Home
Sondex - Heath Exchangers Operation and
Contents
1. freezing wrong transport lifting Even after stopping the installation some parts of it can still be hot The heat exchanger may only be used with the fluids specified on the datasheet The hot medium may not flow through the apparatus without the cold medium flowing through This 15 to prevent damage to the apparatus In case the cold medium is present but does not flow while the hot medium is flowing through the cold medium will start boiling and the apparatues will be damaged Sudden pressure and temperature changes should be prevented When a heat exchanger filled with water or a water mixture which is not in operation is exposed to temperatures below zero the plates can become deformed If a danger of frost occurs the heat exchanger should be drained completely Demountable plate heat exchangers can always leak We advise you to take this into account while installing Preferably you should install a drip tray underneath the heat exchanger to prevent leakages onto the floor and or danger to electrical equipment If the heat exchanger is being used with temperatures above 60 C or with ageressive fluids we advise you shroud the heat exchanger to prevent the risk of touching If welding activities have to be carried out near the heat exchanger never use the heat exchanger for earthing the construction work Electrical currents can cause severe damage to both plate and gasket If you have to weld dismantle the con
2. 49 4171 788330 Fax 49 4171 788350 E mail info sondex de Internet www sondex de Poland SONDEX Poland Phone 48 58 676 0012 Fax 48 58 676 0497 E mail Ksw sondex pl Internet www sondex pl Holland SONDEX BV Phone 31 299 674 934 Fax 31 299 674 936 E mail info sondex nl Internet www sondex nl USA SONDEX Inc USA Phone 502 933 9991 Fax 502 933 9914 E mail sales sondex usa com Internet www sondex dk Denmark Corporate Head Office SONDEX A S Jernet 9 DK 6000 Kolding Tel 45 76 30 61 00 Fax 45 75 53 89 68 45 75 50 50 19 E mail info sondex dk Internet www sondex dk 24
3. These flexible connections need to be fitted in a longitudinal direction to the plate package The pipe work needs to be thoroughly cleaned and flushed before connecting up to the heat exchanger Always install vents on both sides of the heat exchanger Note For proper venting the vents should be fitted on the highest point in the direction of the flow of the medium preferably on an air vessel To enable the heat exchanger to be opened when necessary shut off valves should be provided in all connections Make sure that the pipe work connected to the heat exchanger is secured against pressure peaks surges and temperature shocks Threaded pipe connections If a plate type heat exchanger is provided with threaded pipe connections make sure that these connections do not rotate when attaching unions or flanges Rotation of the pipes could damage the gasket inside the unit which seals against the back of the pipe connection Flange connections If the connection is rubber lined the liner will act as the flange gasket Bolt the connecting flange directly to the endplate using the drilled and tapped holes provided Tighten the bolts evenly do not over tighten as this could strip the threads cut into the frame plate If loose backing flanges are fitted to the heat exchanger a suitable gasket 1s required to seal the flange Unless otherwise stated the liquid circuits should be connected to flow in reverse directions through the
4. been assembled incorrectly unit is running in co current flow instead of counter current check with contract drawing and alter pipe work if necessary Check direction of pump flows e air lock has developed in the plate package or pipe work 23 10 AFTER SALES SERVICE 10 1 Ordering parts When ordering parts it is important that the correct details are given At least the following should be quoted Project and order number Exchanger type and manufacturing number see name plate Required parts When ordering separate plates it 1s important that the correct plate code index and type of plate 15 given See chapter 5 2 When ordering separate gaskets it is important to indicate the correct gasket material When ordering tie bolts the existing ones should be measured 1 order to get new ones of the same size 10 2 Modifications to the heat exchanger The plate heat exchanger is built up in modules and therefore flexible with respect to enlargements or reductions It is easy to change the capacity by respectively enlarging or reducing the number of plates We would be pleased to advise you 10 3 Contacts Australia SONDEX Australia PTY LTD Phone 61 3 9728 6564 Fax 61 3 9728 6579 E mail info sondexaustralia com au Internet www sondexaustralia com Italy SONDEX Italy S r l Phone 39 0363 905086 Fax 39 0363 905422 E mail info sondex it Internet www sondex it Germany SONDEX Deutschland GmbH Phone
5. exchanger counter current Refer to the contract drawing or quotation details if the connections are not marked 13 7 COMMISSIONING 7 1 Commissioning and pre checks 2 Commissioning may only be done by staff which has been trained specially for the job or by SONDEX commissioning engineers Control maintenance and repair of the installation may only be done by authorized trained and properly instructed staff Maintenance and cleaning may only be done with a shut down heat exchanger Check if all connections are fitted correctly see also 6 3 Filtration The media flowing through the heat exchanger should not contain particles larger than 0 5 mm diameter If necessary filters should be fitted Check the pressures and temperatures of the media and make sure that these are not more than the values specified on the identification plate It is essential that the heat exchanger is not subjected to thermal or mechanical shock as this could lead to premature gasket failure Operation Start cold circuit first than the hot circuit Fully vent the system Close isolation valves between pump and exchanger Fully open valve fitted into return line from the exchanger Start the circulation pump Gradually open closed valve fitted to inlet line of exchanger Vent system again if necessary Repeat the above for the secondary circuit 7 4 When using steam as one of the media Use slow acting contro
6. PLATE TYPE HEAT EXCHANGERS OPERATION amp MAINTENANCE MANUAL Project Customer Exchanger type Serial number Year PED category Art 3 par 3 Cat 1 Cat 2 Cat 3 Cat 4 Approved by NB number Remarks The contents of this publication are based on the latest information available and the materials that are used at the time of printing However because of rapid developments in this field we cannot be held liable for changes in specifications affecting the contents of this publication COPYRIGHT Copyright SONDEX HOLDING A S rights reserved No part of this publication may be reproduced or distributed without prior written permission of SONDEX HOLDING A S 1 FOREWORD This manual is a guide for installation commissioning and maintenance of plate type heat exchangers supplied by SONDEX It is meant for those who are responsible for the installation the use and maintenance of the heat exchangers We recommend that you read this manual carefully before commencing any work 2 INTRODUCTION This manual is applicable for all heat exchangers produced and supplied by SONDEX SONDEX can not be held responsible or liable for damage as a result of incorrect installation use and or maintenance of SONDEX plate type heat exchanger as well as not complying with the instructions in this manual Please note that our plate type heat exchangers are specially designed and built for the operating conditions p
7. ame plate Exceeding these values even as short lasting pressure peaks will cause damage to the unit and be the cause of problems To avoid costly repairs we advise you to have the installation work and maintenance carried out by properly trained personnel You can also contact relevant SONDEX Sales Office Possible solution Leakage At the connections Check the rubber liners if fitted Check the flange packing if fitted Check the O ring on the first plate Fit the pipes tension free Mixing of primary and secondary Check the plates for holes and or circuit cracks In plate package Check the assembly distance Check the condition of the packings Check the proper position of the packings The operating conditions deviate Adjust the operating conditions from the specification Insufficient Air in the system De aerate the pipe system capacity Check the pipe work for possible air traps The operating conditions deviate Adjust the operating conditions from the specification The heat exchanger 15 dirty Clean the heat exchanger The connections have been Redo the fitting work interchanged Too high Flow larger than the design flow Adjust the flow pressure drop Channels in plate s blocked Flush clean Check the pressure indicator Medium deviating from the Addition of for instance anti freeze design will increase the pressure drop Air in the system De aerate the pipe system Check th
8. at the follower shall have a parallel opening motion Pull the follower back towards the column Remove the plates without damaging the gaskets CAUTION Ensure unit is depressurized and drained of hot and or aggressive product before unit is opened to prevent personal injury CAUTION Sharp Edges When handling plates gloves should be worn Recommendation Mark the plate package before opening You could mark the plate package with a diagonal line on the outside or number the plates in sequence 17 8 4 Cleaning the plates CAUTION Always wear gloves and eye goggles when using detergents Use nylon or other types of soft scrubbing brushes with detergent Never use a metal brush steel wool or sand glass paper This will damage the passivation film of the plates Use Acetone or other types of solvents which do not contain chlorine to remove old gasket glue Alternatively use an LP gas flame heating the reverse side of the plate Do not use any other type of gas which may produce a harder flame Boiling water can be used with some success Consult a cleaning specialist for a suitable choice of detergent Ensure that all detergents used are compatible with the plate and gasket material before use In case plates are removed for manual cleaning make sure they are re fitted in the same order Always remove plates one by one and number them A high pressure cleaner can be used but with abs
9. at all the nuts and bearing boxes are running freely If not clean and lubricate or replace If the unit does not fully seal 1t may be tightened step by step to give dimension A min This dimension is mentioned on the nameplate see fig 1 The maximum tightening torque must not however be exceeded Under no circumstances distance A may be smaller than A min Tightening of the plate package can only be done with a fully depressurised unit Maintenance of the heat exchanger Time interval once a year as a minimum Check temperatures and flows against commissioning data Check general condition and look for any signs of leakage Wipe clean all painted parts and check surfaces for signs of damage touch up if necessary Check bolts and bars for rust and clean Lightly coat threaded parts with molybdenum grease or a corrosion inhibitor ensure that no grease etc falls onto the plate gaskets If rollers are fitted to the follower frame plate lubricate the bearings with light machine oil 2l 9 PROBLEM SOLVING If you have problems with your plate type heat exchanger in most cases these can be solved by your own personnel Please find below a summary of possible problems as well as possible causes and solutions A condition for the continuous proper functioning of your plate type heat exchanger is strict compliance with the permissible values for pressure and temperature mentioned on the n
10. e installation area It is very important that enough space around the plate type heat exchanger is kept free for servicing of the unit renewal of plates tightening of the package As the free space around the unit should be 1 5 to 2 x the width of the unit 6 1 Transport lifting and storage Transport WARNING To prevent personal injury always use appropriate hoisting equipment If you are to lift the heat exchanger itself straps should be used They should be placed as shown on the picture j p 2 Lifting Usually the heat exchanger will be supplied on a pallet The back side of the head will then be tightened to the pallet This allows you to transport the unit by means of a fork lift truck Rising of the unit Remove all tightening elements from the pallet straps around one bolt on each side as shown on the picture Never use steel cables or chains Lift the heat exchanger from the pallet Lower the heat exchanger slowly to horizontal and on its feet and place it in its end position on the floor Remove the straps and tighten the heat exchanger to the floor Never lift the heat exchanger by using the connections or studs around them Attention ALWAYS Use the lifting eyes if fitted Lift the top side of the head Attach the straps to the bolts close to the head NEVER Lift using the connections Lift the follower Lift using an intermediate
11. e pipe work for possible air traps 22 For nearly all leakage problems it will be necessary to dismantle the unit before any attempts to rectify the fault can be made Mark the area s where the leakage seems to be with a felt tip marker or similar before taking apart the exchanger Cold leakage is caused by a sudden change in temperature The sealing properties of certain elastomers are temporarily reduced when the temperature changes suddenly No action is required as the gaskets should re seal after the temperature has stabilised Gasket failures are generally a result of old age excessive exposure to ozone high operating temperature above the temp limit of the material exposure to pressure surges chemical attack physical damage resulting from poor assembly practise or damage resulting from a misaligned plate check the hanging system at the top of the plate for distortion Decrease in performance ts generally a result of plate surfaces require cleaning or de scaling pumps or associated controls have failed plate channels blocked liquid flows not as per design specification associated chiller cooling tower boiler under sized cooling water temperature to the exchanger is higher than the design heating media temperature to the exchanger is lower than the design steam flow not sufficient control valve malfunction steam trap broken or jammed unit becomes filled with condensate plate package has
12. ect see fig 11 Fig 11 Packing replacement Clip on gaskets This type of gasket Sonder Snap and Sonder Lock new generation glue free gasket require no adhesive They are located by pushing the gasket fully down into the gasket groove The gaskets are held in place by the interference fit narrowed portions of the gasket groove are pressed to ensure a secure fit Make sure groove and gasket are clean Glue type gaskets The surfaces need to be clean and free of oil Only use chloride free glues like Pliobond 20 or 30 Bostic 1782 EC 1099 and Bond Spray 77 Follow the instructions of the manufacturer these will be printed on the cover of the glue CAUTION When using commercial solvents and adhesives follow the manufacturers recommendations carefully as many of these materials are hazardous 19 8 7 O rings Make sure that the flat side of the O ring fits into the special packing groove of the plate If the O ring is not provided with a flat side the thinnest side of the O ring needs to be fitted into the groove It can be necessary to use a little glue for positioning the O ring during assembly of the heat exchanger Rubber liners On some model types the rubber frame plate nozzle liners have an O ring moulded into the liner itself This moulded O ring fits into the gasket groove in the first plate Therefore if new gaskets have been fitted the O ring portion of the gasket around the nozzle hole wil
13. ks forming connections between the different sections Two connections can be placed in the same corner block having connection to two different sections in the plate heat exchanger For the exact application of your plate type heat exchanger please check the documentation which was supplied with the heat exchanger The SONDEX plates are designed in such a way that they can be used both as right and as left plates The plates just have to be turned 180 Right and left plates On a right plate the flow runs from hole 2 to hole 3 or reverse from hole 3 to hole 2 On a left plate the flow runs from hole 1 to hole 4 or reverse from hole 4 to hole 1 The opening of the corner holes are described in a plate code index For instance 1234 means that all corner holes are open Every plate can be identified by the packing configuration the plate code index and thermal short or thermal long execution es Plate t t j 4 7777 7 Yj Y Vi ff 7 A ARRA E ee Right hand flow plate with gasket Thermal short plate Left hand flow plate with gasket End plate with gasket Thermal long plate D 4 N ON 2 O WN 1 gy i lt 7 4 gt s z m i p ki ee A a 10 6 INSTALLATION 6 1 Requirements to th
14. l have to be cut off prior to assembly back into the frame Tightening of the plate package and pressure testing Lightly oil the tie bolt threads Do not allow oil or grease onto the gaskets or the gasket seating faces on the back of the plates Wet or contaminated plates can become misaligned during tightening In this case dismantle clean and dry all areas in contact with the gaskets Evenly tighten all bolts in the correct order refer page 17 fig 10 We advise the use of ratchet spanners Ensure clamping is as uniform as possible thus keeping the frames and plates parallel throughout the operation Avoid skewing the frame plates by more than 5 mm Tightening is complete when the distance between the inside faces of both frame plates equals the A distance as shown on the contract drawing see fig 12 This tightening distance can also be calculated using the following formula Assembly distance No of plates x plate thickness coefficient The coefficients vary depending on the model type If in doubt please check with the relevant SONDEX Sales Office Finally check that all bolts are in tension and clean any spilt oil off the frame plates On completion the unit can be pressure tested test pressure 1s stated on the name plate Fig 12 20 8 8 If dimension A is not reached with application of maximum tightening torque check the number of plates and dimension A on the datasheet check th
15. l valves and mechanisms only Before start up Ensure that the steam control valve is fully closed Ensure that the heat exchanger is fully drained of condensate Start cold circuit first then the steam side Open steam control valve slowly this prevents water hammer of any condensate in the steam line and reduces the pressure thermal shock to the exchanger Ensure that the steam trap is correctly sized to allow full condensate discharge this prevents water clogging inside the exchanger Check for proper operation Check for pressure pulses in the system caused by the pumps or control valves If found stop operation and rectify Continuous pressure pulses will result in fatigue failure of the plates Visually check the unit for leakages Check that all vents are closed to prevent air being sucked into the system When in operation the conditions should not be changed The max conditions specified on the identification name plate should not be exceeded Shut down for a short period If the plate type heat exchanger has to be shut down for a short period please follow the following procedure Slowly close the control valve in the hot circuit whilst maintaining the full flow in the cold circuit Switch off the hot circuit pump Cool down the heat exchanger to the level of the cold medium Slowly close the control valve in the cold circuit Switch off the cold circuit pump Close all
16. necting flanges and isolate the heat exchanger from the system CONSTRUCTION Upper bar Dell Frame The heat exchanger consists of a frame plate Head a pressure plate Follower a carrying bar a lower bar and a column Tightening bolts are used to press the plates together This 15 depending on the type of heat exchanger and can be different in some applications 22 5 3 Column Plates The plate package consists of plates with a groove along the rim of the plate and around the ports The number of plates is as well as size and dimension dependant on the thermal output required Depending on the application stainless steel or titanium plates might be used Gaskets The groove provided in the plates holds the special gasket The purpose of this gasket is to prevent intermixing of the media and leakage to the outside The gaskets are selected to suit the actual combination of temperature chemical environment and possible other conditions to be considered They can be supplied in Viton Nitrile or EPDM The following types of packings are being used in our plate type heat exchangers Glue gaskets Clip on gaskets Sonder Lock gaskets new generation Clip on gasket Clip on gasket Sonder Lock gasket 5 4 Special applications If the plate heat exchanger works with several fluids at the same time it can be necessary to insert intermediate frames The intermediate frames are equipped with corner bloc
17. o take the necessary protective measures depending on the nature of your process or circumstances related to it at your plant Please note that our plate type heat exchangers are especially designed and built for the operating conditions pressures temperatures capacities and type of fluids provided by the customer Sudden pressure peaks beyond the normal operating pressure or pressure surges which can occur during starting up or stopping of the system can severely damage the heat exchanger and should be prevented SONDEX can not be held responsible for any damage as a result of any operation deviating from the original design conditions If you wish to alter the design conditions please contact us You may only commission the heat exchanger under the modified conditions after inspection and written approval by SONDEX Also the name plate on the heat exchanger will be adapted Precautions All potential personal injury hazards are identified by safety alert symbol non harm can be caused by burning as a result of touching the heat exchanger or other parts of the installation the uncontrolled release of pressurized media with which the danger of burning and other injuries is present contact with chemicals touching sharp edges of the installation Damage to equipment can be caused by external forces corrosion chemical action erosion water hammer thermal and or mechanical shock
18. olute care and never add abrasives If the cover is thick from scale or organic material the plates can be put ina barrel with qualified cleaning material Before fitting chemical cleaned plates they need to be thoroughly rinsed with fresh water Important Cleaning is an important part influencing the effectiveness of the plate heat exchanger Insufficient cleaning can have the following results too low circulation flow insufficient thermal output life time of the heat exchanger will be shortened If a plate has to be renewed because of serious damage one should make sure that the plates next to this plate are also being replaced 18 4 i fi J s 8 5 99 8 6 Plate replacement The plates must be clean dry and free from oil or grease If there are any oil deposits on the gaskets or on the gasket seating area then there is a strong likelihood that the plates shall slip out of place when the unit is being tightened If the gaskets are contaminated with dirt or grit then these could cause leakage make sure that all seating areas are flat clean and undamaged always use new gaskets Correct Fit the plates according to the Plate Sequence Sheet ensure all gaskets face towards the fixed head frame plate Wrong Alternate between left and right handed plates if the plate edges form a regular honeycomb pattern the left right hand sequence is corr
19. plate Lift with a strap attached close to the follower Storage Should it be necessary to store the heat exchanger for a longer period 1 month or more certain precautions should be taken in order to prevent unnecessary damage to the equipment Preferably the heat exchanger should be stored inside in a room with a temperature around 15 to 20 C and a humidity of max 70 If this is not possible place the heat exchanger in a wooden case which is provided with a lining on the inside against penetration of moisture There should absolutely not be any ozone producing equipment in the room like electric motors or arc welding equipment since ozone destroys many rubber materials Also do not store organic solvents or acids in the room and avoid heat or ultraviolet radiation 6 2 Installing the pipe connections Depending on the type the SONDEX plate type heat exchanger will be provided with flanges couplings threaded pipes etc When connecting the pipe system to the heat exchanger make sure that no stress or strain is imposed by the pipe system on to the heat exchanger We advise you of the following Heavy pipe work needs to be supported This will prevent heavy forces onto the heat exchanger Always install flexible connections on to the follower to prevent vibrations on to the heat exchanger These flexible connections also prevent expansion of the pipe work caused by temperature influence onto the heat exchanger
20. plates Plate replacement Gasket replacement Tightening of the plate pack and pressure testing Maintenance of the heat exchanger PROBLEM SOLVING AFTER SALES SERVICE Ordering parts Modifications to the heat exchanger Contacts 4 1 GENERAL Identification of the heat exchanger All plate type heat exchangers supplied by SONDEX are provided with a name plate On this plate the following details are specified type of heat exchanger year of manufacture manufacturing number nominal capacity in kW transmission area in m max working pressure in bar test pressure in bar max working temperature in C assembling measure in mm Fig 1 4 2 4 3 Correct operation This user manual provides information and instructions for correct and safe operation of the unit Many accidents are caused by incorrect use It is essential that you study the instructions carefully and above all ensure the availability to those who install maintain and operate the apparatus on a daily basis This manual will be of no value if it is not available at the time when your staff needs it Should you have a problem with your SONDEX Heat Exchanger which is beyond the scope of this manual do not hesitate to contact us The installation should not be put into operation before all indistinctnesses have been solved To avoid injuries and damages follow the instructions and local applicable safety regulations Als
21. remaining isolating valves Shut down for a long period If the unit is to be taken off line for an extended period of time then the following procedure can be followed Allow unit to cool down Drain all circuits Lubricate tie bolts Loosen tie bolts until the plate pack is relaxed max a size 10 The tie bolts should not be removed or loosened to such an extent that dirt is allowed to enter in between the plates We recommend that a warning notice 1s attached to the exchanger to remind personnel that the tie bolts need adjustment before the unit can be put back into service Cover the plate pack with black plastic to exclude any sun light Please also see chapter 6 1 Storage 15 8 MAINTENANCE 8 1 Clean in place CIP CIP cleaning clean in place To use CIP cleaning it is a condition that the scaling on the plates is soluble All materials in the whole circulation system of course have to be resistant to the cleaning detergent We advise you to ask for a confirmation from the supplier of the cleaning detergent that it will not damage the materials in the heat exchanger 8 2 If the solution requires recirculation select a flow that is as high as possible and certainly no less than the service or product flows Follow the instructions as given by the detergent supplier cleaning specialist We suggest that for recirculated cleaning detergent methods the fluid should be pumped th
22. ressures temperatures capacities and type of fluids provided by the customer Sudden pressure peaks beyond the normal operating pressure or pressure surges which can occur during starting up or stopping of the system can severely damage the heat exchanger and should be prevented SONDEX can not be held responsible for any damage as a result of any operation deviating from the original design conditions If you wish to alter the design conditions please contact us refer page 24 You may only commission the heat exchanger under the modified conditions after inspection and written approval by SONDEX Also the name plate on the heat exchanger will be adapted 3 SAFETY ALERT NOTICES Refer to applicable SAFETY ALERT notices within the manual All SAFETY ALERT notices are applicable to personal injury and identified by the following symbol 10 4 1 4 3 5 1 oe 5 3 5 4 10 1 10 2 10 3 CONTENTS FOREWORD INTRODUCTION SAFETY ALERT NOTICES GENERAL Identification of the heat exchanger Correct operation Cautions CONSTRUCTION Frame Plates Gaskets Special executions INSTALLATION Requirements to the installation area Transport lifting storage Installing the pipe connections COMMISSIONING OPERATION Commissioning and pre checks Operation Shut down for a short period Shut down for a long period MAINTENANCE Clean in place CIP Some cleaning detergents Opening the heat exchanger Cleaning the
23. rough the exchanger for no less than 30 minutes Rinsing After using any type of cleaning agent always rinse thoroughly with fresh water If cleaning in place then circulate fresh water for at least 10 minutes Some cleaning detergents Oil and grease can be removed with a water emulsifying oil solvent 1 e BP system Organic and grease cover can be removed with sodium hydroxide NaOH maximum concentration 1 5 max temp 85 C Mixture for 1 5 concentration 5 ltr 30 NaOH per 100 ltr water Stone and limestone can be removed with nitric acid HNO3 max concentration 1 5 max temp 65 C Mixture for 1 5 concentration 2 4 ltr HNO3 62 100 Itr water Nitric acid also has an affective build up effect on the passivation film of stainless steel exposed skin eyes and mucous membranes Use of protective eyewear 0 CAUTION Nitric acid and Sodium Hydroxide may cause injury to and gloves is strongly recommended 16 8 3 Opening the heat exchanger When opening and assembling the heat exchanger observe the following Measure and note the actual a size Use the correct tools and lubricant Shut down the heat exchanger as described under 7 3 Make sure the heat exchanger cools down lt 40 C with EPDM lt 20 C Ensure there is no pressure on any part of the unit Clean the clamping bolts and grease them Loosen the clamping bolts equally in the correct order fig 10 1 th
Download Pdf Manuals
Related Search
Related Contents
Sony Mobile Communications AB - Ignition Online-Shop 記入例 取扱説明書 - KDDI AR-7H - Alto-Shaam, Inc. The User Guide PCV-L630 Copyright © All rights reserved.
Failed to retrieve file