miniOMNIAlog User Manual EN_09_2014_NEXT_rev6

image

Contents

1. miniOMNIAlog OVERVIEW miniOMNIAlog is a 4 channel datalogger designed for low power consumption and easy installation it reads most analog current voltage NTC Wheathstone bridge vibrating wire and digital sensors Each channel is individually configured at factory Readings are accurate repeatable and stable in temperature VW sensors are read using an algorithm based on Fast Fourier Transform a parameter logged together with the reading shows the quality of the readings Readings are stored into the internal memory and can be downloaded using a USB pen drive or a laptop PC If the mini OMNIAlog is equipped with the GPRS module readings can be automatically transmitted to the user FTP folder or by email No software needs to be installed you simply connect the PC to the USB port and establish a dial up PPP connection Using an internet browser the user could configure the miniOMNIAlog and download data the miniOMNIAlog is fully configurable for each channel it is possible to set the acquisition time the conversion parameters and the alarm method SMS email digital output frequency increasing Itis possible to update the firmware web pages using the USB pen drive miniOMNIAlog does not support a Dial UP M2M remote communication NOTE Power supply type internal batteries or external power supply the measure type of each analog channel current voltage NTC Wheatstone bridge vibrating wire and the present of the
2. 28 10 2014 Page 42 of 80 industries i MET USB connection by USB Isolator Cable USB portin miniOMNIAlog is not isolated For the connection between PC and miniOMNIAlog SISGEO recommends the use of an isolated USB cable The USB isolator cable effects a potential decoupling of all USB connections It is the professional tool to avoid and fight ground loops and equalize currents It is also important to protect the system against overvoltage that could damage miniOMNIAlog or cause flood readings USB isolated cable is especially recommended when the PC and miniOMNIAlog are connected to the main electricity network If you are using this cable you need to consider that the maximum supplied current is 400mA compared to a USB port that provides 500mA maximal 400mA sourced from the 500mA primary input Therefore when miniOMNIAlog is powered using an isolated USB cable it should be noted that the USB port of the PC must be capable of delivering at least 500mA current the connected sensor must not draw more than 35mA If these two conditions are not respected you may experience some communication and power supply disconnections industries 2G GSM GPRS Modem SIM card If the miniOMNIAlog has an internal 2G GSM GPRS modem a SIM with for internet connection is needed The SIM selected must be enabled to internet traffic to send e mails and files on FTP Server for further details call your ISP Internet
3. Firmware Ver 7 It shows the firmware version USB 8 It enables the miniOMNIAlog to PC connection Connection Power Off it permit to power off miniOMNIAlog properly This chapter summarizes the general philosophy of display messages as follows each code is univocal so for example 1 always identifies the miniOMNIAlog STATE menu letter is used as a message of successful operation letter E followed by a number means an error in operations when sleep state is on the display is off to awake the system up you have to press a key To turn on the system you have to press the key a second time now miniOMNIAlog is totally on and displays the first entry of the main prae E menu EN Li m EN 1 i 4 I 1 1 industries State Menu 1 If you press Enter key in correspondence to the miniOMNIAlog state menu 1 entry the miniOMNIAlog will display the current state MiniOMNIAlog Display code Description state RUN r miniOMNIAlog in run CONFIG C miniOMNIAlog in configuration STOP 5 miniOMNIAlog in stop n RUN mode CONFIG mode STOP mode The user can read the miniOMNIAlog state when he enters the menu As the user enters the miniOMNIAlog state a 15 sec timeout begin
4. Iron disulfide Life 52 nominal voltage 1 5 V min 2 A continuous current discharge min 2 A pulse industries capability min 3 Ah capacity Rev 6 28 10 2014 Page 12 of 80 H MEXT industries Information about Internal Batteries Lithium iron disulfide LiFeS2 batteries have a much lower sensitivity to temperature compared to other chemical systems The recommended operating temperature range is 40 C to 60 C 40 F to 140 F As with all battery systems service life is reduced as the discharge temperature is lowered below room temperature Batteries generate power through chemical reactions and these typically run much more slowly at lower temperatures However even at 40 C LiFeS2 batteries perform well at the rating drain 200mA LiFeS2 batteries can deliver approximately full rated capacity at 40 C if they are discharged at 25mA Thus at these rates batteries give comparable performances over the entire 100 C operating range 25 mA 250 mA gt Rev 6 28 10 2014 Page 13 of 80 21 40 nnne 21 Page 14 of 80 Rev 6 28 10 2014 industries Internal Batteries substitution warning Insert batteries in the batteries holder making sure of the correspondence between the polarities of battery and those of batteries holder Batteries that are inserted incorrectly could cr
5. NOTE the 192 168 125 1 IP address cant be changed by the user e You will be requested the miniOMNIAlog log in and you can browse in its pages industries Every time that you need to reconnect a miniOMNIAlog or connect a new one you have to open miniOMNIAlog Connection Tool select the correct COM port and click on CONNECT industries Try to install wrong version miniOMNIAlog Connection Tool has two different version One for 32bit operative systems and one for 64bit operative systems miniOMNIAlog Connection Tool 64 bit on 32 bit operative system If you try to launch a 64 bit version tool on 32 bit operative system after the installation the following error message appears C Program FilesminiOMNIAlogConnect miniOMNIAlogConnect exe The version of this file is not compatible with the version of Windows you re running Check your computer s system information to see whether you need an x86 32 bit or x64 64 bit version of the program and then contact the software publisher To solve this problem you have to uninstall the tool Control Panel Programs and Features and re install the correct version of miniOMNIAlog Connection Tool miniOMNIAlog Connection Tool 32 bit on 64 bit operative system After the installation you try to launch a 32 bit version tool on 64 bit operative system no message appears and all seams works fine But when the miniOMNIAlog Connection tool try to create a new connection the follow
6. h industries OMNIA os User Manual from FW 0 12 22 industries Index PROVISIONS DISPOSAL IDENTIFICATION LABELS 5 miniOMNIAlog OVERVIEW miniOMNIAlog default setting 7 INSTALLATION PROCEDURE 8 GROUND SYSTEM HOW TO OPEN miniOMNIAlog CASE 9 miniOMNIAlog POWER SUPPLY 10 Information about Internal Batteries Internal Batteries Substitution Warnings DISPLAY AND KEYBOARD FUNCTIONALITY 14 State menu 1 Battery menu 2 Firmware update menu 3 Set USB flash driver for miniOMNIAlog firmware update 19 Data copy menu 4 Export file Measure and Measure log format 22 Start menu 5 Stop menu 6 Firmware version menu 7 USB connection menu 8 11 13 16 17 18 21 23 23 23 24 Power off menu 9 Test signal modem menu A HOW CONNECT miniOMNIAlog TO PC 26 miniOMNIAlog LOCAL CONNECTION 27 miniOMNIAlog Connection Tool 28 PC miniOMNIAlog connection Try to install wrong version HOW TO DISCONNECT PC FROM miniOMNIAlog 37 Unplug USB without any disconnection procedure USB CONNECTION BY USB ISOLATOR CABLE 38 2G GSM GPRS MODEM SIM card Caution to be taken with 2G GSM GPRS modem APN configuration WEB PAGES FUNCTIONALITY 42 Type of users Web interface language setup WIRING SCHEMES Local analog sensor Digitalized sensor Wiring RELAY OUTPUT VOLT FREE CLOSURE 51 ANOMALIES and ALARM WARNINGS 51 25 25 32 36 37
7. reg annem 7 4 6 29 10 2014 75 80 industries Hardware configuration After the software configuration of miniOMNIAlog channels it is necessary to change also the hardware configuration according to the measure type of each channels To change the hardware configuration follows these steps Disconnect the power supply from the miniOMNIAlog According to the Measure Type and Power Supply configurated by web pages for each Channel insert the jumper on the electronic board Channel jumpers following the schemes below 23 44 LT gt n f NL 0 4 Channels jumpers Channels Terminal Board CH1 CH2 CH3 CH4 industries VOLTAGE 24Vdc 12Vdc 5Vdc External 4 20mA CURRENT LOOP 2 WIRES 24Vdc 12Vdc External JL D X 9u I Lu lt co QD C Lu lt Q C Lu c Q Lu industries 4 20mA TRANSMITTER 3 4 WIRES 24Vdc 12Vdc External I OLU t c Q C Lu t cO Q CO Lu RATIOMETRIC 6 WIRES only 5Vdc lt 2 C Lu industries THERMISTOR NTC lt c 2 C Lu VIBRATING WIRE lt c 2 C Lu industries VIBRATING WIRE THERMISTOR I t QD C uu Example If you have configured the channel CH1 as Voltage instrument with 12V Power Supply you should insert jumper at position B1 and D1 If you have confi
8. 39 39 40 41 43 43 44 44 45 46 ts gt lt MAINTENANCE 53 TROUBLESHOOTING F A Q ASSISTANCE APPENDIX A HOW TO CHANGE THE HARDWARE AND SOFTWARE CHANNELS CONFIGURATION 62 Firmware configuration 63 One input measure type Two input measure type HARDWARE CONFIGURATION 67 54 59 60 61 64 65 industries Provisions Install OMNIAlog in order to avoid the direct sun radiation The product should not be installed in small places and or without ventilation with high humidity levels or in the presence of flammable or explosive liquids Do not open the box with bad weather conditions rain snow etc or if you want to avoid the entry of humid alr miniOMNIAlog was programmed to work at temperatures between 30 C and 60 C batteries from 20 C to 60 and to be conserved at temperatures between 40 C e 85 C batteries from 0 C to 40 C Too extreme temperatures can temporarily shorten batteries lifetime or cause the temporary malfunctioning of miniOMNIAlog After tightening the cable glands consider to seal accurately the instrumental cables with silicone or expanded lather to guarantee the correct degree of protection of the box Electrical connections must be done by qualified technician respecting the current regulations Before doing works verify that all connections also the ones free from potential are voltage free Maintenance works have to be d
9. Drivers VCP htm You have to do this operation only one time for each PC utilized with miniOMNIAlog After that every time a new miniOMNIAlog is connected to these PCs it will be automatically recognized because the driver is already installed on your PC SISGEO suggests to check periodically the new releases of driver at the previous link industries miniOMNIAlog Connection Tool The tool for the creation of the dial up remote connection is in folder miniOMNIAlog Connection Tool that you could find in the USB flash drive supplied together with the datalogger You could download it also in SISGEO website in the page of the product This tool allows to create the dial up remote connection and to add the virtual modem 56000bps automatically The tool is necessary only the first time you connect miniOMNIAlog to the PC or every time a new miniOMNIAlog is connected to the PC System minimum requirements The tool is compatible with the following Microsoft operating systems Windows 7 32bit and 64bit Windows 8 32bit and 64bit No particular hardware resources are required Instead it is necessary to have administrative rights in order to execute the software Installation To install the tool do as follows 1 Enter in folder miniOMNIAlog Connect Tool Two folders are displayed 1 b gt miniOMNIAlog Connect Tool gt Favorites Desktop Downloads d Recent places 22 Dropbox 32 bit Version 64 b
10. Service Provider Watch the following images to insert the SIM correctly NOTE remove the power supply before proceeding Insert the SIM card in the SIM slot NOTE pay attention to insert the SIM Card in the right side Lock the SIM slot NOTE the antenna connector is very delicate pay attention to not damage its cable CAUTION TO BE TAKEN WITH 2G GSM GPRS MODEM In case miniOMNIAlog sends measures or alarms by e mail or on FTP server the user has to take into account that the USB serial of communication is shared with the 2G GSM GPRS modem serial of communication For this reason if the user launches miniOMNIAlog from webpages the PC automatically disconnects If the user connects later miniOMNIAlog is automatically put in STOP mode Therefore it will be possible to surf the pages Furthermore it is impossible to visualize the measures in automatic update in page VISUALIZATION MEASURES NOTE SISGEO suggests during installation to not enable e mail or data transmission on FTP server both measures and alarms Once the user has verified the accuracy of readings it is possible to enable e mail or data transmission on FTP server industries APN configuration On the miniOMNIAlog web server you can find a page where you have to edit an APN command This command is necessary to configure the 2G GSM GPRS modem with the correct parameters according to the selected SIM these parameters depend on y
11. and Dataloggers Select miniOMNIAlog datalogger from the list Inthe right higher part select Download Firmware the download of the zip file will start the download ends you will have on the PC a file called FW x yy zz where x is the major release yy is the web pages version and 77 is the firmware version It is necessary to extract the zip file content in the main directory of an USB flash drive SISGEO supplies with miniOMNIAlog a 4GB pen drive already FAT32 formatted and suitable for miniOMNIAlog reading the USB pen drive can include other files In case of problems during the firmware download from SISGEO website or temporary unavailability It is possible to request the new firmware version contacting SISGEO assistance at assistance 2sisgeo com Notes and remarks 1 The USB flash drive used for the firmware update must be FAT32 formatted Otherwise the pen drive will not be read from miniOMNIAlog and it will be impossible to update the firmware 2 Itis necessary to copy the whole content of the ZIP file WEB folders FW and Restore directly in the main directory of the USB pen drive do not use sub folders NOTE SISGEO suggests to use a USB flash drive only for this purpose in order to avoid any unexpected data loss C FIRMWARE UPDATE According to the value modified in the firmware version x yy zz it is necessary to proceed in different ways You have two dif
12. any bugs or to implement any improvements and to exploit miniOMNIAlog possibilities NOTE the code structure x yy zz of the firmware version is modified according to the improvement corrections importance carried out between two versions When the value x is modified it means that the improvement modification is of high importance because it changes data structure In this case you need to proceed as explained in chapter Update with database structure modification CHECK NEW FIRMWARE AVAILABILITY To check for any firmware update you have two possibilities Automatic check only with miniOMNIAlog connected to internet COMING SOON Manual check on SISGEO website www sisgeo com Automatic check happens only when miniOMNIAlog is connected to internet through internal 2G GSM GPRS modem miniOMNIAlog is programmed to check every 7 days for any new firmware version When a new version is found the status icon will become red The user through miniOMNIAlog web pages will be informed that on SISGEO website a new version is available This new version must be downloaded to proceed with the update New firmware available icon E No new firmware available icon Itis possible to check anytime for new firmware on SISGEO website NEW FIRMWARE DOWNLOAD For both possibilities the download must be performed manually on a PC connected to internet Connect to SISGEO website and in the page PRODUCTS choose Readout Units
13. to understand the eventual logs 2 verify the instrument with a portable datalogger 3 verify the connection of instruments on miniOMNIAlog inputs 4 change the parameters Excitation time accepted values from 5 to 100 and Delay Time accepted values from 20 to 100 focusing on this last one 5 try to contract the parameters Start Frequency and End Frequency according to the value read with the portable datalogger 6 consultthe reference manual of the instrument One or more analog instruments are not read Follow these steps testing after each 7 verify the events log and refer to the manual miniOMNIAlog amp OMNIAlog Codes Alarms Events to understand the eventual logs 8 verify the instrument with a portable datalogger 9 verify the connection of instruments on miniOMNIAlog inputs 10 verify that the configured parameters are coherent and correct according to the type of connected instrument power supply warm up time etc 11 consult the reference manual of the instrument F A Q Frequently asked questions It is possible to find all F A Q on SISGEO website at the following link http www sisgeo com faq readout units and dataloggers i 1 industries ASSISTANCE After sales assistance for calibrations maintenance and repairs is performed by Next Industries Service Department The authorization of shipment shall be activated by RMA Return Manufacturer Authorization Send back the instrume
14. E mail info dsisgeo com http www sisgeo com HOW TO CHANGE THE HARDWARE and SOFTWARE CHANNELS CONFIGURATION SISGEO is not responsible for any malfunctioning or damages following the change of the hardware firmware configuration described in this document To change the firmware you must access miniOMNIAlog through the configurator user Sisgeo this user has more privileges than user Admin and therefore you must be really careful to avoid problems The hardware e firmware changes must be coherent i e if the channel CH1 hardware is configured with vibrating wire measure also the software configuration must be coherent 1 2 4 The following are possible configurations Measure Type Power Supply Available Current loop 2 wires 24V 12V external Transmitter 3 4 wires 24V 12V external Voltage 4 wires 24V 12V 5V external Wheatstone bridge 6 wires 2 channels used ef industries Firmware configuration In order to configure local analog channels it s necessary to connect the miniOMNIAlog to a pc see the miniOMNIAlog Quick Start Manual Once established the connection on your internet browser insert the IP address of the miniOMNIAlog 192 168 125 1 as default and login as Sisgeo user with the credentials reported below USR Sisgeo PSW In the main menu click on Channels Configuration Locals in this page it is possible to set local an
15. GPRS module are configured at factory The user is not authorized to modify these settings industries miniOMNIAlog default setting miniOMNIAlog utilizes the following IP address for USB connection with the PC IP Address 192 168 125 1 NOTE this IP address cannot be changed by the user because it is configured at factory This IP could be utilized only to use the web server on USB communication After the connection miniOMNIAlog asks for the access credentials NOTES miniOMNIAlog is compatible with the main internet browsers FireFox IE9 Safari Chrome SISGEO recommends the use of FireFox to manage miniOMNIAlog First page upload can take some time Following there are the default credentials User Admin User User User Admin User User Psw Admin Deus User industries INSTALLATION PROCEDURE You can use the four holes 6mm to fix the miniOMNIAlog according to your application Screws and anchor plugs suggested 5mm are not supplied 127 Rev 6 28 10 2014 Page 9 of 80 industries GROUND SYSTEM The protections integrated in the miniOMNIAlog system work correctly only if connected to the ground Use an appropriate green yellow conductor to connect the plug to the ground as shown below The ground system must be designed manufactured and certified according to the rules and laws in force HOW to OPEN miniOMNIAlog Case To open the miniOMNIAlog case use a little screwdriver
16. ON To create and establish the first connection between PC and miniOMNIAlog do as follows e Connect miniOMNIAlog to the PC using the supplied USB cable e Wait for the end of the installation of the USB drivers NOTE if the installation doesn t start automatically it is possible to trace the drivers on the USB flash drive supplied with miniOMNIAlog It is also possible to download it from SISGEO website and do a manual installation e Start the tool miniOMNIAlog Connect NOTE the tool has to be started with function Run as administrator right button of the mouse on tool icon otherwise the configuration doesn t end well This procedure is necessary also if you are the administrator of the PC Open Open file location Troubleshoot compatibility Pin to Start T Zip aif Edit with Notepad Unpin from Taskbar Send to Cut Copy Create shortcut Delete Rename Properties e Ifyou As administrator the following error will appear Please run this app as administrator Refer to manual for details Rev 6 28 10 2014 Page 36 of 80 industries So the tool opens Select the COM port assigned to miniOMNIAlog during the installation of the USB driver NOTE to know which COM port has been assigned to miniOMNIAlog look to the COM ports list in Control Panel Device Manager maintaining the PC connected to miniOMNIAlog e miniOMNIAlog Connection Tool 64bit v1 5 Con
17. ST industries 4 20mA Current Loop 2 wires 4 20 mA Current Loop 2 wires SINGLE External Power Supply LOOP ONLY for EXT POWER SUPPLY e Do not connect with ext power supply PWR GNDPWR 4 20mA Transmitter 3 4 wires Rev 6 28 10 2014 CH 1 4 Page 52 of 80 MEST industries CH 1 4 4 20 mA Transmitter 3 4 wires SINGLE External Power Supply GND Signal 3 Dono connect with 3 wires ONLY for EXT POWER SUPPLY e Do not connect with ext power supply a SISGEO PWR e Onlyfor 3 wiresinstrument Q GNDPWR Thermistor NTC CH 1 4 Thermistor 2 wires 30000 25 SISGEO Vibrating Wire Page 53 of 80 Rev 6 28 10 2014 industries VibratingWire 2 wires CH 1 4 Vibrating Wire with Thermistor Vibrating Wire with Thermistor 4 wires CH 1 4 THERMISTOR 30000 25 Rev 6 28 10 2014 Page 54 of 80 industries Ratiometric 6 wire Ratiometric 6 wire External Power Supply Vdc 2 d Signal 3 ONLY for EXT POWER SUPPLY PWR e Do not connect with ext power supply GND PWR siscEo NOTE for this measure type two channels Ch1 Ch2 Ch2 Ch3 or Ch3 Ch4 are necessary to read the instrument Potentiometer Potentiometer 3wires SINGLE External Powe
18. alog channels on miniOMNIAlog Click on the Enable field in order to activate the channel Click on the Edit button in order to configure the channel Menu Local Channels Enabling Status cows fo loca sed to a 3919 ils vag Configuration Channels Configuration Enable Edit Acquisition Identification Description Measure Wiring scheme 2 v venie DEFAULT Voltage Wirrg scheme Virtual Osta Monitor 4 Edit 2 DEFAULI AN Z Ihermistor NTC Wirimg scheme Advanced 7 Edit 3 DEFAULT AN 3 Ratiometric 6 wires Wiring scheme Edit 4 DEFAULT AN 3 Ratiometric wires scheme Sew cancel industries One input measure type Select 1 by the Input Nr drop down menu Menu Local Channel Configuration Status This page allows to configure a local analog channel with 1 or 2 inputs and their acquisition frequency Configuration Channels Configuration O Digitals Description Parameter O Virtuals Channel 1 InputNr gt Advanced Acquisition Default X Multiplexer Disabled ME Selecting the measure type by the Measure Type drop down menu F Battery 100 27 11 13 Sisgeo miniOMNIAlog Alarm FW 0 06 13 M 1010 Menu Input Configuration Status poge allows to configure OMN Mbog local onatog inputs Configuration Chann
19. aragraph provides FTP server sending data troubleshooting tips The e mail transmission involves different devices In this document we try to determine which device could cause the problem and then we try to solve it The System is composed as follows 1 miniOMNIAlog 2 Internet Service Provider ISP allows the communication between miniOMNIAlog and FTP server 3 server FTP physical space in which it is possible to memorize files NOTA the FTP server could be completely transferred to societies that offer an hosting FTP service It could also be internal In this secondo case you have to ask for information to your IT manager First of all insure with your IPS that 1 The SIM card is enabled to the internet traffic through APN 2 The data transmission on FTP server is allowed on the used APN Insure with your system administrator or with the society that supplies the hosting FTP service that 1 there are no momentary breakdowns on FTP server 2 the username and password of FTP account are valid and accepted 3 thatthe FTP account and the same FTP server that the user wants to use are active These points do not depend on SISGEO SISGEO cannot solve these problems If you don t have problem with the ISP and the FTP server you could proceed looking for causes on miniOMNIAlog If miniOMNIAlog doesn t send any data on FTP server also if configured Follow these steps testing after each 1 verify the events log and r
20. as to be disposed of in accordance with the European directive 2002 96 CE Recycable materials contained in the device will be recuperated to avoid the environmental degradation For further information adress to the local disposal authorithy to device seller miniOMNIAlog contains electronic components and batteries that have to be disposed of separately from domestic waste When this product reach its useful life it is necessary to bring it to a gathering place for the recycling of electronical components An uncorrected disposal on the part of the user could be subject to penalties IDENTIFICATION LABELS Every miniOMNIAlog datalogger from now on indicated simply as miniOMNIAlog or datalogger has two type of identification labels The first label placed on the upper side of miniOMNIAlog shows the registration Serial Number of the product p 7T 20130599 It is important to communicate these data in case of request of information or accessories concerning the product The second label placed on the back side of miniOMNIAlog shows information about the electrical equipment of the product Respect the requirements written on the label The lack of respect for these requirements could damage the product or put in danger the operator Electric rating 12W from internal NR AA 1 5V batteries 12Vz 127W from dedicated AC DC power source IP grade 67 A 0470 industries
21. back to main menu and will start the timeout display it can be set up from the web At timeout display expiration the display will turn off While the menu shows the copy state error code or OK Select key causes the display back to main menu and timeout reset display While the menu shows the copy result Enter key causes the timeout reset from 15 sec industries Rev 6 28 10 2014 Page 24 of 80 industries Export File Measure and Measure Log Format With miniOMNIAlog you can download data measures events log alarms logs using USB flash drive aPC through web interface aFTP or e mail A USB flash Drive After the copy using a USB flash drive a folder with the following format will be automatically created lt miniOMNIAlogname gt Log Within the folder there will be the following four csv files ALog_dd_mm_yy csv in this file there are all the alarms detected from the miniOMNIAlog dd mm yy csv in this file the events recorded from the miniOMNIAlog are saved MLog dd mm yy csv in this file the measures in log format are saved There are also other information such as any alarm for the sensors the measurements unit the vibrating wire measurements parameters etc MLog dd mm yy Column csv in this file the measures ordered in columns are saved This kind of display is suited for data management with spreadsheet In the file name d
22. d is the day mm is the month and yy is the year B PC When you download data directly from the miniOMNIAlog web pages there is a specific field for each data file you can choose the destination folder on your PC and the file name if your Internet browser is well configured C FTP or e mail If you set the miniOMNIAlog to transmit the csv reading file only the one ordered in columns by e mail or by FTP the name ofthe file is the following mLog dd mm yy hh mm csv In the file name hh is the hour mm is the minute industries Start Menu 5 If you press Enter key in correspondence to the menu entry Start miniOMNIAlog 5 the miniOMNIAlog will start acquisitions Letter is displayed if the miniOMNIAlog is successfully started if an error has occurred the system will go to error state and an error code will be shown After starting result is shown a 15 sec timeout is started After that the miniOMNIAlog will come back to main menu and will start the timeout display At timeout display expiration the display will turn off While the menu shows the start state error code or OK Select key causes the display returning back to main menu and timeout reset display Stop Menu 6 If you press Enter key in correspondence to the menu entry Stop miniOMNIAlog 6 the miniOMNIAlog will stop acquisitions Number 8 followed by letter A are displayed if the operation is successful if an error has occurred the system will g
23. dings changes in real time i 1 industries Type of user Users type in miniOMNIAlog system are Admin this user CANNOT change analog channels it can change for example acquisition frequency or change the polynomial This user cannot change settings which depend on hardware system User this user can only view and download data Web interface language setup To modify the web interface language connect miniOMNIAlog and access to web interface with the user Admin or User that needs to change the language Then Select from left menu Advanced and in the submenus User Management the page it will be displayed select Language Insert the password in the field Old password Press Save changes Now the web interface will be converted in the selected language To convert also the left menu it is necessary to refresh the web page pressing F5 or the specific symbol on the internet browser address bar NOTE To avoid the conservation of the old language it is necessary to completely delete the internet browser cache industries WIRING SCHEMES Local analog sensor The Instruments measure type that can be read with miniOMNIAlog are Voltage 4 20mA Current Loop 2 wires 4 20mA Transmitter 3 4 wires Thermistor NTC Vibrating Wire Vibrating Wire with Thermistor Ratiometric 2 channels needed On the miniOMNIAlog electronic board there are four analog channels Each channel has four clamps for the
24. doesn t coincide with the ESP Gmail AOL etc Resolution First of all insure with your IPS that 1 The SIM card is enabled to the internet 2 The e mail transmission is allowed on the used APN Secondly insure with your ESP that 3 there are no momentary breakdowns on ESP server 4 theusername and password of your e mail account are valid and accepted 5 the e mail account you want to use is active These points do not depend on SISGEO SISGEO cannot solve these problems If you don t have any problem with the ISP and the ESP you could proceed looking for causes on miniOMNIAlog If miniOMNIAlog doesn t send any e mail although it is configured Follow these steps testing after each 6 verify the events log and refer to manual miniOMNIAlog amp OMNIAlog Codes Alarms Events to understand the eventual logs 7 verify that the SIM card is properly inserted in its slot eo verify you inserted your SMTP server account correctly SMTP Server Configuration page 9 verify that SMTP account is a simple authentication miniOMNIAlog doesn t support SSL 10 verify that there is a 2G GSM GPRS coverage on the site were miniOMNIAlog is installed In some place there is only a 3G and 4G coverage miniOMNIAlog is not compatible with 3G 4G and CDMA networks 11 verify that there is a good 2G GSM GPRS signal on the site were miniOMNIAlog is installed industries miniOMNIAlog FTP server Sending data Troubleshooting This p
25. eate a short circuit Do not recharge non rechargeable batteries Do not mix used batteries with the new ones or with batteries of different brand model Expired batteries have to be removed immediately from the batteries holder and correctly disposed of according to what was established by local rules if batteries are left in the batteries holder some losses could happen and these could damage the miniOMNIAlog I industries DISPLAY AND KEYBOARD FUNCTIONALITY miniOMNIAlog is provided with a 7 segment display and 2 input keys Select Enter The display is started by pressing down one of the 2 keys You can scroll the menu using Select key If the user doesn t send any input in a time equal to Timeout Display configured in Energy Management web page the display will turn off and the miniOMNIAlog will return in Sleep state 7 SEGMENT DISPLAY KEYBOARD SELECT KEY ENTER KEY a p P ao ry o Lu wai Ja A4 1 P 1 4 141 industries This is the chart of states on display Item Menu Display Code Description Test signal A Tests and shows the 2G GSM GPRS modem signal from modem 0 to 3 State 1 It shows miniOMNIAlog state Battery 2 It shows battery state Firmware 3 It allows miniOMNIAlog firmware updating update Copy Data 4 It copies logs on USB drive Start 5 It starts the miniOMNIAlog Stop 6 It stops the miniOMNIAlog
26. eate the program s shortcuts in the following Start Menu folder To continue click Next If you would like to select a different folder click Browse Browse _ Bak next gt 7 In summary page click on INSTALL i Setup miniOMNIAlogConnect Ready to Install Setup is now ready to begin installing miniOMNIAlogConnect on your computer Click Install to continue with the installation or click Back if you want to review or change any settings Destination location C Program Files x86 miniOMNIAlogConnect Start Menu folder iniOMNIAloaC 8 Therefore the installation starts This lasts only few seconds Rev 6 28 10 2014 Page 34 of 80 SE gt lt industries j9 Setup miniOMNIAlogConnect Installing Please wait while Setup installs miniOMNIAlogConnect on your computer Creating shortcuts C V Windows Start yminiOMNIAlogConnectlminiOMNIAlogConnect Ink 9 Atthe end of the installation the following confirmation message appears 15 Setup miniOMNIAlogConnect Completing the miniOMNIAlogConnect Setup Wizard Setup has finished installing miniOMNIAlogConnect on your computer The application may be launched by selecting the installed icons Click Finish to exit Setup 10 Click on FINISH Rev 6 28 10 2014 Page 35 of 80 i MEXT industries i Fog i PC miniOMNIAlog CONNECTI
27. efer to manual miniOMNIAlog amp OMNIAlog Codes Alarms Events to understand the eventual logs 2 verify that the SIM card is property insert in its slot 3 verify that you have inserted your FTP server account correctly Measure log data transfert page 4 verify that the FTP server address is inserted in numeric format exemple 62 100 100 1 5 verify that the FTP server is a basic authentication FTP for example not MD5 KERBEROS etc and that doesn t utilize any secure layer for example SSH SSL FTPS SFTP etc miniOMNIAlog does not support secure layer and encrypted authentication encrypted username and password EU NEXT 6 verify that there is a 2G GSM GPRS coverage on the site were miniOMNIAlog is installed In some place there is only a 3G or 4G coverage miniOMNIAlog is not compatible with 3G 4G and CDMA networks 7 verify that there is a good 2G GSM GPRS signal on the site were miniOMNIAlog is installed E MEXT miniOMNIAlog Measure Troubleshooting Are you up to date 1 Verify that you installed the last version of firmware 2 Verify that you have the correct power supply from battery pack or external power supply on the V IN clamp of miniOMNIAlog This paragraph provides measure data troubleshooting tips One or more vibrating wire instruments are not read Follow these steps testing after each 1 verify the events log and refer to the manual miniOMNIAlog amp OMNIAlog Codes Alarms Events
28. els Configuration TEE Data Monito Advanced aput _ Identification AN A Description Voltage Jal 4 20 mA Current Loop 2 wires Power Supply 4 20enA Transmitter Measure Unit a Ratiometnc 6 wires Warm Up sec Thermistor NTC Conversion L A Zero Reading Sensibility Poly Coeff Rev 6 28 10 2014 Page 73 of 80 industries Two inputs measure type Select Z by the Input Nr drop down menu Menu Local Channel Configuration Status Configuration Channels Configuration o m Digitals Description Parameter This page allows to configure a local analog channel with 1 or 2 inputs and their acquisition frequency Virtuals Data Monitor Input Nr ACO Multiplexer Disabled Selecting the measure type by the Measure Type drop down menu only Vibrating wire Thermistor is available Input Configuration ya sieas tela Alarms Cootiguration Rev 6 28 10 2014 Page 74 of 80 Ss MEXT industries Configure if necessary the second input NTC also Input Configuration The aurei ocn punt DAI Vah tent md nre vc uw LE x n 00004 e LE Range fa done Pv fof s A entr ed hmmm moms 4 p Maniis ds beaten
29. esn t appear under Windows Device Manager as virtual COM port paragraph restart your computer remove and reinstall the USB driver and restart your computer remove the power supply on V IN clamp for 10 seconds and try to reconnect Make sure that the username and password for remote connection are correct using Hyper Terminal check if the baud rate of serial communication is setting to 115200bps After having established the connection with Hyper Terminal if you press ENTER the miniOMNIAlog must answer The connection through miniOMNIAlog and computer falls down Follow these steps testing after each 1 2 be sure that your PC is not set on Energy Saving mode if you are using an isolated USB cable keep in mind that these cables usually can provide a limited current Try to change the USB cable Try with another USB port of your PC EU MEXT miniOMNIAlog e mail Sending Troubleshooting This paragraph provides miniOMNIAlog e mail sending troubleshooting tips The e mail transmission involves different devices In this document we try to determine which device could cause the problem and then we try to solve it The system is composed as follows 1 miniOMNIAlog 2 Internet Service Provider ISP allows the communication between miniOMNIAlog and the e mail server 3 E mail Server ESP allows to send and to receive e mails NOTE it may be that the ISP Telecom Vodafone AT amp T Varizon etc
30. ferent options U Update without database structure modification x value doesn t change while values and or zz change U Update with database structure modification Value x changes In case of Update with database structure modification the old configuration is not compatible with the new version of firmware Also the log files Measures Events and Alarms must be deleted after firmware update If these logs are not deleted there is the possibility to obtain wrong CSV files after the first download industries Data Copy Menu 4 NOTE miniOMNIAlog should be in Stop or Config state before using this function If you press Enter key in correspondence to the menu entry Data Copy 4 the miniOMNIAlog copies all logs on USB Drive Flashing letter d is displayed during files copy At the end of the copy flashing number dot will be shown to indicate to the user to remove USB flash drive and after that letter if copy was successful If an error occurred the system will go to error state and an error code will be shown WARNING it is not possible to connect USB hard drives to this port because these devices need too much current to work correctly In addition it is not possible to connect to this port any device different from flash drive 1 Bluetooth key internet key ect At copy process completed a 15 sec timeout starts After that the miniOMNIAlog will come
31. g Enter key in Power off 9 menu the miniOMNIAlog shows the character Now it is possible to remove the power supply internal batteries or external power supply NOTE the miniOMNIAlog could be powered off only if it is in STOP mode see Stop Menu 6 section in this manual Test signal modem Menu Pressing Enter key in Test signal modem menu entry A the miniOMNIAlog shows a blinking A and after it displays a number from 0 to 3 This value indicates the quality of signal 0 No signal Bad 1 Low signal 2 Good signal 3 Excellent If you select this function without the presence of the internal modem an error E7 appears on the display EM L _ 7 i industries E7 NOTE miniOMNIAlog has to be in STOP or CONFIG mode before using this function Otherwise miniOMNIAlog shows error E3 industries How connect miniOMNIAlog to PC The miniOMNIAlog can be found in RUN mode stand by miniOMNIAlog timed waiting for an acquisition CONFIG mode STOP mode ERROR state Connect the PC trough the USB cable to the miniUSB port of miniOMNIAlog From this moment and as long as the USB cable is disconnected the power supply will be taken from the PC ue 13b od D USB device Select item 8 from display menu and click enter Letter will appear on display meaning that the miniOMNIA
32. gured the channel CH2 as 4 20mA Current Loop 2 wires with 24V Power Supply you should insert jumper at position B2 EZ and H2 If you have configured the channel CH3 as Ratiometric 6 wires with 5V Power Supply you should insert jumper at position C3 D3 For this measure type two channels CH1 CH2 CH2 Ch3 or 4 are necessary If you have configured the channel CH4 as Vibrating Wire Thermistor NTC you should insert jumper at position A4 D4 F4 and G4 ATTENTION For sensors wiring it is necessary to refer to the Wiring scheme on miniOMNIAlog web pages
33. ing massage appears e miniOMNIAlog Connection Tool 32bit v1 5 E Refresh ports list Problem during modem installation Connect Modem not installed The 32 bit tool is able to works under 64 bit operative system but is not able to create the connection because the driver of dial up connection is different Also in this case to solve this problem you have to uninstall the tool Control Panel Programs and Features and re install the correct version of miniOMNIAlog Connection Tool industries Bg HOW to disconnect PC from miniOMNIAlog To disconnect the PC from miniOMNIAlog follows this steps onminiOMNIAlog web page press Logout button on Microsoft Windows select the Network icon on the application bar 14 10 25 10 2013 Networks menu will open Networks Airplane mode Off B Connections Dial up Connection miniOMNIAlog Dial Up Connect Disconnect Press on Disconnect button to close the Dial Up connection between PC and miniOMNIAlog NOTE when the USB cable is unplugged the miniOMNIAlog is rebooted This is necessary to switch from the USB power supply to the miniOMNIAlog power supply internal batteries or external power supply Unplug USB cable without any disconnection procedure If you unplug the USB cable without following the correct disconnection procedure the miniOMNIAlog is rebooted Under Data Monitor Events a Power Fail log appears Rev 6
34. insert the screwdriver into the hole in the yellow plastic and press down to unlock the case dA industries miniOMNIAlog POWER SUPPLY miniOMNIAlog is powered by e 6AAnon rechargeable batteries or anexternal power supply i e solar panel Here below are shown the clamps where the power supply is connected Respect the polarity To preserve batteries life during PC connection the power supply is automatically taken from the PC through USB cable connection In any case it is necessary to connect to a power supply NOTE the maximum current permitted on the mini USB connector is 500mA This current limitation must be taken into account when you are powering this device for example it is not possible to turn on the 2G GSM GPRS modem when the USB cable is connected to the PC SYSTEM POWER REQUIREMENTS Voltage 9 to 14 V DC reverse polarity protected max 12W External rechargeable battery i e from a little solar panel system 12V DC nominal In case of external power supply the external power source must be separated from the parts in dangerous voltage with a double insulation and must guarantee an insulation of at least 3000Vrms An external switch appropriately labeled has to be integrated into the plant for power disconnection The power cable used must have a section of at least 0 5mmq and a rating of 70 C Internal non rechargeable batteries no external power supply 6 batteries size AA chemistry Lithium
35. instrument signals A B C D and one channel for the instruments shield Channels Terminal Board CH 1 CH 2 CH 3 CHA industries Digitalized sensor miniOMNIAlog can read also the SISGEO digitalized RS 485 MODBUS instruments like In Place Inclinometers and Tiltmeters On the miniOMNIAlog board there is one clamp for the digitalized instruments connection Every clamp has 5 terminals for communication RS 485 D D and GND 2 for the instruments power supply V OUT V and GND ATTENTION The voltage V OUT V and GND is switched on and off from the software V OUT is the unregulated power supply input V IN V and V It is not possible to power the digitalized instruments when the USB connection is on RS 485 clamp has a resistance of 1200 the same resistance should be exposed at the end of 485 bus industries E MEXT Wiring Refer to the following image for the correct wiring of instruments analog and digitalized to the clamp You have to push the little button over the clamp insert the wire and release the button Following this scheme for each instruments measure type Voltage Voltage 4 wires SINGLE External Power Supply CH 1 4 Vdc qd GND PWR Sensor 9 ONLY for EXT POWER SUPPLY PWR Do not connect with ext power supply CN GND PWR siscEO Rev 6 28 10 2014 Page 51 of 80 ME
36. is in configuration mode No acquisition is in progress In this mode it is possible to modify configuration parameters channel configurations acquisition time etc delete and download logs Only Admin user can modify the Config mode Stop miniOMNIAlog is stopped No acquisition is in progress In this mode it is possible to download logs but it is not possible to change the configuration NOTE the humidity value shows N C because miniOMNIAlog hasn t a humidity sensor on board CONFIGURATION ACQUISITIONS in this page itis possible to set acquisitions frequency CHANNELS CONFIGURATION LOCALS in this page it is possible to set local analog channels on miniOMNIAlog ATTENTION For sensors wiring it is necessary to refer to the schemes on miniOMNIAlog web pages or to the par Connection Schematics at the end of this manual CHANNELS CONFIGURATION DIGITALS In this page it is possible to set digital channels to allow miniOMNIAlog to read digital instruments Until now SISGEO digitalized inclinometers and Tiltmeter RS 485 communication interface and MODBUS RTU communication protocol have been implemented For further information refer to the digitized sensors manual DATA MONITOR MEASURE In this page it is possible to display last miniOMNIAlog acquisition cycle It is also possible to download miniOMNIAlog executed and saved acquisitions NOTE the speed of refresh of the web page may not be sufficient to see the rea
37. it Version amp Foto iCloud 2 According to the version of your Operative System 32 bit 64bit enter in the respective folder 3 Inside the folder do a double click on the executable file miniOMNIAlogConnectSetup exe NOTE it is necessary to be administrator to start the installation 4 Thetool installation starts In the following display click on Next industries iS Setup miniOMNIAlogConnect Welcome to the miniOMNIAlogConnect Setup Wizard This will install miniOMNIAlogConnect version 1 5 on your computer It is recommended that you close all other applications before continuing Click Next to continue or Cancel to exit Setup 5 Indicate the path in which extract the files You could use the one of default Once you selected the path click on Next 5 Setup miniOMNIAlogConnect Select Destination Location Where should miniOMNIAlogConnect be installed d Setup will install miniOMNIAlogConnect into the following folder To continue dick Next If you would like to select a different folder dick Browse Browse At least 1 0 MB of free disk space is required lt Back Next gt Cancel 6 Select the name of the folder you want to add to the START menu and push NEXT Rev 6 28 10 2014 Page 33 of 80 industries fey Setup miniOMNIAlogConnect Select Start Menu Folder Where should Setup place the program s shortcuts Setup will cr
38. log is correctly set up in STOP state After that flashing number 0 will appear on display meaning that the miniOMNIAlog is waiting for a connection The miniOMNIAlog waits for connection for 30 sec After 30 sec you should repeat connection procedure from point 1 to start a connection Start PC connection by clicking on connect button in the connection window see the par miniOMNIAlog local connection After connection number 0 will appear on display Open Browser and enter address 192 168 125 1 Enter miniOMNIAlog Username and Password see the par miniOMNIAlog default setting Now it is possible to surf the configuration pages ts gt lt miniOMNIAlog LOCAL CONNECTION To establish a connection through Dial up call with a PC follow the next steps 1 Install the USB driver FTDI driver 2 miniOMNIAlog Connection Tool to create the virtual 56000 bps modem and to create the dial up connection 3 miniOMNIAlog setup To communicate with miniOMNIAlog by USB connection a small driver FTDI Driver is needed to permit to the PC to recognize the miniOMNIAlog Usually if your PC is already connected to the internet when you connect miniOMNIAlog Microsoft Windows is able to download and install this driver automatically If Microsoft Windows does not install the driver automatically or your PC is not connected to the internet you can download the driver for free at the following link http www ftdichip com
39. nal power supply on the V IN clamp of miniOMNIAlog check if the voltage is within the range accepted by miniOMNIAlog and stable If miniOMNIAlog doesn t turn on or the display stops responding Follow this step testing after each 1 remove power supply on V IN clamp for 10 seconds and try to reconnect If miniOMNIAlog doesn t appear under Windows Device Manager as virtual COM port Follow these steps testing after each 1 restart your computer 2 remove and reinstall the USB driver and restart your computer 3 remove power supply on V IN clamp for 10 seconds and try to reconnect Itis impossible to upload the configuration Follow this step testing after each 1 in webpage STATUS verify that OMNIAlog is in Config 2 make sure that the configuration you are trying to upload has been created with the same major release of the firmware on OMNIAlog NOTE if what is written above is correct the configuration file could be altered In this case OMNIAlog warns with an error message the file is no more usable We suggest to repeat the configuration process If OMNIAlog blocks during an acquisition Follow this step testing after each 1 verify the events log and refer to the manual miniOMNIAlog amp OMNIAlog Codes Alarms Events for the comprehension of the eventual logs POSET 2 verify that OMNIAlog has a correctly power supply If the power supply is below the minimum threshold or over the maximum threshold of power
40. nect e Ifthe COM port doesn t appear in the list it is possible to click on bottom Refresh ports list to update the available ports After selecting the right COM port click on Connect e miniOMNIAlog Connection Tool 64bit v1 5 Connect e The creation of the remote connection starts e miniOMNIAlog Connection Tool 64bit v1 5 9 industries the configuration ended a confirmation message appears Connection Connection successfully created Please select State 8 on miniOMNIAlog and than press OK to connect Refer to manual for details Cancel As describe in the message select menu 8 on miniOMNIAlog and press ENTER button of miniOMNIAlog keyboard When the 0 blinking press OK on the tool industries e Clicking on OK the connection starts e miniOMNIAlog Connection Tool 64bit v1 5 Connection on Standard 56000 bps Modem 2 When the connection with miniOMNIAlog is established the following window appears 2 miniOMNIAlog Connection Tool 64bit v1 5 Refresh ports list OMS Connect Connected on Standard 56000 bps Modem 2 miniOMNIAlog default IP address is 192 168 125 1 e In this window you can find a reminder of defult IP address of miniOMNIAlog e Itis possible to close the tool clicking on the X of the window e miniOMNIAlog Connection Tool 64bit v1 5 coms Connect e Open any internet browser and enter the IP address 192 168 125 1
41. nt equipment with their complete accessories using suitable packaging or even better the original ones The shipping costs shall be covered by the sender Please return to the following address with suitable delivery document NEXT INDUSTRIES S r l Via F Serpero 4 F2 20060 MASATE MI On the delivery document is mandatory to indicate the RMA code received Technical assistance e mail assistance next industries com industries Rev 6 28 10 2014 Page 69 of 80 industries R amp TTE Declaration of Conformity DoC Address Via Serpero 4 F1 20060 Masate Milano Italy hereby declare under our sole responsibility that the product to which this declaration relates is in conformity with the essential requirements and other relevant requirements of the R amp TTE Directive 1999 5 EC The product is in conformity with the following standards and or other normative documents HEALTH amp SAFETY Art 3 1 a EN 61010 1 2010 EN 62311 2008 EMC Art 3 1 b EN 301489 1 V 1 9 2 EN 301489 7 V 1 3 1 SPECTRUM Art 3 2 EN 301511 V 9 0 2 OTHER Art 3 3 and voluntary Not applicable specs Supplementary information Notified body involved Place and date of issue of this DoC MASATE MI November 27 2013 Name in print ROMANO LAMPERTI Title MANAGING DIRECTOR SISGEO S r 1 Via F Serpero 4 F1 20060 MASATE MI Tel 39 02 95 764130 Fax 39 02 95 762011
42. o to error state and an error code will be shown After stop result is shown a 15 sec timeout is started After that the miniOMNIAlog will come back to main menu and will start the timeout display At timeout display expiration the display will turn off While the menu shows the stop state error code or OK Select key causes the display returning back to main menu and timeout reset display Firmware version Menu 7 If you press Enter key in correspondence to the menu entry Firmware Version 7 the miniOMNIAlog will show the installed firmware version Firmware version is displayed like the string F X X X X X X only once After that the menu goes back to main menu 1 i 1 i industries USB connection Menu 8 If you press Enter key in correspondence to the menu entry Usb connection 8 the miniOMNIAlog will show the letter A and then the flashing number 0 to indicate to the user that PC connection can be started time for connection is 30 sec and after that the miniOMNIAlog goes back to main menu As connection is on the flashing number 0 becomes permanent The user can now use the miniOMNIAlog by PC NOTE As the user removes the miniOMNIAlog from PC so he removes remote PC connection the display goes back to connection state flashing 0 for 40 sec and during this time the user could reconnect After 40 sec it goes back to main menu industries Power off Menu 9 u Pressin
43. one only by qualified technicians Periodically verify the voltage of the external battery in case of a value inferior to 11 5Vdc consider the substitution of the battery and check on the causes Anyway battery has to be substituted after 5 years If for every reasons the battery capacity descends under 50 consider its immediate substitution Periodically verify the voltage of batteries in batteries holder in case of a value inferior to 8 4V consider the substitution of the battery and check on the causes Avoid any activity that can put the battery poles in short circuit use of non original SISGEO spare parts can cause abnormal functioning and dangers for people and things Supplied equipments and devices are not suitable to be installed in potentially dangerous areas or in areas where the use of explosion proof components is prescribed In potentially explosive areas it is necessary to shut down miniOMNIAlog Possible sparks could cause explosions or fires causing serious injuries or even death Generally areas with a potentially explosive atmospehere are signalled Consider the periodic substitution of bags of hygroscopic salts miniOMNIAlog contains fragile parts and components Do not drop disassemble press or deform miniOMNIAlog Do not use miniOMNIAlog if it is damaged The lack of respect for this behavior could damage the installed equipment industries DISPOSAL The disused devices h
44. our ISP On the miniOMNIAlog web server select the Advanced page from the left menu select the Connection page In the Connection page you have to O write the APN of your Internet Service Provider ISP in the APN field e g web omnitel it NOTE if in place of APN there is the field AT command initialization it is necessary to insert the following command CGDCONT 1 IP APN e g CGDCONT Zz1 IP web omnitel it write the telephone number in Telephone Number field to establish GPRS connection Usually the number is 99 1 connection using the default CID 1 overrode with the AT CGDCONT command write the Username and Password according to your ISP parameter Press Save Changes to confirm the modifications Reboot miniOMNIAlog to make the changes effective MEXT WEB PAGES FUNCTIONALITY NOTE The uploading speed of pages could be very slow especially at first access This occurs because the browser hasn t memorized the web pages in its cache yet You have to wait until the pages are completely loaded without repeatedly refresh the page Here you can find a brief description of the main miniOMNIAlog web pages Web pages are the same of OMNIAlog pages or fields cannot be modified STATUS Shows miniOMNIAlog status In this page is shown the current miniOMNIAlog mode Run miniOMNIAlog is set and started It will start acquisitions according to selected configuration Config miniOMNIAlog
45. r Supply CH 1 4 GND PWR ONLY forEXT POWER SUPPLY Do not connect with ext power supply Digitalized Instruments Rev 6 28 10 2014 Page 55 of 80 Digitized Instruments chain Direct connection 3 2 8 a 5 3 E 5 Rev 6 28 10 2014 Page 56 of 80 industries hh MEXT Relay Output volt free closure On the miniOMNIAlog board there is one clamp for the relay output for alarm etc managed from the software The relay output is a volt free closure low voltage 30V 1A Relay Output Note The relay output change for 1 minute Anomalies and Alarm Warnings Error Codes When the miniOMNIAlog is in error status it shows the letter E and error codes one after the other Following there are miniOMNIAlog error codes General Communication or FTP MAIL connection EO Error It refers to log events on web server USB Drive not found Error in file copy train He copy a already state E4 ltisimpossibletostartthe miniOMNlAlogg l simpossibletostoptheminiOMNlAlog is MEXT industries The system shows general error codes because it has a simple display and so it would be difficult to encode each case The system will log the event error and it will be visible and downloadable from the web 1 P 1 4 industries Icons and power supply alarm thresholds miniOMNIAlog with exte
46. rnal power supply Icon showed plug Display L High alarm threshold 14V Low alarm threshold 10 5V miniOMNIAlog with internal battery pack Icons showed cell battery Full battery voltage 9 6V Medium battery 8 76V voltage 9 6V Low battery Voltage x 8 76V Display 3 lines Voltage 2 9 6V 2 lines 8 76V voltage 9 6V 1 line voltage lt 8 76V High alarm threshold not present Low alarm threshold 8 76V 1 P 1 4 41 industries Maintenance Always disconnect miniOMNIAlog from its power source during maintenance REPAIR OR MODIFY miniOMNIAlog SISGEO doesn t allow the user to repair or modify miniOMNIAlog The lack of respect of this instruction could provoke damages that aren t covered by any warranty In case of malfunctioning contact the assistance SISGEO miniOMNIAlog cleanliness To clean miniOMNIAlog use a soft cloth without using any cleaning product CALIBRATION SISGEO suggests a periodic calibration of miniOMNIAlog every 2 years or when necessary Contact the Technical Assistance SISGEO to receive further information I industries TROUBLESHOOTING miniOMNIAlog Basic Troubleshooting This paragraph provides basic miniOMNIAlog troubleshooting tips Are you up to date 1 Verify that you installed the last version of firmware 2 Verify that you have the last and the correct version of USB driver 3 Verify that you have an adequate power supply from battery pack or exter
47. s After that the miniOMNIAlog will come back to main menu and will start the timeout display At timeout display expiration the display will turn off While the menu shows the display state Select key causes the display returning back to main menu and timeout reset display industries Battery Menu 2 If you press Enter key in correspondence to the Battery menu entry 2 the miniOMNIAlog will display the batteries charge state Here follows the battery levels code scheme Battery level Display Code Description Low m Battery under 30 Medium Battery 50 High Battery 100 Saas SSS DENEN EET S SS LOW charge MEDIUM charge HIGH charge The user can read the miniOMNIAlog state when he enters the menu As soon as the user enters the battery state a 15 sec timeout starts After that the miniOMNIAlog will come back to main menu and will start the timeout display it can be set up from the internet At timeout display expiration the display will turn off While the menu shows the display state Select key causes the display returning back to main menu and timeout reset display NOTE if the miniOMNIAlog has an external power supply battery state will L or not important in case of external power supply industries Firmware updating menu 3 NOTE miniOMNIAlog should be in Stop or Config state before using
48. supply OMNIAlog blocks every activity in progress 3 verify the alarm log to identify the problem and refer to the manual miniOMNIAlog amp OMNIAlog_ Codes Alarms Events to understand the eventual logs 4 verify if in alarm log it is present an overcurrent error In case of overcurrent OMNIAlog stops the acquisition 5 verify the available memory In case of full memory OMNIAlog stops the acquisition Itis impossible to download data on the USB flash drive Follow this step testing after each 1 verify that the USB flash drive is formatted in FAT32 2 verify with the PC that the USB flash drive is read without any errors 1 try with a different USB flash drive MEST industries miniOMNIAlog Local Communication Troubleshooting This paragraph provides miniOMNIAlog local communication troubleshooting tips Are you up to date 1 2 3 Verify that you installed the last version of firmware Verify that you have the last and the correct version of USB driver Verify that you have the correct power supply from battery pack or external power supply on the V IN clamp of miniOMNIAlog If you are not able to establish the connection with miniOMNIAlog Follow these steps testing after each 1 2 E M IE a be sure that on 7 segment display a blinking 0 appears If an 8 appears wait for a blinking 0 check if the virtual COM port is showed under Microsoft Windows Device Manager see If miniOMNIAlog do
49. this function If you press Enter key in correspondence to the menu entry Firmware updating 3 the miniOMNIAlog will run the web and firmware updating from USB flash drive This menu is different from the others as updating needs a restart and systems management that are different from standard operations Flashing d letter is shown on display during files copy At the end of files copy the miniOMNIAlog 1 shows error if USB flash drive was not found and waits for timeout display or Select key to go back to main menu 2 shows error if files copy failed for a time equal to timeout and then resets After reset the miniOMNIAlog will go to its normal state 3 resets and starts bootloader for firmware updating if files copy was successful flashing b letter will appear during firmware reprogramming After firmware updating two things can happen I firmware updating was successful letter A is showed for a time equal to timeout and after that miniOMNIAlog goes to the normal state II firmware updating failed the miniOMNIAlog restores old versions from web and resets letter E is showed for 15 sec ul NOTE after firmware update to communicate with miniOMNIAlog you have to unplug and re plug the power supply Set USB flash drive for miniOMNIAlog firmware update SISGEO strongly recommends to keep miniOMNIAlog updated to the last firmware version available to ensure the best performances to solve