1. at risk whilst carrying out maintenance work 3 Rectifier booster block protection fuse This fuse is dependent on the status of the re settable input fuse 1 a fault occurring to the rectifier booster will open this protection before the input fuse intervenes ensuring that the power supply to the connected load is not interrupted as the by pass line will remain powered 11 SPEDLPX0205REN PHELL CH ELETTR ONA ig riello Ups patos Pus 4 Rectifier Booster When the mains power supply is present this converts the mains alternating current AC into a direct current DC whilst controlling the power factor If the mains power supply fails it increases the voltage from the battery to an appropriate voltage level to power the inverter stage 5 Inverter Converts the direct current DC into alternating current AC to supply the load 6 Automatic by pass Used for switching between the inverter output and the mains supply or vice versa without interrupting the power supply to the load this activates if any overloads or faults occur 7 Output switch Used To isolate the UPS when carrying out maintenance work 9 Output EMI filter Output filter for protecting the load against any electromagnetic disturbances 10 Maintenance free sealed lead acid batteries Supplies power to the inverter to support the load when the incoming mains power supply fails 11 Battery expansion from 1000 to 3000VA models Enables extende
2. fans 6 IEC output sockets max 104A Telephone modem protection net or intranet Communication expansion slot Input thermal re settable protection 9 Battery expansion connector ad 24 SPEDLPX0205REN PHELL CH ELETTR ONA Fi riello Ups DIALOG PLUS gt 11 2 Rear panel 2000ER 3000 3000ER VA Models rad Dialog Plus 2000 ER VA a co x Le 7 X Nu I Gi FE AN gt O 8 b iy ON e E LI y 6 Ee Nr gt SN Hu 3 u P E i amd N i A N e O M J NN M y i ua PC f 5 AN O NE RS232 serial communication port Cooling fans Telephone modem protection net or intranet Input thermal re settable protection IEC mains input plug 25 SPEDLPX0205REN 0090 Dialog Plus 3000 3000 ER VA 0 os O A 3 Co p P f N Ke y IN IEC output sockets max 10A Communication expansion slot Battery expansion connector IEC 16A output socket Output socket fuse holders TECHNICAL DATA gt 12 1 Tower models MODEL Dialog Plus DLP 70 Dialog Plus DLP 100 Dialog Plus DLP 100ER Dialog Plus DLP 150 Dialog Plus DLP 200 Dialog Plus DLP 200ER Dialog Plus DLP 300 Dialog Plus DLP SOLER POWER 700VA 450W 1000VA 700W 1000VA 700W 1500VA 1050W 2000VA 1400W 2000VA 1400W 3000VA 2100W 3000VA 21
3. the default value LCHELETTR CHI PEL Wriello ups amos Pus 9 OPTIONS gt 9 1 Summary table of the options available DESCRIPTION DIMENSIONS HxWxD mm WEIGHT KG Isolating transformer module for DLP 100 DLP 150 480x158x348 22 Isolating transformer module for AH ADLER 480x158x348 30 PowerShield communication software full version Remote display panel with led ISOLATING TRANSFORMER MODULE Enables the UPS output to be galvanically isolated from the input Enables the user to modily the neutral regime for example from TT to TN or from TT to IT to increase the continuity of the power supply IT systems or to increase the level of protection to the users TN systems The transformer may be connected to the input or to the output of the UPS gt 9 2 Installation of the baffery expansion module MAINS POWER SUPPLY gt 9 2 1 Configuration of the battery expansion module Following the installation of one or more battery expansion modules the correct total Ah value must be entered into the UPS memory This may be done by using the UPSTools program which can be found on the same disc as the UPS management software once this has been installed correctly 19 SPEDLPX0205REN E lii i a Wriello Ups owoc PLus FRONT PANEL gt 10 1 Display panel The LED display panel enables the user to check the UPS status and operating mode It indicates in which mode th
4. 00W BACK UP min 8 internal batteries 8 internal batteries O external batteries 8 internal batteries 13 internal batteries O external batteries 8 internal batteries O external batteries gt 12 2 Back up expansion modules for tower version DIMENSIONS HxWxD mm 236x158x400 236x158x400 236x158x400 236x158x500 348x192x460 348x192x460 348x192x460 348x192x460 For types and back up times of the Dialog Plus Tower models refer to the Riello Ups s price list SPEDLPX0205REN 26 WAriello ups Mew WEIGHT Kg 12 14 8 34 14 SO 14 Wi riello ups gt 12 3 Summary data sheets MODEL Input phases Rated voltage Maximum input voltage before battery intervention Minimum input voltage before battery intervention applied load 100 Rated frequency Input frequency tolerance Maximum current In rush current Power factor Current distortion THDi Input protection Hold up time interruption to the mains supply before battery intervention Maximum voltage acceptable for switching to the mains supply Minimum voltage acceptable for switching to the mains supply SPEDLPX0205REN 700VA SLA 1000VA 5A Thermal switch 7 A 27 1000VA ER INPUT 220 230 240 V single phase 1500VA 2000VA 300 V single phase 110 5 V single phase load 0 60 160 5 V single phase load 80 100 2000VA ER 3000VA Standard 50Hz
5. 21 Dialog Plus Rack DLPR 220 2200 VA 1540 W 12 88 88 x483x480 Il 27 Dialog Plus Rack DLPR 220 ER 2200 VA 1540 W External batteries 88x483x480 13 Dialog Plus Rack DLPR 300 3000 VA 2100 W 8 88 88 x483x480 J2 27 Dialog Plus Rack DLPR 300 ER 3000 VA 2100 W External batteries 88x483x480 14 Note 88mm 2U 176mm 4U 2U 2U 483mm 19 31 SPEDLPX0205REN m Wi riello ups gt 13 2 Back up expansion modules for rack version For types and back up times of the Dialog Plus Rack models refer to the Riello Ups s price list gt 13 3 Rear panel view MODELS REAR VIEWS bes Ny Y ee pg n Dialog Plus rack 700VA o a le ms SM Dialog Plus rack 1000 a HS ape SN AM Bl im 1000 ER VA T INE Mis CH Dialog Plus rack 1500VA FTN o in N NES SI y n 32 SPEDLPX0205REN J Ct ELETTRONICA Dialog Plus rack 2200VA Dialog Plus rack 2200 ER VA Dialog Plus rack 3000 3000 ER VA SPEDLPX0205REN R W riello Ups ees PLUS WENN S r3 r3 r3 r3 r3 r3 Ltd Fr SN M AU TT 0 o ae NNI ZUM a a PRESE E N KC sue 2 i a hg NSG ff HS a Se SN j i Vir ris a n NES H gt a ESN x SG R MIT yN Ny TS Eus THE cre eee rl Su M 6 c 2 4 T y 33 WM T x M E x N S P Cr Hin we Se 3 n Wi riello ups Battery Box 1 RS232 serial communication po
6. 5 2000 VA 3000 VA 1400 W 2100 W lt 5 Same as the mains for variations between 5 96 3000VA ER External batteries External batteries External batteries 3000 VA 2100 W j B Wi riello ups patos mus MODEL 700VA 1000VA 1000VA ER 1500VA 2000VA 2000VA ER 3000VA Freguency variation velocity Hz sec IE Voltage reset after dynamic variation 20 me Voltage distortion linear load soi Voltage distortion P non linear load OVERLOAD TIMES INVERTER OVERLOAD WITH MAINS SUPPLY AVAILABLE 100 lt Load lt 110 SICA 110 lt Load lt 150 o Load gt 15096 10 VARIOUS AC AC efficiency double 90 conversion operation i Maximum permanent operating temperature QURE Ambient operating o temperature AUC Recommended operating temperature for the 20 25 C batteries Humidity 9596 without condensation Protections Excessive battery discharge overcurrent short circuit overvoltage undervoltage over temperature Compliance with safety EN62040 1 1 regulations Directives 73 23 EEC and 93 68 EEC EMC compliance EN50091 2 cl A directive 89 336 EEC Noise lt 40 dB A at 1 metre DIMENSIONS Height mm 236 296 236 236 348 348 348 Width mm 158 158 158 158 182 192 192 29 SPEDLPX0205REN 3000VA ER 348 22 j B Wi riello ups MODEL 700VA 1000VA 1000VA ER 1500VA 2000VA 2000VA ER 3000VA 3000VA ER Depth mm 400 400 400 500 460 460 460 460 Weight in Kg with 3 14 14 standard bac
7. OBJECTIVE This technical document has been produced to be used by UPS system designers and installers The objective of this document is to provide and illustrate the technical information required to enable you to choose the correct UPS to suit your needs the information reguired to set up and configure the system the information concerning the installation and location of the UPS the information the UPS displays locally to the user or to the monitoring systems it is connected to e g control centres etc a list of the possible options available to configure the UPS to the operators specific reguirements DESCRIPTION OF THE SYSTEM The new Dialog Plus range ot UPS has been designed to offer a high level of versatility and reliability Utilising the latest ON LINE technology meaning that the alternating current AC supplied to the load is first converted to direct current DC and then back to AC again to ensure a perfectly sinusoidal output the frequency and voltage are constantly monitored using microprocessor digital control this control ensures true independence of the input power supply The Dialog Plus range of UPS is also supplied with an automatic by pass system the bypass system can instantly switch the load on to the incoming power supply in the event ot any unforeseen overvoltages overloads or any other power or load related problems and therefore a continuous power supply even during the most critical conditions
8. RIELLO ELETTRONICA riello UPS TECHNICAL SPECIFICATIONS i DIALOG PLUS 700 3000VA SINGLE PHASE On line double conversion VFI technology SPEDLPX0205REN Wirelous 3 Table of contents OBJECTIVE 3 DESCRIPTION OF THE SYSTEM 3 APPLICATIONS 4 CHARACTERISTICS 4 NORMATIVE REFERENCES 7 gt 5 1 Main reference standards 7 gt 5 2 Standards relating to systems and installation 8 SUPPLIED EQUIPMENTS AND ACCESSORIES 9 gt 6 1 Tower version 9 gt 6 2 Rack version 10 BLOCK DIAGRAM 11 gt 7 1 Block diagram of the UPS 1 gt 2 Options 1 INTERFACING 15 gt 8 1 Serial communication port 75 gt 8 2 Communication software 16 gt 8 3 Configuration software 18 OPTIONS 19 gt 9 1 Summary table of the options available 19 gt 9 2 Installation of the battery expansion module 19 gt 9 2 1 Configuration of the battery expansion module RE FRONT PANEL 20 gt 10 1 Display panel 20 gt 10 2 Description of the display panel icons 20 gt 70 3 UPS front view 23 REAR PANEL 24 gt 11 1 Rear panel 700 2000 VA Models 24 gt 11 2 Rear panel 2000ER 3000 3000ER VA Models 25 TECHNICAL DATA 26 gt 12 1 Tower models 26 gt 12 2 Back up expansion modules for tower version 26 gt 12 3 Summary data sheets 27 DIALOG PLUS RACK 31 gt 13 1 Rack models 31 gt 13 2 Back up expansion modules for rack version 32 gt 13 3 Rear panel view 32 SPEDLPX0205REN PHELL CHELETTH CHA ig riello Ups maocmas 1
9. Switches to bypass after 30 min Switches to bypass after 30 sec Switches to bypass after 10 sec Switches to bypass after 0 5 sec 22 OVERLOAD TIMES from battery Shutdown after 30 min if battery back up time allows Shutdown after 30 sec Shutdown after 10 sec Shutdown after 0 5 sec LCHELETTR CHI PEL gt 70 3 UPS front view 1 LED mimic panel 2 ON button 3 OFF button SPEDLPX0205REN ig riello Ups mao Dialog Plus 700 1000 1500VA 23 RELLO ELETTR ODA Fi riello Ups REAR PANEL gt 11 1 Rear panel 700 2000 VA Models Dialog Plus 700VA Dialog Plus 1000 1000ER 1500VA 7 Pom Pos 71 oe 7 y 2 1 7 Q2 21 2 A N HER ll RN s J 3 O C Lj j Mol AN F x NN Fi es N NN A d 6 x f 6 N ER d MU FEN Ka 4 o N 4 y NN Sf n a Xx Xx TN T O A N 5 o ie a 5 nl o O JU n H SS f NS d Dialog Plus 2000VA N 2 SN x 5 O 1 cy NM 7 os 9 7 di Pd 7 CAN d ZK x M KEN 6 Q 4 a O y EN 5 p RS232 serial communication port 5 IEC mains input plug Cooling
10. ack up time of the batteries Wide input voltage tolerances without any use of the batteries Up to 120Ah back up time expandability This is possible using additional external battery packs in combination with the ER version of UPS which includes an improved and upgraded battery charger Compact dimensions One of the smallest on the market Thanks to microprocessor control IGBT technology internal batteries ventilation front to rear which eliminates the need for any clearance down either side of the unit Reduced noise 40db A Due to use of high frequency IGBT technology innovations in the design of the magnetic parts Advanced Communication Operational parameters selection via the software Using the free software supplied with the system it is possible to configure the UPS operating parameters to suit the environment in which it is to be installed and operated see page 18 Monitoring and shutdown software included Powershield provides an efficient and intuitive system for controlling and monitoring the UPS displaying all of the most important information such as input voltage applied load battery capacity etc using a series of bar charts The software is able to provide detailed information even if the UPS has malfunctioned enabling the user to find out why the fault has occurred and when Powershield has been developed using a client server architecture
11. arious systems even systems in different ranges thereby increasing the productivity and reliability of the range High overload capacity The UPS can supply overloads up to 15096 during mains supply or battery operation SPEDLPX0205REN PHELL CH ELETTR ONA ig riello Ups pivocras Programmable timer This function enables the user to program the timer to automatically switch the system on or off at specific times configurable via the software Stand by During Stand by function the inverter is switched off and the batteries are charged The stand by function is automatically activated when the UPS is switched off Frequency auto selection The UPS can be configured to automatically select the output frequency 50 or 60Hz by using the input frequency as its reference 50 or 60Hz Battery start up cold start The UPS can be switched on even when no incoming mains supply is available Auto restart Following a mains supply failure once the UPS has shutdown upon reaching the end of its designed battery autonomy time the system can be configured to automatically restart once the incoming mains supply returns configurable via the software GS T V certified The Dialog Plus range has been tested and approved by the official certification agency GS TUV which guarantees the products performance and reliability Network phone and computer protection The UPS provides overv
12. configurable via the software to 50Hz 60Hz or auto select 6 2 72 Thermal 10 BY PASS ion A 10A n AI 39 switch Thermal switch A 12A 40ms 264V single phase 180V single phase 13 4 A 14 4 A Thermal switch 16 A 3000VA ER 16 A j B Wi riello ups MODEL 700VA Back up in minutes No Batteries Battery nominal voltage Type of battery Battery configuration Type of recharge Recharge current Recharge time Intervention time loss of the mains power supply Battery ripple current Battery voltage stability batteries fully charged Battery protection 8 2 24 V Rated voltage Wave form Frequency Frequency converter function Current peak factor from EN62040 3 regulation Rated output VA Rated output W Static variation Dynamic variation with load impact from 0 to 100 Output frequency variation supply present supply lost 700 VA 490 W SPEDLPX0205REN 1000VA 1000 VA 700 W 28 1000VA ER 1500VA BATTERIES External batteries 9 13 External batteries 4 8 External batteries 48 V 96 V Ah Sealed lead maintenance free In series Two voltage levels A 4hr typical 2000VA 2000VA ER 3000VA External batteries 8 External batteries 9 External batteries 96V Zero lt 0 01C lt 0 7 Fuse OUTPUT 220 230 240 V selectable Sinewave 50 60 0 2 Hz selectable Yes with batteries 3 1000 VA 1500 VA 2000 VA 700 W 1050 W 1400 W se 1
13. cordingly 14 SPEDLPX0205REN Wiriello fleli0ups moser 8 INTERFACING gt 8 1 Serial communication port The UPS has the tollowing communication ports see UPS views RS232 serial port COMMUNICATION SLOT expansion slot for additional interface cards RS232 serial port The RS232 serial port enables the connection of a PC COM port by means of a pin to pin serial cable providedt RS232 CONNECTOR PN Vani 1 PIN No SIGNAL 1 Contact closed UPS failure Bypass Alarm 2 TXD 3 RXD SD remote shutdown O 4 5 GND 6 12Vdc interface power input 7 PNP Signal 8 Contact closed battery low pre alarm 9 Contact closed on battery mode 0 If a different cable is used it should be a pin to pin type with a max length of 3 metres 2 Opto isolated contacts max 35Vdc 15mA S SD Whilst the UPS is in battery mode the UPS will perform a complete shutdown when 5 1 5Vdc is applied between PIN 3 and PIN 5 for at least 20 seconds Communication Slot All Dialog Plus come with an expansion slot for the fitting of optional communication cards so that the unit is compatible with most communication options Some examples Serial port duplexer Ethernet network agent with TCP IP HTTP and SNMP protocols RS232 RS485 port with JBUS MODBUS protocol For more details on the options available visit the manufacturer s web site 15 SPEDLPX0205REN L Wi riello ups patos us g
14. d battery autonomy for prolonged power outages 12 Battery charger A DC DC module to recharge the batteries it is deactivated when the mains power supply fails 13 Battery protection Battery to UPS protection fuses 14 Intelligent slot To slot in any auxiliary communication card accessory cards 15 Net Tel protection on RJ11 and RJ45 Protection for network or phone connection from any overvoltages 16 RS232 interface Enables monitoring and shut down software connection 17 Mimic panel The mimic panel provides the user with visual LED and acoustic buzzer signals relating to the status of the UPS The panel also enables the user to control and send basic commands to the UPS 12 SPEDLPX0205REN L Wi riello ups patos us Operafing modes NORMAL mode During NORMAL mode the UPS power is taken from the incoming mains supply whilst the UPS output load is supplied by the inverter refer to the block diagram and the batteries are maintained at a fully charged state Automatic BY PASS mode The UPS will switch to BYPASS mode in the event of one of the following scenarios a Immediately after the UPS is switched on if the mains power supply is present The UPS output is automatically switched onto the by pass line therefore the load is temporarily powered by the incoming mains power supply This enables the user to exceed the applied load in rush current without tripping the fuses to the inver
15. e UPS is working on mains on by pass on battery it shows the load applied the battery charge level and warns of any error conditions occurring On line UPS Unit Display panel for the Tower and Rack versions Q 25 50 75 100 N 3 a mn n HE lt TOWER VERSION RACK VERSION gt Moy V BAT 6 Load level indicator Battery failure indicator Battery level indicator Load powered by bypass indicator LOE Mains mode indicator Fault Stand by indicator ORORORO Battery mode indicator Battery low indicator gt 10 2 Description of the display panel icons Led indicator panel This section provides a detailed description of all of the LED indicators on the display panel ICON STATUS DESCRIPTION Red Steady The UPS has an error or fault Kad The UPS is in stand by mode Flashing Green Steady The UPS is operating on mains power L 7 The UPS is operating in bypass mode Green Flashing The input voltage is out of the accepted tolerance 20 SPEDLPX0205REN Wi riello ups The UPS is operating in battery mode and the audible alarm will Green i Sie y sound at regular intervals 7 When operating from battery power the UPS will signal that it is Green Flashing about to switch off due to the end of discharge In this state the alarm will sound at regular intervals of 1 sec see table 1 Red Steady Indicates a battery test failure Dr Yellow Steady The loads connected
16. ensure that the UPS continues to provide the highest level of protection and performance Overload An overload occurs when the connected load requires a level of power higher than that for which the UPS has been designed This condition is indicated by the red overload LED located on the load LED bar also during this condition the buzzer will sound To rectify this condition the user must switch the UPS off OFF button reduce the applied load and switch the UPS back on again ON button 13 SPEDLPX0205REN PHELL CH ELETTR ONA Wriello ups patos mus _ Mains out of tolerance The UPS is designed to function with a wide range of input voltages This ensures that the batteries do not intervene unnecessarily thus increasing the back up time should an actual blackout occur The microprocessor continuously checks the input voltage and frequency to ensure a high standard of operation and will switch the load onto the by pass within a wide tolerance range Overtemperature If the internal temperature exceeds the acceptable limits the UPS will protect itself by shutting down During this situation the Stop Stand by LED will illuminate and the buzzer will sound continuously Batteries depleted The microprocessor carries out a periodic battery efficiency test If the batteries fail the test the red Battery failure efficiency 6096 LED will illuminate In this condition the UPS batteries should be replaced ac
17. is guaranteed The Dialog Plus range of UPS is available in two formats tower or 19 rack mount both of which are available as either Q Standard with batteries located inside of the UPS Q ER without any batteries located inside the UPS but including a powerful battery charger max 8A This version can only be used in combination with an external battery box for long autonomy times The following diagrams show the tower versions Tower version MODEL Dialog Plus Dialog Plus Dialog Plus Dialog Plus Dialog Plus 70 100 100ER 150 200 200ER 300 300ER Nominal power VA 700 1000 1500 2000 3000 Nominal output Vac 220 230 240 voltage Dimensions HxWxD mm 236x158x400 236x158x400 236x158x500 348x192x460 348x192x460 Weight Kg 12 14 8 19 34 14 35 14 3 SPEDLPX0205REN Wirellous Mren Rack version Dialog Dialog Plus Dialog Plus Dialog Plus Dialog Plus MODEL Plus rack rack rack rack rack 70 100 100 ER 150 220 220 ER 300 300 ER Nominal power VA 700 1000 1500 2200 3000 Serine oven Vac 220 230 240 voltage 483x480x176 483x480x176 i 1 Dimensions WxDxH mm 483x390x88 483x390x868 483x480x88 483x480x838 483x480x88 Weight Kg 13 16 9 2 38 13 39 14 U Note 88mm 2U 176mm 4U 2U 2U 483mm 19 APPLICATIONS gt Persona
18. ith the following equipments O UPS a O User g SI Manual E Jd ii p d 10 SPEDLPX0205REN QO IEC 16A loose plug only tor 300 300 ER models Q Battery expansion connector only for ER models ONLY FOR DIALOG PLUS RACK 220 300 MODELS a BATTERY BOX Z MMR AT nr IT T Fuge 264 01 400v a AN NN j a ER RELLO ELETTR ODA Wriello ups patos PLUS BLOCK DIAGRAM gt 7 1 Block diagram of the UPS Output Input Input filter a PFC Boost Inverter Output filter mw fuse Output G A WA E Input T Besta backfeed relay Automatic bypass input protection 6 Battery charger 12 vi DC DC Boost Battery fuse 10 Batteries Battery Expansion 14 15 16 17 Ei Intelligent Net Tel RS232 Mimic slot protection interface panel gt 7 2 Options Isolating transformer Battery back up extension Remote led mimic panel Net Adapter USB Converter Multiplexer LEGEND 1 Re settable input protection 2 Input EMI filter back feed protection Input filter for protecting the UPS and load against any electromagnetic disturbances Back feed protection intervenes when the mains power supply fails therefore isolating the UPS from the input socket to prevent any back feed to the mains power supply This protection is required to prevent any voltage from returning to the supply which could put the operator
19. ives 73 23 Low voltage directive entorcing the obligatory CE marking from 1 1 97 This directive concerns all satety issues associated with the equipment 89 336 Electromagnetic compatibility directive enforcing the obligatory CE marking from 1 1 96 This directive concerns all issues of immunity and emissions relating to the UPS at its place of installation gt 5 2 Standards relating to systems and installation The above product regulations refer specifically to uninterruptible power supply systems It is these regulations that manufacturers of uninterruptible power supply systems are obliged to adhere to However with regard to the electrical system the installer must refer to other standards These standards are HD384 IEC60364 for electrical systems in general Standard EN60439 1 concerning control equipment Standard EN50272 2 for battery installation SPEDLPX0205REN PELL CHELETTH ODA Fi riello Ups 6 SUPPLIED EQUIPMENT AND ACCESSORIES gt 6 1 Tower version The tower version UPS is supplied together with the following equipments O UPS OQ RS232 serial cable a IEC 10A or 16A Power supply cable u IEC 16A loose plug only for 300 300ER model SPEDLPX0205REN MELLO ELETTRONICA Wriello ups 2 6 2 Rack version DIALOG PLUS The rack version UPS is supplied together w
20. k up 12 14 19 34 l 35 external batteries external batteries external batteries integrated batteries Mechanical characteristics Shielded metal cabinet with an applied plastic front panel display Level ot protection IP215 Resistance to vibrations lt 2G G Power dissipated with load 49 77 77 115 140 140 210 210 present VW Colour Metallic grey Input differential current I mA OUTPUT PROTECTION FIGURES RECOMMENDED VALUES FOR DISCRIMINATION Normal fuses Gl In Rated current 7 Normal circuit breakers Rees eurem curve C Ultra rapid fuses UR URG In Rated current 2 Cable input Rear Input connections IEC socket Output connections 4 EC sockets 1 RS 232 1 Net Tel protection slot 6 IEC sockets 1 RS 232 1 Net Tel protection slot Cooling Forced ventilation Maximum installation 1000m altitude Altitude Power derating 1096 for every 1000m above 1000m above sea level 30 SPEDLPX0205REN Wriello ups piaLoe PLUS 13 DIALOG PLUS RACK gt 13 1 Rack models MODELS FRONT VIEWS Dialog Plus Rack DLPR 700 1500 VA Dialog Plus Rack DLPR 2200 3000 VA Battery box included for models DLPR 2200 3000 VA MODELS POWER AUTONOMY min DIMENSIONS HWD mm WEIGHT Kg Dialog Plus Rack DLPR 70 700 VA 490 W 8 88x483x390 13 Dialog Plus Rack DLPR 100 1000 VA 700 W 8 88x483x390 16 Dialog Plus Rack DLPR 100 ER 1000 VA 700 W External batteries 88x483x390 7 Dialog Plus Rack DLPR 150 1500 VA 1050 W 8 88x483x480
21. l computers gt Small IT networks gt Local Area Networks LAN gt Workstations gt Servers gt Point of sale POS systems gt Data centres gt Industrial PLC s gt Cash registers gt Electrical medical equipment gt Emergency devices lights alarms CHARACTERISTICS The system provides a stable and reliable voltage On Line double conversion VFI technology in accordance with European standard IEC62040 3 with filters for suppressing atmospheric and mains borne disturbances The On Line technology provides the maximum protection for the connected loads The double conversion stage filters and stabilises the input voltage and then reproduces it free of any disturbances such as overvoltages variations in frequency and voltage noise etc The IEC62040 3 standard defines this technology as VFI Voltage and Frequency Independent meaning that the output voltage and frequency are completely independent of any variations or disturbances caused to the incoming mains supply High level of reliability versatility and easy maintenance High level of reliability total microprocessor control The digital control system dramatically improves the overall reliability and efficiency of the UPS resulting in a reduction in the number of electronic components required the microprocessor controls and monitors all of the functions of the UPS from one common control card The control card can be used across a number of v
22. oltage protection via the RJ11 and RJ45 connectors Re settable input protection The UPS input is connected via a re settable fuse to protect against overloads or short circuits Low consumption Low impact on the mains power supply sinusoidal absorption The input current absorbed by the UPS from the mains supply is sinusoidal This means that the system has a very low impact on the incoming mains supply network and as a consequence on the other electrical devices that are connected to it Load power factor correction UPS input power factor close to 1 The UPS absorbs power from the incoming mains supply with a power factor close to 1 even if the systems supplied by the UPS have a power factor inferior to this For example if the UPS supplies a piece of IT equipment with an input power factor of 0 65 the UPS input power factor will still remain close to 1 ensuring that any mains supply power factor correction banks are not overloaded SPEDLPX0205REN PELL CH ELETTR ODA ig riello Ups mocmas Battery optimisation High level of battery reliability automatic battery test The UPS carries out battery tests automatically these tests enable the system to periodically check the efficiency of the batteries in order to prevent any faults occurring to them The test does not in any way compromise the supply to the connected equipment and given the short duration seconds it does not affect the life or the b
23. osh that has a client server architecture Enabling the user to access the Windows Novell IBM OS 2 and the most commonly available UNIX operating systems when using a TCP IP network It also enables the user to support the NetMan series network agents to control the UPS via a network and furthermore comes with multilingual support Detailed display of all the UPS data PowerShield provides all the data required to make an accurate and swift assessment of the UPS operation and status Block diagram and operational diagram of a UPS PowerShield displays a block diagram of the UPS thus providing the user with conceptual information as to the status of the system Automatic saving of the events log and graphical display of the most important values All of the events regarding the operation of the UPS are saved and recorded thus allowing the user to monitor such data as the input voltage applied load or the remaining back up time available from the batteries Alarm notification via e mail and SMS It is possible to configure PowerShield to automatically notify of an alarm via an e mail or SMS message Programming the UPS commands Enables the user to program all of the commands that would normally be carried out manually to be performed automatically for example shutting down or switching the servers back on UPS battery test etc 17 SPEDLPX0205REN gt 8 3 Configuration software Configuration Software Winello
24. ps e UPSTools sottware enables the user to configure the UPS and provides a full view of the system parameters and status through the RS232 serial port Refer to the paragraph UPS Configuration tor a list of the contigurable values available UPS Configuration The following table lists all of the possible configurable values available so as to best adapt the UPS to the user requirements The configuration can only be modified using the UPSTools software provided FUNCTION Automatic Restart Battery low alarm Output frequency Output voltage Bypass voltage threshold Battery capacity SPEDLPX0205REN DESCRIPTION Automatic restart when the mains power supply returns Remaining battery charge level setting for the battery low alarm Enables the user to select the output frequency Enables the user to select the output voltage Selects the voltage range accepted for switching over to the bypass Enables the user to set the capacity of battery DEFAULT Enabled 3 min 50Hz 230 Vac Low 180V High 264V Standard 2Ah ER 65Ah 18 POSSIBLE CONFIGURATIONS Disabled Enabled 99 in steps of 1 minute 50Hz 60Hz Auto the UPS will set the output to match the input frequency either 50 or 60 Hz 220 Vac 230 Vac 240 Vac Low 180 200 in steps of 1V High 250 264 in steps of 1V The user must set the capacity of the battery if the actual capacity is different from
25. rt 3 IEC output sockets max 104A 5 IEC mains input plug IEC output socket 16A 2 Cooling fans 4 Input thermal re settable protection 6 Battery expansion connector 34 SPEDLPX0205REN
26. s means that the power systems used to power them must be able to provide an absolutely precise and even more importantly absolutely reliable source of power The standards produced by IEC CENELEC in the IEC EN62040 and EN50091 series cover all aspects of the product safety electromagnetic compatibility and performance In more detail this series is divided into the following individual standards EN62040 1 Uninterruptible power supply systems UPS general provisions and safety provisions EN62040 1 1 Uninterruptible power supply systems UPS general provisions and safety provisions used in areas accessible to the operator EN60950 CEI74 2 ITE Information Technology Equipment safety EN50091 2 Uninterruptible power supply systems UPS electromagnetic compatibility provisions EN50081 2 Electromagnetic compatibility immunity IEC1000 4 2 Immunity Electro Static Discharge ESD IEC 1000 4 3 Immunity electromagnetic tields IEC 1000 4 4 Immunity transient overvoltages BURST EC1000 4 5 Immunity current surges Surge SPEDLPX0205REN L Wi riello ups moen EC6 1000 4 11 Low freguency disturbances EN50141 Induced radio interference EN55022 Radio frequency disturbance ENV62040 3 Uninterruptible power supply systems UPS performance provisions and test procedures EC146 CEI22 Semiconductor electronic converters EC529 CEI70 1 Degree of protection of casings European Direct
27. t 8 2 Communication software MAIN CHARACTERISTICS 1 2 3 4 5 Sequential and prioritised shutdown PowerShield enables the user to shutdown the network without having to individually switch off each PC or server and before doing so Powershield will save the work that was being done regardless of the application that was being used The user may also define their own shutdown procedure and also prioritise the shutdown of critical components within the system such as vital and non vital servers Multiplatform compatibility PowerShield provides the user with a standard control and monitoring capability using TCP IP communication protocol This enables the user to monitor computers that use different operating systems from a single console For example not only could the user monitor a UNIX server from a PC with Windows 98 the user could also connect to UPS systems situated in different locations by using either a dedicated network intranet or the Internet Events scheduling PowerShield enables the user to define their own shutdown switch off and on procedures for the systems that are connected to the UPS Not only does this noticeably increase the degree of security of the system it also enables the user to make significant energy savings Message management PowerShield keeps the user constantly informed of the status of the UPS whether locally or by sending messages to users connected to the network l
28. t is also possible to create a list of the people who will receive messages by e mail fax and SMS should a fault or sudden blackout occur Integrated SNMP agent PowerShield contains an integrated SNMP agent for managing the UPS via SNMP This agent is able to send all of the information regarding the UPS and is capable of generating traps using the RFC 1628 MIB standard This enables the user to control the UPS using SNMP compatible workstations such as HP Open View Novell Managewise and IBM NetView OPERATING SYSTEMS SUPPPORTED Powershield FULL version Windows 95 98 Me NT 4 0 Win 2000 Win 2003 Server XP Novell Netware 3 x 4 x 5 x Intra NetWare IBM OS 2 Warp and Server Mac OS 9 X OSX The most commonly available UNIX systems such as IBM AIX HP UNIX SUN OS SPARC SUN Solaris INTEL and SPARC SCO Unix and UnixWare Siemens SINIX Silicon Graphic IRIX Compaq True 4 UNIX and DEC UNIX Linux BSD UNIX and FreeBSD UNIX 16 SPEDLPX0205REN PHELL CH ELETTR ONA ig riello Ups patos Pus POWERSHIELD SOFTWARE FUNCTIONS 1 2 3 4 9 6 7 Graphical monitoring of the UPS status PowerShield is the easy to use yet powerful program that enables the user to monitor and control the UPS systems There are various graphical versions including Windows Java OS 2 and MacOS MACOS version The PowerShield software is the only UPS control and shutdown software available for the Macint
29. ter During the transition the microprocessor ensures that the inverter output is synchronised in phase with the incoming mains power supply before the load is switched onto the inverter b lf the inverter is permanently overloaded The inverter will continue to supply power the load even when there is a temporary overload condition If this overload condition persists the inverter protection is tripped and the UPS will switch the load onto the by pass line therefore the load will be powered from the incoming mains supply c If the voltage produced by the inverter exceeds the allowable tolerance limits d It the inverter or rectifier booster malfunctions or fails completely BATTERY mode The UPS operates in BATTERY mode when the mains power supply fails short interruptions or total black outs During this mode the buzzer sounds intermittently a During battery back up autonomy mode b When the back up time limit has been reached Approximately 3 minutes from the end of the back up time period configurable via the software the yellow battery discharged LED will illuminate and if the management software has been installed the programmed shutdown of the IT applications will begin if configured to do so Error conditions The UPS is designed to function reliably and to automatically guarantee the protection of the connected load However particular operating conditions may exist which the operator should be aware of to
30. that renders it flexible and easy to use with multilingual support and on line help The Powershield software is provided free of charge with an SNMP agent this version will operate on 6 SPEDLPX0205REN PHELL CH ELETTR ONA ig riello Ups mocnu Windows 95 98 2000 Windows 2003 Server Me Xp NT4 0 Novell Mac OS Mac Osx Mac Os 9 x amp Linux operating systems The software enables the user to programme the automatic start up and shutdown of the system on a weekly basis The UPS also contains the following hardware interfaces RS232 serial port signals interface slot for the installation of various adaptors NORMATIVE REFERENCES gt 5 1 Main reference standards The company quality system has been certified as conforming to ISO 9001 Certificate No CERT O4674 99 AQ VEN SINCERT This covers all of the procedures operating methods and controls from the design stage to production sales through to the after sales service support This certification guarantees the following aspects to our customers the use of quality materials rigorous standards in production and testing receptiveness and openness to our customers constant support of all our customers As well as conforming to this certification the company also produces state of the art products as dictated by the requirements of the standards quoted below The advances that have taken place in Information Technology system
31. to the UPS are being supplied by the bypass Represents the estimated percentage of battery charge using 5 LED s see table 2 8 B BH ll Green Active Holding the ON button down for at least 10 seconds will show the input voltage value see table 3 Green Red Indicates the 96 of load applied to the UPS in relation to the nominal 25 50 75 100 via A Active value The last icon indicates overload see table 4 Table 1 battery status Battery status LED battery working Normal j Low i LED illuminated steady A LED flashing 1 flash per second Table 2 battery level Battery LED bar Battery level 1 2 3 4 5 0 20 i 2090 4090 i 40 60 i 60 80 i i i 80 100 s i i 21 SPEDLPX0205REN m Wi riello ups patos Pus Table 3 input voltage Input Voltage 190V 200V 200V 230V 230V 250V 250V 260V gt 260V Table 4 load level Load level 0 596 5 2596 2596 5096 5096 7 596 75 102 gt 102 LED illuminated steady Overloads on the UPS 25 Battery LED bar 2 3 Load LED bar 50 75 100 The following table shows how the UPS reacts when overloads occur during mains or battery operation and indicates the time that the UPS will continue to supply power to the load OVERLOAD LEVEL 102 lt Load lt 109 110 lt Load lt 130 130 lt Load lt 150 Load gt 150 SPEDLPX0205REN OVERLOAD TIMES from mains