay eui jo Spud YO ey Y99YD Burges 42949 219 eleJpneq ssaJ ppe Ae s suon eJnfijuoo 428423 SJ0 SIS2 1
25. ss on the bus and setting the same value to Max master parameter The device now understands being at the last address of the bus and passes the token to the first device Tel 358 0 201 2121 e Fax 358 0 201 212 205 Annex Protocol implementation conformance statement Honeywell 38 10 Annex Protocol implementation conform ance statement PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT NORMATIVE This annex is part of this Standard and is required for its use BACnet Protocol Implementation Conformance Statement Date November 7 2008 Vendor Name Honeywell Product Name Honeywell SmartDrive xxx xxx MAC ID Product Model Number Honeywell SmartDrive Applications Software Version xxx Firmware Revision 1 BACnet Protocol Revision 4 Product Description Honeywell SmartDrive HVAC BACnet Standardized Device Profile Annex L BACnet Application Specific Controller B ASC List all BACnet Interoperability Building Blocks Supported Annex K DS RP B DS RPM B DS WP B DS WPM B DM DDB B DM DOB B Segmentation Capability Segmented requests supportedWindow Size Segmented responses supportedWindow Size Standard Object Types Supported An object type is supported if it may be present in the device For each standard Object Type supported provide the following data 1 Whether objects of this type are dynamically creatable using the CreateObject service Honeywell 39 Annex Protocol implementa
26. than zero is selected the value is used as Device Object s Instance number The actual value is shown in the Monitor menu The de fault value for this parameter is generated from the Ethernet MAC address Last 2 octets will be used XX XX XX XX FF FF P5 7 3 1 5 COMMUNICATION TIME OUT BACnet board initiates a communication error if the board is a sole master in the network for a time defined with this parameter 0 means that no fault is generated Honeywell 21 Programming 5 3 2 BACnet MS TP monitoring values P5 7 3 2 1 FIELDBUS PROTOCOL STATUS Fieldbus Protocol Status tells the status of the protocol INITIALIZING Protocol is starting up STOPPED Protocol is timeouted or not used OPERATIONAL Protocol is running Major fault in protocol requires restarting rar If fault remains contact fieldbus vacon com Table 8 FB protocol statuses P5 7 3 2 2 COMMUNICATION STATUS The Communication status shows how many error and how many good messages the frequency converter has received The Communication status includes a common error counter that counts CRC and parity errors and a counter for good messages Only messages to the current slave in use are counted in the good messages not MS TP token packages Bad Frames Good messages Number of messages received Number of messages received 0 99 0 999 with errors without errors Table 9 P5 7 3 2 3 ACTUAL INSTANCE NUMBER Shows the act
27. tion conformance statement Whether objects of this type are dynamically deletable using the DeleteObject service List of the optional properties supported List of all properties that are writable where not otherwise required by this standard List of proprietary properties and for each its property identifier datatype and meaning oo P Go N List of any property range restrictions Data Link Layer Options MS TP master Clause 9 baud rate s 9600 19200 34800 76800 supports autobaud detec tion BACnet IP Annex J Device Address Binding Is static device binding supported This is currently necessary for two way communication with MS TP slaves and certain other devices O Yes No Networking Options Router Clause 6 List all routing configurations e g ARCNET Ethernet Ethernet MS TP etc L Annex H BACnet Tunneling Router over IP BACnet IP Broadcast Management Device BBMD Does the BBMD support registrations by Foreign Devices L Yes O No Character Sets Supported Indicating support for multiple character sets does not imply that they can all be supported si multaneously E ANSI X3 4 L IBM Microsoft DBCS L ISO 8859 1 L ISO 10646 UCS 2 L1 ISO 10646 UCS 4 LI JIS C 6226 If this product is a communication gateway describe the types of non BACnet equipment net works s that the gateway supports Find out more For more information on Honeywell s variable frequency drives and other Honeyw
28. ual instance number P5 7 3 2 4 FAULT CODE Shows BACnet MS TP fault codes Code Code name Description 0 None 1 Sole Master No other devices on the bus 2 Duplicate MAC ID Two devices have identical MAC ID No baudrate detected by Autobaud paga Tele Tauli ing P5 7 3 1 2 Autobauding Table 10 P5 7 3 2 5 CONTROL WORD Shows the Control Word received from the bus Programming Honeywell 22 P5 7 3 2 6 STATUS WORD Shows the current Status Word that is sent to the bus Honeywell 23 Programming 5 4 BACnet IP parameter descriptions 5 4 1 Ethernet common settings P5 8 1 1 IP ADDRESS MODE Selectable alternatives are DHCP Dynamic Host Configuration Protocol and Fixed DHCP protocol gives IP addresses to new devices connecting to local network This address is valid for a certain period of time A fixed IP address is specified manually and it does not change When the mode is changed from DHCP to Fixed the addresses will read IP 192 168 0 10 Subnet mask 0 0 0 0 Default gateway 0 0 0 0 P5 8 1 2 IP ADDRESS An IP address is a series of numbers like above specific to the device connected to the Inter net P5 8 1 3 SUBNET MASK The network mask marks all the bits of an IP address for the identification of the network and the subnetwork P5 8 1 4 DEFAULT GATEWAY Gateway address is the IP address of a network point that acts as an entrance to another net work P5 8 1 5 MAC ADDRESS The
29. wd Rev Direction of motor Fwd Rev C BV17 Reset Fault commend i reset Active 0 Reset C Fault from drive BV18 Stop By Coast Stop Drive by coast 0 1 C BV19 Stop By Ramp Stop Drive by ramp 0 1 C BV20 Quick Stop Quick Stop 0 1 C BV21 Zero Ramp Stop by zero ramp 0 1 C BV22 Hold Ramp Hold ramp 0 1 C BV23 BusCtrl Activate Bus control 0 1 C BV24 BusRef Activate Bus reference 0 1 C BV25 fb control word Bit 10 fb control word bit 10 0 1 C BV26 fb control word Bit 11 fb control word bit 11 0 1 C BV27 fb control word Bit 12 fb control word bit 12 0 1 C Communications Honeywell 28 BV28 fb control word Bit 13 fb control word bit 13 0 1 C BV29 fb control word Bit 14 fb control word bit 14 0 1 C BV30 fb control word Bit 15 fb control word bit 15 0 1 C Table 13 NOTE Present Value Access Types R Read only W Writeable C Commandable Commandable values support priority arrays amp relinquish defaults Honeywell 29 Communications 6 1 2 Analog Value Object Instance ID Object Name Description Units Present valne Access Type AVO Frequency Setpoint Frequency Setpoint Hz R AV1 Output Frequency Output Frequency Hz R AV2 Motor Speed Motor Speed rpm R AV3 Load power Motor Shaft Power R AV4 Kilowatt Hours total Ger EE kWh R AV5 Motor Current Motor Current A R AV6 DC link Voltage DC link Voltage V R AV7
30. y If the VFD is used as a part of a machine the machine manufacturer is respon sible for providing the machine with a supply disconnecting device EN 60204 1 Only spare parts delivered by Honeywell can be used At power up power brake or fault reset the motor will start immediately if the start signal is active unless the pulse control for Start Stop logic has been selected Futhermore the I O functionalities including start inputs may change if parame ters applications or software are changed Disconnect therefore the motor if an unexpected start can cause danger The motor starts automatically after automatic fault reset if the autoreset func tion is activated See the Application Manual for more detailed information Prior to measurements on the motor or the motor cable disconnect the motor cable from the VFD Do not touch the components on the circuit boards Static voltage discharge may damage the components Check that the EMC level of the VFD corresponds to the requirements of your supply network In a domestic environment this product may cause radio interference in which case supplementary mitigation measures may be required PERPRPPPPbPbPP5PPEP 1 3 Grounding and ground fault protection A CAUTION The Honeywell SmartDrive must always be grounded with a ground conductor to the ground terminal marked with d The earth leakage current of the drive exceeds 3 5mA AC According to EN6180
Download Pdf Manuals
Related Search
Related Contents
Weider WCCR4406 User's Manual FT - Cytrol Forte NOTICE IDRA 3000 SV versions ventouse Manuel d`installation et d`entretien Log Cradle - GHP Group Copyright © All rights reserved.
Failed to retrieve file