Home

- Power Logic

image

Contents

1. Trending and forecasting as viewed from PowerLogic ION7650 web page ee ee ey 6 ON7550 7650 series power and energy meters Report generator log configured to provide power Inputs and outputs All models provide digital inputs as well as Form C mechanical relays and Form A solid state relays digital outputs Optional digital and analog I O is also available Digital output relays respond to internal alarms external digital input status changes or commands over communications Use digital inputs to trigger alarms or logging synchronize to a demand pulse or control conditional energy accumulation Type Electro mechanical relays Solid state relays Analog op tion Digital VO CARD Input output 3 Form C relays R1 R3 Form C contacts NO K NC 4 Form A digital outputs D1 D41 4 inputs Al 1 to Al 4 4 outputs AO1 to AO4 8 inputs S1 S8 8 inputs option DI1 DI8 Specifications 250 Vac 30 Vdc max voltage 380 Vac 125 Vdc Turn on time 15 ms max Turn off time 5 ms max Update rate 2 cycle or 1 sec Max voltage 30 Vdc max current 80 mA isolation optical update rate Ya cycle or 1 sec Signal type DC current range O to 20 mA scalable 4 to 20 or O to 1 mA accuracy 0 3 of full scale update rate 1 sec Signal type DC current range 0 20 mA scalable 4 20 or 1 mA to 1 mA scalable O 1 update
2. current disturbance sag swell detection COMTRADE format waveform records are now available only for meters with the Ethernet port option V Complete communications Ethernet RJ 45 modular or SC fiber Serial RS 485 and or RS 252 Modem Gateway functionality simplifies communications architecture and reduces leased line or connection costs Concurrent independent ports communicate with protocols such as ION DNP 3 0 IEC 61850 Modbus RTU Modbus TCP Modbus Master Ethernet port allows the following concurrent connections 24 Modbus 8 generic ION DNP Modbus 4 IEC 61850 dedicated client 1 FTP and 1 SNMP Dial out capability when memory is near full Data push capability through SMTP email i gt all DF ip iis Be it np ae ce i j oJ _ e tee i i a i hi t N ee aa so w iy Tappa E un e H a PRE eee DALIT o Eh Fe I ly ty iy EE T i n Aa i eae I s i NT E T F a E gt Patented ION technology Provides a modular flexible architecture that offers extensive user programmability Uniquely addresses complex monitoring and control applications Adapts to changing needs avoiding obsolescence Disturbance direction detection V Determine the location of a disturbance more quickly and accurately by determining the direction of the disturbance relative to the meter Analysis results are captured in the event log al
3. meter functions such as meter resets and has multiple programmable screens for numeric and time stamped values frequency spectrum harmonics trend logs and name plate data The large display automatically scrolls through displays screens that present at a glance Volts Amps power energy and demand values Screens are easily customized to suit user requirements Set parameter measurements via front panel to comply with regional preferences Modbus Master feature allows display of real time parameters of any downstream modbus devices Va Vb Ve v h b k M 6 360 10 kWh del 0 79 OU TOU Fay LOU mdi TOU Oma Energy received delivered display 1 Harmonics Mag Ham Wi Harm ji Vd Ham Harmonic current display CHE A rit Dt bt ad td HANIN NTA Se TT AT AANA AM UML tifhitil iii uhitili IN HTH qe ee Trend display Power and energy measurements High accuracy four quadrant energy metering in accordance with IEC 62053 22 Class 0 2S for both 3 and 2 element systems Real bidirectional reactive and apparent values Fully programmable integrating period 1 5 10 15 30 60 min or other Supports block rolling block and predicted demand calculations such as kW kVAr and kVA demand min max Volts and Amps demand min max cumulative demand demand on any instantaneous measurement Measurement specifications Parameter Accuracy CAE aD Voltage line line line neutral per
4. rate Y2 cycle or 1 sec SCOM self excited dry contact sensing no external voltage required Min pulse width 1 ms max pulse rate 20 pulses sec Timing resolution 1 ms update rate Ya cycle after timing resolution isolation 300 V peak max rated voltage 120 Vdc external excitation Self excited internal 30 Vdc supply dry contact sensing or with external excitation 1 3 mm to 0 1 mm 16 AWG to 28 AWG min pulse width 20 ms max pulse rate 25 pulses sec updated Y2 cycle after timing resolution PowerLogic ION7650 scom S8 S7 S6 S5 S4 S3 S2 S1 Ai A2 AB Ald AO1 A02 A03 A04 I O card DIS le Q STSSVHVG IOV VYSHGG Communications Multiple communication ports that operate simultaneously allow the meters to be used as part of a power and energy management system and to interface with other automation systems Upload waveforms alarms billing data and more to software for viewing and analysis EtherGate and ModemGate The meters can provide gateway functionality depending on communication options EtherGate provides access via Modbus TCP thr
5. to www squared com to find your nearest authorized distributor or call 1 888 SquareD d IL 2 D 65 2 cyc 65 2 cyc E ISO 9001 DMSA Global File 002188 As standards specifications and designs develop from time always ask for confirmation of the information given in this publication Square D PowerLogic ION ION Enterprise MeterM il webmeter and Modbus are either trademarks or registered trademarks of Schneider Electric or its affiliates Other marks used herein may be the property of their respective owners TD This document has been printed on recycled paper October 2010 tk 7 c c ICAWIILY 2010 Schneider Electric All Rights Reserved
6. 00 3 2 EN61000 3 2 IEC 61000 3 3 EN61000 3 3 FCC Part 15 Subpart B Class A Digital Device EN55011 CISPR 11 EN55022 CISPR 22 EN61000 6 4 EN50081 2 Environmental conditions Operating temperature 20 C to 70 C no formation of ice 4 F to 158 F Low Voltage DC Power Supply 20 C to 50 C 4 F to 122 F Storage 40 C to 85 C 40 F to 185 F Humidity 5 to 95 non condensing ION7550 7650 series power and energy meters 7 PowerLogic ION7550 7650 series features and options Features and options MASLRO Power energy and demand Power quality Sag swell harmonics monitoring Harmonics individual even odd up to Harmonics magnitude phase and inter harmonics Symmetrical components zero positive negative Recording compliant with IEC 61000 4 30 class A ed 2 IEC61000 4 15 flicker EN50160 compliance checking Transient detection microseconds 20 us for 50 Hz 17 us for 60 Hz Sampling rate max samples cycle Disturbance direction detection Logging and recording Memory standard optional Min max historical waveform logging Time stamp resolution in seconds Historical trend information via front panel display GPS time synchronization Communications and l O IEC 61850 RS 232 485 RS 485 Ethernet optical Internal modem 3 port DNP 3 0 via serial modem Ethernet I R ports Modbus RTU slave master Modbus TCP EtherGate ModemGate MeterM il WebMeter Analog in
7. Advanced power quality analysis coupled with revenue accuracy in a web compatible meter PowerLogic ON7550 ION7650 series Energy and power meters D sauaRED by Schneider Electric PowerLogic ION7550 7650 series power and energy meters Used at key distribution points and sensitive loads the PowerLogic ION7550 and ION7650 series meters offer unmatched functionality including advanced power quality analysis coupled with revenue accuracy multiple communications options web compatibility and control capabilities Integrate these meters with our PowerLogic ION Enterprise software or share operations data with existing SCADA systems through multiple communication channels and protocols Typical applications For infrastructure industrials and buildings e Energy savings gt Measure efficiency reveal opportunities and verify savings gt Reduce peak demand surcharges gt Reduce power factor penalties gt Strengthen rate negotiation with energy suppliers gt Enable participation in load curtailment programs e g demand response gt Identify billing discrepancies gt Leverage existing infrastructure capacity and avoid over building gt Support proactive maintenance to prolong asset life e Energy availability and reliability gt Validate that power quality complies with the energy contract gt Verify the reliable operation of equipment gt Improve response to power quality related problem
8. Norway Portugal Spain Sweden Switzerland United Kingdom ANSI Type 2 optical port Protocols include ION DNP 3 0 Modbus RTU Data rates COM 4 1200 bps to 19 200 bps Half duplex Protocols TCP IP Telnet ION Modbus TCP SNMP Interface IEEE 802 3 1998 ISO IEC 8802 31993 IEC 61850 Ethernet Data rates 10 Mbps Half duplex Ethernet port 1OBASE T 100BASE TX Connectors RJ45 cabling unshielded twisted pair cable 0 5 mm 24 AWG max length 100 m 109 yds Isolation Transformer isolated to 1500 V RMS MeterM il automatically emails user configured high priority alarm notifications or scheduled system status update messages to anyone anywhere within the facility or around the world 100BASE FX fibre connectors ST Cabling Fibre optic cable 62 5 125 um nominal wavelength 820 nm max length 2000 m General specifications Description Specifications Accuracy IEC 62053 22 0 25 1 A and 5A tested by KEMA Complies with ANSI C12 20 Class 10 and Class 20 IEC 1010 1 EN61010 1 CSA C22 2 No 1010 1 UL 61010B 1 Electromagnetic Immunity IEEE C 37 90 1 1989 EN50082 2 IEC 61000 4 2 EN61000 4 2 IEC 8012 IEC 61000 4 3 EN61000 4 3 IEC 801 3 Radiated EM Field Immunity Safety construction Electromagnetic compatibility IEC 61000 4 4 EN61000 4 4 IEC 801 4 Electric Fast Transient IEC 61000 4 5 EN61000 4 5 IEC 801 5 Surge Immunity IEC 61000 4 6 EN61000 4 6 IEC 801 6 Conducted Immunity IEC 610
9. arameters IEC 61000 4 30 ION7650 only monitor compliance of relevant 4 30 parameters such as power frequency magnitude of supply voltage flicker supply voltage sags swells transients and voltage interruptions Transient ION7650 only voltage waveforms of transient activity i e ITI CBEMA Type 1 disturbances e COMTRADE waveform format records are available directly from the meter via the FTP server meters with Ethernet port option only 4 30 Flicker Profile 10 Minute interval Ew id Max Disturbance Ficker a i Vakia Diza 1 i Hi Ti i j A aly r fe Fi I ih A ri A i we IIIA ANA p a heel Fe iri SS a A E A a fi Pe OE OT TO RTT o et Tiare Wi 10 min PST W210 min PST Vo 10 min PST Disturbance Baseline Baseline Example screen from PowerLogic ION Enterprise software showing continuous wide area monitoring data capture and reporting for power quality and reliability conditions ION7550 7650 series power and energy meters 5 Data Waveforms 500 events 1 5 yrs 1 80 Data and event logging Ships with a comprehensive data logging configuration Data is prioritized and stored on board in nonvolatile memory to eliminate data gaps in the event of outages or server downtime Retrieved data is stored in an ODBC compliant database when using ION Enterprise Trending and forecasting capabilities track specified quantities over time and forecast the va
10. de 4 Wire Wye 3 Wire Wye 3 Wire Delta Direct Delta and single phase systems four voltage and five current inputs Specifications 347 Vac direct line to neutral 600 Vac direct line to line RMS 1500 Vac RMS continuous 5 MQ phase phase Vref 1200 V peak 5 A 10 A and or 20 A 1 A 2 A 5A optional current range 600 V RMS CAT III IEC 61010 1 2500 Vac 60 Hz for 1 min 0 05 VA phase at 5 A standard 0 015 VA phase at 1 A optional 0 002 O phase phase Vref 0 015 O optional current range Standard AC 85 Vac to 240 Vac 10 47 Hz to 68 Hz DC 110 Vdc to 300 Vdc 10 Burden Typical 15 VA max 35 VA Optional low voltage DC power supply Rated inputs DC 20 Vdc to 60 Vdc 410 Burden Typical 12 VA max 18 VA Current probes with AC voltage output Rated inputs Overload Impedance Options 1 V RMS 5 5 V CAT IEC 61010 1 220 kQ max Current probe inputs for use with O Vac to 1 Vac current probes Probes sold separately Accuracy depends on probe specs Current probe inputs with three calibrated Universal Technic 10 A clamp on CTs meeting IEC 61086 accuracy ON7550 7650 series power and energy meters Front panel Use for both display and configuration purposes The large backlit LCD display screen and the numerous selection navigation and configuration softkeys allow quick Secure access to basic meter configuration screens The front panel also provides access to many other
11. lue of future quantities View trending and forecasting data through the meter s web pages Logging capacity is available in 5 MB or 10 MB configurations Default depth and interval of logging is set at the factory and depends upon on board memory size e Revenue log configured for use with UTS MV 90 billing software Logs kWh del int KWh rec int KVARh del int KVARN rec int values Historic logs record standard power system quantities such as phase current phase voltage and power factor system data for ION Enterprise software Event log Trend display logs gt Multiple tariffs and time of use TOU calculations 20 year calendar with automatic leap year and seasonal time adjustments and clock synchronization over communications channel or GPS TOU is configured four seasons five daily profiles per season four tariff periods per daily profile Automatic mid season rate change Active reactive and apparent energy and demand automatic recording of max peak demand during each tariff period gt Example logging configurations lION7550 lION7650 Event 500 events 2 9 yrs 3605 500 events 1 3 yrs 3605 500 events 3 1 yrs 180 U 16 parameters recorded every 15 min 2I 30 waveforms on 6 channels at the max sampling rate BI 30 waveforms on 12 channels with any selectable format for example 6 channels are 512 samples cycle for 4 cycles and 6 channels are 32 samples cycle for 54 cycles
12. ong with a time stamp and confidence level indicating level of certainty V Alarm setpoint learning Helps simplify alarming configurations by monitoring normal operating parameters and over time learning what constitutes a sag swell transient or high and low setpoint Learning can be configured in either ION Setup or PowerLogic ION Enterprise software V Trending and forecasting Forecast values such as demand to better control demand charges and billing rates View results via the meter s web pages Analyse trends to support proactive maintenance schedules V Transtormer line loss compensation Automatically measure compensate and correct for transformer or line losses when meter is physically separated from the point of billing or change of ownership V Inputs and outputs Digital and analog inputs and outputs for pulse counting demand metering for other WAGES utilities equipment status position monitoring demand synchronization triggering conditional energy metering equipment control or interfacing ION7550 7650 series power and energy meters 3 Input s Voltage inputs Nominal full scale Overload Input impedance Fault capture Current inputs Nominal current Max voltage Withstand Load burden Impedance Control power Operating range Installation M 7 56 a at Designed to fit DIN standard 192 cutout 186 mm by 186 mm Circuit and control power connections inclu
13. ough the meter s Ethernet port to devices communicating via Modbus connected to the meter s serial ports ModemGate provides access from the telephone network to devices connected to the meter s serial ports EtherGate Ethernet Serial ModemGate Telephone line aap Internet connectivity Exchange information using XML to integrate with custom reporting spreadsheet database and other applications WebMeter an on board web server provides access to real time values and PO data through any web enabled device and even supports basic meter configuration tasks Port Specifications Protocols include ION Modbus RTU Modbus Master DNP 3 0 GPS EtherGate ModemGate Data rates 300 bps to 115 200 bps RS 485 limited to 57 600 bps Connectors male DB9 RS 232 DTE or captured wire RS 485 Duplex Full RS 232 Half RS 485 serial RS 252 RS 485 port COM 1 Serial RS 485 port COM 2 Protocols include ION Modbus RTU Modbus Master DNP 3 0 GPS EtherGate ModemGate Data rates 300 bps to 57 600 bps 2400 to 38400 Duplex Half Internal modem COM 3 Data rates 300 bps to 33 6 kbps V 3 4 V 32 bis V 32 V 22 bis V 22 A B V 23 V 21 Bell 212A Bell 103 Supports automatic data rate detection RJ11 interface Approvals FCC P68 USA Industry Canada CS 03 Also approved for use in Austria Belgium Denmark Finland France Germany Greece Iceland Ireland Italy Luxembourg Netherlands
14. phase min max unbalance Frequency present 0 005 Hz min max Current 11 12 13 0 1 Current 14 15 0 4 Power real kW reactive IEC 62053 22 kVAr apparent kVA Class 0 2817 oer phase total Energy real kWh IEC 62053 22 reactive kVArh Class 0 2S apparent KVAh in out kKWA kVA demand IEC 62053 22 calculations Class 0 2S Power factor at Unity PF 0 2 I Refer to user s manual for valid measurement ranges 2 Refer to compliance section Not applicable for NICT meters contact factory for measurement specifications Power quality Power quality compliance monitoring for international quality of supply standards plus specific data for localized and custom compliance agreements and network connection requirements e Harmonics all models individual harmonics up to the 63 K factor and total harmonics distortion THD e Sag swell all models voltage waveforms for sags and swells i e ITI CBEMA Type 2 and Type 3 disturbances report on each disturbance s magnitude and duration Detect sub disturbances during a sag swell event Disturbance direction detection all models analyze disturbance information to determine the direction of the disturbance relative to the meter Results are provided in the event log along with time stamp and the level of certainty of disturbance direction EN50160 ION7650 with EN50160 ordering option only monitor compliance with EN50160 p
15. puts outputs optional Digital status inputs outputs Relay outputs standard Setpoints alarming and control Setpoints number min response time Math logic trig log linearization formulas Call out on single and multi condition alarms Alarm setpoint learning Schneider Electric USA Inc 295 Tech Park Drive LaVergne TN 37086 Tel 615 287 3500 www PowerLogic com Document Number 3000BRO604R10 10 Software integration Integrate within PowerLogic facility level or enterprise wide power and energy management systems Real time data and data logs stored on board can be automatically retrieved on a scheduled basis for analysis at the system level Compatible with PowerLogic ION Enterprise and PowerLogic ION Setup Modbus compatibility and register based logged data supports integration and data access by building automation SCADA and other third party systems lION7550 ION7650 e PowerLogic ION Enterprise software e ION Setup software e Modbus Master e Internet connectivity e XML compatibility Special features flash based firmware Flash based firmware allows upgrades via communications without removing the meter from the site Simply download the latest firmware from www powerlogic com Real time data data logs and waveforms stored on board 5 MB 10 MB 5 MB 10 MB 0 001 0 001 Whatever your need Schneider Electric has the solution To find genuine Schneider Electric and Square D Brand products go
16. s 2 ON7550 7650 series power and energy meters For electric utilities e Energy availability and reliability gt Improve T amp D network reliability gt Enhance substation automation to reduce field service time gt Maximize the use of existing infrastructure e Revenue metering and power quality gt Install new high accuracy metering at all interchange points gt Improve or verify metering accuracy at existing interchange points gt Verify compliance with new power quality standards gt Analyze and isolate the source of power quality problems Features gt High visibility multilingual IEC IEEE contigureable display Large backlit LCD presents multiple simultaneous real time and time stamped historical parameters as well as graphical trends and histograms gt High accuracy standards Meets stringent IEC and ANSI measurement accuracy standards such as IEC 62053 22 Class 0 28 ANSI C12 20 0 2 Class 10 and 20 gt Digital fault recording Simultaneously capture voltage and current channels for sub cycle disturbance transients as well as multi cycle sags swells and outages 1024 samples cycle waveform recording 20 17 us transient capture 50 60 Hz gt Power quality analysis and compliance monitoring A choice of THD metering individual current and voltage harmonics readings waveform capture EN50160 and flicker PowerLogic ION7650 only power quality compliance evaluation and voltage and