Home
User`s Manual
Contents
1. _A1S62TCRTBW S2 Tt 2 Performance Specification The A1S62TC performance specification is indicated in Table 2 1 Table 2 1 A1S62TC performance specification Specification A1S62TCRT S2 Temperature input points 2 channel module Supported platinum i y Refer to Table 2 2 temperature measuring resistor _ Ambient temperature Specification 23 C 5 C accuracy Ambient temperature 0 to 55 C Item Full scale x 0 3 1 digit 1 Full scale x 0 7 1 digit 1 0 5s 2 channel It is not connected with the number of channels used Heating control output period 1 to 100s Cooling control output period Sensor compensation value setting 50 00 to 50 00 Operation when sensor input is Upscale pracessin disconnected P P 9 Heating proportional band Ph Cooling proportional band Pc Within the temperature range set by the platinum temperature measuring resistor to be used Cooling method setting Air cooling water cooling Output signal ON OFF pulse Rated load voltage 10 2 to 30 0VDC peak voltage 30 0VDC 0 1A 1 point 0 4A common Maximum inrush current 0 4A 10ms Transistor a output Me ai cament when Less than 0 1mA Maximum voltage drop 1 0VDC TYP 0 1A when ON 2 5VDC MAX 0 1A OFF gt ON Less than 2ms ON OFF Less than 2ms resistor load Between the input and grounding transformer insulation Between the input and channel transformer insulation Sampling period 0 1 to 1000 0 Set
2. Insert the wire breakage detection connector installation screw into the mounting holes in the module and after tightening the connector installation screw with specified toque If the connector is not property installed and tightened it may result in error detetion of wire breakage WIRING PRECAUTIONS Z CAUTION Be sure to ground the shield wire with a special programmable controller ground of Type III or above Not doing so could result in malfunction Use applicable solderless terminals and tighten with the specified torque If any solderless spade terminal is used it may be disconnected when the terminal screw comes loose resulting in failure When wiring in the programmable controller be sure that it is done correctly by checking the product s rated voltage and the terminal layout Connecting a power supply that is different from the rating or incorrectly wiring the product could result in fire or failure Tighten the terminal screws with specified torque Loose terminal screws may cause a short circuit fire or malfunction Tightening the terminal screws too far may cause damage to the screw and or the module resulting in short circuit or malfunctions Be sure that cuttings wire chips or other foreign matter do not enter the module Foreign matter may start a fire or cause failure or malfunctions Be sure to fix communication cables and power cables leading from the module by placing them in the duct or clamping
3. For CH1 2 Do not bunch the cables with the main circuit high voltage cable or BW2 For CH2 load cables from other than programmable controller or install them FHNctunusanie close to each other Install the cables far apart from high frequency circuits such as the high voltage cable and inverter load main circuit as much as possible This increases the noises surges and induction 3 Perform a one point grounding for the shielded line and shields of the seal and cable at the programmable controller However there may be cases when grounding should be performed externally depending on the noise condition the system highly reliable an external cabling with low noise effects are 5 2 Module connection example 1 A1S62TCRT S2 A1S62TCRT S2 L1H Lic 3 Oo T L2H E o L2C Heating Cooling ICOM A DC24V 7 p Tes Contro b1 2 S target 5 A ff aHa B2 iL b2 1 Please use the cable with shield 2 A1S62TCRTBW S2 A1S62TCRTBW S2 4 L1H Q x L1C 3 5 7 L2H E g zs L2C Heating Cooling COM tj DC24V 7 A f o 3 ATH S T K BIL 5 Y Contro b1
4. 21 497 3084 TAIWAN Tope Co Ltd FRANCE _ Diltronic S A Tel 886 2 8228 0658 Tel 01 34 51 33 00 INDIA AmtechElectronics PVT Ltd ITALY ELNET s n c Tel 02712 25324 Tel 041 50 19 939 Table 2 2 The types of supported platinum temperature measuring resistor and the measured temperature range Platinum suring resistor temperature range resolution temperature range resolution 200 0 to 600 0 0 1 200 0 to 200 0 ae 200 0 to 500 0 5a 300 to 900 200 0 to 200 0 300 0 to 300 0 For the general specifications refer to the User s Manual for the programmable controller CPU used Pt 100 3 Name of Each Part 4 Loading and Installation Precautions when handling the A1S62TC and installation environment are A1S62TCRT S2 A1S62TCRTBW S2 sitar ea explained PE SUTE IRUN n Sata D For details of implementing and setting up this unit please refer to the User s 1 rtre Ne ene Manual for the programmable controller CPU used cH2j C OUTE sa AM D Is 4 14 Handling Instructions S 4 LH 1 The module case is made of pla
5. 5 target k E a A2 fol 2 i Bz i b2 E BWi 5 4 i 1 Please use the cable with shield 2 Refer to the following for the connection of the wire breakage detection connector Cable with shield Connect to BW1 For CH1 BW2 For CH2 NC Unusable 6 External Dimensions 6 1 A1S62TCRT S2 cu A1S62TCRT S2 pH OUTO DRUN com Coura KLAR LAR AR ARS AAA INO INGOT 130 5 12 a m 5 0 gt m N Jo a a Jo nv o 6 5 93 6 3 69 0 26 6 2 A1S62TCRTBW S2 34 5 1 39 au AIS62TCRTBW S2 HOUT O RUN a 130 5 12 a m o o gt o a s xy o LJ M 42 1 65 65 93 6 3 69 0 26 Warranty 0 71 60 24 5 34 5 1 39 Unit mm inch 6 Lal SE v S Mitsubishi will not be held liable for damage caused by factors found not to be the cause of Mitsubishi machine damage or lost profits caused by faults in the Mitsubishi products damage secondary damage accident comp
6. MITSUBISHI A1S62TCRT S2 Heating Cooling Temperature Control Module A1S62TCRIBW S2 Heating Cooling Temperature Control Module with Wire Breakage Detection Function Mitsubishi General Purpose Programmable Controller User s Manual Hardware Thank you for purchasing the Mitsubishi general purpose programmable controller MELSEC A series Prior to use please read this manual thoroughly and familiarize yourself with the product A1S62TCRT U HW E Type IB NA 66801 E 0804 MEE MEUSEG 1997 MITSUBISHI ELECTRIC CORPORATION SAFETY PRECAUTIONS Read these precautions before using When using Mitsubishi equipment thoroughly read this manual and the associated manuals introduced in the manual Also pay careful attention to safety and handle the module properly These precautions apply only to Mitsubishi equipment Refer to the CPU module user s manual for a description of the programmable controller system safety precautions These SAFETY PRECAUTIONS classify the safety precautions into two categories DANGER and CAUTION lt sDANGER Procedures which may lead to a dangerous condition and cause death or serious injury if not carried out properly Z CAUTION Procedures which may lead to a dangerous condition and cause superficial to medium injury or physical damage only if not carried out properly Depending on circumstances procedures indicated by CAUTION may also be lin
7. al Perseo Ingr 2 Via Paracelso 12 l 20041 Agrate Brianza Milano Italy Tel 39 039 60531 Spain Mitsubishi Electric Europe B V Spanish Branch Carretera de Rubi 76 80 E 08190 Sant Cugat del Valles Barcelona Spain Tel 34 93 565 3131 France Mitsubishi Electric Europe B V French Branch 25 Boulevard des Bouvets F 92741 Nanterre Cedex France TEL 33 1 5568 5568 South Africa Circuit Breaker Industries Ltd Private Bag 2016 ZA 1600 Isando South Africa Tel 27 11 928 2000 Hong Kong China Taiwan Korea Singapore Thailand Indonesia India Australia Mitsubishi Electric Automation Hong Kong Ltd 10th Floor Manulife Tower 169 Electric Road North Point Hong Kong Tel 852 2887 8870 Mitsubishi Electric Automation Shanghai Ltd 4IF Zhi Fu Plazz No 80 Xin Chang Road Shanghai 200003 China Tel 86 21 6120 0808 Setsuyo Enterprise Co Ltd 6F No 105 Wu Kung 3rd Rd Wu Ku Hsiang Taipei Hsine Taiwan Tel 886 2 2299 2499 Mitsubishi Electric Automation Korea Co Ltd 1480 6 Gayang dong Gangseo ku Seoul 157 200 Korea Tel 82 2 3660 9552 Mitsubishi Electric Asia Pte Ltd 307 Alexandra Road 05 01 02 Mitsubishi Electric Building Singapore 159943 Tel 65 6470 2460 Mitsubishi Electric Automation Thailand Co Ltd Bang Chan Industrial Estate No 111 Moo 4 Serithai Rd T Kannayao A Kannayao Bangkok 10230 Thailand Tel 66 2 517 1326 P T Autoteknind
8. ensation caused by special factors unpredictable by Mitsubishi damages to products other than Mitsubishi products and to other duties A ror safe use e This product has been manufactured as a general purpose part for general industries and has not been designed or manufactured to be incorporated in a device or system used in purposes related to human life e Before using the product for special purposes such as nuclear power electric power aerospace medicine or passenger movement vehicles consult with Mitsubishi e This product has been manufactured under strict quality control However when installing the product where major accidents or losses could occur if the product fails install appropriate backup or failsafe functions in the system aT Country Region Sales office Tel Country Region Sales office Tel U S A Mitsubishi Electric Automation Inc 500 Corporate Woods Parkway Vernon Hills IL 60061 U S A Tel 1 847 478 2100 Brazil MELCO TEC Rep Com e Assessoria Tecnica Ltda Rua Correia Dias 184 Edificio Paraiso Trade Center 8 andar Paraiso Sao Paulo SP Brazil Tel 55 11 5908 8331 Germany Mitsubishi Electric Europe B V German Branch Gothaer Strasse 8 D 40880 Ratingen GERMANY Tel 49 2102 486 0 U K Mitsubishi Electric Europe B V UK Branch Travellers Lane Hatfield Hertfordshire AL10 8XB U K Tel 44 1707 276100 Italy Mitsubishi Electric Europe B V Italian Branch Centro Dir Colleoni P
9. ked to serious results In any case it is important to follow the directions for usage Store this manual in a safe place so that you can take it out and read it whenever necessary Always forward it to the end user DESIGN PRECAUTIONS lt gt DANGER Configure a safety circuit external to the programmable controller so that the entire system operates safety even if there is an external power error or if the programmable controller is malfunctioning A CAUTION Do not bundle or near the control cables and communication cables with the main circuit and power cables Keep them at least 100mm 3 94inch away from such cables Noise may cause malfunction INSTALLATION PRECAUTIONS Z CAUTION Use the programmable controller in the environment given in the general specifications of the this manual Using the programmable controller outside the range of the general specifications may result in electric shock fire or malfunctioning or may damage or degrade the module Insert the tabs at the bottom of the module into the mounting holes in the base module before installing the module and after tightening the module fixing screws with specified torque If the connector is not property installed and tightened If may result in malfunctioning failure or cause the module to lam out Do not directly touch the module s conductive parts or electronic components Doing so could cause malfunction or failure in the module
10. o Sumber Makmur Muara Karang Selatan Block A Utara No 1 Kav No 11 Kawasan Industri Pergudangan Jakarta Utara 14440 P O Box 5045 Jakarta 11050 Indonesia Tel 62 21 6630833 Messung Systems Pvt Ltd Electronic Sadan NO III Unit No15 M I D C Bhosari Pune 411026 India Tel 91 20 2712 3130 Mitsubishi Electric Australia Pty Ltd 348 Victoria Road Rydalmere N S W 2116 Australia Tel 61 2 9684 7777 a MITSUBISHI ELECTRIC CORPORATION HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN NAGOYA WORKS 1 14 YADA MINAMI 5 CHOME HIGASHL KU NAGOYA JAPAN When exported from Japan this manual does not require application to the Ministry of Economy Trade and Industry for service transaction permi Specifications subject to change without notice Printed in Japan on recycled paper
11. rganic solvents Number 1 LED RUN A1S62TC operation status display 6 Locations exposed to the direct rays of the sun ON Normal operation in progress A a Flashing 2 sec ON 2 sec OFF Write data error 7 Locations where strong power and magnetic fields are generated Flashing 1 sec ON 1 sec OFF Hardware error 8 Locations where vibration and shock are directly transmitted to the ol 2 OFF 5V power shutoff Watchdog timer error main module Transistor output status display ON Transistor output ON OFF Transistor output OFF ALI Alert alarm status display 5 Wiring ON Alert alarm is ON Flashing The measured temperature range is exceeded The precaution when wiring and the module connection example are shown M The platinum temperature measuring below resistor is not connected The platinum temperature measuring resistor cable is disconnected 5 1 Precaution when wiring OFF Alert alarm is OFF BR W Heater wire breakage detection status display In order to have the best result from the A1S62TC functions and to make ON Heater wire breakage is detected OFF Heater wire breakage is not detected Wire breakage Connector for current sensor necessary detection The external wiring precautions are shown below Connector Wire breakage detection 1 Use separate cables for the alternating current and A1S62TC external connector installation screw input signals to avoid A C surges and induction effects BW1
12. stic Be sure not to drop it or subject it Ca aeg to strong vibration Hech O c 4 2 Do not remove the module printed circuit boards from the case rae lo aal It may cause trouble ASSO ETO 3 When connecting the wiring do not allow wire cuttings or other foreign E NC ne matter to enter from the top of the module Remove any foreign matter l H from the module NC NC O 4 Tighten the module installation screws within the following tightening E pas 3 torque range NC NC aa aa L pa D pas D Module installation screw M4 screw 78 to 118Necm 97 Ors Var Ga alle I Wire breakage detection connector installation 15 to 30Necm screw M2 6 screws Use only for A1S62TCRTBW S2 yer A1S62TCRT S2 A1S62TCRTBW S2 4 2 Installations Enviroment A1S62TCRT S2 LED A1S62TCRTBW S2 LED Never install the AnS series programmable controller system in the following environments A1S62TCRT S2 A1S62TCRTBW S2 1 Locations where the ambient temperature is outside the range of 0 to H OUT O ORUN 55 C C 2 Locations where the ambient humidity is outside the range of 10 to BR W 90 RH Bee 3 Locations where dew condensation takes place due to sudden L RM temperature changes 4 Locations where there are corrosive and or combustible gasses 5 Locations where there is a high level of conductive power such as Name Description _ _ dust and iron filings oil mist salt and o
13. them Cables not placed in the duct or without clamping may hang or shift allowing them to be accidentally pulled which may result in a module malfunction and cable damage When detaching the communication cable from the module do not pull the cable portion For cables with connectors hold the connector at the junction to the module then detach it For cables without connectors first loosen the screw at the junction then detach to the cable Pulling the cable portion while it is connected to the module may cause a malfunction or damage to the module and cable STARTING AND MAINTENANCE PRECAUTIONS CAUTION Do not touch the terminal while the power is on It may cause malfunction Make sure to switch all phases of the external power supply off before cleaning or re tightening the terminal screws If you do not switch off the external power supply it will cause failure or malfunction of the module Tightening the screw too far may cause damage to the screw and or the module resulting in fallout short circuit or malfunctions Never disassemble or modify the module This may cause failure malfunctioning injury and or fire Make sure to switch all phases of the external power supply off before mounting or removing the module If you do not switch off the external power supply it will cause failure or malfunction of the module Do not install remove the terminal block more than 50 times after the first use of the prod
14. uct IEC 61131 2 compliant Always make sure to touch the grounded metal to discharge the electricity charged in the body etc before touching the module Failure to do so may cause a failure or malfunctions of the module DISPOSAL PRECAUTION A CAUTION When disposing of this product handle it as industrial waste About This Manual The following product manuals are available Please use this table as a reference to request the appropriate manual as necessary Detailed manual Manual name Manual No Model Code A1S62TCRT S2 Heating Cooling Temperature Control Module A1S62TCRTBW S2 Heating Cooling Temperature Control Module with Wire Breakage Detection Function User s Manual SH 3644 13JL36 Please read A1S62TCRT S2 Heating Cooling Temperature Control Module A1S62TCRTBW S2 Heating Cooling Temperature Control Module with Wire Breakage Detection Function User s Manual Detailed edition when using this unit 1 General Description This user s manual describes the specification name of each part wiring etc of the A1S62TCRT S2 Heating Cooling Temperature Control Module Hereafter abbreviated as A1S62TCRT S2 A1S62TCRTBW S2 Heating Cooling Temperature Control Module with Wire Breakage Detection Function Hereafter abbreviated as A1S62TCRTBW S2 A1S62TCRT S2 and A1S62TCRTBW S2 abbreviated as A1S62TC After unpacking confirm that there is the following products Main body Main body ANS62TCRT S2_
15. value setting range Maximum load current Response time Insulation method Table 2 1 A1S62TC performance specification continued Specification A1S62TCRT S2 A1S62TCRTBW S2 URD manufactured current sensor 2 CTL 12 S36 8 0 0 to 100 0A Current sensor CTL 6 P H 0 00 to 20 00A Former model CTL 6 P is also appli 5 Multiplex method A D conversion Number of alert 3 to 255 delays Supported solder less terminal R1 25 3 1 25 YS3 RAV1 25 3 V1 25 YS3A Internal consumed current 5VDC 0 19A Heater wire breakage disconnection specification Input method For the noise resistance dielectric withstand voltage and insulation resistance for the programmable controller system which uses this module refer to the power module specification found in the CPU Module User s Manual 1 1 digit error depends on the input range For setting unit of 1 C 1 C For setting unit of 0 1 C 0 1 C 2 Only the URD International Ltd current sensor can be used Sales channels for current sensors manufactures by URD International Ltd are listed as follows U S A Julia Industries Inc KOREA Joyang Trading Co Tel 949 831 0111 Tel 02 521 2294 BRAZIL Ananda Industial Ltda Sewon Tech Co Ltd Tel 011 5584 0959 Tel 02 868 9355 9356 UNITED Keum Ho Corporation KINGDOM Omni Components Tel 51 319 4155 4156 Tel 024 7622 5757 HONG KONG Weltronics Components Ltd GERMANY Allied Electronics GmbH Tel 2410 0623 Tel 02