LabWindows/CVI PID Control Toolkit User Manual
Contents
1. E LeadLag Demo m Lag Time 4002 Lead Time 0 00 Waveform Type Square 0 38 Sine 0 00 Input 46 21 Output Timer Interval Figure 4 4 The User Interface of the Lead Lag Example Hardware Examples PID with MIO Board Example The PID with MIO board example turns the computer into a single loop PID controller when you use an NI DAQ device Connect the analog output to the analog input through the resistor capacitor network Note You must have the appropriate hardware to run this example The pin numbers shown correspond to the standard MIO pinouts such as a standard 50 pin cable from an E Series DAQ device National Instruments Corporation 4 5 LabWindows CVI PID Control Toolkit User Manual Chapter 4 Process Control Examples MIO Board 10 0 Device 4 1 Input Channel 4 0 amp 0 Dutput Channel 4 0 2 0 Kp Ti 3200000 0 0080 2 0 Td 00060 6 0 Apply Autotune Result 10 0 0 EH 300 Setpoint Timer Interval 0 00000 Process Variable itor Network Schematic up this network assumes MIO E series DAQ board pinouts alues are not critical at all Feel free to iment with other networks Figure 4 5 The User Interface of the MIO Board Example This example adjusts the analog output so that the input PV equals the SP The example displays the SP and PV on a strip chart You can experiment with different co
2. Complete the following steps to perform the open loop tuning procedure 1 Put the controller in manual mode set the output to a nominal operating value and allow the PV to settle completely Record the PV and output values 2 Make a step change in the output Record the new output value 3 Wait for the PV to settle From the chart determine the values as derived from the sample displayed in Figure 3 1 The variables represent the following values Td Deadtime in minutes T Time constant in minutes e K Process gain change in PV change in output asso rae ses ere en sss seass lt ILL 63 2 Max Min Zi PV VA asas l i 4 T Figure 3 1 Output and Process Variable Strip Chart 4 Multiply the measured values by the factors shown in Table 3 2 and enter the new tuning parameters into your controller Table 3 2 provides the proper values for a quarter decay ratio If you want less overshoot reduce the gain K National Instruments Corporation 3 3 LabWindows CVI PID Control Toolkit User Manual Chapter 3 Using the PID Control Toolkit Table 3 2 Factors for Determining Tuning Parameter Values Open Loop Controller PB Percent Reset Minutes Rate Minutes P 100 KT T PI 110 KT T 3 33 Ty PID 80 KT T 2 00 Ty 0 50 Ty Using the PID Library The following sections describe how to use the PID Library
3. It is not necessary to switch off the existing controller and perform the experiment under open loop conditions In the setpoint relay experiment the SP signal mirrors the SP for the PID controller LabWindows CVI PID Control Toolkit User Manual 2 8 ni com Using the PID Control Toolkit This chapter contains the basic information you need to design a control strategy using the PID Control Toolkit functions Designing a Control Strategy When you design a control strategy sketch a flowchart that includes the physical process and control elements such as valves and measurements Add feedback from the process and any required computations Then use the PID Control Toolkit functions to translate the flowchart into an application You can handle the inputs and outputs using DAQ devices FieldPoint I O modules GPIB boards or serial I O ports You can adjust polling rates in real time Potential polling rates are limited only by your hardware Setting Timing According to control theory a control system must sample a physical process at a rate that is approximately 10 times faster than the fastest time constant in the physical process For example a time constant of 60 s is typical for a temperature control loop in a small system In this case a cycle time of 6 s is sufficient Faster cycling offers no improvement in performance Corripio 1990 The PID control feature lead lag feature and setpoint profile feature in the
4. It is not necessary to adjust Lag because the lag time is time aware LabWindows CVI PID Control Toolkit User Manual 4 2 ni com Chapter 4 Process Control Examples Manual Automatic Control Example This example is an extension of the general PID simulator that demonstrates switching between automatic and manual modes E Manual Automatic Control m o 100 0 Plant Parameters Static Gain Load 60 0 225 4000 Dead Cycles Dead Band 20 0 4 20 Lag Noise rd 1 00 4025 60 0 Pid Parameters 100 0 Kp Ti 232 2000 00150 EY j 50 00 Setpoint Td 2500 0 00 2500 60 72258 Process Variable 1 0 0010 50 00 4 50 00 93 70512 Controller Output aoe rf Manual 100 00 100 00 Off 0n Timer Interval LoopBackT ype 3 0 10 Simulator Figure 4 2 The User Interface of the Manual Automatic Control Example Use the Manual switch to switch between the two modes When the PID controller is in manual mode you can use the Manual Control knob to control the PID controller output At any time you can change the controller to automatic mode by turning the Manual switch off The transition between the manual and automatic modes is bumpless and smooth National Instruments Corporation 4 3 LabWindows CVI PID Control Toolkit User Manual Chapter 4 Process Control Examples Gain Scheduling Example This example is an extension of the general
5. PID Control Toolkit are time dependent A component can acquire the timing information either from a value you supply to the pidAttrDeltart attribute or from the built in internal timer By default the pidAttrUseInternalTimer attribute is set to 1 so the component uses the internal timer Call PidSetAttribute and PidGetAttribute to set and get PID controller attributes The internal timer calculates new timing information each time PidNextOutput is called When the function is called the timer determines the time since the last call to PidNextOutput and uses that time difference in its calculations Note The internal timer uses the Windows SDK GetTickCount function Therefore do not try to run the PID loops faster than 5 or 10 Hz when you use the internal timer National Instruments Corporation 3 1 LabWindows CVI PID Control Toolkit User Manual Chapter 3 Using the PID Control Toolkit You can set the component to use the value you have supplied to the pidAttrDeltaT attribute by setting pidAttrUseInternalTimer to 0 Use the p dAttrDeltaT attribute for fast loops including instances in which you use acquisition hardware to time the controller input Refer to the samples pid Hardware Timed Pid HardwareTimedPid pr j example program which illustrates how to use hardware timing in DAQ with PID control for more information Tuning Controllers Manually The following controller tuning procedures are based on the work of Ziegler and N
6. in it EXCEPT AS SPECIFIED HEREIN NATIONAL INSTRUMENTS MAKES NO WARRANTIES EXPRESS OR IMPLIED AND SPECIFICALLY DISCLAIMS ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE CUSTOMER S RIGHT TO RECOVER DAMAGES CAUSED BY FAULT OR NEGLIGENCE ON THE PART OF NATIONAL INSTRUMENTS SHALL BE LIMITED TO THE AMOUNT THERETOFORE PAID BY THE CUSTOMER NATIONAL INSTRUMENTS WILL NOT BE LIABLE FOR DAMAGES RESULTING FROM LOSS OF DATA PROFITS USE OF PRODUCTS OR INCIDENTAL OR CONSEQUENTIAL DAMAGES EVEN IF ADVISED OF THE POSSIBILITY THEREOF This limitation of the liability of National Instruments will apply regardless of the form of action whether in contract or tort including negligence Any action against National Instruments must be brought within one year after the cause of action accrues National Instruments shall not be liable for any delay in performance due to causes beyond its reasonable control The warranty provided herein does not cover damages defects malfunctions or service failures caused by owner s failure to follow the National Instruments installation operation or maintenance instructions owner s modification of the product owner s abuse misuse or negligent acts and power failure or surges fire flood accident actions of third parties or other events outside reasonable control Copyright Under the copyright laws this publication may not be reproduced or transmitted in any form electronic or mechanical includi
7. k umin The following formula shows the practical model of the PID controller K SP P Wm peu u t SP n rJ The PID functions use an integral sum correction algorithm that facilitates anti windup and bumpless manual to automatic transfers Windup occurs at the upper limit of the controller output for example 100 When the error e decreases the controller output decreases moving out of the windup area The integral sum correction algorithm prevents abrupt controller output changes when you switch from manual to automatic mode or change any other parameters The default ranges for the SP PV and output parameters correspond to percentage values however you can use actual engineering units If you use engineering units you must adjust the corresponding ranges accordingly The 7 and parameters are specified in minutes In manual mode you can change the manual input to increase or decrease the output All the PID control functions are reentrant Multiple calls from high level functions use separate and distinct data hy Note As a general rule manually drive the PV until it meets or comes close to the SP before you perform the manual to automatic transfer Gain Scheduling Gain scheduling refers to a system in which you change controller parameters based on measured operating conditions For example the scheduling variable can be the SP the PV a controller output or an external signal For hist
8. loop after each increment As you increase K the value of the PV should begin to oscillate Keep making changes until the oscillation is sustained neither growing nor decaying over time Record the controller proportional band PB as a percent where PB 100 K 4 Record the period of oscillation T in minutes Multiply the measured values by the factors shown in Table 3 1 and enter the new tuning parameters into your controller Table 3 1 provides the proper values for a quarter decay ratio If you want less overshoot increase the gain K Note Proportional gain K is related to proportional band PB as follows K 100 PB LabWindows CVI PID Control Toolkit User Manual 3 2 ni com Chapter 3 Using the PID Control Toolkit Table 3 1 Factors for Determining Tuning Parameter Values Closed Loop Controller PB Percent Reset Minutes Rate Minutes P 2 00 PI 2 22 0 83 T PID 1 67 0 50 T 0 125 T Open Loop Step Test Tuning Procedure The open loop step test tuning procedure assumes that you can model any process as a first order lag and a pure deadtime This method requires more analysis than the closed loop tuning procedure but the process does not need to reach sustained oscillation Therefore the open loop tuning procedure might be quicker and more reliable for many processes Observe the output and the PV on a strip chart that shows time on the x axis
9. percentage The lead lag compensator coerces the controller output to the specified range LabWindows CVI PID Control Toolkit User Manual 3 8 ni com Chapter 3 Using the PID Control Toolkit For more information refer to the samples pid Lead Lag LeadLag prj example program Using PID with Setpoint Profiling Using the setpoint profiling feature you can generate a profile of setpoint values over time for a ramp and soak type PID application For example you might want to ramp the setpoint temperature of an oven control system over time and then hold or soak the setpoint at a certain temperature for another period of time Use this feature to implement any arbitrary combination of ramp hold and step functions Provide setpoint time pairs to the setpoint profile The setpoint profile maintains the setpoint specified in each pair for the corresponding times specified in the time array You can use the setpoint profiler as follows 1 Call PidSetpointProfileCreate to create a setpoint profile Use a pair of time and setpoint value arrays to specify the setpoint profile with the time values in ascending order 2 Use PidSetSetpointProfileAttribute to set the setpoint profile attributes Use PidSetpointProfileNextSetpoint to obtain the setpoint from the profile in a loop and provide this setpoint to the controller 4 the control loop ends call PidSetpointProfileDiscard to discard the setpoint profile and release its
10. provided to the controller This step is optional and required only in cases in which the controller input is derived from the acquired DAQ input c Supply this input to the controller and obtain the controller output d Modify manipulate the controller output so that it can be output on the DAQ device This step is optional and required only in cases in which the output on the DAQ device is derived from the controller output e Write the output to the DAQ device 4 Discard the controller to release its resources Also clear all the DAQ tasks In some cases just before clearing the DAQ tasks the DAQ device outputs a 0 The control loops can be timed in the following ways e Software Timed In software timed control loops the timing is controlled by the loop To increase the timing insert a delay at the end of the loop e Hardware Timed lIn hardware timed control loops the timing is controlled by the DAQ device The DAQ device is configured with the appropriate sample rate and the sample mode is set to hardware timed For more information about DAQ refer to the NI DAQmx Help or Traditional NI DAQ Legacy C Function Reference Help depending on the DAQ API you are using Also refer to the DAQ example programs National Instruments Corporation 3 11 LabWindows CVI PID Control Toolkit User Manual Process Control Examples This chapter describes examples that use the PID Control Toolkit for LabWindows CVI which are
11. resources Also call PidDiscard to discard the PID controller At any time in the control loop you can use pidSetpointProfileAttrElapsedTime to get the elapsed time You also can check if the profile is complete using the pidSetpointProfileAttrProfileComplete attribute For more information refer to the samples pid Setpoint Profiling SetpointProfiling prj example program Using Ramp Generators A ramp generator is a simple component that you can use to generate a ramp output Typically you use a ramp generator as follows 1 Call PidRampCreate to create a ramp generator Specify the SP initial output and the rate at which the output of the ramp changes 2 Call PidSetRampAttribute to set the ramp generator attributes Use PidRampNextOutput to obtain the output of the ramp in a loop 4 Call PidRampDiscard to discard the ramp generator and release its resources National Instruments Corporation 3 9 LabWindows CVI PID Control Toolkit User Manual Chapter 3 Using the PID Control Toolkit Converting between Percentage of Full Scale and Engineering Units 5 As described the previous sections the default SP PV and output ranges for PID Library functions correspond to a percentage of the full scale Proportional gain K relates percentage of full scale output to percentage of full scale input This is the default behavior of many PID controllers used for process control applications To implement PID in this wa
12. to implement a control strategy PID Controller The PID controller requires several inputs including SP PID gains timer interval in case the internal timer is not used PV and output range PID gains include proportional gain integral time and derivative time The following steps provide an overview of typical PID controller use 1 Provide the PID gains to PidCreate to create a PID controller PidCreate returns a handle that you can use to identify the PID controller in subsequent function calls 2 UsePidSetAttribute to set the PID controller attributes such as SP time interval minimum and maximum controller output values and so on 3 Provide the PV to the controller in a loop and use PidNextOutput to obtain the controller output which is again applied on the system 4 Once the control loop ends call PidDiscard to discard the PID controller and free its resources You can call PidSetAttribute with the pidAttrOutputMin and pidAttrOutputMax attributes to specify the range of the controller output The default range is 100 to 100 which corresponds to values specified in terms of percentage of full scale However you can change this range so that the controller gain relates engineering units to engineering units instead of percentage to percentage The PID controller coerces the controller output to the specified range In addition the PID controller implements integrator anti windup when the controller output is sat
13. 4 759 68 National Instruments Corporation A 1 LabWindows CVI PID Control Toolkit User Manual Technical Support and Professional Services Visit the following sections of the National Instruments Web site at ni com for technical support and professional services Support Online technical support resources at ni com support include the following Self Help Resources For answers and solutions visit the award winning National Instruments Web site for software drivers and updates a searchable KnowledgeBase product manuals step by step troubleshooting wizards thousands of example programs tutorials application notes instrument drivers and so on Free Technical Support All registered users receive free Basic Service which includes access to hundreds of Application Engineers worldwide in the NI Developer Exchange at ni com exchange National Instruments Application Engineers make sure every question receives an answer For information about other technical support options in your area visit ni com services or contact your local office at ni com contact Training and Certification Visit ni com training for self paced training eLearning virtual classrooms interactive CDs and Certification program information You also can register for instructor led hands on courses at locations around the world System Integration If you have time constraints limited in house technical resources or other project challen
14. 4 damping ratio normal some overshoot or slow little overshoot Refer to the following tuning formula tables for each type of loop performance Table 2 1 Tuning Formula under P Only Control Fast Controller K T Ta P 0 5K PI 0 4K 0 8T PID 0 6K 0 5T 0 12 LabWindows CVI PID Control Toolkit User Manual 2 6 ni com Chapter 2 PID Algorithms Table 2 2 Tuning Formula under P Only Control Normal Controller K T Ta P 0 2K PI 0 18K 0 8T PID 0 25K 0 5T 0 12 Table 2 3 Tuning Formula under P Only Control Slow Controller K Ta P 0 13K PI 0 13K 0 8T PID 0 15K OST 0 127 Table 2 4 Tuning Formula under or PID Control Fast Controller K T Ta P T t PI 0 9 3 331 PID LATA 2 01 0 5 Table 2 5 Tuning Formula under PI or PID Control Normal Controller K T Ta P 0 44 PI 0 47 t 5 331 PID 0 53T 1 4 01 0 81 National Instruments Corporation LabWindows CVI PID Control Toolkit User Manual Chapter 2 PID Algorithms Table 2 6 Tuning Formula under PI or PID Control Slow Controller K Ti Ta P 0 26T 1 PI 0 24T 1 5 331 PID 0 32T 1 4 01 0 81 3 Note During tuning the process remains under closed loop PID control
15. D Control Toolkit User Manual System Requirements Your computer must meet the following minimum system requirements to run the PID Control Toolkit LabWindows CVI 7 0 or later e Windows 2000 XP Installation Instructions If you install the PID Control Toolkit on a computer that has multiple versions of LabWindows CVI installed the toolkit is installed with the latest version Also if you already have an earlier version of the LabWindows CVI PID Control Toolkit installed on your computer you must uninstall it before installing this version of the PID Control Toolkit Complete the following steps to install the PID Control Toolkit 1 Insert the PID Control Toolkit CD into the CD ROM drive 2 Click Install Toolkit 3 Follow the instructions on the screen When the PID Control Toolkit has been successfully installed click Finish National Instruments Corporation 1 1 LabWindows CVI PID Control Toolkit User Manual Chapter 1 Overview of the PID Control Toolkit PID Control Toolkit Applications The PID Control Toolkit contains functions you can use to develop LabWindows CVI control applications For more information about the types of applications you can develop refer to the example programs that are installed with the toolkit These examples are described in Chapter 4 Process Control Examples PID Control Currently the Proportional Integral Derivative PID algorithm is the most common control algorithm use
16. ID Algorithms Implementing the PID Algorithm with the PID Functions This section describes how the PID functions implement the positional PID algorithm Error Calculation The following formula represents the current error used in calculating proportional integral and derivative action e k SP PV Proportional Action Proportional action is the controller gain times the error as shown in the following formula up k K e k Trapezoidal Integration Trapezoidal integration is used to avoid sharp changes in integral action when there is a sudden change in the PV or SP Use nonlinear adjustment of the integral action to counteract overshoot The following formula represents the trapezoidal integration action um y eres e i Dr izl Partial Derivative Action Because of abrupt changes in the SP only apply derivative action to the PV not to the error to avoid derivative kick The following formula represents the partial derivative action T up 27 PV GO PVAE D Controller Output Controller output is the summation of the proportional integral and derivative action as shown in the following formula u k up k uj k up K LabWindows CVI PID Control Toolkit User Manual 2 2 ni com Chapter 2 PID Algorithms Output Limiting The actual controller output is limited to the range specified for control output as follows if u k gt u max then u k u max and If u K lt u then u
17. INCLUDING WITHOUT LIMITATION THE APPROPRIATE DESIGN PROCESS AND SAFETY LEVEL OF SUCH SYSTEM OR APPLICATION Contents About This Manual Cony nf oh S 355555 bss bas Beek cues ben Vil Related Documentation vii Chapter 1 Overview of the PID Control Toolkit Package Contents eeiam It enter br e eo oe ede lee EX epo edad 1 1 System Requirements teet eet pensis 1 1 Installation Instructions 1 1 PID Control Toolkit Applications eese nennen 1 2 PID Control e UG ES iP Rte Ie P ER eR I ERES 1 2 Chapter 2 PID Algorithms tita fee ee ree e o eee teer e pe Dre edes 2 1 Implementing the PID Algorithm with the PID Functions 2 2 Gain Scheduling eee eto epe e te ORE Cnr 2 3 The Precise PND Algorithm eere tite ee eR Ire e eene 2 4 Error Calculation iode e e bete 2 4 Proportional ACh OM e ert eee e erae tiene e Tee eset 2 4 Trapezoidal eene 2 5 The A totunin oi Ete P E Oen eet 2 5 Tuning ineo teet da teet ad dens 2 6 Chapter 3 Using the PID Control Toolkit Desigmng a Control Strategy er tee pe rp mne 3 1 Setting Timing eee UG ERE Le re PETERE LEER e TR tastes 3 1 Tuning Controllers Manually pe 3 2 Using th PID Tei Dray e e ote ere cene e o ed dee d Hed 3 4 PUD Controller ep rt tete 3 4 Using PID with Auto
18. LabWindows CVI PID Control Toolkit User Manual November 2005 4 NATIONAL 371685A 01 INSTRUMENTS Worldwide Technical Support and Product Information ni com National Instruments Corporate Headquarters 11500 North Mopac Expressway Austin Texas 78759 3504 USA Tel 512 683 0100 Worldwide Offices Australia 1800 300 800 Austria 43 0 662 45 79 90 0 Belgium 32 0 2 757 00 20 Brazil 55 11 3262 3599 Canada 800 433 3488 China 86 21 6555 7838 Czech Republic 420 224 235 774 Denmark 45 45 76 26 00 Finland 385 0 9 725 725 11 France 33 0 1 48 14 24 24 Germany 49 0 89 741 31 30 India 91 80 51190000 Israel 972 0 3 6393737 Italy 39 02 413091 Japan 81 3 5472 2970 Korea 82 02 3451 3400 Lebanon 961 0 1 33 28 28 Malaysia 1800 887710 Mexico 01 800 010 0793 Netherlands 31 0 348 433 466 New Zealand 0800 553 322 Norway 47 0 66 90 76 60 Poland 48 22 3390150 Portugal 351 210 311 210 Russia 7 095 783 68 51 Singapore 1800 226 5886 Slovenia 386 3 425 4200 South Africa 27 0 11 805 8197 Spain 34 91 640 0085 Sweden 46 0 8 587 895 00 Switzerland 41 56 200 51 51 Taiwan 886 02 2377 2222 Thailand 662 278 6777 United Kingdom 44 0 1635 523545 For further support information refer to the Technical Support and Professional Services appendix To comment on National Instruments documentation refer to the National Instruments Web site at ni com info and enter the info code feedback 2005 National Instruments Corporation All rights res
19. PID simulator that demonstrates the gain scheduling capability of the PID Control Toolkit G p Gain Scheduling Pid o 100 0 Plant Parameters Load 2 Lag gum 4 4000 Dead Cycles DeadBand Noise 20 0 p 32 00 4025 Gain Schedule 1 7500 0 0050 0 0005 30 0000 100 0 2 0000 0 0100 0 0010 60 0000 0 4 3000 Setpoint Current Gains 30 00003 Process Variable Gain Schedule Criteria GSV Kp 1 7500 0 00002 Controller Output 1 Setpoint 4 20 00 9 0050 Timer Interval Loop Back Type Figure 4 3 The User Interface of the Gain Scheduling Example By changing the SP you can observe how the PID gains change according to the gain schedule Refer to the Using PID with Gain Scheduling section of Chapter 3 Using the PID Control Toolkit for more information about how gains are scheduled You also can change the gain schedule criteria in this example LabWindows CVI PID Control Toolkit User Manual 4 4 ni com Chapter 4 Process Control Examples Lead Lag Example The Lead Lag example uses a sine wave or a square wave for excitation The waveform is synchronized to the Timer Interval you specify When you vary the tuning parameters you can see the time domain response of the Lead Lag example A large Lead Time setting causes a wild ringing on the output a large Lag Time setting heavily filters the signal making it almost disappear
20. PV to 1 By default this attribute is set to 0 You can use PidSet ProcessVariableFilter and PidGet ProcessVariableFilter to set or get custom filters As discussed in the Setting Timing section the sampling rate of the control system should be at least 10 times faster than the fastest time constant of the physical system Therefore if correctly sampled any frequency components of the measured signal that are greater than one tenth of the sampling frequency are a result of noise in the measured signal Gains in the PID controller can amplify this noise and produce unnecessary wear on actuators and other system components The filtered PV uses a low pass fifth order Finite Impulse Response FIR filter to filter out unwanted noise from input signals The cutoff frequency of the low pass filter is one tenth of the sampling frequency regardless of the actual sampling frequency value Output Rate Limiting Sudden changes in control output are undesirable or even dangerous for many control applications For example a sudden large change in the SP can cause a very large change in controller output Although in theory this large change in controller output results in fast system response it may also cause unnecessary wear on actuators or sudden large power demands In addition the PID controller can amplify noise in the system which results in a constantly changing controller output National Instruments Corporation 3 5 LabWindows CVI PID Cont
21. Y COMPUTER HARDWARE MALFUNCTIONS COMPUTER OPERATING SYSTEM SOFTWARE FITNESS FITNESS OF COMPILERS AND DEVELOPMENT SOFTWARE USED TO DEVELOP AN APPLICATION INSTALLATION ERRORS SOFTWARE AND HARDWARE COMPATIBILITY PROBLEMS MALFUNCTIONS OR FAILURES OF ELECTRONIC MONITORING OR CONTROL DEVICES TRANSIENT FAILURES OF ELECTRONIC SYSTEMS HARDWARE AND OR SOFTWARE UNANTICIPATED USES OR MISUSES OR ERRORS ON THE PART OF THE USER OR APPLICATIONS DESIGNER ADVERSE FACTORS SUCH AS THESE ARE HEREAFTER COLLECTIVELY TERMED SYSTEM FAILURES ANY APPLICATION WHERE A SYSTEM FAILURE WOULD CREATE A RISK OF HARM TO PROPERTY OR PERSONS INCLUDING THE RISK OF BODILY INJURY AND DEATH SHOULD NOT BE RELIANT SOLELY UPON ONE FORM OF ELECTRONIC SYSTEM DUE TO THE RISK OF SYSTEM FAILURE TO AVOID DAMAGE INJURY OR DEATH THE USER OR APPLICATION DESIGNER MUST TAKE REASONABLY PRUDENT STEPS TO PROTECT AGAINST SYSTEM FAILURES INCLUDING BUT NOT LIMITED TO BACK UP OR SHUT DOWN MECHANISMS BECAUSE EACH END USER SYSTEM IS CUSTOMIZED AND DIFFERS FROM NATIONAL INSTRUMENTS TESTING PLATFORMS AND BECAUSE A USER OR APPLICATION DESIGNER MAY USE NATIONAL INSTRUMENTS PRODUCTS IN COMBINATION WITH OTHER PRODUCTS IN A MANNER NOT EVALUATED OR CONTEMPLATED BY NATIONAL INSTRUMENTS THE USER OR APPLICATION DESIGNER IS ULTIMATELY RESPONSIBLE FOR VERIFYING AND VALIDATING THE SUITABILITY OF NATIONAL INSTRUMENTS PRODUCTS WHENEVER NATIONAL INSTRUMENTS PRODUCTS ARE INCORPORATED IN A SYSTEM OR APPLICATION
22. abVIEW that uses the functions exposed by the DLL you created in the previous step 3 Download the VI onto the RT target and run it Note If you are using LabWindows CVI 8 0 or later you also can download the DLL directly to the RT target without creating a VI in LabVIEW Refer to the LabWindows CVI Help for more information about downloading RT DLLs directly from LabWindows CVI Because RT systems do not support user interfaces you cannot use wizard based autotuning in PID applications that are targeted for RT platforms Any applications that are targeted for RT must not include the following functions PidAutotuneShowDialog PidAutotuneCloseDialog However you can use other functions in the Autotuning class to tune the PID controller LabWindows CVI PID Control Toolkit User Manual 3 10 ni com Chapter 3 Using the PID Control Toolkit Using PID with DAQ Devices This section addresses several important issues you might encounter when you use the DAQ APIs to control actual processes Complete the following steps to use the PID Library with a DAQ device 1 Configure the DAQ device and channels for both input and output Also configure the sample clocks if necessary 2 Call PidCreate to create the PID controller Then call P dSetAttribute to configure the controller attributes 3 Within the control loop complete the following steps Read the input from the DAQ device Modify manipulate the input so that it can be
23. algorithm tuning formulas 2 6 PI control fast 2 7 PI control normal 2 7 PI control slow 2 8 P only control normal 2 7 P only control slow 2 7 bumpless transfer 2 3 calculating controller action 2 1 classic autotuning example 3 0 closed loop tuning procedure 3 2 control strategy designing 3 1 controller action 2 1 gain 2 1 output 2 2 PID 1 2 conventions used in the manual vii Corripio A B A 1 National Instruments Corporation l 1 D DAQ devices using PID with 3 11 derivative action 2 1 derivative time 2 1 diagnostic tools NI resources B 1 distributing applications 3 7 documentation conventions used in manual vii NI resources B 1 related documentation vii drivers NI resources B 1 E engineering units converting from percentage of full scale 3 10 error calculation 2 2 examples classic autotuning 3 6 gain scheduling 3 8 4 4 general PID 4 2 hardware 4 5 hardware timed 3 2 lead lag 3 9 4 5 manual automatic control 4 3 NI resources B 1 PID with MIO board 4 5 setpoint profiling 3 9 simulation 4 1 wizard based autotuning 3 6 F fast PID algorithm 3 5 LabWindows CVI PID Control Toolkit User Manual Index G gain schedule contents 3 7 gain scheduling 2 3 3 7 example 3 8 4 4 general PID example 4 2 H hardware examples 4 5 hardware timed example 3 2 help technical support B 1 help file accessing 1 3 installati
24. allback function only when the autotuning is complete 2 Provide the PV to the controller in a loop and obtain the controller output which is again applied on the system 3 While the PID control loop is being run call PidAutotuneShowDialog if you want to use wizard based autotuning This function launches the Autotuning Wizard To use classic autotuning call the functions in the Autotuning class 4 Once the control loop ends call PidDiscard to discard the PID controller and release its resources For more information refer to the samples pid Autotuning Classic Autotuning ClassicAutotune prj and samples pid Autotuning Wizard Autotuning WizardAutotune prj example programs LabWindows CVI PID Control Toolkit User Manual 3 6 ni com Chapter 3 Using the PID Control Toolkit Distributing Applications That Use Wizard Based Autotuning Use the LabWindows CVI application distribution feature to deploy applications you create using the PID Control Toolkit The PID Control Toolkit installs cvIPIDRunt ime msm in the C Program Files Common Files Merge Modules directory This file installs CVIPIDAtUI d11 in the system directory If you deploy applications that use wizard based autotuning you must add this merge module to the distribution The version of LabWindows CVI you are using determines how you add the merge module to the distribution If you are using LabWindows CVI 7 x create a file group in the distribution kit named _mMSMS_ Inc
25. d in industry Often PID is used to control processes that include heating and cooling systems fluid level monitoring flow control and pressure control When using PID control you must specify a process variable and a setpoint The process variable is the system parameter you want to control such as temperature pressure or flow rate The setpoint is the desired value for the parameter you are controlling A PID controller determines a controller output value such as the heater power or valve position When applied to the system the controller output value drives the process variable toward the setpoint value You can use the PID Control Toolkit functions with National Instruments hardware to develop LabWindows CVI control applications Use I O hardware such as DAQ devices FieldPoint I O modules or GPIB boards to connect your PC to the system you want to control You can use the LabWindows CVI I O functions with the PID Control Toolkit to develop a control application or modify the examples provided with the toolkit Using the PID Control Toolkit functions you can develop the following control applications based on PID controllers e Proportional P proportional integral PI proportional derivative PD and proportional integral derivative PID algorithms e Gain scheduled PID e PID autotuning e Precise PID Lead lag compensation e Setpoint profile generation e Multiloop cascade control e Feedforward control e Ov
26. ed to produce a full range change in output due to proportional control action PB 100 K Pounds per square inch ni com ramp reentrant execution setpoint SP span T time constant T trapezoidal integration W windup area National Instruments Corporation G 5 Glossary The total transient plus steady state time response resulting from a sudden increase in the rate of change from zero to some finite value of input stimulus Mode in which calls to multiple instances of a function can execute in parallel with distinct and separate data storage Seconds An input variable that sets the desired value of the controlled process variable The algebraic difference between the upper and lower range values In process instrumentation the value T in minutes in an exponential response term A exp t T or in one of the transform factors such as 1 sT A numerical integration in which the current value and the previous value are used to calculate the addition of the current value to the integral value Volts The time during which the controller output is saturated at the maximum or minimum value The integral action of a simple PID controller continues to increase wind up while the controller is in the windup area LabWindows CVI PID Control Toolkit User Manual Index A applications 1 2 autotuning classic 2 6 procedure 3 6 wizard based distributing applications 3 7 autotuning
27. erride minimum maximum selector control e Ratio bias control LabWindows CVI PID Control Toolkit User Manual 1 2 ni com Chapter 1 Overview of the PID Control Toolkit Refer to the LabWindows CVI PID Control Toolkit Help which you can access by selecting Start Programs National Instruments PID Control Toolkit for CVI LabWindows CVI PID Help for more information about the functions National Instruments Corporation 1 3 LabWindows CVI PID Control Toolkit User Manual PID Algorithms This chapter explains the PID precise PID and autotuning algorithms The PID Algorithm The PID controller compares the setpoint SP to the process variable PV to obtain the error e as follows e SP PV Then the PID controller calculates the controller action u t as follows In this equation K is the controller gain u t K egens T EE If the error and the controller output have the same range 100 to 100 controller gain is the reciprocal of proportional band 7 is the integral time in minutes also called the reset time and T is the derivative time in minutes also called the rate time The following formula represents the proportional action u t K e The following formula represents the integral action K u t eat 0 The following formula represents the derivative action d up t National Instruments Corporation 2 1 LabWindows CVI PID Control Toolkit User Manual Chapter 2 P
28. erved Important Information Warranty The media on which you receive National Instruments software are warranted not to fail to execute programming instructions due to defects in materials and workmanship for a period of 90 days from date of shipment as evidenced by receipts or other documentation National Instruments will at its option repair or replace software media that do not execute programming instructions if National Instruments receives notice of such defects during the warranty period National Instruments does not warrant that the operation of the software shall be uninterrupted or error free A Return Material Authorization RMA number must be obtained from the factory and clearly marked on the outside of the package before any equipment will be accepted for warranty work National Instruments will pay the shipping costs of returning to the owner parts which are covered by warranty National Instruments believes that the information in this document is accurate The document has been carefully reviewed for technical accuracy In the event that technical or typographical errors exist National Instruments reserves the right to make changes to subsequent editions of this document without prior notice to holders of this edition The reader should consult National Instruments if errors are suspected In no event shall National Instruments be liable for any damages arising out of or related to this document or the information contained
29. expressed in units of the output or in percent of output span LabWindows CVI PID Control Toolkit User Manual Glossary 0 output limiting overshoot PD PI PID PID control PID controller process gain K process variable PV proportional action proportional band PB PSI LabWindows CVI PID Control Toolkit User Manual G 4 Preventing a controller s output from traveling beyond a desired maximum range The maximum excursion beyond the final steady state value of output as the result of an input change Proportional Proportional derivative Proportional integral Proportional integral derivative A common control strategy in which a process variable is measured and compared to a desired setpoint to determine an error signal A proportional gain P is applied to the error signal an integral gain 1 is applied to the integral of the error signal and a derivative gain D is applied to the derivative of the error signal The controller output is a linear combination of the three resulting values A controller that produces proportional plus integral reset plus derivative rate control action For a linear process the ratio of the magnitudes of the measured process response to that of the manipulated variable The measured variable such as pressure or temperature in a process to be controlled Control response in which the output is proportional to the input The change in input requir
30. g examples NI resources B 1 proportional action 2 2 precise PID algorithm 2 4 R rate time 2 1 real time targets using PID on 3 10 related documentation vii requirements system 1 1 reset time 2 1 setpoint 1 2 profiling example 3 9 relay experiment 2 6 simulation examples 4 1 software NI resources B 1 step test tuning procedure 3 3 support technical B 1 system requirements 1 1 National Instruments Corporation I 3 Index T technical support B 1 timing information acquiring 3 1 timing setting 3 1 training and certification NI resources B 1 trapezoidal integration 2 2 2 5 troubleshooting NI resources B 1 tuning procedure closed loop 3 2 open loop 3 3 step test 3 3 ultimate gain 3 2 U ultimate gain tuning procedure 3 2 W Web resources B 1 windup 2 3 wizard based autotuning distributing applications 3 7 example 3 6 Z Ziegler J G A 1 LabWindows CVI PID Control Toolkit User Manual
31. ges National Instruments Alliance Partner members can help To learn more call your local NI office or visit ni com alliance If you searched ni com and could not find the answers you need contact your local office or NI corporate headquarters Phone numbers for our worldwide offices are listed at the front of this manual You also can visit the Worldwide Offices section of ni com niglobal to access the branch office Web sites which provide up to date contact information support phone numbers email addresses and current events National Instruments Corporation B 1 LabWindows CVI PID Control Toolkit User Manual Glossary A algorithm autotuning Autotuning Wizard bias bumpless transfer cascade control closed loop controller controller output cycle time National Instruments Corporation G 1 A prescribed set of well defined rules or processes for the solution of a problem in a finite number of steps Automatically testing a process under control to determine the controller gains that will provide the best controller performance An automated graphical user interface provided in the Autotuning functions The Autotuning Wizard gathers some information about the desired control from the user and then steps through the PID autotuning process You must specify to use wizard based autotuning in PidCreateWithAutotune to use this feature The offset added to a controller s output A proce
32. ichols the developers of the Quarter Decay Ratio tuning techniques derived from a combination of theory and empirical observations Corripio 1990 Experiment with these techniques and with one of the process control simulation examples to compare them For different processes one method might be easier or more accurate than another For example some techniques that work best when used with online controllers cannot stand the large upsets described here To perform these tests set up your control strategy with the PV SP and output displayed on a large strip chart with the axes showing the values versus time Refer to the Closed Loop Ultimate Gain Tuning Procedure and Open Loop Step Test Tuning Procedure sections for more information about disturbing the loop and determining the response from the graph Refer to Tuning of Industrial Control Systems as listed in Appendix A References for more information about these procedures Closed Loop Ultimate Gain Tuning Procedure Although the closed loop ultimate gain tuning procedure is very accurate you must put your process in steady state oscillation and observe the PV on a strip chart Complete the following steps to perform the closed loop tuning procedure 1 Set both the derivative time and the integral time on your PID controller to 0 2 With the controller in automatic mode carefully increase the proportional gain in small increments Make a small change in the SP to disturb the
33. icon denotes a note which alerts you to important information Bold text denotes items that you must select or click in the software such as menu items and dialog box options Bold text also denotes parameter names Italic text denotes variables emphasis a cross reference or an introduction to a key concept Italic text also denotes text that is a placeholder for a word or value that you must supply Text in this font denotes text or characters that you should enter from the keyboard sections of code programming examples and syntax examples This font is also used for the proper names of disk drives paths directories programs subprograms subroutines device names functions operations variables filenames and extensions Related Documentation The following documents contain information that you may find helpful as you read this manual e LabWindows CVI PID Control Toolkit Help e LabWindows CVI Help e NI DAQmx Help e Traditional NI DAQ Legacy C Function Reference Help National Instruments Corporation Vii LabWindows CVI PID Control Toolkit User Manual Overview of the PID Control Toolkit This chapter lists the contents of the PID Control Toolkit for LabWindows CVI describes how to install the toolkit and describes PID control applications Package Contents The PID Control Toolkit contains the following materials e Software that includes control functions and example programs e LabWindows CVI PI
34. ing for good SP responses often yields sluggish load disturbance responses The factor b when set to less than one reduces the SP response overshoot without affecting the load disturbance response indicating the use of a Two Degree of Freedom PID algorithm B is an index of the SP response importance from zero to one For example if you consider load response the most important loop performance set to 0 0 Conversely if you want the PV to quickly follow the SP change set to 1 0 up k K eb k LabWindows CVI PID Control Toolkit User Manual 2 4 ni com Chapter 2 PID Algorithms Trapezoidal Integration Trapezoidal integration is used to avoid sharp changes in integral action when there is a sudden change in the PV or SP Use nonlinear adjustment of integral action to counteract the overshoot The larger the error the smaller the integral action as shown in the following formula and in Figure 2 1 K i azizi 1 IN ur PH aa e E rng 0 9 0 8 0 7 0 6 0 5 0 4 0 3 0 2 0 1 00 4000 750 500 250 00 250 500 750 1000 Error Figure 2 1 Nonlinear Multiple for Integral Action SP 100 The Autotuning Algorithm Use autotuning to improve performance Often many controllers are poorly tuned As a result some controllers are too aggressive and some controllers are too sluggish PID controllers are difficult to tune when you do not know the process dynamics
35. installed in the samples pid directory The examples contain both simulation and hardware examples You do not need any DAQ devices to run the simulation examples but you must have the appropriate hardware to run the hardware examples Simulation Examples The simulation examples demonstrate how to control a process that is simulated entirely in software You can use these examples to learn how to operate a PID controller without connecting the control application to a real physical process Some of the simulation examples use a plant simulator or a simple loop back type The plant simulator is used with feedback control loops Typically you can use the plant simulator as follows 1 Create a plant simulator and use PlantCreate to obtain a handle 2 Use UpdatePlant Parameters to supply the plant characteristics You can use this function to update the plant characteristics at any point 3 Within the feedback control loop use PlantNextProcessVariable to supply the output of the PID controller to the plant and obtain the new PV 4 After the feedback loop terminates use PlantDiscard to discard the plant To calculate the new PV the plant simulator scales the value provided according to the process gain It then adds noise and the resulting process response to the old level value using a first order lag filter For a simple loop back the PV within the feedback loop is calculated as follows new PV z old PV 0 2 controller ou
36. losed loop by reacting to how fast something is changing rather than its current state This process speeds up the reaction Lag compensation stabilizes a closed loop by slowing down the reaction to the present value so that the correction is made more slowly and does not overshoot This process slows down the reaction The typical usage of the lead lag follows 1 Pass gains to PidLeadLagCreate to create a lead lag compensator PidLeadLagCreate returns a handle you can use to identify the lead lag compensator in subsequent function calls 2 Use PidSetLeadLagAttribute and PidGetLeadLagAttribute to set and get the lead lag compensator attributes such as time intervals and minimum maximum output values Provide the input to the compensator in a loop and use PidLeadLagNextOutput to obtain the output This output is either applied to the system or to the controller based on whether the lead lag is being used as an input or an output filter 3 Once the control loop ends call PidLeadLagDiscard to discard the lead lag compensator and release its resources Also call PidDiscard to discard the PID controller The lead lag compensator can be used either as an input or an output filter to the PID controller The default output range is 100 to 100 which corresponds to values specified in terms of percentage of full scale However you can change this range so that the controller gain relates engineering units to engineering units instead of percentage to
37. lude CVIPIDRuntime msm in that file group Build the distribution kit andCVIPIDRuntime msm will be seamlessly merged in as an MSI merge module instead of just being included as a file If you are using LabWindows CVI 8 0 and later click Add Additional Module in the Drivers amp Components tab of the Edit Installer dialog box In the Select Merge Module dialog box browse to and select CVIPIDRuntime msm For additional information about distributing LabWindows CVI applications refer to the LabWindows CVI Help Using PID with Gain Scheduling Most processes are non linear Therefore PID parameters that produce a desired response at one operating point might not produce a satisfactory response at another operating point Using the gain scheduling feature you can apply different sets of PID parameters for different regions of controller operation The gain scheduler selects and outputs one set of PID gains from a gain schedule based on the current gain scheduling value The gain scheduling value input can be anything and is based on the gain scheduling criteria that you set Use the pidGSAttrGainScheduleCriteria attribute to set the gain scheduling criteria Call P dSetGainScheduleAttribute and PidGetGainScheduleAttribute to set and get gain scheduling attributes The pidGSAttrGainScheduleCriteria attribute can take the following values e Setpoint e Process variable e Controller output e Gain schedule variable provided by the user thro
38. ng photocopying recording storing in an information retrieval system or translating in whole or in part without the prior written consent of National Instruments Corporation Trademarks National Instruments NI ni com and LabVIEW are trademarks of National Instruments Corporation Refer to the Terms of Use section on ni com legal for more information about National Instruments trademarks Other product and company names mentioned herein are trademarks or trade names of their respective companies Members of the National Instruments Alliance Partner Program are business entities independent from National Instruments and have no agency partnership or joint venture relationship with National Instruments Patents For patents covering National Instruments products refer to the appropriate location Help Patents in your software the patents txt file on your CD or ni com patents WARNING REGARDING USE OF NATIONAL INSTRUMENTS PRODUCTS 1 NATIONAL INSTRUMENTS PRODUCTS ARE NOT DESIGNED WITH COMPONENTS AND TESTING FOR A LEVEL OF RELIABILITY SUITABLE FOR USE IN OR IN CONNECTION WITH SURGICAL IMPLANTS OR AS CRITICAL COMPONENTS IN ANY LIFE SUPPORT SYSTEMS WHOSE FAILURE TO PERFORM CAN REASONABLY BE EXPECTED TO CAUSE SIGNIFICANT INJURY TO A HUMAN 2 IN ANY APPLICATION INCLUDING THE ABOVE RELIABILITY OF OPERATION OF THE SOFTWARE PRODUCTS CAN BE IMPAIRED BY ADVERSE FACTORS INCLUDING BUT NOT LIMITED TO FLUCTUATIONS IN ELECTRICAL POWER SUPPL
39. ntroller tuning methods to find the fastest setting time with the least amount of overshoot The default tuning parameters are optimal for the given network The input span is 5 to 5 V and the output span is 0 to 10 V Both the PV and SP are in volts Set the analog input of the DAQ device to differential input mode in the 5 V range and set the output to bipolar in the 10 V range These are all factory defaults If you use other settings change the DAQ device configuration settings to correspond to the new settings The recommended network has a DC gain of 0 33 and an effective deadtime of about 5 seconds LabWindows CVI PID Control Toolkit User Manual 4 6 ni com References The Instrument Society of America ISA the organization that sets standards for process control instrumentation in the United States offers a catalog of books journals and training materials to teach you the basics of process control programming Corripio 1990 is an ISA Independent Learning Module book It is organized as a self study program covering measurement and control techniques selection of controllers and advanced control techniques This book provides detailed yet easily understandable tuning procedures The following material is referenced in this manual Corripio A B 1990 Tuning of Industrial Control Systems Raleigh North Carolina ISA Ziegler J G and N B Nichols 1942 Optimum Settings for Automatic Controllers Trans ASME 6
40. on instructions 1 1 instrument drivers NI resources B 1 integral action 2 1 integral time 2 1 K KnowledgeBase B 1 L lag compensation 3 8 lead compensation 3 8 lead lag compensator 3 8 lead lag example 3 9 lead lag examples 4 5 manual automatic control example 4 3 MIO board example 4 5 LabWindows CVI PID Control Toolkit User Manual National Instruments support and services B 1 Nichols N B A 1 nonlinear adjustment of integral action 2 2 2 5 0 open loop tuning procedure 3 3 output limiting 2 3 output rate limiting 3 5 P package contents 1 1 partial derivative action 2 2 percentage of full scale converting from engineering units 3 10 PID algorithm 2 1 to 2 3 autotuning algorithm 2 5 to 2 8 calculating controller action controller output 2 2 error calculation 2 2 nonlinear adjustment of integral action 2 2 output limiting 2 3 partial derivative action 2 2 proportional action 2 2 trapezoidal integration 2 2 gain scheduling 2 3 PID controller 1 2 typical use 3 4 PID Library 3 4 pidAttrAlgorithm 3 5 pidAttrLimitOutputRate 3 6 pidAttrUseInternalTimer 3 1 pidGSAttrGainScheduleCriteria 3 7 ni com precise PID algorithm 3 5 calculating controller action nonlinear adjustment of integral action 2 5 proportional action 2 4 trapezoidal integration 2 5 error calculation 2 4 proportional action 2 4 trapezoidal integration 2 5 process variable 1 2 programmin
41. oop For a linear system or element the ratio of the magnitude amplitude or a steady state sinusoidal output relative to the causal input the length of a phasor from the origin to a point of the transfer locus in a complex plane The process of applying different controller gains for different regions of operation of a controller Gain scheduling is most often used in controlling nonlinear physical processes Hertz Cycles per second LabWindows CVI PID Control Toolkit User Manual G 2 ni com Instrument Society of America ISA integral control action L lag linearity factor load disturbance noise National Instruments Corporation G 3 Glossary The organization that sets standards for process control instrumentation in the United States Control action in which the output is proportional to the time integral of the input That is the rate of change of output is proportional to the input Process gain Controller gain A lowpass filter or integrating response with respect to time A value ranging from 0 to 1 used to specify the linearity of a calculation A value of 1 indicates a linear operation A value of 0 indicates a squared nonlinear operation The ability of a controller to compensate for changes in physical parameters of a controlled process while the setpoint value remains constant Milliseconds In process instrumentation an unwanted component of a signal or variable Noise may be
42. or disturbances In this case use autotuning Before you begin autotuning you must establish a stable controller even if you cannot properly tune the controller on your own National Instruments Corporation 2 5 LabWindows CVI PID Control Toolkit User Manual Chapter 2 PID Algorithms Figure 2 2 illustrates the autotuning procedure excited by the setpoint relay experiment which connects a relay and an extra feedback signal with the SP Notice that the PID Library autotuning functions directly implement this process The existing controller remains in the loop SP THES e PV tro _ P I Controller gt Process 1 Relay Figure 2 2 Process under PID Control with Setpoint Relay For most systems the nonlinear relay characteristic generates a limiting cycle from which the autotuning algorithm identifies the relevant information needed for PID tuning If the existing controller is proportional only the autotuning algorithm identifies the ultimate gain K and ultimate period T If the existing model is PI or PID the autotuning algorithm identifies the dead time and time constant 7 which are two parameters in the integral plus deadtime model as follows TS e rs Gs Tuning Formulas This package uses Ziegler and Nichols heuristic methods for determining the parameters of a PID controller When you autotune select one of the following types of loop performance fast 1
43. orical reasons the term gain scheduling is used even if other parameters such as the derivative time or integral time parameters change Gain scheduling effectively controls a system whose dynamics change with the operating conditions National Instruments Corporation 2 3 LabWindows CVI PID Control Toolkit User Manual Chapter 2 PID Algorithms The Precise PID Algorithm Error Calculation The following formula represents the current error used in calculating proportional integral and derivative action e k SP PV L 1 L Ll range The error for calculating proportional action is shown in the following formula eb k B SP PV L 1 L BEEN range where SP is the range of the SP is the setpoint factor for the Two Degree of Freedom PID algorithm described in the Proportional Action section and L is the linearity factor that produces a nonlinear gain term in which the controller gain increases with the magnitude of the error If Z is 1 the controller is linear A value of 0 1 makes the minimum gain of the controller 10 Use of a nonlinear gain term is referred to as a precise PID algorithm Proportional Action In applications SP changes are usually larger and faster than load disturbances while load disturbances appear as a slow departure of the controlled variable from the SP PID tuning for good load disturbance responses often results in SP responses with unacceptable oscillation However tun
44. rol Toolkit User Manual Chapter 3 Using the PID Control Toolkit You can use output rate limiting to avoid the problem of sudden changes in controller output To enable output rate limiting set pidAttrLimitOutputRate to l set pidAttrOutputRate and pidAttrInitialOutput to limit the rate of change of the controller output and specify the controller output value on the first iteration of the control loop respectively Call PidSetAttribute and PidGetAttribute to set and get these attributes Using PID with Autotuning You can use autotuning to improve controller performance There are two ways in which you can autotune a controller Wizard Based Autotuning You can use the PID Autotuning Wizard to tune the parameters e Classic Autotuning You can use the functions in the Autotuning class to develop a custom autotuning user interface Complete the following steps to autotune a controller These steps explain both wizard based and classic autotuning 1 Call PidcreateWithAutotune to create the controller and obtain the PID handle that identifies that controller in subsequent function calls The PID Library invokes the callback function provided to PidCreateWithAutotune when the following PID events occur pidNoiseEstimateEvent Noise estimation is complete e pidRelayCycleEvent A setpoint relay cycle is complete pidAutotuneEvent Autotuning is complete When you use wizard based autotuning the library invokes the c
45. ss in which the next output always increments from the current output regardless of the current controller output value Therefore transfer from automatic to manual control is always bumpless Control in which the output of one controller is the setpoint for another controller A signal path that includes a forward path a feedback path and a summing point and that forms a closed circuit Also called a feedback loop Hardware and or software used to maintain parameters of a physical process at desired values A quantity or condition that is varied as a function of the actuating error signal so as to change the value of the directly controlled variable The time between samples in a discrete digital control system LabWindows CVI PID Control Toolkit User Manual Glossary D damping DC dead time derivative control action EGU F feedback control feedback loop G gain gain scheduling The progressive reduction or suppression of oscillation in a device or system Direct current The interval of time expressed in minutes between initiation of an input change or stimulus and the start of the resulting observable response Control response to the time rate of change of a variable Engineering units Control in which a measured variable is compared to its desired value to produce an actuating error signal that is acted upon in such a way as to reduce the magnitude of the error See closed l
46. tput National Instruments Corporation 4 1 LabWindows CVI PID Control Toolkit User Manual Chapter 4 Process Control Examples General PID Example This simple PID application uses the PID Control Toolkit to simulate a simple control loop with a general plant model This example uses a simple integrating process such as a level control loop with added noise valve deadband lag deadtime and variable loading all of which you can adjust F General Pid Control 100 0 Plant Parameters Static Gain Load 60 0 25 4000 Dead Cycles Dead Band 20 0 T 20 Lag Noise 31 00 3025 60 0 Pid Parameters 100 0 Kp Ti 0 99 2000 00150 35000 Setpoint T 0 00000 Process Variable 4 00010 0 00000 Controller Output Timer Interval LoopBackType Figure 4 1 The User Interface of the General PID Example You can think of this general PID simulation as a pressure control application The next execution of the control loop reads and delays the previous value position and then scales it according to the process gain The gain represents the process response versus the valve position The gain might have units of PSI per value percentage The process deadtime Dead Cycles is a multiple of the cycle time rather than an absolute fixed delay If you change the cycle time you must adjust the process deadtime to keep the process response constant
47. tuning et 3 6 Using PID with Gain Scheduling pt 3 7 Using PID with Lead Lat erne eaa ea E e E aar ialay 3 8 Using PID with Setpoint Profiling et 3 9 Using Ramp Generators ciroen a R 3 9 Converting between Percentage of Full Scale and Engineering Units 3 10 National Instruments Corporation V LabWindows CVI PID Control Toolkit User Manual Contents Using PID on Real Time RT Targets seen 3 10 Using PID with DAQ Devices eese eene 3 11 Chapter 4 Process Control Examples Simulation Examples o e e ett e erede iode e ee odds 4 1 Hardware Examples ett e ere en D e ees 4 5 Appendix A References Appendix B Technical Support and Professional Services Glossary Index LabWindows CVI PID Control Toolkit User Manual vi ni com About This Manual Conventions The LabWindows CVI PID Control Toolkit User Manual describes the PID Control Toolkit for LabWindows CVI The manual describes the features functions and operation of the toolkit To use this manual you need a basic understanding of process control strategies and algorithms 3 bold italic monospace The following conventions appear in this manual The symbol leads you through nested menu items and dialog box options to a final action The sequence File Page Setup Options directs you to pull down the File menu select the Page Setup item and select Options from the last dialog box This
48. ugh the pidGSAttrUserGainScheduleVariable attribute The gain schedule is a list of gain sets A gain set consists of the following features e Proportional gain K Integral time 77 National Instruments Corporation 3 7 LabWindows CVI PID Control Toolkit User Manual Chapter 3 Using the PID Control Toolkit e Derivative time 7 e Gain control value The PID Library uses the gain set that has the smallest control value that is greater than the value of the signal specified by the gain schedule criteria For example if three gain sets have control values equal to 10 20 and 30 and the value of the signal specified by the gain schedule criteria is 15 then the second gain set is used If the value of the signal specified by the gain schedule criteria is greater than the gain schedule s largest control value then the gain set with the largest control value is used You also can set pidGSAttrSelectionMode to pidManual to allow you to set the gain sets manually By default the mode is automatic For more information refer to the samples pid Gain Scheduling GainScheduling prj example program Using PID with Lead Lag The lead lag compensator uses a positional algorithm that approximates a true exponential lead lag Feed forward control schemes often use this kind of algorithm as a dynamic compensator Using lead lag you can simulate inertia of motors slow settling times in pipes and so on Lead compensation stabilizes a c
49. urated at the specified minimum or maximum values Refer to Chapter 2 PID Algorithms for more information about anti windup LabWindows CVI PID Control Toolkit User Manual 3 4 ni com Chapter 3 Using the PID Control Toolkit PID Algorithms The PID controller can use the following types of PID algorithms to determine the controller output e Fast PID algorithm pidFastPidAlgorithm Precise PID algorithm pidPrecisePidAlgorithm Use the pidAttrAlgorithm attribute which you can set using PidSetAttribute to specify the algorithm to use pidFastPidAlgorithm is the default value The fast PID algorithm is faster and simpler than the precise PID algorithm Use the fast algorithm in fast control loops The precise PID algorithm uses the Two Degree of Freedom algorithm to control the PV which gives better results than the fast PID algorithm The precise PID algorithm also uses extra parameters such as Beta Linearity and Setpoint Range which you can specify using PidSetAttribute The precise PID algorithm implements a bumpless manual to automatic transfer which ensures a smooth controller output during the transition from manual to automatic control mode Control Input Filter You can use the filtered PV to filter high frequency noise from the measured values in a control application For example you can use a filtered PV if you are measuring process variable values using a DAQ device To use a filtered PV set pidAttrUseFiltered
50. y you must scale all inputs to percentage of full scale and all controller outputs to actual engineering units such as volts for analog output You can use PidConvertEGUToPercentage to convert any input from real engineering units to percentage of full scale and PidConvert PercentageToEGU to convert the controller output from percentage to real engineering units PidConvert PercentageToEGU has an additional input parameter bCoerce The default value of bCoerce is TRUE which indicates that the output is coerced to the range Note The PID Library functions do not use the setpoint range and output range information to convert values to percentages in the PID algorithm The controller gain relates the output in engineering units to the input in engineering units For example a gain value of 1 produces an output of 10 for a difference between the SP and PV of 10 regardless of the output range and setpoint range Using PID on Real Time RT Targets Some PID applications are deterministic and therefore cannot be run on desktop operating systems Because the PID Library is supported on real time RT platforms such as LabVIEW Real Time you can use it to develop deterministic applications Complete the following steps to run a PID application on an RT target 1 Create a DLL using the PID Library When you build the DLL set the Run time support option in the LabWindows CVI Target Settings dialog box to Real time only 2 Create a VI in L
Download Pdf Manuals
Related Search
Related Contents
New World NW802FZ EVGA 03G-P4-3668-KR NVIDIA GeForce GTX 660 Ti 3GB graphics card KRAMER ELECTRONICS, LTD. Life Fitness GS6 User's Manual Warranty Experimental Life Energy Meter Steel City 20130VS Use and Care Manual Christie LX450 LCD x3 User Guide Manual 子ども用衣類の安全確保について 参考資料 - 東京くらしWeb Samsung Galaxy Ace 3 User Manual Copyright © All rights reserved.