Home
RS-232C Interface Module type AJ65BT
Contents
1. Disposal Precautions A CAUTION When disposing of the product handle it as industrial waste About Manuals The following manuals are also related to this product In necessary order them by quoting the details in the tables below Detailed manual Manual Number Model Code IB 66781 13JL24 Manual Number Model Code 1B 66721 135872 Manual Name RS 232C Interface Module Type AJ65BT R2 User s Manual Related Manuals Manual Name Control amp Communication Link System Master Local Module Type AJ61BT11 A1SJ61BT11 User s Manual Control amp Communication Link System Master Local Module Type AJ61QBT11 A1SJ61QBT11 User s Manual CC Link System Master Local Module User s Manual QJ61BT11N 1B 66722 135873 SH 080394E 13JR64 Please RS 232C Interface Module Type AJ65BT R2 User s Manual before using this module Compliance with the EMC Low Voltage Directive When incorporating the Mitsubishi PLC into other machinery or equipment and keeping compliance with the EMC and low voltage directives refer to Chapter 3 EMC Directives and Low Voltage Directives of the User s Manual Hardware included with the CPU module or base unit used The CE logo is printed on the rating plate of the PLC indicating compliance with the EMC and low voltage directives To conform this product to the EMC Directive and Low Voltage Directive refer to the Section of CC Link Modules in Chapter 3 EMC Directive and L
2. module or cable could be damaged by the cable variation movement or unintentional pulling leading to malfunctioning caused by an improper cable connection Do not install the control lines together with the communication cables or bring them close to each other Failure to do so may cause malfunctions due to noise Note that the Z CAUTION level may lead to a serious consequence according to the circumstances Always follow the instructions of both levels because they are important to personal safety Please save this manual to make it accessible when required and always forward it to the end user Design Precautions amp DANGER If a communication error occurs in the data link the following will occur in the station having the communication error Use the communication status information and configure an interlock circuit in the sequence program so that the system will operate safely Incorrect outputs and incorrect operations can lead to accidents 1 All points of the general purpose input from this module will turn OFF Do not remove the communication cable or power supply cable connected to the module by pulling on the cable section If the cable has a connector hold the connector at the section connected to the module and remove If the cable does not have a connector loosen the screws at the section connected to the module and remove Pulling on the cable while connected to the module could lead to module o
3. 0ms or less 2 points common COM1 Sink source common type 9 pin connector I O section 7 point terminal block M3 5 screw 3 R Including transmission circuit Terminal Signal Terminal Signal and module power terminal No name No name Applicable wire 10 75 to 2mm TB3 XD Applicable crimp RAV1 25 3 5 RAV2 3 5 TB2 JIS C 2805 compliant Table 2 2 General purpose output specifications T Transistor output sink type Working load voltage 10 2 to 28 8VDC 12 24vDC range ripple rate within 5 6 cong Max load current 0 1A point 0 2A common Max rush current 0 4A_ 10ms or less Leakage current at OFF 1 5VDC or less MAX 0 1A ON Output type Response OFF on 2msorless 10 2 to 28 8VDC ripple rate within 5 Current 50mA or less TYP 24VDC per common Not including external load current Surge killer Zener diode Common method 2 points common COM2 External connection 9 pin connector I O section method 7 point terminal block M3 5 screw Including transmission circuit and module power terminal Terminal Signal Terminal Signal No name No name Applicable wire size 0 75 to 2mm Applicable crimp RAV1 25 3 5 RAV2 3 5 JIS C tae com2 terminal 2805 compliant 3 Part Names and Settings 1 4 3
4. 2 BRATE STATIONNO MITSUBISHI MBAs A Details Operation display _LED name Details LEDs ON Power is ON OFF Power is OFF S08 xeo ON Operating normally eO vco Default RUN OFF Power 24VDC is OFF or WDT error is YDO occurring ON Communicating normally LRUN_ OFF Communication stopped Time over error ON Any transmission speed or station number out of range is set Flickering at constant intervals The transmission speed or station number has been changed after the power is L turned on Flickering not constant intervals The terminating resistor is not connected The module or CC Link dedicated cable is ERR being affected by noise SD OFF Communicating normally ON Data link Sending data OFF Data link Not sending data ON Data link Receiving data OFF Datalink Not receiving data XC XD ON General purpose input XC XD is ON OFF General purpose input XC XD is OFF YC YD ON General purpose output YC YD is ON OFF General purpose output YC YD is OFF ON Sending RS 232C data RS 232 C SD OFF Not sending RS 232C data ON Receiving RS 232C data RS 232 C RD OFF Not receiving RS 232C data ON RS 232C transmission error RS 232 C ERR OFF No error Details Station No setting Set the module s station No Default setting 0 switch Setting range 1 to 64 0 Master module STATION NO H X 10 set
5. 33 1 5568 5568 Tel 91 20 2712 3130 South Africa Circuit Breaker Industries Ltd Australia Mitsubishi Electric Australia Pty Ltd Private Bag 2016 ZA 1600 Isando 348 Victoria Road Rydalmere South Africa N S W 2116 Australia Tel 27 11 928 2000 Tel 61 2 9684 7777 a MITSUBISHI ELECTRIC CORPORATION HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN NAGOYA WORKS 1 14 YADA MINAMI 5 CHOME HIGASHI KU NAGOYA JAPAN When exported from Japan this manual does not require application to the Ministry of Economy Trade and Industry for service transaction permission Specifications subject to change without notice Printed in Japan on recycled paper
6. MITSUBISHI RS 232C Interface Module type AJ65BT R2 User s Manual Hardware AJ65BT R2 Thank you for purchasing the Mitsubishi program logic controller MELSEC A series Prior to use please read this and relevant manuals thorougly to fully understand the product MODEL AJ65BT R2 U HW E MODEL CODE 13JL23 IB NA 66780 C 0604 MEE MEISEG 1997 MITSUBISHI ELECTRIC CORPORATION e SAFETY PRECAUTIONS e Always read these instructions before using this equipment Before using this product please read this manual and the relevant manuals introduced in this manual carefully and pay full attention to safety to handle the product correctly The instructions given in this manual are concerned with this product For the safety instructions of the programmable controller system please read the CPU module user s manual In this manual the safety instructions are ranked as DANGER and CAUTION Design Precautions A CAUTION Do not bind the control wire or communication cable with the main circuit or power wire or place the control wire near these Separate by at least 100mm or more Failure to observe this could lead to malfunctions caused by noise Always connect the master module and CC Link dedicated cable at the data link terminal block If the data link terminal block and general purpose input output terminal block are incorrectly inserted module trouble could occur Data lin
7. ctioning Always install the terminal covers enclosed with the product before turning ON the power or operating the product after installation or wiring work Failure to install the terminal cover could lead to electric shocks Always ground the FG terminal with Class D grounding Class 3 grounding dedicated of the PLC Failure to do so could lead to malfunctioning Always confirm the product s rated voltage and terminal layout before wiring the module Connecting with a power supply other than the rated power supply or incorrect wiring could lead to fires or trouble Tighten the terminal screws within the specified torque range A loose terminal screw could lead to short circuiting or malfunctioning If the terminal screw is too tight dropping or short circuiting could occur due to screw damage 1 Indicates that incorrect handling may cause hazardous i DANGER conditions resulting in death or severe injury L Indicates that incorrect handling may cause hazardous l Z CAUTION conditions resulting in medium or slight personal injury L or physical damage Make sure that foreign matter such as cutting chips or wire scraps do not enter the module Failure to observe this could lead to fires trouble or malfunctioning The communication cables and power supply cable connected to the module must be placed in a conduit or fixed with a clamp If the cable is not placed in a conduit or fixed with a clamp the
8. ctric Europe B V German 6F No 105 Wu Kung 3rd Rd Wu Ku Branch Hsiang Taipei Hsine Taiwan Gothaer Strasse 8 D 40880 Ratingen Tel 886 2 2299 2499 GERMANY Korea Mitsubishi Electric Automation Korea Tel 49 2102 486 0 Co Ltd U K Mitsubishi Electric Europe B V UK 1480 6 Gayang dong Gangseo ku Branch Seoul 157 200 Korea i ii Tel 82 2 3660 9552 R TR Padield Hemordshie Singapore Mitsubishi Electric Asia Pte Ltd Tel 44 1707 276100 307 Alexandra Road 05 01 02 Mitsubishi Electric Building Italy Mitsubishi Electric Europe B V Italian Singapore 159943 Branch Tel 65 6470 2460 Centro Dir Colleoni Pal Perseo ingr 2 Thailand Mitsubishi Electric Automation Thailand Via Paracelso 12 20041 Agrate Brianza Co Ltd Milano Italy Bang Chan Industrial Estate No 111 Tel 39 039 60531 Moo 4 Serithai Rd T Kannayao Spain Mitsubishi Electric Europe B V Spanish A Kannayao Bangkok 10230 Thailand Branch Tel 66 2 517 1326 Carretera de Rubi 76 80 Indonesia P T Autoteknindo Sumber Makmur E 08190 Sant Cugat del Valles Muara Karang Selatan Block A Utara Barcelona Spain No 1 Kav No 11 Kawasan Industri Tel 34 93 565 3131 Pergudangan Jakarta Utara 14440 _ France Mitsubishi Electric Europe B V French FO Bor tie takarta 11050 Indonesia pranon d B F 9274 India Messung Systems Pvt Ltd a Boulevard des Bouvele foetal Electronic Sadan NO lil Unit No15 Nanterre Cedex France M I D C Bhosari Pune 411026 India TEL
9. d N SLO CC Link dedicated FG cable ov cable TY 246 N A 4 5 installation hole MITSUBISHI MAES Asesaree 000665 Always connect the modules on both ends of the data link with the terminator enclosed with the master module Connect across DA DB ADG t 4 o 4 5 161 6 33 5 2 Connection with external device 0 187 170 Er The method of connecting the AJ65BT R2 and external device with i RS 232C is show below Unit mm inch Pin Signal Signal direction Name g AJ65BT R24 gt No abbrev external device ksen ae detection The following type of Reception data RD RXD connector is mounted on SD TXD the AJ65BT R2 side so ER DTR use a mate connector that matches this type G Data set ready DR DSR eee RS RTS pati TAYER 8 Transmission enable CS CTS her ae en Ce a ay Figure 5 1 RS 232C interface specifications 1 Example of connection for DC code control and DTR DSR signal control Warranty Cable connection and signal Mitsubishi will not be held liable for damage caused by factors found not to be method the cause of Mitsubishi machine damage or lost profits caused by faults in the SD 3 Mitsubishi products damage secondary damage accident compensation caused by special factors unpredictable by Mitsubishi damages to products other than Mitsubishi products and to othe
10. efer to section 2 2 No of occupied stations 1 station RX RY 32 points each RWw RWr 4 points each Connection cable CC Link dedicated cable 2 Withstand voltage One minute at 500VAC between DC external terminal batch and grounding Insulation resistance 10MQ or more with 500VDC insulation resistance meter between DC external terminal batch and grounding Noise withstand level DC type noise voltage 500Vp p With noise width 1 us noise frequency 25 to 60Hz noise simulator Module installation M4 x 0 7mm X 16mm or more screw screw Tightening torque range 0 78 to 1 18N m DIN rail may also be used for mounting Applicable DIN rail TH35 7 5Fe TH35 7 5Al TH35 15Fe JIS C 2812 compliant External Power supply 24VDC 10 Data link specificat Current consumption 0 11A Tolerable instantaneous ims power failure time For the general specifications refer to the RS 232C Interface Module Type AJ65BT R2 User s Manual 2 2 General purpose input output specifications The general purpose input output specifications of the AJ65BT R2 are shown in Tables 2 1 and 2 2 Table 2 1 General purpose input specifications DC input sink source common type AJ65BT R2 External connection No of input points nsulation method Photo coupler insulation Rated input 24VDC current range ripple rate within 5 simultaneous Response JOFF 10ms or less time gt ON 1
11. k terminal General purpose input block output terminal block Mounting Precautions A CAUTION Use the module in an environment that meets the general specifications given in the RS 232C Interface Module Type AJ65BT R2 User s Manual Using it outside the general specifications could lead to electric shocks fires malfunctioning product damage or deterioration Always connect the crimp press fit or solder the connector wire connections with the maker designated tools and securely connect the connector to the module An incomplete connection could lead to short circuits or malfunctioning Do not directly touch the conductive section of the module Failure to observe this could lead to module malfunctioning or trouble Securely fix the module with the DIN rail or installation screw Tighten the installation screw within the designated torque range A loose screw could lead to dropping short circuiting or malfunctioning If the screw is too tight dropping or short circuiting could occur due to screw damage Securely mount the connector of each connection cable to the mounting section An incomplete connection could lead to malfunctioning caused by an incorrect contact Wiring Precautions A CAUTION Before starting installation or wiring work be sure to shut off all phases of external power supply used by the system Failure to shut off all phases could lead to electric shocks product damage or malfun
12. ow Voltage Directive in the User s Manual Hardware of the CPU module used or the PLC CPU supplied with the base unit 1 Overview This manual explains the specifications handling instructions wiring of the RS 232C Interface Module Type AJ65BT R2 hereinafter referred to as the AJ65BT R2 which is used as an intelligent device station in the CC Link system 1 Included product After unpacking confirm that the following is included Quantity AJ65BT R2 RS 232C Interface Module Type AJ65BT R2 2 Specifications 2 1 Performance specifications of the AJ65BT R2 The AJ65BT R2 performance specifications are shown below Performance specifications Interface specifications RS 232C compliant 1 channel Refer to section 5 2 ificati itch Transmission method Full duplex communication method Synchronization Start stop synchronization method method Transmission speed 300 600 1200 2400 4800 9600 19200bps Select with RS 232C transmission specification setting switch no i 2 2 5 Data format Star bit 1 3 Data bit o Parity bit 1 Yes 0 No Q Stop bit g Error detection With parity check even odd None Communication control DTR DSR ER DR control flow control DC1 DC3 control OS reception area 5120 bytes General purpose Input side 24VDC sink source common type 2 points input output Output side Transistor output sink type 12 24VDC 2 points specifications Terminal block R
13. r cable damage or malfunctioning caused by an improper cable connection 2 All points of the general purpose output from this module will turn FF Startup Maintenance Precautions A CAUTION When power is ON do not touch the terminals Doing so can cause an electric shock or malfunction The input output may turn ON or OFF depending on the module trouble Provide a circuit that externally monitors input output signals that could lead to serious trouble Before cleaning or tightening the terminal screws and module mounting screws be sure to shut off all phases of external power supply used by the system Failure to shut off all phases could lead to module trouble or malfunctioning Startup Maintenance Precautions A CAUTION Do not touch the connector inside the lid at the top of the module Failure to observe this could lead to module trouble or malfunctioning Never disassemble or modify the module Failure to observe this could lead to trouble malfunctioning injuries or fires Do not drop or apply any strong impact to the module Doing so may damage the module Before installing or removing the module on the panel be sure to shut off all phases of external power supply used by the system Failure to shut off all phases could lead to module trouble or malfunctioning Do not install remove the terminal block more than 50 times after the first use of the product IEC 61131 2 compliant
14. r duties a Avro sate uso e This product has been manufactured as a general purpose part for general industries and has not been designed or manufactured to be incorporated in a 2 Example of connection for only DC code control device or system used in purposes related to human life p y e Before using the product for special purposes such as nuclear power electric AJ65BT R2 side DTE Cable connection and signal External device DTE power aerospace medicine or passenger movement vehicles consult with Signal abbrev Pi No method Signal abbrev Mitsubishi E 3 SD e This product has been manufactured under strict quality control However M eo when installing the product where major accidents or losses could occur if the e 7 product fails install appropriate backup or failsafe functions in the system o o Country Region Sales office Tel Country Region Sales office Tel e i U S A Mitsubishi Electric Automation Inc Hong Kong Mitsubishi Electric Automation Hills IL 60061 U S A 10th Floor Manulife Tower 169 Electric Brazil MELCO TEC Rep Com e Assessoria Tel 852 2887 8870 Tecnica Ltda China Mitsubishi Electric Automation ia Di Shanghai Ltd Rua Correia Dias 184 4 F Zhi Fu Plazz No 80 Xin Chang Road ificio Paraiso Trade Center 8 andar Shangh i ghai 200003 China Paraiso Sao Paulo SP Brazil Tel 86 21 6120 0808 Tel 55 11 5908 8331 Taiwan Setsuyo Enterprise Co Ltd Germany Mitsubishi Ele
15. s the 10th place of the station No x 1 sets the 1st place of the station No Transmission speed 156kbps BRAT e Set the module s transmission speed 2 p for data link 2 5Mbps Default setting 0 5Mbps 10Mbps Setting error Data link transmission speed setting switch No Name Setting details o Ne On line mode Mode for on line communication using transmission Set when using the 5 reception buffer transmission reception buffer On line mode using buffer memory automatic update function Setting error RUN LED turns OFF Setting error RUN LED turns OFF Use notpossible Setting error RUN LED turns OFF Setting error RUN LED turns OFF Mode for confirming that module runs mode independently Setting error RUN LED turns OFF Setting error RUN LED turns OFF RS 232C i transmission Setting switch state Default specifications setting ig ON OFF setting switch Mode for on line communication Set when using the buffer memory automatic update function sw 12346678 m i m m F m m i SW1 Transmission me 4800bps 9600bps 19200bps 0 OFF 1 0N Daa brenn 8 7 ON ae No mle Odi OFF Swe 1 Data link terminal Connect a CC Link dedicated cable for power supply and data block link 2 piece terminal block RS 232C interface Connect an RS 232C cable for connection with external device General purpose Connect the input output wire input ou
16. tput terminal block Reset switch Returns to the power ON status Connector Use prohibited 4 Mounting and Installation 4 1 Precautions for handling For handling instructions such as module installation removal read SAFETY PRECAUTIONS given at the beginning of this manual 1 Tighten the module installation screws and terminal block screws within the following range Screw place Tightening torque range Module installation screw M4 screw 0 78 to 1 18Nem Terminal block terminal screw M3 5 screw 0 59 to 0 88Nem Terminal block installation screw M4 screw 0 98 to 1 37Nem 2 When using the DIN rail adaptor install the DIN rail while observing the following points a Applicable DIN rail type JIS C 2812 compliant TH35 7 5Fe TH35 7 5Al TH35 15Fe b DIN rail installation screw pitch When installing the DIN rail tighten the screws at a pitch of 200mm or less 4 2 Installation environment When installing the PLC refer to the CC Link system master module s User s Manual 5 Wiring 6 External Dimensions 5 1 Data Link o The method of connecting the AJ65BT R2 master module and remote i i NS module with a CC Link dedicated cable is shown below gt D Master module AJ65BT R2 Remote module Ss gt EEEN EE SEN p Terminator 5 Terminator SLD H CC Link dedicate