1. IIl MMM www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel 1 Summary Temperature control panel is a device to control indoor temperature It adjust the room temperature and relative humidity according to the measured temperature and relative humidity generally implemented by controlling indoor temperature controller and fan coil actuator one the bus Temperature control panel closely bound up with our living environment For example in an air conditioned room people would feel comfortable only the room temperature and relative humidity is under in a certain range Then we can monitor the current actual indoor temperature relative humidity through the panel if itis beyond control the temperature control panel will send a signal to adjust the indoor temperature and humidity by air condition It is also widely applied in other industries such as food industry temperature and humidity are essential greenhouse and other humidity related industries User can adjust the indoor temperature according to their needs by capacitive touch buttons LCD screen displays the status of the current temperature control This user manual provides specific technical information including installation and programming details In the case of actual use and contact a description of how to use the temperature control panel as well as expla
2. 22 4 5 PARAMETER SETTING INTERFACE HEATING COOLING CONTROL 33 4 6 PARAMETER SETTING INTERFACE FAN COIL 39 4 7 PARAMETER WINDOW FAN COIL HEATING COOLING 40 4 8 PARAMETER WINDOW THRESHOLD VALUE 42 4 8 1 Temperature threshold 43 4 8 2 Humidity threshold 46 4 9 PARAMETER WINDOW LOGIC 49 4 10 PARAMETER WINDOW TIMER PAGE 1 AND TIMER PAGE 2 53 4 11 PARAMETER WINDOW PUSHBUTTON 56 FIGURE 4 12 PARAMETER WINDOW AIR 66 5 COMMUNICATION OBJECT DESCRIPTION 69 5 1 GENERAL SETTING COMMUNICATION
3. Fan Coil Heating Hour 8 5 Fan Coil General Threshold value Minute 0 Temperature threshold value 1 Logic Reaction at regular time byte value 0 255 M Timer Page 1 2 Venue 2 Pushbutton Interface Time 2 enable Week Monday Hour 8 Minute 0 z Reaction at regular time No reaction Device 1 1 5 Thermostat General Settings Time 9 enable Measurement Settings Heating setpoint Week Monday gt tz Heating control Fan Coil Heating Hour 8 Fan Coil General Threshold value Minute 0 Temperature threshold value 1 Humidity threshold value 1 Operating mode unchange logic 1 Reaction at regular time No reaction Triar Piga Time 10 Timer Page 2 Pushbutton Interface Week Monday Hour 8 S Minute 0 f Operating mode unchange x Reaction at regular time No reaction 11 disable Figure 4 10 parameter window Timer Page 1 and Timer Page 2 Parameter Time x Options enable disable 54 pu Trr R s M M J www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel This parameter is used to activate a timing time After the tim
4. 2 100 1 bit value 0 1 Time 9 value 1 bit de me PE 101 1 bit value 0 1 Time 10 value 1 bit 6 2 102 1 bit value 0 1 Time 11 value Dh EI 103 1 bit value 0 1 Time 12 value 1 bit 104 1 bit value 0 1 Time 13 value fbt TS B 105 1 bit value 0 1 Time 14 value 1 bit j al 106 1 bit value 0 1 Time 15 value 1 bit E 22 107 1 bit value 0 1 Time 16 value TID 805 p Figure 5 5 Timer communication object Number Communication object name Functions Data Types Attribute 51 Time Timer 3 byte C R W T This communication object is used to modify the LCD screen displaying time by bus 52 Disable room temperature timer Timer 1bit C W This communication object is used to disable or enable the Timer function Receive telegram 1 disable the timer function Receive telegram 0 enable the timer function 92 107 1bit value 4byte value Time X value X 1 16 1bit 4byte C T When the timer time reaches this communication object sends the appropriate data values to the bus the user can select the appropriate data type and value in the parameter Reaction at regular time and the parameter Output value as required for transmission 5 6 Pushbutton Interface Communication Object 5 6 1 Switch Communication Object n2 53 Switch 1 input 1 CH A Switch 1 bit C T n 54 Switch 2 input 1 CH A switch long 1 bit C 82 55 Disable input 1 CH A Disable 1
5. 69 www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel 5 2 HEATING COOLING CONTROL COMMUNICATION OBJECT 70 5 3 THRESHOLD VALUE COMMUNICATION 75 5 4 LOGIC COMMUNICATION 78 5 5 TIMER PAGE 1 2 COMMUNICATION 78 5 6 PUSHBUTTON INTERFACE COMMUNICATION 79 5 6 1 Switch Communication Object 79 5 6 2 Dimming Communication Object 80 5 6 3 Shutter Communication Object 81 5 6 4 Scene Communication object 82 5 6 5 Temperature limiter underfloor heating Communication Object 82 5 7 AIR CONDITION COMMUNICATION OBJECTS 83 3
6. AJ fmi Hc www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel 80 then the valve will be opened for 8mins closed for 2mins all cycles in this way Temperature control panel will calculate the control value every 30 seconds according to temperature conditions ratio range and integration time If you select Two Position Control you can set a delay interval through parameter to prevent that the small decline or rise of temperature causes the frequent switching on off of actuator and results in the frequent switching on off of the valve The delay interval is symmetrically disposed above and below the set temperature e g in the cooling mode if the set temperature is 21 C the delay interval is 2 C then the controlled object will send an on or 100 telegram at 22 C and open the valve for cooling when the temperature drops to 20 the controlled object will send an off or 0 telegram and close the valve to stop cooling Temperature setpoint is the temperature set under current working mode If you choose fan coil Control the type of communication object of control value will be the same with that of Continuous PI Control In addition the page Fan Coil Heating Cooling is visible Different control types have different parameters and object but most of them are similar In order not to
7. Un J 2 ulis dim __ _ www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel 1BYTE If this parameter is visible when function switchover blinds roller shutter selects shutter and is used to set the object types of Output shutter UP DOWN and Output Stop lamella adj Parameter Cyclical transmission tele repetition Entry 0 1s Options 3 250 The parameter is visible when selecting 1bit in the parameter object type where setting the switch s long press operation the interval of two telegrams is sent cyclically In Input 1 2 3 when selecting Scene for Function of input 1 2 3 the parameter window is seen as Figure 4 11 5 if this function is enabled sending and saving the scene can be achieved Device 1 1 5 Thermostat General Settings Measurement Settings MT 4 Heating setpoint i Number of scene 1 Heating control Fan Coil Heating i Storage function light scenes enable Fan Coil General i Z Threshold value Long operation after 10 m Temperature threshold value 1 i Humidity threshold value 1 Logic logic 1 Timer Page 1 Timer Page 2 Pushbutton Interface Input 1 Input 2 Input 3 Input 4 Figure 4 11 5 parameter window Scene Parameter Number of scene Options 1 64 Here Number of scene can be set and its range 1 64 when t
8. B after bus voltage recovery Timer Page 2 Pushbutton Interface Figure 4 9 1 Parameter window Logic Parameter Active logic function Options enable disable Here is to set whether to enable logic functions Parameter logic1 Parameter logic 2 Options enable disable This parameter sets whether to enable logic 1 and logic 2 If select enable it means logic 1 and logic 2 are enabled and their parameter window can be seen in Figure 4 9 2 Parameter The value of communication object input A after bus voltage recovery Parameter The value of communication object input B after bus voltage recovery Options 0 1 This parameter sets logic values of Input A and Input B when the bus on a power on reset Input A and Input B logic values can be changed via the communication object communication object logic Input A and communication object logic Input B 49 pau SE 9SRHM G u eee www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel In Figure 4 9 2 in the parameter window of logic1 and the logic 2 Input 1 and Input 2 for the first run logic operation and the operation result is then runs logical operation with Input3 at last the final logical result is obtained according to the final results two different types of data transmission
9. 22 38 Humidity threshold value 1 block Humidity threshold value 1 1 bit CE R 2 39 Change humidity threshold value 2 Humidity threshold value 2 2Byte C R W 82 40 1 bit output humidity Humidity threshold value 2 1 bit C Ri Fx 22 41 1 byte output humidity Humidity threshold value 2 1Byte C R 82 42 Humidity threshold value 2 block Humidity threshold value 2 1 bit ER MW Figure 5 3 Threshold value communication object Numbe Communication object name Functions Data Types Attribute r 27 31 Chang temperature threshold value 1 2 Temperature threshold value 1 2 2byte C R W This communication object is used to change the temperature s high threshold value Telegram 0 50 C 76 E E au3ac c E SSMIEOGAG EF J nH www video star com cn maketing a video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel 28 32 1 bit output temperature Temperature threshold value 1 2 Ibit C RT When the temperature is higher than the current high threshold or below the low threshold 1bit telegram be sent via this object to the bus specific telegrams be set by the parameter logic Ibit telegram value 0 1 29 33 byte output temperature Temperature threshold value 1 2 Ibyte C RT When the temperature is higher than the current high thres
10. J www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel Once setting the internal and external sensor if the thermostat panel does not receive the temperature send by external temperature sensor within the set monitoring time temperature control panel will consider the external sensor is faulty so that only use the measurement by temperature control panel to control The monitoring time will be re timed when the thermostat panel receives each packet send from the external temperature sensor Note The monitoring time from temperature control panel for external temperature sensor should be at least 2 times for the time that the external temperature sensor sending messages for preventing packets missing Parameters Period of sending temperature Options Do not send 5s 10s 2h This parameter sets the time interval of sensor for sending temperature to the bus loop through Actual temperature Parameters Indoor and outdoor temperature Options disable enable The parameter is visible when the Temperature sensor selecting internal sensor and external sensor which can be used to set whether to alternately display the indoor temperature and outdoor temperature on the display Outdoor temperature taken from the object 84 Parameters Indoor and outdoor temperature switch time second Options 0 255 s The parameter will
11. Entry 0 15 s Fan Coil Heating Fan Coil General Reaction on short operation No action z Threshold value Reaction on long operation brighter darker X Temperature threshold value 1 Humidity threshold value 1 i Step size for dimming 1 56 Logic logic 1 i Transmission dimming stop telegram yes Timer Page 1 i Cyclical transmission of dimming enable Timer Page 2 i telegrams Pushbutton Interface i Input 1 i Time between two dimming telegrams 10 Input 2 Input 3 Input 4 Figure 4 11 3 parameter window Switch Dimming Parameter Long operation after Options 3 250 This parameter defines the contact input s effective time for a long operation If the connecting time of input contacts is longer that the set time the operation is considered as long operation Parameter Reaction on short operation Options no action off on toggle If select Dimming and Switching in Dimming functionality the parameter is visible Through this 60 m POP RD s e M e ieri www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel parameter user can set the operation after Switch X is triggered namely the switching operations when the contact input is short operation Parameter Reaction on long operation Options brighter darker brighter darker
12. 1bit 0 1 1byte 0 255 Here is to set the value of the logic object sends when the logic results are 1 and O Parameter cycle time for logic min This parameter is used to set the interval of the object logic 1 2 1bit 1byte output cyclically sends on the bus only when the parameter if logic result 0 1 set cyclically sending is it enabled Parameter use block of the logic 1 2 output Options yes no This parameter sets whether to disable the threshold value if enabled the object logic 1 2 block is visible when the object receives telegram 1 threshold value is disabled when the object receives telegram O the threshold value is enabled When select yes the following parameters can be seen Parameter Behaviour when setting the lock Options do not send the same as logic result 0 the same as logic resultz 1 52 pu PPPII E M Mnt X J a c www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel This parameter sets the action when the threshold value is disabled Select do not send no action Select the same as logic result 0 when the object logic 1 2 block receives telegram 1 the object logic 1 2 1bit 1byte output sends the same telegram as with telegram O Select the same as logic 1 when
13. 1bit telegram is sent e through this object the telegram is set by parameter 1bit telegram value 46 49 Logic 1 2 1 byte output Logic 1 2 1byte C R T When the logical result is 1 or 0 1bit telegram is sent e through this object the telegram is set by parameter 1byte telegram value in 4 8 47 50 Logic 1 2 block Logic 1 2 1bit C RW This communication object is used to disable or enable the logic function Disabled and enabled actions can be set by the parameter Receive telegram 1 disable the logic function Receive telegram 0 enable the logic function 5 5 Timer Page 1 2 communication object 22 51 Time Time 3Bye C R W T 2 52 Disable room temperature timer Time 1 bit C 78 p T WQ E D H 22 2 Ys T www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel e 92 1 bit value 0 1 Time 1 value 1 bit G T 2 93 1 bit value 0 1 Time 2 value 1 bit CS CN 2 94 1 bit value 0 1 Time 3 value 1 bit x 95 1 bit value 0 1 Time 4 value Tb 4 55 5 5 4 2 96 1 bit value 0 1 Time 5 value 1 bit 55 22 97 1 bit value 0 1 Time 6 value 1 bit 2362 m2 98 1 bit value 0 1 Time 7 value 1 bit E 22 99 1 bit value 0 1 Time 8 value 1 bit
14. 83 D RH t A P V oie Kp SB www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel 67 Switch to low auto speed Temperature control 1 bit C T In Air condition the object is visible when selecting 1 bit in Object type for controlling air condition When the wind speed is low sending 1 when the speed is automatic it will send 0 68 83 setpoint for cooling A B Setpoint temperature 1 bit C T In Air condition the object is visible when selecting 1 bit in Object type for controlling air condition When the temperature is set as A 1 will be sent when the set temperature is B 0 will be sent 84 I TPIBOD A DEG e rs P P nun n www video star com cn maketing a video star com cn Tel 8620 39338986 Fax 8620 39338465
15. AM PM means the time display system in temperature control panel for 12 hour Parameters Send current time Options Do not send 1s 30s 1min 30min 1h This parameter set sends the current time on the bus Do not send means don t send time to the bus 16 HR R E K A hi Mni s M NT www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel 1s means sending the time to the bus per second 30s means sending time to the bus per 30s 1min means sending the time to the bus every 1 minute 30min means sending the time to the bus every 30 minutes 1h means sending the time to the bus every 1 hour Parameters Warning tone Options disable enable The parameters mainly are set in the temperature control panel keys about whether to open the tone Disable is not enabled tone enable to enable beep Parameter Control device Options HVAC air condition This parameter is used to select the type of heating and cooling systems HVAC means the fan coil system controlling the temperature by controlling fan coil actuator air condition means home air conditioning system adjusting household air temperature by controlling the infrared device Parameter Temperature control system Options Cooling Heating Heating
16. Modulation mode this parameter is very necessary In PWM mode if the control value is very small it will cause the valve open for a very short time and close for very long it may be not long enough to open the valve thus will not make a good regulation of room temperature and the valve will be easily damaged Parameter maximum control value Options 70 100 This parameter is used to set the maximum allowable value of the control value When control value calculated from PI is larger than the set maximum value temperature control panel will send the 37 TT M Z S EB CI Vja n ll ag e m MV www video star com cn maketing a video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel maximum value If you use a temperature control panel to control an actuator using PWM Pulse Width Modulation mode this parameter is very necessary In PWM mode if the PI control value is very large it will cause the valve open for a very long time and close for very short it may be not long enough to close the valve thus will not make a good regulation of room temperature and the valve will be easily damaged Parameters send control value at variation of Options 0 15 This parameter is visible only when the control type is continuous PI control visible Only when setting the certain amount of
17. Shutter control in Function of input 1 2 3 seen in Figure 4 11 4 After enabling this function user can control the shutter through one or two input operations Device 1 1 5 Thermostat mnc p MR D NEES E SA General Settings Function of input 1 Shutter Control Measurement Settings i Long operation after 10 Heating control i Fan Coil Heating Function switchover blinds roller shutte Shutter Fan Coil General d Threshold value i Objet type 1 BIT Temperature threshold value 1 Humidity threshold value 1 Cyclical transmission tele repetition 30 Entry 0 15 22 Logic logic 1 Timer Page 1 Timer Page 2 Pushbutton Interface Input 1 Input 2 Input 3 Input 4 Figure 4 11 4 parameter window Shutter control Parameter Long operation after Options 3 250 This parameter defines the contact input s effective time for a long operation If the connecting time of input contacts is longer that the set time the operation is considered as long operation Parameter Function switchover blinds roller shutter Options Shutter Roller shutter Set action performed when contact input is operated Note that if the parameter reaction on operation selects toggle its direction is negated after each time sending a moving telegram Parameter Object type Options 1BIT 62 m DH SGB E E IJ J
18. by the humidity threshold or the message received from the bus also it can be obtained by getting the opposite message to participate in the logic operation the message 1 bit 1 byte will be output according to the result triggering the switch of other equipment or to adjust output of valves 12 www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel 3 7 ban enable temperature and humidity control function the threshold value and the logical function The temperature and humidity control functions can be prohibited or enabled by bus when the temperature humidity function is banned the temperature control panel will not be able to send the control values The threshold value and the logical function can also be banned or enabled by bus when the threshold function is banned the temperature control panel will not determine the current threshold values range of temperature and humidity and will not control it When logic functions are banned logic operation from temperature control panel will be disrupted as well as the control of this function 3 8 timing function Temperature control panel offers 16 timing time so users can set the timing time regularly according to their using habits which automatically adjust the working mode and send the appropriate value When arrived at timing time it can automatically switch to the correspondi
19. temperature control which send by the Actual temperature This is the proportion summing process Parameters Send temperature at variation of C Options Do not send 0 1 0 2 3 This parameter define Actual temperature can send the current temperature to the bus when a certain amount of temperature change If the option is Do not send the temperature only be sent to the bus through the Actual temperature because the temperature measurement value is not automatically transmitted to the bus If an option is 3 the Actual temperature can send the current temperature to the bus when the temperature reached changes at least Parameter Monitoring time of external sensor in min 0 inactive Options 0 255 min This parameter will be visible when choosing external sensor or internal and external sensor about sensor type to set monitoring time of the thermostat panel to external temperature sensor If setting the monitoring time to 0 will not be monitoring the external temperature sensor Once setting the external sensor if the thermostat panel does not receive the temperature send from external temperature sensor within the set monitoring time temperature control panel will consider the external sensor is faulty will stop controlling and control sending packets of controlling stop 20 m PT UH H HB E BI S RM us
20. 2 and once changing in the bus will save the new value when the power of the BUS is off Parameter Negative hysteresis temperature x0 1 C Options 5 50 43 www video star com cn maketing a video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel This parameter is used to set the hysteresis value of the low threshold value to high threshold value Assuming the hysteresis value is 3 C then the lower threshold high threshold value 3 C When the high threshold changes the low threshold changes accordingly Parameter If temperature is lower than threshold value Parameter If temperature is upper than threshold value Options do not send telegram send following telegram once send following telegram cyclically These two parameters are used to respectively set ways of sending telegram to the object 1bit 1byte output temperature when the detected temperature is below the low threshold or above the high threshold If select do not send telegram no telegram is sent if select send following telegram once the telegram is sent once if select send cyclically the telegram is sent cyclically send cyclically time can be set in the below cycle time for temperature threshold value min and at most two values can be set in the below logic1bit 1byte telegram value Parameter logic 1 bit 1byte telegram value Options Logic 1bit 0 1 1byte 0 255 This pa
21. 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel 3 Actual temperature Temperature 2 byte C R T The communication object is used to send the current temperature that is detected by the thermostat panel sensor to the bus the transmission time is set via parameter settings When there is an external temperature sensor the object is used to send the proportion and sum of temperatures sent by multiple sensors or temperature by external sensor 4 rel humidity Humidity 2 byte C R T The communication object is used to send the current humidity that is detected by the thermostat panel sensor to the bus the transmission time is set via parameter settings 5 Operating mode forced object Setpoint temperature 1 byte C R W This communication object is mandatory conversion of operating mode and has the highest priority Different telegrams mean different operating modes as follows 0 Auto comfortable 1 comfort mode 2 Standby mode 3 Night Mode 4 Frozen protection heat protection 5 255 Reserved do not use For example when an object receives a telegram 2 the thermostat panel will control the actuator according to the standby mode setting 6 Window status Setpoint temperature 1 bit C R W This communication object is used to connect a window contact Receive telegram 1 the windows open Receive telegram 0 the
22. and Cooling Basic and additional cooling Basic and additional heating Basic and additional Heating and Cooling This parameter is used to set the temperature control feature you can select the basic heating and cooling can also choose the basic heating and cooling plus auxiliary heating and cooling Select cooling heating enabling cooling heating function or both enabled when selecting its options the corresponding settings interface heating cooling setpoint and heating cooling control visible in the interface can be set with the corresponding parameters Parameter Control action when display off 17 PHO S SE I L n en www video star com cn maketing a video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel Options All off Protect mode This parameter is a command need to be send when the display off All off means the command of sending off the fan and coil instructions when the screen being turned off Protect mode means the command of the room mode transfer to protected mode when the screen being turned off Parameters Heating and cooling share object Options yes Activation no Do not activate This parameter is visible when choosing Heating and Cooling or Basic and additional Heating and Cooling in temperature control function this parameter is use
23. and cyclically means that both change and sending as well as cyclically sending Parameter Period of sending setpoint Options 5 64 10s 2h This option sets the time period of cyclically send the parameter Send setpoint is visible when selecting the cyclically or on change and cyclically Parameter Object type for controlling air condition Options 1bit 1byte This option is set to format of sending command 1bit means that using different 1bit communication objects to control different commands the specific information can be seen in the description of 64 83 communication objects 67 a S J A rs i ac Tl www video star com cn maketing a video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel Parameter Command for air condition on Parameter Command for air condition off Options 1 64 These two parameters are to set the command value of air conditioner ON OFF When parameter Object type for controlling air condition is selected 1byte it is visible Parameter Command for heating mode Parameter Command for air cooling mode Options 1 64 These two parameters are to set the command value of switching between heating and cooling mode When parameter Object type for controlling air condition is selected 1byte it is visibl
24. be visible when the parameter Indoor and outdoor temperature selecting enable which is used to set the time interval for the internal temperature and external temperature alternately 21 mau P r Ke eel www video star com cn maketing a video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel Parameters Humidity correction in Optional 15 15 This parameter defines the correction settings of humidity that sensor measured to prevent much error between the moisture measurement with the actual humidity example setting correction value to 196 if the humidity measured by the sensor is 4096 then the corrected humidity is 40 1 41 Parameters Send rel Humidity at variation of Options Do not send 1 2 20 This parameter defines to change when humidity change a certain amount the communication object rel Humidity can send current humidity to the bus If choosing do not send humidity measurements are not automatically sent to the bus can sent automatically after be read through communication objects rel Humidity If choosing 3 the communication object rel humidity will send to the current temperature on the bus when the humidity changed to 396 Parameters Period of sending humidity Options Do not send 5s 10s 2h This parameter setting define
25. brighten or darken command User can control the dimming device on the bus conduct relative dimming When the input is disconnected it will send an end command to stop dimming 80 L www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel 55 58 61 Disable input 1 2 3 CH A Disable Ibit C W When the channel function is enabled the communication object is activated which is used to disable enable channel function When this communication object receives a logic value of 0 the channel function is enabled receives 1 disabled When the channel function is disabled control telegrams sent by all objects are invalid When the bus power is restored channel function is enabled by default If all communications objects with channel function are Disable the operations performed are the same 5 6 3 Shutter Communication Object 2 53 Output shutter UP DOWN CH A Blind 1 bit C T n 54 Output Stop lamella adj CH A Blind 1 bit gs T 55 Disable input 1 CH A Disable 1 bit 2 56 Output shutter UP DOWN CH B Blind GU 4 82 57 Output Stop lamella adj CH B Blind 1 bit C m 4 ng 58 Disable input 2 CH B Disable Tb eG n 59 Output shutter UP DOWN CH C Blind 1 bit 62 lt lt 60 Output Stop lamella adj CH C Blind 1 bit Gu T 22 61 Disable input 3 C
26. cooling function The cooling comfort temperature setpoint can be set here Temperature setpoint of cooling comfort mode Temperature setpoint of heating comfort mode dead zone If the values of dead zone is 3 C temperature setpoint of heating comfort mode is 22 C that means the temperature setpoint of the cooling comfort mode is 25 30 EEE SS a ee www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel Parameter of setpoint increase for standby mode at cooling in 0 1Celsius option 0 100 Parameter of setpoint increase for standby mode at cooling in 0 1Celsius is use for setting the increment that decides the stand by mode s temperature setpoint which is changed with the comfort temperature setpoint under the circumstance of cooling function For example if setting the increment of 3 C when the comfort temperature setpoint is 23 C the stand by mode s temperature setpoint will be 26 C Parameter of setpoint increase for night mode at cooling in 0 1Celsius option 0 100 Parameter of setpoint increase for night mode at cooling in 0 1Celsius is use for setting the increment that decides the night mode s temperature setpoint which is changed with the comfort temperature setpoint under the circumstance of cooling function For example if setting the deduction of 2 C when the comfort temperat
27. maketing a video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel temperature is between the high and low thresholds the object value cannot be determined the telegram is not sent even though in case of sending cyclically This parameter can be seen in use block of the temperature threshold output if User selects yes 4 8 2 Humidity threshold value Device 1 1 5 Thermostat General Settings idi humidity threshold value in 96 60 Heating setpoint MTM Negative hysteresis humidity in 96 2 m Fan Coil Heating NE 5 If humidity is lower than threshold send following telegram once X Fan Coil General Aum Threshold value Temperature threshold value 1 Logic 1bit telegram value 0 1 0 x Humidity threshold value 1 Tm lbyte telegram value 0 255 0 TEN If humidity is upper than threshold send following telegram once Timer Page 2 be Pushbutton Interface Logic 1bit telegram value 0 1 uM 1byte telegram value 0 255 255 Cycle time for humidity threshold 10 E value in min if used Use block of the humidity threshold output Figure 4 8 2 Parameter window Humidity threshold value 1 2 Parameter Humidity threshold value Options 0 100 This parameter sets a high threshold value humidity this threshold value can be changed as cha
28. object type of operating mode is 1bit and is used to activate night mode Receiving telegram 1 will activate night mode receiving telegram 0 will not activate night mode Receive telegram 1 activate night mode Receive telegram 0 not activate night mode 11 Active frost heat protection mode Setpoint temperature 1 bit C RW The communication object is visible when the object type of operating mode is 1bit and is used to activate the frost heat protection mode Receiving telegram 1 will activate the frost heat protection mode receiving telegram will not activate the frost heat protection mode Receive telegram 1 activate the frost heat protection mode Receive telegram 0 not activate the frost heat protection mode 12 Temperature operating mode Setpoint temperature 1 byte C RW switchover The communication object is visible when the object type of operating mode is 1bit and is used to switch to mode Different telegrams mean different operating modes as follows Auto comfortable 1 comfort mode 2 Standby mode 3 Night Mode 4 Frozen protection heat protection 5 255 Reserved do not use For example when an object receives a telegram 2 the thermostat panel will control the actuator according to the standby mode setting Communication object of operating mode switching has priority thermostat panel activates the operating mode accor
29. temperature sensor input 2 Technical Parameter Size Structure chart and Wire Map Temperature control panel use standard 86 wall mounted installation through the bust terminal connected to EIB KNX system 2 1 Technical Parameter Power supply EIB KNX voltage EIB KNX current drain EIB KNX power consumption Auxiliary power supply voltage power consumption Input 3 way key channel One way NTC temperature input Key scan voltage Key scan current Operating and instruction Red LED and buttons Green LED flashing Connection input EIB KNX 21 30V DC Max 12mA 360 20 30V DC lt 2W Individually configurable buttons Configurable NTC characteristics 3 3V DC Max 0 5mA Distribution of physical address Indicates device working properly Connecting five lines about 30cm long up to 10m Bus connection terminal diameter 5 www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel 0 8mm Temperature range operating 5 C 45 C storage 25 55 C transportation 25 C 70 Environmental conditions humidity 8096 No condensation CE Standard Certification installation standard 86 wall mounted installation size 86 86mm weight temperature Measuring range 40 C 80 C Resolution 0 1 C Accuracy 0 5 C humidity Measuring range 0 100 RH Resolution 0 0196 Accuracy 3 RH 2 2 Size Struc
30. the object logic 1 2 block receives telegram 1 the object logic 1 2 1bit 1byte output sends the same telegram as with telegram 1 Parameter Behaviour when releasing the lock Options Do not send Update This parameter sets the action when the logic is started again Select do not send when the object humidity threshold value1 2 block receives the telegram O if the threshold value changes 1bit 1byte output humidity value will be sent immediately but not vice versa If selecting update when logic 1 2 bock receives telegram O no matter whether the logic results change the value of logic 1 2 1bit 1byte output will be sent immediately 4 10 parameter window Timer Page 1 and Timer Page 2 Parameter window of Timer Page 1 and Timer Page 2 is shown in Figure 4 10 here is to set the relevant parameters of timer Thermostat panel can set schedule to automatically adjust the work mode A thermostat panel has 16 timing times and each timing time has its own work mode If the current time is equal to a timing time it will automatically switch to the corresponding work mode and send the corresponding data 53 www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS 59 KNX EIB Temperature Control Panel Device 1 1 5 Thermostat General Settings 1 enable Measurement Settings i Heating setpoint Week Monday Heating control
31. threshold value is enabled When select yes the following parameters can be seen Parameter Behaviour when setting the lock Options Do not send telegram Send the same telegram as lower threshold Send the same telegram as upper threshold This parameter sets the action when the threshold value is banned Select do not send no action Select Send the same telegram as lower threshold when the object humidity threshold value1 2 block receives telegram 1 the object 1bit 1byte output humidity sends the same telegram as lower threshold Select Send the same telegram as upper threshold when the object humidity threshold value1 2 block receives telegram 1 the object 1bit 1byte output humidity sends the same telegram as higher threshold This parameter can be seen in use block of the humidity threshold output if User selects yes Parameter Behaviour when releasing the lock Options Do not send Update This parameter sets the action when the threshold value is started again Select do not send when the object humidity threshold value1 2 block receives the telegram O if the threshold value changes 1bit 1byte output humidity value will be sent immediately but not vice versa If the current humidity is between high and low thresholds no telegram will be sent if loop sending is enabled the previous telegram will be loop sent Select update when the object humidity threshold value1 2 block receiv
32. to the bus when power is 58 www video star com cn maketing a video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel restored this parameter is visible when it does not distinguish between long and short operation If selecting yes it will send the current switch value of Switch X to the bus when power is restored but only when the parameter Reaction on closing the contact rising edge opening the contact falling edge all options don t select Toggle will it send the current switch value of Switch X to the bus if any of the options selects Toggle no value will be sent in the bus If the current operation is No reaction or Stop cyclic transmission no value will be sent Parameter Cyclical send Tele Tele Switch Options no always if switch off if switch on Here is to set whether to cyclically send the current switch value of Switch X to the bus Parameter option Always is selected regardless of the object Switch X in the current switch value is 0 or 1 the switch will send cyclically the current value to the bus Parameter option is set as If switch off or If switch on Only when the current value is the same as the option the value will be cyclically sent Parameter Interval of Tele cyclic send Base Factor Base Options 0 5s 1s 1h Factor Options 1 255 Here set the interval of cyclically sending telegrams the paramete
33. two position control 1 bit on off Send telegrams two position control 1byte 0 100 Send telegrams continuous PI control 0 100 Send telegrams switching PI control on off Send telegrams switching PI control on off Send telegrams fan coil control 0 100 21 fan automatic or fan manual Fan 1 bit C R T This communication object is used to switch over fan between auto and manual when parameter Switchover fan between auto and manual selects object Automatic ON OFF Send the telegram 1 fan automatic Send the telegram 0 fan manual when parameter Switchover fan between auto and manual selects object Manual ON OFF 74 a a a 9 c M 1 www video star com cn maketing a video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel Send the telegram 1 fan manual Send the telegram 0 fan automatic 22 Fan manual stage Fan 1 byte C R T This communication object is used to send the control value of fan manual to change the wind speed 23 Lock temperature control Temperature control 1bit C R W This communication object is used to disable enable temperature control including disable enable basic heating cooling control and additional heating cooling control When receiving telegram 1 the object Basic heating cooling control value and object addit
34. when someone at home Stand by mode is applied to the daytime when no one at home for saving the energy Night mode is applied for the night time when someone at home Frost Heating protecting mode is applied for the long time going out in order to prevent the devices from damaging by the highest or lowest temperature 24 n H www video star com cn maketing a video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel Parameter of Object type for operating mode switchover Options 1bit 1byte This Parameter is use for giving a definition of object type when switching mode room s temperature work patterns When choosing 1bit you can find the type of Active frost heating protection mode Active night mode and Active comfort mode These types can switch the room temperature controller into different work patterns The work pattern will switch to stand by mode when the value of all these three type is 0 Choosing 1bit the priority of every work patterns are as follows Frost heating protection Comfort night standby forcing Window Presenc 1bit switching Work pattern switchover status e to be object Comfort Standby Night Frost heating activated protection 01 X X X X X X Comfort 02 X X X X X X Standby 03 X X X X X x Night 04 x X
35. won t be sent It only can be sent to the bus after reading by setpoint temperature When choosing on change the temperature setpoint will be sent to the bus after the changing of temperature setpoint When choosing cyclically the temperature setpoint will be sent to the bus recurrently Once the temperature setpoint are changed it will be sent one week later When choosing change and cyclically the temperature setpoint will be sent to the bus recurrently Once the temperature setpoint are changed it will be sent immediately Cycling time starts over Parameter of Period of sending setpoint Options 5s 26 D ee www video star com cn maketing a video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel 10s 2h Parameter of Send setpoint is use for setting the interval of sending a temperature setpoint recurrently from its sensor to bus The interval setting can be found in choosing cyclically or on change and cyclically in the Parameter of Send setpoint Parameter of switchover between heating and cooling Options automate switchover by dead zone manual switchover by object This parameter is use for setting the switching ways of Heating cooling function When choosing automate switchover by dead zone it will switch to heating cooling automatically according to the dead zone It will switch to the cooling syste
36. 0 100 0 to close the valve 100 to open the valve if it is between 0 and 100 the actuator will adjust the controlling output according to the duty cycle of control target value For example assuming the cycle is 10mins set in the switch actuator the controlling value is 60 then the valve will be opened for 6mins closed for 4mins all cycles in this way Temperature control panel according to temperature conditions ratio range and integration time calculate the control value every 30 seconds and output the control value based on the output conditions Note If no cycle parameter is set in the switch actuator the actuator will not cyclically transmit the controlling value according to its duty cycle In this case this application of the panel may not be suitable for controlling switch actuator and applies only to actuators which could receive 1byte type controlling value If you select Switching PI Control the controlled object sends switch value and directly controls the output of actuator by the switch command which means the controlled object directly switches solenoid valve The period of cyclical transmitting of switch value can be set through parameter and the temperature control panel will send switch value according to the duty cycle of control target value For example assuming the cycle is 10mins set in the temperature control panel the controlling value is 34 o C A
37. 8465 GVS K BUS KNX EIB Temperature Control Panel Higher than high threshold value Action 1 Lower than low threshold value Low threshold value lt temperature h Action 2 4 8 1 Temperature threshold value Device 1 1 5 Thermostat General Settings Actual temperature or humidity High threshold value Low threshold value Measurement Settings Temperature threshold value 250 E in 0 1 Celsius Heating setpoint i Heating control i Negative hysteresis temperature 10 Fan Coil Heating mun 0 1 Celsius Fan Coil General If temperature is lower than threshold send following telegram once Threshold value i value Temperature threshold value 1 i Logic 1bit telegram value 0 1 Logic Timer Page 1 1byte telegram value 0 255 0 Timer Page 2 Been Pushbutton Interface If temperature is upper than threshold send following telegram once value Logic 1bit telegram value 0 1 1 x 1byte telegram value 0 255 255 S Cycle time for temperature threshold 10 S qo value in min if used Use block of the temperature threshold i output Figure 4 8 1 Parameter window Temperature threshold value 1 2 Parameter Temperature threshold value x0 1 C Options 0 500 This parameter sets a high threshold value of temperature this threshold value can be changed as change temperature threshold value1
38. 86 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel internal sensor and external sensor This parameter defines the type of temperature sensor If selecting internal sensor the temperature measured by the temperature sensor panel will be read or send to the bus by the Actual temperature so that controller will control according to the temperature If selecting external sensor the temperature will be measured by an external temperature sensor temperature control panel receives the temperature send from the bus temperature sensor by Input external temperature Temperature control panel will control according to this temperature When you select this option after power up the panel began to control the temperature only when the temperature control panel received the temperature from an external sensor Once selecting internal sensor and external sensor the local sensor and external temperature sensor will be used simultaneously this sets suit for a large area to temperature control such as a lobby where using many sensors at the same time temperature sensors B get the temperature from sensor A then get the proportion of the sum itself and then it will control the temperature based on the results of summation or transmits the result to the summing sensor C or give the sum to sensor C which will control temperature after receives the temperature and got the proportion of the sum itself too The proporti
39. 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel Parameter Setpoint heat protection at cooling 0 1Celsius Options 0 500 Here it sets the temperature setpoint of cooling function under heat protection mode This temperature setpoint is set independently and is not affected by the comfort mode Parameter Minimum distance between heating setpoint and cooling setpoint 0 1Celsius Options 0 100 This parameter defines the minimum distance between of heating and cooling function This parameter determines the comfort cooling temperature setpoint Comfort temperature setpoint under cooling mode comfort temperature setpoint under heating mode minimum distance For example if the minimum distance is 3 C comfort temperature setpoint under heating mode is 22 C then the comfort temperature setpoint under cooling mode is 25 4 5 Parameter setting interface Heating Cooling Control Heating Cooling Control parameter setting interface is as shown in Figure 4 5 where related parameters of temperature control is set The temperature control panel provides a variety of controlling types such as continuous control switching control 2 position control and Fan coil control used for controlling different types of temperature controllers Under normal circumstances we can control the fan coil actuator by temperature control panel to switch on off the electric valve and adjust the speed
40. C the floor temperature cyclically sending refers to parameter y 5 period of sending temperature 5 7 Air Condition Communication Objects 63 IR command number Temperature control 1Byte T 2 64 Air condition on off Temperature control 1bit C p 65 Mode heating cooling Temperature control 1bit C TI 82 66 Switch over high medium speed Temperature control 1bit C ss 22 67 switch to low speed Temperature control 1 bit T 82 68 setpoint for heating 16 17 Setpoint temperature 1bit C Ux nz 69 setpoint for heating 18 19 Setpoint temperature 1 bit C T x 70 setpoint for heating 20 21 Setpoint temperature 1 bit C 22 71 setpoint for heating 22 23 Setpoint temperature 1 bit C 22 72 setpoint for heating 24 25 Setpoint temperature 1 bit T 22 73 setpoint for heating 26 27 Setpoint temperature 1 bit C T 82 74 setpoint for heating 28 29 Setpoint temperature 1 bit C T 75 setpoint for heating 30 31 Setpoint temperature 1 bit C To ost 22 76 setpoint for cooling 16 17 Setpoint temperature 1 bit C p 22 77 setpoint for cooling 18 19 Setpoint temperature 1bit 22 78 setpoint for cooling 20 21 Setpoint temperature 1bit C T z2 79 setpoint for cooling 22 23 Setpoint temperature 1 bit C T 2 2 80 setpoint for cooling 24 25 Setpoint temperature 1 bit C qs 22 81 setpoint for cooling 26 27 Setpoint temperature 1bit C T 2 82 set
41. H C Disable 1 bit C WE m Figure 5 6 3 shutter communication object Number Communication object name Functions Data Types Attribute 53 56 59 Output shutter UP DOWN CH A B C Blind 1bit 1byte C T The communication object by sending commands to the bus moves up down curtains The communication object can send 1bit or 1bytecommands by Function of switchover blinds roller shutter choose curtain type by Object type select the telegram type When the communication object is 1bit send 1 to move downward send 0 to move upward When the telegram is 1 byte telegrams are sent based on the value set by the user 54 57 60 Stop lamella adj CH A B C Blind 1bit 1 byte C T The communication objects by sending commands to the bus stop adjust curtains The communication object can send 1bit or 1bytecommands by Function of switchover blinds roller shutter choose curtain type by Object type select the telegram type When the communication object is 1bit send 1 to stop or move downward send 0 to stop or move upward When the telegram is 1 byte telegrams are sent based on the value set by the user 55 58 61 Disable input 1 2 3 CH A B C Disable 1bit When the channel function is enabled the communication object is activated which is used to disable enable channel function When this communication object receives a logic value of 0 the channel function is enab
42. If select Dimming and Switching in Dimming functionality the parameter is visible Here is to set when the contact input is long operation operations performed on dimmable devices relative dimming brighten or darken the input is disconnected stop dimming If select brighter darker the contact input is long operation both the brighter and darker can be performed but at first is brighter then the later operation is the inverse of the former operation Parameter Step size for dimming Options 100 50 1 56 This parameter sets the brightness range percentage of cyclically sending dimming telegrams Parameter Transmission dimming stop telegram Options yes no It sets whether to send stop dimming telegram when the dimming stops Parameter Cyclical transmission of dimming telegrams Options disable enable It sets whether to cyclically send dimming telegram Parameter Time between two dimming telegrams in 0 1s Options 3 250 61 m U T RSS J Ha ss f ee www video star com cn maketing a video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel If selecting enable in the parameter Cyclical transmission of dimming telegrams then the parameter is visible Here is to set the interval of cyclical transmission of dimming telegrams In parameter window Input 1 2 3 select
43. Parameter input X X21 6 Options do not use temperature threshold value 1 temperature threshold value 1 inverted temperature threshold value 2 temperature threshold value 2 inverted humidity threshold value1 50 a C J G C www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel humidity threshold value1 inverted humidity threshold value 2 humidity threshold value 2 inverted communication object input A communication object input A inverted communication object input B communication object input B Here is to set the input value of logic operations logic input value of logic 1 is input1 input3 logic input value of logic2 is input4 input5 If one of the logic input isn t used the logic input and its logic operations should be ignored If in a certain threshold state no telegrams are sent then in this case logic input is not involved in the logic operation equivalent do not use and if the threshold function is disabled and in this case logic input is also equivalent to not use If the object value of the threshold value is in an indeterminate state logic input doesn t participate in logic operations If temperature and humidity testing fail the relevant logic inputs are not involved in logical operations Parameter The logic function type between i
44. TURE 1 11 3 5 THRESHOLD 12 3 6 LOGICAL 12 3 7 BAN ENABLE TEMPERATURE AND HUMIDITY CONTROL FUNCTION THE THRESHOLD VALUE AND THE LOGICAL ui epo X 13 3 8 TIMING 13 3 9 BINARY INPUT AND TEMPERATURE SENSOR INPUT 13 4 ETS SYSTEM PARAMETER SETUP 5 85 13 4 1 13 4 2 PARAMETER SETTINGS WINDOW 13 4 3 PARAMETER SETTING INTERFACE MEASUREMENT SETTINGS 18 4 4 PARAMETER SETTING INTERFACE HEATING COOLING SETPOINT
45. X X X X Frost heating protection 00 1 X X X X X Frost heating protection 00 0 1 X X X x Comfort 00 0 0 1 0 0 0 Comfort 00 0 0 0 1 0 0 Standby 00 0 0 0 0 1 0 Night 00 0 0 0 0 0 1 Frost heating protection When choosing 1byte you can find the type of Temperature operating mode switchover Under this circumstances different Room temperature controller can be switched into different work patterns by setting every value of type Values to the work pattern is as follows 0 Automation comfort mode 1 Comfort mode 2 Stand by mode 3 Night mode 4 Frost Heating protecting mode 5 Reserved 25 L UE www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel forcing switchover Window status Presence object Operating mode Work pattern switchover to be activated 01 X X X Comfort 02 x x x Standby 03 x x X Night 04 X X X Frost heating protection 00 1 X X Frost heating protection 00 0 1 X Comfort 00 0 0 01 Comfort 00 0 0 02 Standby 00 0 0 03 Night 00 0 0 04 Frost heating protection Parameter of Send setpoint Options do not send on change cyclically on change and cyclically In the Parameter of Send setpoint the ways of sending the temperature setpoint be set When choosing do not send the temperature setpoint
46. aches the time to return to the automatic mode the communication object 21 sends packets to return to automatic speed mode Parameter Threshold value in for fan speed 3 at heating Parameter Threshold value in for fan speed 2 at heating Parameter Threshold value in for fan speed 1 at heating Options 0 100 Threshold value in for fan speed 3 at heating to set packet value that communication object 22 Fan manual stage outputs when the fan coil is switched to high speed 3 Threshold value in for fan speed 2 at heating to set packet value that communication object 22 Fan manual stage outputs when the fan coil is switched to high speed 2 Threshold value in for fan speed 1 at heating to set packet value that communication object 22 Fan manual stage outputs when the fan coil is switched to high speed 1 Parameter Fan speed for switching to comfort mode Parameter Fan speed for switching to standby mode Parameter Fan speed for switching to night mode Parameter Fan speed for switching to frost heat protection mode 41 www video star com cn maketing a video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel Options auto 1 2 3 no change This parameter is to set wind sharing speed of fain coil in different operating modes Each mode can be set its corresponding wind speed When switching to a working mode the communication object sends the cont
47. an not be switched only display comfort mode The Set Key is only used to switch heating and cooling General Settings 3P Measurement Settings i Setpoint 25 Threshold value i A i Send setpoint on change x Logic Pushbutton Interface Object type for controlling air conditio 1 byte Input 1 Input 2 Command for air condition on 1 Input 3 i Input 4 i Command for air condition off 2 Air Condition i m Command for heating mode 3 lt Command for cooling mode 4 Command for fan speed high 5 Command for fan speed medium 6 gt Command for fan speed low Ji Command for fan speed auto stop 8 E i Command for setpoint 16 Celsius 9 for cooling ic df int 17 Celsi Be Command for setpoint elsius 10 i for cooling eeaeee WWW a Command for setpoint 18 Celsius 11 i for cooling Hax 5020 5 555405 GVS KBUS KNX EIB Temperature Control Panel Figure 4 12 parameter window Air Condition Parameter Setpoint Options 16 32 This option is to set the setpoint temperature the air conditioner It is used to achieve thermostatic control Parameter Send setpoint Options Do not send on change cyclically on change and cyclically This option is set to send the way of the set temperature do not send means do not send commands on change means that there is a change on the sending cyclically means cyclically Send on change
48. arameter values of 1 integral time The integral 36 ree M Pu 22 22 4 www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel time must be appropriately set If it is too large it will make adjustment very slow and oscillation unobvious If it is too small it will cause adjustment very fast and oscillation 0 means not using integral term Parameters invert control value Options Normal Inverse Here it sets the method of control object sending control value normal transmit or negative transmit to suit control value to the type of valve If you select normal the control object Heating Cooling control value will send normal control values If you select Inverse control object Heating Cooling control value will send negative control value If control value is off or 096 negative control value will be on or 100 If control value is on or 100 negative control is off or 0 If control value is 60 then negative control value is 40 Parameters minimum control value Options 0 30 This parameter is used to set the minimum allowable value of the PI control value When control value calculated from PI is less than the set minimum value temperature control panel will send the minimum value If you use a temperature control panel to control an actuator using PWM Pulse Width
49. ating cooling setpoint Temperature display Celsius C Heating control Fan Coil Heating i Backlight in no operation in day 96 60 Cooling control i Fan Coil General i Backlight in operation in day 96 100 Threshold value i es Logic Backlight in no operation at night 96 50 Timer Page 1 2 i Backlight in operation at night 96 90 Pushbutton Interface i ca i Time of backlight delay s 5 i Switch day night mode automatically no Time mode 24H Send current time Do not send Warning tone enable Control device HVAC i Controller anction when display off Protect mode Temperature control system heating and cooling Heating and cooling share object no Figure 4 2 General settings Parameter Settings interface Parameter Send In operation object Options No Send value 0 cyclically Send value 1 cyclically BR Send In operation object Wy Send value 0 cyclically Send value 1 cyclically These parameter set the temperature control panel cycle and send a message 1 or 0 to the bus which shows that the panel is working well If fail it will stop sending the message 1 or 0 Options for No do not send Options for the value 0 cyclically send or send the value 1 cyclically temperature control panel will send a message 0 or 1 according to the set period of time so the object in operation and Transmi
50. bit C w 52 56 Switch 1 input 2 CH B Switch 1 bit cs 57 Switch 2 input 2 CH B switch long 1 bit C T 2 58 Disable input 2 CH B Disable 1 bit 82 59 Switch 1 input 3 CH C Switch 1 bit C T 60 Switch 2 input 3 CH C switch long 1 bit C cs 61 Disable input 3 CH C Disable 1 bit C w 5 6 1 Switch Communication Object 79 www video star com cn maketing a video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel Number Communication object name Functions Data Types Attribute 53 56 59 Switch 1 input 1 2 3 CH A Switch 1bit C W T When CH A Switch is enabled this communication object is visible through short push according to the parameters settings performs the corresponding actions e g ON OFF TOGGLE etc When the telegram is 1 ON When the telegram is 0 OFF 54 57 60 Switch 2 input 1 2 3 CH A Switch long 1 bit C T When CH A Switch is enabled this communication object is visible through long push according to the parameters settings performs the corresponding actions e g ON OFF TOGGLE etc When the telegram is 1 ON When the telegram is 0 OFF 55 58 61 Disable input 1 2 3 CH A Disable 1bit C W When the channel function is enabled the communication object is act
51. can be achieved When the final logic result is 1 user can specify the values of two different types of transmission on the bus when the final result is 0 user may further specify two different types of transmission on the bus Each time the temperature control panel detects the input of new logical values it will re do a logic operation while updating the final result of logic operation Logic functions can also set ways of sending the value of logical objects user can disable enable logic functions Device 1 1 5 Thermostat General Settings i do not Measurement Settings itt Heating setpoint input 2 do not use Heating control Fan Coil Heating input 3 do not use Fan Coil General The logic function type between AND input 1 and input 2 Temperature threshold value 1 ETE NETUS Humidity threshold value 1 The logic function type between AND M Logic input 3 and result of input 1 2 logici If logic result 0 send following telegram once Timer Page 1 Timer Page 2 1bit telegram value 0 1 Pushbutton Interface 1byte telegram value 0 255 0 If logic result 1 send following telegram once 1bit telegram value 0 1 215 1byte telegram value 0 255 255 Cz Cycle time for logic in min if used 10 Cz Use block of the logic 1 output no Figure 4 9 2 Parameter window Logic 1 2
52. can send two object types the value of the object is set the following parameters logic1bit 1byte telegram value Parameter logic 1 bit 1byte telegram value Options Logic 1bit 0 1 1byte 0 255 This parameter is used to specify the telegram value that object 1bit 1byte output humidity sends when the current humidity is below the low threshold and above the high threshold After a bus reset or programming if the current humidity is between the low threshold and the high threshold the object does not send telegram to the bus Parameter Cycle time for humidity threshold value min if used Options 1 255 This parameter is used to set the object 1bit 1byte output humidity cycle time on the bus to send the value of the interval only when the parameter If humidity is lower upper than threshold value set loop send it to use Parameter use block of the humidity threshold output Options yes no This parameter sets whether to enable the threshold value if enabled the object humidity 47 mau C M EXICG a __ _ www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel threshold value1 2 block is visible when the object receives telegram 1 threshold value is disabled when the object receives telegram O the
53. change of control value the object heating cooling control value sends current control value to the bus 0 means not using this parameter Parameters period of sending control value 1 255 min Options 0 255 This parameter sets time interval of control value cyclically send control value to the bus 0 means not using this parameter Each time it sends a control value to the bus cyclical sending time will be re timing Note the cycle time here should corresponds to the monitoring time of temperature control actuator therefore the time of cyclical sending telegram should be half or less of the monitoring time of temperature control actuator to prevent that temperature control actuators fail to monitor because of omission of cyclical telegram and mistakenly judge temperature control panel breaks down Parameter PWM cycle time 1 255 min Options 1 255 This parameter is visible only when the control type is switching control and is used to set the period of control object cyclical sending switch value Temperature control panel sends switch value according to the duty cycle of control value For example if the period is set to be 10mins control value is 80 temperature control panel will send an open packet every 8 min and send an closed packet every 2 min and continue to cycle this way If the control value changes the duty cycle of temperature control panel sending open close telegram will change while the pe
54. cn Tel 8620 39338986 Fax 8620 39338465 GVS K BUS KNX EIB Temperature Control Panel backlit screen Received telegram values 1 the backlight brightness of backlit screen in daytime 0 the backlight brightness of backlit screen at night This communication object is used to receive telegram value from the bus to switch the backlight brightness of 5 2 Heating cooling control Communication Object e 2 Input external temperature Temperature 2Bye C R W nj 3 Actual temperature Temperature 2Bye C R 4 rel humidity Humidity a 2 5 Operating mode forcing object Setpoint temperature iBye C R W z2 6 Windows status Setpoint temperature 1 bit COR M ES 22 7 Presence object Setpoint temperature 1 bit C cR o 2 8 Active comfort mode Setpoint temperature 1 bit ee ea 22 9 Active standby mode Setpoint temperature 1 bit C SR Wo 5 10 Active night mode Setpoint temperature 1 bit CR we 82 11 Active frost heat protection mode Setpoint temperature 1 bit C cR oW Be 13 Heating cooling switchover Temperature control 1 bit COR WO u 2 14 Basic comfort temperature at heating Setpoint temperature 2Byte C R W 82 15 Heating setpoint Setpoint temperature 2Bye C R T 82 16 Cooling setpoint Setpoint temperature 2Byte C R 22 17 Output HVAC status Temperature control 1Byte T a2 18 Output RHCC status Temperature con
55. control 2 point control and fan coil control different types of control is suitable for different types of temperature controller Continuous control Continuous control s control values is calculated by the actual temperature and set temperature and then control the opening of continuous valve attain the comfortable room temperature state For example when the current control values is 5096 of the largest the valve position will open to 5096 according to the control values If the output control values is the maximum the valve is fully open Continuous control can realize the on off and stop three step operations specific action is shown in the figure below Control value Valve position 100 26 T Tirne Continuous control can realize the most precise temperature adjustment without quite big overshoot At the same time the frequency of the positioning valve actuator can maintain at a low level Continuous control can also control the rise and fall valve of the fan coil or KNX valve actuator PWM control 11 au T o c nay www video star com cn maketing a video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel PWM pulse width modulation control s values is calculated according to the actual temperature and set temperature and then calculate the on and
56. d by multiple triggering when the contact repeatedly jitter which is the minimum effective time of contact input Parameter Limit number of Tele Options yes No This parameter sets limits on the number of binary input telegrams sent to the main bus in order to reduce the burden of bus If selecting Yes the parameter Max Number Tele Within a period is visible Parameter Max Number Tele Within a period Options 30 60 100 127 This parameter sets the number of telegrams can be sent in a maximum of 17 seconds Bus voltage is restored the device initialization is complete the timer starts and starts counting telegrams once the maximum allowed number of telegrams sent once reached then no telegrams will be sent to the bus until the end of 17 seconds After the end of the 17 seconds the timer re starts and the telegram restarts to count Parameter Function of input 1 Options No function Switch Switch Dimming Shutter control Scene In parameter window Input 1 2 3 select Switch in Function of input 1 2 3 seen in Figure 4 11 2 57 a a ee ee eel www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel Device 1 1 5 Thermostat General Settings i Function of input 1 Switch Measurement Settings i Reaction on closing the contact OFF x Heating control Rising edge switc
57. d to select whether the heating and cooling control value share a communication object to accommodate two or four control system controls 4 3 parameter setting interface Measurement Settings Measurement Settings parameter setting interface as shown in Figure 4 3 where the main set some general parameters to measure temperature and humidity Device 1 1 5 CHTC 86 01 1 11 General Settings Temperature sensor internal sensor Measurement Settings PH Internal temperature correction 0 Cooling control in 0 1Celsius Fan Coil General Threshold value Send temperature at variation of 03 Celsius Logic i Timer Page 1 i Period of sending temperature 2 min 2 Pushbutton Interface Enalbe display outdoor temprature enable M Input 1 i nii P Indoor and outdoor temperature switch 10 2 d k time second Input 3 Input 4 i Humidity correction in 96 0 Send rel humidity at variation of 96 1 Period of sending humidity 2 Figure 4 3 Measurement Settings parameter setting interface Parameter Temperature sensor Options internal sensor external sensor 18 mEI HR EUcG C n Zfnd n o www video star com cn maketing a video star com cn Tel 8620 393389
58. ding to the priority of a communication object of operating mode More information is seen in 4 4 Object type for operating mode switchover 13 Heating cooling switchover Temperature control 1bit R W The communication object is for heating cooling switchover Receiving telegram 1 will activate heating receiving telegram 0 will activate cooling 72 pmRR SS M s c J A T se www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel Receiving telegram 1 heating Receiving telegram 0 cooling 14 Basic comfort temperature at Setpoint temperature 2byte C R W heating This object is mainly used to change the setpoint value of temperature in comfort mode and after the change a new value will be saved when the bus is powered off Telegram 0 50 C If the first page parameter Temperature control system selects heating and cooling this object is mainly used to change the comfort temperature value of heating the comfort temperature value of cooling is determined by the comfort temperature value of dead zone and heating More information is seen in 4 4 switchover between heating and cooling 15 Heating setpoint Setpoint temperature 2 byte C R T The comm
59. e Parameter Command for fan speed high Parameter Command for fan speed medium Parameter Command for fan speed low Parameter Command for fan speed auto stop Options 1 64 These parameters are used to set the command value of switching speed velocity When parameter Object type for controlling air condition is selected 1byte it is visible Parameter Command for setpoint 16 31Celsius Options 1 64 These parameters are to adjust the command value of set temperature When parameter Object type for controlling air condition is selected 1byte it is visible Auto on time Parameter Hour Options 0 23 Parameter Minute Options 0 59 68 p T S A e c C o G p r 5c0 c g www video star com cn maketing a video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel This parameter is to set the ON time of air conditioner Long Press the timer button to modify the timing value and its timing number is 1 Auto off time Parameter Hour Options 0 23 Parameter Minute Options 0 59 This parameter is to set the OFF time of air conditioner Long Press the timer button to modify the timing value and its timing number is 2 5 Communication Object Description Communication objects are media for devices on the bus to communicate with other devices a
60. e sensor for RTC Measurement Settings i Lead i Resistor of external temperature sensor 33K Heating control i Fan Coil Heating B value of external temperature sensor 3950 Fan Coil General Threshold value Temperature threshold value 1 Humidity threshold value 1 Logic logic 1 Timer Page 1 Timer Page 2 Pushbutton Interface Input 1 Input 2 Input 3 Input 4 Figure 4 11 6 parameter window Input 4 Parameter Function of input 4 Options No function external temperature sensor for RTC temperature limiter underfloor heating If temperature sensor inputs is used as an external temperature sensor of thermostat panel it should be connected an external NTC thermistor but also selects external sensor or internal sensor and external sensor for Temperature sensor in Measurement Settings Note if temperature sensor input is used as an external temperature sensor the communication object of external temperature on 64 pma ZE X XI E _ _ www video star com cn maketing a video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel the bus into the external temperature is invalid Parameter Resistor of external temperature sensor Options 1K 5K 200K This parameter sets the resistance value of the external temperature sensor thermist
61. er 0 63 In parameter Number of scene scene number is 1 64 and the communication object Number of light scene sends scene number 0 63 E g in parameter Number of scene scene number is 1 and the communication object Number of light scene sends scene number 0 55 58 61 Disable input 1 2 3 CH A B C Disable 1 bit When the channel function is enabled the communication object is activated which is used to disable enable channel function When this communication object receives a logic value of 0 the channel function is enabled receives 1 disabled When the channel function is disabled control telegrams sent by all objects are invalid When the bus power is restored channel function is enabled by default 5 6 5 Temperature limiter underfloor heating Communication Object 62 Floor temperature CH D Temperature 2Bye C R T Figure 5 6 5 NTC communication object Number Communication object name Functions Data types Attribute 54 Floor temperature External temperature sensor 2 byte C T 82 EE d M www video star com cn maketing a video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS X Bus9 KNX EIB Temperature Control Panel This communication object is used to send the current floor temperature Floor temperature sending variation refers to arameter Send temperature at variation of
62. er sets the action when the threshold value is banned Select do not send no action Select Send the same telegram as lower threshold when the object temperature threshold value1 2 block receives telegram 1 the object 1bit 1byte output temperature sends the same telegram as lower threshold Select Send the same telegram as upper threshold when the object temperature threshold value1 2 block receives telegram 1 the object 1bit 1byte output temperature sends the same telegram as upper threshold This parameter can be seen in use block of the temperature threshold output if User selects yes Parameter Behaviour when releasing the lock Options Do not send Update This parameter sets the action when the threshold value is started again Select do not send when the object temperature threshold value1 2 block receives the telegram 0 if the threshold value changes 1bit 1byte output temperature value will be sent immediately but not vice versa If the current temperature is between high and low thresholds no telegram will be sent if loop sending is enabled the previous telegram will be loop sent Select update when the object temperature threshold value1 2 block receives telegram O the object 1bit 1byte output temperature updates according to the threshold range of the current temperature no matter whether the object value changes the telegram is sent If the current 45 www video star com cn
63. er sets the data value that is sent to the bus 4 11 Parameter window Pushbutton Interface Pushbutton Interface has three binary inputs and a temperature sensor input three binary inputs can be set to switch dimming curtains and other functions Temperature sensor inputs can be connected an external NTC thermistor as an external temperature sensor of thermostat panel or as a temperature limiter of underfloor heating to stop heating when the heating temperature is higher than the limit Device 1 1 5 Thermostat General Settings Pushbutton Interface Function enable x Measurement Settings Heating setpoint Debounce time 50ms B Heating control Fan Coil Heating i Limit number of Tele Yes Fan Coil General i Threshold value Telegrams per 17 senconds 127 Temperature threshold value 1 Humidity threshold value 1 Logic logic 1 Timer Page 1 Timer Page 2 Pushbutton Interface Input 1 Input 2 Input 3 Input 4 56 T TP O P ICO O Ff O 1 www video star com cn maketing a video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel Figure 4 11 1 Parameter window Pushbutton Interface Parameter Debounce Time Options 10ms 20ms 150ms Debounce time set here to prevent unnecessary repeatedly operations cause
64. erature 2byte C R W This communication object would display when parameter Setpoint adjustment Selects absolute adjustment it is used to modify the night mode temperature at cooling 91 Setpoint heat protection Setpoint temperature 2byte C R W This communication object would display when parameter Setpoint adjustment Selects absolute adjustment it is used to modify the heat protection mode temperature at cooling 5 3 Threshold value communication object 2 27 Change temperature threshold value 1 Temperature threshold value 1 2Byte R W 2 28 1 bit output temperature Temperature threshold value 1 1 bit R 22 29 1 byte output temperature Temperature threshold value 1 1Bye C R T ej 30 Temperature threshold value 1 block Temperature threshold value 1 1 bit 22 31 Change temperature threshold value 2 Temperature threshold value 2 2Byte C R W 22 32 1 bit output temperature Temperature threshold value 2 1 bit C R 55 22 1 byte output temperature Temperature threshold value 2 1Bye C R K 2 34 Temperature threshold value 2 block Temperature threshold value 2 1 bit C R 2 35 Change humidity threshold value 1 Humidity threshold value 1 2Byte C R W 22 36 1 bit output humidity Humidity threshold value 1 1 bit C R T 22 37 1 byte output humidity Humidity threshold value 1 iBye C R
65. es telegram 0 the object 1bit 1byte output temperature updates according to the threshold range of the current humidity no matter whether the object value changes the telegram is sent If the current humidity is between the high and low thresholds the object value cannot be determined the telegram is not sent even though in case of sending cyclically This parameter can be seen in use block of the humidity threshold output if User selects yes 48 www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel 4 9 Parameter window Logic Parameter window Logic shows in Figure 4 9 1 Temperature controller provides two logic functions each function has three logic inputs each input can be freely set telegrams may be sent by the temperature threshold 1bit or humidity threshold 1bit or from the bus these telegrams can also be negated then participate in logic operations Device 1 1 5 Thermostat General Settings 5 Active logic function enable Measurement Settings Heating setpoint Logic 1 ae Heating control Fan Coil Heating Logic 2 disable Fan Coil General niue The value of communication object 0 input Temperature threshold value 1 after bus voltage recovery Humidity threshold value 1 Logic The value of communication object 0 1 mpat
66. except the comfort mode For the option of absolute adjustment the temperature setpoint of comfort mode stand by mode night mode protecting mode has its independent temperature setpoint which is not affected by the temperature setpoint of comfort mode The parameter as below is use for setting relative adjusting way on temperature setpoint It can be found if you choose the relative adjustment from the Setpoint adjustment Parameter of Basic comfort setpoint at heating in 0 1Celsius Options 0 500 The comfort temperature setpoint can be set here under the heating function All the temperature setpoint is referred to the basic comfortable temperature setpoint of heating function Temperature setpoint for all modes changes with the basic comfortable temperature setpoint of heating function The setpoint can be set by bus and it will keep saving the new value after changing Parameter of Setpoint decrease for standby mode at heating in 0 1Celsius option 0 100 29 DG G R EEESIES ENMM M 9 H CQCOMM c IM n 4 uNQ M www video star com cn maketing a video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel Parameter of Setpoint decrease for standby mode at heating in 0 1Celsius is use for setting the reduction that decides the stand by mode s temperature setpoint which is changed w
67. h 1 Fan Coil Heating 2 i Reaction on opening the contact no action Fan Coil General Falling edge switch 1 Threshold value i Temperature threshold value 1 Reaction on closing the contact OFF M Humidity threshold value 1 Rising switch 2 Logic Reaction on opening the contact no action 1 i Falling edge switch 2 umer re i Send object value after voltage recovery 2 if YES not equal TOGGLE Pushbutton Interface i Input 1 i Cyclic send Tele Tele switch always iie Interval of Tele cyclic send 20s Input 3 Base 1 Input 4 i Interval of Tele cyclic send 20s Base 2 Factor 1 255 10 Figure 4 11 2 parameter window Scene Parameter Reaction on closing the contact rising edge switch 1 2 Parameter Reaction on opening the contact falling edge switch 1 2 Options No function off on toggle Here is to set the switch value that the object Switch X sent when performing the operation If selecting no action no actions will be performed If selecting toggle it will perform the inverse operation namely inverse the last value and send again such as before executing the On to operate inverted perform the Off operation Parameter Send object value after voltage recovery if yes not equal toggle Options yes No Here to set whether to send the current switch value of Switch X
68. he switch is operated via 1 byte communication object Input x scene The scene is sent Parameter storage function light scenes Options enable disable Here is to set whether to enable scene saving If select enable long press the switch will save the scene short press the switch will call scene the calling and saving of the scene are controlled by the 63 UE gP s a n ga poncmP MgQ www video star com cn maketing a video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel same 1byte communication object Parameter Long operation after Options 3 250 Scene save function is enabled this parameter can be seen here to set the time of the detection long press the switch Parameter window Input 4 is seen as Figure 4 11 6 Temperature sensor inputs can be connected an external NTC thermistor as an external temperature sensor of thermostat panel or as a temperature limiter of underfloor heating to stop heating when the heating temperature is higher than the limit Device 1 1 5 Thermostat General Settings i Function of input 4 external temperatur
69. hold or below the low threshold 1bit telegram be sent via this object to the bus specific telegrams be set by the parameter 1byte telegram value 0 255 30 34 Temperature threshold value 1 2 block Temperature threshold value 1 2 Ibit C RLW This communication object is used to disable or enable the function of the temperature threshold value Disabled and enabled actions can be set by the parameter Receive telegram 1 disable the temperature threshold value Receive telegram 0 enable the temperature threshold value 35 39 Change humidity threshold value 1 2 Humidity threshold value 1 2 2byte R W This communication object is used to change the humidity s high threshold value telegram range 0 100 36 40 1 bit output temperature Humidity threshold value 1 2 Ibit C R T When the humidity is higher than the current high threshold or below the low threshold Ibit telegram be sent via this object to the bus specific telegrams can be set the parameter logic 1bit telegram value 0 1 37 41 1 byte output humidity Humidity threshold value 1 2 Ibyte C RT When the humidity is higher than the current high threshold or below the low threshold Ibit telegram be sent via this object to the bus specific telegrams be set by the parameter 1 telegram value 0 255 38 42 Humidity threshold value 1 2 bl
70. in how to use it via practical using example 1 1 Product and function instruction Temperature control panel mainly used in building control systems and installed with EIB KNX bus and other devices together as a system It s connected directly to the terminal via the EIB bus no need of additional power supply Standard 86 wall mounted installation You can use the engineering design software ETS version above ETS3 with VD3 VD4 ETS files to allocate physical address and set up Parameter Main function summarized as below gt Capacitive touch buttons LCD display gt Selected internal and external temperature sensor gt Basic and additional heating and cooling temperature control function gt Relative and absolute room temperature adjustment function gt Variety of temperature control mode continuous PI control switching PI control and on off control www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K Bus 9 KNX EIB Temperature Control Panel gt gt gt gt gt Logical function gt With PI parameters self tuning and manual tuning two kinds of control modes Timing room temperature control switch mode and transmit data function Manual and automatic three speed fan control Temperature and humidity threshold function Three way binary input for controlling the switching dimming curtains and scenes one for external NTC thermistor
71. ing Parameter Control value type Options 1bit ON OFF 1byte 0 100 This parameter is visible only when the control type is Two position control and is used to set the type of control object If the option is 1bit the object Heating Cooling control value sends on and off If the option is 1byte the object Heating Cooling control value sends only 0 and 10096 4 6 Parameter setting interface Fan Coil General Fan Coil General parameter setting interface is as shown in Figure 4 6 Here it sets the general parameters of fan coil Device 1 1 5 Thermostat General Settings 5 Number of fan levels 3 levels x Measurement Settings Heating setpomt Switchover fan between auto and object Manual ON OFF Heating control manual Fan Coil Heating Fan Coil General mm Threshold value ww Logic Timer Page 1 Timer Page 2 Pushbutton Interface GVS KBUS KNX EIB Temperature Control Panel Figure 4 6 Fan Coil General Parameter Setting Interface Parameters Number of fan level Options 1 level 2 levels 3 levels This parameter is used to set the levels of wind speed The maximum wind speed does not exceed the levels Parameter Switchover fan between auto and manual Options object Automatic ON OFF object Manual ON OFF This parameter is used to set the automatic and manual switchover of wind speed When you select object Automatic ON OFF and switch to aut
72. ing is enabled timing mode switching and manually adjust the timing time can be achieved If the 16 timers has overlap time thermostat will send the front timer mode and data to the bus when regular time enabled users can long press the timer button to modify the regular time Parameter Week Options Monday Tuesday Wednesday Thursday Friday Saturday Sunday Monday Wednesday Thursday Friday Monday Friday Saturday Sunday Monday Sunday This parameter sets the date Users can set according to their needs Parameter Hour Options 0 23 This parameter is used to set time in hours Parameter Minute Options 0 59 This parameter is used to set time in minutes Parameter operating mode Options comfort mode standby mode night mode frost heat protection 55 www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel unchanged This parameter sets the room control mode when the set timing time reaches Parameter Reaction at regular time Options No reaction 1bit value 0 1 2bit value 0 3 4bit value 0 15 1byte value 0 255 2byte value 32768 32767 2byte value 0 65535 4byte value 0 4294967295 This parameter sets the data type thermostat panel sent to the bus when the set timing time reaches Options Output value Options 0 1 0 3 0 15 0 255 32768 32767 0 65535 0 4294967295 This paramet
73. ion and heating and time on the screen can be set by buttons Icon mode button mainly used to switch four kinds of room temperature control modes the iconsb ade ot mode night mode and the protection mode different models correspond to different setting from left to right are respectively the comfortable mode preparing temperature In addition the mode key can switch heating and refrigeration functions When the database is set to the heating and refrigeration both needed you can long press the button of manual Switchover by object to switch the heating and refrigeration which is on the Heating cooling setpoint parameter page s parameters Switchover between Heating and cooling Li Increasing key the key is mainly used to upward adjust current set temperature or time regularly When adjust the set temperature the increment is 0 5 when adjust the set time the increment is 1 E Reducing key the key is mainly used to downward adjust the current set temperature or time regularly When adjust the set temperature the reduction is 0 5 C when adjust the time the reduction is www video star com cn maketing a video star com cn Tel 8620 39338986 x 8620 39338465 GVS K Bus 9 KNX EIB Temperature Control Panel 1 EA Wind speed key the key is used to adjust the fan speed The icon E indicates the wind speed which is divided into four gears automatic transmission 1 2 and 3 transmission which can als
74. ional heating cooling control value stop sending control telegrams when receiving telegram 0 they update control value immediately Receive telegram 1 disable temperature control Receive telegram 0 enable temperature control Note Stop control telegrams is restricted by the minimum and maximum control value if there is a limit if the control values are negated stop control telegrams are negated too 26 Lock additional stage Temperature control 1bit This communication object is used to disable or enable additional heating cooling control When receiving telegram 1 the object additional heating cooling control value stop sending control telegrams when receiving telegram O it updates control value immediately Receive telegram 1 disable additional heating cooling control value Receive telegram 0 enable additional heating cooling control value Note Stop control telegrams is restricted by the minimum and maximum control value if there is a limit if the control values are negated stop control telegrams are negated too 84 Outdoor temperature Setpoint temperature 2byte C This communication object would display when parameter Enable display outdoor temperature Selects enable it 18 used to receive outdoor temperature from the bus 85 Heating standby setpoint Setpoint temperature 2byte C Thi
75. it2 flag of enabling night mode 1 enable 0 disable 73 T LL G en m i www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel flag of enabling frost heat protection mode 1 enable 0 disable Bit4 flag of banning temperature control 1 banned 0 enabled Bit5 flag of heating cooling O cooling 1 heating Bit6 flag of dead zone Select both heating and cooling control functions and when the current temperature is in the dead zone set 1 otherwise set 0 Bit7 flag of frost alarm When the actual temperature is below 5 set 1 otherwise set 0 This bit is only as alert signs has no effect on the temperature control 18 Output RHCC status Temperature control 2 byte C R T RHCC Status Report Bit no 0 error 1 alarm 0 normal 8 heating or cooling 0 cooling 1 heating 12 Dewpoint alarm 1 alarm 0 normal 13 frost alarm 1 alarm 0 normal 14 over heat cold alarm 1 alarm 0 normal 19 20 24 25 Basic heating cooling control value Temperature control 1bit byte C R T Additional heating cooling control value This communication object is used to send the control value of heating cooling to control actuator ON OFF and adjust the room temperature Send telegrams
76. ith the comfort temperature setpoint under the circumstance of heating function For example if setting the deduction of 3 C when the comfort temperature setpoint is 23 C the stand by mode s temperature setpoint will be 20 C Parameter of Setpoint decrease for night mode at heating in 0 1Celsius option 0 100 Parameter of Setpoint decrease for night mode at heating in 0 1Celsius is use for setting the reduction that decides the night mode s temperature setpoint which is changed with the comfort temperature setpoint under the circumstance of heating function For example if setting the deduction of 2 C when the comfort temperature setpoint is 23 C the stand by mode s temperature setpoint will be 21 C Parameter of Setpoint frost protection at heating in 0 1Celsius option 0 255 Parameter of Setpoint frost protection at heating in 0 1Celsius is use for setting the temperature setpoint of X Frost Heat protection mode The current temperature is not allow to be below the temperature setpoint of heating function in Frost Heat protection mode Otherwise the temperature control panel will send an order to the relative heating control of heating the room for avoiding too low temperature Parameter of positive dead zone between heating and cooling in 0 1Celsius option 0 100 Parameter of positive dead zone between heating and cooling in O 1Celsius is to definite dead zone between heating function and
77. itional heating This parameter defines the temperature control function of temperature limiter For example if selecting basic heating the thermistor temperature of temperature sensor is higher than the limit temperature the basic heating stop heating the control value is 0 If selecting basic heating the thermistor temperature of temperature sensor is lower than the limit temperature the basic heating restarts Additional heating has a similar situation Note that the temperature limiter s influence on the set temperature the heating temperature will not reach the set temperature higher than the limit Figure 4 12 parameter window Air Condition These parameters is used to set the air conditioning control There are two object types Ibit or Ibyte If Ibit type is selected control commands are sent by 161 objects and different objects corresponds to a different commands If 1byte type is selected control command sent by Ibyte object different 1 byte value corresponds to a different commands These control commands similar to the air conditioning on the remote control commands Users can learn the air conditioner remote control commands to the infrared transmitter module configure the temperature control panel with corresponding parameters then users can send through these commands by operating the temperature control panel to control the infrared transmitter module Under this setting the 4 room temperature modes invalid and c
78. ivated which is used to disable enable channel function When this communication object receives a logic value of 0 the channel function is enabled receives 1 disabled When the channel function is disabled control telegrams sent by all objects are invalid When the bus power is restored channel function is enabled by default If all communications objects with channel function are Disable the operations performed are the same 5 6 2 Dimming Communication Object 82 53 Switch CH A Switch 1 bit W 54 Dimming CH A Dimming 55 Disable input 1 CH A Disable 1bit C W s gt 82 56 Switch CH B Switch tht e 7 WI 82157 Dimming CH B Dimming 4 bit qu 58 Disable input 2 CH B Disable Tht Woe 59 Switch CH C Switch 1 bit T 60 Dimming CH Dimming Abe CO 61 Disable input 3 CH C Disable 1bit C W 5 6 2 Dimming Communication Object Number Communication object name Functions Data Types Attribute 53 56 59 Switch 1 input 1 2 3 CH A Switch Ibit C WT When CH A Switch is enabled this communication object is visible through short push according to the parameters settings performs the corresponding actions e g ON OFF TOGGLE etc When the telegram is 1 ON When the telegram is 0 OFF 54 57 60 Switch 2 input 1 2 3 CH A Switch long 4bit C T The communication object via contact input send
79. klight value from operating status to non operation status Namely when nobody operates screen delaying the parameter time entering the screen backlight without operation Parameter Switch day night mode automatically 15 SSS SSS www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel Options no yes Set the mode automatically switches about whether to activate the day night backlight brightness If you choose no conduct day or night light switch through the communication objects Day night mode If you choose yes setting up automatic switching by setting the time moment Parameter Time for switching to night at hour 0 23 minute 0 59 Set the time that LCD backlight brightness backlight switch to night For example once setting to 18 00 that means the backlight brightness of the LCD screen automatically switches to night mode when the time is 18 00 pm Parameter Time for switching to day at hour 0 23 minute 0 59 Set the time that LCD backlight brightness of the backlight switch to daylight For example once setting to 6 00 that means LCD backlight brightness automatically switched to day mode when the time is 6 00 Parameter Time mode Options 24H AM PM This parameter set show the mode of time display 24H indicates the time on the temperature control panel display system for 24 hours
80. led receives 1 disabled When the channel function is disabled control telegrams sent by all objects are invalid When the bus power is restored channel function is enabled by default 81 S Ec P He n c www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel 5 6 4 Scene Communication object 53 Input 1 Scene Scene number 1Byte T 55 Disable input 1 CH A Disable ibt C 52 56 Input 2 Scene Scene number 1Byte 3 58 Disable input 2 CH B Disable te g wW 59 Input 3 Scene Scene number 1Byte 82 61 Disable input 3 CH C Disable ibt W Figure 5 6 4 scene communication object Number Communication object name Functions Data types Attribute 53 56 59 Input 1 2 3 Scene Scene number 1byte C T The object is a scene number short press keys the corresponding set scene number will be sent to the bus Long push to keep the scene number This object sends a scene number by operating the switch short press to call the scene and long press to save the current scene The scene number is set in parameter Number of scene Set an 8bit instruction binary coded FXNNNNNN F 0 call the scene 1 save the scene X Undecided no application NNNNNN scene numb
81. m if the current temperature is warmer than the temperature setpoint under cooling comfort mode It will switch to the cooling system if the current temperature is lower than the temperature setpoint under heating comfort mode When Choosing switching heating cooling automatically in the parameter of Switchover between heating and cooling the object of Heating cooling switchover will send the current status of heating cooling to the fan coil controller or any other corresponding controllers to warm cool Under the condition of relative adjustment we can know the temperature setpoint under the cooling comfort mode by setting the parameter in different dead zone Details are as follows Temperature setpoint of the cooling comfort mode Temperature setpoint of the heating comfort mode dead zone If the values of dead zone is 3 C temperature setpoint under the heating comfort mode is 22 C that means the temperature setpoint of the cooling comfort mode is 25 C When choosing manual switchover by object we can switch the heating cooling function by the type of Heating cooling switchover If the type receive the order of 1 it will switch into heating function If the type receive the order of 0 it will switch into cooling function Parameter of Automatic transmission heating cooling switchover Options when control option changes when control value changes The parameter of Automatic transmission heating co
82. n change Fan Coil General iiis g Threshold value Switchover between heating and automatic switchover by dead zone Logic cooling Timer Page 1 s T utomatic transmission heating cooling when control option changes v Timer Paga switchover d E Pushbutton Interface Input 1 Cyclic transmission of heating cooling 0 Input 2 switchover in min 0 inactive Input 3 Period of sending HVAC status 5 min Input 4 Setpoint adjustment absolute adjustment Heating comfort setpoint in 0 1Celsius 210 Heating standby setpoint in 0 1 Celsius 190 Heating night setpoint in 0 1Celsius 170 Setpoint frost protection at heating 70 in O 1Celsius Cooling comfort setpoint in 0 1Celsius 230 Cooling standby setpoint in 0 1Celsius 250 Cooling night setpoint in 0 1Celsius 270 Setpoint heat protection at cooling 350 in O 1Celsius Minimum distance between heating 20 setpoint and cooling setpoint Figure 4 4 3 Parameter setting interface of Heating cooling setpoint Parameter of operation mode after reset Options comfort standby night Frost heat protection Here we can set the work patterns which is after BUS DEVICE RESET or after programming There are 4 work patterns in temperature controller including comfort mode stand by mode night mode and Frost Heating protecting mode Every mode has its corresponding temperature setting Comfort mode is applied to the daytime
83. nd only through communication objects can carry out bus communication the following is detailed description of each function of the thermostat panel s communication objects Note C means enabling communication functions W means the value of communication objects can be modified through the bus R means the value of communication objects can be read through the bus means the communication object has a transmission function U means the value of the communication objects can be updated 5 1 General Setting Communication Object 2 0 In operation General 1 bit Cl Poo 821 Day night mode Day night switch 1 bit CS ROO E Figure 5 1 General Communication Object Number Communication object name Functions Data Types Attribute 0 In operation General 1bit C T This communication object cyclically sends telegram 1 or 0 on the bus to show that the thermostat panel is in normal operation It is enabled when the parameter Send in operation object selects end value 0 cyclically or send value 1 cyclically but it is disabled if selecting do not send If selecting send value 0 cyclically sending telegram 0 if selecting send value 1 cyclically sending telegram 1 1 Day night mode General 1bit C R W 69 au T H o E c oe eee www video star com cn maketing video star com
84. ng working mode and the corresponding numerical values 3 9 binary input and temperature sensor input Temperature control panel offers binary input and three roads which is used to switch dimming curtains and scene controls One way is externally connected to temperature sensor input which can be a NTC thermistor as an external temperature sensor or as a floor heating temperature limiter stops heating when floor heating is higher than the limited temperature heating 4 ETS system parameter setup instructions 4 1 overview Temperature control panel can be set at different control modes according to users needs here we introduce the database settings of temperature control panel below 4 2 parameter Settings window General General parameter Setting interface as shown in figure 4 2 the interface are mainly some of the general temperature control panel parameter Settings such as the choice of heating and refrigeration 13 T SB j I www video star com cn maketing a video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel control functions by temperature control LCD backlight brightness parameter setting and so on Device 1 1 5 Thermostat General Settings Meare SNE Send In operation object no He
85. nge humidity threshold value1 2 and once changing in the bus will save the new value when the power of the BUS is off Parameter Negative hysteresis humidity Options 1 10 This parameter is used to set the hysteresis value of the low threshold value to high threshold value Assuming the hysteresis value is 596 then the lower threshold high threshold value 5 When the high threshold changes the low threshold changes accordingly Parameter If humidity is lower than threshold value 46 aum T I c 2420 20 _ www video star com cn maketing a video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel Parameter If humidity is upper than threshold value Options Do not send telegram Send following telegram once Send following telegram cyclically These two parameters are used to respectively set ways of sending telegram to the object 1bit 1byte output humidity when the detected humidity is below the low threshold or above the high threshold If select do not send telegram the object does not sends telegram If select send following telegram once the object sends telegram once If select send cyclically the object sends telegram cyclically sending time can be set in the following parameter cycle time for humidity threshold value min in the settings you
86. nput 1 4 and input 2 5 Options AND OR XOR This parameter sets the logic operations of Input 1 4 and Input 2 5 Three kinds of logic operations relations AND OR Parameter The logic function type between input3 6 and result of input 1 2 4 5 Options AND OR XOR This parameter sets the logic operations results or relations of Input 3 6 and Input 1 4 Input 2 5 providing three kinds of logic operations relations AND OR 51 m L Ra ssm Je eBge ewT aen C Dig o www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K Bus 9 KNX EIB Temperature Control Panel Parameter if logic resultz 0 1 Options do not send telegram send following telegram once send following telegram cyclically Here is to set the way of the logic object sends value when the logic results are 1 and O If select do not send telegram the object does not sends telegram If select send following telegram once the object sends telegram once If select send cyclically the object sends telegram cyclically sending time can be set in the following parameter cycle time for humidity threshold value min in the settings you can send two object types the value of the object is set in the following parameters logic1bit 1byte telegram value Parameter logic 1 bit 1byte telegram value Options
87. ns e EIJ KNX GVS Guangzhou Video star Electronics Industrial Co Ltd K BUS amp Temperature Control Panel Thermostat User Manuals Ver 1 86 01 1 11 KNX EIB Home and Building Intelligent Control System www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS 59 KNX EIB Temperature Control Panel Catalogue 1 4 1 1 PRODUCT AND FUNCTION 4 2 TECHNICAL PARAMETER SIZE STRUCTURE CHART AND WIRE MAP 5 2 2 SIZE STRUCTURE 6 2 3 BUTTON OPERATION INSTRUCTION 9 3 PROJECT DESIGN AND 10 3 1 5 10 3 2 THE EXTERNAL AND INTERNAL TEMPERATURE SENSOR 10 3 3 BASIC HEATING REFRIGERATION AND ADDITIONAL HEATING REFRIGERATION CONTROL FUNCTIONS 11 3 4 THE TEMPERA
88. nt is set independently and is not affected by the comfort mode Parameters Heating night setpoint in 0 1Celsius Options 0 500 Here it sets the temperature setpoint of heating function under night mode This temperature setpoint is set independently and is not affected by the comfort mode Parameter Setpoint frost protection at heating 0 1Celsius Options 0 255 Here it sets the temperature setpoint of heating function under frost protection mode This temperature setpoint is set independently and is not affected by the comfort mode Parameters Cooling comfort setpoint in 0 1Celsius Options 0 500 Here it sets the comfort temperature setpoint of cooling function Unlike that of relative adjustment this setpoint does not affect the setpoint of temperature under other modes Parameters Cooling standby setpoint in 0 1Celsius Options 0 500 Here it sets the temperature setpoint of cooling function under standby mode This temperature setpoint is set independently and is not affected by the comfort mode Parameters Cooling night setpoint in 0 1Celsius Options 0 500 Here it sets the temperature setpoint of cooling function under night mode This temperature setpoint is set independently and is not affected by the comfort mode 32 m DTI SC a e H DO1 Din u www video star com cn maketing video star com cn Tel
89. nual operation and so on Temperature control panel also provide binary input 3 road which can be used to switch dimming curtains and scene control 3 2 The external and internal temperature sensor Temperature control panel can provide three temperature acquisition ways from temperature sensor in temperature control panel from bus to receive external temperature from external NTC thermistors 10 m P mT ZSUSU J v ae www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel 3 3 Basic heating refrigeration and additional heating refrigeration control functions Temperature control panel has the basic heating refrigeration output control function according to the temperature set by the user in addition to basic heating refrigeration control function there is additional heating refrigeration control function as a supplement to the temperature control When the actual temperature and set temperature have a large deviation additional heating refrigeration control function can let a room faster heating or cooling 3 4 the temperature control Temperature control panel use relative adjustment in all kinds of temperature setting values of work mode At the same time it also provide a variety of types of controls such as continuous PI control switch mode PI
90. o Switch the wind speed Timed key the key is mainly used for timing and modifying the regular time Before entering the timing Settings short press it can implement the timing function the icon S 27 the open of timing function at this time the short press of mode key is locked and the operation is invalid the mode switches according to the periodic time If the icon don t show anything the timing function don t open Before entering the long press of timing time setting the humidity display area will not display the humidity temporarily but use the serial number to modify time the 0 shows modifying the current time value the other 1 16 show 16 regular time values At this point the modifying place will twinkle and you can short press switch to modify it then adjust the current value through the increase or decrease button When completed long press timing Settings exits the humidity and time return to normal display 3 Project design and application 3 1 Summary Maximum number of Maximum number of Maximum number of Application program communication group address joint address Thermostat 108 180 180 Temperature control panel mainly send output control value to fan coil actuator through collecting temperature and setting temperature so as to realize the effect of indoor constant temperature Temperature control panel can also carry out fan speed adjustment room mode switching and timing Settings by KNX ma
91. ock Humidity threshold value 1 2 Ibit W This communication object is used to disable or enable the function of the humidity threshold value Disabled and enabled actions can be set by the parameter Receive telegram 1 disable the humidity threshold value Receive telegram 0 enable the humidity threshold value TI m TP L J J MGRn clm d QS www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel 5 4 Logic Communication Object 43 Logic input A Logic input 1 bit C R BR 44 Logic input B Logic input 1 bit C R 2 45 Logic 1 1 bit output Logic 1 1 bit ETRIE 2 46 Logic 1 1 byte output Logic 1 1Bye C R T 47 Logic 1 block Logic 1 1 bit GR W 48 Logic 2 1 bit output Logic 2 1 bit E OR iE 2 49 Logic 2 1 byte output Logic 2 1Byte C R T 82 50 Logic 2 block Logic 2 1 bit C R Figure 5 4 Logic communication object Number Communication object name Functions Data Types Attribute 43 Logic input A Logic input 1bit C RW This communication object is used to receive the value of logic Input A 44 Logic input B Logic input 1bit C RW This communication object is used to receive the value of logic Input B 45 48 Logic 1 2 1 bit output Logic 1 2 1bit C R T When the logical result is 1 or 0
92. of fan to adjust the room temperature making the temperature vary within the predetermined range Device 1 1 5 Thermostat General Settings Control continuous PI control Measurement Settings Heating cooling setpoint Control parameter of heating system auto tuning _ Heating control Cooling control Mode of control value at heating Fan Coil General Threshold value Minimum control value in 96 at heating 0 Logic amen Timer Page 1 Maximum control value in at heating 100 Timer Page 2 Send control value at variation of 96 4 0 inactive Period of sending control value in min 10 0 inactive Device 1 1 5 Thermostat General Settings Control type continuous PI control Measurement Settings typ Heating cooling setpoint Control parameter of cooling system auto tuning x Heating control Cooling control Invert control value Fan Coil General Threshold value Minimum control value in at cooling 0 4 GVS KBUS KNX EIB Temperature Control Panel Figure 4 5 Heating cooling contro parameter setting interface Parameter Control type Options continuous PI control switching PI control two position control fan coil control If you choose Continuous PI Control the controlled object transmits of 0 255 corresponds to
93. off time of the switch valve to control it to achieve a comfortable room temperature state Switch valve only has open and full close two control operations PWM control needs to set a fixed cycle time at first such as setting the PWM cycle for 15 minutes when the control values is 20 of the maximum the valve will open 15 20 minutes Close 15 80 12 minutes When the control values is 50 of the maximum the valve will open 15 5096 7 5 minutes Close 15 50 7 5 minutes Schematic diagram is shown below Control value Valve position 100 26 96 Time PWM control is a relatively accurate adjustment if you choose the appropriate cycle the temperature overshoot will not be very big a simple low cost common switch valve actuator can be used It can be used to control ordinary switch valve of the fan coil electric valve or KNX valve driver 3 5 threshold function Temperature and humidity each provides two threshold functions the temperature control panel based on threshold range of the current temperature and humidity triggers two different types 1bit 1 byte of data to sent to the bus which can control other equipment switches or adjust related output of valves 3 6 logical function Temperature control panel provides two logic functions each has three inputs each input can be arbitrarily set it can be the message 1bit sent by the temperature threshold or the message 1bit sent
94. oling switchover can be found if you choose 27 uU A S M SESEIc X A m U Hn lln www video star com cn maketing a video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel the automate switchover by dead zone from the Switchover between heating and cooling you ll see two options as follows when control option changes means sending the heating cooling status if the control function changes when control value changes means sending the heating cooling status if the control value changes Parameter of Cyclic transmission of heating cooling switchover in min Options 0 255min The parameter of Cyclic transmission of heating cooling switchover in min can be found if you choose the automate switchover by dead zone from the Switchover between heating and cooling This parameter is use for setting the sending time period of heating cooling status Parameter of control option after reset Options cooling heating control option before reset The parameter of control option after reset can be found if you choose the manual switchover by object from the switchover between heating and cooling This parameter is use for setting the control function after the bus resetting or programming When choosing the control o
95. omatic wind speed mode communication object 21 sends 1 When you switch to manual wind speed mode communication object 21 sends 0 and communication object 22 sends the control value of corresponding wind When choosing object Manual ON OFF and switch to manual wind speed mode communication object 21 sends 1 and communication object 22 sends the control value of corresponding wind When you switch to automatic wind speed mode communication object 21 sends 0 4 7 Parameter window Fan Coil Heating Cooling Parameter window Fan Coil Heating Cooling shown in Figure 4 7 General Settings i i Automatic return from manual 0 Measurement Settings i 2 adjustment Heating setpoint 0 inactive min Heating control Fan Coil Heating i Threshold value in 96 for fan speed 1 20 iz Fan Coil General at heating Threshold value Threshold value in 96 for fan speed 2 40 Logic i at heating Timer Page 1 i Threshold value in 96 for fan speed 3 80 2 i F at heating Pushbutton Interface i i Fan speed for switching to comfort no change mode GVS KBUS KNX EIB Temperature Control Panel Figure 4 7 Parameter window Fan Coil Heating Cooling Parameter Automatic return from manual adjustment Options 1 255 This parameter sets time of Automatic return from manual adjustment After user manually switching the wind speed the wind speed re
96. on of the sum results of multiple temperature sensors is set through the Actual temperature the temperature send from the external temperature sensor is received by Input external temperature Parameters Internal External temperature correction Options 128 127 value 0 1 It sets the temperature correction which can correct the temperature detected by internal external sensors to prevent too much error between the actual temperature and the measured one For example if the amendment data is 50 the temperature detected by sensor is 20 so the temperature corrected is 20 50 0 1 25 Parameters Weighting interior exterior Options 0 100 10 90 19 mau E ee A N www video star com cn maketing a video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K Bus 9 KNX EIB Temperature Control Panel 100 0 This parameter is visible when selecting Internal and External sensor in the sensor type it can set the proportion between the measured temperature of temperature control panel sensor and an external sensor For example the option is 40 60 so the panel temperature sensor A occupies 40 an external sensor B occupies 60 temperature control the temperature x 40 A the temperature of B x 60 temperature control panel will control temperature according to the calculated
97. on the controlled object Parameters got from PI auto tuning may not be optimal During the process of PI auto tuning please do not adjust temperature setpoint or convert heating and refrigeration to prevent interference of PI auto tuning In the option of user defined parameter PI parameter values can be set through the following two parameters and application of temperature control panel will calculate the control value basing on the given parameter values PI parameter values of other options are specified Parameter proportional range x 0 1 C Options 10 100 In the parameter control parameter of heating cooling system when the option is user defined parameter this parameter is visible and is used to set parameter values of P proportional band with the unit is C Proportional factor equals to 255 divided by ratio range The proper ratio range must be appropriately set If it is too small it will cause very fast adjustment and overshoot If it is too large it will cause very slow adjustment but not overshoot For example the ratio range is 5 when temperature deviation is 2 C proportional control value will be 255 5 2 102 PI control value equals proportional control value plus integral term control value Parameters reset time min Options 0 255 In the parameter control parameter of heating cooling system when the option is user defined parameter this parameter is visible and is used to set p
98. ong vibration electromagnetic interference are Its location should avoid breaking the appearance and integrity of the building installed with a outdoor weatherproof shield 3 As far as possible away from door window and air vents If impossible the distance should not less than 2m 4 Try to avoid using environment in the dusty environment and installing in poorly ventilated place 5 Avoid working in extreme conditions and chemical vapors otherwise it will cause inaccurate readings of temperature control panel 8 m TD BG SS rlrrcI u e J Q ds ua n A ur www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel 2 3 Button operation instruction SUN MON TUE WED THU FR SAT call grec NE ZPO LCD display the current temperature setting temperature the heating and cooling working mode wind speed weeks time timing marks relative humidity Button on the circuit board from left to right mode key increasing key reducing key wind speed key timing button and power button underneath 9 Power button the power button is used for the switch display Just electricity temperature control panel LCD screen does not display anything until you press the power button on screen At this point the pattern temperature refrigerat
99. or Parameter B value of external temperature sensor Options 3275 3380 4200 This parameter sets the B value of the external temperature sensor thermistor When a temperature sensor input is used as underfloor heating temperature limiter you need to connect an NTC thermistor and put the thermistor into the floor inside In Measurement Settings it doesn t matter whether to select external sensor or internal sensor and external sensor for Temperature sensor Communication objects 62 Floor temperature is used to send the current floor temperature Floor temperature sending variation refers to parameter Send temperature at variation of C the floor temperature cyclically sending refers to parameter period of sending temperature The following parameter is visible if selecting temperature limiter underfloor heating in the Function of input 4 Parameter Limit temperature in 1Celsius Options 1 50 This parameter sets the limit temperature of sensor inputs Parameter Negative hysteresis temperature in 0 1 Celsius Options 5 50 65 mau E cX X 2 A Eee www video star com cn maketing a video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel This parameter sets the hysteresis of temperature limit Parameter Acting on Options basic heating add
100. point for cooling 28 29 Setpoint temperature 1 bit C T 2 83 setpoint for cooling 30 31 Setpoint temperature 1 bit Toss Figure 5 7 air condition communication object Number Communication object name Functions Data types Attribute 63 IR command number Temperature control Ibyte C T In the first parameter Control device selects air condition and selecting 1byte in Object type for controlling air condition this communication object can be seen This communication object is scene number for sending the appropriate command value If command for air condition on is set as 1 when the thermostat panel is ON it will send 1 on the bus 64 Air condition on off Temperature control 1 bit C T In Air condition the object is visible when selecting 1 bit in Object type for controlling air condition When the thermostat panel is ON sending 1 when OFF sending 0 65 Mode heating cooling Temperature control 1 bit CT In Air condition the object is visible when selecting 1 bit in Object type for controlling air condition When heating sending 1 when cooling sending 0 66 Switch to high medium speed Temperature control 1 bit C T In Air condition the object is visible when selecting 1 bit in Object type for controlling air condition When the wind speed is high sending 1 when the speed is medium it will send 0
101. protection at heating 70 EJ in O 1Celsius Figure 4 4 1 Parameter setting interface of Heating setpoint Device 1 1 5 CHTC 86 01 1 11 General Settings 5 r Operating mode after reset comfort mode x Measurement Settings Cooling setpoint a Object type for operating mode 1 byte x Cooling control switchover Fan Coil General i h Threshold value Send setpoint on change Logic Period of sending HVAC and RHCC 30s Timer Page 1 status Timer Page 2 s EE Setpoint adjustment relative adjustment sie Basic comfort setpoint at cooling 230 Input 2 0 1Celsius Input 3 Input 4 Setpoint increase for standby mode 20 S at cooling in 0 1Celsius Setpoint increase for night mode 40 te at cooling in 0 1Celsius Setpoint heat protection at cooling 350 in O 1Celsius Figure 4 4 2 Parameter setting interface of Cooling setpoint 23 mE I RE G a e i aw www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel Device 1 1 5 CHTC 86 01 1 11 General Settings Operating mode after reset comfort mode Measurement Settings SCORE COO se pom Object type for operating mode 1 byte Heating control switchover Cooling control h o
102. ption before reset After bus power reset the current control function is referring to the function before the bus off electricity otherwise it is referring to the default cooling function after programming Parameter of Period of sending HVAC status Options do not send 5s 10s 2h Parameter of Period of sending HVAC status is use for setting the interval of sending HVAV to the bus recurrently through type of Output HVAC status The HVAC status is updated once every 30 seconds 28 au T SSI cA cC Y Uc eel www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel Status of type Output HVAC status Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 BitO Frost Dead zone Heating Cooling Temperatur Frost Heat Nigh Stand by Comf warning status sign sign e control protection t mode ort sign Prohibiting mode mod mode EnableSig e n Noted Current temperature lt 5 C Value of frost warning is 1 Parameter of Setpoint adjustment Options relative adjustment absolute adjustment Parameter of Setpoint adjustment is use for setting the adjusting way of the temperature setpoint For the option of relative adjustment the temperature setpoint is referred to definite comfortable temperature setpoint in every mode
103. r is visible when setting cyclically sending its cycle Base x Factor Parameter Reaction on closing the contact Rising edge switch 1 2 Options No function off on toggle This parameter is visible only distinguish long short operation Here is to set the performed the operation when performing long short operation When the input operation is determined as be long or 59 www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS K Bus 9 KNX EIB Temperature Control Panel short operation the object values are updated immediately Parameter Long operation after basexFactor Base Options 100ms 1s Mh Factor Options 2 255 This parameter is visible when it distinguishes between long and short operation Here is to set the effective time of long operation If the connecting time of input contacts is longer that the set time the operation is considered as long operation or short operation Time TL BasexFactor In parameter window Input 1 2 3 select Switch Dimming in Function of input 1 2 3 seen in Figure 4 11 3 After this function is enabled user through one input operation can control switching and dimming devices simultaneously Device 1 1 5 Thermostat General Settings Switch Dimmi Measurement Settings js Luncnon sitch pimming pesto Soom i Long operation after 30 Heating control
104. rameter is used to specify the telegram value that object 1bit 1byte output temperature sends when the current temperature is below the low threshold and above the high threshold After a bus reset or programming if the current temperature is between the low threshold and the high threshold the object does not send telegram to the bus Parameter Cycle time for temperature threshold value min if used Options 1 255 This parameter is used to set the object 1bit 1byte output temperature cycle time on the bus to send the value of the interval only when the parameter If temperature is lower upper than threshold value set loop send it to use Parameter use block of the temperature threshold output 44 mau E Ms I n A Wpn t www video star com cn maketing a video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel Options yes no This parameter sets whether to enable the threshold value if enabled the object temperature threshold value1 2 block is visible when the object receives telegram 1 threshold value is disabled when the object receives telegram 0 the threshold value is enabled Parameter Behaviour when setting the lock Options Do not send telegram Send the same telegram as lower threshold Send the same telegram as upper threshold This paramet
105. repeat the description of these similar parameters we do not make distinguish description of parameters of different controlling types If one type of control does not have some parameter then it does not have the function of the parameter Parameter control parameter of heating system Options Hot water heating 5K 150min Floor heating 5K 240 min Electric heating 4K 100min Split unit 4K 90min auto tuning User defined parameter Parameter control parameter of cooling system Options Cooling ceiling 5K 240min Split unit 4K 90min PI auto tuning 35 www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel User defined parameter If the option is PI auto tuning you can obtain the PI parameters through auto tuning After programming the temperature control panel starts auto tuning makes room temperature oscillate upper and lower around temperature setpoint through fully open and fully close operations After two oscillation cycles parameters will be calculated according to the amplitude and period of oscillation waveform Finally the the self tuning state ends and turns to PI control state which controls according to the parameters got from auto tuning When the bus turns off and then turns on PI continues to control according to those parameters The period of Self tuning ranges from tens of minutes to several hours depending
106. riod is still the time set by parameters If the control object sends a fully open or fully closed packet the temperature control panel will still 38 www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel cyclically send telegrams The two control type continuous PI control and switching PI control have same PI control value but different control object The control object of continuous PI sends out PI control 1byte directly but control object of switching PI outputs an on off control telegram according to the duty cycle of control object Parameters Symmetrical hysteresis temperature x 0 1 C Options 5 50 This parameter is visible only when the control type Two position control and is used to set a delay interval to prevent that the small decline or rise of temperature causes the frequent switching on off of actuator and results in the frequent switching on off of the valve If the delay interval is set to be too large it will reduce the number of actuator s action and extend actuator s life but it will reduce control accuracy For example in the mode of heating if temperature setpoint is 20 C the delay interval is 2 C then the control object will send an on telegram at 19 open the valve and start heating When temperature rises to 21 C the control object will send an off telegram close the valve and stop heat
107. rol value the corresponding wind speed is entered Each switching to an operation mode timing mark start timing in speed return mode time will return to automatic speed mode 4 8 Parameter window Threshold value Parameter window Threshold value is shown in Figure 4 8 here is to set the threshold values of of temperature and humidity which can be enabled in the interface When the temperature threshold value is enabled the parameter window is shown in Figure 4 8 1 when the humidity threshold value when enabled the parameter window is shown in Figure 4 8 2 Temperature control panel according to the current temperature and humidity within the threshold value range triggers to send two different types of 1bit 1byte data to the BUS to control other devices Device 1 1 5 Thermostat General Settings E 4 i Temperature threshold value 1 disable Measurement Settings i Heating setpoint i Temperature threshold value 2 disable M Heating control Fan Coil Heating Humidity threshold value 1 disable X Fan Coil General i re ea ee i Humidity threshold value 2 disable Logic Timer Page 1 Timer Page 2 Pushbutton Interface Figure 4 8 Parameter window Threshold value Setpoints of threshold values 42 aum T S X c ee P P c J c n ga n www video star com cn maketing a video star com cn Tel 8620 39338986 Fax 8620 3933
108. s communication object would display when parameter Setpoint adjustment Selects absolute adjustment it is used to modify the standby mode temperature at heating 86 Heating night setpoint Setpoint temperature C This communication object would display when parameter Setpoint adjustment Selects absolute adjustment it is 75 ma R SEESBE c J M c Pn a un ml www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel used to modify the night mode temperature at heating 87 Setpoint frost protection Setpoint temperature 2byte C R W This communication object would display when parameter Setpoint adjustment Selects absolute adjustment it is used to modify the frost protection mode temperature at heating 88 Cooling comfort setpoint Setpoint temperature 2byte C R W This communication object is used to modify the comfort mode temperature at cooling 89 Cooling standby setpoint Setpoint temperature 2byte C R W This communication object would display when parameter Setpoint adjustment Selects absolute adjustment it is used to modify the standby mode temperature at cooling 90 Cooling night setpoint Setpoint temp
109. s the transmission time interval of the thermostat panel cycle send to other devices in the bus through its communication objects rel humidity 4 4 Parameter setting interface Heating Cooling setpoint In the setting of Temperature control system parameter s setting content will be different in this 22 T BS iwe wn J w E gg www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS 59 KNX EIB Temperature Control Panel page according to your choice from Cooling Heating or Heating and Cooling temperature can be set here under any work patterns including relative mode and absolute mode General Settings Operating mode after reset comfort mode x Measurement Settings Heating setpoint Object type for operating mode 1 byte gt Heating control switchover Fan Coil General h on change Threshold value EUM 9 M Logic Period of sending HVAC status 5 min 1 Timer Page 2 Setpoint adjustment relative adjustment Pushbutton Interface Input 1 Basic comfort setpoint at heating 210 Input 2 in 0 1Celsius Input 3 Setpoint decrease for standby mode 20 Input 4 at heating in 0 1Celsius Setpoint decrease for night mode 40 ted at heating in 0 1Celsius Setpoint frost
110. ssion period of in operation object parameter will be visible 14 E HP www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel Parameter Transmission period of In operation object Options 5s 10s 2h This parameter is the communication object sending period for testing whether temperature control panel is normal or not and mainly being sent to the bus circularly to tell whether temperature control panel is normal or not through object in operation Parameter Temperature display Options Celsius C Fahrenheit F Here setting the LCD panel temperature display unit Choose Celsius C the temperature will be displayed in Celsius Choose Fahrenheit F the temperature will be displayed in Fahrenheit Parameter Backlight in no operation in day Parameter Backlight in operation in day Parameter Backlight in no operation in night Parameter Backlight in operation in night Options 0 100 This parameter is mainly used to set up the LCD panel backlight brightness in the daytime or at night under the condition of operation and non operation The user can set the day or night through the bus also can identify the day or night by time points Parameter Time of backlight delay s Options 5 50s This parameter is mainly used for setting the bac
111. trol 2Bye C R T 22 19 Basic heating control value Temperature control iBye C T 82 20 Basic cooling control value Temperature control 1 bit CR ts T a 21 Automatic fan ON OFF 1 bit C T 22 22 Fan manual stage 1Byte C R T 2 23 Lock temperature control Temperature control 1 bit R 24 Additional heating control value Temperature control 1 R mq 2 25 Additional cooling control value Temperature control 1Byte C R E 82 26 Lock additional stage 1 bit C R W 4 12 Temperature operating mode switchover Setpoint temperature 1Byte C R 84 outdoor temperature Temperature 2Bye R W 85 Heating standby setpoint Setpoint temperature 2Byte C R 86 Heating night setpoint Setpoint temperature 28 R W 8 87 Setpoint heat protection Setpoint temperature 2Bye C R W 88 Cooling comfort setpoint Setpoint temperature 2Byte C R W 89 Cooling standby setpoint Setpoint temperature 28 C R W 90 Cooling night setpoint Setpoint temperature 28ye W 91 Setpoint frost protection Setpoint temperature 2Bye C R W Figure 5 2 Temperature control communication object Number Communication object name Functions Data Types Attribute 2 Input external temperature Temperature 2 byte C RW This communication object is for receiving temperature the external temperature sensor sends on the bus 70 www video star com cn maketing video star com cn Tel 8620
112. ture Picture 22 6 www video star com cn maketing a video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS 59 KNX EIB Temperature Control Panel r 23 4m 4 r 20 Inm r 86 15mm 13 0m T C TN 88 Lt 1888 688885 SUN MON TUE WED TWU FRI SAT Figure2 2 1 Temperature control panel Size picture 32 Omm 45 Figure2 2 2Temperature control panel coupler size picture 7 mE I RE WMETCOEA a nP R Qn P www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel 9 Figure2 2 2Temperature control panel connect picture Auxiliary power supply 4 KNX EIB BUS temperature C 8 3 push button input To ensure the accuracy and stability of the measurement temperature control panel please note the following items 1 Keep away from air conditioners refrigerators stoves and other areas sensitive to changes in air temperature 2 Should not be installed in direct sunlight and away from a str
113. unication object is used to send the heating setpoint of the current operating mode on the bus sending way depends on the parameter send setpoint in 4 4 The communication object is used to modify the heating setpoint of the current operating mode Note that due to the relative adjustment of setpoint temperature the setpoint temperature in standby mode night mode and frost heat protection mode can only be increased to the maximum setpoint temperature comfort mode 16 Cooling setpoint Setpoint temperature 2 byte C R T The communication object is used to send the cooling setpoint of the current operating mode on the bus sending way depends on the parameter send setpoint in 4 4 The communication object is used to modify the cooling setpoint of the current operating mode Note that due to the relative adjustment of setpoint temperature the setpoint temperature in standby mode night mode and frost heat protection mode can only be decreased to the minimum setpoint temperature comfort mode 17 Output HVAC status Temperature control 1 byte C R T This communication object is used to report the status of temperature control updated every 30 seconds the interval of cyclically sending depends on parameter Period of sending HVAC status Each 1byte means as follows flag of enabling comfort mode 1 enable 0 disable Bit1 flag of enabling standby mode 1 enable 0 disable B
114. ure setpoint is 23 C the night mode s temperature setpoint will be 25 C Parameter setpoint heat protection at cooling in 0 1Celsius Options 0 500 This parameter is used to set the temperature setpoint for overheat protection In the overheating protection mode of cooling function the temperature is not allowed to be higher than the set temperature otherwise the temperature control panel will trigger a control telegram to so that the corresponding Cooling actuator start colling the room to avoid temperature to be over high When the parameter Setpoint adjustment select absolute adjustment the following parameters are visible to set the temperature setpoint of absolute adjustment Parameters Heating comfort setpoint in 0 1Celsius Options 0 500 Here it sets the temperature setpoint of heating function under Comfort Mode Unlike that of relative adjustment the setpoint of absolute adjustment does not affect the setpoint under other modes Parameters Heating standby setpoint in 0 1Celsius 31 o SEMEZIE D R J G Dre n AB www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel Options 0 500 Here it sets the temperature setpoint of heating function under standby mode This temperature setpoi
115. windows closed 7 Presence object Setpoint temperature 1 bit C RW This communication object is used to connect presence sensor Receive telegram 1 somebody or something exists Receive telegram 0 somebody or something doesn t exist 8 Active comfort mode Setpoint temperature 1 bit C RW The communication object is visible when the object type of operating mode is 1bit and is used to activate comfort mode Receiving telegram 1 will activate comfort mode receiving telegram 0 will not activate comfort mode Receive telegram 1 activate comfort mode Receive telegram 0 not activate comfort mode 9 Active standby mode Setpoint temperature 1 bit C RW 71 au T sIc 2 M Rn www video star com cn maketing video star com cn Tel 8620 39338986 Fax 8620 39338465 GVS KBUS KNX EIB Temperature Control Panel The communication object is visible when the object type of operating mode is 1bit and is used to activate standby mode Receiving telegram 1 will activate standby mode receiving telegram 0 will not activate standby mode Receive telegram 1 activate standby mode Receive telegram 0 not activate standby mode 10 Active night mode Setpoint temperature 1 bit C R W The communication object is visible when the
Download Pdf Manuals
Related Search
Related Contents
USER MANUAL Ewent EW2506 Installation and User`s Manual Global Tracking and PC de Secretária ASUS Kenmore 795.5107 Refrigerator User Manual Viewsonic X Series VP2650wb HOUZER S-175U EARTH Instructions / Assembly Guides pratiques Avast - antivirus Guía de Liberty City Humminbird 737 GPS Fish Finder User Manual Copyright © All rights reserved.