1. To Order For new or replacement vibration switches call 1 800 4Marley ABC DEF ms Ly O OO Example M 5 111 010 A J Hazard Rating 0 None 1 UL cUL Explosion Proof Class Div 1 Groups C and D Class Il Div 1 Groups E F and G 2 UL cUL Explosion Proof Class l Div 1 Groups B C and D Class Il Div 1 Groups E F and G J Contacts 1 SPDT 2 DPDT J Full Scale Range 1 5g 2 2g 3 10g D J Reset Coil and Startup Delay O None 1 115VAC 2 230VAC 3 24VDC 4 115VDC J Wiring Entry Mounting Plate retro fit 1 NPT 6 M20x1 5 m Environmental Rating O or blank NEMA 4 IP65 1 NEMA 4X IP65 Tested for compliance with the applicable EC Electromagnetic Com patibility requirements CE note When Option C 2 Option D cannot 3 for operation in the horizontal axis When Option A 1 or A 2 Option E cannot 6 M 5 vibraton switch P user manual WHERE IDEAS MEET INDUSTRY This electronic equipment was manufactured according to high quality stan Note dards to ensure safe and reliable operation when used as intended Due to its nature this equipment may contain small quantities of substances known to be hazardous to the environment or to human health if released into the environ ment For this reason Waste Electrical and Electronic Equipment commonly known as WEEE should never be disposed of in the public waste stream The Crossed Out Waste Bin label affixed to this product is a re
2. or beyond the maximum setting and may not trip on vibration Getting The Adjustment Position Back To Normal Once an adjustment is out of range and the rod and spring have not been dislodged the switch may be adjusted back to normal settings With the switch cover removed rotate the adjusting rod clockwise until it bottoms out Push the right hand side of the trip plate down to reset the switch At this point the NORM CLOSED CONTACT is closed Rotate the adjusting rod approximately two turns counter clockwise slowly or until the trip bar moves up with a click Then rotate the adjusting rod clockwise one full turn If the cooling product fan start or run position trips the switch then rotate the adjusting rod clockwise in 1 increments until the trip holds in Note operaton specifications Electrical Reset and Startup Lockout The optional electrical reset circuit consists of an electrical solenoid in series with a thermistor If the rated voltage is continuously applied to the reset circuit at startup the reset solenoid energizes for a fixed time interval approximately 30 seconds after which time the solenoid is automatically de energized by the thermistor This action provides a trip lockout during machine startup roughness The voltage must be removed from the reset circuit when the fan motor is stopped to allow the thermistor to cool off The switch mechanism can then be reset electrically by a momentary application of the reset vo
3. SIP gt lt WHERE IDEAS MEET INDUSTRY M 5 vibration switch INSTALLATION OPERATION MAINTENANCE M2010 1241 ISSUED 04 2013 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING THIS PRODUCT gt Marley A Caution installation This bulletin should be used by experienced personnel as a guide to the instal lation of the Marley M 5 vibration switch Selection or installation of equipment should always be accompanied by competent technical assistance Before proceeding to install and wire the unit read and thoroughly under stand these instructions The switch model number should be checked to confirm that you have the correct hazardous area rating for your ap plication Installation 1 The sensitive axis of the vibration switch is perpendicular to the mounting base The preferred mounting is with the sensitive axis in the horizontal plane since most machines vibrate more in that plane Mount the switch solidly to the frame of the machine In most cases the switch or mounting bracket will come preinstalled 2 Remove the cover and wire the switch es into the alarm or shutdown circuit Do not exceed switch contact ratings listed in the specifications Keep field wiring away from the moving part of the mechanism 3 Observe all local electrical codes 4 All the power must be switched off before opening of the enclosure in an explosive atmosphere 5 The Vibration Switch must be electrically c
4. all speeds During installation and testing if a problem with either the sensitizing or desensitizing setting is suspected or you think the unit is defective do not attempt to adjust the setpoint Call 800 462 7539 or 281 940 1802 Field Service or 713 702 8805 Technical Assistance after hours for troubleshooting To test the operation of the electrical contacts in the vibration switch please follow one of the provided procedures below The first test procedure is the recommended procedure to use without having to remove the switch cover Test 1 Do not adjust the setpoint Loosen the four mounting bolts on the vibration switch support do not remove Either lightly tap or shake the vibration switch thus triggering the unit indicating the unit is active Retighten the mounting bolts and reset the unit Test 2 Do not adjust setpoint Remove the cover to expose the inside of the switch Using a screwdriver toggle the trip plate to force the electrical contacts open and closed The trip plate is bright metal and measures 1 x 1 and is located towards the bottom of the switch With the adjusting pin located to the left the normally closed contact will be closed when the right hand side of the trip plate is depressed Check continuity at the terminal points COMMON and NORM CLOSED or at the fan controller to confirm contacts are op erational A typical control circuit uses a closed contact to allow the fan to run An open contact means e
5. ltage or it can be reset manually If the fan motor is restarted immediately after a shutdown the lockout period will be shortened because the thermistor will be hot An increase in the ambient temperature will also shorten the lockout period Specifications Function Armature mechanism trips on high vibration and operates snap action switch es Frequency Range 0 to 3600 RPM Reset Local reset plus optional remote reset electrical coil See How to Order D Start Delay Applying reset coil voltage at start up holds mechanism from tripping for 20 30 seconds after which the switch is active Requires electric reset option Temperature Range 40 F to 160 F Enclosure High strength copper free o of 1 max aluminum alloy Environmental Rating NEMA 4 IP 65 amp CE Mark NEMA 4X Optional Switch Contact s Rating 15 amps 125 or 480 VAC hp 125 VAC 1 4 hp 250 VAC amp 125 VDC amp 250 VDC Hazard Rating See How to Order A Weight 4 0 Ib dimensions wiring Schematic 75 x 375 Holes 4 U 5 56 Mounting Holes G gt 2 33 Mounting Holes ra Push Button Reset Ground Connection 5 33 4 43 Mounting Plate Wiring Dependent on switch configuration DPDT Contacts SPDT Contacts L 7 Reset Coil L 4 Reset Coil N 8 Reset Coil N 5 Reset Coil replacement How
6. minder to dispose of this product in accordance with local WEEE regulations If you have questions about the disposal process please contact SPX Cooling Technologies customer service SPX COOLING TECHNOLOGIES INC 7401 W 129 STREET OVERLAND PARK KANSAS 66213 USA P 913 664 7400 F 913 664 7439 spxcooling spx com In the interest of technological progress all products are subject to design and or material change without notice ISSUED 04 2013 M2010 1241 COPYRIGHT 2013 SPX Corporation
7. onnected by means of a flame proof cable gland or stopping box certified to EN 50018 6 For ambient temperatures below 14 F and above 1 40 F use field wiring suitable for both minimum and maximum ambient temperature 7 Reinstall the cover by first insuring the sealing gasket is in place and properly seated in the grove in the housing Place the cover on the unit and install the four cover bolts Torque the four bolts to 16 ft lb Caution should be used to not over torque the bolts as this could damage the housing and compromise the seal 8 The temporary conduit entry plugs are placed in the housing to provide physical protection for the threads during shipping Once the unit is installed in the field these plugs must be replaced These temporary plugs do not provide adequate environmental protection for the switch when installed in the field A Warning A Caution Note operation Vibration Switch Testing The vibration switch is a safety circuit acting as a run permissive for the VFD or starter controlling the fan motor Follow lockout tagout procedures on the fan starting equipment A special tool is required to adjust the setpoint do not attempt to adjust Adjusting the setpoint will VOID the warranty The setpoint is factory set at 1g which is more than sufficient to allow the mechanical equipment to get up to speed without tripping the motor The default trip setting should allow for a full voltage start and operation at
8. xcessive vibration has occurred shutting off the starter or VFD Note operation As stated previously adjusting the setpoint will void the warranty on this switch If by either accident or intentionally the setpoint is tampered with the following instructions are provided indicating how to properly readjust the setpoint If the proper setpoint cannot be achieved through these steps then call for technical assistance In order to adjust the setpoint a special tool is required and may be furnished upon request from SPX Cooling Technologies Turning Setpoint Adjustment Too Far Counter Clockwise If the setpoint adjustment is turned too far counter clockwise approximately 3 4 turns the switch will trip and will not stay in a reset position after de pressing the manual reset push button At approximately 11 turns the switch will trip and cannot be reset because the spring and adjusting rod have dislodged out of position There is no mechanical stop position when turning counter clockwise Repair of the in ternal mechanism can be accomplished in the field by removing the internal switch mechanism from the switch body The switch mechanism is held in with three screws Once removed the adjusting rod and spring may be put back into operating position Turning Setpoint Adjustment Too Far Clockwise The adjusting rod has a nylon stop bushing preventing the rod from being over turned Once the adjustment bottoms out the switch is at