1. Relay closes when the level value is less than 2 0m 1 6 0 N c 1 0 The pump is turned on for draining when the level is over 6m and stops when the level decreases to 1m It is applied to the draining well c 1 0 3 6 0 The pump is turned on for water inflow when the level decreases to 1m and stops when the level rises to 6m It s applied to the inlet well 4 3 4 Setting of Relay 2 P04 Set Relay 2 in the same way as above 5 Ultrasonic Level Meter 3 Installation 3 1 External dimension The probe s dimension changes with different measuring range Any difference will be informed in advance 150 G2 Installation way In an open environment install it with brackets and fix with the built in flange For pools or tanks make a hole that is a little larger than the probe s diameter 60mm at the installation position Then screw and tighten the flange The installation must ensure that the probe surface is horizontal to the level measured 3 2 Wiring Srst mcz24y ZLSJS Y4OZ m DJ 4 Ee vI Ha v 4 20mA and RS485 adopts the same two wiring terminals SPST1 and SPST2 correspond to the setting of parameters P03 and P04 See 4 3 3 Setting of Relay 1 P03 and 4 3 4 Setting of Relay 2 P04 for details Ultrasonic Level Meter 3 3 Definitions of installation parameters Blindarea t The highest liquid level easuring distance L current liqu
2. Displays distance with P before the number and the state of the relay Press A to choose the mode needed and then press OK to confirm 4 3 6 Probe s height P06 By Menu P06 display the probe s height check if the probe s height is in consistent with the situation on site or calibrate the level Change the probe s height value based on on site situation 4 3 7 Setting of ID No P07 Used when communication is proceeding especially multi computer communication is made The default is 01 4 3 8 Setting of baud rate P08 Used when communication is proceeding Three choices are available 2400 4800 and 9600 4 3 9 Setting of blind area P09 Change the meter s blind area to adapt to some complex situations on site For example prevent prominent things around the probe from affecting the meter Generally there is no need to change the factory default 4 3 10 Setting of reaction velocity P10 The faster the level changes the quicker the meter is required to react and the greater the data the meter displays fluctuates conversely the reaction velocity is slow and the data is stable If the level doesn t change quite fast there is generally no need to change the factory default 4 3 11 4 20mA testing P11 P11 4 20mA test menu Press OK and then press A to conduct 4 20mA output test 4 3 12 Setting of wave generating capacity P12 Set the wave generating capacity which has been set when delivered and d
3. Points on restriction The warranty card should be properly kept by the user to be as the warranty certificate If lost it won t be reissued The company shall own the warranty card s interpretation power and have the right to amend the card s contents without advance notice T Ultrasonic Level Meter CONTENTS TOUN anaa e E E a eeunune 2 lechnical dataci a a a a a ance eeaaeeaaeeeen SINISCAN AMON zie a a aa 2 9 1External GIMGNSIOM sses kretene er eR ree aE EEr e EEEE Deane E ERRUER E E 2 ee NN WING eae eee r a TE E E r a T 2 3 3 Definitions of installation parameters Sera a eiai 3 3 4 Installation DMNCIplGSs 2cc0 26ite ee ee ea 3c INStallation Precautions arsaa aan a amare E ERA eee A DE DUGGING ccinn cx sce aaiencnenen eoactanesemen ene coait a aa a a 4 A TKeyboard directives sinansa sd ates seeudcia a ERE 4 2 PASSW ONC direis scree Ret cds a aa a a 4 A SPAVAMIGIGMSCUING orero ical aay as a Mi acaecan hn obuaeaes a eatuies 4 3 1Calibratingof level P01 oo ccc ccc cee eee e ee eee tease eae teas eeaeeeaeenaeeeas 4 AS 2OCUING OL ZOMANPOZ Acntlce ee eos ae eed 5 ASS Seuing Or Relay 1 POS ine a E 4 3 4Setting of Relay 2 P04 oo ccc c eee eee eee e nsec eee sees eeeeeeneeeneees 4 3 5Setting of display Mode PO5 ccc ece eee eee eee eeeeeeeeeeeeeeeaeenneeeees 43 OProbe S Height POG niceties chenetcnene titers eee td idencheneieus ed Waeciencce net atix AO SCUING OHI NO POT dacicdeduviestrnneitdeac
4. directives Mode Menu Press Mode the password interface will appear and input password to enter the menu When setting press Mode to cancel the setting after finishing setting press Mode to withdraw from the menu a Page down and number In menu the key is used as the page down key of menu when changing data the key is used as number key P Shift and page up In menu the key is used as the page up key of menu when changing data the key is used as shift key OK Confirmation Choose menu or confirm option and data 4 2 Password directives Press key Mode the password interface will appear press key A to change the first place into 1 and press key OK to enter the interface of parameter setting menu 4 3 Parameter setting 4 3 1 Calibrating of level P01 After the meter is installed and electrified the value of level will display The datum is often inconsistent with the actual level so it needs to calibrate the level Steps to calibrate the level are as follows Press Mode input the password and then press OK to enter the parameter setting menu P01 is the level calibration menu press OK to calibrate the level P01 Change the number into the actual value of level such as 2 100 with shift and A change number and press OK to confirm Then press Mode to exit from the parameter setting menu Now it displays 2 100 on LCD Screen 4
5. MT100L Ultrasonic Level Meter USER MANUAL Dalian Metery Technology co Ltd Ultrasonic Level Meter Receipt Acknowledgement of Warranty Card for Ultrasonic Level Contact address ee Contact person ee Product type Date of acceptance Setter check in charge Product type Date of acceptance Setter check in charge Warranty policies Producto Notes on oo Card for Ultrasonic Level Meter Producto The user shall show the warranty card when the meter is repaired If any fault arises because of normal using during the warranty period the meter will be repaired for free by virtue of the warranty card Warranty period The warranty period of products of the company shall last twelve months since the date of acceptance check Following cases are beyond the scope of free warranty The product or its part is beyond the period of free warranty Hardware fault caused by that the application environment does not meet the product s application requirements Faults or damage caused by bad power supply environment or by foreign matter s entering the equipment Faults caused by the operation that is not carried out according to application methods and points for attention stated in the using and operation manual Faults caused by natural factors and force majeure such as thunder flood and water Faults or damage caused by dismounting or repair without permission by unauthorized refit or by abuse
6. eaucrdans ao Ne adnan ess 6 4 3 8Setting of baud rate P08 o oo cc cece cece eee eee e eee eee eeeeeneeeeeeeenees 6 4 3 9Setting of blind area P09 0 2 ccc ecc cece cece cece eeeeeseeeseeeseeesneesneenees 6 4 3 10Setting of reaction velocity P10 ccc cece eee e ence ee eeeeeeeeeaee ees 6 4 3 11 4 20mA testing P11 oo ccc ccc cece cece eee e eee ee ee eae e ee ea eaten eaeaeenenes 6 4 3 12 Setting of wave generating capacity P12 ccc cece ese e eee eeeeeee eae 6 Receipt Acknowledgement of Warranty Card ccccsecseeseeeeees 7 Ultrasonic Level Meter 1 Outline Sincerely thank you for buying our ultrasonic level meter The meter includes several proprietary technologies is safe and clean with high precision and long service life stable and reliable and convenient to install and maintain and is applicable to various fields of acid alkali salt anticorrosion and high temperature The meter can be connected to display meters or various DCS systems through 4 20mA or RS485 Agreement Modbus or other custom agreements to provide real time level data for the operation of industrial automation The meter is with following features For circuit design high quality power modules are selected to be as power supply parts and highly stable and reliably imported devices are used as components of the meter It can fully replace imported foreign meters of the same type Patent sonic wave intelligent techn
7. id level mounting hight TH As shown the meter s probe generates wave which hits the level and then is reflected back to the probe After receiving the wave the probe calculates the time interval between generating and receiving wave and works out the measuring distance L The meter s mounting height TH minus L is the current level H Mileage refers to the distance measurable by the meter TH should be less than the mileage Blind area refers to the area which cannot be measured by the meter around the probe The space between the highest level and the probe should be larger than the blind area If the blind area is 0 3m the space between the highest level and the probe must be over 0 3m The probe s generating wave is a spreading process namely there are direction angles to which the attention should be paid in installation Otherwise the wave may hit bumps on pool walls or the channel s edges 3 4 Installation principles 1 The distance between the probe s emitting surface and the lowest level must be less than the measuring range of the meter chosen 2 The distance between the probe s emitting surface and the highest level must be larger than the blind area of the meter chosen 3 The probe s emitting surface must keep parallel to surface 4 Do not install probe at feed or discharge ports positively below and other positions where surface fluctuates fiercely 5 If the poor or tank wa
8. ll is not smooth the probe s installation position must be over 0 3m away from the poor or tank wall 6 If the distance between the probe s emitting surface and the highest level is less than the blind area of the meter chosen it needs to install a extension tube which is over 120mm in diameter and 0 35m 0 50m in length installed vertically and with smooth internal walls The hole on the tank must be larger than the extension tuber s inside diameter Or the tube touches the tank bottom The tuber diameter is over 80mm A hole is made at the tube bottom so as to the surface inside the tube is the same high as that inside the tank Ultrasonic Level Meter 3 5 Installation precautions 1 Where the meter is installed outdoors it s better to install a sun shied so as to prolong the meter s service life 2 Electrical wires and cable protective pipes must be well sealed in order to prevent water accumulation 3 The meter has lightning protection component but when it is used in regions where it thunders frequently it is suggested that a lightning protection device for exclusive use be separately installed at wire inlet and outlet of the meter 4 If the meter is used at place where it is quite hot or cold namely ambient temperature may exceed the meter s working requirement it is suggested that the high or low temperature resistance device be set around the level meter 4 Debugging e w 0 amp 4 1 Keyboard
9. oesn t need changing After setting press Mode to exit from the setting menu Ultrasonic Level Meter 4 3 2 Setting of 20m P02 When the meter works normally press Mode to enter the parameter setting menu Press Ato choose P02 menu The number in the second line is the level corresponding to 20mA Press OK to set 4 3 3 Setting of Relay 1 P03 POS 13 0 hc 8 0 i ey os Anumberi B C number2 When the relay logic is edited the twinkling number is the number changeable currently Press A the number will be changed Positions Aand C c More than 7 Less than Positive B 4 AND means when the level value simultaneously meets two conditions the relay closes otherwise the relay releases P OR means when the level value meets any of the two conditions the relay close otherwise the relay releases Only under the former condition Position C and Number 2 will become invisible It means when the level value meets the former condition the relay closes otherwise the relay releases N Under the former condition the relay closes generally to turn on pump under the latter condition the relay releases generally to stop pump Its mainly used to control the draining well and the inlet well Corresponding level value or level difference value may be input at the positions of Number 1 and Number 2 For example a 3 0 Relay closes when the level value is over 3 0m Cc 2 0
10. ology software can make intelligentized echo analysis It needs neither debugging nor other special steps This technology has functions of dynamic thinking and dynamic analysis Our sonic wave intelligent patent technology greatly improves the meter s precision and the precision of level is up to 0 3 which is enough to resist various interference waves The meter is a non contact one and does not directly contact so the fault rate is low The meter can be installed in several different ways and the user can calibrate the meter according to the Manual The meter s all input and output lines must be with such protection functions as lightning protection and short circuit prevention 2 Technical data Measuring range O 15m Chosen based on actual measuring range Blind area 0 25m 0 6m Ranging accuracy 0 3 Standard condition Ranging resolution Imm Pressure Less than four atmospheric pressure Meter display With LCD to display levels or distances Analog output 4 20mA Digital output RS485 Agreement Modbus or custom agreement Power supply voltage DC24V AC220V a built in lightningproof device Ambient temperature 20 C 60 C Protection grade IP65 1 Ultrasonic Level Meter 4 3 5 Setting of display mode P05 Change the display mode by Menu P0O5 There are 3 display modes available for selection 1 H displays level and the state of the relay 2 H displays level and temperature 3 d