TE-7000 Room Command Module
Contents
1. JBHNSON CONTRSLS European Electronic Controls Catalog Catalog Section A Product Bulletin TE 7000 Issue Date 1198 TE 7000 Room Command Module Jhtroduction The TE 7000 Room Command Module is designed for use with the VMA1400 series VAV Modular Assembly The VMA1400 is a control device for a variable air volume VAV terminal unit that provides conditioned air to the room in which the TE 7000 is installed The module has an NTC temperature sensor a dial for setpoint adjustment within the range of 12 to 28 C or 3 to 3K and an occupancy button with an LED indicator If the VAV controller is not already in occupied mode as shown by the LED indicator the occupant may press the occupancy button to obtain comfort control for a set period of time normally defaulted to one hour The module also has a built in connector for a PC with the software to test and commission the VMA1400 series VAV Modular Assembly and the air supply system Figure 1 TE 7000 Room Command Module Features and Benefits O Modern attractive cover in white or off white which snaps onto a plug in mounting base Q Terminals located on mounting base 0 Service tool connection Q Range of standard mounting kits Blends with room d cor Easy to install and service Easy to wire and test Variable Air Volume system can be commissioned and balanced at the room module location Flexibility in mounting possibilities
2. 3 Install the endcaps provided by snapping them Figure 14 omie the Wallpieta See Figura Ty iar pire Note For an asymmetrical range insert screws into Figure 12 Reattaching the Cover to the Wallplate differently lettered holes on each side TE 7000 Series Room Command Module Product Technical Bulletin 5 Preliminary This material will change Table 1 Ranges Hoes 5585F F 122c 57 5 82 5 13 3 26 7 59 3 80 7 14 3 25 7 61 2 78 8 15 3 24 7 63 77 16 3 23 7 65 75 17 3 22 7 66 8 73 2 18 3 21 7 68 6 71 4 19 3 20 7 Figure 14 Dial stop Screws 5 Press the dial knob back in place on the cover making sure the pointer indentation is aligned with the 70 F or 20 C mark at the top of the circle Then place the cover over the lower edge of the TE 7000 base and push the upper part of the cover until it clicks firmly into place Setpoint Dial To replace a serrated setpoint dial with a smooth dial follow Steps 1 2 3 and 5 in the Dial Stop Screws section substituting a smooth dial for the serrated dial in Step 5 Communication Port A 6 pin communication port is located on the bottom of the TE 7000 to connect a Personal Computer PC to the TE 7000 The PC software is used to test balance and commission the VMA1400 Series VAV Modular Assembly Communication Part Figure 15 6 pin Communication Port Wiring A ono Equipment Damage Hazard Disconnect the power supply before wiring
3. connections are made to avoid electrical shock or possible equipment damage Make wiring connections to the terminal blocks in the base of the TE 7000 module using No 24 16 AWG wire Follow the wiring diagram shown in Figure 16 IMPORTANT All wiring to the module is low voltage Class 2 and must be separated from the power line voltage wiring Do not run wiring close to transformers or high frequency generating equipment Complete and verify all wiring connections before applying power to the controller VMA1400 Bl1 Maximum Baill 1B AWG D E mr Communica lion Recormnernt 82 Purl Figure 16 Wiring to a TE 7000 Room Command Module with an NTC Sensor or Remote Sensor Note Check the VMA configuration to verify that the 55 to 85 F setpoint range has been defined to accommodate the TE 7000 Refer to the Variable Air Volume Modular Assembly VMA Application Note LIT 6375125 in the HVAC PRO for Windows User Manual for more information 6 TE 7000 Series Room Command Module Product Technical Bulletin Preliminary This material will change Table 2 Nominal Temperature vs Replacement and Repair Resistance for Thermistor Sensor Field repairs must not be made To order a Resistance ohms replacement refer to the Ordering Information section p for the desired product code number and contact your oe e 7 mems 40 4 swo Johnson Control representative na Ordering Information Table 3 Room Comm
4. over the lower edge of the TM 9100 base and push the upper part of the cover until it clicks firmly into place A5 1 Serrated Dial Knob To replace a smooth dial knob with a serrated knob follow steps 1 2 3 and 5 under Dial Stop Screws substituting a serrated knob for the smooth knob in Step 5 Figure 5 Module with Serrated Dial Knob TE 7000 Service Tool Socket The service tool socket is accessed by sliding the panel upwards as shown in Figure 6 below mm om x siding panel Service Tool Socket ES Es cont Figure 6 Service Tool Socket TE 7000 7 Dimensions in mm Figure 7 Basic Model TE 7000 800x Figure 8 Plug in Mounting Base 12 42 Figure 9 Wall Box Mounting Kit Figure 10 Panel Mounting Kit TM 9100 8941 W TM9100 8951 W Me i 13 Be Figure 11 Surface Mounting Kit TM 9100 893x W A5 1 8 TE 7000 NTC K2 Resistance Table Temperature in Resistance in Q 0 7352 8 5 5717 8 10 4481 5 15 3537 9 20 2812 8 25 2252 0 30 1814 4 35 1470 6 40 1199 6 Specifications Supply Voltage Power from VMA1400 VAV Modular Assembly Ambient Operating 0 to 50 Conditions 10 to 90 RH noncondensing Ambient Storage 20 to 70 Conditions Terminations Temperature Sensor Remote Set Point Occupancy Button and Mode Indicator Mounting Housing Dimensions HxWxD Shippi
5. 1998 Johnson Controls Inc Order No DS 24 130 E A5 1 A pplication Overview The TE 7000 Room Command Module is used specifically with the VMA1400 series VAV Modular Assembly and includes e an NTC K2 temperature sensor see the NTC K2 Resistance Table on page 10 e a setpoint dial and potentiometer for remote setpoint adjustment of 12to28 or 3 to 3K e an LED to indicate the occupancy mode as follows steady on occupied comfort mode blinking standby mode off unoccupied or off mode e an occupancy button switch in a series circuit with an LED to either 1 command the occupied mode from the standby or unoccupied mode for a set period of time or 2 change the occupancy mode to occupied standby or unoccupied for a set period of time as defined in the configuration data base of the VMA device e a socket for the connection of a PC with testing and commissioning software via an RS485 RS232 converter A cable is available for use with the IU 9100 converter see ordering codes The Room Command Module is connected by an 8 wire cable to the VMA and requires no other source of power A5 1 TE 7000 Ordering Codes European Models With System 91 Type Service Tool Connector Ordering Code TE 7000 8002 TE 7000 8002 W TE 7000 8003 TE 7000 8003 W Color Setpoint Dial Range Off White 12 to 286 Gray Base White 12 to 286 White Base Off White 3 to 3 K Gray Base White 3 t
6. Provides easy wiring and testing Makes the TE 7000 adaptable for most installations Allows commissioning and balancing of VAV system at the room module location 1 www johnsoncontrols com Preliminary This material will change Preliminary This material will change P roduct Overview The TE 7000 Room Command Module is used specifically with the VMA1400 Series VAV Modular Assembly and is not compatible with TE 6400 Metastat applications The TE 7000 0001 and TE 7000 0002 provide remote adjustment of the setpoint of the controller while the TE 7000 0003 model provides remote offset adjustment change to the room temperature setpoint programmed into the controller The LED located directly above the Temporary Occupancy button on the TE 7000 indicates the current operating mode of the VMA1400 as follows e LED on e LED off e LED flashing Occupied mode Comfort Unoccupied mode Night Standby mode The TE 7000 Temporary Occupancy button provides a means to circumvent day night programming and turn the HVAC system on or off manually If pressed for more than a second the controller mode is changed Dimensions 3 15 EE p Kas 3 15 Setanint g 7 Da LED a Tempurary Oncupancy i Rurttan Figure 2 TE 7000 Cover Dimensions in mm Figure 4 TE 7000 Wallplate Dimensions in mm 2 TE 7000 Series Room Command Module Product Technical Bulletin Preliminary This material will ch
7. Temperature Sensor TE 7000 800X 2 Set point 12 28 C Push botton Mode Selector with Led 3 Set point 3K indication Comfort Led On TE 7000 000X Stand by Led blinking 1 Set point 55 85 F Night Led Off 2 Set point 12 28 C 3 Set point 0 Set point override range 55 85 C 3K On request concealed pot for set point override Wiring Connections P N 24 85638 897 Rev A
8. and Modules Ordering Code Setpoint Scale TE 7000 0001 55 to 85 F TE 7000 0002 12 to 28 C TE 7000 0003 to no units Table 4 Replacement Parts and Accessories TE 6400 603 End Caps 2 TM 9100 8901 Dial Stop Screws Kit bag of 100 self tapping screws Resistance 6000 ahms s000 TM 9100 8902 Serrated Knob Kit bag of 10 knobs AUKIC T 4000 119 Stat Adjustment Tool to open 3000 module 2000 ACC INSL 0 Wallbox Mounting Pad 1090 bag of 10 4104 1016 Fl 97 32 BA 43 ACC INSL 1 Surface Mounting Pad Temperature F C bag of 10 Figure 17 Temperature vs Resistance for Thermistor Sensor TE 7000 Series Room Command Module Product Technical Bulletin 7 S pecifications Product Supply Voltage Ambient Operating Conditions Ambient Storage Conditions Terminations Thermistor Sensor Setpoint Temporary Occupancy Button Mode Indicator Mounting Housing Dimensions H x W x D Shipping Weight Agency Compliance The performance specifications are nominal and conform to acceptable industry standards For application at conditions beyond these Preliminary This material will change TE 7000 Series Room Command Module Power from VMA1400 VAV Modular Assembly 32 to 122 F 0 to 50 C 10 to 90 RH non condensing 4 to 158 F 20 to 70 C 100 RH non condensing Terminal block accommodates 24 to 16 AWG maximum wire Temperature Coefficient Nonlinear negative temperature coef
9. ange nstallation Install the TE 7000 where the occupant can easily read and adjust the setpoint dial Locate the module where the temperature is representative of the general room conditions Avoid mounting the TE 7000 near cold or warm air drafts radiant heat or direct sunlight IMPORTANT Do not mount the module on an exterior wall All wiring connections must be made in accordance with the National Electrical Code and all local regulations Parts Included room command module with attached surface mounting base e separate wallplate for wallbox mounting wallplate endcaps 2 e serrated setpoint dial attached smooth setpoint dial separate e dial stop self tapping screws 2 e hollow plastic wall anchors 2 e No 8x1 1 4 in slotted pan head sheet metal screws 2 e No 6 32 x 1 2 in flat head machine screws 2 Tools Needed e 1 16 in 1 5 mm Allen wrench or stat adjustment tool T 4000 119 e screwdrivers flat blade 1 4 in and 3 16 in tip e screwdriver Phillips No 1 tip e 5 16 in drill bit and drill e hammer M ounting The TE 7000 series allows for two mounting methods surface mount and wallbox mount For instructions on surface mounting follow the instructions for removing the cover and proceed to the Surface Mounting Procedure section For wallbox mounting follow the instructions for removing the cover and proceed to the Wallbox Mounting Procedure section No
10. d air to the space in which the TE 7000 is installed The module has an NTC Negative Temperature Coefficient temperature sensor a dial for setpoint adjustment within the range of 55 to 85 F 12 to 28 C or 5 F and a Temporary Occupancy button with a Light Emitting Diode LED indicator If the VMA controller is not already in occupied mode as shown by the LED indicator the occupant may press the Temporary Occupancy button to request comfort contro for a set period of time The TE 7000 also has a 6 pin communication port to connect a Personal Computer PC The PC software is used to test balance and commission the VMA1400 Series VAV Modular Assembly Figure 1 TE 7000 Series Room Command Module Shown with Fahrenheit and Celsius Setpoint Dials Features and Benefits High Accuracy Thermistor Sensor Choice of Setpoint Dials Adjustable Rotation Stops Temporary Occupancy Button External LED Mode Indicator Snap in Plug in Terminals Located on Mounting Base Choice of Wallbox Mounting Base included with all models 6 pin Communication Port sensors 1998 Johnson Controls Inc Part No 24 85638 1028 Rev Code No LIT 216335 Provides a low cost alternative to expensive alloy Provides aesthetic flexibility Provide limits to user setpoint adjustment range Enables the user to adjust room comfort by selecting the controller s operation mode Shows the controller s current operation mode
11. ficient Reference Resistance 2 25k ohms at 77 F 25 C Accuracy 0 36 F 0 2 C in the range of 32 to 158 F 0 to 70 C 2k ohm potentiometer with 4 99k ohm parallel resistor Momentary contact Red LED Direct surface mount or 2 x 4 in 51 x 102 mm wallbox mounting base Material Protection Flame resistant thermoplastic self extinguishing UL94 VO NEMA 1 IP 30 IEC529 3 2 x 3 2 x 1 3 in 80 x 80 x 33 mm 0 33 Ib 0 15 kg CE Directive 89 336 EEC EN 50081 1 EN 50082 2 specifications consult the local Johnson Controls office Johnson Controls Inc shall not be liable for damages resulting from misapplication or misuse of its products SON CONTRELS Controls Group 507 E Michigan Street P O Box 423 Milwaukee WI 53201 www johnsoncontrols com 8 TE 7000 Series Room Command Module Product Technical Bulletin CONRES O INSTALLING TE 7000 ROOM COMMAND MODULE MOUNTING 1 Remove the base of the module from the cover by inserting a pointed tool a special tool Ordering Code TM 9100 8900 is available from Johnson Controls into the small hole at the center top of the cover See Figure 1 2 While pressing down gently prise the base away from the cover 3 As the two parts separate remove the tool and continue to pull the cover away from the base until the cover is in free 4 Mount the base on the wall to cover the electrical output and secure with at least two screws Built in NTC
12. lplate 2 Pull the wiring through the wallbox These instructions assume a standard 2 x 4 in 51 x 102 mm wallbox is used 3 Rotate the wallplate so that one of the arrows on the wallplate points up 4 Fasten the wallplate to the wallbox using the No 6 screws provided See Figure 8 Seraw Wir ng ta TE 000 Ne 6 Screws Figure 9 Terminal Locations Shown on Inside of TE 7000 Surface Mount Base Note The terminal locations on the back of the TE 7000 cover are opposite of those marked on the base See Figures 9 and 11 5 Remove the terminal blocks from the TE 7000 base by lifting the plastic fingers on the back of the base and sliding each terminal block down and out of the retainer See Figure 10 Discard this TE 7000 base Plastic Fingers on the Bask of tha TE F000 Base Figure 10 Removing the Terminal Blocks from TE 7000 Surface Mount Base 4 TE 7000 Series Room Command Module Product Technical Bulletin Preliminary This material will change Diat stop Screws Push the terminal blocks onto the pins located inside the TE 7000 cover with screw heads toward the board and the wire leads exiting terminal blocks from the bottom as shown in Figure 11 To VMAI400 2 A pair of self tapping screws can be installed to mechanically limit the range of the TE 7000 setpoint dial between 5 F and 0 4 F or between 55 and 85F 12 to 28C and 68 to 71F 19 to 21C 1 Remo
13. ng Weight Agency Compliance The performance specifications are nominal and conform to acceptable industry standards 10 to 90 RH noncondensing Terminal block in base for 1 x 1 5mm 16 AWG maximum cable NTC Thermistor 0 to 40 2252 Q at 25 2 0 KQ potentiometer with 4 99 KQ parallel resistor marked for 12 to 28 or 3 to 3 K Mechanical limitation of travel available with dial stop screws See ordering codes Momentary contact and LED in series circuit Direct surface mount plastic base for surface mount with wiring conduit and recessed wall box and panel mounting kits See ordering codes Material ABS polycarbonate self extinguishing VO UL94 Protection IP30 IEC529 80 x 80 x 33 mm 0 15 kg CE Directive 89 336 EEC EN50081 1 EN 50082 1 For application at conditions beyond these specifications consult the local Johnson Controls office Johnson Controls Inc shall not be liable for damages resulting from misapplication or misuse of its products Johnson Controls International Westendhof 8 45143 Essen Germany A5 1 Rev Level 1198 European Electronic Controls Catalog Printed in Germany contig FANs 216 1628 3 Product Technical Bulletin TE 7000 Issue Date 1298 TE 7000 Series Room Command Module The TE 7000 Room Command Module is designed for use with the VMA1400 Series VAV Modular Assembly a control device for a Variable Air Volume VAV terminal unit that provides conditione
14. o 3 K White Base Note Add K to code for setpoint dial with serrated edge e g TE 7000 8002 WK Accessories Ordering Code TE 7000 8900 TM 9100 8900 TM 9100 8901 TM 9100 8902 TM 9100 8902 W TM 9100 8930 TM 9100 8931 TM 9100 8931 W TM 9100 8941 W TM 9100 8951 W TE 7000 8002 K Description Service Tool Connector Cable 1 5m for use with IU 9100 converter Special Tool to open module Dial Stop Screws Kit bag of 100 self tapping screws Serrated Knob Kit bag of 10 knobs Off white Serrated Knob Kit bag of 10 knobs White Surface Mounting Kit Gray Surface Mounting Kit Off white Surface Mounting Kit White Wall Box Mounting Kit White Panel Mounting Kit White For information purposes only North American Models from Customer Service in Milwau USA wall plate acc kee all in off white with gray essory serrated knob and telephone jack Service Tool connector Ordering Code TE 7000 0001 Setpoint Dial Range 65 to 85 F TE 7000 0002 12 to 286 TE 7000 0003 to no units TE 7000 Mounting and Wiring Instructions The TE 7000 module is designed for wall mounting in the room to be controlled using at least two of the four screw holes on the base The module may be mounted directly on the wall or one of the three mounting kits may be used The wiring enters from the back through the base Choose an appropriate place where the tem
15. perature is representative of the general room conditions Avoid cold or warm draughts from doors or windows and exposure to radiant heat from lamps radiators or direct sunlight However sufficient air circulation over the module is required for a satisfactory response to room temperature changes Place insulation material in the wiring conduit or any open space behind the wall to prevent air entering the module through the base Remove the base from the cover by inserting the point of the special tool TM 9100 8900 into the small hole at the center top of the cover While pressing down gently prise the base away from the cover As the two parts separate remove the tool and continue to pull the cover away from the base until the cover is free To reassemble the module place the cover over the lower edge of the base and push the upper part of the cover until it clicks firmly in place The TM 9100 893x W Surface Mounting Kit Screw the kit directly on the wall using holes A and mount the base of the module on the kit using the two screws included and inserting them in the two opposite holes B as indicated below The TM 9100 8941 W Wall Box Mounting Kit e Adjust height D turning screws A to match the depth of the wall box Yl A N Max 62 mm Min 55 mm gt D Min 45 mm e Inser
16. t the kit into the wall box in the position shown below e Tighten screws B until the prongs clamp properly on the box e Mount the base of the module on the kit as shown below using the two screws included and inserting them in two opposite holes of the four marked C DAR gt I A5 1 The TM 9100 8951 W Panel Mounting Kit e Cut a circular hole in the panel with a diameter dimension as shown below LA Max 60 mm Min 57 mm A Z Max 12 mm e Turn prongs A as shown below Insert the kit into the panel in the position shown below e Turn prongs A as shown below Turn screws B until the kit is fixed on the panel e Mount the base of the module on the kit as shown below using the two screws included and inserting them in two opposite holes of the four marked C A5 1 TE 7000 Wiring Instructions The installation of electrical wiring must conform to local codes and should be carried out by authorized personnel only Users should ensure that all Johnson Controls products are used safely and without risk to health or property Before connecting or disconnecting any wires ensure that all power supplies have been switched off and all wires are potential free to prevent eq
17. te All TE 7000 models include the Wallbox Mounting Base Kit Discard the kit if surface mounting the module Removing the Cover To remove the cover from the base insert a 1 16 in 1 5 mm Allen wrench or T 4000 119 Stat Adjustment Tool into the small hole located in the center of the top of the cover While pressing down gently on the tool pull the cover away from the base until it is free See Figure 5 Inser sal iol or Allen wrench heave Figure 5 Removing the Cover from the Base Surface Mounting Procedure WOUREEBEEE Figure 6 Installing a Surface Mounted TE 7000 TE 7000 Series Room Command Module Product Technical Bulletin 3 Preliminary This material will change To surface mount the TE 7000 1 Pull the wiring through the wall 2 Place the base against the wall and mark the screw holes using the base as a template 3 Drill two 5 16 in 8 mm holes insert anchors position base then drive the screws 4 Wire to appropriate terminals as shown in Figure 16 Reassembling the Surface Mounted TE 7000 If using the dial stop screws proceed to the Dial Stop Screws section To reassemble the TE 7000 place the cover against the bottom edge of the base and push the upper part of the cover until it clicks firmly into place See Figure 7 Figure 7 Reattaching the Cover to the Base Wallbox Mounting Procedure To wallbox mount the TE 7000 1 Loosen the cover screw installed in the wal
18. the cover While pressing down gently prise the base away from the cover As the two parts separate remove the tool and continue to pull the cover away from the base until the cover is free Set the dial to the center top position with the pointer indentation at the 0 K or 20 C mark Then insert the special TM tool Ordering Code TM 9100 8900 through the hole in the back of the cover 1 and push gently until the dial knob becomes free 2 MMI LE LE Dd VITITITIVITITITT tmtbremd Figure 3 Removing the Dial Knob On the front of the module cover you will see a series of seven holes on either side of the set point dial pivot which had been hidden by the knob Figure 4 Dial Stop Screws 4 To limit travel of the dial choose the desired range and insert screws in the corresponding holes For example for a limitation of 2 5 K insert one screw each in the holes marked A in Figure 4 tmtbhole Note For an asymmetrical range you may insert screws into differently lettered holes on each side 12 28 C 3K A 13 3 26 7 2 5 B 14 3 25 7 2 1 Cc 15 3 24 7 1 8 D 16 3 23 7 1 4 E 17 3 22 7 1 F 18 3 21 7 0 7 G 19 3 20 7 0 3 5 Press the dial knob back in place on the cover making sure the pointer indentation is aligned with the 0 K or 20 C mark at the top of the circle Then place the cover
19. uipment damage and electrical shock Terminations are made on the terminal blocks in the base of the module which accept 1 5 mm 16 AWG wires All wiring to the module is at extra low safe voltage and must be separated from power line voltage wiring Do not run wiring close to transformers or high frequency generating equipment Complete and verify all wiring connections before applying power to the VMA1400 to which the module is connected Do not attempt field repairs If the module does not operate properly when correctly wired it should be replaced VMA14x0 TBI TE 7000 es Se hie ee os Sean z x 1 BM __ COMMON 19 1 l 2 Y Set Point 15V l 25 3 i 26 A1 a NTCSensor 37 ACOM i l Occupancy 28 A2 i i Button i i iene a i l i TB2 ay l l lp pay Mode 34 5 LED 36 6 a a 8 l S Service i e o o Tool l COM ZB ZB nasin L A a lq Min 0 8 mm diameter wire Figure 2 Wiring Diagram TE 7000 Diat stop Screws A pair of self tapping screws can be installed to mechanically limit the range of the TM 9100 set point dial between 3 K and 0 3 K or between 12 28 C and 19 3 20 7 C 1 Remove the base of the module from the cover by inserting the point of the special tool TM 9100 8900 into the small hole at the center top of
20. ve the base of the module from the cover by inserting a 1 16 in 1 5 mm Allen wrench or T 4000 119 Stat Adjustment Tool into the small hole located in the center of the top of the cover While pressing down gently on the tool pull the cover away from the base until it is free Set the dial to the center top position with the pointer indentation at the 70 F 20 C mark 3 Insert the Stat Adjustment Tool through the hole in the back of the cover 1 and push gently until the Figure 11 Inside View of TE 7000 Cover dial knob is free 2 with Terminal Blocks Positioned for Wallplate Mounting TOTITITIIIIT IGF 7 Wire to appropriate terminals as shown in 1 Lee 2 Figure 16 Reassembling the Wallbox Mounted TE 7000 If using the dial stop screws proceed to the Dial Stop Grew SEGUIN Figure 13 Removing the Setpoint Dial To replace the TE 7000 cover onto the installed wallplate 4 On the front of the module cover there is a series of 1 Place the bottom edge of the cover against the Save bles On aiina SiE ofthe SEPON Mal PNDR which had been hidden by the knob bottom edge of the wallplate 2 Rotate the cover up onto the wallplate and tighten t Mirra mavera ne diel Noone une desned range and insert screws in the corresponding holes See the cover screw using the stat tool or Allen Sse a 3 wrench See Figure 12 Table 1 For example for a limitation of 4 2F f i insert one screw each in the holes marked A in