1. Gas System Software Manual By Peter Kravtsov E mail pkravt gmail com This document location http Ikst pnpi nw ru pdf cbm_rich_gas_soft pdf February 2011 Gas system software manual Introduction The software described in this document was developed for the slow control of the gas systems in STAR and PHENIX detectors and after some modifications is used to control CBM RICH gas system The software provides manual control of the gas system and data acquisition for all sensors shows measured system parameters and maintains the gas system database Besides the software reacts on some gas system faults and takes care for automatic recovering The gas system software works in Windows 2000 or Windows XP The software consists of three separate programs Gas system control program does most of the job and controls the gas system DBViewer 1 provides visualization of the data for any gas system process variable and export data from the database to MS Excel or tab delimited text file for further analysis Charts 2 program displays up to ten selected system parameters in the time chart format Besides it could be used for tabular display of the process variables with extra alarm signals for every parameter in the table In addition the TCP IP client server is implemented in the Charts software so that it can be used remotely for monitoring the system under control The software utilizes MS Access database engine to keep the hist
2. S Y KA KB PTE 8 4336 S AVG Snew 1 AVG Sold TT 1 11 952 V Log coefficients changing in DB 02 1 2048 V Save channels config on exit H20 1 2048 FM 1 0 N Name Comment Ch Special branch for ct Ch Channel Ch Channe Channe Ch HSHHRHHTHHHHHHH HS ooo Oooog Fig 5 Database configuration First 32 Fast channels correspond to 32 sensors of the slow control module Channels 33 36 correspond to four analog outputs of the slow control module Sensor value for these channels is calculated from the voltage using the following formula S v KA KB Every channel has the following editable properties e name e value coefficients KA and KB e averaging coefficient AVG e sensor units e branch e comment Name units and comment are simple strings that used to identify system parameter in visualization software Averaging coefficient AVG is used to average the sensor values Running average is calculated by the formula S AVG S 1 AVG 84 Thus AVG 1 means no averaging AVG 0 1 is equal to averaging by 10 samples Page 10 of 12 Gas system software manual The channel branches are used for data channel grouping in Charts and DBViewer programs For the systems with 100 or more parameters it becomes very useful to group these parameters by subsystem In this particular case only two groups are used GAS branch contains all gas system par
3. ameters while all slow control module specific parameters belong to Device branch like PID coefficients device reading time etc There is also special Disabled branch for unused parameters Usually it is not displayed in Charts and DB Viewer programs Using small toolbar in top right corner of the window operator can read and save channel configuration to ini file Usually it is saved automatically at the program shutdown if checkbox Save channels config on exit is checked This ini file is also used for the Charts program to display the list of the available parameters Channel configuration can also be saved or read from the current database Database control toolbar provides two actions for changing the active database create a new database and open existing database In addition the software has special limit for the database file size set to 800Mb in Fig 5 By reaching this limit it starts new database automatically with the date and time in the name and writes an appropriate message in the main log Page 11 of 12 Gas system software manual References 1 DBViewer Manual http Ikst pnpi nw ru pdf DB Viewer2en pdf 2 Charts User Manual http Ikst pnpi nw ru pdf chartsen pdf 3 See gas system scheme 4 Alarm System Manual http Ikst pnpi nw ru pdf alarm_manual pdf Page 12 of 12
4. are logs alarm message BPCV1 should be slightly adjusted in this case to increase the exhaust flow which in turn will increase the fresh gas flow to detector Fig 2 shows the normal operation starting without any fail ai 17 02 2011 11 29 02 Normal operation mode starting i 17 02 2011 11 29 02 Checking Purifier amp Dryer lt 1 00ppm i 17 02 2011 11 30 02 Purifier amp Dryer are OK Switching to normal loop and checking FM1 A 17 02 2011 11 31 02 FM1 flow is OK fa 17 02 2011 11 31 02 Transition to Normal operation mode accomplished Fig 2 Start normal operation messages Stop circulation button stops compressor and switch the gas system to simple purge mode through the FM1 System parameters System parameters tab Fig 3 contains communication parameters for the slow control electronics and fine tuning parameters for the system regulation loops Communication parameters are adjusted during assembling of the system and most of them should be kept untouched during gas system operation The Connect button is used to connect to slow control module at the selected com port It could also be used to reconnect the device if it was switched off The device is connected automatically during program startup The most important parameters here are Data poll interval and Database interval The first one defines the time period between data reading from the slow control electronics Database interval defines the time period of
5. cking cycle This means that no valves and devices are affected if nothing happens with alarm situation i e neither alarms nor alarm returns happened The alarms configuration is stored in special ini file There are two copies of alarms setup normal and default Normal setup is used each time the program starts while defaults intended to be used as a reference The buttons at the window s bottom allows performing the following service tasks oy Save alarms configuration to binary file nO Load alarms configuration from binary file an Export alarms configuration to tab delimited text file Export alarms configuration to MS Excel file Th Save alarms configuration to registry as defaults Add new alarm to bottom of alarms list Copy current alarm to a new one at the bottom of the list Move current alarm up just for aesthetic purposes Move current alarm down just for aesthetic purposes Delete selected alarm from the list x 2S alo Database The Database tab contains the database parameters and also the sensor coefficients Fig 5 All gas system parameters channels are divided into three groups Fast Slow and Control Only Fast and Control groups are used for the gas system Page 9 of 12 Gas system software manual Channels _ M Database Fast channels a PT 1 1 2048 F 3 Ga e 29 D 2 PT 2 1 2048 E Max DB size MB 800 PT 3 1 2048 7 PT 4 1 2048
6. le alarms and to control the gas system operation parameters Note that all alarms are disabled by default at program start All gas system parameters are logged into the database with specified time interval Current database name is always shown in the window caption Each software event is logged into the event log at the bottom of the main window and into the current database as well In case of alarm trigger the alarm message is also logged and corresponding sensor is displayed in red color in the list Page 4 of 12 Gas system software manual Pressure regulation controls are used to control the pressure inside the detector or fresh gas flow Enable PT4 regulation checkbox switches the PID control algorithm in the slow control module which stabilizes detector pressure at specified setpoint Set Enable PT4 regulation button sends pressure regulation parameters to slow PT4 setpoint _ Set control module If Enable PT4 regulation checkbox is M1 manual pi cleared operator can control FM1 flow controller directly Three mode buttons are used to control the basic gas system procedures Purging Mode button starts and stops the purging procedure Before starting the purging operator should specify the desired pressure in the detector and total purging gas volume 10 litres in Fig 1 Then by starting the purging mode the software will open all necessary valves and smoothly increase the flow to minimize pre
7. n Update buttons reads these parameters from slow control module Set button sends changed parameters back to the device Alarms The Alarms configuration tabsheet Fig 4 is designed to display and change alarms levels and actions to be taken in case of any particular alarm The following parameters are available for every alarm e Alarm name with enable checkbox which allows enable or disable each particular alarm e Active sensor for this alarm e Alarm level sensor value exceeding level causes alarm e Alarm recovery level sensor value below this level recovers system from alarm once it has been triggered Page 7 of 12 Gas system software manual e Threshold sign sensor value comparison sign e Count number of exceeding sensor readings for alarm e Alarm message which will be logged in case of alarm e Alarm message color e Valves pattern that will be applied in case of alarm gt Database DAQ32 About Main control System parameters i Aammname Enabled Sensor Level Recovey Count Alarm mossage PT 4 high alarm PT 4 4 000 3 800 0 PT4 pressweistooh sst lt CS s CS S PT 4 low alarm PT 4 0 500 0 600 0 Oxygen high alarm 02 200 000 190000 0 Moisture high alarm H20 200 000 130 000 0 Solenoid Valves and devices configuration PT1 low alarm PT 1 0 500 0 600 0 Pddsv 1 P lt P lt P lt FM1 low alarm FM 1 0 200 0 250 0 Pdsv 2 e lt b lt lt q Psv 3 gt lt a gt lt a g
8. ory of all system parameters and event messages DBViewer and Charts programs are documented separately Page 2 of 12 Gas system software manual Gas system control program The main control process contains two threads The first one provides graphical user interface GUI and events log while the second thread does data acquisition device control and alarms handling The priority of the second thread is set to highest value for reliable work in crowded system The main window contains several tabs 1 Main control provides basic gas system control 2 System parameters tab is used for control electronics specific parameters like communication properties reading interval 3 Alarms tab contains alarm handlers list 4 Database tab is used for the database control and also for changing the sensor coefficients 5 DAQ32 tab can be used for fine tuning the DAQ32 module and is not necessary for gas system operation Main control The Main control tab of the gas system software gives user a possibility to control gas system manually Fig 1 It has simplified gas scheme in the main window 3 The buttons on the gas scheme represent every solenoid valve and device controlled by software Red button state means either closed valve or switched off device while green one stays for open valve or switched on device Note that some solenoid valves and devices are controlled by the pressure switch PIS1 and therefore may be blocked fo
9. r software control Page 3 of 12 Gas system software manual Date era 2 8mbar Vent line 3 0mbar PT 4 291 0K TT 1 Bubbler Purging gas volume 6 7 L Purging ends at 17 02 11 11 28 23 oO Alarm Message Instruments Smaaaag 17 02 2011 17 02 2011 17 02 2011 17 02 2011 17 02 2011 17 02 2011 Log started Loading settings Database in use D DATA test3 mdb Program started Version 1 0 0 305 DAQ Thread started Purging mode started V DAQ32 Name Value Units GAS SYSTEM PT 1 0 978 bar PT 2 0 250 bar PT 3 2 842 mbar PT 4 3 009 mbar PTB 976 570 mbar TT 1 291 011 02 34 713 H20 2 924 FM 1 1 906 Refr Index 1 000414 Sensor voltage PT 1 4 149 PT 2 0 000 PT 3 3 944 PT 4 4 105 PTB 3 332 TT 1 2 073 02 1 372 H20 1 219 FM 1 0 953 Channel 010 0 000 Channel 011 0 000 Channel 012 0 000 Cha 1 HNI anno lt lt ececececccccdc gt Enable PT4 regulation PT4 setpoint 2 000 Set y Alarms Disabled Purging L amp Purging Mode a D start Normal srr Stop circulation i R 140 WI0 New PT4 parameters were set to device Fig 1 Main control of the gas system All the sensors being read by the software are displayed at right side of the window There is a possibility to see sensor s voltages which can be useful for coefficients calculation Additional controls beneath the sensors list are used to enable or disab
10. ssure overshoot Then it calculates the gas volume passed through the FM1 controller and shows it along with the estimated finish time for purging Fig 1 By purging 90 of required gas volume the software opens SV3 and purge analyzers also to remove traces of oxygen and water if necessary When the necessary volume passed through the detector the software displays the message about finishing the purging and keeps the system in purging mode as the safest configuration Start Normal button serves to begin the normal gas system operation with recirculation of the gas The procedure is as follows Fig 2 The software starts gas circulation by switching on the compressor with closing the valves SV1 SV3 SV4 SV7 and opening the valves SV2 SV5 SV6 This configuration connects analyzers to purifier and dryer output Then after one minute the software checks the oxygen and moisture content If one of them does not fall below 100ppm they will be checked during 5 minutes in total and in case of high impurity concentration the software logs the corresponding message and keeps the system in this configuration After successful checking the purification units SV5 valve is closed and SV4 valve is opened to establish the normal circulation gas flow through the purification units and to connect analyzers to compressor Page 5 of 12 Gas system software manual output Then FM1 flow is checked after one minute If it falls below 0 2slpm the softw
11. t Pdsv 4 gt lt a gt Pdsv 5 gt gt lt gt Psv 6 PdAlarm P lt P lt Pdsv 7 a P lt Compressor P lt P lt P lt gt lt gt gt gt gt gt gt gt P lt 0pen ALL PClose ALL Don t touch ALL M Alarm Threshold sign Sensor data gt Level causes alarm C Sensor data lt Level causes alarm PT 4 high alarm PT 4 gt 4 00 mbar Return at PT 4 lt 3 80 mbar JS Apply Load Defauts x a ep z wr bi set Fig 4 Alarms configuration Alarms handling algorithm is very similar to that implemented in the hardware Alarm System which was developed for STAR and PHENIX experiments see Alarm System Manual 2 for details After each measuring cycle DAQ thread compares alarm thresholds for all enabled alarms with appropriate sensor values using alarm comparison signs If the sensor value exceeds the alarm level it displays alarm message and updates valves according to the alarm valves configuration red valves will be closed green will be open while gray will be left intact storing the list of affected valves in memory Upon alarm recovery event i e if the sensor value returns to alarm return level the code Page 8 of 12 Gas system software manual changes only those valves which were not alarmed by the other sensors making use of the stored list of the changed outputs Note that instead of special default state used in Alarm System PC software uses current valves state at every alarms che
12. the data saved to the database It is recommended to set Database interval to at least 20 seconds since the gas system processes are slow enough In case of alarm the data saved to the database immediately out of turn Ask valves control confirmation checkbox prevents accidental clicking on the valves in the main control tab A confirmation will be requested by every valve switching if this checkbox is checked Page 6 of 12 Gas system software manual Main control System parameters Alarms Database DAQ32 M Communication parameters PT4 control COM Port 3 Data poll interval Is PT4 Enable regulation IV Speed Me oM sp 2000 _P 50 XRAMTimeDut 3 3 Database interval TS cmar fi KD fio I a ee COmax 65535 K_I 10 Reconnect s f 5 ST Device delay ms f oo Connect F Ask valves control confirmation Save comm mesages toDB Stop DAG Update Set Fig 3 System parameters tab PT4 control group allows fine tuning of the PID regulation loop for detector pressure Setpoint SP repeats the setpoint from main control tab t_max value defines time constant of the PID algorithm in seconds COmax is the limit for controller output with maximum value of 65535 K_P K_D K_I are the proportional differential and integral coefficients of the PID algorithm correspondingly It is not recommended to change these parameters during normal system operatio

Download Pdf Manuals

image

Related Search

Related Contents

Lancom Systems IAP-321-3G  MISE À JOUR MANUEL D`ENTRETIEN DES STRUCTURES  Integral IN2T4GEWBEX memory module  Samsung SGH-E370 Εγχειρίδιο χρήσης  ECS A75F-M2 motherboard  4-BAY SATA NETWORK STORAGE ENCLOSURE DNS-343  PDF downloaden - Tv  Origin Storage 500GB 5400RPM Enigma Opal Desktop Drive  Scheduler System User Manual  Outdoor Living Today SS84DD Installation Guide  