Home
beghelli logica
Contents
1. EEE GROUPS AND SCENES All the appliances programmed can be associated to 16 groups each devi ce may pertain to one or more groups or none at all These groups can ena ble specific operations on subsets of the system A scene is a preset coordinated lighting combination that involves several appliances By giving the system the order to go to scene xx from 1 to 16 each ligh ting appliance goes to a particular internally stored brightness condition Given that this value is independent for each lighting appliance preset ligh ting situations can be created and performed simultaneously thus combining in a single command many lighting settings for different appliances For each scene it is possible to decide that the appliance will switch on switch off go to a given brightness percentage or do nothing at all ignoring the order and remaining in the current state of brightness MENU All control unit functions can be accessed from menus a first level enables a general overview of the system activates lights or preset lighting scenes in a second level it is possible to set program and modify the setting of the plant The user can decide to protect the settings programmed activating a password The menus can be scrolled vertically using the arrows 4 and by pres sing D one selects the item currently displayed by pressing E one moves up a level The display back light is activated when a
2. choose the time with or and press 9 to confirm COMMAND EXECUTED The unconditioned on function entails the switching on of the emergency lamps powered by battery even in the presence of mains power without pre set duration in which the charge level of the battery is not under examina tion it is interrupted when the battery is completely run down or by sending a stop test command The autonomy test is associated to the duration that it must have This duration is at the User s discretion and can be selected by scrolling the menu downwards This manual test does not in any way modify the timing and the durations set for the automatic tests In the Maintenance menu Emergency Management 3 2 it is possi ble to inhibit or enable the emergency condition for individual LOGICA appliances groups or the entire system It is not possible to permanently inhibit the emergency function or to pro gramme inhibition for the next blackout each appliance can be inhibited or enabled only if already in blackout conditions otherwise the command will be rejected MAINTENANCE J 9 EMERGENCY 3 2 9 ALL 3 2 1 9 EMERG ENABLED 3 2 1 1 EMERG UNENABLE 3 2 1 2 SWITCH OFF 3 2 1 3 9 COMMAND EXECUTED 9 LOGICA J 2 2 EMERG ENABLED 3 2 2 1 EMERG UNENABLE 3 2 2 2 SUITCH OFF 3 2 2 3 COMMAND EXECUTED GROUP OI 3 2 3 EMERG ENABLED 3 2 3 1 EMERG UNENABLE 3 2 3 2 SUITCH OFF 3 2 3 3 9 COMMAND EXECUTED W
3. Tel 051 9660411 Fax 051 9660444 z 8 UMEN 0 9001 BEGHELLI LOGICA CONTROL UNIT Control unit for centralised management and control of lighting and emergency lighting appliances INSTRUCTIONS FOR USE AND INSTALLATION INDEX WHAT IS THE BEGHELLI LOGICA CONTROL UNIT APPLIANCE FUNCTION page Wiring diagram te Groups and scenes nn Menu Password Initial menu Activate scene menu 1 al Light menu2 Maintenance menu 3 manual test 3 1 emergency function and management 3 2 F error status 3 3 management test 3 4 ml management lamp 3 5 t management group 3 6 t control unit management 3 7 h configuration management 3 8 h status MSG menu eee SPECIFICATIONS page 20 WARNINGS WARRANTIES page 20 WHAT IS THE BEGHELLI LOGICA CONTROL UNIT The Logica control unit has been designed to dialogue with different com munication protocols It enables the simultaneous management of both ligh ting and emergency lighting appliances As well as the various functions dedicated to testing and controlling emergency lighting the Logica control unit can command individual appliances or groups of lamps using the DALI protocol the international protocol that complies with IEC standard 60929 The control unit also allows the creation of customised scenes for controlling the type of lighting according to the varying lighting requirements at different t
4. 1 D ACTIVE SCENE Ol 1 1 ACTIVE SCENE Oe 1 1 Choose the scene to be activated from 01 to 16 and press D to confirm SCENE ACTIVATE Use the lights menu to programme the scenes I Lights 2 Menu This menu enables switching on switching off or dimming individual lighting appliances groups of appliances or the entire system When one enters the third level of the menu it is possible to modify brightness directly in real time by using the and buttons e a brief pressing of the key switches on the appliances at maximum bri ghtness e a brief pressing of the key switches the appliances off e a prolonged pressing of the or keys causes a slow variation of brightness in the chosen direction Finally by releasing the key the lumi naires maintain the brightness achieved between the 14 pre set possible intensities LIGHTS 2 ALL 2 1 D ALL 2 1 1 SUITCH OFF 2 1 1 SET IN SCENE Ol 2 1 1 1 DEL IN SCENE b 2 1 1 2 choose scene from 01 to 16 and press 9 to confirm SCENE STORED SCENE DELETED SUITCH ON MAW 2 1 1 D SET IN SCENE Ol 2 1 1 1 DEL IN SCENE lb 2 1 1 2 SCENE STORED SCENE DELETED pressed lt gt or STEP DIMMER 8 e D SET IN SCENE Ol 2 1 1 gt DEL IN SCENE Ib e l e choose scene from 01 to 16 with or and press 9 to confirm SCENE STORED SCENE DELETED D LOGICA 2 2 106 2 2 1 choose the lamp with or and press 9 to confirm SWITCH
5. OFF 2 2 1 9 SET IN SCENE Ol 2 2 1 1 gt DEL IN SCENE lb 2 2 1 2 choose scene from 01 to 16 with or and press 9 to confirm SCENE STORED SCENE DELETED SWITCH ON MAX 2 2 1 9 SET IN SCENE Ol 2 2 1 1 gt DEL IN SCENE b 2 2 1 2 choose scene from 01 to 16 with or and press 9 to confirm SCENE STORED SCENE DELETED pressed lt gt or STEP DIMMER 8 2 2 1 9 SET IN SCENE Ol 2 2 1 1 gt DEL IN SCENE b 2 2 1 2 choose scene from 01 to 16 with or and press 9 to confirm SCENE STORED SCENE DELETED DALI 2 3 DALI 2 3 1 choose the lamp with or and press D to confirm SUITCH OFF 2 3 1 9 SET IN SCENE 01 2 3 1 1 gt DEL IN SCENE lb 2 3 1 2 choose scene from 01 to 16 with or and press 9 to confirm 8 SCENE STORED SCENE DELETED gt SUITCH ON MAX 2 3 1 D SET IN SCENE Ol 2 3 1 1 gt DEL IN SCENE Ib e 3 le choose scene from 01 to 16 with or and press 9 to confirm SCENE STORED SCENE DELETED pressed STEP DIMMER 8 2 3 gt D SET IN SCENE Ol 2 3 1 4 gt DEL IN SCENE lb e 3 l e choose scene from 01 to 16 with or and press D to confirm SCENE STORED SCENE DELETED GROUP OI 2 4 GROUP oO 2 4 1 Choose the group from 01 to 16 with amp or and press D to confirm SUITCH OFF 2 4 1 D SET IN SCENE Ol 2 4 1 gt DEL IN SCENE lb 2 4 1 2 choose scene from 01 to 16 with or and press D to confirm SCENE STORED SCENE DELETED SUITCH ON MAX
6. key and 0 with the key In the Maintenance menu Control unit management 3 7 it is possible to set current Date Time enable or modify the password set the remote address of the Control Unit in the case of multiple systems order prin touts in the case of local printers set and configure the type of Inputs 4 local switches MAINTENANCE 3 CU MANAGEMENT 3 1 gt PASSWORD ON OFF 3 7 1 gt PASSWORD ON PASSUORD OFF 3 7 1 1 9 CHANGE DATE HOUR 3 1 2 2005 07 01 1 30 3 1 2 1 choose with and then press 9 to confirm D CHANGE PASSWORD 3 1 3 OLD PASSWORD mina NEU PASSWORD mres choose numbers with and keys then press D to confirm 9 CHANGE ADDRESS 3 7 4 ADDRESS 000 3 1 4 1 choose numbers with and keys then press 9 to confirm D LOCAL PRINTER 3 1 5 9 NOT PRESENT PRESENT a7 1 5 1 9 PRINT 3 71 b 9 NONE PRINT 3 1 b default setting CONFIGURATION J 1 b e2 amp PROGRAMMATION 3 1 b 3 ERRORS 3 1 b 4 a In the Menu Config Switches it is possible to assign to every input one of the following options I O Sen Sen Sct 1 0 it is a manual input that allow through a button to switch ON OFF and to dimmer one or more groups of lamps to associate the groups to the swit ches see the paragraph Maintenance menu Management groups 3 6 The other 3 typologies of input Sen Scn Sct work making the commutation between 2 scenes in automatic or manual way In order to as
7. of each Logica luminaire or group and modify the NO TEST SUSPEN 3 5 2 8 settings e g autonomy 1h or 3h the even or odd status NONE ERRORS 3 5 2 9 The information on the luminaire relate to the Software version the pro CENTRALDINER 3 5 2 10 gramming conditions Autonomy 1 or 3 hours even and odd status the pre sence of main supply emergency operation inhibition enabling the test FUNCTION PS 3 5 2 1 ne eae eee eae oo the presence of errors and the settings 2 GROUP Ol 3 5 3 choose with and then press 9 to confirm MAINTENANCE 3 9 D SU 3 5 3 1 D FITTING MANAGEN 3 5 NOT PROG PROG P J 5 J 2 Q AL 3 5 1 H H P 3 5 3 3 D SU 3 5 1 1 ELEN 0DD 3 5 3 4 NOT PROG PROG P J 5 Ire 3 5 35 H H P 3254 lt EN ENAB UNEN P 3 5 3 6 EVEN O0D P 3 5 1 4 STOP TEST P 75 31 3 5 1 5 DEL TEST SUSP P 3 5 3 8 EN ENAB UNEN P 3 5 I b DEL ERRORS P ha STOP TEST P J 52 SELF DIMMER P 3 5 3 10 DEL TEST SUSP P 3 5 1 8 FUNCT SA PS P Jar lt DEL ERRORS P 3 5 1 9 SELF DIMMER P 3 5 1 10 In the Maintenance menu Management groups 3 6 it is possible to assi FUNCT SA PS P 3 5 1 l gn each appliance or switch local to one or more groups or to none at all in a totally free and unrestrictive way There are 16 groups available there is no obligation to start from the lowest numbers EE
8. the next func tional autonomy test and every how many days to perform the subsequent ones periodicity of tests furthermore it is possible to break the system down into odd and even lights in order to make them perform autonomy tests seven days apart odd before even 7 days later The tests cannot be inhibited MAINTENANCE 3 9 TEST MANAGEMENT 3 4 9 NEXT FUNCTIONAL TEST 3 4 1 DAS 3 4 1 choose with and then press 9 to confirm XXX DAYS 3 4 1 1 HOURS 3 4 1 1 choose with and then press 9 to confirm D XXX DAYS XX HOURS J MINUTES J choose with and amp then press 9 to confirm 9 NEXT AUT TEST 3 4 2 DAYS 3 4 2 choose with 4 and then press 9 to confirm a HOURS 3 4 2 1 choose with and amp then press D to confirm a MINUTES 3 4 2 1 choose with and then press D to confirm D FUNC TEST PERIOD 3 4 3 a OAS 3 4 3 1 choose with and then press 9 to confirm 9 AUT TEST PERIOD 3 4 4 DAYS 3 4 4 1 choose with 4 and then press D to confirm D LOGICA XXXX SA 3 5 2 EVEN ODD TEST 3 4 5 D SU vmx 3 5 2 1 CONTEMPORARY 3 4 5 1 PROGRAMMED 3 5 2 2 1 OAYS DEFERRED 3 4 5 2 FUTONON 3H 3 5 2 3 choose with and then press D to confirm 000 FITTING 3 5 2 4 COMMAND EXECUTED MAN on 3 5 2 5 ENERG ENABLED 3 5 2 b In the Maintenance menu Management Lamps 3 5 it is possible to eva NO TEST ON 3 5 2 1 luate the current status
9. 2 4 1 9 SET IN SCENE Ol 2 4 4 DEL IN SCENE lb 2 4 1 2 choose scene from 01 to 16 with or and press D to confirm SCENE STORED SCENE DELETED pressed lt gt or STEP DIMMER 8 2 4 1 9 SET IN SCENE Ol 2 4 DEL IN SCENE ib 2 4 1 2 choose scene from 01 to 16 with or and press 9 to confirm SCENE STORED SCENE DELETED Maintenance 3 menu All Maintenance menus are password protected In the maintenance menu manual test 3 1 it is possible to perform and interrupt manual tests on individual appliances groups or the entire system One can give different test commands on different appliances without waiting for the first to finish before starting the subsequent ones the lamp that receives atest start see Functional 3 1 1 2 autonomously proceeds for the neces sary time 30 sec without requiring the control unit thus giving the opportunity to control other tests on other lamps MAINTENANCE J 9 MANUAL TEST J 1 Q AL 3 1 1 STOP TEST 3 1 1 1 FUNCTIONAL 3 1 1 2 SUITCH ON INC 3 1 1 3 00h Olmin OOsec 3 1 1 4 choose the time with or and press D to confirm COMMAND EXECUTED LOGICA 3 1 2 D STOP TEST 3 1 2 1 FUNCTIONAL 3 1 2 2 SWITCH ON INC 3 1 2 3 00h OOmin OOsec 3 1 2 4 choose the time with or and press 9 to confirm COMMAND EXECUTED GROUP O1 3 1 3 STOP TEST 3 1 3 1 FUNCTIONAL 3 1 3 2 SWITCH ON INC 3 1 3 3 00h Olmin OOsec 3 1 3 4
10. EE_ _ _ E _EE_ E_ _ E __EE_EE_ _ _ _ EE 14 15 ee At the last level of this menu 16 figures will be displayed 0 or 1 by going towards the right you can select the x group numbered from 1 to 16 from left to right and with the keys and you can pass from the figure 0 to 1 and vice versa The figure 1 identifies the belonging to the selected group An appliance can therefore also have all 1 belongs to all groups just some or none so as to be completely independent from the other appliances The local switches four are managed in the same way they are assigned to one or more groups when a button is pressed the action on off dimmer addresses all the lamps that belong to the groups that the pressed button belongs to This management concerns the entire lighting and emergency lighting system and therefore both the DALI and Logica appliances MAINTENANCE J 9 GROUP MANAGEMENT 3 b Q AL J b 9 1001000100111011 3 b 1 1 choose 1 with the key and 0 with the key LOGICA J b 2 1001000100111011 J b 2 1 choose 1 with the lt gt key and 0 with the key DALI 3 b 3 1001000100111011 3 b 3 choose 1 with the key and 0 with the key SUITCH 3 b 4 choose 1 4 with the keys and 9 Waa 3 b 4 1 choose 1 with the key and 0 with the key GROUP OI J b 5 choose 1 16 with the keys and 9 1111111111111111 J3 b 5 1 TE choose 1 with the
11. MSG 4 menu STATUS NSG 4 9 000 LOGICA LAMP 4 1 00 DALI LAMP He TOT 000 FITTING Mad 001 ERR LOGICA 4 4 00 ERR DALI 4 5 TOT 000 ERRORS 4 b D W 219 0 V199 4 1
12. SPECIFICATIONS Battery NiCd 7V 0 75Ah Power supply voltage 230V 50Hz Max input from mains 10Va WARNINGS WARRANTIES Before connecting this appliance check that the rating plate data corre spond to the mains data This appliance must be used solely for the purpose for which it was built Any other use is to be considered as improper and may cause damage The manufacturer will not be liable for any damage to human beings animals or properties caused by improper wrong or unreasonable use Before any cleaning or maintenance operation disconnect the appliance from the mains The product cannot be disposed as unsorted municipal waste It must be collected separately to prevent negative environmental impacts In accor X dance with the procedures of Directive 2002 96 and relevant national laws and regulations adopted pursuant to this Directive on the disposal of waste at the end of the life cycle of the product any violation is sanctioned by law Beghelli products are covered by laws on intellectual property Should any repairs be necessary contact an authorised service centre and always request the use of original spare parts Failure to comply with the above may undermine the safety of the appliance For repairs replacements under guarantee contact an Authorised Dealer O O z E J 3 334 900 395 A lt Beghelli www beghelli com BEGHELLI S p A Via Mozzeghine 13 15 40050 MONTEVEGLIO BO
13. hereas the enable disable functions are reversible the off function is irre versible unless the mains power comes back on it is useful to maintain the charge of the light accumulators and if referred to the entire system it is used to disable it in the event of particularly lengthy maintenance operations When the operations have been completed the control unit switches off and in order to change status again the mains supply must come back on In the Maintenance menu Error status 3 3 it is possible to see whether there are error conditions present on the Logica and DALI appliances obtain information about the error conditions and any components that require replacing and to cancel any error condition indicated MAINTENANCE 3 D ERROR STATUS 3 3 9 NONE ERRORS 3 3 1 For each appliance only the errors currently in the memory will appear as well as the possibility to cancel them In the event of the selection of groups of appliances or the entire system the possibility of cancelling errors only is given without further details In order to display the details concerning certain errors of Logica luminaires only press you will receive further information on type of battery or tube which has an eventual failure r 12 In the Maintenance menu Management Test 3 4 it is possible to set the timings and the frequency of the automatic tests of the emergency part of the system it is possible to select when to perform
14. imes of the day It is also possible to adjust the brightness using a dimmer for single appliances or groups even when fitted with a timer or connected to light sensors which makes it possible to light rooms or areas in the most similar way to natural sunlight biodynamic lighting The control unit is composed of a keyboard display for all user operations four programmable switches for light activation an RS485 input for remote connection and the DALI compatible bus input for managing the system The control unit houses the bus built in feeder and can autonomously mana ge acomplete system comprising 128 appliances without requiring further equipment If the local switches are used the normally open buttons must be employed APPLIANCE FUNCTION The control unit manages and controls the status of the programmed applian ces controls routine tests according to the modes set by the user and can perform a vast series of manual operations that can be selected from a series of menus accessible from the keyboard UX UX COM BUS 485 WIRING DIAGRAM P me I 355 i Nay P Eak Beghelli amp T Q 24321 CoBIEA AD re o o o SWITCH MAX 255 CONTROL UNIT LA A NOT POLARIZED MAX 128 LOGICA MAX 128 UNITS MAX 64 DALI
15. ny key is pressed To generate a manual test proceed as follows e select the manual test menu e select the appliance or group of appliances or even the entire system on which the operation is to be performed e select the operation to be performed for instance functional test e press 9 the operation will now be performed and the control unit is ready to receive new commands e PASSWORD In order to avoid a not intentional reset of the plant and to protect settings and the parameters of that one a password can be activated If the User tries to enter in a menu the password is requested and will then be allowed access for 4 minutes Should operations last longer than 4 minu tes the User will be required to enter the password again INITIAL MENU The Initial menu enables the User to use previously entered settings manage lights check the overall state of the system There are four possible options ACTIVE SCENE 1 makes it possible to select and activate one of the 16 pre set scenes LIGHTS 2 makes it possible to activate any appliance and to switch it on switch it off and dimmer it fiRINTENANCE 3 enables access protected by a password to all the set ting and programming functions reserved for system fitters STATUS NSG 4 displays all the control unit status messages currently active Active scene 1 Menu This menu enables the activating of the preset lighting scenes ACTIVE SCENE
16. sociate to every input the relative scenes see the following table Int In2 In3 In4 scene 1 scene 3 scene 5 scene 7 scene 2 scene 4 scene 6 scene 8 For the programming of the scenes see the paragraph Lights 2 menu Sen is an automatic input like motion sensor or manual like stairs lighting which allow to change between 2 fixed scenes through a timer Sen is a manual input that allow to change between 2 fixed scenes ScT is an automatic input that allow to change between 2 fixed scenes making the set of beginning time and end time like external night lighting You also have the possibility of a manual intervention D CONFIG SWITCHES 3 1 7 NI N2 N3 My Onn The setting Timer Sensors is necessary only in case one input at least is set like Sen TIMER SENSOR 3 1 8 NI N2 N3 My The setting Timer Scenes is necessary only in case one input at least is set like ScT D TIMER SCENES 321 9 START STOP SCT 00 00 00 00 In the Maintenance Menu Configuration 3 8 it is possible to configu re the system that is make the control unit search for all the appliances pre sent see NEW 3 8 1 only DALI appliances or only LOGICA appliances MAINTENANCE J CONFIGURATION 3 8 9 NEU 3 8 1 NEU DALI 3 8 2 NEU LOGICA 3 8 3 Configuration does not change the settings that each appliance had pre viously but it merely acquires its address and current status Status