Home
User Manual: MK2430
Contents
1. 46 TGH1389en 08 2012 Operation FZ BEN DER 7 2 Quick reference guide The following images have been provided by way of example only 7 2 1 Display in error free operation There are no warnings or alarms pending e The green Normal LED is lit e The programmed standard information appears on the LC display e A maximum of 3 measuring values can be indicated in the lines 1 3 Power supply OK Med gases OK 09 50 Line1 3 user definable standard display text Line 4 status bar indicates the time of day can be switched off 7 2 2 Display in fault condition A warning or an alarm message is pending e Depending on the type of fault either the yellow LED Warning or the red LED Alarm will light up The green LED Normal goes out e The buzzer sounds at the same time If the cause of the message cannot be reme died immediately the buzzer can be deactivated by pressing Mute d 5 e Information about the message appears on the LC display Intensive care unit 03 Insulation fault Measured value 43 kQ xx yy zzz 09 50 Line 1 Standard display System User defined text here Intensive care unit 03 Line2 3 message text may contain measured value TGH1389en 08 2012 47 E BEN DER Operation Line4 Status line Xx Consecutive number of message displayed yy Number of pending messages Message text page in this case page 1 ZZZ Insulation fault location or test in progre
2. Menu item Mode Page 1 Back Exit Control menu go up one menu level ee Resetting all fault messages pending on the BMS bus 68 AlarmClear 3 EDS start stop Manual starting stopping of test procedures on EDS system 69 4 Test Testing of communication via the BMS bus MK2430 11 Communication only 8 4 5 1 Back Exit menu mode 1 Exit 2 Reset AlarmClear 3 EDS start stop 4 Test Communication 8 4 5 2 Control menu 2 Reset AlarmClear Press 1 to reset all pending fault messages on the BMS bus Reset done will then appear in the last line displayed 1 Exit 2 Reset AlarmClear 3 EDS Start Stop Reset done This reset command is sent via the BMS bus Note that some devices e g PRC470 do not react to this reset 68 TGH1389en 08 2012 Menu mode Operation and setting A BENDER 8 4 5 3 Control menu 3 EDS start stop Press 1 to start and stop the test procedure manually on the EDS system This function can only be activated for the master The current status appears in the last line 1 Exit 1 Exit 2 Reset AlarmClear 2 Reset AlarmClear 3 EDS start stop 3 EDS start stop EDS system running EDS system stop EDS system running Once started EDS4xx 12 and PGH47x run continuously If you exitthe menu the standard display EDSp will appear in the last line in order to indicate continuous running EDS system stop Stops the continuous pass of EDS4xx 12 and PGH47x
3. 785 commercial matters Fax 49 6401 807 789 E mail repair bender service com Please send the devices for repair to the following address Bender GmbH Repair Service Londorfer Strasse 65 35305 Gruenberg Germany 40 TGH1389en 08 2012 Commissioning and testing A BEN DER Field Service On site service for all Bender products e Commissioning parameter setting maintenance trouble shooting for Bender products e Analysis of the electrical installation in the building power quality test EMC test thermography e Practical training courses for customers Tel 49 6401 807 752 762 technical issues 49 6401 807 753 commercial matters Fax 49 6401 807 759 E mail fieldservicegbender service com Available from 7 00 a m to 8 00 p m on 365 days of the year CET UTC 1 Mo Thu 7 00 a m 8 00 p m Fr 7 00 a m 13 00 p m Internet www bender de com 5 4 3 Maintenance MK2430 does not contain any parts that require maintenance Despite this the intervals specified for periodic verification should be adhered to TGH1389en 08 2012 41 4 BEN DER Commissioning and testing 42 TGH1389en 08 2012 VL BENDER 6 Troubleshooting 6 1 Error messages of MK2430 The following errors are recognised by the MK2430 and indicated on the display In addition the buzzer emits a beep code every 10 seconds corresponding to the number of the error MK2430 11 only Settings menu 11 Relay if
4. M 16 3 3 3 eisdem 17 34 BC c 3 4 1 MK2430 12 3 4 2 MK2430 11 c centi lc 17 3444 Interfaces uoa oe cette bna hee uq a EAA 3 4 4 1 BMS bus 3 4 4 2 USB interface naa 18 4 Installation and connection 19 AT Installati nu u saa qanuna S 19 4 1 1 Overview of enclosures lI I anna 19 4 1 2 Dimension diagram flush mounting enclosure 19 4 1 2 1 Flush mounting sessssensssesusssenussenunsssnunssssunssssunesssnnnsssunessennnsenenessennnssen 20 TGH1389en 08 2012 3 2 BENDER Table of Contents 4 1 2 2 Cavity wall and panel mounting sees 21 4 1 2 3 Mounting brackets u u 21 4 1 3 Dimension diagram surface mounting enclosure 22 4 1 3 1 Installation of the surface mounting enclosure w 22 4 2 COMMECCIOMS scssiesscssnsecssnsetscaieseonsescoseadennotcenasanecoontenisesochoicacesssgcesoconsdenedoabeceosoesconsaten 23 4 2 1 Notes ON connection esssennssunssennssunssenussunsssunsssnnssensssunsennusssnssnsussennssunnssnnssnussennn 23 42 2 Wiring diagram cscesssenssesscasssznniesavnseecesseccoassescavauessasscenssccocussieassescoanscgnistcchaseestasyetd 24 4 2 3 Connection assignment a a 26 42 3 1 MK2430 12 si 42 3 2
5. MKA OAIT ass ne rt o EPOR SERERE Poe 4 3 Examples for BMS bus connection and addressing 27 5 Commissioning and testing 33 5 1 Tests before switching on sseessssessesenssssennsssunnsssnnnsssennsssnunsssnunnsssnnnsssnnenne 34 5 2 Tests after switching on sssesssssennsssennsssennssenunsssnnnsssunnsssnnnsssennsssnnnsssnnnssssunnne 35 5 3 Make parameter settings we 35 5 3 1 Settings at the MK2430 u u u 36 5 3 2 Settings in the software TMK SET ssssssssscssssssecssecssssseccssesessecsssneeeesseesssess 37 5 3 3 Tests after parameter setting u u u 38 5 4 Periodic verification and service ertet 38 5 4 1 Periodic verification sonsenennossesnennersennennesseneonnnsseonennersennennnsseneonnsssenenne 38 5 4 2 Service and support u 40 543 MalWetemance y E M 41 6 Troubleshooting secasccnsdesscocosuststssdeernstsnscosteetsonsvoresesoonsussssestesensasassesievees 43 6 1 Error messages of MK2430 6 2 MalfuhctionS u uu a maana uquna muqqa ye cie 45 7 1 Operator control and display elements 45 7 2 Quick reference guide ou eccseseccseseccssesscsssecsssescecssecessseecsssecessueeessneecssnecssneessaeees 47 7 2 1 Display in error free operation
6. _ Bopyoyem umop jeMod K oys y 1e O SpJo28J ejeq Jeo o Jeep sajue Alo siH nu u nu u Jayaweieg ad1A1aS nu w Bummas Bumas 9JoN L3SYNL OEtvCMIN O vCMIN Jesp Asojoey abuey owen UL aS JojouleJeg TGH1389en 08 2012 72 Menu mode Operation and setting FZ BEN DER TGH1389en 08 2012 73 4 BEN DER Menu mode Operation and setting 74 TGH1389en 08 2012 Technical data A BEN DER 9 Technical data 9 1 Technical data Insulation coordination acc to IEC 60664 1 Rated ins lation Voltage a rete ed deret id d E eed dtt Rated impulse voltage pollution degree Supply voltage SUPPLY VOlIQUE Uscita Bett E AC DC24V Frequency Tange k ettet eet eee 0 40 60Hz Operating range U wAC18 28 DC18 30V ROWELLONSUMDLION energie lt 3VA Voltage failure without reset ttt lt 155 Displays and LEDs Display amp hiaractels secet ran four lines 4 x 20 characters Standard message texts n ananassa 20 languages PEE DD lt 150 Programmable text messages aasan 200 History memory messages Staridard text Imessque s u a seen seen 3x 20 characters Additional text message press button to access e 3x20 characters Alarm LEDs a set of LEDs ss NORMAL green WARNING yellow ALARM red Scie ah as German English Buttons 5 ISOMETER test buzzer mute additional
7. 6 2 Malfunctions List of possible errors and proposals for the correction of the faults This error list does not claim to be exhaustive Possible error codes occurring during a test are listed in the chapter Test function on page 49f Errors Possible cause Actions MK2430 display blank Check AC DC 24 V power supply Display is lit up Replace the MK2430 but no characters on the screen Function buttons not working Replace the MK2430 LEDs not working Replace the MK2430 Character matrix visible on display but firmware does not start Processor does not start replace MK2430 Time of day gets lost in case of short term voltage failure Replace the MK2430 Error during transfer of the assign ments or basic settings via the USB interface MK2430 address not properly set menu MK2430 address does not match setting of TMK SET configu ration software USB cable defective wrong serial interface com port set in TMK SET Error on internal BMS bus Device addresses not properly set on the internal bus interface cables A B mixed up network incor rectly terminated or not at all incorrect parameter setting with TMK SET Error relating function of digital inputs Digital inputs not correctly set with TMK SET Defec tive connection does not match pre assignment Incorrect setting neutral medical 44 TGH1389en 08 2012 V BENDER 7 Oper
8. IN8 Alarm Address channel XXX 08 Alarm BSV battery operation IN9 Alarm Address channel XXX 09 Alarm BSV overload IN10 Alarm Address channel XXX 10 Alarm BSV converter failure IN11 Alarm Address channel XXX 11 Alarm BSV fault IN12 Alarm Address channel XXX 12 Alarm BSV test run TGH1389en 08 2012 61 4 BENDER Menu mode Operation and setting 8 4 4 6 Settings menu 6 Buzzer The buzzer will sound in the event of a warning or an alarm message Setting the frequency and repetition rate to distinguish the two buzzer tones 1 Exit 2 Warning 3 Alarm 1 Exit Back to the main menu 2 Warning 3 Alarm Various standard signals can be selected for Warning and Alarm An individual buzzer sound can be selected via TMK SET During setting the selected buzzer signal will sound and the LED will light up or flash 8 4 4 7 Settings menu 7 Common acknowledgement Setting indicating whether this MK2430 should respond to the acknowledgement of the buzzer buzzer mute initiated by pressing Buzzer mute button dy on another MK or TM operator panel On or Off Activating the common acknowledgement function can for example make it possible to acknowledge mute an alarm buzzer tone on an MK or a TM located in a neigh bouring building from an MK2430 in a central location The alarm message itself will remain visible on the display until its cause has been rectified 1 Exit 2 Common ack On 1 Exit
9. The voltage required for these inputs is provided via the power supply unit which also supplies power to the MK2430 Any message text can be assigned to the inputs 3 4 3 MK2430P The MK2430P contains the programming of the standard display and the factory activation of up to 20 alarm addresses A line containing a note about the assigned equipment can be programmed individually for each alarm address This line appears as the first line in an alarm For many applications with medical IT systems this programming scope is sufficient A programming template in the shape of a form is available for customer specific programming Furthermore up to 200 individual alarms can be programmed in the factory subject to an additional fee This type of programming is recommended for EDS RCMS medical gases or BSV systems TGH1389en 08 2012 17 4 BEN DER System description 3 4 4 Interfaces MK2430 feature a BMS bus and USB interface 3 4 4 1 BMS bus The internal BMS bus is used for communication with MEDICS components e g modules such as UMC UMA UFA UFC LFC or devices like RCMS EDS SMI SMO ATICS alarm indicator and operator panels The MK2430 is the master whenever the address is set to 1 An address setting of 2 150 denotes operation as a slave The Master is responsible for specific tasks Asa master clock it synchronises the time of all devices on the internal BMS bus t
10. 8 4 4 11 Settings menu 11 Relay neaesssssenssssenssssennsssennssssennsssunnsssennsssennsssnnnnsenenn 8 44 2 Settings menu 12 Password 8 4 4 13 Settings menu 13 Service menu unenseonsennnssenessunssennssonssennssnnnssenessannsen 67 8 4 5 Menu 5 Control ice ertet aaa keen trien inii 68 84 5 BACK c 68 8 4 5 2 Control menu 2 Reset AlarmClear 68 8 4 5 3 Control menu 3 EDS start stop a 69 8 4 5 4 Control menu 4 Test communication MK2430 11 only 69 8 4 6 Menu 6 External devices u a 70 8 4 7 Menu 7 Info u 71 8 5 Overview of setting options u 71 TGH1389en 08 2012 5 4 BENDER Table of Contents 9 Technical data 73 91 Technicaldata u S a eere aaar E a W 73 9 1 1 Standards v ccccsscsssssssssessssssesssesssessesssesssesssessesssecesesssessesssessscssesssesssesscsseesseeasesseeessess 76 92 Ordering information secsscsessasscsccgsssscorssesstonsesscspnsnsecgcusscatasasstasgcesosecaeasscccasunsdwases 76 j3dq 79 6 TGH1389en 08 2012 VL BENDER 1 How to get the most out of this manual 1 1 How to use this manual This operating manual describes the currently applicable software version of the MK2430
11. E When an attempt is made to open one of these menus the password entry screen appears automatically Enter password 000 Once a valid password has been entered full access will be granted to all menus except the Service menu until menu mode is exited 52 TGH1389en 08 2012 Menu mode Operation and setting FZ BENDER 8 2 Menu overview diagram The following diagram will help you to familiarise yourself with the menu 1 Exit 2 Values Exit 3 Testaddresses 5 Digital inputs 6 Buzzer 7 Common reset 8 Clock 10 Interface 11 Relay 13 Service menu 1 Exit 2 Reset AlarmClear 3 EDS Start Stop 4 Test communication 6 External devices TGH1389en 08 2012 53 4 BENDER Menu mode Operation and setting 8 3 Main menu functions Menu item Mode Page 1 Back Exit menu mode 2 Measured values No function Displays history with information about messages acknowl u edgements and associated times 55 4 Settings Various settings for this MK2430 57 5 Control This menu offers various options for controlling the overall 68 system Extemal devices Settings on the connected evaluators e g EDS4xx and en RCMSAxx 7 Info Information about the device type the firmware version i and the last time the assignments were transmitted 8 4 The main menu
12. If you exit the menu the standard display EDS will appear in the last line until the current test pass finishes Other abbreviations that might appear in the last line of the display EDSa Automatic mode Insulation fault location has been started by e g ISOMETER ATICS or isoMED427P on PGH47x EDSs Single mode A single pass has been started by IN2 on PGH471 8 4 5 4 Control menu 4 Test communication MK2430 11 only Testing communication via the BMS bus For this purpose an error message is simulated on a digital input This fault message is sent to evaluator devices e g alarm indicator and test combinations MK2430 SMO etc via BMS bus Check that these devices are responding to the fault message as requested 1 Exit 2 Channel 003 Test communication Channel 003 Setting of the channel whose message is to be activated TGH1389en 08 2012 69 4 BENDER Menu mode Operation and setting 8 4 6 Menu 6 External devices This menu is used to set and control external devices Functions include for example displaying information about connected devices address software version device type or continuous displaying a channel on a connected evaluator After calling the menu select the address of the external device to be displayed e g EDS4xx 12 or RCMS4xx 12 1 Back 001 MK2430 002 EDS151 003 ATICS2 ISO V1 08 Address type and version of the connected device are indicated When no de
13. JJ P Q N M TD E oW FJ TGH1389en 08 2012 21 FZ BEN DER Installation and connection 4 1 3 Dimension diagram surface mounting enclosure 17 PG13 5 Fig 4 2 MK2430 in surface mounting enclosure 4 1 3 1 Installation of the surface mounting enclosure A smooth and even surface is a precondition for installation Only use fastening screws of the size specified below Failure to observe this can result in deformation or damage to the enclosure e Use the empty enclosure as a template for marking the drilling holes e Maximum diameter of the screws Thread of screw 3 mm bolt head 7 mm 22 TGH1389en 08 2012 Installation and connection A BEN DER 4 2 Connections Risk of electric shock Before fitting the enclosure and working on the device connections make sure that the power supply has been disconnected and the sys tem is dead Failure to comply with this requirement will expose personnel to the risk ofelectric shock Furthermore the electrical installation may sus tain damage and the device may be destroyed beyond repair gt You must only connect the MK2430 as illustrated in the diagram in this chapter Do not make any changes to the internal wiring Non compliant connection or arbitrary changes can lead to serious malfunctions or even the complete failure ofthe MK2430 The device contains components that can be damaged by electr
14. 1 First MK2430 Test address 3 5 Alarm address 2 3 4 5 6 7 Bus address 2 Second MK2430 Test address 3 5 Alarm address 1 3 4 5 6 7 Bus address 7 Third MK2430 Test address 3 5 Alarm address 1 2 3 4 5 6 28 TGH1389en 08 2012 Installation and co nnection F BENDER Example 2 Intensive care unit with two IT systems and four rooms UFC107E 107TD47 PRC487 PGH474 EDS474 UFC107E 107TD47 PRC487 PGH474 EDS474 MK MK 2430 2430 Device Parameters Address settings First UFC107E switchover and monitoring module 107TD47 Bus address 3 PRC487 Bus address 4 PGH474 Bus address 111 EDS474 12 Bus address 61 Second UFC107E switchover and monitoring module 107TD47 Bus address 5 PRC487 Bus address 6 PGH474 Bus address 112 EDS474 12 Bus address 62 Alarm indicator and test combinations Bus address 1 eee Test address 3 5 Alarm address 2 3 4 5 6 7 8 61 62 111 112 TGH1389en 08 2012 29 4 BEN DER Installation and connection Device Parameters Address settings Bus address 2 Second MK2430 Test address 3 5 Alarm address 1 3 4 5 6 7 8 61 62 111 112 Bus address 7 Third MK2430 Test address 3 5 Alarm address 1 2 3 4 5 6 8 61 62 111 112 Bus address 8 Fourth MK2430 Test address 3 5 Alarm address 1 2 3 4 5 6 7 61 62 111 112 30 TGH1389en 08
15. 2012 Installation and connection BEN DER Example 3 Intensive care unit with two IT systems and four rooms B ATICS EDS151 EDS151 Device Parameters Address settings First switchover and monitoring module ATICS A Bus address 3 EDS151 A Bus address 4 Second switchover and monitoring module ATICS B Bus address 5 EDS151 B Bus address 6 Alarm indicator and test combinations Bus address 1 First MK2430 Test address 3 5 Alarm address 2 3 4 5 6 7 8 Bus address 2 Second MK2430 Test address 3 5 Alarm address 1 3 4 5 6 7 8 Bus address 7 Third MK2430 Test address 3 5 Alarm address 1 2 3 4 5 6 8 Bus address 8 Fourth MK2430 Test address 3 5 Alarm address 1 2 3 4 5 6 7 TGH1389en 08 2012 31 FZ BEN DER Installation and connection Example 4 System with 3 RCMS one MK2430 and one MK800 RCMS460 RCMS460 RCMS460 messaqes upto 16 Device Parameters Address settings Residual current evaluators 1 RCMS460 Bus address 3 2 RCMS460 Bus address 4 3 RCMS460 Bus address 5 Alarm indicator and test combinations Bus address 2 MK2430 Test address Alarm address 1 3 4 5 Bus address 1 MK800 Test address Alarm address 2 3 4 5 32 TGH1389en 08 2012 VL BENDER 5 Commissioning and testing Accomplish start
16. 4 Settings menu 4 Value addresses Currently has no function 8 4 4 5 Settings menu 5 Digital inputs MK2430 11 only Setting of the operational characteristics of digital inputs INO1 IN12 The following setting can be made individually for each input 24V high or OV low If 24V is set for an input an alarm message will be output if 24 Volt exists there If OV is set for an input an alarm message will be output if 0 V exists there It is for this reason that you should always set unused digital inputs to 24V 1 Exit 1 Exit 2 0peration mode 2 Input IT01 24V 3 Function general Alarm at 24V Digital inputs 1 Exit Back to the main menu 2 Operation mode Use the arrow buttons to select the digital input and confirm your selection by pressing Use the arrow buttons to select 24 V or 0 V Press to accept the entry Repeat the procedure to set more digital inputs 3 Function Set the message text category neutral or medical see neutral and specific alarm messages on page 61 Digital input alarm texts A neutral or specific alarm message can be assigned to all digital inputs A neutral alarm message indicates the alarm the channel and the address of the device triggering the alarm In comparison specific alarm messages medical signal non modifiable pre programmed alarms e g oxygen Assign the inputs in accordance with table neutral and specific alarm messages on page 61 Other
17. 8 4 4 Back Exits menu mode 1 Exit 2 Values 3 History 4 Settings 8 4 2 Menu 2 Measured values This menu has no function 54 TGH1389en 08 2012 Menu mode Operation and setting A BENDER 8 4 3 Menu 3 History The MK2430 can store up to 250 messages in the history memory ring buffer Once the MK2430 reaches the limit of 250 messages message 251 will overwrite message 1 The History menu provides information about messages acknowledgements and associated times It also indicates whether an alarm is still pending or when it was acknowledged set to mute with the ck Mute button The complete content of the history memory with additional texts and address of the device sending the message can be displayed on a PC and printed out using the TMK HISTORY software version V3 or higher All interfaces of MK2430 can be used for connection 1 Use the arrow buttons to select the entry you require The most recent entry appears first on the display Older messages can be selected using the arrow buttons Entry No 003 003 From 21 05 11 16 00 Ack 21 05 11 16 00 To 22 05 11 11 15 2 Press J to call up the message text for the selected entry The path the message took to reach MK2430 appears in the last line In this case an insula tion fault was received via the internal BMS bus from address 003 channel 01 The table on the following page contains information about other possible displays System 01 Insulati
18. BEN DER Installation and connection 4 1 2 1 Flush mounting The flush mounting enclosure is already enclosed in the scope of delivery of MK2430 1 Insert the supplied cardboard into the flush mounting enclosure to improve the shape stability and to provide protection against pollution 2 Insert the enclosure so that it is flush with the wall surface IT ED 7 e 2 a LH The flush mounting enclosure must not be installed lopsidedly or warped and must not be installed too deep below the surface 20 TGH1389en 08 2012 Installation and connection A BEN DER 4 1 2 2 Cavity wall and panel mounting For cavity wall or panel mounting you will need a Complete mounting kit Art No B95101000 9 50 mm E 2 50mm N Cavity wall mounting Panel mounting 4 1 2 3 Mounting brackets Use the laterally attached mounting clips to snap the MK2430 into the flush mounting enclosure Two mounting brackets M are used for additional support They are needed in particular if the MK2430 is to be fixed into an existing flush mounting enclosure e g MK2418 which is not intended for snap on mounting This requires Complete mounting kit Art No B95101000 lod leo
19. Data Service months This test must only be performed by an electrically skilled person who has been appoint ed to do so in agreement with the medical locations concerned Before carrying out the tests please refer to the instructions relating to the functional tests in the check list If no national directives apply you should perform the tests recommended by IEC 60364 7 710 2002 11 section 710 62 and DIN VDE 0100 710 VDE 0100 Part 710 2002 11 section 710 62 TGH1389en 08 2012 39 4 BEN DER Commissioning and testing 5 4 2 Service and support Bender would be delighted to provide service for commissioning troubleshooting and periodic verification First Level Support Technical support by phone or e mail for all Bender products e All questions about customer applications e Commissioning Troubleshooting Tel 49 6401 807 760 Fax 49 6401 807 259 only available in Germany 0700BenderHelp Tel and Fax E mail support bender service com Repair Service Repair calibration update and replacement service for all Bender products e Repair calibration testing and analysing Bender products e Hardware and software update for Bender devices e Delivery of replacement devices for faulty or incorrectly delivered Bender devices e Extended warranty for Bender devices with in house repair service resp replace ment devices at no extra cost Tel 49 6401 807 780 technical issues 49 6401 807 784
20. F BENDER Type Description Art No MK2430P 11 As MK2430 11 but programmed in the factory B 9510 0003 MK2430P 12 As MK2430 12 but programmed in the factory B 9510 0004 MK2430A 11 As MK2430 11 but with surface mounting enclosure B 9510 0005 MK2430A 12 As MK2430 12 but with surface mounting enclosure B 9510 0006 MK2430PA 11 As MK2430A 1 1 but programmed in the factory and with B 9510 0007 surface mounting enclosure MK2430PA 12 As MK2430A 1 2 but programmed in the factory and with B 9510 0008 surface mounting enclosure MK2430S 11 As 2430 11 but front plate with screw fixing B 9510 0011 MK2430S 12 As 2430 12 but front plate with screw fixing B 9510 0012 MK2430 Mounting bracket kit for flash mounting enclosure for snap mounting kit on mounting of the MK2430 Mounting kits for cavity wall B 9510 1000 complete mounting panel mounting or DIN rail mounting Flush mount Flush mounting enclosure included in the scope of delivery B 923 710 ing enclosure of MK2430 TMK SET V 4 x parameterisation software for MK2430 MK800 TM800 TMK HISTORY V 3 x for MK2430 MK800 TM800 cum SEE TM1000 and PRC1470 B 9602 0087 USB driver software for MK2430 MK800 and TM800 MEDISET V1 x parameterisation software for TM1000 and PRC1470 TGH1389en 08 2012 79 E BEN DER Technical data 80 TGH1389en 08 2012 VL BENDER INDEX A Acknowledgement 62 Additional text 48
21. Menu based parameter setting German English MK2430 basic parameters and EDS46x EDS47x EDS49x RCMS460 RCMS470 RCMS490 via BMS bus e Types available for flush and surface mounting e Easy commissioning due to predefined alarm text messages e 12 Digital inputs MK2430 11 only e History memory with real time clock to store 250 warnings and alarms e Replaces the MK2418 TGH1389en 08 2012 15 4 BENDER System description 3 3 Functionality 3 3 1 Display operating elements The backlit display features four lines of 20 characters It supplies medical and technical personnel with information that is always clear and unambiguous in order to helpthem to make decisions Every alarm message comprises three lines which appear spontane ously and three additional lines which can be displayed at the touch of a button The fourth line contains status information number of messages test procedures menu information Three LEDs are located above the text display They indicate Normal operation green warnings yellow or alarms red Five buttons are available for acknowledging or setting alarms to mute and warnings for testing the associated devices and for the menu system 3 3 2 Programming Standard message texts can be activated by enabling alarm addresses These texts are available in 20 languages Alarm addresses can be enabled via the device menu system without PC Individual message texts each comprising 6 lines of 20 ch
22. Set function and operating principle yes Enter system numbers or system designations If applicable use semi automatic mode yes Adapt the Isometer type to the test addresses v Save parameter setting to file v Send basic setting to MK v Send messages and alarms to MK TGH1389en 08 2012 37 FZ BEN DER Commissioning and testing 5 3 3 Tests after parameter setting no Select Test mode from the make corrections menu External devices Are all external device settings OK I yes no Simulate fault messages make corrections e g device failure insulation fault Generate a fault directly or select the Test communication function Is the fault correctly signalled by the MK2430 Does the MK2430 react properly to signals at the digital inputs yes MK2430 is ready for operation no make corrections 5 4 Periodic verification and service 5 4 1 Periodic verification Thefollowing periodic verification must be performed on electrical installations in com pliance with the local or national regulations that apply We recommend for your Bender products 38 TGH1389en 08 2012 Commissioning and testing VL BENDER Acquisition if applicable and the interaction between the compo nents on the system The test encompas
23. alarm indicator and test combination The functions and processes described may vary from those featured in other versions It is designed for skilled persons working in electronics and electrical engineering and in particular for those designing installing and operating electrical equipment in the medical sector Chapter 7 Operation on page 45 can also be used as a quick reference guide by medical personnel Before using the equipment please read this operating manual the supplement entitled Important safety instructions for Bender Products and the instruction leaflets supplied with the individual system components This document must be kept in an easily accessible location near to the equipment Should you have any further questions please contact our Technical Sales Department We are also happy to provide on site service Please contact our Service Department for more information Although great care has been taken in the drafting of this operating manual it may nevertheless contain errors and mistakes The Bender Group cannot accept any liability for injury to persons or damage to property resulting from errors or mistakes in this manual TGH1389en 08 2012 7 4 BENDER How to get the most out of this manual 1 2 Explanation of symbols and notes The following terms and symbols are used to denote hazards and instructions in Bender documentation The warning symbol indicates a potential dangerous situation that may resul
24. messages can be assigned to individual or all digital inputs with the TMK SET PC software If freely programmable alarm messages need to be displayed on a different MK2430 or an alarm indicator and operator panel the same alarm messages must have been programmed in the displaying device The alarm messages in the following table are sent to other MK or alarm indicator and operator panels via BMS bus and displayed there in plain text format 60 TGH1389en 08 2012 Menu mode Operation and setting VL BENDER Specific alarm messages These messages contain instructions for medical gases and UPS systems ES Alarm messages for medical gases are signalled by the red ALARM er LED and the buzzer sounding The buzzer can be set to mute ac knowledged It will sound again after 15 minutes by way of remind Non standard settings can only be made using the TMK SET soft ware neutral and specific alarm messages puts Meute alarm Messages Specific alarm messages Function Neutral Function Medical IN1 Alarm Address channel XXX 01 Alarm Oxygen IN2 Alarm Address channel XXX 02 Alarm Vacuum IN3 Alarm Address channel XXX 03 Alarm Nitrous oxide INA Alarm Address channel XXX 04 Alarm Compressed air 5 bar IN5 Alarm Address channel XXX 05 Alarm Compressed air 8 bar ING Alarm Address channel XXX 06 Alarm Nitrogen IN7 Alarm Address channel XXX 07 Alarm CO2
25. of the MK2430 Set parameters v Show version of standard texts and number of activated alarm addresses activated test addresses individually programmed messages a Go back to the main menu 8 5 Overview of setting options Die MK2430 supports various setting modes The table below shows where the individual parameters can be set TGH1389en 08 2012 71 Menu mode Operation and setting soDesseul SIUEUSJUIEUI VL BENDER x x EIN N N A SOI v Ae ds q Ae ds p pjepuejs y ui OWI x x EIN A N A Ae ds p eui SseJppe snq sa ul x IN L OSL L sseippe sDumes sgr SuH x 8N ayep Aep jo eui snq SI BIA 44O jul Jezznq 0 esuodsay x ZW A N A eBpejwouxoe uouuuuoo Aouanbayy S L Temau x OW z juoieing sBum s Jezzng JeAsajul a essayy x x EIN sg see ess w w seDenDue Ajuo x _ 6N UeuuJac 0z ess w 104 eBenBue ueulac x _ 6N UeuuJac ys u3 juo nuaw 104 eBenBue1 psomssed eBueu x _ ZIN 208 666 000 PJomsseq jduuoud P omssed ejeAnov x _ ZLIN A N A jdujoud puomssed Buiuoissiuuuuoo SIu6 L Joy 6a x ELN NO 40 HHO NO Jezzng euin Jejuw 1euJuns euoiny x EIN woyne 440 wone eun M S x x EIN wo ne 31uoof wone yb moeg SWg leuloyui eui uo seuenb WIV OM Uu 9Ag8qQ eui x x ELN S sek sw ep INTV isesodund 188 10 juo eBueyo x x EIN sw09 sw 00 cr jul no 8uul Jejunoo 9s84 Jee o Jeejo
26. text scroll menu Buzzer Buzzer message aaa can be acknowledged adoption of characteristics of new value BUZZER interval treo E usus unan naq Saamna as configurable Vlricus configurable BUZZERTEDERIION c accetti ttt ete T e ERU Heated configurable Inputs MK2430 11 only Digital inputs tnter 12 INT IN12 Galvanic separdti fi nannten ee yes Activation of the digital inputs via potential free contacts extraneous voltage Operating principle N O N C operation individually selectable for each input FARO SRI RE een N O operation Voltage range high sssessscssssssnsseessrsnssecsssnsseesesnsssesersnessesersnessesossessessosessesoenae AC DC10 30V TGH1389en 08 2012 75 4 BENDER Technical data Voltage range IOW tnter AC DCO 2V Recommended cable min J Y St Y 0 8 eu E E AEE E ETRE EE EE 500m Interfaces heat ernennen RS 485 and USB V2 0 V1 1 Technical data for the RS 485 interface Proto llsu ssesesneeninishrenkuken BMS B ud rat une neunten bu etu Et cd 9 6 kbit s EOS estore lt 1200 m Recommended cable twisted pair one end of shield connected to PE J Y St Y min 2x0 8 Terminating resistor 120 Q 0 25 W can be connected via DIP switch Device address BMS DUS l nn cette tetti dices DIP switch 1 150 Factory setting device address 1 master Programming Interfaces RS 485 or
27. the main menu When the MK2430 is connected to the power supply the following information appears on the display for approx 3 seconds It indicates the address and firmware version of the device This information can also be accessed in the Info menu MK2430 11 Addr 001 Software 4 02 D228 Date 02 05 12 www bender de com If the MK2430 was not supplied with voltage for several days a long er time may be required for start up approx 30 seconds In this E case time and date have to be entered again If there are no messages pending the standard display will appear after the start SYSTEM READY 09 50 The standard display and the message texts can be modified in the TMK SET software TGH1389en 08 2012 51 FZ BENDER Menu mode Operation and setting Press the Menu button for approximately two seconds to open the main menu 1 Exit 2 Values 3 History 4 Settings 5 Control 6 External devices 7 Info The following buttons are used on the main menu ESC Exit function or go up one menu level A Y Select menu items xil Confirm selected menu item Enter If no buttons are pressed in a menu for a period of more than five minutes menu mode is exited automatically exception test com E munication in the Control menu and position mode in the Exter nal devices menu Some menus are password protected Password protection is only effective if the password has been enabled switched on
28. up according to the following start up patterns 1 Tests before switching on 2 Tests after switching on 3 Make parameter settings Settings at the MK2430 Settings in the software TMK SET 4 Tests after parameter setting Please note down all settings and attach these to the equipment or installation documentation RS TGH1389en 08 2012 33 F BENDER Commissioning and testing 5 1 Tests before switching on Does the supply voltage match the information on the MK2430 nameplate no built in correctly at the beginning and end of the BMS bus and switched on yes no digital inputs have the appropriate voltage connected correctly yes no devices correctly set according to the plan yes no the BMS bus instruction leaflet adhered to yes no system up to date yes Switch voltage supply on Then proceed with tests after switching on yes no Tees ee erg o Is the supply voltage Connect the supply voltage properly connected properly ves n no Is the BMS bus properly Connect the BMS bus connected properly and check polarity yes of the terminals A B Are terminating resistors Install the terminating resistors properly or switch them on use the DIP switch at MK2430 Term on off MK2430 11 only Do the Make corrections I yes nto MK2430 11 only Are the Make corre
29. we 47 7 2 2 Display in fault condition ssssscssssseccsseescsssecssseesesusecessscccsseesssseecssneeessnseessases 47 T23 Test f lnCtion RR a uqi a a auqa sa 49 4 TGH1389en 08 2012 Table of Contents FZ BENDER 8 Menu mode Operation and setting 51 8 1 Switching on and calling up the main menu sss 51 8 22 Menu overview diagram u 53 83 Main menu functions sseeennsseeennnnseseennunsernennnsserennnnserennnnssereennnsensennnnsrennnnn 54 84 Themain menu cecinere tere bte reete rhet be ebbe bebe eti 1a 54 BA Backs a S asas apa sa aan ua asa aga aqyay 54 8 4 2 Menu 2 Measured values u 54 8 4 3 Men 3 history M 55 8 4 4 Menu 4 Settings 57 BAAN Back qe askha 58 8 4 4 2 Settings menu 2 Alarm addresses eee 58 8 4 4 3 Settings menu 3 Test addresses a 8 4 44 Settings menu 4 Value addresses 8 4 4 5 Settings menu 5 Digital inputs MK2430 11 only 60 8 4 4 6 Settings menu 6 BUZZer u u a 62 8 4 4 7 Settings menu 7 Common acknowledgement 62 8 4 4 8 Settings menu 8 Clock u 63 8 44 9 Settings menu 9 Language 8 4 4410 Settings menu 10 Interface
30. 6 gramme the MK2430 You can use the PC software TMK HISTORY to read out the MK2430 history memory MK2430 11 only Relay output Programmable contact for device errors test of assigned devices device failure and common alarm message Devices without BMS bus connection but with test input e g ISOMETER TGH1389en 08 2012 25 4 BEN DER Installation and connection 4 2 3 Connection assignment The connections are located on the rear of the devices V2 V2 U2 U2 USB 0 IN9 12 IN9 A IN10 B IN11 IN12 Term off 4 2 3 1 MK2430 12 The MK2430 12 features a single terminal strip as it receives all messages via the BMS bus It receives these messages for example from the 107TD47 an MK2430 11 the signal converter SMI47x the EDS or the RCMS Supply voltage Us looped through connection for the supply voltage Us Note U2 V2 Note Make sure that the power supply of MK2430 is isolated against PE If this is not taken into consideration and if a PC is connected to the USB interface the MK 2430 device and the PC may sustain damage USB USB connection Cable Type A plug on type B plug S BMS bus and USB interface shield A B BMS bus Term BMS bus terminating resistor switcha
31. Addresssettings 28 32 Alarm addresses 16 58 Alarm message 16 neutral 60 specific 60 Alarmrelay 43 66 Assignments 71 Automaticmode 69 B Baudrate 65 Beep code 43 Bender Service personnel 67 BMS bus 18 Buzzer 47 62 66 C Cablelength 23 Cavity wall mounting 21 CEST 63 Changeover periods 39 Commissioning 33 Common acknowledgement 62 Communication 69 Connection 23 Control 68 D Date 63 Date format 63 device address 65 Diagram 53 Digital inputs 25 60 Display 16 drill holes 19 E Error codes 50 Errorlist 44 Evaluators 70 External devices 70 F Features 15 Firmware version 51 71 Flush mounting enclosure 20 frequency 62 Functional test 39 G Gases medical 61 H History memory 17 55 Intended use 9 Interfaces 18 TGH1389en 08 2012 81 VL BENDER INDEX L Language 16 64 LEDs 16 M Main menu 52 Master password 67 Measured value addresses 60 medical gases 61 MEDICS 13 MK2430 11 17 MK2430 12 17 MK2430P 17 Mounting brackets 21 0 Operation 45 condition 47 fault free 47 Ordering information 78 Overview of enclosures 19 P Panel mounting 21 parallel indication 14 17 Password 52 67 Periodic verification 38 Personnel 10 Potential free contacts 17 Programming 17 Q Quick reference guide 45 R Regulations for erection and installation 78 Relay mode 66 Relay output 27 Reset 68 S Selective operation 11 Serv
32. Back to the main menu 2 Common ack Setting of the common acknowledgement for the internal bus On Buzzer can be acknowledged muted externally Off Buzzer cannot be acknowledged muted externally 62 TGH1389en 08 2012 Menu mode Operation and setting FZ BENDER 8 4 4 8 Settings menu 8 Clock This menu is used to set the time of day date and date format display These settings remain stored for approx 5 days following a power supply failure The clock switches automatically to central European summer time CEST and winter time CET Reset the clock if the time of day no longer matches your local time following automatic switchover Automatic switchover can be deactivated see 5 Daylight sav 1 Exit CEST 2 Time 17 45 3 Date 21 09 11 4 Format dd mm yy 1 Exit Back to the main menu 2 Time Set time of day hours and minutes 3 Date Set date according to the format indicated in line 4 4 Format Select German dd mm yy or American mm dd yy 5 Daylightsav Setting for automatic switchover to Central European Sum mer Time Auto automatic switchover Off no switchover You can setthe system time of day and date on any MK2430 or alarm indicator and operator panel The settings are transferred via the EU BMS busto the master device address 1 which transfers the settings to all other MK2430 or alarm indicator and operator panels TGH1389en 08 2012 63 PZ BENDER Menu mode Operation and sett
33. FZ BENDER The Power in Electrical Safety Operating Manual MK2430 Alarm indicator and test combination Software version 4 0x TGH1389en 08 2012 FZ BENDER Bender Inc USA 700 Fox Chase Coatesville PA 19320 Toll Free 800 356 4266 Phone 610 383 9200 Fax 610 383 7100 E mail info bender org Canada 5810 Ambler Drive Unit 1 Mississauga ON LAW 4J5 Toll Free 800 243 2438 Phone 905 602 9990 Fax 905 602 9960 E mail infogbender ca com Web http www bender org BENDER Group O Bender Inc All rights reserved Content subject to change F BENDER Table of Contents 1 How to get the most out of this manual 7 1 1 HOW to use this manual J eese ttes treten tttennnnnttnnnnnitenn 7 1 2 Explanation of symbols and notes sessssssssscsssecsssseccssecessusecesneesssutecceneesenseees 8 2 Safety IRSUPUCti ns au pa 9 2 Intended use suu S 9 22 Qualified personnel 2 3 General safety instructions u u 11 2 4 Delivery conditions guarantee warranty and liability 11 3 System description ssereressenssnrssornsnensnnrnsnrnsnsnsrersinsnsnsnerernsnsnsnsnereresnensnens 13 EAE MEDICSP S e M 13 32 Features 3 3 Functionality uuu s aun sauna PRU E MEE Pre vei R 16 3 3 1 Display operating elements eene tnnt ttn 16 3 3 2 Programming pre
34. GH1389en 08 2012 35 4 BEN DER Commissioning and testing 5 3 1 Settings at the MK2430 Use of standard texts 9 Use TMK SET for yes parameter setting for details refer to 5 3 2 Set language e _ Set BMS bus address Set alarm addresses and system numbers l Set test addresses and types of Isometers Use of the standard assignment for medical gases UPS Setting medical Wiring acc to specifications Relay Set function and switching behaviour MK2430 11 no Can the buzzer sound be 9 Modify buzzer settings differentiated from signals of other devices ver Common acknowledgement on off EEE ENS Set time date l Set and activate password 36 TGH1389en 08 2012 Commissioning and testing VL BENDER 5 3 2 Settings in the software TMK SET Set language v Set password Set buzzer v Common acknowledgement on off Y MK2430 11 no v Set device address Standard display Enter the required text v Program alarm addresses for standard alarm ng messages Y Enter individual alarm messages for the required channels v Enter test addresses Y Use of standard assignment for medical gases BSV yes yes Y Setting medical Wiring acc to specifications Y Digital inputs Set function and operating principle v Relay
35. GH1389en 08 2012 System description A BEN DER and the messages will flash up alternately on the LC display The address of the device triggering the alarm can also be called up The audible signal sounds again once a configurable period of time has elapsed repetition can be deactivated Internal device parameters alarm addresses test addresses and the parameter setting for EDS and RCM systems can be accessed via the menu system As a master the MK2430 can also be used as master device in installations with a number of IT and EDS systems The test button can be used to check the operation of the associated devices e g insulation monitoring devices LIM Line Isolation Monitors or GFCI Ground Fault Circuit Interrupters A message is output only on the MK2430 on which the test button TEST was pressed The test and its individual evaluations are carried out sequentially Once the process is complete a message indicating that the test has been successful or a fault message is output MK2430 features e Display of operating status warning and alarm messages in accordance with IEC 60364 7 710 2002 11 DIN VDE 0100 710 2002 11 and other standards e Backlit clear LC text display 4 x 20 characters e Standard texts for messages in 20 languages e 200 freely programmable message texts with TMK SET PC software Bustechnology for easy installation and reduced fire load e Audible alarm can be acknowledged or set to mute e
36. USB V2 0 V1 1 USB cable Type A plug on type B plug SON WARE Gene TMK SET V 3 0 and higher Factory setting Dass WO tette n de e et UA activated Max cable length in case of power supply of 1 2 3 MK24 from one AN450 0 28 mm Z B J Y S Y N X 0 6 RT E 60 40 m 0 5 mm Z B JEY SOY N X 0 8 ne 250 70 m 05 mm 400 100 m 1 5 mn 800 210 10m 25 mn 1300 360 20 m Max cable length in case of power supply of 1 2 3 MK24 from one AN410 0 28 mm B JEU Y MOO cc een 300 150 100 n 0 5 mm zB J Y St Y nx 0 8 anne 500 250 150 n 0 75 MHI anre pini d Rd 7501375 250n 15mm2_I___ RONDE 1500 750 500n 2 5 Hi ea a E e a A 2500 1200 750 n Colours Front TOI enc n ERR RR DR RAL 7035 light grey RAL 7040 basalt grey VEI M RAL 5005 ultramarine blue IONE Plate en esse RAL 7035 light grey 76 TGH1389en 08 2012 Technical data A BEN DER Switching elements MK2430 11 only Tu cm EINEN 1 changeover contact FUNGON SERAN programmable Operating princip e s N C or N O operation programmable Electrical service life under rated operating conditions 10 000 switching operations Contact data acc to IEC 60947 5 1 Utilisation category DC 12 Rated operational voltage 24V Rated operational current EDEN i OEREIN 1A inimum contact rating ttt 1 mAat AC DC 10V General data EMC immu
37. aracters can be programmed with the TMK SET software An LED yellow or red and an audible signal can be assigned to each message For this purpose the PC is connected to the USB interface or BMS bus RS 485 16 TGH1389en 08 2012 System description A BEN DER 3 3 3 History memory Warnings and alarms are written to the history memory automatically with date and time stamp 250 text messages can be saved After this each subsequent message then overwrites the oldest message in the history memory message 251 will overwrite message 1 etc The history memory can be read out via the operating menu or the TMK HISTORY PC software 3 4 Versions 3 4 1 MK2430 12 The MK2430 12 is used for visual and audible indication of alarms from Bender s EDS RCMS and MEDICS systems and for testing assigned devices e g insulation monitoring devices LIM GFCI Furthermore the MK2430 12 can also be used as parallel indication in conjunction with MK2430 11 resp SMI472 12 The programmed message texts are displayed on the LCD in the selected language 3 4 2 MK2430 11 The MK2430 11 features all the functions of the MK2430 12 plus 12 digital inputs and a programmable relay output All digital inputs are electrically isolated in three groups of 4 The input voltage is AC DC 10 30V 2 5 mA HIGH 10 30 V LOW 0 2 V In practice these digital inputs IN1 IN12 are controlled via potential free contacts N C or N O operation configurable
38. ation This chapter can also be used as a quick reference guide by medical operating personnel 7 1 Operator control and display elements 3 4 5 8 6 7 9 LED and LCD LED NORMAL Power On indicator green only lights up if no warnings or alarms are pending 2 LED WARNING Warnings yellow 3 LED ALARM Alarm messages red 4 LCD Display of operating status and alarm messages as well as menu functions TGH1389en 08 2012 45 F BENDER Operation The buttons have the following functions MK2430 settings for display and control functions No In operating mode In menu mode ESC button d Mute button Exit function without saving 5 Set buzzer to mute following alarm resp go up one menu level acknowledge alarm When the buzzer is sounding you can press ESC to set it to mute Button i additional text Down button Y 6 Switch between display text and possi D m own in menu ble additional text for message Scroll button j z Scroll through the warnings and alarms Up button A if there is more than one message pend Up in the menu ing TEST button Press and release LED test 8 Press and hold down Initiate testing of No function assigned devices insulation monitoring devices LIM GFCI MENU button 9 Starts menu mode in order to make ENTER button Confirm menu option selection
39. ble 26 TGH1389en 08 2012 Installation and connection A BEN DER 4 2 3 2 MK2430 11 The MK2430 11 alarm indicator and test combination provides additional terminal strips for the 12 digital inputs and one optional relay output IN1 IN12 Digital inputs 1 12 0 IN1 4 Common connection O for the digital inputs 1 4 0 IN5 8 Common connection O for the digital inputs 5 8 0 IN9 12 Common connection O for the digital inputs 9 12 21 22 24 Relay output option NC no function not connected Also refer to Settings menu 5 Digital inputs MK2430 11 only auf Seite 60 4 3 Examples for BMS bus connection and addressing Missing or incorrectly installed terminating resistors e g in the mid dle ofthe bus will cause bus instability Please also note the informa tion on the BMS Bus operating manual TGH1389en 08 2012 27 F BENDER Installation and connection Example 1 Operating theatre or intensive care unit with two IT systems and three rooms UMC107E 107TD47 PRC487 UMC107E PRC487 107TD47 NN gases Device Parameters Address settings First changeover and monitoring module UMC107E 107TD47 Bus address 3 PRC487 Bus address 4 Second changeover and monitoring module UMC107E 107TD47 Bus address 5 PRC487 Bus address 6 Alarm indicator and test combinations Bus address
40. controls data traffic on the BMS bus In order to program the MK2430 a PC must be connected tothe BMS bus either via an RS 232 RS 485 adapter orto a USB RS 485 adapter 3 4 4 2 USB interface A PC can also be connected to the MK2430 via the USB interface with a USB cable Type A plug onto Type B plug The interface can only be accessed when the MK2430 has been removed Only the connected MK2430 can be read out and set via the USB interface Optional software e Youcan use the the TMK SET PC software to display and change the MK2430 settings e You can use the PC software TMK HISTORY to read out the MK2430 history memory 18 TGH1389en 08 2012 VL BENDER 4 Installation and connection 4 1 Installation 4 1 1 Overview of enclosures The MK2430 in flush mounting enclosure with a special mounting kit also suitable for installation in a panel or cavity wall MK2430A in surface mounting enclosure 4 1 2 Dimension diagram flush mounting enclosure 1 r j I r I D 3 171 ooo U 86 Fig 4 1 MK2430 in flush mounting enclosure front panel cut out 161x77 mm The MK2430 is mounted in its enclosure by means of clips In addi tion the MK2430 can be secured in its enclosure with screws For this E purpose markings for the drilling holes are prepared at the rear of the front plate drilling hole 3 mm counterboring 6 mm TGH1389en 08 2012 19 4
41. ctions digital inputs connected properly I yes no Are the other devices gt Make corrections Are the addresses on all Make corrections possibly Are the rules specified in Make corrections Are all devices inthe gt Update the respective device Provide the appropriate operating voltage you first have to switch supply voltage on 34 TGH1389en 08 2012 Commissioning and testing 5 2 Tests after switching on no Connect a PC utilizing TMK SET software Activate the TMK SET function Bus scanning Are addresses and software versions of connected devices OK J yes Set MK2430 parameters 5 3 Make parameter settings Does the MK2430 display YES a fault message Make corrections If Check the supply voltage 9 of MK2430 terminals U2 required connect another V2 Voltage OK or different power supply unit for MK2430 supply vos Fix the MK2430 to the enclosure Does anything appear on no Did the supply voltage or the MK2430 display the MK2430 fail Remove yes the fault Make a note of the message Adapt the indicating device to the system or remove the fault Make corrections All settings can be carried out via the TMK SET software KS see diagrams VL BENDER Alternatively some settings can be carried out via the MK2430 menu T
42. ddresses for devices whose alarm messages are to be displayed as standard messages on this MK2430 The address of this MK2430 is automatically set to On All other alarm addresses are set to Off Set the addresses of devices whose messages are to be displayed on this MK2430 to On Only these addresses are monitored for presence on the BMS bus If a device cannot be found on the bus an alarm message will appear The text of individual messages can be modified using the TMK SET software If anumber of systems or areas e g several operating theatres are connected to the MK2430 the system numbers 1 4 can be assigned to them 1 Exit 1 Exit 2 Edit table 2 Address 002 On 3 Clear table System No nn Alarm addresses Exit Back to the main menu Edit table Use the arrow buttons to select the address on the internal BMS bus and confirm your selection by pressing J Use the arrow buttons to select On and activate this address Off deactivate Press J to accept the entry Use the arrow buttons to select System no nn and confirm your selection by pressing 1 Repeat the procedure to activate more alarm addresses N 3 Clear table Deactivate all addresses off Clear table is only possible when there are no test addresses activated see setting menu 3 Test addresses 58 TGH1389en 08 2012 Menu mode Operation and setting A BENDER Possible system number settings
43. eck the function of the assigned insulation monitoring devices e g 107TD47 IRDH LIM Line Isolation Monitors and GFCI Ground Fault Circuit interrupters A message is output only on the MK2430 on which the test button TEST was pressed 1 Test all devices 1 Test all devices 2 Test single device 2 Test single device Addr 3 01 02 107TD47 1 Test all devices Test of all devices set in the Test addresses menu 2 Testsingle device Selecta device using the arrow buttons and press 1 button During the test the text TEST will appear in the status bar TEST flashes if the message on the display is associated with the test The assigned devices are tested one after the other The MK2430 automatically evaluates the messages that appear Once the process is complete either a common message indicating that the test has been successful or an error message is output If more than one device has been tested a separate error code will be displayed for each device failing the test TGH1389en 08 2012 49 E BEN DER Operation The following error codes are displayed in the event of an ISOMETER failing the test Error Meaning for the 107TD47 Meaning for the IRDH Note code hospital ISOMETER Industrial ISOMETER No messages received from ISO No messages received from ISO 0 METER despite it confirming the METER despite it confirming the test command test co
44. es e Display and operating units such as TM operator panels or MK alarm indicator and test combinations e Single and three phase monitoring modules Examples of modules in the MEDICS system include UMC USC UFC and EDS insulation fault loca tion systems e Communication between these components via the BMS bus two wire connec tion The connection of third party technical systems by means of protocol converters gateways or via digital inputs and relay outputs The real strength of MEDICS is to be found in communication between all involved components and the resulting information provided to the user The functionality of the equipment is continuously monitored Operating states irregularities faults and equipment failures are displayed This means high operational reliability of the instal lation for the user 3 2 Features On its backlit LC display 4 x 20 characters the MK2430 displays messages from all BMS bus devices assigned via alarm addresses As well as being used as a standalone indicator the MK2430 also supports parallel indication in different rooms In the event of an alarm message the yellow WARNING LED or the red ALARM LED lights up and the message appears on the LC display in plain text format At the same time there is an audible signal acknowledgeable can be switched to mute If a second message is received whilst the first is still pending the audible signal will sound again 14 T
45. faults e Device failure e Test results e Measured values The LC text display makes this information easy to understand The connection between the MKs and the changeover and monitoring modules is implemented with bus technology During normal operation the MK2430 indicates the readiness for operation of the system The MK2430 11 features 12 digital inputs allowing messages from other technical equipment to be recorded and displayed on the MK2430 for example from medical gases or additional battery supported safety power supply systems BSV systems TGH1389en 08 2012 9 4 BEN DER Safety instructions MK2430 come into use in e healthcare facilities industrial and office buildings e public buildings Please heed the limits of the area of application indicated in the technical specifications Use which deviates from or is beyond the scope of these technical specifications is considered non compliant Use for the intended purpose also includes e Device specific settings compliant with local equipment and operating condi tions The observation of all information in the operating manual e Compliance with test intervals 2 2 Qualified personnel Only appropriately qualified personnel may work on Bender devices Personnel who are familiar with the installation commissioning and operation of the equipment and have undergone appropriate training are considered skilled persons Such personnel must have read this operati
46. ice 40 Setting 57 Setting possibilities 71 Setting values 39 Shape stability 20 Single mode 69 Snap on mounting 21 Software 16 18 Standard display 47 51 Status line 48 49 Switching on 34 35 System components 7 T Terminating resistor 23 25 26 27 TEST 49 Test procedure 69 Text messages 17 Time 63 TMK SET 58 60 61 Transmission speed 65 U USB interface 18 82 TGH1389en 08 2012 Bender Inc USA 700 Fox Chase Coatesville PA 19320 Toll Free 800 356 4266 Phone 610 383 9200 Fax 610 383 7100 E mail info bender org Canada 5810 Ambler Drive Unit 1 Mississauga ON LAW 4J5 Toll Free 800 243 2438 Phone 905 602 9990 Fax 905 602 9960 E mail info bender ca com Web http www bender org FZ BENDER
47. ing 8 4 4 9 Settings menu 9 Language Selection of the language for using the menus and displaying messages alarm and operational status messages on the MK2430 Changes take effect immediately 1 Exit 2 Menu English English 3 Mess 1 Exit Back to the main menu 2 Menu Set the operating language for the menu English or Deutsch 3 Message Set the display language for the messages You may select English English French Italian Portuguese Spanish Portuguese Brazilian Dutch Norwegian Swedish Finnish Danish Polish Hungarian Czech Slovenian Croatian Serbian Turkish Indonesian RS The language setting activates the language specific special charac ters However user defined alarm texts remain unchanged Therefore do not program or transfer the individual alarm texts until the language settings are configured 64 TGH1389en 08 2012 Menu mode Operation and setting A BENDER 8 4 4 10 Settings menu 10 Interface Setting of the device address of this MK2430 and indication of the transmission speed baud rate for the connection to the internal BMS bus RS 485 1 Exit 2 Addr RS485 001 3 Baud RS485 09600 1 Exit Back to the main menu 2 Addr Device address setting of this MK2430 Any address can be selected within the range of 1 150 the addresses 100 to 110 are intended for special applications e g PC OPC and cannot be used for devices Factory set
48. ing of bus Aare zes for devices which are to carry out a 59 test when the TEST button is pressed 4 Measured value No function 60 addresses 5 Digital MK2430 11 only Setting of the operational characteristics 60 inputs of digital inputs Setting of the frequency and repetition rate of buzzer sig 62 nal Setting whether this MK2430 should respond to a common 7 Common ta acknowledgement initiated via the reset button on an exter 62 acknowledgement nal device Setting of the date and time on the real time clock on this MK2430 At the same time this setting is sent via BMS bus 8 Clock and all other devices are synchronised The device with 63 address 1 MK2430 or alarm indicator and operator panel synchronises all other devices every hour 9 Language Selection of operating language for the MK2430 German or 64 English 10 Interface Setting of the device address and baud rate for this MK2430 65 11 Relay Mode of operation and function of the common alarm relay 66 alarm relay on the MK2430 11 12 Password Change password activate deactivate password 67 Reserved for settings to be made by authorised Bender Service personnel Call up information about the device sta 13 Service menu 67 TGH1389en 08 2012 57 4 BENDER Menu mode Operation and setting 8 4 4 1 Back Exit menu mode 1 Exit 2 Alarm addresses 3 Test addresses 4 Value addresses 8 4 4 2 Settings menu 2 Alarm addresses Setting of bus a
49. mmand Only insulation fault message Only insulation fault message 1 Channel 1 received received from channel 1 2 Only overload fault message Only insulation fault message Channel 2 received received from channel 2 3 Onlyinsulation fault message and Channel 1 overload message received and2 4 Only overtemperature message Channel 3 received Onlyinsulation fault message and Chanel 5 overtemperature message and3 received 6 Only overload message and over Channel 2 temperature message received and3 Unable to send test command as Unable to send test command as 14 Slave only request not received slave request not received slave 15 ISOMETER did not confirm the ISOMETER did not confirm the test no response test no response Notes about error codes e For MK2430 operating as slaves on the BMS bus a time out of 50 seconds is applicable for error codes 0 and 14 Error code 14 is displayed if the test has been requested on a slave but the test command cannot be sent because the MK2430 was not scanned This can be the case if the address gap upstream of the MK2430 is so large that the master does not scan the MK2430 refer to BMS bus operating manual This error code is less of an indicator that an ISOMETER is faulty and much more of an indicator of a fault on the BMS bus system 50 TGH1389en 08 2012 VL BENDER 8 Menu mode Operation and setting 8 1 Switching on and calling up
50. nditions of sale and delivery set out by Bender apply Conditions of sale and delivery can be obtained from Bender in printed or electronic format TGH1389en 08 2012 11 4 BEN DER Safety instructions 12 TGH1389en 08 2012 V BENDER 3 System description 3 1 MEDICS The MK2430 alarm indicator and test combinations are integral components of the MEDICS system MEDICS is an intelligent system that guarantees safe power supply in medical locations Example of a section of a hospital with the MEDICS system internal BMS bus Main distribution Central building process control Internal BMS bus Main distribution board 2 UMC710D4 Distribution board for AG2 rooms ICU KK in SMI472 12 UMC107E UFCIOTE Locations for medical use TGH1389en 08 2012 13 4 BEN DER System description Legend to example MK2430 Alarm indicator and test combination RCMS Residual current monitoring system for TN S systems SMI472 Signal converter for third party systems e g med gases BSV sys tems TM Alarm indicator and operator panel UFC107E Changeover and monitoring module for IT systems with EDS in sulation fault location system UMC107E Changeover and monitoring module for IT systems UMC710D Changeover module for main distribution boards USC710D Control module for changeover modules preferably in main distri bution boards MEDICS includ
51. ng manual and understood all instructions relating to safety 10 TGH1389en 08 2012 Safety instructions A BEN DER 2 3 General safety instructions Bender devices are designed and built in accordance with the state of the art and accepted rules in respect of technical safety However the use of such devices may introduce risks to the life and limb of the user or third parties and or result in damage to Bender devices or other property Only use Bender equipment Asintended n perfect working order in compliance with the accident prevention regulations and guidelines appli cable at the location of use Eliminate all faults immediately which may endanger safety Do not make any unauthorised changes and only use replacement parts and optional accessories purchased from or recommended by the manufacturer of the equipment Failure to observe this requirement can result in fire electric shock and injury Information plates must always be clearly legible Replace damaged or illegible plates immediately Make sure that the dimension of the BSV battery supported safety power supply the generator set and the whole wiring is adequate The applicable national and international standards must be observed here Only in this way selective opera tion of safety devices can be achieved and a high degree of safety in case of over load and short circuit can be ensured 2 4 Delivery conditions guarantee warranty and liability The co
52. ni EMC emissio Classification of climatic conditions acc to IEC 60721 acc to EN 61000 6 2 2002 08 acc to EN 61000 6 6 2007 09 Stationary Transport Long term s Operating terperatufe sauce tt R man 5 55 C Classification of mechanical conditions acc to IEC 60721 SCION AN USE aea A S is mus a Susu m u a 3M4 lire 2M2 Kin Stern Je enter 1M3 Operating mode nennen continuous operation Mounting S display oriented Connection pluggable screw terminals Connection properties supply voltage BMS bus Connection of single conductors rigid flexible conductor size 02 02 25 mm AWG 24 12 flexible with ferrules without with plastic sleeve nn 025 25 025 25mm Multi conductor connection 2 conductors with the same cross section igid flexible NINE RO RO 02 1 02 15 mm flexible with ferrule without plastic Sleeve 025 1 mm flexible with TWIN ferrule with plastic s leeve__ aasan 05 15mm TGH1389en 08 2012 77 4 BEN DER Technical data Connection properties inputs Connection of single conductors rigid flexible conductor size 0 08 1 5 0 08 1 5 mm AWG 28 16 exible with ferrules without with plastic sleeve ann 0 25 1 5 0 25 0 5 mm2 ulti conductor connection 2 conductors with the same cross section rigid flexible 0 08 0 5 0 08 0 75 mm exible with ferrule without pla
53. nn Meaning 00 No text appears in line 1 of the alarm message 01 04 Texts System 01 to System 04 are displayed T Programmed text is displayed 8 4 4 3 Settings menu 3 Test addresses Setting of bus addresses for insulation monitoring devices e g 107TD47 IRDH transfer switching devices with monitoring functions ATICS LIM Line Isolation Monitors and GFCI Ground Fault Circuit interrupters which are to carry out a test when the TEST button is pressed The setting can only be made for devices which have also been activated in the Alarm addresses menu and or programmed for individual alarm texts Individual alarm texts are a minimum requirement for e Channel 1 3 setting 107TD47 e Channel 1 setting IRDHxxx 1 Exit 1 Exit 2 Edit table 2 Address 002 3 Clear table Ger tetyp MED Iso Test addresses 1 Exit Back to the main menu 2 Edit table Use the arrow buttons to select the internal BMS bus ad dress and confirm your selection by pressing 4 Use the arrow buttons to select the device type LIM Line Isolation Monitors GFCI Ground Fault Circuit interrupter IND Iso Industrial Insulation monitoring device MED Iso Medical insulation monitoring device Off Address deactivated Press J to accept the entry Repeat the procedure to activate more addresses 3 Clear table Deactivate all addresses off TGH1389en 08 2012 59 4 BENDER Menu mode Operation and setting 8 4 4
54. o static discharges ESD When work activities are carried out atthe opened device the safety precautions for the dissipation of electro static electricity have to be observed gt P 4 2 1 Notes on connection e Connect the MK2430 to the supply voltage terminals U2 V2 If you are connecting the MK2430 to a DC 24 V supply take the line voltage drop into account if you are using long supply cables for the supply voltage Consider the maximum permissible cable lengths for the supply voltage U2 V2 when using an AN450 or AN410 power supply unit refer to Technical data e The connection to the internal BMS bus is made via the terminals A B Connect the BMS bus as described on the BMS bus instruction leaflet Use a shielded cable of at least mm or 0 8 mm cross section for the interface line e g J Y St Y n x 2 x 0 8 Connect the shield to PE at one end When wiring the bus connection please note that a 4 wire cable 2 x BUS 2 x US with suitable cross section is required when routing the supply voltage U e Set the terminating resistor for the BMS bus on the Term DIP switch Factory set ting off e MK2430 11 only Use cables with a cross section of at least 0 75 mm 2 when con necting the digital inputs and the relay output The maximum cable length per connection is 500 m TGH1389en 08 2012 23 Installation and connection VL BENDER 4 2 2 Wiring diagram LL dO V OW LL 0 VOMIN USWOS UO3WOS c Us
55. on fault Meas value T Address 003 01 3 Asshown in the example above the min and max values display can be called up by pressing A 4 Press J again to go back to the entry selection screen Repeat this process for all required messages Then press ESC to exit the menu TGH1389en 08 2012 55 4 BENDER Menu mode Operation and setting Possible displays in the last line of the history memory message text display Text Meaning Address Address of the device triggering the message aaa device address kk aaa kk channel no of the message ia mp Number kk of digital input on this MK which triggered the message Note that the current history entry was created as the result of a test initi TESTex ated on this MK Note that the current history entry was created as the result of a test and TESTin was triggered on the device assigned to it insulation monitoring device LIM GFCI 56 TGH1389en 08 2012 Menu mode Operation and setting 8 4 4 Menu 4 Settings The following menu options are available for configuring the MK2430 VL BENDER tus make settings for specific operating conditions and run firmware update Menu item Mode Page 1 Back Exit Settings menu go up one menu level 2 Alarm Setting of bus addresses for devices whose alarm messages 58 addresses are to be displayed on this MK2430 3 Testaddresses Sett
56. ounds Also other Buzzer function signalling devices can be installed to indicate pending mes sages on the MK2430 Programming via TMK SET gt individual alarms or operating Programmable messages 66 TGH1389en 08 2012 Menu mode Operation and setting A BENDER 8 4 4 12 Settings menu 12 Password Change activate deactivate password 1 Exit 2 Password 3 Status 1 Exit Back to the main menu 2 Password Change password Factory setting 807 3 Status Activate or deactivate password protection Some menus are password protected Password protection is only effective if the password has been enabled switched on ES When an attempt is made to open a window the entry screen for en tering the password appears automatically Enter password 0 00 Once a valid password has been entered full access will be granted to all menus except the Service menu until menu mode is exited 8 4 4 13 Settings menu 13 Service menu The Service menu is reserved for settings made by authorised Bender Service personnel It can only be accessed subject to the entry of a master password In the Service menu information about the device status can be called up and settings for specific operating conditions can be made TGH1389en 08 2012 67 4 BENDER Menu mode Operation and setting 8 4 5 Menu 5 Control This menu offers various options for controlling individual devices or the overall system
57. q3 SOL IWS OWT DAN UU DSA ZI dOEFZYN OWN ZL O VZMW wa3skS eSdIGAW TGH1389en 08 2012 24 Installation and connection A BEN DER Legend to wiring diagram Terminating resistor If two or more devices are connected to each other via the BMS bus each bus 1 line must be terminated with a resistor R 120 Q at the start and end of the BMS bus can be connected via DIP switch on the MK2430 and alarm indicator and operator panel BMS bus connection A variety of Bender devices with a BMS bus can be connected to the BMS bus These may include 107TD47 insulation monitoring devices PRC487 control devices RCMS470 residual current evaluators and many more 3 Power supply unit in the MEDICS module sufficient for supplying power to at least three MK2430 Cable between the MEDICS module and MK2430 Please observe the permissi 4 ble cable lengths and cross sections when using the AN450 power supply unit in MEDICS modules Digital inputs The digital inputs may be controlled either via internal or exter nal voltage or potential free contacts If the inputs are controlled via an exter 5 nal voltage the common O is applied to terminal 0 and the 1 signal to the relevant input IN1 IN12 In this case the connections between the termi nals 0 and V2 and the common connections and U2 are not required USB interface For PC connection The TMK SET PC software is used to pro
58. ses the following Inspection Marking display elements mechanical components wiring parameterisation connection of third party systems eval uation of fault memory Measurement Internal external supply voltages potentials bus voltage bus protocol bus scan Testing Device function device communication Documentation Test results recommendations for eliminating defects To be Test performed Interval by Functional test of the IT system monitoring insulation load cur Once rent transformer temperature and connection monitoring by Medical every pressing the TEST button on the alarm indicator and test combi personnel working nation or on the alarm indicator and operator panel day Functional test of the changeover module Electrically Functional test of the automatic changeover modules Every six DNE tos skilled per Please observe the information in the chapter Testing the change en months over module operating manual of the changeover module Functional test of the IT system monitoring insulation load cur Electrically Everv six rent transformer temperature and connection monitoring on the skilled per m insulation monitoring device son Electricall I s y Every 12 Checking the setting values and changeover periods skilled per months son Test the transfer switching device the IT system monitoring and Bender Every 24 the connection to the SCADA system Supervisory Control and
59. ss see table 09 50 Time of day example Possible displays during insulation fault location or testing zzz Meaning EDSa EDS insulation fault location in progress automatic EDSp Continuous EDS insulation fault location in progress EDSs Single pass EDS fault location in progress EDS EDS insulation fault location was deactivated the current measur ing sequence is still running Test in progress TEST flashes if the message on the display is asso TEST f ciated with the test noMA No MASTER MAST Device is currently substitute master P e Press the 5 button 6 for detailed information Since 01 05 12 16 52 Device ISOMETER Addr channel 003 00 xxlyy iM 17 30 Line 1 date and time the message occurred Line 2 device triggering the message Line 3 Address of the device sending the message Line 4 Xx consecutive number of the message displayed yy 2 number of pending messages message text page in this case page 2 17 30 time of day example 48 TGH1389en 08 2012 Operation FZ BEN DER The display may deviate accordingly in case of user defined messages E If messages are pending and one ofthe arrow buttons is pressed the current message will appear on the display If no further button is pressed this indication will be displayed for 15 seconds 7 2 3 Test function Press and hold down the TEST button for at least one second to ch
60. stic sleeve a aaaaaaaasasasasas 0 25 0 34 mm exible with TWIN ferrule with plastic sleeve t 0 5 mm Stripping engtli s ccena te tte tee eret emt tte epa 7 mm Tightening torque sessessscssssssecssssssssonessecscrneeecsusnseceseanssessesnssseecaneesessasessessnsnssesonan 0 5 0 6 Nm Degree of protection internal components DIN EN 60529 IP50 surface mounting type IP54 Degree of protection terminals DIN EN 60529 Flammability class casti epit tede RO ei Weight cett tiet 9 1 1 Standards The MK2430 alarm indicator and test combination meets the requirements of the regulations for installation IEC 60364 7 710 2002 11 and DIN VDE 0100 710 VDE 0100 Teil 710 IEC 60364 7 710 2002 11 9 2 Ordering information Type Description Art No Alarm indicator and test combination according to IEC 60364 7 710 2002 11 DIN VDE 0100 710 featuring a BMS bus and a USB interface 12 digital inputs one relay output alarm texts programmable via interfaces and PC standard text display Version Flush mounting enclosure MK2430 11 B 9510 0001 Alarm indicator and test combination according to IEC 60364 7 710 2002 11 DIN VDE 0100 710 MK2430 12 featuring a BMS bus and a USB interface B 9510 0002 alarm texts can be programmed via interfaces and PC standard text display Version Flush mounting enclosure 78 TGH1389en 08 2012 Technical data
61. t in bodily injury and or damage to property Observe the associated safety instructions This symbol indicates important information about the correct use of the equipment purchased Failure to observe the associated instructions can result in equipment malfunctioning or cause problems in the environment in which it is being used e P This symbol indicates tips for using the equipment and particular use ful information This type of information will help you to optimise your use of the equipment 8 TGH1389en 08 2012 VL BENDER 2 Safety instructions 2 1 Intended use The universal MK2430 alarm indicator and test combination is used for visual and audible indication of operating status and alarm messages from Bender s EDS RCMS ATICS and MEDICS systems In MEDICS monitoring systems the MK2430 meets the requirements of IEC 60364 7 710 2002 11 and DIN VDE 0100 710 2002 11 in respect of test functions for IT system monitoring and alarms from changeover devices The IT system monitoring equipment can be tested using the programmable test button Important display functions e Normal operation indicator green LED e Insulation fault e Overload e Overtemperature e Messages from EDS insulation fault location systems and RCMS residual cur rent monitoring systems e Interruption of the phase conductor or PE conductor of the ISOMETER e Supply line failure e Power supply fault conditions and changeover system
62. the function device error has been set also the alarm relay switches No Displays Description Actions 1 DISPLAY ERROR Display defective Replace the MK2430 switch off the device for 10 2 minutes switch on again if 2 AC BUSERRORO Fault C bus unsuccessful Replace the MK2430 3 RTCERROR Clock chip defective Replace the MK2430 Replace memory chip D15 4 FLASH ERROR Assignment chip defective socketed or replace MK2430 Address of the MK2430 on the 5 Address ERROR XXX intemalBNS bus is alreadyin T ange the MK2430 address in the menu use XXX current address 6 Overflow ERROR 03 More than 80 alarm messages Reduce number of messages are present at the same time Overflow ERROR 05 More than 200 device failure Reduce number of messages messages are present Overflow ERROR 07 More than 99 text messages Reduce number of messages are present Automatic correction of the Overflow ERROR 08 history memory is carried out because of voltage interrup tion Make a note of the error code Overflow ERROR 11 Stack Error and contact Bender Service 7 Checksum ERROR Program memory defective Replace the MK2430 Please make a note of the cause of error the error number and if applicable the error code This information facilitates the diagnosis and repair of the equipment X Error code TGH1389en 08 2012 43 VL BENDER Troubleshooting
63. ting is address 001 master 3 Baud The fixed pre assigned baud rate is 9600 Bit s Change the corresponding device address if a number of MK2430 are connected to one internal BMS bus One MK2430 must have the address 1 master All other MK2430 are addressed in consecutive order 2 3 4 There should be no gaps between addresses to ensure smooth system functioning also refer to the BMS bus operating manual Data exchange will only work between devices with the same baud rate TGH1389en 08 2012 65 4 BENDER Menu mode Operation and setting 8 4 4 11 Settings menu 11 Relay Set the mode of operation and function of the optional alarm relay on the alarm indicator and test combination This menu only exists on the MK2430 11 1 Exit 2 0peration mode N O 3 Function Device error 1 Exit Back to the main menu 2 Relay mode Set the mode of operation N O N O operation N C N C operation 3 Mode Alarm relay switches in the event of Setting Description Device error Relay switches in case of an internal fault on the MK2430 11 Common alarm Relay switches in case of any warning or alarm message Relay switches as soon as the MK2430 recognises a device Device failure failure Relay switches for approx 3 seconds once a test is started via the TEST button at the assigned devices insulation monitoring devices LIM GFCI ISOMETER test The relay switches as soon as the buzzer s
64. vice is detected under this address the character appears Use the arrow buttons to select the address of the external device and confirm your selection with the I button If the device has been recognised the MK2430 will read the current settings of the connected device The device type is displayed in the first line of the display Use the Up Down buttons to select the appropriate function or device setting Confirm with the 1 button Example 1 Exit 107TD47 1 Exit 107TD47 2 Position mode 2 Chan t 1 Re 20 KQ Numerous setting options are available in the EDS or RCMS menu These are described in more detail in the operating manuals for the corresponding systems Exit EDS470 General Channel Relay 70 TGH1389en 08 2012 Menu mode Operation and setting FZ BENDER 8 4 7 Menu 7 Info MK2430 11 Addr 001 Software 4 02 D228 Date 02 09 11 www bender de com Information about the device type the firmware version and the last time the assign ments were transmitted Assignments are settings carried out via the PC software TMK SET e Enter standard texts e Assign texts and functions to alarm messages and digital inputs of the MK2430 e Set parameters Select ESC Exit menu mode A Show date of last assignment transmission Assignments are settings carried out via PC software e g TMK SET Enter standard texts Assign texts and functions to the alarm messages and digital inputs
Download Pdf Manuals
Related Search
Related Contents
LG ND4520 docking speaker 安全増防爆対応ヒーター Zanussi DE 6754 S Instruction Booklet Kenmore 303.9380612 Dehumidifier User Manual Samsung S AM Bubble Washer with Diamond Drum, 6 kg, White Kasutusjuhend User Manual Hamilton Beach 49615 User's Manual バネル一ラSF夕イプ Copyright © All rights reserved.
Failed to retrieve file