Home
Fluke Reliable Power Meters
Contents
1. switchroom Phase A Demand Mar 19 1996 04 57 45 143 KAH TWN 03209 Mar 19 1996 2163 mesu DiS Mar 19 1996 With 1652 option you can track demand using averaging intervals from 5 minutes to 1 hour Databank Service Entrance Phase B Current Harmonics Oct 13 1994 21 14 52 K 25 10 1S a 2 v 5 a i5 b 8 5 60 With 1653 option you can display harmonics up to the 63rd as a spectrum or table Power Lab 120 PC outlet Phase A Transition Voltage Event 1090 Sep 04 1994 00 50 46 937 1 kV 26 667 milliseconds div With the 1658 High speed Power Quality Option you can capture and view transients as short as 500 ns Power Quality e Logging RMS voltage and RMS current on all channels All Power Recorders e Phasor diagrams e Frequency trends e Real time oscilloscope display of voltage and current on all channels e Watts and demand trends e KWH individual phases and total 1652 Power Consumption Option e VA and VAR trends e Power Factor trends true and displacement e Oscilloscope display of power meters for each phase e Voltage and current THD trends e Voltage and current imbalance 1653 Harmonics and Flicker Option e Harmonic spectrum phase magnitude to 63rd harmonic e Tracking of individual harmonics e Flicker e Voltage waveshape faults as short as 130 ps duration 1000 V peak 1651 Power Quality Option e Voltage sags swells e Simulations current cor
2. 0 5 V over entire range 14 bits 90 millivolts 0 5 0 1 of probe range probe uncertainty 100 mV 600 Vrms 14 bits 90 millivolts 1000 V peak impulse Voltage neutral 10 mV 70 Vrms 100 V peak Nominal fundamental frequency 50 60 Hz 0 1 Hz as Voltage and current sampling 128 samples per cycle on 50 60 Hz Voltage and current sampling rate 6 4 7 7 kS s depending upon line frequency Voltage and current rms measurements Processed for every full cycle Power Measurements W VA VAR PF dPF processed for very full cycle Impulse measurements Standard speed unit with option 1651 6 4 7 7 kS s depending upon line frequency Impulse Voltage 200 1000 V peak 10 bits 12 volts 5 36V over entire range Impulse measurements High speed unit sampling rate Sampling rate 2mm o o S O 5 36V over entire range Impulse Voltage 200 6400 V peak 10 bits 12 volts Note Option 1658 adds high speed waveform capture in addition to high speed peak detect Event memory 6 000 simultaneous voltage and current events 96 000 with option 1662 Communication 10 base T Ethernet RJ 45 connector also available with Parallel interface Optional TC PIP Stack enables communication via Internet Power Recorder Reliable Power Meters 3 Electrical safety 600 V CAT III Operating voltages 85 264 VAC 47 440 Hz 10 15 V DC with 4250 or 4255 optional cable Power consumption 40 watts Batteries NiCd
3. FLUKE Power Quality Reliable Power Meters Power Recorder Full Disclosure monitoring for the most comprehensive power quality studies Sp nee meee phone SOCKS pore eS ize yy 14 bit 7 8 kHz A to D converter supplies data for RMS and FFT processing DSP performs FFT calculations in 10 ps L gt D S P sample amp hold Voltage input attenuator lt 4 kHz l ni 4MB cache impulse y logic RMS and transient data are synchronized in cache memory and stored in database on hard drive Optional transient capture system uses a 10 bit 2 MS s A to D converter to capture transients up to 6400V and as fast as 500ns Power Recorder Architecture Technical Data Every measurement every event on every cycle all the time without thresholds Full Disclosure Technology is part of all Fluke and RPM three phase power quality tools It makes the power recorder a unique professional instrument that increases your ability to maintain and troubleshoot your plant s power quality Full Disclosure Technology uses patented sampling hardware and algorithms to record everything your loads see e The sampling system processes every cycle on all channels recording min max avg values and looking for sags swells or transients e The system can store 6000 events up to 96 000 with Multisession Option You can see everything from sub cycle events to long term
4. battery recharges automatically while line power is applied Power the instrument for 5 minutes after power is removed and allows controlled shutdown of monitor Monitoring resumes after power is restored Mechanical Available enclosures Standard enclosure Hostile environment enclosure size 8 5 x 12 x 3 21 25 cm x 30 cm x 7 5 cm Weight 13 lbs 6 Kg Operating temperature O 50 C 32 122 F 90 RH non condensing Standards UL3111 IEC 868 Included accessories All units include user manual line cord 5 voltage leads and 5 alligator clips Units with Ethernet interface include a 10 ft ethernet cable socket socket adapter and 2 ft cross over cable Parallel units include a parallel cable Power Quality Configuration 1650 56 1650 50 Standard _ Ethernet_ Standard 1650 15 Hostile Ethernet High speed 1650 51 Hostile Ethernet__ Standard ae 1650 10 Parallel High speed 1650 11 Parallel Standard Accessories Power Analysis Software with User Manual Professional Report Writer Software requires 5000 RPM Scenario Analysis Software Master Polling And Annunciation Software requires 5000 RPM Sub Polling And Annunciation Software requires 5000 RPM and 5500 RPM 24 inch 1000 Amp Flexi Ct 48 inch 1000 Amp Flexi Ct Bus bar Voltage F Type Probe Set Of 5 Plunger Type Voltage Probe 5 Syringe Action Reliable Power M
5. ents Power Recorders are configurable so you can expand their capabilities to meet your growing needs Use Report Writer software on your PC to automatically create power quality surveys with text and graphics Polling and Alarms software allows you to configure and monitor multiple instruments retrieve data periodically and set up alarms to notify operators of events Building 4 Panel 14p3 Phase A Voltage Waveform May 03 1994 11 48 47 13 333 milliseconds div 118 43 RMS CF 1 35 Real time waveform displays show up to 9 channels 4 voltage 5 current including ground and neutral current Building 4 Panel 14p3 Fundamental Phasor Vectors May 03 1994 11 48 47 EEE Real time voltage and current meters feature phasor diagrams to help with correct hookup Databank Service Entrance Phase B RMS Yoltage Nov 04 1994 19 51 24 K 1 6 1951 Nou D 199 v 18 40 0ct0 194 301 dae t Trend windows give you an overview of power parameters fast Measurements are processed for every cycle Min max and average values are plotted so you can quickly see the worst case 2 Reliable Power Meters Power Recorder FLUKE Power Quality Building 4 Panel 14p3 Phase B Power Vectors May 03 1994 11 43 47 ental Power Values tor 0 93 Lag Distortion X 10 With 1652 option real time meter and vector diagram displays Watts VA VAR PF and dPF Routers hv
6. eters A Fluke Company PO Box 9090 Everett WA USA 98206 Fluke Europe B V PO Box 1186 5602 BD Eindhoven The Netherlands For more information call In the U S A 800 443 5853 or Fax 425 446 5116 In Europe M East Africa 31 40 2 675 200 or Fax 31 40 2 675 222 In Canada 800 36 FLUKE or Fax 905 890 6866 From other countries 1 425 446 5500 or Fax 1 425 446 5116 Web access http www reliablemeters com 2003 Reliable Power Meters A Fluke Corporation All rights reserved Printed in U S A 7 2003 2095638 A ENG N Rev A
7. outages with clear detail e Records power parameters rms voltage rms current harmonics flicker and monitors for power quality events on all channels simultaneously without hav ing to reconfigure e No need to set thresholds You won t be disappointed by missed events or a memory full of noise e Because there are no thresholds to set Full Disclosure technology system records any changes in measure ments even the ones that are almost out of tolerance Event Tolerance Summary CBEMA Instruments with manually programmed thresholds create a large dead zone where no information is captured Full disclosure monitors have low adaptive thresholds and capture all the data Full Disclosure technology cap tures thousands of voltage events and related cur rent information without having to set thresholds 4 4 10us 100us ims 833ms 1s Databank Service Entrance CBEMA Phase B Event Tolerance Summary November 10 1994 264 events Full Disclosure technology lets you plot events on any power tolerance curve CBEMA ITIC and ANSI curves are included or create your own 10 4s 100 ts ims 833ms The choice of the PQ professional 5 Current channels allow you to monitor neutral and ground current in addition to phases Extruded metal enclosure is designed to handle a lifetime of use Ethernet interface makes downloads fast and easy Multi session option multiplies event capture capability to 96 000 ev
8. responding to correlated with voltage events e Power tolerance curves e Voltage and current waveshape faults 1658 High Speed Power Quality Option e Voltage and current sags swells e Power tolerance curves e Transients as short as 500 ns duration 6400 V peak with peak detect or detailed waveform graphs 1662 Multi Session Option e Allows a recorder to store up to 16 measurement sessions p e Each session can consist of up to 6000 events increasing the event storage to 96 000 1663 TCP IP Option e Enables Ethernet equipped instruments to communicate via Internet Software completes the system There are two software packages available for the Power Recorder Both packages handle seamless communication with the Power Recorder graphical display of power system parameters and data management tools The Power Analyzer System software package e Offers optional Report Writer software e Offers Alarming and Polling Option Scenario Software e Allows plotting multiple measurement sessions on one timescale e Includes facilities for comparing trends from multiple databases e Calculates a Power Quality Index a single figure of merit that characterizes the overall performance of a power system The Power Quality Index allows you to trend system performance over time and determine whether a system is improving or degrading Specifications Number of channels 9 4 voltage 5 current Voltage phases 1 5
Download Pdf Manuals
Related Search
Related Contents
EZPOS 70D_EZPPC70D Service Manual 20090330 取 扱 説 明 書 Manuale dei Servomotori Asincroni HDP ad DOMESTIC UPRIGHT VACUUM CLEANER OWNERS Istruzioni per l`uso 021090 Manual Neutron Crosstrainer 8kg NL-UK-FR 周辺機器/インバータをお使いになるお客様へ/標準価格 Projet de Charte du parc national de La Réunion Copyright © All rights reserved.