basicDIM RCL manual
Contents
1. E T basicDIM sensor basicDIM sensor SEI Dio E DR Serer ma N Link Line Dre ON T 230v 001A nza SE A u preparation Lux en Max 25 ta 0 60 C FIR D2 Er 1c 70C GND basicDIM RCL control device luminaire group 2 Grp 2 The connected presence detectors basicDIM sensor control luminaire groups 1 2 and 3 basicDIM sensor basicDIM sensor luminaire groups 1 2 and 3 Notes eS Dl a Y sa Rae o naa N Line N i 230v 0 014 12v wire preparation LUX 05 180 sa BI Max 25 ta 0 60 C PR D2 ta te 70C GND basicDIM RCL control device luminaire group 3 Grp 3 The connected presence detectors basicDIM sensor control i basicDIM sensor basicDIM sensor Up to 20 basicDIM RCL control devices can be connected by wiring them in parallel to the Link Line digital interface The basicDIM sensors connected to the basicDIM RCL control device only control other luminaire groups via the Link Line control line if the lighting was previously switched on using the momentary action switch con nected to input T
2. basicDIM RCL Product manual 1 01 02 2011 len 9 English PROJECT DESIGN Operating multiple luminaire groups manually Conventional 230 V 50 60 Hz momentary action switches can be connected to input T on the basicDIM RCL control device One momentary action switch connected to the T inputs of the basicDIM RCL control devices in the system can be used to operate all luminaires all luminaire groups simultaneously The momentary action switch connected to input T functions in the operating mode selected using the rotary switch on the basicDIM RCL control device Daylight linked closed loop control mode OFF briefly pressing the momentary action switch alternates between recalling the value last set for all luminaire groups and switching off all lighting Holding down the momentary action switch alternates between dimming and brightening all lighting all luminaire groups between 1 and 100 Daylight linked closed loop control mode ON briefly pressing the momentary action switch alternates between enabling and disabling daylight linked closed loop control for all basicDIM RCL control devices When enabled all lighting is smoothly adjusted to maintain the required illuminance Holding down the momentary action switch alternates between dimming and brightening all luminaire groups between 1 and 100 Example operating all luminaire groups simultaneously ny 220 240V SOISOHz O Bu
3. DSI control line Link Line control line Line cross section Maximum line length Line cross section Maximum line length 2 x 0 50 mm 125m 1 x 0 50 mm 125 m 2x 0 75 mm 125m 1x 0 75 mm 125m 2 x 1 00 mm 125m 1x 1 00 mm 125 m 2 x 1 50 mm 250 m 1 x 1 50 mm 250 m Wiring topology The following topologies may be used for DSI wiring Ki me N gt Le Sb A y N 1 7 NO 7 A y A NIZ co AN gt e Va INS Sis LN o Oe Y i E Y e gt in line structure CN intree structure lt Y instar structure W Notes Every output on the basicDIM RCL control device must be wired separately The outputs cannot be connected to each other electrically Ring topologies are not permitted 14 basicDIM RCL Product manual 1 0 02 2011 en Wiring diagram 220 240 V AC max 4 Sensoren basicDIM Sensor 50 60 Hz max 25 Lampenbetriebsger te EA TE max 25 lamp control ballasts PCA 25 ballasts maximum PCA TE zo 3 3 3 max 25 reattori PCA TE z 2 a m x 25 dispositivos de control de lappa PCA TE max 25 hulpapparaten voor lampen PCA TE basicDIM RCL Product manual 1 0102 2011 len 15 English INSTALLATION Carrying out an installation test Carry out the installation test once electrical i
4. 12 basicDIM RCL Product manual 1 0 02 2011 en PROJECT DESIGN Incorporating daylight linked closed loop control into the project design In addition to the basicDIM RCL control device a basicDIM sensor is required for daylight linked closed loop con trol The basicDIM sensor detects both artificial and natural light reflected from the workspace Input LUX 12V u N e LUX N e _ PIR Ne re GND NO basicDIM sensor basicDIM sensor Notes Up to four basicDIM sensors can be connected to each basicDIM RCL control device in parallel For information regarding project design and positioning and mounting the basicDIM sensor see the installa tion instructions for the basicDIM sensor The basicDIM sensors 5DP 19f 5DP 41rc and 5DP 41rs can be connected in parallel Working range for daylight linked closed loop control basicDIM RCL Srp1 basicDIM RCL Grp2 basicDIM RCL rpt basicDIM RCL 6rp2 gt basicdiM sensor IF basicdiM sensor baseDiM sensor Das sen Notes Only the luminaires illuminating a workspace monitored by a basicDIM sensor should be regulated using daylight linked closed loop control Adjacent luminaires that are regulated via a second sensor should n
5. basicDIM RCL control device luminaire group 1 Grp 1 m m 2 Max 25DSI PCA basicDIM RCL control device luminaire group 2 Grp 2 L p 220 240V S060Hz O L el Pis basicDIM RCL control device luminaire group 3 Grp 3 O m 7 D1 Max 25DSIPCA pe Notes Any number of momentary action switches can be connected to input T on the basicDIM RCL contro device in parallel The phase L adjacent to the inputs does not have to be the same as the phase used to supply power to the basicDIM RCL control device However only phases assigned to the same sub circuit may be connected 10 basicDIM RCL Product manual 1 0 02 2011 en PROJECT DESIGN Incorporating presence detectors basicDIM sensor into the project design Controlling individual luminaire groups using presence detectors basicDIM sensor The basicDIM sensor controls the luminaire group connected to the basicDIM RCL control device Input PIR ctor Tr u EA Ln basicDIM sensor basicDIM sensor Notes Up to four basicDIM sensors can be connected to each basicDIM RCL control device in parallel The basicDIM sensors 5DP 19f 5DP 41rc and 5DP 41rs can be connected in parallel In the project design position the basicDIM sensor so tha
6. Run on time Mode Status 5 ON never OFF 20 min ON manual Note The rotary switch is not only used to set the mode for presence control but also to set the mode for daylight linked closed loop control at the same time Mode OFF never OFF change to brightness value 10 Mode OFF never OFF see section Description of functions page 5 Run on times for mode OFF never OFF The run on time is fixed at 20 min Configurable functions Position Presence control Daylight linked closed loop control Mode Run on time Mode Status B OFF never OFF 20 min ON manual Note The rotary switch is not only used to set the mode for presence control but also to set the mode for daylight linked closed loop control at the same time 20 basicDIM RCL Product manual 1 01 02 2011 I en CONFIGURATION Mode no PIR Mode no PIR see section Description of functions page 5 Configurable functions Position Presence control Daylight linked closed loop control Mode Run on time Mode Status D no PIR ON manual E no PIR ON automatic Note The rotary switch is not only used to set the mode for presence control but also to set the mode for daylight linked closed loop control at the same time Configuring daylight linked closed loop control Daylight linked closed loop control has two operating modes status automatic and manual Automatic daylight linked closed
7. Then the value brightness that was enabled before the power supply was interrupted is output e Daylight linked closed loop control was enabled before power supply was interrupted mode ON After power supply is restored value is first output as 1 brightness 10 if mode OFF never OFF is enabled Then the value brightness that is currently being calculated via daylight linked closed loop control is output Note If the lighting was switched off before the power supply to the basicDIM RCL control device was interrupted the connected luminaires will go to a value of 0 when the power supply is restored 16 basicDIM RCL Product manual 1 0 02 2011 en Configuration CONFIGURATION Before beginning configuration carry out an installation test see section Carrying out an installation test page 16 Configuring functions The basicDIM RCL control device provides a range of functions Determine which function is desired and use a screwdriver to configure that function on the rotary switch on the basicDIM RCL control device see section Description of functions page 5 Configurable functions Position Presence control Daylight linked closed loop control Mode Run on time Mode Status 0 ON OFF 20 min 0 manual 1 ON OFF 20 min 0 automatic 2 ON OFF 30 min ON manual 3 ON OFF 40 min ON manual 4 ON OFF adaptiv
8. as someone enters the detection range of the basicDIM sensor Up to 20 basicDIM RCL control devices can be easily wired together with the Link Line control line Presence control can then be extended to include up to 20 luminaire groups basicDIM RCL overview 14 a 220 240V 50 60Hz TRIDONIG 5 2 N Link Line Art No 86458998 E Pare EEN CE ON D1 p 8 4 B e ei Swteerona 1 Power supply adaptor L N 220 230 240 V 50 60 Hz 2 Digital interface Link Line for connecting up to 20 basicDIM RCL control devices 3 Input T for direct connection of conventional 230 V 50 60 Hz momentary action switches for smoothly adjusting the luminaire group 4 Outputs D1 and D2 for one luminaire group 5 Rotary switch for setting functions presence control daylight linked closed loop control test 6 Jumper reserved for future settings Must always be fitted in order to operate the basicDIM RCL control device properly 7 Jumper for enabling disabling configuration 8 Inputs 12V LUX PIR and GND for connecting basicDIM sensors basicDIM RCL Product manual 1 0 02 2011 len 3 English Basic functions Output for luminaire group No more than 25 DSI control gear elements can be connected to the output The DSI contr
9. conformity CE For disposal in accordance with the WEEE Tridonic hereby declares that the basicDIM RCL Directive complies with the relevant EU Directives e Return the device to Tridonic or dispose of the device in accordance with national regulations e Do not dispose of the device in non recyclable waste e Do not burn the device Glossary Control gear An electrical device used to operate a lamp Includes electronic ballasts smoothly adjustable electronic ballasts DSI compatible electronic ballasts transformers phase dimmers switching actuators etc llluminance in lux Ix Illuminance describes the amount of luminous flux falling on a surface DSI Digital Serial Interface A standardised interface for digitally operating control gear DSI load A DSI load is a DSI compatible lamp control gear such as an electronic ballast or electronic transformer Usually lamp control gear counts as one DSI load See the technical data for further information Wiring topology Types and options for laying the DSI control line star linear and or tree topologies Luminaire group A group of luminaires that can be jointly controlled 30 basicDIM RCL Product manual 1 0 02 2011 len Go to www tridonic com to find your personal contact at Tridonic Art no 24166467 01 2011 We reserve the right to make technical changes without notice Please contact your local sales office for further information
10. groups 1 Hold down the momentary action switch connected to the T inputs for 20 seconds 2 After 20 seconds all luminaire groups switch to 50 brightness 3 The luminaire groups are synchronised Note After synchronisation holding down the momentary action switch will dim the lighting basicDIM RCL Product manual 1 0102 2011 len 25 English Replacing devices Replacing control gear or luminaires 1 Ensure that the new device control gear luminaire can be used see section Incorporating luminaire groups into the project design page 8 2 Disconnect the basicDIM system from the power supply 3 Replace the device control gear luminaire Several devices control gear luminaires can be replaced at the same time 4 Switch the power supply back on The basicDIM system automatically initialises the new device control gear luminaire and is immediately ready for operation Replacing basicDIM sensors 1 Disconnect the basicDIM system from the power supply 2 Replace the basicDIM sensor Several basicDIM sensors can be replaced at the same time 3 Switch the power supply back on 4 Configure the daylight linked closed loop control see section Enabling and disabling configuration of the ideal illuminance page 23 The basicDIM system automatically initialises the new basicDIM sensor and is immediately ready for operation Replacing the basicDIM RCL control device 1 Disconnect the basicDIM system from t
11. one is located in the detection range the lighting is dimmed to a brightness level of 10 once the run on time has elapsed The brightness level is fixed at 10 Mode OFF never OFF change to brightness value 10 The lighting is switched on manually If no one is located in the detection range the lighting is dimmed to a brightness level of 10 once the run on time has elapsed The brightness level is fixed at 10 basicDIM RCL Product manual 1 0102 2011 len 5 English DESCRIPTION OF FUNCTIONS Mode no PIR Presence control is disabled Notes Mode no PIR daylight linked closed loop control is enabled All presence detectors and motion sensors connected to input PIR function in the operating mode are set on the basicDIM RCL control device If no basicDIM sensor is connected to input PIR set the rotary switch to position D or E mode no PIR Presence control via Link Line digital interface If multiple basicDIM RCL control devices are connected to the Link Line digital interface in parallel information that the presence of a person has been detected is transmitted to all basicDIM RCL control devices that are connected Daylight linked closed loop control Optimal lighting conditions promote a feeling of wellbeing and boost motivation The best light of all is natural daylight However if daylight is not available in sufficient quantity or quality it is necessary to supplement it with artificial light Thro
12. Briefly press the momentary action switch twice double click within 60 seconds 5 The connected luminaires blink once to confirm that configuration has been successfully enabled Setting the ideal illuminance The ideal illuminance is set when the lowest illuminance in operation occurs in the workspace Darken the room by closing the blinds curtains etc If it is impossible to darken the room artificially set the ideal illuminance in the evening or at night 1 Place a luxmeter on the work surface e g desk situated under the luminaire group 2 Use the momentary action switch to smoothly adjust the lighting until the ideal illuminance is reached This can be seen on the luxmeter 3 Wait approx 40 seconds 4 Compare the illuminance on the luxmeter with the desired ideal illuminance Repeat steps 2 and 3 if there is any deviation Saving the ideal illuminance 1 Briefly press the momentary action switch connected to input T twice 2 The connected luminaires blink twice to confirm that the ideal illuminance has been successfully saved Disabling configuration of the ideal illuminance 1 Briefly press the momentary action switch connected to input T 2 The lighting switches off Notes The brightness values detected by the basicDIM sensors are processed by the basicDIM RCL control device and used for daylight linked closed loop control The basicDIM sensors should not be covered to set the ideal illuminance Changes to
13. TRIDONIC Y enlightening your ideas basicDIM RCL Product manual EN TABLE OF CONTENTS Table of contents Safety instructions 00 00 a nn na AR a RA u are 2 Introduction su 200000 200 200000 na A AR A 3 basicDIM RCL overvieW 1 cen etree teen etree etn a ia E be ARa i 3 Basic functions iia en eee kunia Seiad aire aha bed oka Sayeed E a Raw and 4 Description Of functions 4 4 ae a an 5 DOMINO s hice ent es ee rar Nee 5 Presence CONO coin id a en a er er 5 Daylight linkediclosed l00p CONUO casona ias ch0en ds cba badd ias ran 6 Project design cc carr eater ceed eee sae ee a laa 8 ncorporating luminaire groups into the project design 6 eee 8 ncorporating operation into the project design aoaaa 9 ncorporating presence detectors basicDIM sensors into the project design 0 2 00 cece eee 11 ncorporating daylight linked closed loop control into the project design 0 0 00 cee eee eee 13 Installation coco an an ana ran 14 DSicontrolilines Link Line Control liie 4 024 444 coca tia iia ib a dc oe et 14 WING GAG AM nassen ee en od ae oe dared wh aoa es SEM a ae Pa ede 15 Carrying out an installation testo tener tenet teenies 16 CONTQUIATION se ci ia A A ae Dew eRe Care 17 Configuring TUNCTONS he unse ded anew eda da Bes aha Pee RE ae oe aeRO Renate 17 Setting MUMMMAMGE lt i A ERE 18 Configuring presence control 0 rori ere ior tE RED EEEE EE OEE EEEE EE aE nenne 18 Con
14. ance is reached This can be seen on the luxmeter 3 Wait approx 40 seconds 4 Compare the illuminance on the luxmeter with the desired ideal illuminance Repeat steps 2 and 3 if there is any deviation Saving the ideal illuminance 1 Briefly press the momentary action switch connected to input T twice 2 The connected luminaires blink twice to confirm that the ideal illuminance has been successfully saved basicDIM RCL Product manual 1 0102 2011 len 23 English CONFIGURATION Setting the ideal illuminance using the light dark procedure of a basicDIM sensor If the Light set jumper is not or cannot be fitted on the basicDIM RCL control device for setting the ideal il luminance e g because the basicDIM RCL control device is installed somewhere difficult to access such as in a luminaire or in a suspended ceiling the ideal illuminance can alternatively be set using the light dark procedure of a basicDIM sensor Enabling configuration of the ideal illuminance Configuration must first be enabled in order to set the ideal illuminance Carry out a light dark procedure using a basicDIM sensor connected to the basicDIM RCL control device to enable configuration Enable 1 Brighten the luminaires to 100 2 Shine a bright torch on the basicDIM sensor three times at intervals of approximately one second light dark procedure 3 The connected luminaires blink once to confirm that the light dark procedure was successful 4
15. e ON manual 5 ON never OFF 20 min ON manual 6 ON OFF adaptive OFF 7 ON OFF 20 min OFF 8 only OFF 10 min ON manual 9 only OFF 20 min ON manual A only OFF 30 min ON manual B OFF never OFF 20 min 0 manual C only OFF 20 min OFF D no PIR ON manual E no PIR ON automatic Test F ON OFF 15 sec ON manual Note The rotary switch is not only used to set the mode for presence control but also to set the mode for daylight linked closed loop control at the same time basicDIM RCL Product manual 1 0102 2011 len 17 English CONFIGURATION Setting illuminance Different tasks call for different required illuminance levels see section Extract of required illuminance ac cording to EN 12464 page 29 The basicDIM RCL control device can be used to recall a lighting scene and configure it individually Setting illuminance and recalling the set value without daylight linked closed loop control The output can be smoothly adjusted to achieve the required illuminance Ix using the momentary action switch connected to input T The basicDIM RCL control device records the set value Briefly pressing the momentary action switch or entering the detection range of the presence detector recalls the last set value Briefly pressing the momentary action switch again or leaving the detection range of the presence detector switches off the lighting To enable the Set illuminance and recall set value without dayligh
16. figuring daylight linked closed loop control s an eenaa 21 Synchronising luminaire groups a ae en aa 25 Replacing devices sic cas seeng raras a na ea as 26 Technical data iii A A ikea 27 Frequently asked questions seien onere ccoo a ee nee kn 28 Extract of required illuminance according to EN 12464 0 0 ect eee ens 29 DISPOsalla a 44 4 82 ace Denia Sere ae Hees ta he Pages HLTA E a anh dey eRe 30 GOSSA eea da pte eek es ele Wastin es sath Aa as Sah ie le aa eee a eae Re 30 AA E Bea ae ee Eher Een 30 basicDIM RCL Product manual 1 0102 2011 len 1 English Safety instructions The instructions in this section have been com piled to ensure that operators and users of Tridonic basicDIM RCL lighting control are able to detect potential risks in good time and take the necessary preventative measures The operator must ensure that all users fully under stand these instructions and adhere to them This device may only be installed and configured by suitably qualified personnel Intended use Proper use Control of indoor lighting systems The device may only be used for this intended purpose Improper use Outdoor use Extensions and modifications to the product Use of third party components and accessories that have not been specifically approved by Tridonic N Warning Improper use could result in injury malfunction or damage to property The operator must inform all users of the potential risks associated wi
17. he power supply 2 Replace the basicDIM RCL control device 3 Set the rotary switch on the basicDIM RCL control device to the desired function mode see section Configuring functions page 17 4 Switch the power supply back on 5 Set the illuminance if necessary see section Setting illuminance page 18 6 Configure the daylight linked closed loop control if necessary see section Enabling and disabling configura tion of the ideal illuminance page 23 26 basicDIM RCL Product manual 1 01 02 2011 I en TECHNICAL DATA Technical data ominal voltage 220 230 240 V AC 50 60 Hz Permitted input voltage 198 264 V AC 50 60 Hz Power l0SS 2 2222222 lt 15W Outputs D1 D2 DSI control line Capacity o soore reuni Max 25 DSl compatible control gear elements DSUSIONAL z 4 a aa 12 V Manchester Code DSI control line NYM 2 x 1 5 mm HO5WV U 2 x 1 5 mm Mains line NYM 2 x 1 5 mm HO5W U 2 x 1 5 mm Terminals 0 75 2 5 mm Housing material Flame retardant polycarbonate halogen free WEINE Cin ec ny approx 350 g Permitted ambient temp 0 to 60 C Storage temperature 25 to 55 C Protection type P20 Line length DSI control line Line cross section Maximum line length 2 x 0 50 mm 125m 2 x 0 75 mm 125m 2 x 1 00 mm 125m 2 x 1 50 mm 250 m Confo
18. ime Mode Status 0 ON OFF 20 min ON manual 1 ON OFF 20 min ON automatic 2 ON OFF 30 min ON manual 3 ON OFF 40 min ON manual 4 ON OFF adaptive ON manual 6 ON OFF adaptive OFF 7 ON OFF 20 min OFF Note The rotary switch is not only used to set the mode for presence control bu linked closed loop control at the same time Mode only OFF switch off lighting Mode only OFF see section Description of functions page 5 Run on times for mode only OFF The run on times are fixed Available settings 10 min 20 min 30 min Configurable functions also to set the mode for daylight Position Presence control Daylight linked closed loop control Mode Run on time Mode Status 8 only OFF 10 min ON manual 9 only OFF 20 min ON manual A only OFF 30 min ON manual C only OFF 20 min OFF Note The rotary switch is not only used to set the mode for presence control bu linked closed loop control at the same time also to set the mode for daylight basicDIM RCL Product manual 1 0 02 2011 len 19 English CONFIGURATION Mode ON never OFF switch on the lighting and change to brightness value 10 Mode ON never OFF see section Description of functions page 5 Run on times for mode ON never OFF The run on time is fixed at 20 min Configurable functions Position Presence control Daylight linked closed loop control Mode
19. ion switches can be connected to input T on the basicDIM RCL control device The momentary action switch connected to input T functions in the operating mode set by the rotary switch on the basicDIM RCL control device Daylight linked closed loop control mode OFF briefly pressing the momentary action switch alternates between recalling the value last set for the luminaires luminaire group connected to the basicDIM RCL control device and switching off the luminaires luminaire group Holding down the momentary action switch alternates between dimming and brightening the luminaires luminaire group between 1 and 100 Daylight linked closed loop control mode ON briefly pressing the momentary action switch alternates between enabling and disabling daylight linked closed loop control When enabled the lighting is smoothly ad justed to maintain the required illuminance Holding down the momentary action switch alternates between dim ming and brightening the luminaires luminaire group between 1 and 100 Example operating luminaire groups individually L Hink tine basicDIM RCL control device individual operation of luminaire group 1 Grp 1 a a o basicDIM RCL control device individual operation of luminaire group 2 Grp 2 a m O L p 220 240 5060H Ess basicDIM RCL control device individual operation of luminaire group 3 Grp 3 or L N o Max 25 DSI PCA
20. ion that the presence of a person has been detected is transmitted to all basicDIM RCL control devices that are connected What components do I have to reconfigure when replacing a basicDIM RCL control device e see section Replacing the basicDIM RCL control device page 26 Are the current user settings saved if the power is interrupted e Yes When power is restored the settings that were active before the power supply was interrupted are recalled 28 basicDIM RCL Product manual 1 01 02 2011 I en Extract of required illuminance according to EN 12464 Type of room Task or activity Maintained illuminance En in the task area Ix Office work Filing copying 300 Circulation areas in work rooms 300 Writing 500 Reading data processing 500 CAD workstations 500 Conference and meeting rooms 500 Reception desks 300 Archives 200 Public areas service Entrance halls 100 ES Cloakrooms 200 Waiting rooms 200 Cash desks and counters 300 Design and drawing Drawing rooms 500 foams Drawing rooms in art colleges 750 Technical drawing rooms 750 Side rooms Stairwells escalators moving walkways 150 Canteens 200 Buffet areas 300 Staffrooms 100 Gymnasiums 300 Kitchenettes 200 Catering kitchens 500 Changing rooms wash rooms and restrooms 200 First aid rooms 500 basicDIM RCL Product manual 1 0102 2011 len 29 English Disposal CE
21. l illuminance Configuration must be enabled in order to set the ideal illuminance Insert the Light set jumper into the basicDIM RCL control device to enable configuration Enable For Installation Function selector oy and Jumpers see manual a 5 E P np Light set enabied mam mum Sue Enabling configuration jumper is fitted Light set disabled mmm e e 230V 0 01A 12V NO wire preparation LUX N 0 5 1 50 eat PIR N E 1a 0 60 C Me to 70c GND NO Disable For Installation Function selector and Jumpers see manual Light set enabled muaa mmm Light set disabled mmm e e Disabling configuration jumper is not fitted 230V 0 01A 12V wire preparation LUX 0 5 1 50 PIR ta 0 600 gt I tc 70C GND Note Enabling and disabling configuration is only possible in manual operating mode status Setting the ideal illuminance The ideal illuminance is set when the lowest illuminance in operation occurs in the workspace Darken the room by closing the blinds curtains etc If it is impossible to darken the room artificially set the ideal illuminance in the evening or at night 1 Place a luxmeter on the work surface e g desk situated under the luminaire group 2 Use the momentary action switch to smoothly adjust the lighting until the ideal illumin
22. loop control Every time the illuminance is changed manually by holding down the momentary action switch connected to input T the ideal illuminance is changed Holding down the momentary action switch smoothly adjusts the lighting to achieve the required illuminance Ix The basicDIM RCL control device records this set value automatically and then considers it to be the ideal illumi nance for daylight linked closed loop control Briefly pressing the momentary action switch or entering the detection range of the presence detector causes he value currently being calculated via daylight linked closed loop control to be output at the luminaires Briefly pressing the momentary action switch again or leaving the detection range of the presence detector switches off he lighting Configurable functions Position Presence control Daylight linked closed loop control Mode Run on time Mode Status 1 ON OFF 20 min ON automatic E no PIR ON automatic Note The rotary switch is not only used to set the mode for daylight linked closed loop control but also to set the mode for presence control at the same time basicDIM RCL Product manual 1 0102 2011 len 21 English CONFIGURATION Setting and saving the ideal illuminance The ideal illuminance is set by holding down the momentary action switch connected to input T 1 Switch on the lighting by briefly pressing the momentary action switch 2 Smoothly adju
23. nsor and used to regulate the artificial light to main ain the required illuminance basiDIM CL pt bask RCL 672 One basicDIM sensor is required for each area in the Ph x na a wono AS 1272 room The basicDIM sensor can also be used for pres Sia 4 ence detection at the same time ale i Ae i A a I N a SR Notes For more information relating to project design positioning and mounting the basicDIM sensor see the instal lation instructions for the basicDIM sensor For information on configuration see section Daylight linked closed loop control page 6 If a daylight linked luminaire group is adjusted daylight linked closed loop control continues at this value basicDIM RCL Product manual 1 0102 2011 len 7 English PROJECT DESIGN Project design Recommended procedure 1 Ascertain the customer s needs and requirements 2 Incorporate luminaire groups into the project design 3 Incorporate operation into the project design 4 Incorporate presence detectors into the project design 5 Incorporate daylight linked closed loop control into the project design Incorporating luminaire groups into the project design A separate basicDIM RCL control device must be included in the project design for each luminaire group Luminaires within a luminaire group cannot be controlled individually No more than 25 DSI control gear eleme
24. nstallation has been completed in full and tested Set the rotary switch on the basicDIM RCL control device to position F for the installation test Overview What is tested How is it tested What happens if the installation is OK Output Hold down the momentary action All connected luminaires brighten or switch connected to input T dim Input T Hold down the momentary action All connected luminaires brighten or switch connected to input T dim Presence control Set rotary switch on basicDIM RCL If a person enters the detection range control device to position F presence of the basicDIM sensor the lighting is control mode ON OFF run on time switched on After the person exits the 15 seconds detection range the lighting switches off in 15 seconds Daylight linked closed Set the rotary switch on the When the basicDIM sensor is covered loop control basicDIM RCL control device to posi the lighting slowly brightens tion F daylight linked closed loop When the basicDIM sensor is illumi control mode ON status manual nated the lighting slowly dims Note Daylight linked dimming bright ening may take several minutes Interrupting the power supply on the basicDIM RCL control device e Daylight linked closed loop control was disabled before power supply was interrupted mode OFF After power supply is restored value is first output as 1 brightness 10 if mode OFF never OFF is enabled
25. nts can be connected to the output Notes Only DSI control gear may be connected to the output of the basicDIM RCL control device A separate basicDIM RCL control device must be included in the project design for each luminaire group If multiple luminaire groups are required it must first be determined which luminaires belong to which luminaire groups and the cabling must be planned accordingly If daylight linked closed loop control is included in the project design it must be taken into account that each luminaire group will be controlled individually When luminaire groups are being incorporated into the project design it must be noted that daylight affects the different areas of the room in different ways see section Configuring daylight linked closed loop control page 21 Plan the cabling accordingly If presence control is included in the project design it must be taken into account that each luminaire group will be controlled individually If multiple control devices are connected to each other via the Link Line inter face multiple luminaire groups can be controlled in parallel For details on the type of cabling DSI control line and installation material required see section Carrying out an installation test page 16 8 basicDIM RCL Product manual 1 0 02 2011 len Incorporating operation into the project design Operating individual luminaire groups manually Conventional 230 V 50 60 Hz momentary act
26. ol gear elements con nected are controlled together Input T on the control device Input T is designed for dimming and brightening the lighting by holding down the switch The input can only be used for single momentary action switch operation If the lighting is switched off manually briefly pressing the switch recalls the last value set for the luminaire group Multiple conventional 230 V 50 60 Hz momentary action switches can be connected to the input in parallel Inputs PIR and LUX on the control device Up to four basicDIM sensors can be connected to the PIR and LUX inputs in parallel Presence control The basicDIM RCL control device enables lighting to be controlled by the presence absence of people In addition to the basicDIM RCL control device basicDIM sensors are also required for this function Link Line digital interface Up to 20 basicDIM RCL control devices can be electrically connected using the interface Up to date presence control information is transmitted via the Link Line to all basicDIM RCL control devices connected to the digital interface Daylight linked closed loop control The basicDIM RCL control device enables lighting to be regulated by the level of daylight entering the room In addition to the basicDIM RCL control device at least one basicDIM sensor is required for this function 4 basicDIM RCL Product manual 1 0102 2011 len DESCRIPTION OF FUNCTIONS Description of functions Dimming Dimming is
27. ot illuminate the workspace monitored by the first sensor in order to enable efficient daylight linked closed loop control Daylight linked closed loop control relies on the measurement of the artificial and natural daylight reflected from a workspace This measuring procedure does not give exact data for the actual illuminance on the workspace Daylight linked closed loop control deliberately reacts to changes in the daylight levels slowly in order for these reactions to be perceived as little as possible basicDIM RCL Product manual 1 0102 2011 len 13 English INSTALLATION Installation DSI control lines Link Line control line The DSI control lines can be laid together with a 230 V AC power supply line provided that it is sufficiently insu lated 2 x basic insulation The control lines can consist of conventional installation material and do not have to be braided or shielded When selecting the control line ensure that the maximum resistance is 8 ohm per 300 m length of control line The installation material must be approved for low voltage installation up to 1000 V DIN VDE 0472 Part 508 e g HO5V V U 2 x 0 75 mm HO5V V U 2 x 1 50 mm Insulation of DSI interfaces The insulation of the digital interfaces meets the requirements for basic insulation and was tested in accordance with EN 60928 There is no guarantee of compliance with SELV standards Line cross sections and lengths
28. rmity EN 61547 Equipment for general lighting purposes EMC immunity requirements EN 61347 1 Lamp controlgear General and safety requirements EN 61347 2 11 Lamp controlgear Particular requirements for miscellaneous electronic circuits used with luminaires EN 55015 Limits and methods of measurement of radio disturbance characteristics of electrical lighting and similar equipment ICE 60695 2 11 Fire hazard testing Test methods Glowing hot wire based test methods Glow wire flammability test method for end products Kis basicDIM RCL Product manual 1 0 102 2011 len 27 English Frequently asked questions How many luminaires control gear elements can connect to one output e A maximum of 25 DSI control gear elements can be connected How can connect more than 25 DSI loads to one output e Use the DSI V T amplifier art no 86458690 to connect up to 50 additional control gear elements I have luminaires with both DALI and DSI control gear Can I run both control gear types from one basicDIM RCL control device e No Only DSI control gear may be connected How many sensors can be connected to a basicDIM RCL control device e A maximum of four basicDIM sensors may be connected Can I assign one presence detector basicDIM sensor to multiple luminaire groups basicDIM RCL control devices e Yes If multiple basicDIM RCL control devices are connected to the Link Line digital interface in parallel infor mat
29. st the lighting to achieve the desired illuminance Ix by holding down the momentary action switch 3 Save the current illuminance Ix as the ideal illuminance by releasing the momentary action switch Manual daylight linked closed loop control Every time the illuminance Ix is changed manually by holding down the momentary action switch connected to input T daylight linked closed loop control is disabled Holding down the momentary action switch smoothly adjusts the lighting to achieve the desired illuminance lx When the illuminance is changed daylight linked closed loop control is disabled until the momentary action switch is briefly pressed or the lighting is switched on off via presence control Configurable functions Position Presence control Daylight linked closed loop control Mode Run on time Mode Status 0 ON OFF 20 min ON manual 2 ON OFF 30 min ON manual 3 ON OFF 40 min ON manual 4 ON OFF adaptive ON manual 5 ON never OFF 20 min ON manual 8 only OFF 10 min ON manual 9 only OFF 20 min ON manual A only OFF 30 min ON manual B ON never OFF 20 min ON manual D no PIR ON manual Note The rotary switch is not only used to set the mode for daylight linked closed loop control but also to set the mode for presence control at the same time 22 basicDIM RCL Product manual 1 01 02 2011 I en CONFIGURATION Enabling and disabling configuration of the idea
30. t it is located above the workspace Reception characteristics are changed by reflections on the walls furniture or floor The detection ranges of several basicDIM sensors installed close to each other can overlap Avoid sources of heat within the detection range e g printers copiers fax machines For information regarding project design installation materials cable and positioning and mounting the basicDIM sensor consult the data sheet for the basicDIM sensor basicDIM RCL Product manual 1 0102 2011 len 11 English detectors basicDIM sensors PROJECT DESIGN Controlling multiple luminaire groups using presence If multiple basicDIM RCL control devices are connected by the Link Line digital interface in parallel information that the presence of a person has been detected by a basicDIM sensor is transmitted to all basicDIM RCL control devices that are connected en a For Installation Function selector m 220 240 and Jumpers see manual es P N Link Line moe en ld 230v 0 014 12V wire preparation LUX st 05 150 an ON Pa I PT basicDIM RCL control device luminaire group 1 Grp 1 The connected presence detectors basicDIM sensor control luminaire groups 1 2 and 3
31. t linked closed loop control function select one of the following settings and configure it on the rotary switch Configurable functions Position Presence control Daylight linked closed loop control Mode Run on time Mode Status 6 ON OFF adaptive OFF i ON OFF 20 min OFF C only OFF 20 min OFF Note The rotary switch is not only used to set the mode for presence control but also to set the mode for daylight linked closed loop control at the same time Configuring presence control Configure the desired presence control function using the rotary switch on the basicDIM RCL control device Mode ON OFF recall lighting scene and switch off lighting Mode ON OFF see section Description of functions page 5 Run on times for mode ON OFF The run on time can be fixed or adaptive as required If the run on time is set to adaptive the system differen tiates between times when people rarely enter the detection range of the presence detector and times when the range is quite active The duration of the run on time between 4 min and 20 min is then adapted via presence control to suit the situation 18 basicDIM RCL Product manual 1 0 02 2011 en Configurable functions CONFIGURATION Available settings 20 min 30 min 40 min adaptive between 4 min and 20 min Position Presence control Daylight linked closed loop control Mode Run on t
32. th the use of the equipment and of protective countermeasures Environment Not to be used in corrosive or explosive environments SAFETY INSTRUCTIONS A Dangers associated with the operation of the system Danger of electrocution Countermeasures Disconnect the power to the entire lighting system before working on the lighting system Risk of damage caused by condensation Countermeasures Prior to commissioning the system wait until the con trol device is at room temperature and completely dry Risk of damage caused by humidity Countermeasures Only use the control device in dry rooms and protect it against humidity Electromagnetic compatibility EMC Although the Tridonic control device meets the strin gent requirements of the appropriate directives and standards on electromagnetic compatibility it could potentially interfere with other devices under certain circumstances 2 basicDIM RCL Product manual 1 0 02 2011 en Introduction The basicDIM RCL is a digital control device which can be used to operate up to 25 DSI control gear elements simultaneously in one luminaire group The luminaires connected to the basicDIM RCL control device can be daylight linked using up to four basicDIM sensors The system enables lighting to be operated in an energy saving way by switching the lighting off when nobody is present A further advantage of presence control is that the lighting is immediately switched on again as soon
33. the smooth adjustment of the brightness provided by the lighting The basicDIM RCL control device enables the user to smoothly adjust the lighting manually at any time Presence control The most expensive light is a light that is left on in unused rooms and work areas The basicDIM RCL control device enables lighting to be operated in an energy saving way by switching the lighting off when nobody is present A further advantage of presence control is that the lighting is immediately switched on again as soon as someone enters the detection range of a basicDIM sensor Mode ON OFF switch on and off lighting If a person enters the detection range of the basicDIM sensor the lighting is switched on If no one is located in the detection range the lighting is switched off once the run on time has elapsed If the momentary action switch connected to input T is briefly pressed when someone is present in the range the lighting is switched off for 15 minutes If the momentary action switch is briefly pressed again the lighting is switched on to the last set value Mode only OFF switch off lighting The lighting is switched on manually If no one is located in the detection range of the presence detector the lighting is switched off once the run on time has elapsed Mode ON never OFF switch on the lighting and change to brightness value 10 If a person enters the detection range of the presence detector the lighting is switched on If no
34. ughout the day the basicDIM RCL control device automatically balances the level of artificial light in a room against the amount of daylight Example of daylight linked closed loop control Day basicDIM RCL Grp1 basicDIM RCL Grp2 basicDIM RCL Grp3 If a large amount of daylight is entering the room the first luminaire group Grp1 next to TE TE the window is dimmed The luminaires in the luminaire groups Grp2 Grp3 are brightened to provide the required illuminance 25 50 Required illuminance Daylight Artificial light 6 basicDIM RCL Product manual 1 0 02 2011 en Twilight basicDIM RCL Grp1 basicDIM RCL Grp2 basicDIM RCL Grp3 If the level of daylight in the room falls the lumi naires in the other groups Grp1 Grp2 Grp3 are brightened as necessary to provide the required illuminance Required illuminance Daylight Artificial light Notes For information on project design see section Incorporating daylight linked closed loop control into the project design page 13 For information on configuration see section Configuring daylight linked closed loop control page 21 Example of daylight linked closed loop control look down The basicDIM sensor is mounted on the ceiling over the workspace The light reflected from the workspace both artificial and natural daylight is detected by the basicDIM se
35. workspaces or in the surrounding area e g turning pages of a newspaper can cause deviations from the set ideal illuminance Make sure that the same lighting conditions in the room darkening exist for all basicDIM sensors during configuration daylight linked closed loop control Make sure that no artificial or natural daylight reaches the lens of the basicDIM sensor directly 24 basicDIM RCL Product manual 1 0 02 2011 len CONFIGURATION Daylight linked dimming off and on Bright Out Bright In The basicDIM RCL control device is configured so that if the lighting is switched on and a large amount of day light is entering the room the artificial light is dimmed off and then later if there is less daylight entering the room the artificial light is dimmed on again If the lighting is dimmed off via daylight linking it will remain off even if a presence is detected via presence con trol If the lighting is dimmed off via daylight linking it will switch on if the momentary action switch connected to input T is briefly pressed The lighting is dimmed off again via daylight linking after 10 minutes have passed and if the daylight conditions have not changed Synchronising luminaire groups If a momentary action switch is connected to the T inputs of multiple basicDIM RCL control devices the lumi naires may exhibit different levels of brightness after a number of smooth adjustments have been made Synchronising luminaire