DUO-CEL User Manual

image

Contents

1. S aa e E du uvieu 5 8 USER CONTROLS dx a a aa aE Sa Eaa aaa haa k Ea uous 6 PAGE 2 of 6 EQUIPMENT PUBLICATION ISSUE No amp DATE 09 03 12 FIRECLASS DUO CEL OM_FC_DUO CEL_USER WRITTEN BY RKP CHECKED BY AP 1 Introduction This document contains the necessary information for operating the FIRECLASS DUO CEL Conventional Fire Detection control panel NOTE In order to comply strictly with the requirements of EN54 4 1998 Clause 6 2 1 Power Supply Equipment Enclosure shall meet at least classification IP30 of EN 60529 1991 a rubber bung is inserted into the Keyswitch hole when not in use Ensure that the rubber bung is re inserted each time the key is removed from the panel 2 User Operation Fire and Fault Conditions This panel is capable of operating the fire alarm sounders in various ways e Sounder circuits can operate per zone or all together e Sounder circuits can be continuous or pulsed All users should be fully aware of the particular configuration of their system and should have received training in the basic operation of the system The following information is provided as a quick reference guide only 21 Ifa fire is detected On the DUO CEL Fire Alarm Panel e The general Fire LED will flash and the buzzer will sound e The relevant zone Fire LED s will flash indicating the loca
2. only the circuits currently in test When controls are unlocked ae When controls are unlocked and in Toggles the selected circuit between Test amp Normal states First operation enables the circuit select mode subsequent Select operations move the flashing cursor through the available Whe icontrols are unlo ked circuits until the last circuit then exits the circuit select mode PAGE 6 of 6
3. 0 0c0ccccssssssscsssssscsssssceeesesesesesesesesesesessseeessssssssessecseseresereees 3 2 5 OPERATE THE FIRE ALARM SOUNDERS IN EVACUATE 3 2 6 JIFAFAULTAS DETECTED lt i desc AA 3 2 7 TO SILENCE THE pU R a r aa 3 2 8 SYSTEM FAULT INDIGATION 3 2 9 USER ACTIONS IN THE EVENT OF A FAULT 4 3 PANEL OPERATION a r dus deus tin 4 3 1 amp TEST 4 3 1 1 test disable re enable circuits 4 3 1 2 TO VIEW the disabled CHGUIISE 2 4 3 1 3 TOVIEW INE 4 Bre TES Te E a 4 4 DUO CEL REPEATER PANEL OPERATION 0 0 c cscecececececececececececesececececesecesecusesecesesecesesesecesecesucesesesesesususesesesesess 4 5 ROUTINE TESTING AND MAINTENANCE c cccscccecececececececececececececececececesecececesecesesesesecesesesusesesesecusesesusesususesesesesess 4 6 USER RESPONSIBILITIES ascuten uses EE E E E os A ews E 4 USER INDICATIONS E S OEE
4. FIRECLASS DUO CEL OM_FC_DUO CEL_USER 09 03 12 8 User Controls SUPPLY ON GENERAL FIRE GENERAL FAULT GENERAL TEST GENERAL DISABLE ALERT EVAC ON FIRE SIGNAL ON FIRE SIGNAL FAULT SNDR FLT DIS TEST SYSTEM FAULT PSU FAULT FUSED FAILED EARTH FAULT REPEATER FAULT REMOTE I P FAULT CONTROLS ON WRITTEN BY RKP CHECKED BY AP EVACUATE SILENCE BUZZER SILENCE RESOUND ALARMS DISABLE SELECT Access Controls Keyswitch Switch Functionality Button Availability Operates all sounders continuously and illuminates the Evacuate Alert Evac On LED until the Silence Resound Alarms When controls are unlocked button is operated Silence Buzzer Silences the internal buzzer on the Panel amp Repeaters When controls are locked or unlocked Silence Resound When any sounders are active press to silence sounders When controls are unlocked Alarms Press again to resound the silenced sounders Press to clear any fault amp alarm conditions and return the Reset panel to the quiescent state When controls are unlocked Displays Alarm Counter When controls are locked Disable only the currently disabled circuits When controls are unlocked Toggles the selected circuit between Disabled amp Enabled When controls are unlocked and in states circuit select mode Press to illuminate all LEDs and sound the buzzer for 5 Whenicontrols are locked seconds Test
5. data corrupted PSU Fault Yellow OFF power supply is healthy FLASH PSU fault and or battery fault Fuse Failed Yellow OFF Auxiliary 24Vdc output available FLASH Electronic Fuse on Auxiliary 24Vdc output activated Earth Fault Yellow OFF No cable faults to Earth FLASH One or more cable faults to Earth Repeater Fault Yellow No Repeater faults FLASH or more Repeater faults Remote Control Fault Yellow OFF No faults on Remote Control input FLASH Fault on Remote Control input Controls On Yellow OFF User Controls disabled ON User Controls enabled FLASH Select mode active GENERAL FIRE GENERAL FAULT GENERAL TEST GENERAL DISABLE ALERT EVAC ON FIRE SIGNAL ON FIRE SIGNAL FAULT SNDR FLT DIS TEST SYSTEM FAULT PSU FAULT FUSED FAILED EARTH FAULT REPEATER FAULT REMOTE FAULT CONTROLS ON EVACUATE SILENCE BUZZER SILENCE RESOUND ALARMS DISABLE TEST SELECT Zone Location Indications Indicator Colour Operating Condition User Zone OFF No Alarm on zone FLASH New Alarm on zone ON Alarm accepted on zone Location Text Red NOTE With Detector MCP discrimination the left LED is for MCPs EVACUATE the right LED for Detectors ALERT User Zone Yellow OFF No Fault on zone circuit FLASH Fault on zone circuit Location Text ON Zone circuit Disabled or in Test PAGE 5 of 6 EQUIPMENT PUBLICATION ISSUE No amp DATE 0
6. EQUIPMENT FIRECLASS DUO CEL WRITTEN BY RKP PUBLICATION _FC_DUO CEL_USER CHECKED BY AP ISSUE No amp DATE 0 09 03 12 APPROVED BY JBJ ontrol Qauipment Limited FIRECLASS DUO CEL FIRE DETECTION ALARM PANEL User Operation Manual DANGER THIS EQUIPMENT CONTAINS HAZARDOUS VOLTAGES THAT CAN CAUSE DEATH SERIOUS PERSONAL INJURY OR EQUIPMENT DAMAGE THIS EQUIPMENT CONTAINS NO USER SERVICEABLE PARTS DO NOT REMOVE THE FRONT COVER REFER ALL MAINTENANCE TO SUITABLY QUALIFIED PERSONNEL PAGE 1 of 6 EQUIPMENT FIRECLASS DUO CEL WRITTEN BY RKP PUBLICATION _FC_DUO CEL_USER CHECKED BY AP ISSUE No amp DATE 0 09 03 12 List of Contents De INTRODUCTION SG au wus da db und A di du un da dbus aurabiue sd da 3 2 USER OPERATION FIRE AND FAULT CONDITIONS 0 0 c c cececececececececececececececececesesecececesecucucusesususesususesesesesusesesess 3 AR JIF ATFIREIS DETEC MEDS E E covet EE 3 2 2 TOSILENCE THE FIRE ALARM SOUNDERS 000cccssssesssscsecsscscscccscseseeeseseseseseseseseessesssasesaeasasassssessseesererees 3 23 TO RESOUND THE FIRE ALARM SOUNDERS AFTER THEY HAVE BEEN 1_ 3 24 TO RESET THE PANEL FROM A FIRE ALARM
7. e system log book 3 Panel Operation 3 1 Disablement amp Test Conditions Each zone circuit can be disabled or placed into the test mode individually All sounder circuits can be disabled or placed into the test mode as a group The Fire Signal output can be disabled or placed into test mode 3 1 1 To test disable or re enable circuits 1 Turn the Access Key to the vertical position 2 Press the Select button to enter the Select Mode e The Controls On LED will flash e cursor indication will pulse rapidly the yellow Zone 1 fault LED e The yellow fault LED for any circuit currently in test or disabled will be illuminated 3 Press the Select button to move the cursor to the required circuit fault LED For each circuit the cursor is on the General Disablement amp General Test LEDs will indicate the current status for that circuit i General Test amp General Disablement LEDS OFF Circuit is in normal operating mode ii General Test LED pulsing Circuit is in Test mode General Disablement LED pulsing Circuit is Disabled 4 To change the status of the selected circuit press the Disable or Test button as required e Circuit is currently not disabled or in test Press the Disable button to disable Press the Test button to test e Circuit is currently disabled Press the Disable button to re enable Press the Test button to test the disabled condition will also be cleared C
8. ircuit is currently in test Press the Test button to clear the test press the Disable button to disable the test condition will also be cleared 5 To exit from the Select mode either remove the Access Controls Key to lock the controls or press the Select button repeatedly to scroll the flashing cursor through the remaining circuits until the Controls On LED stops flashing and the flashing cursor is cleared 3 1 2 To view the disabled circuits 1 Turn the Access Key to the vertical position 2 Press and hold the Disable button Only the General Disablement LED and the fault LEDs of any disabled circuits will be illuminated 3 Release the Disable button to return the display to normal 3 1 3 To view the circuits in test 1 Turn the Access Key to the vertical position 2 Press and hold the Test button Only the General Test LED and the fault LEDs of any circuits in test will be illuminated 3 Release the Test button to return the display to normal 3 2 Display Test Remove the Access Controls Key to lock the controls then press the Test button All LEDs on the display will illuminate and the internal buzzer will sound for 5 seconds 4 DUO CEL Repeater Panel Operation The repeater panel operation is identical to the Alarm panel except that the disablement amp Test facilities cannot be controlled from the repeater The display is similar but the Disable and Select buttons are not present 5 Routine Testi
9. ng and maintenance See FIRECLASS DUO CEL Log Book for details 6 User responsibilities See FIRECLASS DUO CEL Log Book for details PAGE 4 of 6 EQUIPMENT FIRECLASS DUO CEL WRITTEN BY RKP PUBLICATION _FC_DUO CEL_USER CHECKED BY AP ISSUE No amp DATE 09 03 12 7 User Indications General Indicator Section Indicator Colour Operating Condition Supply On Green OFF No mains or battery power ON Panel has power battery and or mains General Fire Red OFF Quiescent FLASH New Alarm Condition ON Alarm Accepted General Fault Yellow OFF No faults present FLASH One or more faults present General Test Yellow OFF No circuits in Test ON One or more circuits in Test General Disablement Yellow OFF No circuits Disabled ON One or more circuits Disabled Alert Evac On Red OFF No Alert or Evacuate FLASH Remote Alert Evacuate active ON Panel Evacuate active Fire Signal On Red OFF Fire Routing output not active ON Fire Routing output active OFF No fault on Fire Routing output FLASH Fault on Fire Routing output Fire Signal Fit Dis Tst Yellow ON Fire Routing output Disabled or in Test Sounder Flt Dis Tst Yellow OFF No Fault on Sounder circuits FLASH Fault on one or more Sounder circuits ON Sounder circuits Disabled or in Test System Fault Yellow OFF System is working correctly ON System is in the SAFE state Microcontroller failed or EEPROM
10. r will operate e fire alarm sounders will operate continuously Press the Silence Resound Alarm button to silence the fire alarm sounders and clear the Alert Evac LED e Remove the Access Controls Key to lock the controls 2 6 Ifa fault is detected e The panel buzzer will sound e General Fault LED will flash e One or more fault LEDs will flash identifying which element of the system is faulty e When the fault is corrected the fault indication will clear automatically except for the Fuse Failed indication which requires the Reset button to be pressed 2 7 To Silence the buzzer Press the Silence Buzzer button The buzzer will silence 2 8 System Fault Indication In the event of a complete system failure a System Fault will be indicated e The SYSTEM FAULT and GENERAL FAULT LED illuminate All other LEDs will be extinguished e internal buzzer will sound continuously PAGE 3 of 6 EQUIPMENT PUBLICATION ISSUE No amp DATE 09 03 12 FIRECLASS DUO CEL OM_FC_DUO CEL_USER WRITTEN BY RKP CHECKED BY AP Warning In the System Fault condition the panel is not functional and fire alarm cover is no longer available 2 9 User actions in the event of a fault e Determine the area affected by the fault and decide whether special actions such as fire patrols are needed in that area e your service engineer immediately e Record the event in th
11. tion of the fire e Fire Signal output and LED will operate e Fire Alarm sounders will operate immediately pulsed or continuous zonally or together as per configuration e Fire Relay will operate immediately Locate the source of the fire alarm an LED will be visible on the detector which has been activated 2 2 To silence the fire alarm sounders e the Access Key to the vertical position Press the Silence Resound Alarms button once only e The fire alarm sounders will become silent e The General Fire LED and the Zone Fire LED s will become steady e Remove the Access Controls Key to lock the controls 2 3 resound the fire alarm sounders after they have been silenced e Turn the Access Controls Key on the panel door to the vertical position Press the Silence Resound Alarms button once only e Remove the Access Controls Key to lock the controls 2 4 reset the panel from a Fire Alarm e After the fire has been extinguished turn the Access Controls Key on the panel door to the vertical position Press the Reset button e The General Fire LED and the Zone Fire LED s will clear e Remove the Access Controls Key to lock the controls 2 5 operate the fire alarm sounders in Evacuate Mode e Turn the Access Controls Key on the panel door to the vertical position Press the Evacuate button e The Alert Evac LED will illuminate and the panel buzze

Download Pdf Manuals

image

Related Search

Related Contents

Manual do usuário  販売代理店 御中 - 株式会社ジェイティエス/JTS  安全 のた めに 危険 安全 のた めに 危険 取扱説明マニュアル  MOLYKOTE® Separator Spray Aceite  Pompes à chaleur Air/Eau  Security GSM Alarm System  Automated indoor Surveillance Quadcopter with image recognition  LT3/LT7 Thermal Image Camera User Manual  REWACRYL ROOF  iTunes Connect Developer Guide  