Home
XYR6000 Differential Pressure Spec
Contents
1. Ambient Temperature 401085 4010185 40t085 40 to 185 40 to 85 40 to 185 Meter Body Temperature 40 to 110 40 to 230 40 to 125 40 to 257 40 to 85 40 to 185 Humidity RH 10 to 55 0 to 100 0 to 100 0 to 100 Vacuum Region Minimum Pressure mmHg absolute Atmospheric 25 2 short term inH2O absolute Atmospheric 13 1 short term Maximum Allowable STDW924 STDW930 STDW974 4500psi 310 bar Working Pressure MAWP Static Pressure Limit Maximum Allowable Working Pressure MAWP Overpressure XYR6000 products are rated to Limit Maximum Allowable Working Pressure MAWP depends on Approval Agency and transmitter materials of construction Vibration Maximum of 4g over 15 to 200Hz Maximum of 40g For CTFE fill fluid the rating is 15 to 110 C 5 to 230 F Short term equals 2 hours at 70 C 158 F 3MAWP applies for temperature range 40 to 125 C However Static Pressure Limit is de rated to 3000 psi from 26 to 40 C Use of graphite o rings de rates transmitter to 3625 psi Use of Adapter with graphite o rings de rates transmitter to 3000 psi Consult factory for MAWP of XYR6000 transmitters with CSA approval Wireless Specifications Wireless Communication 2 400 to 2 483 5 MHz 2 4 GHz Frequency Hopping Spread Spectrum FHSS USA FCC Certified Canada IC Certified European Union RTTE ETSI Conformity RF Transmitter Power 125 mW 20 9 dBm maximum per FCC IC n
2. Or visit Honeywell on the World Wide Web at http www honeywell com 34 XY 03 22 Page 11 Model Selection Guide 34 XY 16 38 Model Selection Guide Honeywell Proprietary 34 XY 16 38 Issue 2 Instructions Select the desired Key Number The arrow to the right marks the selection available Make one selection from each table and Il using the column below the proper arrow Select as many Table Ill options as desired if no options or approvals are desired specify 9X A denotes unrestricted availability A letter denotes restricted availability Restrictions follow Table V List Price equals Key Number 1 sum of all sw 00000 XXXX selections made Selection Availability 0 10 to 0 400 0 0 25 to 0 1000 mbar Body Rating 4500 psi 310 bar Differential 0 5 to 0 100 psi 0 0 34 to 0 7 bar Pressure Body Rating 4500 psi 310 bar 0 100 to 0 3000 psi 0 7 to 0 210 bar STDW974 V Body Rating 4500 psi 310 bar p Process Valves Barrier Diaphragms METER BODY Heads and Plugs Carbon Steel 316 SS 316L SS Carbon Steel 316 SS Hastelloy C Carbon Steel 316 SS Monel Materials of Carbon Steel 316 SS Tantalum Construction 316 SS 316 SS 316L SS 316 SS 316 SS Hastelloy C 316 SS 316 SS Monel 316 SS 316 SS Tantalum Hastelloy C Hastelloy C Hastelloy C Hastelloy C Hastelloy C Tantalum Monel Monel Monel cr 5 22 4 CTFE Process Head 1 4 NPT 1 2 NPT with
3. in of span 30 psi nere oss 2 or doors o 2 oa spanpsi span bar 0 1625 of span For URV below reference point 30 psi effect equals 30 psi 2 bar t 0 0125 0 15 or 0 0125 0 15 in of span spanpsi span bar 0 30 of span For URV below reference point 30 psi effect equals 30 psi z or sloso in of span span psi span bar Stability 0 04 of URL per year Performance specifications are based on reference conditions of 25 C 77 F zero 0 static pressure 10 to 55 RH and 316L Stainless Steel barrier diaphragm Performance Under Rated Conditions Model STDW974 0 to 3000 psi 210 bar Upper Range Limit psi 3000 bar 210 100 7 psi Zero Elevation and Suppression 0 6 and 10096 URL bar 0 175 of calibrated span or upper range value URV whichever is greater terminal based For URV below reference point 300 psi accuracy equals 300 psi aa 220 or s oo25 oid 21881 in 96 of span spanpsi span bar Minimum Span Accuracy Reference Includes combined effects of linearity hysteresis and repeatability 34 XY 03 22 Page 6 Zero Temperature Effect per 0 20 of span 28 C 50 F For URV below reference point 500 psi effect equals 500 psi 35 bar 0 20 or 0 20 in 96 of span span psi span bar Combined Zero and Span 0 30 of span Temperature Effect per 28 C 50 F For URV below re
4. Adapter on 1 4 NPT Head Eora A a rU TABLEII No Selection 7 7 00000 T Carbon Steel heads are zinc plated Not recommended for water service due to hydrogen migration Use Stainless Steel heads Vent Drains are Teflon coated for lubricity 34 XY 03 22 Page 12 TABLE Ill ANTENNA OPTIONS Selection Availability Antenna s Integral Right angle vertical Standard Integral Straight horizontal Remote Omnidirectional 8 dBi Remote Directional 14 dBi Cable A for None Remote Antenna 1 0m remote Cable A TNC R N Req d to connect to XYR 6000 3 0m remote Cable A TNC R N Req d to connect to XYR 6000 10 0m remote Cable A TNC R N Req d to connect to XYR 6000 Lightning Protection None for remote Antenna Lightning Protection 1 0m Cable B to Antenna N N With Cable B Lightning Protection 3 0m Cable B to Antenna N N Lightning Protection 10 0m Cable B to Antenna N N TABLE IV OPTIONS None Transmitter Housing amp Electronics Options Custom Calibration and I D in Memory Transmitter Configuration and ID in Memory M20 Conduit Thread 1 2 NPT is standard 1 2 NPT to 3 4 NPT 316 SS Conduit Adapter Stainless Steel Customer Wired On Tag 4 lines 28 characters per line customer supplied information Stainless Steel Customer Wired On Tag blank End Cap Warning Label in Spanish End Cap Warning Label in Portuguese End Cap Warning Label in Italian End Cap Warning Label in German Mete
5. Over Pressure Leak Test with F3392 Certificate Calibration Test Report and Certificate of Conformance F3399 Certificate of Conformance F3391 Certificate Options Certificate of Origin F0195 NACE Certificate F0198 Warranty Options Additional Warranty 1 year Additional Warranty 2 years Approval Body Approval Type Location or Classification No hazardous location approvals Nonincendive Nonincendive CL I Div 2 Groups A B C amp D CL II amp Ill Div 2 Groups F amp G 4 Ta 85 C Non Sparking Class I EX AEx nC IIC T4 Ta lt 85 C Zone 2 IP 66 ATEX Non Sparking Ex Il 3 GD Ex nL IIC 4 Ta lt 85 C Zone 2 IP 66 67 WARNING Division 2 Zone 2 apparatus may only be connected to processes classified as non hazardous or Division 2 Zone 2 Connection to hazardous flammable or ignition capable Division 1 Zone 0 or 1 process is not permitted TABLE V Factory Identification XXXX o RESTRICTIONS Restriction Available Only With Not Available With Letter Table Selection Table Selection Select only one option from this group Ba 3 Select oni Table IV S2 S3 S4 S5 T2 T3 V2 V3 Notes See ST 89 for Published Specials with pricing See ST 95 and User s Manual for part numbers To request a quotation for a non published special fax RFQ to 602 313 6155 or email to ace honeywell com 34 XY 03 22 Page 14 OneWireless and XYR are trademarks and Experion i
6. Honeywell XYR 6000 Wireless Pressure Transmitter 34 XY 03 22 Differential Pressure Models 8 13 07 Specification and STDW924 Oto 400 inH20 0 to 1 000 mbar STDW930 Oto 100 psi 0 to 7 000 mbar Model Selection STDW974 Oto 3000 psi 0 to 210 000 mbar Guide Introduction Building upon the tremendously successful ST 3000 series transmitter line Honeywell brings simple safe and secure wireless technology to its measurement portfolio in the XYR 6000 Series Wireless Transmitters The XYR 6000 series measurements are part of the WNSIA Wireless Network for Secure Industrial Applications compliant field devices Measurement and information without wires The XYR 6000 wireless transmitters series enable customers to obtain data and create information from remote and hazardous measurement locations without the need to run wires where running wire is cost prohibitive and or the measurement is in a hazardous location Without wires transmitters can be installed and operational in minutes quickly providing information back to your system XYR 6000 wireless transmitters send information to a multinode or series of multinodes creating a MESH infrastructure Wireless System Gateways WSG provide the path to bring that information into Experion PKS or any other control system wirelessly via OPC client or Modbus TCP Each multinode accepts signals from up to 20 wireless transmitters reporting at 1 second and up to 400 transmitt
7. equirements Hazardous Location See the Model Selection Guide on page 11 Certifications 34 XY 03 22 Page 7 Physical Specifications Barrier Diaphragms Material 316L SS Hastelloy C 276 Monel Tantalum Gold plated 316LSS Gold plated STDW924 STDW930 STDW974 Hastelloy C 276 Gold plated Monel Process Head Material 316 SS Carbon Steel zinc plated Monel Hastelloy STDW924 STDW930 STDW974 Head Gaskets Glass filled PTFE standard Viton and graphite optional Meter Body Bolting Carbon Steel Zinc plated standard Options include 316 SS NACE A286 SS bolts with NACE 304 SS nuts and B7M Optional Adapter Flange and Adapter Flange materials include 316 SS Hastelloy C 276 and Monel Options for Bolts bolting include carbon steel 31655 NACE A286SS and B7M Standard adapter flange gasket material is glass filled PTFE Viton and graphite optional Mounting Bracket Carbon Steel Zinc plated or Stainless Steel angle bracket or Carbon Steel flat bracket available standard options Fill Fluid Silicone DC 200 oil or CTFE Chlorotrifluoroethylene Electronic Housing Epoxy Polyester hybrid paint Low Copper Aluminum Meets NEMA 4X hosedown and corrosion resistant IP 66 67 hosedown and submersible to 1m Process Connections 1 4 inch NPT 1 2 inch NPT with adapter Process heads meet DIN 19213 requirements Can be mounted in virtually any position using the standard mounting bracket Mounting should result in the antenna be
8. ers Figure 1 XYR 6000 Differential Pressure Transmitters reporting at slower rates Up to 20 multinodes can be implemented in the same infrastructure WSG also provides Modbus TCP data access to wireless data in addition to OPC Implement the value of wireless technology today Transmitter power is supplied by two D Measure remote access points simply safe and securely size lithium batteries with an expected e Obtain and utilize previously inaccessible information due to high lifetime of up to ten years Transmitter wiring cost or hazardous locations range with the integral antenna is 1000 e Easily meet Regulatory Requirements 305 m under ideal conditions i Improve process efficiency Pressure transmitters continue to bring a e Enhance Flexibility to proven technology to a wide spectrum of monitor applications pressure measurement applications from that have no access to power furnace combustion airflow rate to that are remote or difficult to reach hydrostatic tank gauging that may require frequent reconfiguration The STDW series Differential Pressure can where manual readings have been required previously be used with any primary flow element to provide proven repeatable flow measurement 34 XY 03 22 Page 2 Specifications Operating Conditions All Models Parameter Reference Rated Condition Operative Limits Transportation and Condition Storage at zero static i 77 2
9. ference point 500 psi effect equals 500 psi soto soa 2228 or soo 2d 38 in 96 of span spanpsi span bar Zero Static Pressure Effect per 0 1625 of span 1000 psi 70 bar For URV below reference point 500 psi effect equals 500 psi u in of span spanpsi span bar Combined Zero and Span Static 0 30 of span Pressure Effect per 1000 psi 70 bar For URV below reference point 500 psi effect equals 500 psi 5009 sos soa 252 in 96 of span spanpsi span bar Stability 0 03 of URL per year e Performance specifications are based on reference conditions of 25 C 77 F zero 0 static pressure 10 to 55 RH 316L Stainless Steel barrier diaphragm Performance under Rated Conditions General for all Models Lightning Surge Arrester Frequency range 0 3 GHz 50 Ohms VSWR 1 1 3 Max Insertion Loss 0 4 dB Remote antenna only Connectors Type N Female Max Gas Tube Element 90 V 2096 Impulse Breakdown Voltage 1 000 V 20 Maximum Withstand Current 5 KA CE Conformity These transmitters are in conformity with the protection requirements of European Council Directives 89 336 EEC the EMC Directive and 1999 5 EC the Telecommunications Directive per EN 300 328 V1 7 1 EN301 893 V1 3 1 EN301 489 17 V1 2 1 EN301 489 1 V1 6 1 and EN61326 1 1st Edition 2002 02 Industrial Locations Electrical Equipment for Measurement Control and Laboratory Use EMC R
10. inH20 1000 mbar Upper Range Limit inH2O 400 39 2 F 4 C is standard reference temperature for inH2O range mbar 1000 Minimum Span inH2O 10 mbar 25 Zero Elevation and Suppression 5 to 10096 URL Accuracy Reference Includes 0 10 of calibrated span or upper range value URV whichever is greater terminal combined effects of linearity based hysteresis and repeatability For URV below reference point 25 inH2O accuracy equals Accuracy includes residual error after averaging successive 25 inH 4O 62 mbar readings 0 125 0 05 or oss oof mee in of span span inH O span mbar Zero Temperature Effect per 0 15 of span 28 C 50 F For URV below reference point 50 inH2O effect equals 50 inH 50 125mbar 0 15 or 0 15 in of span spaninH 0 span mbar Combined Zero and Span 0 225 of span Temperature Effect per 28 C 50 For below reference point 50 inH2O effect equals 50 inH O 0 0754 0 15 or 0 075 0 15 125 in of span span inH span mbar Zero Static Pressure Effect per 0 1625 of span 1000 psi 70 bar For URV below reference point 50 inH2O effect equals 50 inH 0 0125 0 15 or 0 0125 0 15 125 mbar in of span spaninH span mbar Combined Zero and Span Static 0 30 of span Pressure Effect per 1000 psi 70 bar For URV below reference poin
11. ing vertically oriented Bracket is designed to mount on 2 inch 50 mm vertical or horizontal pipe See Figure 2 Figure 2 Examples of typical mounting positions 34 XY 03 22 Page 8 millimeters Reference Dimensions inches 121 0 228 6 5 00 4 10 9 00 CLEARANCE CLEARANCE FOR FOR CAP CAP REMOVAL REMOVAL 4 i BATTERY REPLACEMENT DISPLAY MANIPULAT ION ONDUIT CONNECTION OPTIONALLY 1 2 OR M20 PTIONAL VENT DRAIN POSITION GH PRESSURE LOW PRESSURE CONNECTION CONNECTION 4 NPT 1 4 NPT Figure 3 Typical mounting dimensions for STDW924 STDW930 and STDW974 side view 34 XY 03 22 Page 9 00 98 6 M 3 88 C OPTIONAL VENT DRAIN POSITION o e o eo e NPT OPTIONAL ADAPTERS FOR 1 2 Figure 4 Typical mounting dimensions for STDW924 STDW930 and STDW974 rear view 34 XY 03 22 Page 10 Options Ordering Information Mounting Bracket The angle mounting bracket is available in either zinc plated carbon steel or stainless steel and is suitable for horizontal or vertical mounting on a two inch 50 millimeter pipe as well as wall mounting An optional flat mounting bracket is also available in carbon steel for two inch 50 millimeter pipe mounting Tagging Option TG Up to 30 characters can be added on the stainless steel nameplate mounted on the transmitter s electronics housing a
12. ot including antenna or 400 mW 26 0 dBm maximum EIRP including antenna for USA and Canadian locations 100 mW 20 0 dBm maximum EIRP per RTTE ETSI including antenna for EU locations Integral 2 dBi omnidirectional monopole Remote 8 dBi omnidirectional monopole with up to 20 m cable and lightning surge arrester Remote 14dBi Directional with up to 20 m cable and lightning surge arrester Signal Range Nominal 305 m 1 000 feet between Field Transmitter and Infrastructure Unit multinode or Gateway Unit with a clear line of sight Actual range will vary depending on antennas cables and site topography Remote antenna cables JC C a a II z C P Till CABLE A LMR 400DB TYPE N MALE 50018110 001 1m 3 3 ft TNC R 50018110 003 3m 10 ft 50018110 010 10m 33 ft CABLE B LMR 400DB TYPE N MALE 50018278 001 1m 3 3ft TYPE N MALE 50018278 003 3m 10 ft 50018278 010 10m 33ft REMOTE ANTENNA XYR 6000 WIRELESS TRANSMITTER REMOTE ANTENNA Cable A XYR 6000 Cable B WIRELESS TRANSMITTER LIGHTNING SURGE ARRESTOR CABLE PARAMETERS LIGHTNING SURGE ARRESTOR CABLE A BLENGTH CAPACITANCE INDUCTANCE PARAMETERS 78 4 pF CAPACITANCE 1 pF 235 2 pF INDUCTANCE 10 nH 784 pF 34 XY 03 22 Page 3 34 XY 03 22 Page 4 Performance Under Rated Conditions Model STDW924 0 to 400
13. r Body Options 316 SS Bolts and 316 SS Nuts for Process Heads B7M Bolts and Nuts for Process Heads NACE A286 SS Bolts and NACE 304 SS Nuts for Process Heads 316 SS Adapter Flange 1 2 NPT with CS Bolts 316 SS Adapter Flange 1 2 NPT with 316 SS Bolts 316 SS Adapter Flange 1 2 NPT with NACE A286 SS Bolts 316 SS Adapter Flange 1 2 NPT with B7M Bolts Hastelloy C Adapter Flange 1 2 NPT with CS Bolts Hastelloy C Adapter Flange 1 2 NPT with 316 SS Bolts Monel Adapter Flange 1 2 NPT with CS Bolts Monel Adapter Flange 1 2 NPT with 316 SS Bolts 316 SS Blind Adapter Flange with CS Bolts 316 SS Blind Adapter Flange with 316 SS Bolts 316 SS Blind Adapter Flange with NACE A286 SS Bolts 316 SS Blind Adapter Flange with B7M Bolts Side Vent Drain End Vent Drain is standard 316 SS Center Vent Drain and Bushing Viton Process Head Gaskets adapter gaskets ordered separately Viton Adapter Flange Gaskets Graphite Process Head amp Adapter Flange Gaskets Transmitter Mounting Brackets Options Mounting Bracket Carbon Steel Mounting Bracket 304 SS Flat Mounting Bracket Carbon Steel Diaphragm Options Gold plated diaphragm s on 316 SS Gold plated diaphragm s on Monel or Hastelloy ONLY Table IV continued on next page 34 XY 03 22 Page 13 TABLE IV OPTIONS continued Selection Availability Options User s Manual Paper Copy Clean Transmitter for Oxygen or Chlorine Service with Certificate
14. s a registered trademark of Honeywell International Inc Honeywell Honeywell Field Solutions Honeywell International Inc 2500 W Union Hill Drive Phoenix Arizona 85027 Honeywell International Inc
15. t 50 inH2O effect equals 50 inH O 0 15 0 15 ai or 0 15 0 15 125 mbar in of span spaninH 0 span mbar Stability 0 015 of URL per year Performance specifications are based on reference conditions of 25 C 77 F zero 0 static pressure 10 to 55 RH and 316L Stainless Steel barrier diaphragm 34 XY 03 22 Page 5 Performance Under Rated Conditions Model STDW930 0 to 100 psi 7000 mbar Upper Range Limit psi bar Minimum Span psi bar Zero Elevation and Suppression Accuracy Reference Includes combined effects of linearity hysteresis and repeatability Accuracy includes residual error after averaging successive readings Zero Temperature Effect per 28 C 50 F Combined Zero and Span Temperature Effect per 28 C 50 F Zero Static Pressure Effect per 1000 psi 70 bar Combined Zero and Span Static Pressure Effect per 1000 psi 70 bar 100 7 5 0 35 5 to 100 URL 0 10 of calibrated span or upper range value URV whichever is greater terminal based For URV below reference point 20 psi accuracy equals 20 psi 1 4 bar 0 125 0 05 or 0 0125 0 05 _ in of span span psi span bar 0 15 of span For URV below reference point 30 psi effect equals 30 psi 2bar 0 15 or 0 15 in of span span psi span bar 0 225 of span For URV below reference point 30 psi effect equals
16. t no extra cost Note that a separate nameplate on the meter body contains the serial number and body related data A stainless steel wired on tag with additional data of up to 4 lines of 28 characters is also available The number of characters for tagging includes spaces Transmitter Configuration All configurable parameters are accessible via the WNSIA network via READ WRITE transactions Specifications are subject to change without notice Contact your nearest Honeywell sales office or In the U S Honeywell Industrial Automation amp Control 16404 North Black Canyon Hwy Phoenix AZ 85053 1 800 288 7491 In Canada The Honeywell Centre 155 Gordon Baker Rd North York Ontario M2H 3N7 1 800 461 0013 In Latin America Honeywell Inc 480 Sawgrass Corporate Parkway Suite 200 Sunrise FL 33325 954 845 2600 In Europe and Africa Honeywell S A Avenue du Bourget 1 1140 Brussels Belgium In Eastern Europe Honeywell Praha S r o Budejovicka 1 140 21 Prague 4 Czech Republic In the Middle East Honeywell Middle East Ltd Khalifa Street Sheikh Faisal Building Abu Dhabi U A E In Asia Honeywell Asia Pacific Inc Honeywell Building 17 Changi Business Park Central 1 Singapore 486073 Republic of Singapore In the Pacific Honeywell Pty Ltd 5 Thomas Holt Drive North Ryde NSW Australia 2113 61 2 9353 7000 In Japan Honeywell K K 14 6 Shibaura 1 chrome Minato ku Tokyo Japan 105 0023