2. IC I FINDING Manual Compiled by Craig Brown FOURWAYS 1 If c nditioning im p N ut di Vw W WW OE M Wal sS y 4 UWWUUEKEAE EBEN LED 4A w i ET 5 P i w A b 1 L A 44 72 C e 4 UI FR EVE OO UI Va ined ese ii D q p CT p e Tools required e t check on site e Checking the gas e Unit not cooling e Unit not heating e Water leak e Compressor not starting e Outdoor fan not starting e Testing the capacitor e Vacuuming and charging the system e Checking for gas leaks e Sizing a room for a unit e What to prepare before you call for technical assistance N N N OQ Ooo HS coc PO N SUNG SAM The air conditioning technician requires a number of specialized tools to carry out his job effectively Among these are the basic hand tools and ladders and so forth There are also a number of items that are critical in the diagnosing of faults on modern air conditioners These are tools that you MUST carry if you hope to diagnose faults e Agood set of accurate gauges e quality vacuum pump in good working order e A multi meter including a clamp amp meter e A capacitor tester if this function is not available on the multi meter e An accurate digital thermometer An accurate digital scale that can weigh in refrigerant to two decimal points 0 m 1ST CHECK ON SITE W
3. Please remember to include any passageways or open areas such as bathrooms leading off the space you require conditioned Also high ceilinged areas will require extra capacity Remember that glass allows a lot of heat into a room and also allows just as much heat to escape when you are in heating mode Big windows will mean you need to upsize Electric equipment and people also add significant heat load to a room If unsure contact a sales representative Remember when quoting that an R22 unit requires at least 1 5m of piping between the indoor and outdoor to reduce noise and pressure an R410a unit requires at least 2 5m of piping between the indoor and the outdoor for the same reason WHAT TO PREPARE BEFORE YOU CALL FOR TECHNICAL ADVICE sometimes after checking everything you can you still cannot get the unit right If this is the case there are technical advisors employed by Fourways Air Conditioning that will be happy to assist you over the phone If they cannot help you solve the problem over the phone they may arrange to visit your site with you to assist you with rectifying your problem When you call please have the following information at hand e The model number of the indoor unit e The error code that the unit is displaying on the indoor unit outdoor unit and remote e As much history of the unit as possible what previous repairs have been done spares changed etc FOURWAYS 7 4 7 e e e Pificonditioning
4. chance the unit is short of refrigerant Treat refrigerant gas with the utmost respect It has the potential to deliver a serious and painful injury If you have a leak on an R410a inverter system recover the gas repair the leak pressure test with nitrogen to ensure the leaks are repaired vacuum the system to 1Torr 1000 micron and weigh in the correct amount of refrigerant as specified on the unit s labels UNIT NOT COOLING There are a number of issues that can cause a unit to stop cooling A lack of refrigerant a blockage or a lack of air flow are the most common causes Are the filters clean Are the indoor and outdoor coils clean Is the gas pressure correct An overcharge or undercharge can prevent effective cooling Is the airflow unhindered Is the indoor barrel fan clean Is there a section of indoor coil that is not the same temperature as the rest If so this could indicate a blockage e Are there any kinked pipes e sthe compressor and outdoor fan running e Are the amps within range High amps can indicate overcharge or a blockage low amps can indicate bypassing on the reverse valve or a shortage of refrigerant UNIT NOT HEATING J Solenoid valve apply power and test by touching with a screwdriver it should be magnetised The issues that affect the heating performance of the unit are similar to those that affect the cooling We are again checking refrigerant charge air flow and for signs of a bl
5. ed in the compressor will not start If the contactor is not pulling in we need to check the various safeties on the unit an HP or LP switch or discharge temperature sensor or other safety switch can keep the compressor from coming in Normally the safeties run in series on the neutral side of the contactor coil so if even one safety is out the contactor will not pull in If you have continuity on your neutral and your live to the contactor is good you should be able to measure 220VAC at the connection points for the coil of the contactor If you are measuring 220VAC and the contactor is still not pulling in the contactor is most likely faulty OUTDOOR FAN NOT STARTING If the outdoor fan is not running when the unit is on cooling the head pressure will climb and the unit will trip Just remember that in heating operation there are times when the outdoor fan will not be running e sthere an obstruction stopping the fan blade from turning e Test on the fan terminals to neutral to see if there is 220VAC if not the PC board is not giving the signal for the outdoor fan to turn on e sthe fan capacitor within its correct range 0 m TESTING THE CAPACITOR The compressor s capacitor is responsible for starting the compressor and the fan capacitor is responsible for starting the fan If either of these fails their respective component will not start In order to test these you must first switch off the p
6. for the air conditioner s power supply this usually has an orange switch This circuit breaker allows for the start up current of compressor without tripping Remember that the start up current of the compressor is normally 4 to 6 times higher than the running current If you suspect that the compressor may be seized this can be checked by first ensuring that the capacitor is within range See capacitor testing for the procedure If the capacitor is within range and the compressor still trips its circuit breaker or hums you can use your clamp ammeter to check the current being drawn by the compressor as it tries to start If the current keeps climbing until the klixon OLP trips the compressor is seized and needs to be replaced If the unit is tripping the earth leakage the first thing that needs to be checked is that the compressor is not down to earth In order to do this you can follow this procedure first ensure that the power supply to the unit is off The wires need to be removed from the compressor terminals Please pay careful attention to where they came off as if you put them back in the wrong order the compressor will not run Once the wires are off measure between the pins of the compressor with your multi meter set on ohms Q There should be a resistance reading between each of the pins You can then measure each of the pins to an earth you can use the red test lead on each of the compressor pins one at a time and the black tes
7. hen you arrive on site for the first time there are a number of checks you need to carry out before you begin to try to diagnose a problem These may seem obvious but it is easy to overlook something simple and waste a lot of time looking for a more complex fault than what actually exists A few minutes spent checking the simple things can save hours and plenty of money on something misdiagnosed Is the power supply to the unit on and correct 230VAC or 10 in the case of a single phase unit and 380 415 VAC in the case of a 3 phase system Are the filters and indoor coil clean and free of obstruction Is the indoor unit barrel fan clean This is very important as a dirty barrel fan causes a multitude of problems Are there any lights flashing or error codes displayed on the indoor unit or remote control Is the outdoor unit coil clean and free of obstructions A bush or tree that has grown against the coil will severely restrict airflow cause high head pressure problems Does the outdoor fan look in good condition and unobstructed Do the interconnecting cables or pipes look damaged e Are there obvious oily marks on the pipes flare nuts coil unit casing These could indicate a leak CHECKING GAS Gas can only be accurately checked whilst the unit is running Our units use either R22 or R410a You must ensure that you use R410a gauges on an R410a unit Using R22 gauges on an R410a system is dangerous A technician s safe
8. l of the drain or indoor unit e Isthe indoor unit level If the unit is at an angle the condensate water will leak from the unit before it can reach the drain e sthe drain running at a downwards angle Any up turn in the drain pipe can cause water to flood back to the indoor unit e sthe drain pipe blocked e Check the drip tray and indoor unit back body for cracks Water marks can indicate a crack too small to see with the naked eye e s there sufficient air flow through the unit e sthe barrel fan clean e sthe gas pressure correct e sthe unit sized correctly An undersized unit can run until it eventually freezes up and then leaks e Is the unit being run constantly for extended periods of time COMPRESSOR NOT STARTING The compressor should come in when the indoor unit calls for either heating or cooling and it should cycle off regularly If the compressor is not starting or is tripping the power there are a number of checks that need to be made TRIPPING THE POWER Firstly if the compressor is tripping the power we need to establish if it is tripping the earth leakage or if it is tripping its own circuit breaker If it is tripping the earth leakage there is a chance that the compressor is down to earth If it is tripping its own circuit breaker it could be that the compressor is seized the capacitor is faulty or the circuit breaker is too small incorrect Please use a curve 1 circuit breaker
9. n the correct amount If an R410a system loses more than 15 of its total charge it needs to be recharged completely with virgin refrigerant This is because R410a is a blend and the ratio of the blend needs to be maintained CHECKING FOR GAS LEAKS It is of utmost importance that your system is gas tight If you have a leak the system will give endless problems and you may end up losing the compressor and risk blocking the 4way reverse valve There are a number of ways to find a leak on the system Any place you find oil spots on the system piping or arm flex is an indication that there is a leak nearby One can also make use of electronic leak detectors or my favourite method soap and glycerine To make a leak detection liquid mix 1 part sunlight soap and 1 part glycerine into a container Paint this mixture onto any spots you suspect may be leaking The pressure inside the system from the refrigerant or nitrogen will cause this mixture to bubble any place it is leaking out The leak can then be repaired and the system re pressure tested and finally vacuumed SIZING A ROOM FOR A UNIT Please note that this section is a guideline and factors not mentioned here can have a dramatic effect on heat load If you are unsure about what size air conditioner an area will require please contact one of the sales representatives at Fourways Air Conditioning to assist you The general rule for the Highveld region is 550BTUs per square meter of room size
10. n the pressure this is the indoor fan motor starting up There after the pressure will begin to climb again Once it reaches around 26bar 2600kPa 390psi the outdoor fan should cycle off or slow down depending on the model The pressure Should now begin to drop Once the pressure reaches about 17bar 1700kPa 260psi the outdoor fan should start up again or speed up If the unit is failing to reach a point where the outdoor fan motor cycles off you could be short of gas If the unit is overshooting on pressure and the compressor is tripping out before the fan stops slows you could be overcharged To get check the pressure in an R410a fixed speed compressor follow the same procedures as with the R22 unit but the pressures will be different On cooling you should be looking for around 8 2bar 820kPa 130psi On heating the fan should cycle off at around 32bar 3200kPa 500psi On an R410a inverter unit to test the pressure on cooling set the unit to cooling on the lowest set temperature Listen to the outdoor unit as it starts up You should hear the compressor ramping up When it seems that the compressor is running at its fastest speed the pressure should be around 8 2bar 820kPa 130psi This is a rough guide as there is no way of knowing the exact frequency of the compressor when you are checking the pressure If the pressure is significantly below this with the compressor running at what sounds like its highest speed there is a good
11. ockage Remember that the indoor unit will only start once the indoor coil has reached temperature so we are expecting the compressor to start before the indoor unit e Are the filters clean e Are the indoor and outdoor coils clean e sthe gas pressure correct An overcharge or undercharge can prevent effective heating e sthe airflow unhindered e sthe indoor barrel fan clean e sthere a section of indoor coil that is not the same temperature as the rest If so this could indicate a blockage e Are there any kinked pipes e isthe compressor running e Are the amps within range High amps can indicate overcharge or a blockage low amps can indicate bypassing on the reverse valve or a shortage of refrigerant e If you feel that all of the pipes going into the 4way reverse valve are the same temperature hot this normally indicates that the reverse valve is faulty e Check that the electrical terminal that supplies a power to the solenoid that controls the 4way reverse valve An absence of power could indicate a damaged communication cable or faulty PC board e Check that the solenoid valve is securely attached to the 4way reverse valve e To check if the solenoid is working apply power to it and touch it with a steel screw driver it should be magnetised db Eaa Water leaking from the indoor unit can be caused by several factors including the unit freezing up a blocked drain or broken pipes drain pans and the leve
12. ower supply to the unit Capacitors are measured in microfarads the symbol for which is uf In order to check if a capacitor is working first we need to check its uf rating on the side of the capacitor We then remove the wires on the capacitor making sure to remember where they go in order to put them back correctly Once the wires are off we short the pins together with a screw driver Be careful not to shock yourself while shorting the capacitor out The pictures below are of a fan capacitor and a compressor capacitor respectively you need to short from point A to point B The red ring indicates where the microfarad rating is displayed E Fan Capacitor Compressor Capacitor To test the capacitor we select the capacitor setting on the multi meter This is normally under resistance and is often displayed as nf as the unit on the screen Hold the test leads on A and B It normally takes a few seconds to get an accurate reading Compare the reading you get to what is specified on the casing of the capacitor If it is more than 10 under the rating replace the capacitor VACUUMING AND CHARGING THE SYSTEM When installing a unit or working on a unit with the internal or external pipe work open to the atmosphere it is critical that you vacuum the system once you are done It is important that you use a good vacuum pump and that you replace your vacuum pump s oil regularly Changing the oil in your vacuum pump is explained in the
13. t lead to any copper pipe you should not get a resistance reading here The multi meter should display OL or If you get a reading with an ohm value the compressor is down to earth and needs to be replaced It also means that the system needs to be flushed with flushing liquid and then vacuumed thoroughly and a bi direction burn out drier fitted to the suction line COMPRESSOR NOT STARTING r If the compressor is not starting we need to determine where the interruption of power is occurring The first point to test is the live to the compressor from the PC board The live to the compressor is the terminal labelled 1 on the indoor and outdoor unit If you measure from the neutral terminal to 1 and you are not getting 220VAC the PC board is not sending the signal for the compressor to start This can be due to a PC board fault or possibly a sensor error If you are getting power to 1 terminal on the indoor and outdoor units the problem lies in the outdoor unit If you are getting 220VAC on the indoor terminal but not on the outdoor terminal the fault lies with the communication cable Let us assume that we are working on a unit that the compressor is started with a contactor We need to establish if the contactor is pulling in If it is pulling in and the compressor is still not starting we need to check that we have continuity through the contactor If a point has been burnt on the contactor even if it is pull
14. ty comes first Checking the pressure on a R22 unit is straight forward and easier to get an accurate reading On an inverter unit it is more difficult but possible to get a good idea of the pressure in the system Remember that the pressure in the system is affected by the ambient temperature On a cold day a unit s pressure will look lower than if you checked on a hot day Heating pressure check fit red hose while unit Cooling pressure check b ue hose fitted to suction port running on cooling then switch unit to heating With the unit on cooling fit the blue hose low pressure to the unit s suction port the bigger of the two ports Once the outdoor unit has started up the pressure should pull right down and slowly start climbing again Once it has settled the pressure should be around 4 4bar 440kPa 60psi While the unit is running in cooling carefully remove the blue hose avoiding refrigerant burns To test the pressure on heating fit the red hose high pressure to the unit s suction port whilst the unit is running on cooling This is because the pressure is lower at the suction port when the unit is on cooling than it is when the unit is on heating Switch the unit onto heating and wait for the unit to start Once the unit starts the pressure should start climbing Once the pressure reaches around 20bar 2000kPa 295psi you should notice a slight dip i
15. user manual follow these directions carefully Checking your vacuum on your gauges is not enough you need a vacuum gauge to check that the vacuum you have pulled is sufficient to remove all the atmospheric moisture out of your system There are vacuum gauges of all shapes and sizes in a variety of price ranges Choose an accurate one within your price range When pulling your vacuum make sure you vacuum to at least 1000micron and make it holds this vacuum for at least an hour If the vacuum rises slowly but stops before it reaches 3000micron there is still moisture in the system If it keeps rising above 3000micron there is a leak on the system Do not rely solely on your vacuum pump for checking for leaks You also need to carry out proper positive pressure testing to ensure your system is leak free When charging R22 gas bottle to be upright When charging R410A gas bottle to be upside down eo Once you are happy that your system is leak free and well vacuumed you can re charge the system The label on the side of the outdoor unit will tell you exactly how much refrigerant you need to add You can weigh in the correct gas charge to the system to ensure that your system is perfectly charged Remember that units must always be charged while they are in the cooling mode R22 units must be charged as vapour the bottle upright and R410a units must be charged as liquid the bottle upside down It is critical to weigh i