1. ae O AO EL Ue oO ZI YOU NL AL M tr za del nl A K lk O EE 2011 70A 777171 553 Ce re TTET FAN SY bo Sa NE oS NU IU a U A A Figure 3 Schematic of TPS 01 with a protective cup 1 base 2 electric terminals 3 RF amp EMI shielded protective cover 4 magnet 5 compression spring 6 bronze rod 7 bronze nose piece 8 heat sensitive element made from a shape memory alloy 9 protective cup 10 O Ring 11 bushing 12 housing made from a high temperature plastic 13 frame of reel 14 electromagnetic coil The protective cup shields the TPS 01 device from possible mechanical and environmental impacts however the cup reduces the sensitivity of the heat sensitive element in the automatically operated TPS 01 devices and as a result increases their activation time 5 2 Use in detection circuit In most applications apart from its use as an activation device TPS 01 is also used as a thermal detector In such applications the device is connected to an existing fire detection line or directly to a fire panel via a specially designed junction box A schematic of TPS 01 with such junction box for use in detection circuit is shown in Figure 4 5 ma KAA coe i wa ie tie le oe gt LE WU Caen ONA S Figure 4 A schematic of TPS with a detection circuit junction box 9 A wiring diagram of TPS connection to a detection circuit is shown in Figure 5 ELEKTRCALLY ACTIVATED INITIATOR DEVICE
2. TO FIRE PANEL DETECTION CIRCIT Figure 5 Wiring diagram of TPS connection to a detection circuit Example of multiple connection of TPS for large protected areas showing on Appendix 1 5 3 Use in hazardous areas TPSPV is a special design version of TPS containing an intrinsically safe interface and designed for use in hazardous areas 6 TECHNICAL CHARACTERISTICS 6 1 Dimensions and Mass protective cup and junction box excluded 1 Length mm not more than 85 mm 2 Diameter mm not more than 65 mm 3 Total mass kg not more than 0 2 6 2 Operation Temperature Ranges 1 TPS 01 72 from 60 to 55 C 2 TPS 01 93 from 60 to 75 C 3 PS 01 110 from 60 to 95 C 4 TP S 01 M from 60 to 95 6 2 Rated Activation Temperature 1 TPS 01 72 2 C 5 C 2 TPS 01 93 93 C 5 C 3 TPS 01 110 110 C 5 C 6 4 Activation Time Activation time depends on the model of T start initial ambient temperature and the temperature increase rate The temperature increase rates TIR of 3 C min and 30 C min have been selected as standard For TIR 30 C min activation time should be in the range of 58 144 seconds and for TIR 3 C min in the range of 580 960 seconds Test results on the TPS72 and TPS110 activation times are showed in the Table 1 Table 1 Activation times for TPS72 and TPS110 Initial ambient TIR 30 C min TIR 3 C min TPS Model air Max time Min time Max time Min time temperature delay s
3. 01 is unit capable of working 12 years without any technical service from the operator 3 PRODUCT RANGE The TPS comes in four different models Three models operate automatically similar to the thermal detectors with rated temperatures The fourth model is designed for manual operation The models are as follows 1 Model TPS 01 72 suitable for cold areas 2 Model TPS 01 93 suitable for motor rooms and tracks 3 Model TPS110 suitable for motor rooms and tracks 4 Model TPSM manual operation All models could be accomplished in all design versions for use in harsh environments in detection circuit or and in hazardous areas 4 OPERATION 4 1 General No external power supply is required for operation of the TPS device TPS device comes in two basic types for automatic and manual operation 4 2 Automatic Operation A schematic of TPS for automatic operation is shown in Figure 1 The main feature of the automatically operated TPS is a special heat sensitive element 7 with a rated temperature reading When subjected to a fire or a heat the element expands at the rated temperature reading and releases a spring loaded rod 10 mounted inside a nosepiece 9 Figure 1 Schematic of TPS 01 automatic operation 1 base 2 electric terminals 3 RF amp EMI shielded protective cover 4 magnet 5 housing made from a high temperature plastic 6 compression spring 7 heat sensitive element made from a shape memory al
4. place during any installation maintenance or service work conducted within the protected area to prevent an accidental discharge of the fire suppression system 7 5 The heat sensitive element shall be firmly fixed in its position in the device 6 All screws on electrical terminals shall have spring washers 7 In case TPS does not incorporate the junction box for use in the detection circuit it should be attached to another appropriate junction box to ensure proper cable connections 8 The device is incapable of generating the electric impulses at levels dangerous for humans or animals 9 The connecting of the cable to the fire suppression units shall always be the last wiring procedure 10 After the system has been commissioned remove the safety pin if required a protective copper cup could be installed after removal of the safety pin to ensure the system is left in operable condition Before removing the pin ensure the heat sensitive element is firmly attached to the bronze rod inside the device 11 Where the protective copper cup is installed bend the edge of the cup into the bushing in two opposite points in order to avoid its accidental removal 12 Hot work must not be carried out within the vicinity of any TPS 01 device as naked flame or exposure to high temperatures may cause activation of the device and the incorporated fire suppression system If so the fire Suppression system shall be disconnected and the device removed prior t
5. TPS 01 AUTONOMOUS DETECTION and ACTIVATION DEVICE Models TPS 01 72 TPS 01 93 TPS 01 110 TPS 01 M User Manual Design Operation amp Installation Manual Sapfir s r o Z hradn 19 90024 Ve k Biel Slovensko Tel 42145916247 E mail info sapfir sro eu www sapfir sro eu CONTENTS 1 10 11 12 13 Introduction General Product Range Operation Application amp Design Technical Characteristics Limitations Installation amp Wiring Safety Requirements service Life amp Maintenance Packaging Disclaimer Warranty 14 Appendix 1 1 INTRODUCTION This document represents a user manual and provides technical information on design operation and maintenance of TPS devices It also includes warranty 2 GENERAL TPS is a unique autonomous thermal activation and detection device that allows detecting a fire and activating a powder aerosol or gaseous fire Suppression system Also the device has features such as provision of a signal to a fire panel and incorporation of an additional output designed to shut down the electrical equipment or activate an alarm depends on a specific modification TPS can also be used as a thermal detector with a fixed temperature reading and can be connected to an existing fire detection circuit or a fire indicating panel TPS 01PV is a special design version of TPS 01 containing an intrinsically safe interface and designed for use in hazardous areas TPS
6. delay s delay s delay s C TPS72 sos s m s TPS110 6 5 Electrical parameters An electrical diagram of the device is showed in Figure 6 ae Output Figure 6 Electrical diagram for TPS The device generates an electric impulse with amplitude of 3 5 V DC at the circuit resistance of 1 0 Ohm The duration of the electric impulse is not less than 1 millisecond for the amplitude of not less than 3 0 V DC The device can activate the following types of electrical initiators MB 2H 3A 1 PP 9 YGP 10 and similar 7 LIMITATIONS The design and application limitations for TPS devices are as follows 1 Volume protected by one device shall not exceed 18 m 2 The dimensions of a protected area shall not exceed e Height 3 0 meters e Width 2 4 meters e Length 2 5 meters The device should be located in the middle of the protected area at 100 150 mm below the ceiling The device is capable of sustaining vibration from 0 5 to 200 Hertz with acceleration of 4g The device is capable of sustaining impacts of up to 4g force of 2 to 50 milliseconds duration The device is suitable for application in hazardous areas of 2ExellT6 category The TPSPV device is an intrinsically safe device and suitable for use in hazardous areas of POExial category N OI A O 8 Maximum relative humidity 98 no condensation 8 INSTALLATION 8 WIRING The installation and wiring requirements for TPS 01 devices are as f
7. loy 8 safety pin 9 bronze nose piece 10 bronze rod 11 frame of reel 12 electromagnetic coil 13 diode The spring moves a cylindrical shape magnet 4 which is mounted on the rod 10 through an induction coil 12 The induction coil generates an electric impulse The impulse is transmitted to the electrical terminals 2 and further to the aerosol or powder fire extinguishers 4 3 Manual Operation A schematic of TPSM for manual operation is shown in Figure 2 In the manually operated TPS a special ring 5 is used instead of the heat sensitive element used in automatically operated models In case of fire a split pin 6 is removed from the device by manually pulling the ring 5 This action releases a spring loaded pin 9 Further sequence of events is identical to that for automatically operated T start 5 DE z f x Figure 2 Schematic of TPS 01 M manual operation 1 base 2 electric terminals 3 RF amp EMI shielded protective cover 4 magnet 5 pull ring 6 split pin 7 bronze nose piece 8 compression spring 9 bronze rod 10 housing made from a high temperature plastic 11 frame of reel 12 electromagnetic coil 13 diode 5 APPLICATION amp DESIGN Depending on the intended use TPS 01 device comes in three various design versions 5 1 Use in harsh environments For applications in harsh environments the TPS 01 can be installed with a special protective cup as shown in Figure 3
8. o any hot work being carried out 10 SERVICE LIFE amp MAINTENANCE 1 The TPS device is maintenance free The reliability of the device is not less than 50 000 hours under normal ambient conditions The service life of the device is 10 years 2 f damaged or exposed to the fire the device shall not be re used 3 Should the heat sensitive element be damaged the device shall not be used 4 Should the device be set off by an accident it shall be returned back to the supplier or the manufacturer It shall not be re used as the heat sensitive element might have been damaged or overheated 11 PACKAGING 1 The devices are placed in a cardboard box There are 10 devices per box 2 Inside the box the devices are placed in rows with a carton packaging material filling the space between the devices 3 A packaging list a user guide and manual are enclosed in a plastic envelope and placed onto the top row one envelope per every ten devices 4 The following labels shall be attached to each cardboard box Fragile Keep in dry place Do not drop Delicate equipment 12 DISCLAIMER This manual is for use by trained and authorized personnel only The document is accurate at time of issue however is subject to changes to its content from time to time 13 WARRANTY The manufacture claims that TPS 01 have undergone a quality control and have no defects Warranty applies for two years from the date of purchase This limited warranty does not co
9. ollows 1 One circuit shall have not more than 10 devices 2 The length of the cable between two devices in a loop shall not exceed 3 meters 3 The devices shall be connected in parallel Normal polarity of to shall be observed 4 The device can be used in high density electromagnetic and high frequency energy zones 5 Activation cables shall be fire resistant with copper conductors A cross section area of each conductor should not be less than 1 mm or 0 5 mm for a multiple core cable 6 If run through a high frequency energy zone such as a two way radio a sonar etc the cable should be screened 7 lf run through the electric magnetic fields of high density such as high voltage transformers in power substations or cable tunnels the cable should be enclosed in a steel conduit 8 Cable screen and steel conduit shall be grounded in accordance with the standard requirements 9 If there is a likelihood of any mechanical damage the cable should be enclosed into a plastic or metal conduit 9 SAFETY REQUIREMENTS The safety requirements for the TPS device are as follows 1 The device shall be installed and maintained in accordance with its design requirements and technical specifications 2 Only authorized personnel can install re set and service the device 3 The device shall only be used as intended for detection of fire and activation of a fire suppression system 4 The attached safety pin shall be in its
10. ver any TPS 01 device that has been damaged or rendered defective as a result of an accident misuse or abuse or serviced by anyone other than authorized service person or by using the parts that are not manufactured or sold specifically for this device or any modification done without written permission of the manufacturer Appendix 1 Multiple connection of TPS 01 with Junctions boxes showing on schematic diagram below In case of axillaries equipment to be shut down simultaneously with activation of extinguishing system one out of two schematic to be chosen For normally open contacts parallel connection is in use For normally close contacts connection in series should be chosen see diagrams below Up to 10 the TPS 01 may be connected to one loop To fire modules To fire indication panel