1. Cold Start amp Clear Displays Cold Start amp Clear FSTs Cold Start amp Clear History Cold Start amp Clear ALL 2 Update Y DK X Cancel Apply Figure 19 Flags screen 2 Click Save Configuration A verification message displays ROCLINK 800 2 Perform Flash Memory Save Configuration Figure 20 Perform screen Rev Nov 12 31 LineGuard 2300 Program User Manual 3 Click Yes to begin the save process The Flash Write Status field on the Flags screen displays In Progress The following message displays ROCLINK 800 i Flash Memory Save Configuration COMPLETED Flash Configuration bytes free 36855 Figure 21 Save Confirmation 4 Click OK The Flash Write Status field on the Flags screen displays Completed 5 Click Update on the Flags screen This completes the process of saving your new configuration Note For archive purposes you should also save this configuration to your PC s hard drive or a removable media such as a diskette or a flash drive using the File gt Save Configuration option on the ROCLINK 800 menu bar 32 Rev Nov 12 LineGuard 2300 Program User Manual Chapter 4 Reference Material This section provides tables of information on the operation of the program and the user defined point types used by the LineGuard program Point Type 22 LineGuard Log Configuration Point Type 23 LineGuard Control Rev Nov
2. From the Directory Tree select User Program gt LineGuard User Prgm 2 Double click 22 LineGuard Valve Control The LineGuard Valve Control screen displays vam ROCLINK 800 LineGuard Valve Control FB107 File Edit View ROC Configure Meter Utilities Tools Window Help OSE IDE G TA ANS hh ee ORR wl IK Event Control Transmitter Fail Voltage Check Valve Closing Point Definition Status Close Dutput Undefined Ed Not Energized Close Limit Switch Undefined i Inactive Manual Close Flag Force Close Close Duration 30 Seconds y Current Close Time 0 Seconds Valve Opening Point Definition Status Open output Undefined E Not Energized Dpen Limit Switch Undefined Bl Inactive Manual Open Flag Force Open Open Duration 30 Seconds v Current Open Time 0 Seconds Print Save As Auto Scan Update Close Appl Figure 15 LineGuard Valve Control 3 Review and change as necessary the values in the following fields Field Description Close Output Click to define the discrete output point used to close the control valve Close Limit Switch Click to define the discrete input point monitoring status of the valve close state During valve closure if this field is defined and the status becomes active the close output will be de activated Rev Nov 12 23 LineGuard 2300 Program User Manual Field Description Manual Close Flag Close Duration Current Close Ti
3. Rev Nov 12 39 LineGuard 2300 Program User Manual Point Type 23 LineGuard Valve Control Parm 17 Event Duration Period R W Name 18 Active Event Time R O System or Data Access User Update Type Program Length Range Default User UINT16 2 0 5 10 15 30 30 60 120 180 240 300 600 UINT16 2 0 gt 65535 0 Version 1 00 1200 1800 1 00 1800 seconds Description of functionality and meaning of values Time in seconds a major alarm must be active before valve closure is initiated Valid duration times are 0 5 10 15 30 60 120 180 240 300 600 1200 and Time in seconds that a major alarm has been active Once this value becomes greater than the event duration period l l is initiated 19 Transmitter Power Output R W Point Def 20 Transmitter Failed Alarm R W Output Point Def User TLP 3 NA 0 0 0 User TLP 3 NA 0 0 0 1 00 Identifies discrete output used to cycle power to the input pressure transmitter This output is used to cycle power to a failed transmitter in an attempt to restore normal transmitter operation Identifies discrete output to be used as an alarm indication of a failed transmitter When defined this output is activated h failed t itter is detected 21 Transmitter Fail Low R W Setpoint 22 Transmitter Fail High R W Setpoint 23 Transmitter Fail Reset R W Sequence Enable User Float 4 Any valid 0 0 float User Fl
4. This read only field displays the current Rate of Pressure Drop RoD The RoD is the average pressure one minute ago minus the current average pressure in units of pressure minute This value is updated every five seconds This read only field displays the last calculated average of Rate of Pressure Drop RoD over the last average sample period This value is used to determine the state of major and minor RoD alarms This value is updated every five seconds This read only field displays the current setting Enabled Disabled threshold SetPoint and current state Status of the Major Low Alarm An average pressure below the indicated threshold activates an alarm initiates a major log and starts valve control if the Major Low Alarm is Enabled If disabled this alarm is ignored This read only field displays the current setting Enabled Disabled threshold SetPoint and current state Status of the Major High Alarm An average pressure above the indicated threshold activates an alarm initiates a major log and starts valve control if the Major High Alarm is enabled If disabled this alarm is ignored This read only field displays the current setting Enabled Disabled threshold SetPoint and current state Status of the Major RoD Alarm An average RoD above the indicated threshold activates an alarm initiates a major log and starts valve control if the Major RoD Alarm is enabled If disabled this alarm is ignore
5. 1 Basic Program Operation Pipeline Pressure Monitoring Rate of Drop RoD Pressure Calculation Data Logging Minor Data Logs This section provides a brief description of the operation of the LineGuard user program The user program monitors pipeline pressure calculates the Rate of Pressure Drop RoD maintains minor and major logs and performs valve control The static pipeline pressure is sampled every 5 seconds and stored as Live Pressure This value is averaged over a configurable period of time called the Average Sample Period and is stored as Average Pressure The Average Sample Period is user configurable from 5 seconds to 60 seconds in 5 second intervals The default Average Sample Period is 60 seconds or 12 samples The Average Pressure is averaged over a moving time window and the time window is defined by the Average Sample Period The Average Pressure is updated every 5 seconds The Average Pressure is used to detect Major and Minor line break conditions The Average Pressure is archived in both Major and Minor data logs The LineGuard device is capable of reacting to a drop in pipeline pressure The current Rate of Pressure Drop RoD is calculated as the change in average pressure over the last minute and is available every sample cycle 5 seconds in units of pressure minutes The current RoD is rolled over to an Average RoD based on the Average Sample Period The Average Sample Period for RoD calculations is equal t
6. 12 33 LineGuard 2300 Program User Manual 4 1 Point Type 22 LineGuard Pressure Log Configuration Point type 22 contains the parameters for configuring and monitoring the LineGuard program The program maintains one logical point of this point type Point Type 22 LineGuard Pressure Log Configuration Parm Name KRG System or Data Length Range Default Version Description of functionality and meaning of User Update Type values 0 Line Pressure Input R W User TLP 3 NA 0 0 0 1 00 Source of pressure value Def 1 Pressure Units R W User UINT8 1 0 1 2 3 0 1 00 Units of pressure reading 0 PSIG 1 PSIA 2 kPaG 3 kPaA 2 Average Sample R W User UINT8 1 5 10 15 25 60 1 00 Period in seconds over which input pressure Period 30 35 40 and Rate of Drop are averaged Valid values 45 50 55 60 include 5 10 15 20 25 30 35 40 45 50 55 Live Pressure R O System Float 4 Any valid float 0 0 1 00 Current reading from pressure input 4 Average Pressure R O System Float 4 Any valid float 0 0 1 00 Average of live pressure over the last average sample period 5 Current Rate of R O System Float 4 Any valid float 0 0 1 00 Calculated as average pressure one minute ago Drop RoD minus current average pressure in units of 6 Average RoD R O System Float 4 Any valid float 0 0 1 00 Average of current RoD over the last average sample period 7 Major Alarm Low R W User UINT8 1 0 1 0 1 00 Major log low alarm enable Enabl DEN i DE 0 Do n
7. 600 1200 and 1800 seconds Active Event Time Sets in seconds the length of time in which a major alarm has been active Once this value becomes greater than the event duration period valve closure is initiated Rev Nov 12 25 LineGuard 2300 Program User Manual Field Description Low Alarm Autoclosure High Alarm Autoclosure RoD Alarm Autoclosure Sets the Low Alarm Autoclosure as on Enabled or off Disabled which allows automatic closure of the valve when the major log low alarm has been active for the event duration period Sets the High Alarm Autoclosure as on Enabled or off Disabled which allows automatic closure of the valve when the major log high alarm has been active for the event duration period Sets the RoD Alarm Autoclosure as on Enabled or off Disabled which allows automatic closure of the valve when the major log RoD alarm has been active for the event duration period 3 Click Apply to save your changes 4 Click Close to return to the ROCLINK 800 screen Proceed to Section 3 2 3 to configure the Transmitter Fail tab 26 Rev Nov 12 LineGuard 2300 Program User Manual 3 2 3 LineGuard Valve Control Transmitter Fail tab Use this screen to configure the actions taken by the program if a failed transmitter is encountered including the length of time the condition must be present to trigger an action and the high and low setpoints for failed transmitter alarms To acce
8. Alarm Major High Alarm Minor Low Alarm Click to select a source to provide the pressure value used in the calculation of average pressure and average RoD Sets the pressure units of measurement used by the program Valid values are PSIG PSIA kPaG and kPaA Sets in seconds the period of time at which pressure and RoD values are archived in the major log Valid values are 5 10 15 and 30 seconds Sets in seconds the period of time at which pressure and RoD values are archived in the minor log Valid values are 30 60 120 180 240 and 300 seconds Sets in seconds the period of time at which input pressure and RoD are averaged Valid values 5 10 15 20 25 30 35 40 45 50 55 and 60 seconds Sets the Major Low Alarm as Enabled or Disabled and defines the threshold SetPoint for triggering an alarm An average pressure below the indicated threshold activates an alarm initiates a major log and starts valve control if the Major Low Alarm is enabled If disabled this alarm is ignored Sets the Major High Alarm as Enabled or Disabled and defines the threshold SetPoint for triggering an alarm An average pressure above the indicated threshold activates an alarm initiates a major log and starts valve control if the Major High Alarm is enabled If disabled this alarm is ignored Sets the Major RoD Alarm as Enabled or Disabled and defines the threshold SetPoint for triggering an alarm
9. Status Log Alarm Setup tab Use this screen to configure the pressure input and the pressure units used by the program You also use this screen to configure alarm parameters including alarm settings alarm setpoints alarm log periods and the average sample period To access this screen 1 Select the Log Alarm Setup tab on the LineGuard Status screen tam ROCLINK 800 LineGuard Status FB107 T File Edit View ROC Configure Meter Utilities Tools Window Help Dedi Paisia go HE oe AM AN 2 LineGuard Status Pressure Input Pt Def Undefined ES Major Log Period Minor Log Period 30 Seconds we 30 Seconds y Major Alarm Setup Major Low Alarm Disabled 2 Major High Alarm Disabled x Major RoD Alarm Disabled nd Minor Alarm Setup Minor Low Alarm Disabled y Minor High Alarm Disabled MA Minor RoD Alarm Disabled gt SetPoint SetPoint SetPoint SetPoint SetPoint SetPoint r Pressure Units PSIG Average Sample Period 60 Seconds 0 0 PSIG 0 0 PSIG 0 0 PSI Min 0 0 PSIG 0 0 PSIG 0 0 PSI Min Print Save s Auto Scan Update Close Ar a Figure 12 LineGuard Status Log Alarm Setup tab 18 Rev Nov 12 LineGuard 2300 Program User Manual 2 Complete the screen fields based on your organization s requirements Field Description Pressure Input Pt Def Pressure Units Major Log Period Minor Log Period Average Sample Period Major Low
10. three sections The upper portion Licenses on Device shows any software licenses installed on the FB107 The middle portion Licenses on Key shows software licenses on the license key The lower portion of the screen License Key Event Log provides a rolling log of the last eight events related to this license key 3 Select the key based license you want to transfer to the FB107 LineGuard 2300 as shown in Figure 1 4 Click Move to Device ROCLINK moves the license from the key to the FB107 and updates the screen Transfer Licenses Between a DEVICE and a KEY Licenses on DEVICE Vendor Name App Code Version Quantity License Source Expiration Time Created LineGuard 2300 RAS 31529 1 00 0 1 No Expiration 11 14 2012 10 30 47 AM Connect to KEY Move to DEVICE Add License Remove Licenses on KEY __ Time Created Application Name Vendor ID endor Name App Code Version Expiration Quantity License Key Event Log pplicatio 11 14 2012 10 30 48 ADD ADM 31529 LineGuard 2300 Export Events Figure 2 License Installed Note An FB107 can hold up to six different licenses although you can install only one instance of each license on the FB107 When you click Move to Device ROCLINK 800 moves only one instance of the license onto the FB107 and automatically decreases the license quantity on the USB key by one 5 Verify the license name displays in the Licenses on Device section of the screen Proceed to Sectio
11. 00 Program User Manual 3 24 LineGuard Valve Control Voltage Check tab Use this screen to configure the actions taken by the program if the unit input voltage is outside of user configured alarm limits To access this screen 1 Select the Voltage Check tab on the LineGuard Valve Control screen vam ROCLINK 800 LineGuard Valve Control FB107 File Edit View ROC Configure Meter Utilities Tools Window Help Dea P SME Ve Nw ME SONER LineGuard Valve Control Event Control Transmitter Fail Voltage Check Voltage Check Enable Input Voltage Alarm Status Disabled v Good Normal Operation Input Voltage Alarm Setup Live Input Voltage 3 291667 Low Alarm Limit 8 0 High Alarm Limit 25 0 Print Save s Auto Scan 2 Update Close 1 Apply Fr Ei ERNE 2 09PM Figure 18 LineGuard Valve Control Voltage Check Tab 2 Review and change as necessary the values in the following fields Field Description Voltage Check Enable Sets the voltage check functionality to Enabled or Disabled If Enabled and input voltage to the unit is outside of the user defined limits see below the program will suspend the line break detection algorithm No action is taken when set to Disabled and the input voltage is outside of limits Input Voltage Alarm Status This read only field shows the current status of the input voltage check Valid values are Good Normal Operation __Low Voltage Control Suspended _
12. 72 T 1 281 879 2699 F 1 281 988 4445 www EmersonProcess com Remote Middle East Africa Emerson Process Management Remote Automation Solutions Emerson FZE P O Box 17033 Jebel Ali Free Zone South 2 Dubai U A E T 971 4 8118100 F 971 4 8865465 www EmersonProcess com Remote Asia Pacific Emerson Process Management Remote Automation Solutions 1 Pandan Crescent Singapore 128461 T 65 6777 8211 F 65 6777 0947 www EmersonProcess com Remote Remote Automation Solutions 2008 2012 Remote Automation Solutions a business unit of Emerson Process Management All rights reserved Remote Automation Solutions a business unit of Emerson Process Management shall not be liable for technical or editorial errors in this manual or omissions from this manual REMOTE AUTOMATION SOLUTIONS MAKES NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE WITH RESPECT TO THIS MANUAL AND IN NO EVENT SHALL REMOTE AUTOMATION SOLUTIONS BE LIABLE FOR ANY INCIDENTAL PUNITIVE SPECIAL OR CONSEQUENTIAL DAMAGES INCLUDING BUT NOT LIMITED TO LOSS OF PRODUCTION LOSS OF PROFITS LOSS OF REVENUE OR USE AND COSTS INCURRED INCLUDING WITHOUT LIMITATION FOR CAPITAL FUEL AND POWER AND CLAIMS OF THIRD PARTIES Bristol Inc Bristol Canada BBI SA de CV and Emerson Process Management Ltd Remote Automation Solutions UK are wholly owned subsidiaries of Emerson Electric Co doing busines
13. Alarm RoD Status Major Alarm Low Setpoint 1 0 1 4 Any valid float 0 0 Minor RoD alarm status O Not active 1 Active Major RoD alarm status O Not active 1 Active Major low alarm setpoint An average pressure below this value will active a major low alarm if bled 20 21 Minor Alarm Low Setpoint Minor Alarm High Setpoint R W R W User User Float Float 4 Any valid float 4 Any valid float 0 0 0 0 Minor low alarm setpoint An average pressure below this value will active a minor low alarm if enabled Minor high alarm setpoint An average pressure above this value will active a minor high alarm if enabled Rev Nov 12 35 LineGuard 2300 Program User Manual Point Type 22 LineGuard Pressure Log Configuration Parm Name ccess System or Data Length Range Default Version Description of functionality and meaning of User Update Type values 22 Major Alarm High R W User Float 4 Any valid float 0 0 1 00 Major high alarm setpoint An average pressure Setpoint above this value will active a major high alarm if enabled 23 Minor Alarm RoD R W User Float 4 Any valid float 0 0 1 00 Minor RoD alarm setpoint An average RoD Setpoint above this value will active a minor RoD alarm if enabled 24 Major Alarm RoD R W User Float 4 Any valid float 0 0 1 00 Major RoD alarm setpoint An average RoD Setpoint above this value will active a major RoD alarm if enabled 25 Mino
14. An average RoD above the indicated threshold activates an alarm initiates a major log and starts valve control if the Major RoD Alarm is enabled If disabled this alarm is ignored Sets the Minor Low Alarm as Enabled or Disabled and defines the threshold SetPoint for triggering an alarm An average pressure below the indicated threshold activates an alarm and initiates a minor log if the Minor Low Alarm is enabled If disabled this alarm is ignored Sets the Minor High Alarm as Enabled or Disabled and defines the threshold SetPoint Tor triggering an alarm An average pressure Rev Nov 12 19 LineGuard 2300 Program User Manual Field Description a Na EEE above the indicated threshold activates an alarm and initiates a minor log if the Minor High Alarm is enabled If disabled this alarm is ignored Sets the Minor RoD Alarm as Enabled or Disabled and defines the threshold Setpoint for triggering an alarm An average RoD above the indicated threshold activates an alarm and initiates a minor log if the Minor RoD Alarm is enabled If disabled this alarm is ignored 3 Click Apply to save your changes 4 Click Close to return to the ROCLINK 800 screen Proceed to Section 3 1 3 to access the RoD Values screen 20 Rev Nov 12 LineGuard 2300 Program User Manual LineGuard Status RoD Values tab Use this screen to view the three highest RoD values recorded since the last system restart
15. CLINK 800 Download Confirmation 9 Click OK The User Program Administrator screen displays see Figure 8 Note that The User Programs Installed in Device frame identifies the installed program s The Status field indicates that the program is running Rev Nov 12 11 LineGuard 2300 Program User Manual User Program Administrator User Programs Installed in Device 1 LineGuard User Pram Name LineGuard User Prgm No Program No Program Version Rev 1 10 Library Version Rev 1 No Program No Program Created 11 09 2012 10 53 31 DRAM Used 16384 No Program CRC 0xC99D FLASH Used 16338 uote Entry Pt Ox540000 Start Stop Displays 21 22 I All Option Status Running Download User Program File F Pragram FilesyLineguard 1 bin Browse Name LineGuard User Pram Download amp Start Download Version Rev 1 10 Created 11 9 2012 10 53 31 AM CRC OxC99D Size 16338 Figure 8 User Program Administrator Note If you install the program before you install the license key the Status field reads License Not Found Install the license key to change the status of the program 10 Click Close The ROCLINK 800 screen displays and the download is complete Proceed to Chapter 3 Configuration 12 Rev Nov 12 LineGuard 2300 Program User Manual Chapter 3 Configuration After you have loaded the LineGuard user program on the FB107 you co
16. Form A6251 Part Number D301346X012 November 2012 LineGuard 2300 Program User Manual FloBoss 107 vem ROCLINK 800 LineGuard Status FB107 TT Eile Edit View ROC Configure Meter Utilities Tools Window Help De Bd Qe HEF We Mt Se 4 On AA LineGuard Status Log Alarm Setup RoD Values Program Status Running No error Average Sample Period Transmitter Status Good Normal Operation 0 0 PSIG 0 0 PSI Min Live Pressure Average Pressure Current RoD Average RoD Enable Disable SetPoint Status Major Low Alarm Disabled 0 0 Clear Major Log Period Major High Alarm Disabled 0 0 Clear Major Log State Major RoD Alarm Disabled 0 0 Clear Number Major Logs Minor Low Alarm Disabled 0 0 Clear Minor Log Period Minor High Alarm Disabled 0 0 Clear Minor Log State Minor RoD Alarm Disabled 0 0 Clear Number Minor Logs Minor Log Index Event Duration 30 Seconds Active Event Time 0 Seconds Reset Clear Logs 0 0 PSIG 60 Seconds 0 0 PSI Min 30 Seconds Clear 0 30 Seconds Clear 0 0 Clear Logs Print Save As Auto Scan 2 Update Close Apply Remote Automation Solutions 4 EMERSON Process Management LineGuard 2300 Program User Manual Revision Tracking Sheet November 2012 This manual may be revised periodically to incorporate new or updated information The revision date of each page appears at the bottom of the page opposite the page number A change in revi
17. LineGuard Valve Control screen displays vem ROCLINK 800 LineGuard Valve Control FB107 File Edit View ROC Configure Meter Utilities Tools Window Help Osa IL BEIS r LT AT VE SZ ORR L P Event Control Transmitter Fail Voltage Check Valve Closing Point Definition Status Undefined Bl Undefined m Close Output Not Energized Close Limit Switch Inactive Manual Close Flag Close Duration Current Close Time Force Close 30 Seconds y 0 Seconds Valve Opening Open output Open Limit Switch Manual Open Flag Open Duration Current Open Time Point Definition Undefined 3 Undefined El Force Open 30 Seconds y 0 Seconds Status Not Energized Inactive Print Save As Auto Scan 2 Update Close Apply Figure 14 LineGuard Valve Control Note The LineGuard Valve Control screen like the other LineGuard Status screen has a tab format Sections 3 2 1 to 3 2 4 discuss the requirements for each tab on the LineGuard Valve Control screen 22 Rev Nov 12 LineGuard 2300 Program User Manual 3 2 1 LineGuard Valve Control LineGuard Valve Control tab Use this screen which displays when you access the LineGuard Valve Control screen to define discrete outputs used by the program to open and close valves You also use the screen to configure valve open and close durations and to manually force valves to open or close To access this screen 1
18. Minor Log Index 0 Event Duration 30 Seconds Active Event Time 0 Seconds Reset Clear Logs Clear Logs Print Save As Auto Scan Update Close dr v Figure 11 LineGuard Status LineGuard Status tab 1 Review the values in the following fields Field Description Program Status This read only field displays the current condition of the user program Valid values are Running No error Running Shutting down Not running No program loaded Not running Program not enabled Not running Library version error Not running No license found and Not running License expired Average Sample Period This read only field displays in seconds the period over which input pressure and Rate of Drop are averaged Valid values include 5 10 15 20 25 30 35 40 45 50 55 and 60 seconds Transmitter Status This read only field displays the current Rev Nov 12 15 LineGuard 2300 Program User Manual Field Description Live Pressure Average Pressure Current RoD Major Low Alarm Major High Alarm Major RoD Alarm Minor Low Alarm transmitter status Valid values are Good Normal Operation Failed Low Pressure and Failed High Pressure This read only field displays the current live value from pressure input This value is updated every five seconds This read only field displays the average pressure over the last average sample period This value is updated every five seconds
19. Progress Possible Failure Detected Failed Power Cycle Initiated Failed Waiting for Power Up Failed Warm Start In Progress Failed Transmitter Updates Suspended and Good Transmitter Recovered Fail Delay Period Sets in seconds the time delay after a transmitter fail is detected before the reset sequence is initiated Transmitter Fail Status This read only field shows the current status of the transmitter Valid values are Good Normal Operation Failed Low Pressure and Failed High Pressure Transmitter Low Setpoint Sets the value for the Transmitter Low Setpoint When the input pressure drops below this value the transmitter is Transmitter High Setpoint Sets the value for the Transmitter High Setpoint When the input pressure rises above this value the transmitter is considered failed Transmitter Power Contact Click to define a discrete output used to cycle power to the input pressure transmitter This output is used to cycle power to a failed transmitter in an attempt to restore normal transmitter operation Transmitter Alarm Contact Click to define a discrete output to be used as an alarm indication of a failed transmitter This output is activated when a failed transmitter is detected 3 Click Apply to save your changes 4 Click Close to return to the ROCLINK 800 screen Proceed to Section 3 2 4 to configure Voltage Check screen 28 Rev Nov 12 LineGuard 23
20. Rev 1 00 Boot Build Date Nov 17 2006 8 32 Integrity AAA A a Uninstall Auto Scan Update Apply ETT Figure 9 ROCLINK 800 Rev Nov 12 13 LineGuard 2300 Program User Manual 3 1 LineGuard Status Screen Use this screen to view the status and parameter settings of the LineGuard program and set the pressure inputs used by the program You also configure alarm parameters including alarm settings alarm setpoints alarm log periods and the average sample period To access this screen 1 From the Directory Tree select User Program gt LineGuard User Prgm 2 Double click Display 421 LineGuard Status The LineGuard Status screen displays tam ROCLINK 800 LineGuard Status FB107 T File Edit View ROC Configure Meter Utilities Tools Window Help Osa ENT IAN AMARO EE VE 1 Log Alarm Setup RoD Values Program Status Running No error Average Sample Period 60 Seconds Transmitter Status Good Normal Operation Live Pressure 0 0 PSIG Average Pressure 0 0 PSIG Current RoD 0 0 PSI Min Average RoD 0 0 PSI Min Enable Disable SetPoint Status Major Low Alarm Disabled 0 0 Clear Major Log Period 30 Seconds Major High Alarm Disabled 0 0 Clear Major Log State Clear Major RoD Alarm Disabled 0 0 Clear Number Major Logs 0 Minor Low Alarm Disabled 0 0 Clear Minor Log Period 30 Seconds Minor High Alarm Disabled 0 0 Clear Minor Log State Clear Minor RoD Alarm Disabled 0 0 Clear Number M
21. Service Pack 2 Windows XP with Service Pack 3 Windows Vista 32 bit or Windows 7 32 bit The sections in this manual provide information in a sequence appropriate for first time users Once you become familiar with the procedures and the software the manual becomes a reference tool This manual has the following major sections Chapter I Introduction Chapter 2 Installation Chapter 3 Configuration Chapter 4 Reference This manual assumes that you are familiar with the FB107 and its configuration For more information refer to the following manuals FloBoss 107 Flow Manager Instruction Manual Form A6206 ROCLINK 800 Configuration Software User Manual for FB107 Form A6217 1 2 Product Overview The LineGuard Electronic Linebreak Detection System is a self contained pipeline monitoring and line break detection device The device is intended to be installed at a pipeline valve site and is designated to provide data acquisition and supervisory control both locally and remotely of a single valve actuator The LineGuard product consists of standard FloBoss 107 Flow Manager hardware and firmware while a user program provides the LineGuard functionality The program is responsible for pressure monitoring data logging and valve control Custom user defined displays are available for configuring and monitoring the operation of the program Rev Nov 12 LineGuard 2300 Program User Manual 1 2
22. These values can be reset by selecting the Clear Logs button on the LineGuard status tab To access this screen 1 Select the RoD Values tab on the LineGuard Status Screen a ROCLINK 800 LineGuard Status FB107 Eile Edit View ROC Configure Meter Utilities Tools Window Help osa BSE ANM SONE oe LineGuard Status Log Alarm Setup i Highest RoD Values 00 00 2000 00 00 00 0 0 PSI Min 00 00 2000 00 00 00 0 0 PSI Min 00 00 2000 00 00 00 0 0 PSI Min Print Save s Auto Scan Update Close Figure 13 LineGuard Status RoD Values tab 2 Complete the screen fields based on your organization s requirements Field Description Highest RoD Values This read only set of fields displays the highest three RoD values recorded since the last system restart The values can be cleared by selecting the Clear Logs button on the LineGuard Status tab The time stamp data is in the format of DD MM YYYY HH MM SS The RoD values are in units of PSI minute or kPa minute 3 Click Close to return to the ROCLINK 800 screen Proceed to Section 3 2 to configure the Valve Control screen 21 LineGuard 2300 Program User Manual 3 2 LineGuard Valve Control Screen Use this screen to configure the parameters used by the program to control valve opening and closing To access this screen 1 From the Directory Tree select User Program gt LineGuard User Prgm 2 Double click 422 LineGuard Valve Control The
23. ___ Rev Nov 12 29 LineGuard 2300 Program User Manual Field Description High Voltage Control Suspended Waiting for Valve Closure to Complete Live Input Voltage This read only field shows the current input voltage supplied to the FloBoss 107 unit Low Alarm Limit Sets the value for the limit at which the input voltage is too low and the line break functionality suspended When the voltage check is enabled and the input voltage drops below this value the program will suspend detection of the line break software and auto closure algorithm High Alarm Limit Sets the value for the limit at which the input voltage is too high and the line break functionality suspended When the voltage check is enabled and the input voltage raises above this value the program will suspend detection of the line break software and auto closure algorithm 3 Click Apply to save your changes 4 Click Close to return to the ROCLINK 800 screen Proceed to Section 3 3 to save your configuration 30 Rev Nov 12 LineGuard 2300 Program User Manual 3 3 Saving the Configuration Whenever you modify or change the configuration it is a good practice to save the final configuration to memory To save the configuration 1 Select ROC gt Flags The Flags screen displays Advanced Restart Flash Memory Warm Start Save Configuration Clear Cold Start Cold Start amp Clear Alarms E vents pe
24. covered 8 Failed Transmitter Updates Suspended 9 Good Transmitter Recovered Delay in seconds after transmitter fail is detected before reset sequence is initiated Indicates current transmitter status 0 Good Normal Operation 1 Failed Low Pressure 2 Failed High Pressure This flag allows the user to enable the voltage check functionality 0 check disabled 1 check enabled When this flag is enabled and the input voltage is outside of the user defined limits the line break detection software and auto closure algorithm are suspended This parameter indicates current status of the voltage check function 0 Voltage is within limits or check is disabled 1 Voltage is low and control suspended 2 Voltage is high and control is suspended 3 Voltage is outside of alarm limits but waiting for valve closure already in progress to complete Rev Nov 12 41 LineGuard 2300 Program User Manual Headquarters Emerson Process Management Remote Automation Solutions 6005 Rogerdale Road Houston TX 77072 U S A T 1 281 879 2699 F 1 281 988 4445 www EmersonProcess com Remote Europe Emerson Process Management Remote Automation Solutions Emerson House Kirkhill Drive Kirkhill Industrial Estate Aberdeen UK AB21 OEU T 44 1224 215700 F 44 1224 215799 www EmersonProcess com Remote North American Latin America Emerson Process Management Remote Automation Solutions 6005 Rogerdale Road Houston TX USA 770
25. d This read only field displays the current setting Enabled Disabled threshold SetPoint and current state Status of the Minor Low Alarm An average pressure below the indicated threshold activates the alarm and a minor log is initiated If disabled this 16 Rev Nov 12 Field LineGuard 2300 Program User Manual Description Minor RoD Alarm E e eee da Major Log State Number Major Logs Minor Log Period Minor Log State Number Minor Logs Minor Log Index Event Duration Active Event Time alarm is ignored this alarm is ignored This read only field displays the current setting Enabled Disabled threshold SetPoint and current state Status of the Minor High Alarm An average pressure above the indicated threshold activates the alarm and a minor log is initiated If disabled This read only field displays the current setting Enabled Disabled threshold SetPoint and current state Status of the Minor RoD Alarm An average RoD above the indicated threshold activates the alarm and a minor log is initiated If disabled this alarm is ignored This read only field displays in seconds the period at which pressure and RoD values are placed in the major log Valid periods are 5 10 15 and 30 seconds This read only field displays the current state of the major log function Valid values are Not Logging Actively Logging and Log is Comp
26. f drop of pressure condition After auto closure has been initiated even a favorable pressure change will not de energize the Close Output and the valve will stroke to completion Any or all of these closure controls may be individually disabled 1f desired by setting the Auto closure for the alarm type to disabled If auto closure is disabled the program will still perform all other functions with the exception of Close Output activation Limit switch inputs may be configured for both the open and close operations During valve closure the program will monitor the Close Limit Switch status if configured and de activate the Close Output when the limit switch status becomes active If the close limit switch input is not defined then the close output will remain energized for the full close duration period During valve opening the program will monitor the Open Limit Switch status if configured and de activate the Open Output when the limit switch status becomes active If the open limit switch input is not defined then the open output will remain energized for the full open duration period Minor and major data logs are collected from the LineGuard unit using the LineGuard Log Utility refer to LineGuard Logs Utility User Manual Form A6177 This software and associated documentation may be purchased from Remote Automation Solutions The interface software allows the user to log on into the LineGuard unit
27. he major log at each log period Event Logs are triggered by changes in SetPoints or parameters that affect program operation The event Log function is performed by the standard FloBoss firmware Event Log entries include conditions such as remote and local commands to change valve position change SetPoints and change in parameters that affect any aspect of the LineGuard operation Event data may be used to establish a history of LineGuard status and pipeline valve activity The event log allows for a maximum of 240 records and overwrites old data as new events occur Alarm Logs are triggered by exceeding operating limits and SetPoints The alarm log function is performed by the standard FloBoss firmware The alarm log collects and stores data not directly related to operator change requests Alarm entries include battery low voltage condition and any other input point high and low condition The alarm log can store up to 240 alarms and overwrites old entries as new alarms are encountered An alarm entry is also created when a Minor or Major Alarm becomes active a Minor or Major Alarm becomes inactive and when automatic valve closure is initiated and a transmitter fail condition becomes active or clears The following user text type alarm is created by the calculation program Alarm Entry Description Auto Close Init Indicates the time at which automatic valve closure was Rev Nov 12 LineGuard 2300 Program User Manual Shutd
28. hen the voltage check is enabled and the input Rev Nov 12 LineGuard 2300 Program User Manual voltage to the FloBoss 107 is outside of one of the alarm limits the program first checks to see if a valve closure is already in progress If a closure is in progress the program will wait for the closure to complete before taking action When the input voltage is out of limits and no closure in is progress line break detection software and value closure algorithm are disabled until the input voltage returns to within limits 1 3 Program Requirements The LineGuard program is compatible with version 1 50 or greater of the FB107 firmware and with version 2 10 or greater ofthe ROCLINK 800 software Program specifics include ROCKLINK Target Unit User Defined Flash Used DRAM Used Display FileName Version Point UDP in bytes in bytes Vecion Number LineGuard_1 bin FB107 1 50 22 23 16 338 16 384 2 10 21 22 ae For information on viewing the memory allocation of user programs refer to the ROCLINK 800 Configuration Software User Manual for FB107 Form A6217 1 3 1 License Key Some applications require that you install a license in the CPU to run the application This license software is specific to these applications and is the property of the individual vendor shown in the Vendor Name field on the License Key Administrator screens RAS and other authorized vendors distribute software licenses on security enha
29. igured from 0 seconds to 1800 seconds 30 minutes If the Average Pressure or Average RoD returns to an allowable level during the Event Duration period then valve closure is not initiated and normal pressure monitoring resumes Once a line break situation has been detected valve closure is completed a major log is filled and then all log recording and valve control stops The user must select Clear Logs on the LineGuard Status screen before normal pressure monitoring logging and control is resumed If the Open Output field is defined the user can open the valve by selecting Force Open on the LineGuard Valve Control screen or remotely If the Open Output field on the LineGuard Valve Control screen is not defined the user must manually open the valve on site The control valve can be opened and closed both remotely and on site by setting the Manual Close Flag or Manual Open Flag When the Manual Open Flag is set the configured Open Output is energized for the Open Duration When the Manual Close Flag is set the configured Close Output is energized for the Close Duration Open Duration and Close Duration values can be configured from 5 seconds to 1800 seconds 30 minutes Rev Nov 12 Data Log Collection Input Error Detection LineGuard 2300 Program User Manual Automatic valve closure can be initiated by a high pressure condition low pressure condition or a high rate o
30. inor Logs O Minor Log Index 0 Event Duration 30 Seconds Active Event Time 0 Seconds Reset Clear Logs Clear Logs Print Save As Auto Scan Update Close App v Figure 10 LineGuard Status Note The LineGuard Status screen like the other LineGuard Valve Control screen has a tab format Sections 3 1 1 3 1 2 and 3 1 3 discuss the requirements for each tab on the LineGuard Status screen 14 Rev Nov 12 LineGuard 2300 Program User Manual 3 1 1 LineGuard Status Screen LineGuard Status tab Use this screen which displays when you access the LineGuard Status screen to view the status and parameter settings of the LineGuard program sam ROCLINK 800 LineGuard Status FB107 File Edit View ROC Configure Meter Utilities Tools Window Help Osa LREIS KELA ANNET Se ORR MOM 3 Log Alarm Setup RoD Values Program Status Running No error Average Sample Period 60 Seconds Transmitter Status Good Normal Operation Live Pressure 0 0 PSIG Average Pressure 0 0 PSIG Current RoD 0 0 PSI Min Average RoD 0 0 PSI Min Enable Disable SetPoint Status Major Low Alarm Disabled 0 0 Clear Major Log Period 30 Seconds Major High Alarm Disabled 0 0 Clear Major Log State Clear Major RoD Alarm Disabled 0 0 Clear Number Major Logs 0 Minor Low Alarm Disabled 0 0 Clear Minor Log Period 30 Seconds Minor High Alarm Disabled 0 0 Clear Minor Log State Clear Minor RoD Alarm Disabled 0 0 Clear Number Minor Logs 0
31. is parameter to a value of 1 forces the system to clear all major and minor logs from the database and set log states to not active The program sets the parameter back to a value of 0 after logs are cleared 33 Minor Log Address R O System UINT32 4 NA 0x0000 1 00 Physical memory address of the first minor log in the database 34 Major Log Address R O System UINT32 4 NA 0x0000 1 00 Physical memory address of the major log in the database 35 Minor Log Value R O System UINT8 1 0 59 0 1 00 Sixty average pressure and RoD values are Index saved in every minor log This index 0 59 points the location in the log at which the next values will be saved 36 Highest RoD Value R O System Float 4 Any positive 0 0 1 10 Contains the highest RoD value calculated float since the last system restart This value can be cleared by selecting the Clear Logs button on the Status tab Length Range Default Version 37 2m4 Highest RoD R O System Float 4 Any positive 0 0 1 10 Contains the second highest RoD value Value float calculated since the last system restart This value can be cleared by selecting the Clear Logs button on the Status tab 38 3 Highest RoD R O System Float 4 Any positive 0 0 1 10 Contains the third highest RoD value calculated Value float since the last system restart This value can be cleared by selecting the Clear Logs button on the Status tab 39 Highest RoD R O System AC20 20 NA moo 1 10 Contains the timestamp fo
32. lete Note This number is always 0 or 1 This read only field displays in seconds the period at which pressure and RoD values are placed in the minor log Valid values are 30 60 120 180 240 and 300 seconds This read only field displays the number of major logs archived This read only field displays the current state of the minor log function Valid values are Not Logging Actively Logging and Log is Complete minor logs archived Note The maximum number of minor logs is 100 valve closure initiates This read only field displays the number of This read only field displays the minor log index points to the most recent minor log in the system Up to 100 minor logs are maintained in the LineGuard database This read only field displays in seconds the configured period in which a major log alarm must be active before major log archival and This read only field displays in seconds the length of time a major alarm has been active Rev Nov 12 17 LineGuard 2300 Program User Manual Field Description Reset Clear Logs Clicking this button clears all major and minor logs from the database and sets the log status to Not Active The records of the highest RoD values are also cleared 2 Click Apply to save any changes you have made to this screen 3 Click Close to return to the ROCLINK 800 screen Proceed to Section 3 1 2 to configure the Log Alarm Setup screen 3 1 2 LineGuard
33. log once all 100 logs are full Minor log data archival will also stop 50 logs 60 values Rev Nov 12 Major Data Logs Event Logs Alarm Logs LineGuard 2300 Program User Manual each after a major log alarm condition becomes active and will not resume until after the user has manually cleared the major log alarm state A Major Log is initiated when a major alarm becomes active the alarm is enabled and the event duration period has been satisfied Alarm conditions include Average Pressure less than the Major Low SetPoint Average Pressure greater than Major High SetPoint and Average RoD greater than Major RoD SetPoint Major Log SetPoints alarms and event durations are user configurable A complete Major Log consists of a time stamp MM DD YY HH MM SS thirty Average Pressure values and thirty Average RoD values prior to the major alarm becoming active and thirty Average Pressure values and thirty Average RoD values after the major alarm became active The time stamp indicates the actual time of the line break Only one major log is saved in the LineGuard unit A major log will be retained and not overwritten until you manually clear the major alarm state by pressing Clear Logs on the LineGuard Status screen Values are stored in the log at a user configurable major log period Valid log periods for a major log include 5 seconds 10 seconds 15 seconds and 30 seconds The current Average Pressure and Average RoD is written to t
34. lue will always be less than or equal to the open duration 4 Click Apply to save your changes 5 Click Close to return to the ROCLINK 800 screen Proceed to Section 3 2 2 to configure the Event Control tab 24 Rev Nov 12 LineGuard 2300 Program User Manual 3 2 2 LineGuard Valve Control Event Control tab Use this screen to configure the length of time an alarm condition is present before starting autoclosure view the length of time an event has been active and enable autoclosure during low alarm conditions To access this screen 1 Select the Event Control tab on the LineGuard Valve Control screen vam ROCLINK 800 LineGuard Valve Control FB107 Eile Edit View ROC Configure Meter Utilities Tools Window Help 5 x Os Ms BEIS Tr TT ARTS NPR SA OOR LOM LineGuard Valve Control 1 Transmitter Fail Voltage Check Event Duration Period 30 Seconds Active Event Time D Seconds Low Alarm Autoclosure Disabled y High Alarm Autoclosure Disabled F RoD Alarm AutoClosure Disabled E Print Save As Auto Scan Update Close Figure 16 LineGuard Valve Control Event Control tab 2 Review and change as necessary the values in the following fields Field Description Event Duration Period Sets in seconds the length of time in which a major log alarm must be active before major log archival and valve closure are initiated Valid values are 0 5 10 15 30 60 120 180 240 300
35. me __ Open output Open Limit Switch s al Sea PA ia ta Current Open Time Click Force Close to force control valve closure by activating the close output point for the configured close duration This field may be written on site or through remote communications Sets in seconds the length of time the close output point remains active after closure is initiated Valid values are from 5 10 15 30 60 120 180 240 300 600 1200 and 1800 seconds This read only field displays the length of time the close output point has been active since valve closure was initiated This value will always be less than or equal to the close duration Click to define the discrete output point used to open the control valve Click to define the discrete input point monitoring status of the valve open state During valve opening if this field is defined and the status becomes active Click Force Open to force opening of the control valve by activating the open output point for the configured open duration This field may be written on site or through remote communications Sets in seconds the length of time the open output point remains active after opening is initiated Valid values are from 5 10 15 30 60 120 180 240 300 600 1200 and 1800 seconds This read only field displays the length of time the open output point has been active since valve opening was initiated This va
36. n 2 2 to download the user program 8 Rev Nov 12 LineGuard 2300 Program User Manual 2 2 Downloading the Program This section provides instructions for installing the program into the Flash memory on the FB107 To download the program using ROCLINK 800 software 1 Connect the FB107 to your computer using the LOI port 2 Start and logon to ROCLINK 800 3 Select Utilities gt User Program Administrator from the ROCLINK menu bar The User Program Administrator screen displays see Figure 3 User Program Administrator User Programs Installed in Device Name No Program No Program No Program Version Library Version No Program i No Program Created DRAM Used 0 No Program CRC FLASH Used 0 No Program E ea art Displays I All Option Status Empty Download User Program File Asa Browse Name Do 12 tart Download Version Created CRC Size m Update Close Figure 3 User Program Administrator 4 Click Browse in the Download User Program File frame The Select User Program File screen displays see Figure 4 5 Select the path and user program file to download from the CD ROM Program files are typically located in the Program Files folder on the CD ROM As Figure 4 shows the screen lists all valid user program files with the BIN extension Rev Nov 12 LineGuard 2300 Program User Manual Select User Program File Look in P
37. nced universal serial bus USB drives You must install the following license keys to use the LineGuard program LineGuard License Key 6 Rev Nov 12 LineGuard 2300 Program User Manual Chapter 2 Installation This section provides instructions for installing the LineGuard program Read Section 1 3 of this manual for program requirements Note The program and license key can be installed in any order The manual shows the installation of the license key first 2 1 Installing the License Key A USB key based license is required to use the LineGuard program 2 1 1 Installing a License To install a USB key based license on the FB107 1 Insert the USB license key in a USB port on your PC 2 Select Utilities gt License Key Administrator gt Transfer Between DEVICE and KEY from the ROCLINK 800 menu bar The Transfer Licenses Between a Device and a Key screen displays Transfer Licenses Between a DEVICE and a KEY Licenses on DEVICE Application Name _ Vendor Name App Code Version Quantity License Source Expiration Time Created Connect to KEY E Move to DEVICE Add License Remove Licenses on KEY rare O se GE 31529 1 1 0 0 No Expiration i 123456789 License Key Event Log Serial Number 9 Time Stamp Action User ID VendorID Export Events Figure 1 Transfer Licenses Between a Device and a Key Rev Nov 12 7 LineGuard 2300 Program User Manual Note This screen has
38. nfigure the program using two program specific screens LineGuard Status and LineGuard Valve Control Use the LineGuard Status screen to view program settings and configure alarms the sample period and the units of measurement used by the program Use the LineGuard Valve Control screen to configure parameters for valve opening and closing and to configure the actions taken by the program when a failed transmitter is encountered or input voltage is out of limits To configure the program after logging onto ROCLINK 800 and successfully installing the program and license key proceed through the program screens as shown in this section You can access all the program specific screens from the main ROCLINK 800 screen sam ROCLINK 800 On Line Ethernet FB107 FB107 TT File Edit View RO igure Meter Utilities Tools Window Help NEIVA MESION LR 2 E e On Line Ethernet FB 107 FB107 vee me KE m Modules Ey 1 0 E Control al 1 amp lid Meter Me MMI Coriolis Interf E User Program Administrator ES LineGuard User Pram Display 21 LineGuard Status Display 22 LineGuard Valve Control User Display General Advanced 1 0 Points Meter Points Diagnostic InstaledModue CPU aetualModule PI Description Application Firmware Revision Rew 150 Part Number w68182 BuldDate 5ept13 2021 Serial Number u 48083X0012 C 07010049 BootRevision
39. nonananinns 25 3 2 3 LineGuard Valve Control Transmitter Fail tab o nnnnnnnnnnnnononinnninocinnnonacininanacanananininns 27 3 24 LineGuard Valve Control Voltage Check taD oooonocininnnininicocicnnoconnncnnnannnn nano ncnn rana rca rincon 29 3 3 Saving the Configuratlon cad dde 31 Chapter 4 Reference Material 33 4 1 Point Type 22 LineGuard Pressure Log Configuration xrrrnranarrnnnnnvvrvnnnnnrrnnnnnnrrnnnernrrnnnerrrrnnnenn 34 4 2 Point Type 23 LineGuard Valve Control rnnnararrnnnanavrnnnnnnvrnnnnnnvrnnnnnnrrnnnersrrnneersrrnnsersrrnnsersrrnneenn 38 Rev Nov 12 iii LineGuard 2300 Program User Manual This page is intentionally left blank iv Rev Nov 12 LineGuard 2300 Program User Manual Chapter 1 Introduction This chapter describes the structure of this manual and presents an overview and installation instructions of the LineGuard 2300 Program for the FloBoss 107 FB107 1 1 Scope and Organization This document serves as the user manual for the LineGuard user program which is intended for use in a FloBoss 107 FB107 This manual describes how to download install and configure the LineGuard user program referred to as the LineGuard program or the program throughout the rest of this manual You access and configure this program using ROCLINK 800 Configuration Software version 2 10 or greater loaded on a personal computer PC running Windows 2000 with
40. o the sample period used in calculating average pressure The Average RoD is used to detect Major and Minor line break conditions The Average RoD is archived in both Major and Minor data logs Four logs are maintained in the LineGuard program Minor Data Logs Major Data Logs Event Logs and Alarm Logs A Minor Log is initiated when a minor alarm is enabled and becomes active Alarm conditions include when the Average Pressure is less than the Minor Low pressure SetPoint Average Pressure greater than the Minor High SetPoint and Average RoD greater than the Minor RoD SetPoint Each Minor Log setpoint and alarm is user configurable A complete minor log consists of a beginning time stamp MM DD YY HH MM SS 60 average pressure values and 60 average RoD values Values are stored in the log at a user configurable Minor Log Period Valid log periods for a minor log include 30 seconds 1 minute 2 minutes 3 minutes 4 minutes and 5 minutes At each log period the current Average Pressure and Average RoD is written to the minor log A Minor Log archives 60 complete log values for Average Pressure and Average RoD values regardless of whether the initiating alarm condition persists A log is archived to memory once the log is complete Another Minor Log is initiated if the minor log alarm condition remains active A total of 100 Minor Logs can be stored in the unit Minor Logs are circular logs with the earliest log overwritten with the newest
41. oat 4 float User UINT8 1 0 1 0 Any valid 0 0 1 00 1 00 1 00 When the input pressure drops below this value the transmitter is considered failed When the input pressure rises above this value the transmitter is considered failed This flag allows the user to enable the reset recover sequence when a failed transmitter is detected O reset disabled 1 reset enabled When this flag is enabled and a transmitter has failed the system will first cycle power to the transmitter and then warm start the FloBoss if transmitter is still failed 40 Rev Nov 12 Point Type 23 LineGuard Valve Control Parm 24 25 26 27 28 Name Transmitter Fail Sequence Transmitter Fail Period Transmitter Fail Status Voltage Check Enable Voltage Check Status Access R O R W R W System or User Update Program User Program User Program Data Type UINT8 UINT16 UINT8 UINT8 Length Range 1 0 9 2 0 gt 65535 1 O 1 1 0 gt 3 Default 0 LineGuard 2300 Program User Manual Version 1 00 Description of functionality and meaning of values This parameter indicates current step of the transmitter reset sequence 0 Transmitter Good No Reset In Progress 1 Possible Failure Detected 2 Failed Power Cycle Initiated 3 Failed Waiting for Power Up 4 Unused step 5 Good Transmitter Recovered 6 Failed Warm Start In Progress 7 Good Transmitter Re
42. ot initiate major log on low alarm 1 Initiate major low on low alarm 8 Minor Alarm Low R W User UINT8 1 0 1 0 1 00 Minor log low alarm enable Enable 0 Do not initiate minor log on low alarm 9 Minor Alarm High R W User UINT8 1 0 1 0 1 00 Minor log high alarm enable Enable 0 Do not initiate minor log on high alarm 1 Initiate minor low on high alarm 34 Rev Nov 12 Point Type 22 LineGuard Pressure Log Configuration Parm H 10 Name Major Alarm High Enable Access RW System or User Update User Data Type UINT8 Range 1 0 1 Default 0 LineGuard 2300 Program User Manual Version 1 00 Description of functionality and meaning of values Major log high alarm enable 0 Do not initiate major log on high alarm 1 Initiate major low on high alarm 12 Minor Alarm RoD Enable Major Alarm RoD Enable RW 1 0 1 Minor log RoD alarm enable 0 Do not initiate minor log on RoD alarm 1 Initiate minor low on RoD alarm Major log RoD alarm enable 0 Do not initiate major log on RoD alarm 1 Initiat jor I RoD al 13 14 Major Alarm Low Status Minor Alarm Low Status Minor Alarm High Status Major low alarm status O Not active 1 Active Minor low alarm status O Not active 1 Active Minor high alarm status O Not active 1 Active Major Alarm High Status Major high alarm status O Not active 1 Active Minor Alarm RoD Status Major
43. own Control Line Break Detection Valve Control Major RoD Indicates the value and time at which the major RoD alarm became active or inactive Major High Indicates the value and time at which the major high alarm became active or inactive Minor Low Indicates the value and time at which the minor low alarm became active or inactive Minor RoD Indicates the value and time at which the minor RoD alarm became active or inactive Minor High Indicates the value and time at which the minor high alarm became active or inactive Trans Low Indicates the value and time at which the pressure value repo f h nsmi dropped below the low limi Indicates the value and time at which the pressure value reported from the transmitter rose above the high limit ig Trans Trans OK Indicates the value and time at which the pressure value reported from the transmitter are within alarm limits The LineGuard program is responsible for automatic valve closure upon the detection of a major line break The Average Pressure and Average RoD are used to detect line break conditions every sample cycle 5 seconds Valve closure is activated when the four following conditions are met a major log alarm becomes active it remains active for the configured Event Duration auto closure is enabled for the event and the Close Output field is defined The major log will continue to record data until 1t becomes full The Event Duration can be conf
44. r Log Period R W User UINT16 2 30 60 120 30 1 00 Minor log period in seconds This is the period 180 240 300 at which pressure and RoD values are placed in a minor log Valid periods are 30 60 120 180 240 and 300 seconds 26 Major Log Period R W User UINT16 2 5 10 15 30 30 1 00 Major log period in seconds This is the period at which pressure and RoD values are placed in the major log Valid periods are 5 10 15 and 30 seconds 27 Major Log State R O System UINT8 1 0 1 2 0 1 00 Current state of the major log function 0 Not Logging 1 Actively logging 2 Log is Complete 28 Minor Log State R O System UINT8 1 0 1 2 0 1 00 Current state of the minor log function 0 Not Logging 1 Actively logging 2 Log is Complete 29 Minor Log Index R O System UINT8 1 0 gt 99 0 1 00 Up to 100 minor logs are maintained in the LineGuard databse The minor log index points to the most recent log in the system 30 Number of Major R O System UINT8 1 0 1 0 1 00 This value shows the number of major logs Logs archived will always be 0 or 1 31 Number of Minor R O System UINT8 1 0 gt 100 0 1 00 This value shows the number of minor logs L hived i f 100 36 Rev Nov 12 LineGuard 2300 Program User Manual Point Type 22 LineGuard Pressure Log Configuration Description of functionality and meaning of Parm Name ccess System or Data values User Update Type 32 Reset Clear Logs R W User System UINT8 1 0 1 0 1 00 Setting th
45. r Manual Data Type TLP 3 NA Length Range Default TLP 3 NA UINT8 1 0 1 0 1 00 UINT8 1 O 1 0 1 00 UINT8 1 O 1 0 1 00 UINT8 1 O 1 0 1 00 UINT8 1 0 1 0 1 00 Version 0 0 0 1 00 0 0 0 1 00 Description of functionality and meaning of values Identifies discrete input used as closed valve limit switch The intent of this input is to indicate when the valve is fully closed When this input point is defined and the close output is active the close output will be de energized when this input status becomes active Identifies discrete input used as opened valve limit switch The intent of this input is to indicate when the valve is fully opened When this input point is defined and the open output is active the open output will be de energized when this input status becomes active Indicates current status of close discrete input limit switch O inactive 1 active Indicates current status of open discrete input limit switch O inactive 1 active Allows the system to prevent valve closure on high major alarm O automatically start valve closure on high alarm 1 do not close valve on high alarm Allows the system to prevent valve closure on low major alarm O automatically start valve closure on low alarm 1 do not close valve on low alarm Allows the system to prevent valve closure on RoD major alarm O automatically start valve closure on RoD alarm 1 do not close valve on RoD alarm
46. r highest RoD value Timestamp in format of DD MM YYYY HH MM SS 40 an Highest RoD R O System AC20 20 NA 1 10 Contains the timestamp for second highest RoD Timestamp value 41 3 Highest RoD R O System AC20 20 NA oan 1 10 Contains the timestamp for third highest RoD Timestamp value Rev Nov 12 37 LineGuard 2300 Program User Manual 4 2 Point Type 23 LineGuard Valve Control Point type 23 contains the parameters for controlling valves in the LineGuard program The program maintains 1 logical point of this point type Point Type 23 LineGuard Valve Control Parm Name PE System or Data Length Range Default Version Description of functionality and User Update Type meaning of values 0 Close Output Point Def R W User TLP 3 NA 0 0 0 1 00 Identifies discrete output used to close the control valve 1 Open Output Point Def R W User TLP 3 NA 0 0 0 1 00 Identifies discrete output used to open the 2 Manual Close Flag R W User UINT8 1 0 1 0 1 00 Setting this parameter to a value of 1 Program will energize the close valve discrete output The system will set the parameter back to 0 after the output i is energized 3 Manual Open Flag R W User UINT8 1 0 1 0 1 00 Setting this parameter toa value of 1 Program will energize the close valve discrete output The system will set the parameter back to 0 after the output i is energized 4 Close Duration R W User UINT16 2 5 10 15 30 1 00 Time in seconds the clo
47. remotely or on site and retrieve logs The utility is intended only for collection of minor and major data logs from the LineGuard device All other operations including program monitoring program configuration and event and alarm log collection are accomplished with the ROCLINK 800 configuration software The program provides error detection for failed transmitters and input power limits The user may enable a check for pressure transmitter fail detection see tab on the LineGuard Valve Control screen The user enters low and high pressure set points When the transmitter fail check is enabled and the input pressure is outside of one of the set points for more than a user defined delay period the program begins a transmitter reset sequence The program first cycles power to the pressure transmitter If the pressure value returns to within the set points normal LineGuard operations are continued If the input pressure remains out of limits the program initiates a restart warm start of the FloBoss 107 If the pressure value returns to within the set points normal LineGuard operations are continued If the input pressure remains out of limits line break detection software and value closure algorithm are disabled until the pressure input value returns to within the expected range The user may enable a check for input voltage error see tab on the LineGuard Valve Control screen The user enters low and high input voltage alarm limits W
48. rogram Files y e ar Ed My Recent Documents My Network File name Lineguard_1 bin Places Files of type User Programs bin S Figure 4 Select User Program File 6 Click Open to select the program file The User Program Administrator screen displays As shown in Figure 5 note that the Download User Program File frame identifies the selected program and that the Download Start button is active User Program Administrator User Programs Installed in Device Name No Program No Program No Program Version Library Version No Program i No Program Created DRAM Used 0 No Program CRC FLASH Used 0 No Program Entry Pt Clear Sta Stop Displays I All Option Status Empty Download User Program File F Program Files Lineguard_1 bin Name LineGuard User Pram Download amp Start Download Rev 1 10 Created 11 9 2012 10 53 31 AM CRC 0xC99D Size 16338 m Update Close Figure 5 User Program Administrator 10 Rev Nov 12 LineGuard 2300 Program User Manual 7 Click Download Start to begin loading the selected programs The following message displays Confirm Download 2 Download amp Start User Program 1 Figure 6 Confirm Download 8 Click Yes to begin the download When the download completes the following message displays ROCLINK 800 1 Download amp Start User Program COMPLETED Figure 7 RO
49. s as Remote Automation Solutions a business unit of Emerson Process Management FloBoss ROCLINK Bristol Bristol Babcock ControlWave TeleFlow Helicoid METCO and OpenEnterprise are trademarks of Remote Automation Solutions AMS PlantWeb and the PlantWeb logo are marks of Emerson Electric Co The Emerson logo is a trademark and service mark of the Emerson Electric Co All other marks are property of their respective owners The contents of this publication are presented for informational purposes only While every effort has been made to ensure informational accuracy they are not to be construed as warranties or guarantees express or implied regarding the products or services described herein or their use or applicability Remote Automation Solutions reserves the right to modify or improve the designs or specifications of such products at any time without notice All sales are governed by Remote Automation Solutions terms and conditions which are available upon request Remote Automation Solutions does not assume responsibility for the selection use or maintenance of any product Responsibility for proper selection use and maintenance of any Remote Automation Solutions product remains solely with the purchaser and end user EMERSON
50. se discrete 30 60 120 output will remain active after being 180 240 energized Valid duration times are 5 10 300 600 15 30 60 120 180 240 300 600 1200 1200 1800 and 1800 seconds 5 Open Duration R W User UINT16 2 5 10 15 30 1 00 Time in seconds the open discrete 30 60 120 output will remain active after being 180 240 energized Valid duration times are 5 10 300 600 15 30 60 120 180 240 300 600 1200 1200 1800 and 1800 seconds 6 Current Close Time R O Program UINT16 2 0 gt 1800 0 1 00 Time in seconds that the close output has been active since being energized 7 Current Close Time R O Program UINT16 2 0 gt 1800 0 1 00 Time in seconds that the open output has been active since being energized 8 Open Output Status R W User UINT8 1 0 1 0 1 00 Indicates current status of open discrete output 0 inactive 1 active 9 Close Output Status R W User UINT8 1 0 1 0 1 00 Indicates current status of close discrete output O inactive 1 active 38 Rev Nov 12 Point Type 23 LineGuard Valve Control Parm H 10 Close Limit Switch Def R W Name Access 11 Open Limit Switch Def R W 12 Close Limit Input Switch R O Status 13 Open Limit Input Switch R O Status 14 Auto closure High Alarm R W Mask 15 Auto closure Low Alarm R W Mask 16 Auto closure RoD Alarm R W Mask System or User Update User User User User LineGuard 2300 Program Use
51. sion date to any page also changes the date of the manual that appears on the front cover Listed below is the revision date of each page if applicable Page Revision All Pages Nov 12 Initial release Jun 08 ii Rev Nov 12 LineGuard 2300 Program User Manual Contents Chapter 1 Introduction 1 1 1 Scope and Organization dia 1 1 2 Product OVervie Wa ti ET 1 1 21 Basic Program Operational italia batidas 2 1 3 Program Requirements ccoo A re ed 6 13 A A ett 6 Chapter 2 Installation 7 2 1 Installing the License Reinan a RE 7 2 14 Installing a License A A aan ee ay 7 2 2 Downloading the Program cccccceceeeee ee eeneee teenies ents eee ee ernie ee ernie nr naar rr cenar nn rr naar AAE aa AEE 9 Chapter 3 Configuration 13 3 1 LineGuard Status Screen ui ii oe 14 3 1 1 LineGuard Status Screen LineGuard Status tab arrrurrrannnvnrrnnnnvvnnnnenrrnnnnenrrnnenenvvnnenern 15 3 1 2 LineGuard Status Log Alarm Setup taD oonoccninnncininncoccnnnoconncnnononcnnnnno carr nnnn rca rra rca rra 18 3 13 LineGuard Status RoD Values tab occccconnccccnncccccnnonicononanoconononanonanoni non cncn nono nnnnnanininns 21 3 2 kineGuard Valve Control O Or O a ld tt nur dte Ge 22 3 2 1 LineGuard Valve Control LineGuard Valve Control tab ooonnccccccccccoonnconennoncnonnonnoos 23 3 2 2 LineGuard Valve Control Event Control tab nccnnnonnccccnnoncnanonanicinonacicononina
52. ss this screen 1 Select the Transmitter Fail tab on the LineGuard Valve Control screen sam ROCLINK 800 LineGuard Valve Control FB107 File Edit View ROC Configure Meter Utilities Tools Window Help OSOS ASIA LA MUA MAROON LMI LineGuard Valve Control Event Control E il Voltage Check Fail Detect Enable Transmitter Reset Sequence Disabled v Transmitter Good No Reset In Progress Fail Delay Period Transmitter Fail Status 5 Seconds Good Normal Operation Transmitter Limits Setup Transmitter Low Setpoint 0 0 PSIG Transmitter High Setpoint 10 0 PSIG Transmitter Fail Output Definitions Transmitter Power Contact Undefined E Transmitter Alarm Contact Undefined i Print Save As Auto Scan Update Close 3 Appl Figure 17 LineGuard Valve Control Transmitter Fail tab 2 Review and change as necessary the values in the following fields Field Description Fail Detect Enable Sets the Fail Detect Enable to Enabled or Disabled If Enabled and a transmitter is failing the system cycles power to the transmitter If the transmitter is still failing after the power cycle the program warm starts the FloBoss No action is taken when set to Disabled and a transmitter has failed Transmitter Reset This read only field shows the current Sequence step of the transmitter reset sequence Rev Nov 12 27 LineGuard 2300 Program User Manual Field Description Valid values are Transmitter Good No Reset In
Download Pdf Manuals
Related Search
Related Contents
Analog tape recorder Elex アクセサリーキット Accessory Kit Kit d`accessoires Комплект 「組立説明書」PDFファイル はこちら E505 E425 E325 E585 - NEC Display Solutions Europe User guide / Torres de Enfriamiento – Marley Sigma – Serie 10/15 Clase 160 / USER MANUAL AtomBox Studio User`s Guide 全ページ一括ダウンロード Manuel d`installation et d`utilisation Copyright © All rights reserved.