1. correctly Delayed safe power down This is the same switch off sequence as for the Safe power down command but postponed by the number of seconds programmed in the Off Delay parameter Delayed safe power down amp reboot This is the same switch off then on sequence as for the Safe power down amp reboot command but postponed by the number of seconds programmed in the Off Delay parameter Delayed On This is the same switch on sequence as for the Immediate On command but postponed by the number of seconds programmed in the On Delay parameter The Save button saves the Off Delay Toggle duration and On Delay parameters on the card Security The administrator must click on Save and enter his her login password to save modifications or run commands The default login and password by default are MGEUPS UNINTERRUPTIBLE POWER PROVIDER 34003991EN GA THE Network Management Card User Manual 19 Downloaded from Hfeodis com electronic components distributor Downloaded from MGE UPS SYSTEMS 4 2 4 UPS weekly schedule programming Click on the Weekly schedule section of the menu UPS configuration may prevent the shutdown and restart commands from being properly run Read the UPS user manual for more information The weekly schedule enables the administrator to optimise power consumption or program a reboot of the protected equipment at a set time
2. In a shutdown sequence the Network Shutdown Modules connected to the card are informed and ensure that each machine is shut down correctly before the UPS output is switched off Up to 7 UPS shutdown sequences can be programmed in one week with a minimum shutdown delay of 30 minutes The On Off sequences are valid only if the card s time has been properly set Security The administrator clicks on Save and enters his her login password to save any edits The login and password by default are MGEUPS MGE UPS SYSTEMS Puisar V 3000 SSS UPS Weekly Schedule b UPS Properties UPS Control weeny Schedule Day Shuto Time Restart Time D Shutdown Parameters Sunday Ew ee Monday 20 00 07 00 Logs and Notification Tuesday 20 00 0700 Measurements Wednesday 20 00 o7 00 Event Log System Lo Thursday 20 00 07 00 D Email Notification Friday 20 00 S 07 00 7 Settings Sarira E E D Network System Notified Applications Access Control Time D Firmware Upload Save Environment Status Settings Log THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card User Manual 34003991 EN GA 20 dis com electronic components distributor MGE UPS SYSTEMS 4 2 5 Shutdown parameters This page enables viewing and configuration of UPS operating parameters in battery mode and for power restoration Click on the Shutd
3. This menu enables the administrator to configure the network parameters of the card and authorisation of the remote upgrade of the embedded system MGE UPS SYSTEMS Puisar M 3000 UPS Network Settings D UPS Properties UPS Control IP Address 172 17 22 252 Weekly Schedule Shutdown Parameters Subnet Mask 255 255 248 0 Alarm Table Gateway Address fi 72 17 17 1 Logs and Notification Measurements a Hostname Jups24 D Event Log 5 System Log Domain Name Jups domain com Email Notification Settings BOOTP DHCP Enabled z System Firmware Upload Enabled z Notified Applications Access Control a Primary DNS Server fi 72 17 16 6 Time Firmware Upload Secondary DNS Server 17217 16 7 Environment SMTP Server for Email Jemipsever SSCS b wans Notification smtpserver Settings Log Save modified settings Save Export settings to file Download Import settings from file l Parcourir Upload IP Address The IP address of the card e g 172 17 22 252 Subnet Mask The mask of the sub network of your network e g 255 255 255 0 Gateway Address Indicate the IP address of the gateway to access the stations located outside the card s subnet e g 172 17 17 1 Hostname must be suited to the card This is the first part of the fully qualified domain name used by the DNS As the card does not support NetBIOS protocol the hostname wi
4. Network Time hh mm ss fi 4 55 29 System Notified Applications Access Control Synchronize with NTP server Hostname Jpoolntp org Firmware Upload Time Zone Environment gt Status GMT Greenwich Mean TIME Dublin Lisbon London x Settings Log Save modified settings Save gt Set manually Enables initialisation of the date and time of the card with the values entered in the Date and Time fields This update is made after clicking on the Save button Maximum drift is 2 min month gt Synchronize with NTP server Enables connection with a time server either available on the company s internal network or on the Web This server communicates GMT time The IP address or hostname of the time server must be entered and the time zone of your geographic area must then be selected from the list Connection is made with the server and the date and time are set after clicking on the Save button Time is updated every five hours thus preventing any drift in the time After two attempts if the NTP server is not accessible the card shifts to manual mode The card uses the NTP protocol UDP 123 port The firewall must be set to transmit queries outside the intranet No error message is generated if the time server contact fails Note 1 The even the card is used in a UPS supporting time stamping the card s time is automatically synchronized with that of the UPS Note 2 After start
5. UPS SYSTEMS Pulsar M 3000 ws UPS Properties UPS Control Save Log Clear Log D Weekly Schedule Alarm Table 50 2006 03 15 14 40 09 230 230 0 100 120 Logs and Notification 2006 03715 14 39 06 230 50 230 0 100 120 F f 2006 03715 14 38 04 230 50 230 0 100 120 a P i 2006 03 15 14 36 56 230 50 230 0 100 120 K RERS Sai 2006 03 15 14 35 50 230 50 230 0 100 120 rae i 2006 03 15 14 34 49 231 50 230 o 100 120 Emalnonteaum 2006 03 15 14 33 44 230 50 230 0 100 120 THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card User Manual 34003991EN GA 24 Downloaded from dis com electronic components distributor MGE UPS SYSTEMS 4 2 8 Event log Click on Event Log in the menu Save log enables all saved values to be opened or saved in CSV format compatible with Excel type spreadsheets Clear log enables deletion of all records The administrator must enter his her login password to validate this action MGE UPS SYSTEMS Puisar M 3000 ups D UPS Properties UPS Control Save Log Clear Log D Weekly Schedule gt Shutdown Parameters Alarm Table Logs and Notification D Measurements Event Log System Log D Email Notification The card can save 435 events The table of managed alarms is included in the appendix 4 2 9 System log Click on System log in the menu Save log enables all saved values to be
6. Connections with Network Shutdown Modules stay in standard mode secure TCP SSL Security Implementation SSL version 3 0 TLS version 1 0 Method gt TLS_RSA_WITH_512_MD5 Auth gt RSA Key Exchange gt RSA Encryption gt RC4_512 THE UNINTERRUPTIBLE POWER PROVIDER 34003991EN GA 37 dis com electronic components distributor Downloaded from MGE UPS SYSTEMS Digest gt MD5 Changes take effect after a card reboot Export settings to file Enables exportation Download button and saving of card configuration information Import settings from file Enables selection of a configuration file Browse button and uploading Upload button of card configuration information THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card User Manual 34003991EN GA is com electronic components distributor 38 Downloaded from MGE UPS SYSTEMS A 4 4 6 Date and time Click on Date and Time in the menu This menu enables initialisation of the date and time of the card in three different ways The date format is always of year month day type MGE UPS SYSTEMS Puisar M 3000 UPS Setting time UPS Properties UPS Control b wedy Schedule Shutdown Parameters Alarm Table Time hh mm ss 14 55 29 Date yyyywimnmidd 2006 0315 Logs and Notification Measurements Event Log System Log Set manually Email Notification Date yyyyirnmidd 2006 03 1 5 Settings
7. For each of the following questions you can press Return to select the value shown in braces or you can enter a new value Should this target obtain IP settings from the network N N Static IP address 172 17 16 16 172 17 21 141 Subnet mask IP address 255 255 0 0 255 255 255 0 Gateway address IP address 0 0 0 0 172 17 17 4 Done Return to the main menu and enter 1 The card restarts with the new IP parameters 3 1 2 Test after configuration To check that the Network Management Card is operational after installation and configuration From a station connected to the same subnet as the card open a web browser and enter the IP address of the card in the address field Check the display of the home page THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card User Manual 34003991EN GA sodis com electronic components distributor MGE UPS SYSTEMS 4 Supervision and administration by browser gt Onacomputer equipped with a Web browser Internet Explorer FireFox or Netscape recommended enter the address initialised previously in the Installation chapter e g http 172 17 16 16 The UPS properties home page is displayed 4 1 1 Optimising the performance of your browser To view status changes on the UPS in real time the browser must be configured so that it automatically refreshes all the objects on the current page Example on IE 6 Tools Internet Options General Parameters menu
8. NOK the battery needs to be checked Deactivated the automatic battery test is not validated on the UPS The About your UPS zone provides information on the UPS and the card in particular the model range and software version About your UPS UPS Name Pulsar M 3000 UPS Firmware revision PR2C Firmware revision _1_03 4 THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card User Manual 34003991EN GA 16 Downloaded from dis com electronic components distributor Downloaded from di MGE UPS SYSTEMS 4 2 2 On line help On line contextual help in English is available at the top of each page by clicking on the Help link which is always located on the top right corner The navigation menu of the on line help is identical to that of the card s pages The Help page always opens a new window MGE UPS SYSTEMS Network Management Card Heip UPS UPS Properties Help UPS Properties UPS Control D Weekly Schedule gt Shutdown Parameter UPS feature identifies the UPS which is powering the electrical network Alarm Table This is the page by default displaying the fundamentals status of the UPS UPS Status feature describes how the UPS is currently working Logs and Notification Measurements Event Log gos a i b Remaining backup time Estimation of the remaining battery backup time System Loa based on the nominal value Email Notification Battery Status give
9. Downloaded from Hfcodis com electronic components distributor 5 2 2 Extended power outage shutdown initiated by the Low battery power message When the Low battery power criterion is displayed the UPS is shut off after taking into account the shutdown duration of the servers Low battery power The message appears if either of the two following criteria is checked PROVIDER 49 MGE UPS SYSTEMS Start shutdown Start shutdown main Utility failure output 1 output Utility restore Utility Shutdown duration Main output Battery capacity under NSM 1 on main output Output 1 Battery capacity under output 1 NSM 2 on output 1 5 2 3 Case of power restoration before the end of the shutdown duration counter If power is restored before the end of the Shutdown Duration the UPS is shut off after the Shutdown Duration for a time equal to the forced reboot delay 10 seconds Start shutdown Start shutdown main Utility failure output 1 output Utility restore Utility Shutdown i duration Forced Reboot Main output Battery capacity under NSM 1 on main output Output 1 NSM 2 on output 1 THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card User Manual 34003991EN GA 50 Downloaded from Hfcodis com electronic components distributor MGE UPS SYSTEMS 6 Configuration via RS232 Use the cord supplied with
10. Programmable outlet controlled outlet Outlet that can be remote switched on or off UM Client components enable management of such outlets REBOOT To restart a system after an interruption To perform an obstacle free reboot it is essential that the system is correctly and carefully shut down beforehand The reboot is usually automatic if the computer is re supplied with electricity from the utility or from the UPS RFC Request for Comments All documents defining internal Internet operation SNMP SIMPLE NETWORK MANAGEMENT PROTOCOL Protocol used to remote supervise administrate and control devices connected to a company network SMTP SIMPLE MAIL TRANSFER PROTOCOL Enables message transfer between e mail servers or between the client and its server It is based on the server s port 25 It is described in RFC 821 SSL Secure Sockets Layers is a protocol developed by Netscape Communications Corporation for securing data transmission in commercial transactions on the Internet Using public key cryptography SSL provides server authentication data encryption and data integrity for client server communications Subnet mask Mask of bits used to identify and differentiate the network address and the equipment address in an IP address Normally the mask is automatically determined by the class of address which defines in a unique manner the network part equipment part division of the IP address Class A interne
11. Security The administrator has to enter his her login password in order to view this information This menu enables The addition of the supervision stations receiving traps and configuration of the trap type gt To list all the Notified Applications and the main parameters To test the operation of notified applications gt by simulating power loss gt by sending a real shutdown sequence MGE UPS SYSTEMS Puisar M 3000 e UPS Notified Applications D UPS Properties UPS Control Weekly Schedule Shutdown Parameters 1 MISFROO79F Shutdown Module V2 6 Master CENTRALIZED 120 Alarm Table z 2 172 17 23 128 HP OV server Logs and Notification Measurements Selectthe applications to be removed Remove Event Log System Log Email Notification Selectthe applications to be tested Utility failure Test Shutdown Test Settings n SF Select the Network Management System to be modified Modify Nis Add NMS D Network System Access Control Time Firmware Upload Environment D Status R Settings Log Up to 50 destinations can be managed by the card Important note It is not necessary to add the Network Shutdown Modules protecting your servers in this list These modules subscribe and unsubscribe themselves automatically Select an entry in the list to modify the values in the edit zone at the bottom of the page The table displays the following information
12. Sends network notifications to the Administrators and Users groups on events declared in the server hosting the NSM If you wish to set up a new configuration for the Network Shutdown Modules already set to central configuration mode proceed as indicated below Change the Network Shutdown Module parameters in the Notified Applications page D Click the Save button gt In this page select the NSMs for which you want to apply the new configuration gt Press the Remove button The NSMs selected will disconnect then reconnect and use the new configuration THE UNINTERRUPTIBLE POWER PROVIDER 36 im Network Management Card User Manual 34003991EN GA Downloaded from dis com electronic components distributor Downloaded from 4 4 5 Access control Click on Access Control in the menu To access this page the login and password are systematically requested if they have not already been entered This menu enables configuration of the different parameters enabling secure access to the card via a browser or SNMP MGE UPS SYSTEMS Pulsar M 3000 MGE UPS SYSTEMS UPS UPS Properties UPS Control Weekly Schedule Shutdown Parameters Alarm Table Logs and Notification Measurements Event Log System Log D Email Notification Settings D Network System Notified Applications gt i a D Time D Firmware Upload Environment Statu
13. System Log Email Notification n g I Measurements Settings a Ea D Network System Log System Notified Applications Access Control Time b Firmware Upload Every 0 ayoa I dayofnextreport F mj D M mj mj mj mi mj M m m mj mj Ej mj o Set Default Environment Status p a i Configure SMTP Server on gt Settings Network Settings Log Show Hide Events Export settings to file Download Import settings from file Parcourir Upload THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card User Manual 34003991 EN GA dis com electronic components distributor z265 Downloaded from MGE UPS SYSTEMS Recipient List On the left side of this page up to four recipients can be configured to receive e mails from the card Each addressee has its own trigger events selected from the right side of the page for which an e mail is sent The card s log indicates e mail transmission errors Each recipient is configured with the following parameters gt Recipient Field is limited to 49 characters this is the e mail address of the person or department to receive the e mail The default value is recipientx domain com gt Attached files The files selected Measurements Event log System log Environment measurements are enclosed with each e mail sent The files are sent in CSV format gt Periodic report In addition to the e mails sent when events occu
14. in the menu to view the list of current alarms The table of managed alarms is included in the appendix THE UPS UPS Properties UPS Control D Weekly Schedule Shutdown Parameters Alarm Table Logs and Notification Measurements Event Log System Log Email Notification Alarm Table UNINTERRUPTIBLE Network Management Card User Manual is com electronic components distributor Ji POWER 34003991 EN GA L PROVIDER z234 MGE UPS SYSTEMS 4 2 7 Measurements Click on Measurements in the menu The following measurements are saved and time stamped env 430 Input voltage Value of the utility voltage supplying the UPS Input frequency Value of the utility frequency supplying the UPS Output voltage Value of the output voltage of your UPS Output load Value of the percentage of load at UPS output Battery capacity Percentage of charge available in the battery Remaining time min Estimation of the remaining backup time The save frequency of these values is defined in the System page 60 seconds by default Approximately 435 time stamps are stored permanently on the card The oldest time stamps are automatically deleted Save Log enables all saved values to be opened or saved in CSV format compatible with Excel type spreadsheets gt Clear Log enables deletion of all records Enter the login password to validate this action MGE
15. 259 248 0 Gateway 172 17 17 1 6 2 2 Choice 2 Modify Network settings Enables the modification of network parameters For each of the following questions you can press lt Return gt to select the value shown in braces or you can enter a new value Should this target obtain IP settings from the network N Static IP address 172 17 21 146 Subnet Mask IP address 255 255 248 017 Gateway address IP address 172 17 17 1 In DHCP mode the card can receive the following parameters according to the DHCP server settings IP address Subnet Mask Gateway address Primary DNS server Secondary DNS server The card must be restarted in order for the new parameters to be taken into account 6 3 Choice 3 Lost password Set Login Password to Default In the even the login or password is lost choice 3 enables the return to the default password MGE UPS SYSTEMS NETWORK MANAGEMENT CARD 1 Reset 2 Network configuration 3 Set Login Password to Default THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card User Manual 34003991EN GA 62 Downloaded from Hfeodis com electronic components distributor MGE UPS SYSTEMS 4 Return to Default Configuration 5 Exit 7 Exit The card is now accessible via the Web with the password MGEUPS Enables the return to the new default password MGEUPS 6 4 Choice 4 Return to Default Configuration MGE UPS SYSTEMS NETWORK M
16. BY BROWSER 14 4 1 1 Optimising the performance of your browser 14 4 2 UPS 15 4 2 1 UPS properties page 15 4 2 2 On line help 17 4 2 3 UPS control 18 4 2 4 UPS weekly schedule programming 20 4 2 5 Shutdown parameters 21 4 2 6 Viewing the alarms 23 4 2 7 Measurements 24 4 2 8 Event log 25 4 2 9 System log 25 4 3 NOTIFICATION 26 THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card User Manual 34003991EN GA Odis com electronic components distributor MGE UPS SYSTEMS 4 3 1 Email Notification 26 4 3 2 E mail Message Settings 28 4 4 CONFIGURATION 30 4 4 1 Network settings 31 4 4 2 System 33 4 4 3 Notified Applications 34 4 4 4 Central shutdown configuration 36 4 4 5 Access control 37 4 4 6 Date and time 39 4 4 7 Firmware upload 40 4 5 ENVIRONMENT SENSOR OPTION 41 4 5 1 Characteristics 41 4 5 2 Environment Status 42 4 5 3 Environment Settings 43 4 5 4 Log 45 5 SERVER PROTECTION 46 5 1 SET UP OF THE SHUTDOWN PARAMETERS 46 5 1 1 Shutdown criteria managed by the Network Management Card 46 5 1 2 Controlled outlets 47 5 1 3 Protection of a server connected to a controlled outlet 48 5 2 THE DIFFERENT SERVER AND UPS SHUTDOWN SEQUENCES 49 5 2 1 Extended power outage shutdown initiated by the Shutdown Timer Shutdown after 49 5 2 2 Extended power outage shutdown
17. D The All button Allows the following information to be displayed D Nr is the index where the application is stored into the table Hostname or Address IP By priority the hostname of the computer is displayed when the IP address can be converted into a hostname by a DNS server or if the application has been entered as a hostname Application Name sent by the application during subscription or entered manually gt Output number of the UPS output from which the client is powered THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card User Manual 34003991EN GA 34 dis com electronic components distributor Downloaded from MGE UPS SYSTEMS Configuration shows where the parameters of the Network Shutdown Module come from Local coming from the application or Central coming from the card The Central shutdown configuration is available by clicking on the Configuration link Shutdown duration the shutdown duration necessary to properly shutdown the computer Shutdown after the time available to the user from the power failure until the launch of the shutoff sequence of the UPS and equipment This parameter is optional Many actions are available on this page gt Remove Depending on the kind of application the selected ones will definitively disappear from the table as SNMP applications or they will disappear and automatically re subscribe as Network Shutdown Module applications gt Utility failu
18. Upload The default severity value is 1 Warning THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card User Manual 34003991 EN GA 35 dis com electronic components distributor MGE UPS SYSTEMS 4 4 4 Central shutdown configuration Click on Notified Applications in the menu then Configuration MGE UPS SYSTEMS Pulsar V 3000 es UPS Central shutdown configuration UPS Properties This configuration will be used by the Network Shutdown Modules on next connection UPS Control Shutdown Parameters Alarm Table Logs and Notification Measurements Event Log System Log Email Notification M Administrators M Users Settings Network Save System Notified Applications Access Control Time Firmware Upload This page is used to define either the shutdown or the notification settings used by the Network Shutdown Modules that connect to Network Management Card These settings are used by the Network Shutdown Modules if they are in central configuration mode or if their configuration is not valid Shutdown duration the shutdown duration necessary to properly shutdown the computer D gt Shutdown after the time available to the user from the power failure until the launch of the shutoff sequence of the UPS and equipment This parameter is optional Uncheck the box if you wish not to use this parameter gt Broadcast
19. electronic commerce IP Internet Protocol Network layer protocol in the TCP IP stack offering a no connection inter network service The IP protocol offers functions for addressing service type specification fragmentation and re assembling and security Defined in RFC 791 MIB MANAGEMENT INFORMATION BASE Group of software commands to control and administrate a device through the network Each type of device server hub PC UPS etc has its own MIB NETWORK MANAGEMENT CARD Communication cards to supervise UPS and communicate with Network Shutdown Module to insure power protection on servers NETWORK MANAGEMENT PROXY Communication software installed on a PC connected to the UPS to supervise it and communicate with Network Shutdown Module to insure power protection on servers NMS NETWORK MANAGEMENT STATION SNMP The dedicated PC or workstation is used on the company s networks to administrate all devices connected to the network Data are transmitted using the SNMP protocol Popular NMS systems include HP OpenView IBM Tivoli CA Unicenter etc NSM NETWORK SHUTDOWN MODULE Protection software installed on a PC or server to protect it THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card User Manual 34003991EN GA 61 Odis com electronic components distributor Downloaded from MGE UPS SYSTEMS NTP Network Time Protocol Protocol to position a set of machines on a network at the same time
20. modified settings Save Export settings to file Download Import settings from file Parcourir Upload The environment sensor measures temperature humidity and gives the status of the 2 contacts used for door alarms or generator unit The temperature and humidity thresholds can be adjusted and can trigger notification and correct shutdown of the protected system The Sensor name is the function name given to the sensor usually it enables location of the sensor Temperature Choose the temperature unit C or F from the selection box High threshold if this value is exceeded a notification if enabled The default value is 40 C 104 F Low threshold If this value is exceeded a notification if enabled The default value is 5 C 41 F Hysteresis must be set to prevent multiple notifications if temperature fluctuates around a threshold The default value is 2 C 3 6 F The high alarm disappears when the value drops below the High threshold Hysteresis value The low alarm disappears when the value returns above the Low threshold Hysteresis value THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card User Manual 34003991EN GA 43 dis com electronic components distributor Downloaded from MGE UPS SYSTEMS Humidity High threshold If this value is exceeded a notification is sent if this is validated The default value is 90 Low threshold If this value
21. opened or saved in CSV format compatible with Excel type spreadsheets gt Clear log enables deletion of all records The administrator must enter his her login password to validate this action MGE UPS SYSTEMS Puisar M 3000 SS Onduleur Ev nements syst me D Propri t s de l onduleur Enregistrer Effacer gt Contr le de l onduleur D Programmation MA Param tres d arr t Tableau des alarmes Historiques et Notification D Mesures Ev nements onduleur Evenements syst me D Notification par Email The card can save 435 events The table of managed alarms is included in the appendix THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card User Manual 34003991EN GA 25 Downloaded from dis com electronic components distributor Downloaded from 4 3 Notification 4 3 1 Email Notification The card offers the possibility of redirecting UPS alarms to an e mail server The format of these e mails is compatible with mobile telephone transfer systems using text messages SMS MGE UPS SYSTEMS B Puisar M 3000 UPS Email Notification UPS Properties UPS Control D Weekly Schedule omain com Shutdown Parameters MGE UPS SYSTEMS recipient2 domain com b Alarm Table recipient3 domain com recipient4 domain com Logs and Notification n gt Measurements Recipient recipienti domain com Event Log m Disabled z
22. tick Every time this page is visited and validate THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card User Manual 34003991EN GA 14 Downloaded from Hleodis com electronic components distributor MGE UPS SYSTEMS 4 2 UPS 4 2 1 UPS properties page This page gives instant access to the essential information about your UPS This page is automatically refreshed every 10 seconds MGE UPS SYSTEMS Network Management Card UPS Properties UPS Control Weekly Schedule Shutdown Parameters b Alarm Table Puisar M3000 Logs and Notification ok Computer Room Measurements D Event Log System Log Email Notification Communication OK Power source AC Power Settings Battery Charging eee Output load level m o System Notified Applications Master output master on Access Control Controlled outlets Group1 On Time Group2 on D Firmware Upload Environment Battery charge level GEE 100 Status Remaining backup time 2h00mn00s D Setting SN Last Periodic Test OK Log Last update 2006 03 15 14 21 24 About your UPS 4 2 1 1 UPS zone general information on the UPS Indication of the picture and generic name of the UPS range Computer room Customised name of your system You can change this name on the System page 4 2 1 2 UPS status zone Essential information The various icons showing the status o
23. uploading Upload button of card configuration information Security The user must be identified to access this page THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card User Manual 34003991EN GA 44 Odis com electronic components distributor MGE UPS SYSTEMS 4 5 4 Log MGE UPS SYSTEMS Puisar M 3000 a UPS Environment Log Data UPS Properties UPS Control D Weekly Schedule Shutdown Parameters Alarm Table Logs and Notification Measurements Event Log System Log D Email Notification Settings Network System Notified Applications Access Control Time D Firmware Upload The two environment sensor measurements Temperature and Humidity are recorded at an interval defined by the Environment log interval in the System settings page By default this period is 300 seconds Each measurement is dated and stored in the log of the UPS s communication card The size of log files is limited by a time indexing system The user can Save the log on his her workstation at any time in a CSV format file The user can also Clear the files contained in the card to reset the log UNINTERRUPTIBLE POWER PROVIDER 34003991EN GA THE 45 Network Management Card User Manual Downloaded from is com electronic components distributor MGE UPS SYSTEMS 5 Server protection 5 1 Set up of the shut
24. upsmgAgentlpAddress 12 1 0 upsmgAgentSubnetMask 12 2 0 upsmgAgentDefGateway 12 3 0 upsmgAgentType 12 6 0 upsmgAgentMibVersion 12 11 0 upsmgAgentFirmwareVersion 12 12 0 12 13 0 upsmgAgentCommUPS 1 yes 2 no THE UNINTERRUPTIBLE Network Management Card User Manual Odis com electronic components distributor 34003991EN GA PROVIDER MGE UPS SYSTEMS If the Environment Sensor is detected the following information are managed upsmgEnvironAmbientTemp 0 1 degr 8 1 0 upsmgEnvironAmbientHumidity 0 1 8 2 0 upsmgEnvironmentNum 8 6 0 upsmgEnvironmentSensorTable 8 7 0 upsmgEnvironmentEntry 8 7 1 0 upsmgEnvironmentindex 8 7 1 1 upsmgEnvironmentComFailure 1 yes 2 no 8 7 1 2 upsmgEnvironmentTemperature 0 1 degr 8 7 1 3 upsmgEnvironmentTemperatureLow 1 yes 2 no 8 7 1 4 upsmgEnvironmentTemperatureHigh 1 yes 2 no 8 7 1 5 upsmgEnvironmentHumidity 0 1 8 7 1 6 upsmgEnvironmentHumidityLow 1 yes 2 no 8 7 1 7 upsmgEnvironmentHumidityHigh 1 yes 2 no 8 7 1 8 upsmgEnvironmentinput1 State closed 1 open 2 8 7 1 9 upsmgEnvironmentinput2State closed 1 open 2 8 7 1 10 THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card User Manual 34003991EN GA 59 Downloaded from Hfcodis com electronic components distributor MGE UPS 5 7 2 2 Table des TRAPS 1 3 6 1 4 1 705 1
25. 11 SNMP traps are sent when alarms appears and desappears Level 1 informational 2 major 3 critical MIB TRAP Trap niveau upsmgBatteryFault Trap 1 Level 3 upsmgBatteryOK Trap 2 Level 1 upsmgAtLowBattery Trap 5 Level 3 upsmgFromLowBattery Trap 6 Level 1 upsmgChargerFault Trap 7 Level 3 upsmgChargerOK Trap 8 Level 1 upsmgOnBattery Trap 11 Level 2 upsmgReturnFromBattery Trap 12 Level 1 upsmgOnByPass Trap 13 Level 2 upsmgReturnFromByPass Trap 14 Level 1 upsmgUtilityFailure Trap 17 Level 2 upsmgUtilityRestored Trap 18 Level 1 upsmgOverLoad Trap 21 Level 3 upsmgLoadOK Trap 22 Level 1 upsmgOverTemperature Trap 23 Level 3 upsmgTemperatureOK Trap 24 Level 1 upsmgOffToStart Trap 29 Level 2 upsmgOfflnProgress Trap 31 Level 3 upsmgCommunicationFailure Trap 37 Level 3 upsmgCommunicationRestored Trap 38 Level 1 If the Environment Sensor is detected the following information are managed upsEnvironmentComFailure Trap 53 Level 2 upsEnvironmentComOK Trap 54 Level 2 upsEnvironmentTemperatureLow Trap 55 Level 2 upsEnvironmentTemperatureHigh Trap 56 Level 2 upsEnvironmentTemperatureOK Trap 57 Level 2 upsEnvironmentHumidityLow Trap 58 Level 2 upsEnvironmentHumidityHigh Trap 59 Level 2 upsEnvironmentHumidityOK Trap 60 Level 2 upsEnvironmentinput1 Closed Trap 61 Leve
26. 27 URL http 172 17 21 146 MGE UPS SYSTEMS LogUpsMesure csv THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card User Manual 34003991EN GA is com electronic components distributor MGE UPS SYSTEMS 29 MGE UPS SYSTEMS 4 4 Configuration The parameters of this menu can only be modified after entering the Login and Password The following screen is proposed automatically Connect to 1 2 16 1 50 User authentification User name maceups Password coocoo C Remember my password The default login and password are MGEUPS Each field accepts up to 10 characters max After the login and password are entered they remain active for 5 minutes If the browser is closed they will have to be re entered An error in either field results in systematic rejection of the requested action save page access card reboot After three unsuccessful attempts the browser must be rebooted These two fields do not travel decoded on the IT network They are encrypted with an MD5 type algorithm ensuring total confidentiality In the event of password loss the user can return to the default values via the maintenance menu THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card User Manual 34003991EN GA 30 Downloaded from dis com electronic components distributor MGE UPS SYSTEMS 4 4 1 Network settings Click on Network in the menu
27. ANAGEMENT CARD Reset Network configuration Set Login Password to Default 1 2 3 4 Return to Default Configuration 5 Exit 7 Exit enables restoration of the default configuration of all the card s parameters Configuration has been set to default one You must Reset the card THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card User Manual 34003991EN GA 53 Downloaded from dis com electronic components distributor Downloaded from 7 Appendices 7 1 Tables of alarms and events 7 1 1 Table of alarms List of time dated alarms Alarm on Battery fuse blown Battery temperature fault Battery charger fault Charger temperature fault End of Warranty Contact MGE hitp Awww mgeups com Icm End of battery life Contacter MGE_http www mgeups com Icm End of life of the wearing parts Contacter MGE_http www mgeups com Icm Chopper fault Normal AC frequency out of tolerance Normal AC fuses blown Normal AC module fault Normal AC voltage out of tolerance Bypass AC frequency out of tolerance Automatic Bypass fault Automatic Bypass overload Automatic Bypass overtemperature Bypass AC phase out of tolerance Automatic Bypass thermal overload Load not protected On Automatic Bypass Bypass AC voltage out of tolerance Load not protected On Manual Bypass Inverter limitation Inverter fuses blown Inverter fault Inverter overload Inverter overtemperature Inverter thermal overload
28. It is possible to delay outlet power on to reduce inrush currents on startup or to sequence the startup of several devices Controlled outlet startup after a given time is based on startup of the main outlet THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card User Manual 34003991EN GA 48 Odis com electronic components distributor UPS restarts when utility power is restored depending on its configuration each time a client subscribes unsubscribes 5 2 The different server and UPS shutdown sequences MGE UPS SYSTEMS 5 2 1 Extended power outage shutdown initiated by the Shutdown Timer Shutdown after During battery backup time the Shutdown Timer of the Network Management Card is reached After a user defined backup time period Shutdown parameters page the shutdown of all servers is initiated followed by the UPS shutdown depending on its configuration The Shutdown duration Maximum value of shutdown times of the Network Shutdown Modules subscribed to the card This value is updated Start shutdown main Start shutdown i Utility failure output 1 Utility NSM 1 on main output Shutdown after 1 Output 1 Shutdown duration output 1 NSM 2 on output 1 Utility restore Shutdown duration Shutdown after main output Low Battery Level Low Battery Delay THE UNINTERRUPTIBLE POWER Network Management Card User Manual 34003991EN GA
29. Load short circuit Normal AC NOK Low battery UPS communication failed UPS data base not available UPS on battery THE UNINTERRUPTIBLE Network Management Card User Manual codis com electronic components distributor MGE UPS SYSTEMS Alarm off Battery fuse OK Battery temperature OK Battery charger OK Charger temperature OK LCM message OK LCM message OK LCM message OK Chopper OK Normal AC frequency OK Normal AC fuses OK Normal AC module OK Normal AC voltage OK Bypass AC frequency OK Automatic Bypass OK Automatic Bypass load OK Automatic Bypass temperature OK Bypass AC phase OK Automatic Bypass load OK Load protected Return from Bypass Bypass AC voltage OK Inverter end of limitation Input fuses OK Inverter OK Inverter load OK Inverter temperature OK Inverter load OK Load OK Normal AC OK Battery OK UPS communication restored UPS data base OK UPS on normal AC POWER PROVIDER 34003991EN GA 54 Load not powered UPS internal fault Battery fault UPS overload lt Sensor name gt lt Sensor name gt lt Sensor name gt lt Sensor name gt lt Sensor name gt lt Sensor name gt lt Sensor name gt UPS overtemperature Imminent UPS shutoff lt Sensor name gt Temperature is above high threshold xx C Humidity is above high threshold xx Temperature is below low threshold xx C Humidity is below low threshold xx lt Input 1 la
30. Spanish Italian changes the language of the html interface pages reboot the browser after modification History log interval from 5 to 99999 sec 60 by default Measurement save period Environment log interval from 60 to 99999 sec 300 by default Temperature and humidity measurement save period Reset Communication button performs a remote reboot of the card without modifying the configuration This action is compulsory for consideration of any changes made on the Network Settings page Security of this operation is ensured by requesting Login and Password Factory Reset button enables restoration of the default configuration of all the card s parameters TCP IP parameters IP address subnet mask gateway and BootP DHCP value are maintained if the Keep TCP IP parameters option is selected Security of this operation is ensured by requesting Login and Password The default login and password are MGEUPS Export settings to file Enables exportation Download button and saving of card configuration information Import settings from file Enables selection of a configuration file Browse button and uploading Upload button of card configuration information THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card User Manual 34003991EN GA 33 Odis com electronic components distributor Downloaded from MGE UPS SYSTEMS 4 4 3 Notified Applications Click on Notified Applications in the menu
31. ard User Manual 34003991EN GA 47 Odis com electronic components distributor Downloaded from MGE UPS SYSTEMS Start shutdown Start shutdown main Utility failure outlet 1 output Utility restore VW Vv Yy V Utility f Shutdown duration i main output Outlet 1 im Shutdown i alae outlet Shutdown duration 1 NSM 1 on main output Shutdown duration 2 NSM 2 on outlet 1 Shutdown after ait duration 3 NSM 3 on main output 5 1 3 Protection of a server connected to a controlled outlet Network Shutdown Modules NSM starting with version 3 0 are compatible with the controlled outlets After connecting the server electrically to one of the controlled outlets the NSM must be informed of the outlet number to which it is connected Refer to the documentation of the NSM available on the internet site www mgeups com section Download area embedded Software 5 1 3 1 Load shedding or sequential shutdown It is possible to optimise backup time by shutting down non priority equipment or sequencing the shutdown of several devices Two shutdown criteria are possible gt Shutdown of outlets after a set battery back up time After Shutdown of outlets at a given battery discharge level if battery capacity under It is possible to specify values for both criteria The first criterion reached will initiate server shutdown 5 1 3 2 Sequential startup
32. bel gt lt when closed label gt lt Input 1 label gt lt when open label gt lt Input 2 label gt lt when closed label gt lt Input 2 label gt lt when open label gt Load powered UPS OK Battery OK MGE UPS SYSTEMS UPS returns to normal load UPS temperature OK UPS OK lt Sensor name gt seuil haut xx C lt Sensor name gt haut xx lt Sensor name gt seuil bas xx C lt Sensor name gt bas xx lt Sensor name gt lt Sensor name gt lt Sensor name gt lt Sensor name gt La temp rature est au dessus du L humidit est au dessus du seuil La temp rature est en dessous du L humidit est en dessous du seuil lt Input 1 label gt lt when closed label gt lt Input 1 label gt lt when open label gt lt Input 2 label gt lt when closed label gt lt Input 2 label gt lt when open label gt Downloaded from 7 1 2 Table of UPS events List of time dated informations Alarm on Battery fuse blown Battery temperature fault Battery charger fault Charger temperature fault End of Warranty End of battery life End of life of the wearing parts Outlet 1 open Outlet 2 open Chopper fault Normal AC switch Q1 open Normal AC frequency out of tolerance Normal AC fuses blown Normal AC module fault Normal AC voltage out of tolerance Automatic Bypass switch Q4S open Bypass AC frequency out of tolerance Automatic Bypass fault Automatic Bypass ov
33. bles the customisation of the information on the UPS properties pages MGE UPS SYSTEMS Puisar M 3000 ups UPS Properties UPS Control D Weekly Schedule Shutdown Parameters Alarm Table Logs and Notification Measurements Event Log System Log Email Notification Notified Applications Access Control Time Firmware Upload Environment Status Settings Log UPS Contact UPS Location Default Language History log interval sec Environment log interval sec Save modified settings Computer Room Manager Computer Room English x Export settings to file Download Import settings from file Parcourir Upload M Keep TCP IP parameters Reset Communication Factory Reset Ih UPS Contact This text field is limited to 49 characters Enter the name of the person responsible for UPS administration at IT network level and or electrical maintenance This field does not appear on any other Web page By default its value is Computer Room Manager UPS Location Enter a description limited to 49 characters of the location of the UPS in your installation e g Computer room E1 C066 This text is displayed in the home page By default its value is Computer Room Default Language Enables initialisation of the browser language at card connection Choice of one of the available languages English French German
34. bove high threshold lt Xxx gt C or F MGE UPS SYSTEMS Battery switch QF1 closed Manual Bypass switch Q3BP open Inverter end of limitation Input fuses OK Inverter OK Inverter load OK Inverter temperature OK Inverter load OK Output switch Q5N closed Load OK Normal AC OK Battery OK UPS communication restored UPS data base OK UPS on normal AC Load powered UPS OK Battery OK UPS returns to normal load UPS temperature OK UPS OK lt Sensor Name gt Temperature is in normal range lt Sensor Name gt Humidity is above high threshold lt xx gt lt Sensor Name gt Temperature is in normal range lt Sensor Name gt Temperature is below low threshold lt xx gt lt Sensor Name gt Temperature is in normal range C or F lt Sensor Name gt Humidity is below high threshold lt xx gt lt Sensor Name gt Temperature is in normal range lt Sensor name gt lt Input 1 label gt lt when closed label gt lt Sensor name gt lt Input 1 label gt lt when open label gt lt Sensor name gt lt Input 2 label gt lt when closed label gt lt Sensor name gt lt Input 2 label gt lt when open label gt gt 7 1 3 Table of system alarms Network Management Card startup Send test mail SUCCESS Send test mail ERROR Send mail to lt recipient gt ERROR lt Sensor name gt Communication failure lt Sensor name gt Communication restored Firmware u
35. c components distributor Downloaded from MGE UPS SYSTEMS The first shutdown criteria initiates the restart of the shutdown sequence If remaining time is under 0 to 99999 seconds 180 by default is the minimum remaining backup time from which the shutdown sequence is launched If battery capacity is under 0 to 100 this value cannot be less than that of the UPS and is the minimum remaining battery capacity level from which the shutdown sequence is launched Shutdown after 0 to 99999 minutes not validated by default is the operating time in minutes left for users after a switch to backup before starting the shutdown sequence Shutdown duration 120 seconds by default is the time required for complete shutdown of systems when a switch to backup time is long enough to trigger the shutdown sequences It is calculated automatically at the maximum of Shutdown duration of subscribed clients but can be modified in the Advanced mode If battery capacity exceeds Minimum battery level to reach before restarting the UPS after utility restoration Important Certain UPSs do not support this option For the controlled outlets group 1 or group 2 by default The page enables programming of operation time and level in backup mode to manage outlet load shedding in the event of electric power failure D Switch Off after from 0 to 99999 65535 by default defines the time during which the outlet is supplied starting from the moment of
36. can be notified see Notification parameter in the Environment Settings page MGE UPS SYSTEMS Time stamped minimum and maximum temperatures show the extreme values recorded since the last Reset Min Max a thin dotted line shows their positions on the gauge Min and Max can be forced at any time to the current value by clicking on the Reset Min Max button Calibrate The sensor is factory calibrated but the user can apply an offset to adjust the measurement Input 1 and Input 2 show the position of the two contacts acquired by the sensor The position is displayed with the parameters entered in the Environment Settings page The last status change of each contact is time stamped The Internet browser updates this page every 10 seconds THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card User Manual 34003991EN GA dis com electronic components distributor 42 Downloaded from MGE UPS SYSTEMS 4 5 3 Environment Settings MGE UPS SYSTEMS as Pulsar M 3000 UPS D UPS Properties UPS Control D Weekly Schedule Shutdown Parameters Alarm Table Environment Settings Environment sensor Logs and Notification Measurements D Event Log System Log D Email Notification Settings D Network System Notified Applications Access Control Time D Firmware Upload Environment Status Settings Log M Show advanced parameters Save
37. down parameters The Network Shutdown Module on protected server boot subscribes itself automatically to notified applications list and sends its essential data gt IP Address or hostname of the server on which it is installed So that the card can inform it of power events gt Time required to shutdown the server Shutdown Duration configurable in the Set up menu of each NSM The card takes into account the longest shutdown time of all the Network Shutdown Modules subscribed This is the Shutdown duration of the Shutdown parameters page to manage UPS shutdowns without affecting any of Shutdown Modules connected During normal operation the Network Shutdown Module periodically checks its connection with the card In case of a major power event the card sends information to the Network Shutdown Module which reacts according to the situation shutdown order programmed actions messages to the administrator and to users via the network When the server shuts down the Network Shutdown Module unsubscribes itself from the notified applications 5 1 1 Shutdown criteria managed by the Network Management Card During an extended power failure three criteria may cause the server shutdown procedure to be initiated If several criteria are selected See page Shutdown parameters the first criterion encountered will launch the shutdown procedure At the end of the shutdown procedure when all servers have been shut down the UPS may
38. een LED connection activity Ethernet port IMGE UPS SYSTEMS a MAC adresse LED Colour Activity Description ACT Green b Off Card not connected to the network gt On Card connected to the network but without activity Port is active in receiving Flashing transmission 100M Orange D Off Port operating at 10Mbits s On Dd Port operating at 100Mbits s TH Downloaded from E UNINTERRUPTIBLE POWER PROVIDER Odis com electronic components distributor Network Management Card User Manual 34003991EN GA 10 MGE UPS SYSTEMS Service port Colour b Off gt Card startup in progress gt Communication with UPS in progress gt Normal operation Communication with the UPS is operational gt Configuration menu is active Normal operation Configuration menu is deactived Communication with the Environment Sensor option D On Flashing RS232 Orange D Off On Flashing 2 1 3 Installation in the UPS The Network Management Card 66102 can be hot installed in all UPSs of the MGE UPS SYSTEMS range equipped with a Minislot without having to shut it down Remove the protective plastic cover from the Minislot Note the card s MAC address prior to insertion Insert and tighten the card s retaining screws Connect the ETHERNET cable Wait 2 min the card is comp
39. erload Automatic Bypass overtemperature Bypass AC phase out of tolerance Automatic Bypass thermal overload Load not protected On Automatic Bypass Bypass AC voltage out of tolerance THE UNINTERRUPTIBLE Network Management Card User Manual Odis com electronic components distributor POWER 34003991 EN GA Alarm off Battery fuse OK Battery temperature OK Battery charger OK Charger temperature OK LCM message OK LCM message OK LCM message OK Outlet 1 closed Outlet 2 closed Chopper OK Normal AC switch Q1 closed Normal AC frequency OK Normal AC fuses OK Normal AC module OK Normal AC voltage OK Automatic Bypass switch Q4S closed Bypass AC frequency OK Automatic Bypass OK Automatic Bypass load OK Automatic Bypass temperature OK Bypass AC phase OK Automatic Bypass load OK Load protected Return from Bypass Bypass AC voltage OK PROVIDER 55 Downloaded from Battery switch QF1 open Manual Bypass switch Q3BP closed Load not protected On Manual Bypass Inverter limitation Inverter fuses blown Inverter fault Inverter overload Inverter overtemperature Inverter thermal overload Output switch Q5N open Load short circuit Normal AC NOK Low battery UPS communication failed UPS data base not available UPS on battery Load not powered UPS internal fault Battery fault UPS overload UPS overtemperature Imminent UPS shutoff lt Sensor Name gt Temperature is a
40. f the UPS are a e Normal operation e ok e Alarm present This icon links directly to the alarm A page e alarm THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card User Manual 34003991EN GA Downloaded from Hfeodis com electronic components distributor 15 MGE UPS SYSTEMS e Utility power present e Battery operation e Battery fault Be e Loss of communication with the UPS green outlet e Outlet powered Outlet not powered or not protected amp red outlet Communication indicates the status of the communication between the card and the UPS Power source indicates whether the power comes from the utility or from the UPS battery Batteries indicates whether the battery is being charged discharged or is faulty Output load level indicates the power percentage used at UPS output Master output indicates if the UPS output is protected Controlled outlets indicates if the controlled outlets if available are powered 4 2 1 3 Battery status zone Bargraph graph showing the remaining battery charge in percent Battery charge level remaining battery charge in percent Remaining backup time Estimation of the battery s maximum backup time remaining before UPS shutdown Last periodic test Result of the last automatic battery test carried out by the UPS Possible values are OK the test was completed correctly
41. fies the source of the message The default value is ups domain com This field is free However depending on the type of SMTP server configuration it is possible that the server checks that the domain name contained in the Sender address exists and even that the user in the Sender address belongs to this domain Subject enables the user to specify the subject of the e mail to be sent By entering some free text and selecting from several optional fields if desired the message subject is built UPS name recalls the name of the UPS it may or may not be selected UPS location recalls the geographic location of the UPS see System Settings it may or may not be selected Event message identifies the event generating the e mail it may or may not be selected Message text is a free zone The body of the e mail sent is composed of Message text which is free text The date and time of the event as saved in the log URL of the card enabling a direct link with the card to be established Attachments as configured for the e mail recipients duplication of the subject as configured THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card User Manual 34003991 EN GA 28 dis com electronic components distributor Downloaded from ups domain com 4 patrick vincent Objet MGE UPS SYSTEMS Extreme cc 1000 MGE UPS SYSTEMS Extreme 1000C Computer Room Test message Date 2006 02 13 Time 14 24
42. i Windows Unix Novell MacOSX Network connection Network Shutdown Module gt vs a z i Environment sensors Y q gt 1 1 1 Connecting the UPS to the Ethernet network This function can be performed either through network Cards inserted in the UPS Network Management Card or through a software agent running on a nearby PC that is called the Network Management Proxy The Network Management Card or Proxy manages communication with the UPS as well as local protection of the machine on which Proxy is installed periodically accesses the information concerning the UPS makes this information available to the connected applications Network Shutdown Modules Web Browser Network Management Systems Enterprise Power Manager sends notifications on certain events Operation may be in standard secure mode the default mode or in SSL secure mode Secure Socket Layer SSL THE UNINTERRUPTIBLE POWER PROVIDER 4 Network Management Card User Manual 34003991EN GA Downloaded from dis com electronic components distributor Downloaded from MGE UPS SYSTEMS 1 1 2 Protection of the computers servers This function is performed by the Network Shutdown Module installed on each of the servers to be protected Note that the Shutdown Module is available on several Operating Systems The Network Shutdown Module continuously waits for information from the Network Management Card Proxy connected t
43. initiated by the Low battery power message 49 5 2 3 Case of power restoration before the end of the shutdown duration counter 50 6 CONFIGURATION VIA RS232 51 6 1 CHOICE 1 RESTART RESET 51 6 2 CHOICE 2 NETWORK CONFIGURATION 51 6 2 1 Choice 1 Read Network settings 52 6 2 2 Choice 2 Modify Network settings 52 6 3 CHOICE 3 LOST PASSWORD SET LOGIN PASSWORD TO DEFAULT 52 6 4 CHOICE 4 RETURN TO DEFAULT CONFIGURATION 53 7 APPENDICES 54 7 1 TABLES OF ALARMS AND EVENTS 54 7 AA Table of alarms 54 7 1 2 Table of UPS events 55 7 1 3 Table of system alarms 56 7 2 SNMP OBJECTS 57 7 2 1 MGE MIB 57 7 2 2 Table des TRAPS 1 3 6 1 4 1 705 1 11 60 8 GLOSSARY 61 THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card User Manual 34003991EN GA Downloaded from Hfcodis com electronic components distributor MGE UPS SYSTEMS 1 MGE Network Solution 1 1 General Presentation MGE Network Solution gt provides information on events concerning the supply of power to the computers connected to your computer network gt carries out automatic shutdown of computer systems J monitors and controls all the UPSs connected to the network As illustrated in the picture below MGE Network Solution provides these 3 main functions gt supervision of the UPSs over the Network gt protection of the computers gt connexion of the UPS to the Network Supervision Protection
44. is exceeded a notification is sent if this is validated The default value is 5 Hysteresis must be set to prevent multiple notifications if humidity fluctuates around a threshold The default value is 5 The high alarm disappears when the value drops below the High threshold Hysteresis value The low alarm disappears when the value returns above the Low threshold Hysteresis value Input 1 and Input 2 Enter an identifier corresponding to the acquired contact e g rack door air conditioning generator unit etc Max length is 28 characters when closed and when open are the names associated to the two contact positions e g open and closed for a door On and Off for a generator Each status change triggers a notification if enabled When the Notification box is enabled the following functions are activated for each event selected display in the list of current alarms Consideration in the UPS log SNMP trap generation notification by e mail if the Environment sensor notification option is enabled in the e mail notification page The list of messages is given in the appendix System shutdown can be triggered for each notification if this option is enabled If notification is disabled the Shutdown option cannot be used Export settings to file Enables exportation Download button and saving of card configuration information Import settings from file Enables selection of a configuration file Browse button and
45. l 2 upsEnvironmentinput1 Open Trap 62 Level 2 upsEnvironmentInput2Open Trap 64 Level 2 upsEnvironmentinput2Closed Trap 63 Level 2 The level is used to select traps to be sent to the supervisor This adjustment is available from the Notified applications page THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card User Manual 34003991EN GA Downloaded from Hfcodis com electronic components distributor Downloaded from MGE UPS SYSTEMS 8 Glossary Bootp Protocol based on UDP used to allocate an IP address corresponding to an Ethernet card during the startup phase Defined by the RCF 951 Community name Access key to access SNMP agent information DHCP Dynamic Host Configuration Protocol This IETF protocol enables remote automatic self configuration of the IP addresses of a workstation DNS Domain Name Sevicel The DNS protocol ensure correspondence between the name of a machine and its IP address E mail Electronic means of transmitting messages and or files Gateway Interconnection equipment between networks with different conventions to enable communication between them HTML HyperText Markup Language Language used to describe hypertext pages on the web HTTPS is the secure version of HTTP the communication protocol of the World Wide Web It was invented by Netscape Communications Corporation to provide authentication and encrypted communication and is used in
46. letely operational when the green UPS Data LED flashes continuously 2 1 4 Sensor installation option The Environment sensor is available as an option on the Network Management Card and is available from MGE UPS SYSTEMS reference 66846 The sensor allows remote monitoring of the UPS s environment through regular measurements temperature humidity status of two external contacts It also enables notification of alarms e mail trap SNMP according to pre programmed thresholds It is connected to the Service port Settings Sensor directly on the Network Management Card with a standard Ethernet cable 20 meters maximum Recognition is automatic Supervision and configuration are performed via a menu that can be accessed directly from the home page ETHERNET THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card User Manual 34003991EN GA 11 Downloaded from Hfcodis com electronic components distributor Downloaded from MGE UPS SYSTEMS 3 Configuration 3 1 1 Configure IP parameters Once the card has started Connect one end of the cable 34003918 to the Service port If the environment sensor was previously connected the card must be restarted in order to access the configuration menu Connect the other end of the cable to the COM port IOIOI of a PC Launch a HyperTerminal type emulator with the following configuration Speed 9600 Data bits 8 Parity none Stop bits 1 Flow c
47. ll only be sent to DNS if the DHCP server sends it the hostname with the new IP address This mechanism is described in the update of the DNS protocol RFC 2136 Domain Name is the domain to which the card belongs This is the part of the fully qualified domain name that follows the hostname and is used by the DNS The default value of the two parameters comprising the fully qualified domain name ups domain com BOOTP DHCP Authorises choose Enabled configuration of network parameters with your BootP DHCP server when the card is booted Mode of card operation with server After each startup the card makes 5 attempts to recover the network parameters If no response is THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card User Manual 34003991EN GA 31 Downloaded from dis com electronic components distributor Downloaded from MGE UPS SYSTEMS received from the server the card boots with the last saved parameters from the previous start These parameters are those shown on the page The default value for this parameter is Enable Note 1 If the hostname is not used the IP address supplied by the DHCP server must be fixed to maintain connection with the clients installed on the stations to be protected Note 2 During the first connection if the DHCP query is not successful the NMC starts with the following IP configuration IP address 172 17 16 16 Subnet mask 255 255 255 0 Gateway Address 0 0 0 0 Firm
48. n or Web browser They also supply alarms to the Network Shutdown Modules to trigger shutdown or other automatic actions for protected servers Network Management Cards are compatible with the Enterprise Power Management supervision system and with the MGE UPS SYSTEMS network protection system D Network Shutdown Module Entreprise Power Manager Dd Management Pac 2 THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card User Manual 34003991EN GA 6 Odis com electronic components distributor Downloaded from MGE UPS SYSTEMS 1 2 2 Direct sending of E mail When a UPS event occurs the Network Management Card can directly notify up to 4 intranet or extranet addresses by e mail see E mail Notification and E mail message settings 1 2 3 Sending text messages SMS The card offers the possibility of redirecting UPS alarms to an e mail server The format of these e mails is compatible with mobile telephone e mail SMS transfer systems proposed by ISPs The format to be used depends on the service provider For example sms 0660256585 votre login activmail net text messages 1 2 4 Compatibility with the Network Managment Systems NMS Trap sending The Network Management Cards are compatible with the major Network Management Systems IBM Tivoli CA Unicenter HP Insight Manager The Management Pac 2 offering includes the necessary SNMP plug ins to allow an easy integration in the NMS Events are
49. ng the shutdown procedure when the battery level is lower than If Capacity under When the card detects that the remaining backup time percentage is less than the configured level the shutdown sequence is started By default this value is set at 20 Note The UPS already manages an equivalent parameter for the end of backup pre alarm The card does not accept values less than that programmed in the UPS Check the UPS documentation 5 1 1 3 Shutdown when backup time is less than When the Network Management Card detects that the percentage of backup time remaining is less than the value set the shutdown sequence is started 5 1 1 4 Shutdown duration Duration in seconds required for the system protected by the Shutdown Modules to shut down The Network Shutdown Modules transmit their own Shutdown duration to the Network Management Card Based on these values maximum Shutdown duration of all subscribed customer systems that the card will send to the delayed shutdown order to the UPS 5 1 2 Controlled outlets Certain UPS models are equipped with controlled outlets generally 2 which are always dependant on the UPS s main outlet Shutdown of the main outlet systematically causes shutdown of the programmable outlets The following notations are used to identify these outlets D Main outlet Main gt Controlled outlet 1 1 gt Controlled outlet 2 2 THE UNINTERRUPTIBLE POWER PROVIDER Network Management C
50. notified by SNMP trap NMS can subscribe on page Notified Applications gt The trap list is given in the appendix 1 2 5 Environment Sensor option The Environment Sensor 66846 solution comprises a box to be connected to the Card Settings port of the Network Management Cards Environment Sensor enables measurement of temperature and humidity around the UPS consideration of external alarms via 2 dry contacts and notification of alarms according to pre programmed thresholds see Environmen Status and Environment Configuration 1 3 Technical data 1 3 1 Hardware characteristics Dimensions gt Dimensions Lx x H 132 x 66 x 42 mm gt Weight gr 70 g Storage Storage temperature 10 C to 70 C Ambient conditions Operating temperature 0 to 40 C gt Ambient humidity 90 RH max without condensation RoHS 100 compatible 1 3 2 EMC Compatibility When correctly installed and used in accordance with the manufacturer s instructions the Network Management Card complies with the following standards Safety for ATI IEC EN 60950 1 2002 EMC EN 61000 6 2 2002 EN 61000 6 3 2002 IEC EN 62040 2 2002 As per European directives Low voltage 73 23 EEC and 93 68 EEC THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card User Manual 34003991EN GA Sie Odis com electronic components distributor MGE UPS SYSTEMS EMC 89 336 EEC and 93 68 EEC 1 3 3 C
51. o 70 C with 1 C accuracy Measurement of humidity from 0 to 100 with 6 accuracy Min max time stamped function for temperature and humidity Choice of temperature readings in Celsius or Fahrenheit High and low thresholds hysteresis and offset adjustable via Web interface THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card User Manual 34003991EN GA 8 Downloaded from Hfeodis com electronic components distributor Name and status of each configurable contact Recording of events and measurements in the card log Hot installation 1 3 7 MIB Management Information Base gt Compatible with MIB MGE V1 7 The list of objects managed can be found in the appendix 1 3 8 Default parameters MGE UPS SYSTEMS Possibility of notification of status changes by e mail SMS or SNMP trap Position detection of 2 dry contacts maximum sensor contact distance 20 m Connection to the card with straight CAT5 RJ45 network cables maximum card sensor distance 20 m Possibility of shutting down the installation in the event of a threshold being exceeded or on opening closure of a dry contact UPS Location Computer Room Function Parameter Default value Possible value Network IP address 172 17 16 16 Network IP address Subnet mask 255 255 0 0 Network IP address Gateway Address 0 0 0 0 Network IP address BOOTP DHCP Enabled Active Deactivated Firmware Upload Enabled Active Deactivated SMTP server sm
52. o the MGE UPS warns administrators and users if AC power fails and proceeds with graceful system shutdown before the end of battery backup power is reached 1 1 3 Supervision of the UPSs over the network Depending on your needs you can either use your Internet browser to monitor each UPS as Management Proxy and Management Card include a Web server your company s standard Network Management System HP Openview CA Unicenter HP Insight Manager IBM Tivoli Netview To simplify integration of MGE UPSs you can use one of the Network Management System Kits for MGE devices These kits are available on the Management Pac 2 CD ROM ref 66923 the MGE supervisor Enterprise Power Manager network 1 1 4 Connection Before installing the MGE Network Solution the UPS must be set up as indicated in the steps below Shut down the computers to be protected by the UPS Connect the UPS to a wall outlet For UPSs above 3kVA please refer to the UPS installation manual Connect the power cord of each computer to an outlet on the UPS For UPSs above 3kVA please refer to the UPS installation manual POWER PROVIDER THE UNINTERRUPTIBLE Network Management Card User Manual 34003991EN GA dis com electronic components distributor Downloaded from MGE UPS SYSTEMS 1 1 4 1 How to connect UPS agent network Insert the optional card in the UPS and connect the UPS to the computer network Start the MGE UPS then
53. onfiguration The user can configure the card with one of the following means gt Web browser Local serial link network parameters BOOTP DHCP network parameters 1 3 4 Administration Up to 50 workstations protected by Network Shutdown Modules Central or local configuration Up to 5 browsers connected at the same time 3 in SSL Minimum recommended browser versions Internet Explorer 6 x Mozilla Firefox 1 5 Netscape 6 x E mail sending configurable according to UPS alarms and transmission of a periodical report Control of UPS on off switching via the HTML interface Adjustment and control of PowerShare outlets via the HTML interface sequential starting of the installation and optimisation of backup time by shutting down non priority systems Automatic data and time adjustment via NTP server Protection by encrypted password Protection by secure SSL connection Saving of logs in the non volatile memory Languages available English French Spanish German Italian On line help in English available for each page Card firmware updated via the network 1 3 5 Network Fast ETHERNET 10 100 Mbits compatibility with auto negotiation on the RJ45 outlet 1 3 5 1 List of ports used gt BootP DHCP UDP 68 67 gt HTML TCP 80 SSL TCP 443 NSM connection TCP 5000 gt SMTP 25 gt NTP 123 gt SNMP V1 161 gt TRAP SNMP 162 1 3 6 Environment sensor Temperature measurement from 0 t
54. ontrol none Locally reproduce the characters entered option deactivated Enter MGEUPS or mgeups The main menu is displayed MGE UPS SYSTEMS NETWORK MANAGEMENT CARD Network configuration Set Login Password to Default Return to Default Configuration 3 1 1 1 Your network is equipped with a DHCP server The card is configured by default with this service activated The card automatically collects IP parameters To know the IP parameters type 2 then type 1 The menu is displayed Network configuration Mode DHCP MAC address 000623001C07 IP address 172 17 23 18 Subnet mask 255 255 248 0 Gateway 172 17 17 1 Note the IP address To exit enter 3 then 7 The card is operational Note As long as the card is not connected to the network it continuously attempts to make connection Once the connection has been established the operational mode presented in the table above becomes effective 3 1 1 2 Your network is not equipped with a DHCP server In the main menu enter 2 then 2 again Follow the instructions and enter the static IP parameters THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card User Manual 34003991EN GA Odis com electronic components distributor Downloaded from MGE UPS SYSTEMS At the end of the menu wait for the Done message to be displayed indicating that the IP parameters have been saved 1 Read Network settings 2 Modify Network settings
55. own parameters section in the menu to see the list of parameters MGE UPS SYSTEMS Pulsar M 3000 E UPS Shutdown Parameters UPS Properties UPS Control Weekly Schedule Shutdown Parameters Alarm Table Logs and Notification Master gt Measurements gt Event Log System Log Email Notification Shutdown duration fi 20 sec See also additional Shutdown configuration on Environment Settings Shutdown duration fi 20 sec Settings Network System Notified Applications Access Control Time Firmware Upload Shutdown duration fi 20 sec nm Environment Show advanced parameters Status Settings Save modified settings Save Log Export settings to file Download Import settings from file Parcourir Upload When you tick the Show advanced parameters option extra parameters are displayed These parameters enable in particular adjustment of certain thresholds related to the percentage of remaining battery charge level The Output column enables each outlet to be named maximum 20 characters Note As priority is given to the main outlet the card cannot supply the controlled outlets when main outlet power is off For the main outlet Master by default THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card User Manual 34003991EN GA 21 Downloaded from ydis com electroni
56. pgraded THE UNINTERRUPTIBLE Network Management Card User Manual Odis com electronic components distributor POWER PROVIDER 34003991 EN GA 56 Downloaded from 7 2 SNMP objects 7 2 1 MGE MIB The NMC card implement reduce MGEUPS MIB with the objects bellow managed The entire MIB description is available on www mgeups com area Download area embedded Softwares Le chemin d acc s la MIB MGEUPS est 1 3 6 1 4 1 705 1 MGE UPS Network Management Card User Manual Odis com electronic components distributor 34003991EN GA MIB object SNMP Format Add path upsmgldentFamilyName String 1 1 0 upsmgldentModelName String 1 2 0 upsmgldentSerialNumber String 1 7 0 upsmgldentFirmwareVersion String 1 4 0 upsmgConfigLowBatteryTime seconds 4 7 0 upsmgConfigLowBatteryLevel 4 8 0 upsmgConfigAutoRestart 1 yes 2 no 4 9 0 upsmgConfigVARating VA 4 12 0 upsmgBatteryRemainingTime seconds 5 1 0 upsmgBatteryLevel 5 2 0 upsmgBatteryVoltage deciVolts 5 5 0 upsmgBatteryCurrent deciAmps 5 6 0 upsmgBatteryFaultBattery 1 yes 2 no 5 9 0 upsmgBatteryReplacement 1 yes 2 no 5 11 0 upsmgBatteryLowBattery 1 yes 2 no 5 14 0 upsmgBatteryChargerFault 1 yes 2 no 5 15 0 upsmgBatteryLowCondition 1 yes 2 no 5 16 0
57. r a periodic e mail containing the 3 log files can be sent to the recipient every x days at the time specified by the user To configure the first transmission specify the day time and frequency of the next transmission in the next report box After this date the page will show the date and time of the next transmission Data are sent in CSV format Save Saves any modifications Test enables an e mail to be sent to the recipient immediately This is one way of checking e mail transmission particularly access to the SMTP server configured in Network settings A transmission report is added to the system log The event label in the subject and text of the message is replaced with a test label If the user makes any modifications to the page they must be saved before using the Test function Notified events The right side of the page shows the events that can be notified By default only the main events of battery operation and a few UPS alarms are accessible All the events appear if the Show Hide Events option is actuated By default two events are selected for notification The user can modify this pre selection by ticking other events or can on the contrary restore the initial configuration by clicking Set Default Email Message Settings access to the message configuration page Network Settings enables the name of the SMTP server to be entered See page Export settings to file Enables exportation Download button and sa
58. rd to run the new firmware POWER PROVIDER 34003991EN GA dis com electronic components distributor 40 MGE UPS SYSTEMS 4 5 Environment Sensor option The environment sensor 66846 is an option that enables temperature and humidity to be measured and indication of the position of two external contacts It is connected with a standard network cable to the Card Settings port of the Network Management Card The card automatically detects sensor presence The main menu then displays an additional section Environment with the following elements gt Status gt Configuration Log Important note To switch the serial port to the configuration mode just disconnect the cable and reset the card 4 5 1 Characteristics Temperature measurement from 0 to 70 C with 1 C accuracy Measurement of humidity from 0 to 100 with 6 accuracy Min max time stamped function for temperature and humidity Choice of temperature readings in Celsius or Fahrenheit High and low thresholds hysteresis and offset adjustable via Web interface Possibility of notification of status changes by e mail SMS or SNMP trap Position detection of 2 dry contacts maximum sensor contact distance 20 m Name and status of each configurable contact Recording of events and measurements in the card log Possibility of shutting down the installation safely if one of the thresholds is exceeded or dry contact status change Connection
59. re Test Two alarms Utility failure and Utility restored spaced 60 seconds apart will be sent to the applications selected making sure that the applications can be reached over the network Shutdown Test This test simulates a UPS on battery operation It enables an easy check to see if the server protection works correctly No intervention on the UPS is required The applications selected will process the simultaneous alarms and perform an actual shutdown sequence WARNING This test will generate a REAL shutdown sequence of the selected servers on which the Network Shutdown Module application is running D Add NMS allows an SNMP trap receiver to be added such as a Network Management System D Modify NMS allows an SNMP trap receiver to be modified Both buttons open a new window where it is possible to enter the Application name the Hostname or IP Address the Trap community and the severity MGE UPS SYSTEMS Pulsar M 3000 UPS Network Management System UPS Properties UPS Control D Weekly Schedule Nr Shutdown Parameters 1 Application Name HP OV server b Tabl Alarm Tabie Hostname or IP address 172 17 23 126 Logs and Notification Protocol SNMP Y1 Measurements Event Log Trap Community public System Log Severity fi Warning 7 Email Notification Settings Cancel Save D Network System Notified Applications Access Control Time Firmware
60. s Settings Log Enter New Manager Login Enter New Password Confirm New Password Current Community Read Only is Change Community Read Only Security mode Save modified settings Access Control Maus public public Authentication for configuration Full authentication SSL and full authentication Save Export settings to file Download Import settings from file Parcourir Upload Network Management Card User Manual Login This text field is limited to 10 characters Enables secure access and modification of pages Default value MGEUPS Change Confirm password This text field is limited to 10 characters Enables secure access to Configuration menu pages Default value MGEUPS Current Community Read name Indicates the SNMP community name used for read operations Change Community Read Only This text field is limited to 49 characters Enables the SNMP community name used for read operations to be changed Security mode manages the various authentication methods for page access Authentication for configuration Only the configuration pages are protected by login password D gt Full authentication All pages are protected by login password gt SSL and full authentication All pages are protected by login password and are only accessible in SSL SSL Access When selected access to the Web interface is made in secure mode https
61. s informations on the battery autonomy Refresh The Web browser refreshes this page every 10 seconds Settings Network Alarm triangle If an alarm appears a red triangle is displayed Click on it to see the current alarm page System When there is no alarm the green OK icone is displayed Notified Applications Access Control Time Firmware upload Environment Status Settings Log THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card User Manual 34003991 EN GA s com electronic components distributor 17 Downloaded from MGE UPS SYSTEMS 4 2 3 UPS control Click on the UPS Control section in the menu UPS configuration may prevent the shutdown and restart commands from being properly run Read the UPS user manual for more information MGE UPS SYSTEMS Es UPS UPS Control D UPS Properties UPS Control D Weekly Schedule D Shutdown Parameters Puisar M 3000 Toggle Duration Alarm Table Master on Safe power down amp reboot Logs and Notification D Measurements Group On None z Event Log System Log Group2 on None x D Email Notification Settings Network Execute Save System D Notified Applications Access Control Time R D Firmware Upload Environment Status Settings Log This page enables triggering of startup and shutdown sequences for the UPS main output and con
62. shut down to avoid unnecessary discharge of its batteries depending on its configuration Utility failure Start of the shutdown sequence UPS Shut off Shutdown after i Battery capacity Delay before shutdown 100 i gt Remaining autonomy f i If remaining time under i ee Shutdown if Shutdown duration remainig capacity under t Card parameters UPS parameters 0 THE UNINTERRUPTIBLE POWER PROVIDER 46 Network Management Card User Manual 34003991EN GA Downloaded from Hfeodis com electronic components distributor Downloaded from MGE UPS SYSTEMS 5 1 1 1 Backup time before initiating the shutdown procedure Shutdown After Shutdown Timer When the UPS switches to battery the Network Management Card starts the Shutdown Timer countdown and launches the system shutdown procedure at the end of the countdown This value must be chosen so that users have time to complete their tasks and disconnect without exceeding battery backup time Note 1 The Network Shutdown Module can also manage its own Shutdown Timer configurable in the Shutdown Module set up menu of each Network Shutdown Module launched when the UPS switches to battery Note that if this criterion is selected to initiate system shutdown automatic system reboot when power is restored is not guaranteed e g power restoration if only this system was shut down 5 1 1 2 Initiati
63. t address 255 0 0 0 Class B internet address 255 255 0 0 Class C internet address 255 255 255 0 TCP IP Transmission Control Protocol Internet Protocol Common name of a series of protocols developed by the DOD in the US to help build Internet networks throughout the world Telnet Internet protocol used for terminal emulation i e enabling a computer to connect with a server as if it was a simple terminal locally connected to this server Trap SNMP This term describes an event that affects an MIB variable Traps are sent to the manager which is programmed to perform specific tasks upon reception of the THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card User Manual 34003991EN GA 62 Odis com electronic components distributor Downloaded from traps THE UNINTERRUPTIBLE Network Management Card User Manual is com electronic components distributor POWER 34003991EN GA UPS SYSTEMS PROVIDER 63
64. the card DB9 RJ45 cable 1 8 m max fr aT Wy SH temale 089 male Rus 4 a i connector connector female DB9 T naka male RJ45 connector cable connector Connect the card to a computer equipped with a hyperterminal type emulator The serial link must be set at 9600 baud 8 bits no parity 1 stop bit and without flow control Check that UPS power is on gt Enter the MGEUPS or mgeups password non modifiable gt The menu is in English only MGE UPS SYSTEMS NETWORK MANAGEMENT CARD Reset Network configuration 1 2 3 Set Login Password to Default 4 Return to Default Configuration 5 Exit 6 1 Choice 1 Restart Reset Use this function to restart the card two choices are possible 1 Hardware Reset Equivalent to a restart of the electrical power supply 2 Restart application Restarts only the application part 1 Hardware Reset 2 Restart application 3 Exit 6 2 Choice 2 Network Configuration Use this function to access network settings THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card User Manual 34003991 EN GA 51 Downloaded from dis com electronic components distributor MGE UPS SYSTEMS 1 Read Network settings 2 Modify Network settings 3 Exit 6 2 1 Choice 1 Read Network settings Enables reading of the card s routine settings Network configuration Mode DHCP IP address 172 17 21 209 Subnet mask 255
65. the computers 1 1 4 2 Setting up the protection Set up the Network Management Card see user manual Install and configure the Network Shutdown Module on all machines that are to be protected by the UPS The software components for each platform and the user manuals are on the Solution Pac 2 CD or are available for download on the www mgeups com Web site in the Download area section 1 2 Presentation of the Network Management Card NMC 1 2 1 Compatibility with UPSs The Minislot Network Management Card is compatible with the following UPSs Pulsar Evolution 500 800 1100 From technical level 06 Pulsar Evolution 2200 3000 From technical level 05 Pulsar Evolution 1500 From technical level 05 EXtreme C 700 1000 1500 From technical level B2 EXtreme C 2200 3200 From technical level 02 Pulsar EX 700 1000 1500 RT US From technical level 03 Pulsar EX 2200 3200 US From technical level 09 Pulsar M 2200 3000 All models Pulsar 700 1000 1500 All models Note If the UPS s NT is below that indicated in the table above contact MGE s technical support The Network Management Card 66102 is not compatible with Pulsar EX 7 10 Pulsar EX 15 20 30 Pulsar ESV 8 11 14 22 ranges Network Management Cards acquire information on the operation status of the UPS systems and provide remote control of these systems by means of an ETHERNET network from any SNMP administration statio
66. to the Network Management Card by CAT5 straight RJ45 network cables maximum card sensor distance 20 m THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card User Manual 34003991EN GA 41 Downloaded from Hfeodis com electronic components distributor Downloaded from 4 5 2 Environment Status MGE UPS SYSTEMS Puisar M 3000 UPS Environment Status UPS Properties UPS Control D Weekly Schedule Shutdown Parameters Alarm Table Logs and Notification Measurements D Event Log D System Log D Email Notification Settings D Network D System D Notified Applications Access Control Time D Firmware Upload Environment Settings Log orc 22 6 C 70 C Min 18 9 recorded on 2006 03 15 04 24 32 Max 29 5 recorded on 2006 03 14 16 45 37 A i Configure thresholds on Feaci EGER Environment Settings 0 23 0 100 Min 18 4 recorded on mN 4 16 49 17 Max 90 2 recorded on 2006 03 14 16 45 37 A P Configure thresholds on Reset Min Max Calibrate Environment Settings 1970 01 01 00 00 00 Input 1 open 2006 03 15 09 01 19 Input 2 open For both measurements a graduated gauge proposes the following functions The cursor indicates the current value Two red zones to the left and right represent the high and low thresholds that can be set on the Environment Settings page When the measured value enters one of these zones an alarm
67. tpserver 31 characters maximum System UPS Contact Computer Room Manager 49 characters maximum 49 characters maximum History log interval sec 60 5 to 99999 sec Environment log interval sec 300 60 to 99999 sec Default Language English English French Spanish German Italian Manager table empty 50 maximum Access control User name MGEUPS 10 characters maximum Password MGEUPS 10 characters maximum Community name read public 49 characters maximum Trap port 161 Non configurable Date and time Date and time adjustment Synchronise with an NTP server Synchronise with an NTP server Synchronise manually Downloaded from Hfcodis com electronic components distributor NTP server pool ntp org 49 characters maximum Serial link Speed 9600 baud Non configurable Data bits 8 Non configurable Stop bits 1 Non configurable Parity without Non configurable Flow control without Non configurable THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card User Manual 34003991EN GA 9 2 Installation 2 1 1 Unpacking and check on contents The installation kit contents gt A Network Management Card 66102 A serial communication cable for configuration 34003918 Installation manual 34003905 2 1 2 Indications ETHERNET 10 100BT port Service port Settings Sensor Orange LED RS232 activity Green LED communication with the UPS Orange LED 10 100M Gr
68. trolled outlets gt The status of each output is displayed by a symbol associated with the Off label red symbol or On green symbol gt The shutdown sequences take into account the time required for the registered servers to shut down without losing data see shutdown parameters gt The main outlet has priority over the controlled outlets Shutdown of the main outlet causes the controlled outlets to shut down Controlled outlets can only be started if the master outlet is on The Check column proposes six different commands and a command is only actually started after clicking on Execute Safe power down A sequence to switch off output power is launched immediately The systems supplied are shut down correctly while the shutdown sequence is running then the output is cut Safe power down amp reboot A sequence to switch off then restore output power is launched immediately The powered systems are shut down correctly during the shutdown sequence then the output is switched off Finally the restart sequence is launched at the end of the time delay specified in the Toggle duration parameter The output status is updated THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card User Manual 34003991EN GA 18 dis com electronic components distributor MGE UPS SYSTEMS Immediate On A sequence to switch on output power is launched immediately The output is re powered and the systems supplied start up
69. up if the card is in manual mode or if no NTP server was reached the card initializes at 01 01 1970 THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card User Manual 34003991EN GA 39 dis com electronic components distributor Downloaded from MGE UPS SYSTEMS 4 4 7 Firmware upload Click on Firmware Upload in the menu This menu enables a new firmware version to be uploaded MGE UPS SYSTEMS Puisar M 3000 ups UPS Properties x z UPS Control Firmware to Upload Upload Weekly Schedule Shutdown Parameters Alarm Table Logs and Notification Measurements Event Log System Log Email Notification l Parcourir WARNING This action takes a few minutes To upload a new version of the card s firmware select the file to be loaded using the Browse button and click Upload Do not interrupt the operation before the card displays the following screen MGE UPS SYSTEMS Puisar M 3000 UPS Firmware Upload D UPS Properties Firmware to Upload UPS Control D Weekly Schedule Shutdown Parameters Alarm Table Logs and Notification Measurements Event Log System Log Email Notification Network Management Card User Manual THE UNINTERRUPTIBLE L Parcourir _Upload WARNING This action takes a few minutes SUCCESS Fimware was successfully written in FLASH You have to restart the ca
70. upsmgInputPhaseNum 6 1 0 mginputIndex_1 6 2 1 1 1 0 mginputIndex_2 6 2 1 1 2 0 mginputIndex_3 6 2 1 1 3 0 mginputVoltage_1 DeciVolts 6 2 1 2 1 0 mginputVoltage_2 DeciVolts 6 2 1 2 2 0 mginputVoltage_3 DeciVolts 6 2 1 2 3 0 mginputFrequency_1 DeciHz 6 2 1 3 1 0 mginputFrequency_2 DeciHz 6 2 1 3 2 0 mginputFrequency_3 DeciHz 6 2 1 3 3 0 mginputCurrent_1 DeciAmps 6 2 1 6 1 0 mginputCurrent_2 DeciAmps 6 2 1 6 2 0 mginputCurrent_3 DeciAmps 6 2 1 6 3 0 upsmgInputBadStatus 6 3 0 upsmgOutputPhaseNum 7 1 0 mgoutputPhaselndex_1 7 2 1 1 1 0 mgoutputPhaselndex_2 7 2 1 1 2 0 mgoutputPhaselndex_3 7 2 1 1 3 0 mgoutputVoltage_1 deciVolts 7 2 1 2 1 0 THE UNINTERRUPTIBLE POWER PROVIDER lt 57 Downloaded from MGE UPS SYSTEMS mgoutputVoltage_2 deciVolts 7 2 1 2 2 0 mgoutputVoltage_3 deciVolts 7 2 1 2 3 0 mgoutputFrequency_1 deciHz 7 2 1 3 1 0 mgoutputFrequency_2 deciHz 7 2 1 3 2 0 mgoutputFrequency_3 deciHz 7 2 1 3 3 0 mgoutputLoadPerPhase_1 7 2 1 4 1 0 mgoutputLoadPerPhase_2 7 2 1 4 2 0 mgoutputLoadPerPhase_3 7 2 1 4 3 0 mgoutputCurrent_1 deciAmps 7 2 1 5 1 0 mgoutputCurrent_2 deciAmps 7 2 1 5 2 0 mgoutputCurrent_3 deciAmps 7 2 1 5 3 0 upsmgOutputOnBattery 1 yes 2 no 7 3 0 upsmgOutputOnByPass 1 yes 2 no 7 4 0 upsmgOutputUtilityOff 1 yes 2 no 7 7 0 upsmgOutputOverLoad 1 yes 2 no 7 10 0
71. utility failure Caution this time includes the outlet shutdown duration Switch Off if battery capacity under 0 by default is an extra condition for outlet shutdown that can trigger the shutdown sequence before the shutdown duration runs out Shutdown duration is the time required for complete shutdown of the systems supplied by the outlet when an outlet shutdown sequence is launched It is calculated automatically using the maximum shutdown durations of notified applications on the outlets Switch On after from 0 to 99999 default 65535 is the period between main output startup and startup of the relevant programmable outlet therefore outlet startup can be delayed in relation to the main output Important Certain UPSs do not support this option Export settings to file Enables exportation Download button and saving of card configuration information Import settings from file Enables selection of a configuration file Browse button and uploading Upload button of card configuration information Security The administrator has to click on Save and enter his her login password to save any modifications The login and password by default are MGEUPS THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card User Manual 34003991EN GA 22 Odis com electronic components distributor Downloaded from MGE UPS SYSTEMS 4 2 6 Viewing the alarms Pulsar M 3000 MGE UPS SYSTEMS gt Click on Alarm Table
72. ving of card parameterisation information Import settings from file Enables selection of configuration file Browse button and uploading Upload button of card configuration information Security The administrator has to click on Save and enter his her login password to save any modifications The default login and password are MGEUPS THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card User Manual 34003991EN GA 21 Odis com electronic components distributor Downloaded from MGE UPS SYSTEMS 4 3 2 E mail Message Settings This page enables customisation of the content of the messages received by recipients of e mails sent by the card Customisation is common to the four recipients that can be notified see E mail notification MGE UPS SYSTEMS Pulsar M 3000 UPS Email Message Settings UPS Properties UPS Control These settings are common for all the recipients which can be notified by E mail D Weekly Schedule gt Shutdown Parameters Sender Alarm Table Jups domain com a Subject D Measurements gt Event Log M AGE UPS SYSTEMS lt Event message gt System Log Vv MGE UPS SYSTEMS D Email Notification I UPS Name Settings I UPS Location D Network _ a M Event message D System D Notified Applications D Time D Firmware Upload Type here your own text Environment fa Status Settings Save Log D Sender 59 characters maximum identi
73. ware Upload Authorise chose Enabled remote updating of the card s embedded software The default value for this parameter is Enabled Primary DNS Server contains the IP address of the main DNS server ensuring conversion of the domain name to IP address Secondary DNS Server contains the IP address of the secondary DNS server ensuring conversion of the domain name to IP address if the primary DNS server is not available SMTP Server contains the name or IP address of the local server with which the card connects to send e mails It may be filled in either as host domain name DNS resolution or directly with the IP address The default value is smtpserver The card uses the standard port 25 for sending e mails Export settings to file Enables exportation Download button and saving of card configuration information Import settings from file Enables selection of a configuration file Browse button and uploading Upload button of card configuration information Important note The card must be rebooted after any changes to these parameters See System page Security The administrator has to click on Save and enter his her login password to save any modifications THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card User Manual 34003991EN GA 32 Odis com electronic components distributor Downloaded from 4 4 2 System Click on System in the menu MGE UPS SYSTEMS This menu ena
74. www mgeups com MGE UPS SYSTEMS Network Management Card 66102 User Manual Minislot 2006 Edition THE UNINTERRUPTIBLE POWER PROVIDER Network Management Card User Manual 34003991EN GA Page 1 63 Downloaded from dis com electronic components distributor Downloaded from Contents MGE UPS SYSTEMS 1 MGE NETWORK SOLUTION 4 1 1 GENERAL PRESENTATION 4 1 1 1 Connecting the UPS to the Ethernet network 4 1 1 2 Protection of the computers servers 5 1 1 3 Supervision of the UPSs over the network 5 1 1 4 Connection 5 1 2 PRESENTATION OF THE NETWORK MANAGEMENT CARD NMC 6 1 2 1 Compatibility with UPSs 6 1 2 2 Direct sending of E mail 7 1 2 3 Sending text messages SMS 7 1 2 4 Compatibility with the Network Managment Systems NMS Trap sending 7 1 2 5 Environment Sensor option 7 1 3 TECHNICAL DATA 7 1 3 1 Hardware characteristics 7 1 3 2 EMC Compatibility 7 1 3 3 Configuration 8 1 3 4 Administration 8 1 3 5 Network 8 1 3 6 Environment sensor 8 1 3 7 MIB Management Information Base 9 1 3 8 Default parameters 9 2 INSTALLATION 10 2 1 1 Unpacking and check on contents 10 2 1 2 Indications 10 2 1 3 Installation in the UPS 11 2 1 4 Sensor installation option 11 3 CONFIGURATION 12 3 1 1 Configure IP parameters 12 3 1 2 Test after configuration 13 4 SUPERVISION AND ADMINISTRATION