Home

AMB-50

image

Contents

1. European non warranty units can be replaced by your Amprobe Test Tools distributor for a nominalv charge Please check the Where to Buy section on www amprobe com for a list of distributors near you European Correspondence Address Amprobe Test Tools Europe In den Engematten 14 79286 Glottertal Germany Tel 49 0 7684 8009 0 Correspondence only no repair or replacement available from this address European customers please contact your distributor 21 0 AMB 50 5000V Insulation Resistance Tester GUARD EARTH ok 09 EA N10140 oan J 15 RNS RNS save 14 Green Black Red 13 12 D Ye LcD D AUp Button O 4 Scroll Button LINE High Voltage output input terminal Emergency Stop two plugs red test lead to one alligator clip Data Clear the Display Backlight Button High voltage line shielding input terminal V Down Button On Off Button Compare Button Insulation Resistance Button DC Voltages measurement Button O Timer Button AC Voltages measurement Button 12 Test Button 8 USB Button D Data Store Button BD Data Recall Button BD gt Scroll Button two plugs red test lead to one alligator clip 20 GUARD Grounding protection input terminal one plug black test lead to one alligator clip 4 EARTH High resistance measurement inpu
2. Afterward the time increment or decrement by every 30 seconds e Then press and hold TEST button for 2 second to carry out timed measurement TIME 1 and are displayed and blinked on the LCD on every 0 5 seconds e When the set time is reached the insulation resistance measurement voltage will be closed and the measurement will be automatically stopped The LCD displays the insulation resistance reading c Polarization Index PI Measurement e Press TIME button to select timed measurement mode the LCD displays TIME 1 and symbols Press lt and P buttons to set the time 00 10 15 00 Within 1 minute the time increment or decrement by every 5 seconds Afterward the time increment or decrement by every 30 seconds Press TIME button again TIME 2 Pl and G symbols appear on the LCD Press lt and P buttons to set the time 00 15 15 30 Within 1 minute the time increment or decrement by every 10 seconds Afterward the time increment or decrement by every 30 seconds Then press and hold TEST button for 2 seconds to carry out timed measurement TIME 1 and A are displayed and blinked on the LCD on every 0 5 seconds before TIME 1 set time is reached TIME 2 and A are displayed and blinked on the LCD on every 0 5 seconds before TIME 2 set time is reached When the two set time are reached the insulation resistance measurement voltage will be closed and he measurement will be automatically stopped The LCD displays the polar
3. of humidity high temperature explosive inflammable and strong magnetic field e If the Meter is wet dry it before use A WARNING e Do not attempt to repair or service your Meter unless you are qualified to do e Bring this line up This is one sentenceso and have the relevant calibration performance test and service information Replacing the Battery A WARNING To Avoid Electric shock remove all the test leads from the Meter replacing the batteries A OPERATING CAUTION e Don t mix old and new batteries e Make sure the polarity is correct when installing batteries e Do not use the Meter if the battery indicator shows a battery empty condition e Do not carry out measuring with the battery compartment is open Follow the shown picture and proceed as follows to replace the battery e Turn the Meter to OFF and remove all connections from the terminals e Remove the screw from the battery compartment and separate the battery e compartment from the case bottom e Replace with 6pcs of new 1 5V LR14 batteries e Rejoin the case bottom and battery compartment and reinstall the screw 12 Visit www Amprobe com for e Catalog e Application notes e Product specifications e User manuals pe Please Recycle
4. 0mA A OPERATING CAUTION At any output voltage when the tested resistance is les than 10M the testing time cannot exceed 10 seconds continuously 100M 9 99G 5 5 100M 9 99G 5 5 100M 9 99G 5 5 10 0G 20 0G 10 5 10 0G 40 0G 10 5 10 0G 100G 10 5 Accuracy MAINTENANCE AND REPAIR If there appears to be a malfunction during the operation of the meter the following steps should be performed in order to isolate the cause of the problem 1 Check the battery Replace the battery immediately when the symbol EA appears on the LCD 2 Review the operating instructions for possible mistakes in operating procedure Except for the replacement of the battery repair of the meter should be performed only by a Factory Authorized Service Center or by other qualified instrument service personnel The front panel and case can be cleaned with a mild solution of detergent and water Apply sparingly with a soft cloth and allow to dry completely before using Do not use aromatic hydrocarbons Gasoline or chlorinated solvents for cleaning e Periodically wipe the case with a damp cloth and mild detergent Do not use abrasives or solvents e To clean the terminals with cotton bar with detergent as dirt or moisture in the terminals can affect readings e Turn the Meter to OFF when it is not in use e Take out the battery when it is not using for a long time e Do not use or store the Meter in a place
5. A AMPROBE AMB 50 5000V Insulation Resistance Tester Users Manual e Mode d emploi e Bedienungshandbuch e Manual d Uso e Manual de uso A AMPROBE AMB 50 5000V Insulation Resistance Tester Users Manual Limited Warranty and Limitation of Liability Your Amprobe product will be free from defects in material and workmanship for 1 year from the date of purchase This warranty does not cover fuses disposable batteries or damage from accident neglect misuse alteration contamination or abnormal conditions of operation or handling Resellers are not authorized to extend any other warranty on Amprobe s behalf To obtain service during the warranty period return the product with proof of purchase to an authorized Amprobe Test Tools Service Center or to an Amprobe dealer or distributor See Repair Section for details THIS WARRANTY IS YOUR ONLY REMEDY ALL OTHER WARRANTIES WHETHER EXPRESS IMPLIED OR STAUTORY INCLUDING IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY ARE HEREBY DISCLAIMED MANUFACTURER SHALL NOT BE LIABLE FOR ANY SPECIAL INDIRECT INCIDENTAL OR CONSEQUENTIAL DAMAGES OR LOSSES ARISING FROM ANY CAUSE OR THEORY Since some states or countries do not allow the exclusion or limitation of an implied warranty or of incidental or consequential damages this limitation of liability may not apply to you Repair All test tools returned for warranty or non warranty repair or for cali
6. bration should be accompanied by the following your name company s name address telephone number and proof of purchase Additionally please include a brief description of the problem or the service requested and include the test leads with the meter Non warranty repair or replacement charges should be remitted in the form of a check a money order credit card with expiration date or a purchase order made payable to Amprobe Test Tools In Warranty Repairs and Replacement All Countries Please read the warranty statement and check your battery before requesting repair During the warranty period any defective test tool can be returned to your Amprobe Test Tools distributor for an exchange for the same or like product Please check the Where to Buy section on www amprobe com for a list of distributors near you Additionally in the United States and Canada In Warranty repair and replacement units can also be sent to a Amprobe Test Tools Service Center see address below Non Warranty Repairs and Replacement US and Canada Non warranty repairs in the United States and Canada should be sent to a Amprobe Test Tools Service Center Call Amprobe Test Tools or inquire at your point of purchase for current repair and replacement rates In USA In Canada Amprobe Test Tools Amprobe Test Tools Everett WA 98203 Mississauga ON L4Z 1X9 Tel 877 AMPROBE 267 7623 Tel 905 890 7600 Non Warranty Repairs and Replacement Europe
7. ce comparing value After polarization index measurement press to display polarization index TIME 2 insulation resistance value and TIME 1 insulation resistance value in sequence When set the timer duration for the measurement of insulation resistance or polarization index press to increment the time The maximum length of time is 30 minutes and 30 seconds the Meter will automatically carry out measurement When use the compare feature measuring insulation resistance press to increment a resistance comparing value After polarization index measurement press to display polarization index TIME 2 insulation resistance value and TIME 1 insulation resistance value in sequence Press once to start the data transferring to the computer via USB USB symbol shows on the display e Press again to stop the data transferring to the computer via USB USB symbol disappears COMP Set a pass fail limit for insulation tests The default value is 10M measurement In sequence ik Pres o ie atan ressance measurement MEASUREMENT OPERATION Below section explains how to make measurements Press and hold ON OFF to turn on the Meter press again to turn off the Meter The Meter default range is 500V insulation resistance continuous measurement when turning on A Measuring Voltages AAMPROBE OPERATING CAUTION e To avoid harms to you or damages to the Meter please do not attempt to measure voltages higher than 600V or 600V rm
8. ce lower than 20M0 To measure insulation resistance set up the Meter as Figure 5 and do the following 1 Press IR button to select insulation resistance measurement 2 When there is no testing voltage output press A and Y button to select voltages of 500V 1000V 2500V or 5000V 3 When performing insulation resistance tests remove all power from the circuit to be measured and discharged all the power 4 Insert the red test lead into the LINE input terminal and the black test lead into GUARD input terminal 5 Connect the red and black alligator clip to the circuit to be measured negative voltage output from LINE terminal 6 Choose below insulation resistance measurement mode a Continuous Measurement e Press TIME button to select continuous measurement mode there is no timer icon on the LCD e Press 4 and gt hold TEST button for 1 second to carry out continuous measurement Output insulation resistance testing voltage TEST button light up A blinks on every 0 5 seconds e Press TEST button to close the insulation resistance measurement voltage when measurement is completed TEST button lights off A disappears The LCD shows the current insulation resistance measurement value b Timed Measurement e Press TIME button to select timed measurement mode the LCD displays TIME 1 and symbols e Press 4 and P buttons to set the time 00 10 15 00 Within 1 minute the time increment or decrement by every 5 seconds
9. e safety shutter then you will see there is a USB port 3 Insert the included USB cable to the Meteris USB port and the other end to the computer Battery Saver Sleep Mode The Meter enters the Sleep Mode and blanks the display if there is no button press for 15 minutes This is done to conserve battery power The Meter comes out of Sleep Mode when ON OFF button is pressed and hold for 1 second Battery Indication Battery Indicator Battery Voltage 10V or less The battery is empty don t use the Meter as it cannot guarantee accuracy 10 6V 11 5V Good 10V 10 5V The battery is nearly empty replacing battery is necessary At this status the Meter can still do 500V and 1000V output measurement accuracy will not be affected 11 6V or more Full SPECIFICATIONS Safety and Compliances IEC 61010 CAT III 600V overvoltage and double insulation standard Physical Specifications Digital 1999 counts o ESD Analog bar graph Operating Temperature 0 C 40 C 32 F 104 F Storage Temperature 20 C 60 C 4 F 152 F ore lt 85 10 C 40 C below Relative Humidity lt 90 0 C 40 C 8pcs X 1 5V LR14 batteries or power adaptor input voltage 230V 50 60Hz Battery Type 75mA input DC14V 1 0A Power adaptor is not included Dimensions H xW x L 202 x 155 x 94 mm Approx 2kg 4 4 Lbs including battery General Specifications Overloading Display OL on insulation resistance range Battery I
10. eter if it is damaged or metal part is exposed Look for cracks or missing plastic e Be careful when working above 33V rms 46 7V ac rms or 70V DC Such voltages pose a shock hazard e Discharge all loading of circuit under test after measuring high voltage e Do not change battery when the Meter is in wet environment e Place test leads in proper input terminals Make sure all the test leads are firmly connected to the Meter s input terminals e Make sure the Meter is turned off when opening the battery compartment A CAUTION e When performing resistance tests remove all power from the circuit to be measured and discharge all the power e When servicing the Meter use only the same model number or identical electrical specifications of test leads and power adaptor e Do not use the Meter if the battery indicator shows a battery empty condition Take the battery out from the Meter if it is not used for a long time e Do not use or store the Meter in an environment of high temperature humidity explosive inflammable and strong magnetic field The performance of the Meter may deteriorate after dampened e Soft cloth and mild detergent should be used to clean the surface of the Meter when servicing No abrasive and solvent should be used to prevent the surface of the Meter from corrosion damage and accident e Dry the Meter before storing if it is wet OPERATION Key Functions Turn on or off the Meter Press and
11. hold the button for 1 second to turn the Meter on Press anor again to turn off the Meter The Meter default range is 500V insulation resistance continuous measurement when turning on Emergency stop button Press this button when the Meter is hang and cannot turn off the E STOP power Press to turn on or off the display backlight CLEAR ENS Press and hold to clear the stored data Press to store the current measurement value The maximum number of stored reading is 18 When the stored readings memory is full the Meter shows FULL and stop storing Press and hold CLEAR to clear the stored value in order to store the next measurement e Press once to recall the first stored value Press again to exit Load feature Load feature can only be used when there is no high voltage output When the insulation resistance measurement has no testing voltage output press to select one voltage range up Under load mode press to recall the previous stored value When the insulation resistance measurement has no testing voltage output press to select one voltage range down Under load mode press to recall the next stored value When set the timer duration for the measurement of insulation resistance or polarization index press to decrement the time The maximum length of time is 15 minutes and 30 seconds the Meter will automatically carry out measurement When compare feature measuring insulation resistance press to decrement a resistan
12. ization index reading Press P to set through the polarization index TIME 2 insulation resistance reading and TIME 2 insulation resistance reading Information PI 3 minutes _10 minutes reading 30 seconds _ 1minute reading d Compare Function e Press COMP button to select compare feature COMP symbol displays on the LCD e Press and buttons to set the compare value e Below is the list in sequence of the compare value 10MQ 20M0 30M0 40MQ 50M0 60M0 70MO 80MQ 90M O 100MO 200MQ 300MQ 400M0 500M0 600MQ 700MQ 800M0 900M0 1GO 2GO 3GO 4GO 5GO 6GO 7GO 8GO 9GO 10GO 20GQ 330G 40GQ 50GQ 60GO 70GQ 80G 90GO 100G 0 200G 300GQ 400G 500G 600G 700GQ 800G 900G e Press and hold TEST button for 2 seconds to carry out the measurement e The NG symbol will display if the insulation resistance value is smaller than resistance value Otherwise GOOD symbol will be displayed The Use of Power Adaptor 1 Open the side safey shutter then you will see there is a power adaptor input terminal 2 Make sure the Meter is power off and insert the UT513 power adaptor to the input terminal 3 It is highly recommeded to take out all the batteries when you are using the power adaptor 4 Make sure the Meter is power off when you disconnect the UT513 power adaptor from the Meter USB Interface 1 Install the included software the installation guide can be seen from the CD 2 Open the sid
13. leep MOde ccccccccsssssssssecececeececeseaneessseeeeeeeeeeeesseauaeaasseeeeceeeeseseauaeaaaaeeeeeeeeeeseseuageggess Ear E A SPECIFICATIONS PLY SICAL SPECIFICATION Socorro T PO AA dt MA E E E ida ai General SPECIES lali Feature SUMMA td A AA a tv cede a Detailed Accuracy SpecificatiONS occccccnccnccononnnononnncnnnnnnnnoncnnnnnnnnnnr nr ron nn nn rn nnnnnnnnnnnnnnnn nn rr rre rennrnnnncans MAINTENANCE AND REPAIR cia A A A Replacing the A tad edocs ea pee wate a it ed a ent aa SYMBOLS AND WARNINGS SYMBOLS Double Insulated Refer to the manual Dangerous Voltage Direct Current Application around and removal from hazardous live conductors is permitted Do not dispose of this product as unsorted municipal waste UNPACKING AND INSPECTION Your shipping carton should include Symbol Complies with EU directives Alternating Current Earth Ground Conform to relevant Australian standards 1 AMB 50 Insulation Resistance Tester Test Leads 1 set Test Probe 1 set Plug type test Lead with Alligator clip Green Plug type test Lead with Alligator clip Black Two Plugs type test lead with Alligator clip Red Batteries 1 5V LR14 Users Manual Tool Box Software USB Cable Power adaptor gt gt gt O 2 gt gt If any of the items are damaged or missing return the complete package to the place of purchase for an exchange INTRODUCTION AMPROBE AMB 50 insula
14. ndicator Display FE pmm mun Icon Display Equips with function and battery indicator icons Current Consumption Maximum arauna TOA E Average around 20mA Feature Summary Voltage Auto release voltage h f fail level for the insulation COMP Measurement Use the Compare function to set a pass fail compare level for the insulatio measurements Polarization Index is the ratio of insulation resistance You can pre set two point PI Measurement of times and automatically carry out the measurement TIME To carry out measurement by setting a specified time within 15 minutes 10 Detailed Accuracy Specifications Accuracy a of reading number of least significant digits guarantee for 1 year Operating temperature 18 C 28 C Relative humidity 45 75 RH A Voltage Measurement 30 600V 30V 600V 50 60Hz ot ON 2 5 Among them 30 100V 50 60Hz 2 8 B Nsulation Resistance Measurement Outou 500V 1000V 2500V 5000V Voltage Display ree 0 5MO 20GN 2M 0 40GO 5MO 100GN 100M0 1000GN ree i DC 500V 0 20 DC1000V 0 20 DC 2500V 0 20 DC5000V 0 20 Test Current 1mA 1 2mA 500kQ 1mA 1 2mA O 1M0 1mA 1 2mA O 2 5MO 1mA 1 2mA O 5MO 0 50M 99 9M 3 5 2 0M 99 9M 3 5 5 0M 99 9M 3 5 10 0M 29 9M For reference only 30 0M 99 9M 3 5 100M 9 99G 5 5 10 0G 99 9G 10 5 Above 100G 20 5 Humidity Below 50 Short Circuit Less than 2
15. s although readings may be obtained e Special care should be taken when measuring high voltage To measure voltages set up the Meter as Figure 4 and do the following 1 Press DCV or ACV button to select DC voltage or AC voltage measurement 2 Insert the red and green test lead into the tested circuit 3 When measuring DC voltage if the red test lead is negative voltage i i symbol will show on the display Note e When voltage measurement has been completed disconnect the connection between the testing leads and the circuit under test and remove testing leads away from the input terminals of the Meter B Measuring Insulation Resistance AAMPROBE A OPERATING CAUTION e When performing insulation resistance tests remove all power from the circuit to be measured and discharge all the power Operating the Meter must be very careful as it outputs dangerous voltage during measurement Must make sure the tested object is firmed clipped hands are away from the clips then press TEST button to put high voltage Do not short circuit the testing leads during high voltages output or test insulation resistance after high voltages output This kind of incorrect operating may cause sparking and fire which damages the Meter and harms to you Do not measure over 10 seconds when 500V measure resistance lower than 2MQ 1000V measure resistance lower than 5MQ 2500V measure resistance lower than 10MQ 5000V measure resistan
16. t terminal one plug green test lead to one alligator clip Testing leads Two plugs red test lead to one alligator clip One plug black test lead to one alligator clip One plug green test lead to one alligator clip AMB 50 5000V Insulation Resistance Tester Safety Shutter Power adaptor Input Terminal USB Port rir ir nooo Ca sibos3 OND Gn Indicator for DC voltage Q Indicator for data store full Indicator for clearing Indicator for AC voltage Q Indicator for timer Step symbol Indicates selected pass fail compare value Indicates for negative reading Timer 1 symbol Timer 2 symbol Data store is on ci DI GY Time2 1006 IT gt al GooD uy NI A E SAS LOAD P Data recall is on Indicator for polarization index Unit symbols The continuity buzzer is on B Compare feature pass Y Analogue bar graph B Risk of electric shock E Compare feature fail 20 Indicator for power adaptor Battery life indicator CONTENTS SYMBOLS AND WARNINGS viviana A a eda Symbols UNPACKING AND INSPECT ION concisa id INTRODUCTION SAFETY INFORMATION S nriran e EEE E A E E EEEE OPERATION Key Functions MEASUREMENT OPERATION ici its A Measuring VO tE A A Vue aaa tannic B Medsuring Insulation Resistance A Information The Use OF Power ACAD COM ss ida A sed ohn A A RARA USB Interface Battery Saver S
17. tion resistance tester is a handheld instrument designed primarily to make resistance insulation resistance measurement SAFETY INFORMATION This Meter complies with the standards IEC61010 safety measurement requirement in pollution degree 2 overvoltage category CAT III 600V and double insulation CAT Il Local level appliance PORTABLE EQUIPMENT etc with smaller transient voltage overvoltages than CAT III Use the Meter only as specified in this operating manual otherwise the protection provided by the Meter may be impaired ZLADANGER identifies conditions and actions that pose hazard s to the user Ax WARNING identifies avoiding electric shock A CAUTION identifies conditions and actions that may damage the Meter and carrying out accurate measurement ZLADANGER Use of instrument in a manual not specifed by the manufactuer may impair safety features protection provided by the equipment Read the following safety information carefully before using or servicing the instrument e Do not apply more than 600V e Do not use the Meter around explosive gas vapor or dust e Do not use the Meter in a wet environment e When using the test leads keep your figures away from the lead contacts Keep your figures behind the finger guards on the leads e Do not use the Meter with any parts or cover removed e When carrying out insulation measurement do not contact the circuit under test A WARNING e Do not use the M