1. times R or current times resistance refers to Ohm s Law V I xR K Degrees Kelvin NV Network Variable a Stryker CVAHU parameter that can be viewed or modified over the Lon S bus network PWM Pulse Width Modulated output allows analog modulating control of equipment using a digital output on the controller RTD Resistance Temperature Detector refers to a type of temperature sensor whose resistance output changes according to the temperature change of the sensing element TPT Twisted Pair Transceiver VA Volt Amperes a measure of electrical power output or consumption as applied to an AC device Vac Voltage alternating current AC voltage rather than DC voltage VAV Variable Air Volume refers to either a type of air distribution system or VAV Box Controller that controls a single zone in a variable air volume delivery system Constructions of Controller and Wall Module For more details refer to the following literature 63 4529 03 Stryker Lon Configurable VAV CVAHU Controller Specification Data 62 2029 02 Stryker Lon Configurable VAV CVAHU Controller Installation Instructions 63 1322 02 Zio Zio Plus LCD Wall Modules Wall Module Specification Data 62 0271 07 Zio Zio Plus LCD Wall Modules Wall Module Installation Instructions 63 2719 LCD Wall Modules Wall operating guide 209541B LONWORKSO Bus Wiring Guidelines Termination Module Installation Instructions STRYKER CVAHU
2. STRYKER CVAHU ZIO CONFIGURATION GUIDE Figure 86 Parameter Cnfg Out Htg Stg1 Figure 87 Parameter Cnfg Out Htg Stg2 HTG STG1 Displays and allows modification of HTG STG2 Displays and allows modification of logical output configuration terminal assignment for logical output configuration terminal assignment for Heating stage 1 Command This can be changed as Heating stage 2 Command This can be changed as AO 1 AO 2 DOC1 DOA1 DOA2 DOA3 DOB1 AO 1 AO 2 DOC1 DOA1 DOA2 DOA3 DOB1 DOB2 DOB3 DOB4 AO 3 and UNDEFINED DOB2 DOB3 DOB4 AO 3 and UNDEFINED Default Parameter setting UNDEFINED Default Parameter setting UNDEFINED Configuration settings in program are as follows Configuration settings in program are as follows O AO1 O AO1 1 AO2 1 AO2 2 DOC1 DO1 2 DOC1 DO1 3 DOA1 DO2 3 DOA1 DO2 4 DOA2 DO3 4 DOA2 DO3 5 DOA3 DO4 5 DOAS3 DO4 6 DOB1 DOS 6 DOB1 DOS 7 DOB2 DO6 7 DOB2 DO6 8 DOB3 DO7 8 DOB3 DO7 9 DOB4 DO8 9 DOB4 DO8 10 AO3 10 AO3 255 UNDEFINED 255 UNDEFINED 48 STRYKER CVAHU ZIO CONFIGURATION GUIDE Figure 88 Parameter Cnfg Out HtgStg3 Figure 89 Parameter Cnfg Out Fan Out HTG STG3 Displays and allows modification of FAN OUT Displays and allows modification of logical logical output configuration terminal assignment for output configuration terminal assignment for Fan Heating stage 3 Command This can be changed as Start Stop Command This
3. ASHP Default configuration CON Configuration settings in program are as follows 0 CON Conventional control 1 GSHP Water Source Heat Pump WSHP Figure 62 Parameter Cnfg Ctl Clg Tr Heat Pump Control with water status enable signal 255 ASHP Air Source Heat Pump ASHP CLG TR Displays and allows modification of space Heat pump control without water status enable signal cooling PID control throttling range lts value ranges from O to 30 AF Throttling Range TR When TR is nonzero this value of TR is used by the space cooling PID control Auto Gain Selection When TR is 0 Table 5 shows the TR values are used by the space cooling PID control Table 5 TR values used by the space cooling pid control Without With Economizer Economizer Figure 61 Parameter Cnfg Ctl Clg Type CLG TYPE Displays and allows modification of number of cooling heat pump stages as NONE 1STG 2STG 3STG 4STG ANA Default configuration 2STG Configuration settings in program are as follows 0 NONE 1 1STG 2 25TG 3 3STG 4 4STG 10 ANA 35 STRYKER CVAHU ZIO CONFIGURATION GUIDE Figure 63 Parameter Cnfg Ctl Clg lt CLG IT Displays and allows modification of cooling PID control integral time lts value ranges from 0 to 5000 sec Integral Time IT When TR is nonzero this value of IT is used by the space cooling PID control Auto Gain Selection When TR is 0 Table 6 shows the IT values
4. HTGSP LO CLGSP HI CLGSP LO EFHTG HI 19 STRYKER CVAHU ZIO CONFIGURATION GUIDE 52 EFHTGLO 53 EFCLH HI 54 EFCLGLO 55 HP TYPE 56 CLG TYPE 57 CLGTR 58 CLGIT 59 HTG TYPE 60 HTG TR 61 HTGIT 62 FAN MODE 63 OC SNROP 64 Ul 65 Ul2 66 UI3 67 Ul4 68 UI5 69 UIG 70 DN 71 DI2 72 DIS 73 DI4 74 SPC TEMP 75 SPC RH 76 SPC CO2 77 DISCHAIR 78 MIXEDAIR 79 OD ETMP 80 OCC SNSR 81 WINDOW 82 RANGE for AO1 83 RANGE for AO2 84 RANGE for AO3 85 CLG STG1 86 CLG STG2 87 CLG STG3 88 HP CHANG 89 HTG STG1 90 HTG STG2 91 HTG STG3 92 FAN OUT 93 DAMPER 94 TIME 95 HOURS 96 MIN 97 YEAR 98 MONTH 99 DAY 100 SCHEDULE STRYKER CVAHU ZIO CONFIGURATION GUIDE Click NEXT on SENSORS parameter group screen Pa ram eters Other parameter group screens are displayed in PARAMETERS allow the contractor to monitor and or following order adjust parameters in the programmable controller 1 Status Click PARAMETERS soft key on contractor mode 2 Temp SP default home screen to display the first configured category as shown in Figure 14 3 Override 4 Alarms 5 Snsr Cal 6 Wm Confg 7 Confg Ctl 8 Confg Ui 9 Confg Di 10 Confg In 11 AO1 12 AQ2 13 AO3 Figure 14 Parameter group Sensors 14 Cnfg Out e The soft keys changes to DONE EDIT and 15 Fine NEXT as per configuration requirement e Click the EDIT soft key to display the parameter 16 Set Time l
5. for ventilation requirements is adjusted based on indoor air quality IAQ needs in the space IAQ monitoring is provided through either a CO2 sensor or a digital input from a space mounted IAQ limit switch For heat pump configurations up to three compressors can be controlled along with up to three stages of auxiliary heat and a heat cool change over valve Including the supply fan a combination of these items may not exceed eight outputs in a Stryker CVAHU The Stryker CVAHU Controller can monitor a space mounted occupancy sensor and a door window contact These inputs affect the operational mode of the controller The Stryker CVAHU Controller allows other controllers in the system to use the physical inputs and outputs A digital input and an analog input can be configured to read switch states and voltage sensor values respectively and send them out over the S and LON bus network STRYKER CVAHU ZIO CONFIGURATION GUIDE For additional CVAHU Stryker and Zio wall module Prod ucts Cove red latest documents and updates visit This System Engineering Guide describes how to htto www customer honeywell com configure Stryker CVAHU controller via TR71 75 Zio wall module Stryker CVAHU Controllers and related accessories to typical applications are as follows e Stryker CVAHU controller e TR71 75 wall modules And search for CVAHU Stryker and Zio wall module respectively Product Names e 209541B FTT termination modu
6. DI 1 DI 2 DI 3 DI 4 and 4 Ul5 Ul6 DI 1 DI 2 DI 3 DI 4 and UNDEFINED UNDEFINED Default Parameter setting UNDEFINED Default Parameter setting UNDEFINED Configuration settings in program are as follows Configuration settings in program are as follows 0 Ull 0 Uli 1 Ul2 1 Ul2 gt Ul3 2 U3 3 UlA 3 Ul4 4 U5 4 UI5 5 UIG 2 LIO 47 Dli 47 DI1 48 DI 48 Dl2 49 DI3 49 DI3 50 DIA 50 DI4 255 UNDEFINED 255 UNDEFINED 43 STRYKER CVAHU ZIO CONFIGURATION GUIDE AO Analog output range configuration Figure 79 Parameter AO1 Range RANGE Displays and allows modification of analog output1 range This can be changed as 0D10 10D0 2D10 10D2 0A20 20A0 0A22 22A0 4A20 20A4 DIG and UNDEFINED Default Parameter setting UNDEFINED Configuration settings in program are as follows 0 10 209 0D10 Analog voltage 0 to 10VDC direct output 10D0 Analog voltage 0 to 10VDC reverse output 2D10 Analog voltage 2 to 10VDC direct output 10D2 Analog voltage 2 to 10VDC reverse output 0A20 Analog current 0 to 20 mA direct output 20A0 Analog current 0 to 20 mA reverse output 0A22 Analog current 0 to 22 mA direct output 22A0 Analog current 0 to 22 mA reverse output 4A20 20A4 Analog current 4 to 20 mA reverse output Analog current 4 to 20 mA direct output DIG Analog as binary output UNDEFINED 44 AO2 Analog output2
7. Dades ayaa ave bint Ri eii ae 22 Figure 20 Parameter Status Dind Lisa ia 22 Figure 21 Parameter Status mil La la dd ee 23 Figure 22 Parameter Status Aux ECON cooooonncccnnccccncoonccnnnnnonnnonnnnnnnnnnnnnnnnnnnnnnnnnnnrnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnrnnnnnnninnnnnns 23 Figure 23 Parameter Status Free Mod receio eee eed e aa a e ea e EaR e e aA a e e ERE aT daea 23 Figure 24 Parameter Status Free Digi recse E EE E E 23 Figure 25 Parameter Stalls F aeeoa ae Aaaa a Aa 24 Figure 26 Parameter Temp Sp OCC Closerie a a a E E E E 25 Figure 27 Parameter Temp SP OCGC Hliva a a 25 Figure 28 Parameter Temp Sp UNoOC OO seresa ER aaa 25 Figure 29 Parameter Temp Sp Unoc AiG aid di 25 Figure 30 Parameter Temp SD DY ClO iii ii a a a a 26 Figure 31 Parameter Temp Sp Stby PIO oocccccnccccccocnccnnnccnnnnonnccnnnonononononnnnnonnnnnnnnnnonnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnannnnnnnnnns 26 Figure 32 Parameter Temp SO oton tea 26 Fig re 33 Parameter Temp Sp Frz PRO arcanos rs 26 Figure 34 Parameter Temp Sp Eff Sp ccccccseeccesceseecceccceseceeccceesceesceeeeeessseeeeeeccasseeeeccasaeeesecaseeesccesetenscoseeees 27 Figure 35 Parameter Override Fan Ow usais enana 28 Figure 36 Parameter Alarms Emrg Ode iii pi 28 Figure 37 Figure 38 Figure 39 Figure 40 Figure 41 Figure 42 Figure 43 Figure 44 Figure 45 Figure 46 Figure 47 Figure 48 Figure 49 Figure 50 Figure 51 Figure 52 Figure 53 Figure 54 Figure 5
8. Figure 25 Parameter Status Fan FAN Displays fan digital output status as ON or OFF Configuration settings in program are as follows 0 OFF 1 ON 255 UNDEFINED 24 STRYKER CVAHU ZIO CONFIGURATION GUIDE Temp Sp CVAHU temperature setpoint configuration Figure 26 Parameter Temp Sp Occ Clg Figure 28 Parameter Temp Sp Unoc Clg OCC CLG Displays and allows modification of UNOC CLG Displays and allows modification of occupied cooling setpoint Its value ranges from unoccupied cooling setpoint Its value ranges from EFCLG LO to EFCLG HI STBY CLG to 90 Figure 27 Parameter Temp Sp Occ Htg Figure 29 Parameter Temp Sp Unoc Htg OCC HTG Displays and allows modification of UNOC HTG Displays and allows modification of occupied heating setpoint lts value ranges from unoccupied heating setpoint Its value ranges from 50 EFHTG LO to EFHTG HI to STBY HTG 25 STRYKER CVAHU ZIO CONFIGURATION GUIDE Figure 30 Parameter Temp Sp Stby Clg Figure 32 Parameter Temp Sp Setpoint STBY CLG Displays and allows modification of SETPOINT Displays and allows modification of standby cooling setpoint lts value ranges from OCC centre setpoint read from wall module lts value CLG to UNOC CLG ranges from CNTSP LO to CNTSP HI Figure 31 Parameter Temp Sp Stby Htg Figure 33 Parameter Temp Sp Frz Prtc STBY HTG Displays and allows modification of FRG PRTC Displays and allows modification of standby heating setpoint Its value range
9. NEXT as per configuration requirement The Up and Down arrow keys switch the parameter between YES and NO view or no view in tenant mode o YES means that the tenant has access to the parameter on the VIEW MORE screen o NO means that the tenant does not have access to the parameter o If NO is selected for all parameters then the VIEW MORE soft key does not display in tenant mode Click NEXT soft key to cycle through the configured VIEW MORE screen s next parameter or category Click DONE soft key to save configuration changes Click CANCEL soft key to exit VIEW MORE without saving any changes Note Click NEXT DONE and CANCEL to do YES or NO configuration for below mentioned parameters After clicking NEXT on particular screen parameters are displayed in following order E ete ae AOohRRRRR RRA RRA WWHWOWHWOWWOWWHWONNDNDANNDANDANNMDA AA 2222120 DOMANDAAHBD A DOANDARWONDNA DOAOAANDUORWNHNAHA DOO ONOOAWD A OO ZIO HUM ROOMTEMP RH CO DISCHRG OAT OAH OCC SNSR WINDOW MON SWTH MON MODU CLG STG HTG STG DAMPER DMD LIMT TRMNL LD AUX ECON FREE MOD FREE DIG FAN OCC CLG OCC HTG UNOCC CLG UNOCC HTG STBY CLG STBY HTG SETPOINT FRZ PRTC EFF SP FANOVRD EMRGOVRD CLG OVRD HTG OVRD FAN OVRD FROST AQ ALM INVLD SP SPCTEMP ZO TOF ZO H OFF UNITS TYPE CNTR SP CNTSP HI CNTSP LO BYPS MIN HTGSP HI
10. STRYKER CVAHU ZIO CONFIGURATION GUIDE List of Tables Stryker reference COCUMENMS cccccccccseeseececeeeceueeseeceeeeeseeeeeeeceeeeseeeeeeeeeeesesseeseeceeeesseaeaeeeeeessaaaaeeeeeeeesaaas 9 ZIOVETETENCE dos UMSS aaa 10 List of applicable ier atu Gx iii a a 12 PAOEMIGY MISTING iii tica a tacos 13 TR values used by the space cooling pid CONTTOl cccooonccncccconnnnccononcnnnonnnncnnnnonnncnonononnnnnnnnnnnnnnnnnnanoss 35 IT values used by the space cooling Pid CONTTOl ooccccccconccnnccconnncnccnoncnnnnnnoncnnnonnnnnnnnononcnnnnonanrnnnnnnnns 36 TR values used by the space heating pid CONtFOl cooocccncccconncnnccnnnccnncnnoncnonononanonnnononnnnnnnnnrnnnnonannnns 37 IT values used by the space heating pid CONTFOL ooccccccccocncnnccconnnccnononcnnnonnnnnnnnonnnannnnonancnnnnnnnnnnnnnnnnns 37 STRYKER CVAHU ZIO CONFIGURATION GUIDE INTRODUCTION Description of Devices Stryker Lon Configurable CVAHU Controller Figure 1 Stryker Lon Configurable CVAHU Controller General The CUL6438SR CV1 is part of the Stryker family The controllers are Free Topology Transceiver FTT LONMARK certified devices designed to control HVAC equipment This is advanced system feature that allows state of the art commercial building control Each controller is configurable using the NAGARA FRAMEWORK software The Stryker controllers require the Stryker feature to be licensed in the WEBpro w
11. ZIO CONFIGURATION GUIDE STRYKER CV AHU Compatibility The TR70 Series LCD Wall Modules operate with the CONFIGURATION Sylk Enhanced Stryker controller The TR71 TR75 can replace a TR70 in an installation where an upgrade to WEBs AX or Stryker or reprogramming is BY ZIO WALL not desired Features like scheduling additional memory etc are not available Likewise a TR71 is replaced by another TR71 or TR75 without MODULE reprogramming required A TR75 can only be replaced with a TR75 where no reprogramming is desired Contractor Mode Introduction Contractor mode You can navigate to the desired category of parameters You can then begin A A configuring and viewing information from the device yt Each screen below has a brief explanation of the P y data values within the contractor mode are only visiable in English U S units of measure Temperatures however can be shown on the home screen as Cor F Contractor mode allows access to the Setup function Figure 4 Stryker CVAHU configuration by Zio wall maeule of the wall module To enter and exit the setup function press the up and down arrow keys and the Strykers are configured by the new TR71 75 wall middle soft key all at the same time see key positions modules Nearly every configuration parameter is of wall module as shown in Figure 5 available at the Zio wall module so configuration and even balancing is done by simply powering
12. are used by the space cooling PID control Table 6 IT values used by the space cooling pid control Without 1stg 3333 2stg 2000 With Economizer IT 2000 1429 1111 4stg 1111 36 Figure 64 Parameter Cnfg Ctl Htg Type HTG TYPE Displays and allows modification of heating output type for conventional or heat pump auxiliary heat as NONE 1STG 2STG 3STG 4STG ANA Default configuration 2STG Configuration settings in program are as follows 0 NONE 1 1STG 2 2STG 3 3STG 4 4STG 10 ANA Note 1 Modulating heating is not supported for heat pump auxiliary heat Automatic Gain Selection feature is enabled when Throttling Range TR is O Default TR is O STRYKER CVAHU ZIO CONFIGURATION GUIDE Figure 65 Parameter Cnfg Ctl Htg Tr Figure 66 Parameter Cnfg Ctl Htg It HTG TR Displays and allows modification of space HTG IT Displays and allows modification of heating heating PID control throttling range lts value ranges PID control integral time lts value ranges from O to from 0 to 30 AF 5000 sec Throttling Range TR Integral Time IT When TR is nonzero this value of TR is used by the When TR is nonzero this value of IT is used by the space heating PID control space heating PID control Auto Gain Selection Auto Gain Selection When TR is 0 Table 7 shows the TR values are used When TR is 0 Table 8 shows the IT values are used by the space heating PID control by t
13. can be changed as AO 1 AO 1 AO 2 DOC1 DOA1 DOA2 DOA3 DOB1 AO 2 DOC1 DOA1 DOA2 DOA3 DOB1 DOB2 DOB2 DOB3 DOB4 AO 3 and UNDEFINED DOB3 DOB4 AO 3 and UNDEFINED Default Parameter setting UNDEFINED Default Parameter setting UNDEFINED Configuration settings in program are as follows Configuration settings in program are as follows O AO1 O AO1 1 AO2 1 A02 2 DOC1 DO1 2 DOC1 DO1 3 DOA DO2 3 DOA DO2 4 DOA2 DO3 4 DOA2 DO3 5 DOA3 DO4 5 DOA3 DO4 6 DOB1 DOS 6 DOB1 DOS 7 DOB2 DO6 7 DOB2 DO6 8 DOB3 DO7 8 DOB3 DO7 9 DOB4 DO8 9 DOB4 DO8 10 AO3 10 AO3 255 UNDEFINED 255 UNDEFINED 49 STRYKER CVAHU ZIO CONFIGURATION GUIDE Figure 90 Parameter Cnfg Out Damper DAMPER Displays and allows modification of logical output configuration terminal assignment for Damper control signal This can be changed as AO 1 AO 2 AO 3 and UNDEFINED Default Parameter setting UNDEFINED Configuration settings in program are as follows O AO1 1 AO2 10 AO3 255 UNDEFINED 50 Time CVAHU controller time display Figure 91 Parameter Time Time TIME Displays current time in HH MM format STRYKER CVAHU ZIO CONFIGURATION GUIDE Set Time Set Date CVAHU controller time configuration settings CVAHU controller date configuration settings Figure 92 Parameter Set Time Hours Figure 94 Parameter Set Date Year HOURS Displays and allows modificati
14. function block STRYKER CVAHU ZIO CONFIGURATION GUIDE Status CVAHU parameter status display Figure 17 Parameter Status Htg Out Figure 19 Parameter Status Damper HTG OUT Displays cooling output signal DAMPER Displays damper output signal Figure 18 Parameter Status Clg Out Figure 20 Parameter Status Dmd Limit CLG OUT Displays heating output signal DMD LIMIT Displays demand limit setpoint shift status as ON or OFF Configuration settings in program are as follows 0 OFF 1 ON 255 OFF 22 Figure 21 Parameter Status Trmnl Ld TRMNL LD Displays effective terminal load on the controller lts value ranges from 160 to 160 A positive value indicates a cooling load and a negative value indicate heating load STRYKER CVAHU ZIO CONFIGURATION GUIDE Figure 23 Parameter Status Free Mod FREE MOD Displays configured free modulating1 output signal lts value ranges from 0 to 100 It is controlled by network command Figure 22 Parameter Status Aux Econ AUX ECON Displays auxiliary economizer status as ON or OFF Configuration settings in program are as follows 0 OFF 1 ON 255 UNDEFINED 23 Figure 24 Parameter Status Free Dtg FREE DTG Displays configured free digital 1 command status as ON or OFF It is controlled by network command Configuration settings in program are as follows 0 OFF 1 ON 255 UNDEFINED STRYKER CVAHU ZIO CONFIGURATION GUIDE
15. in program are as follows 0 F Deg F C Deg C 255 UNDEFINED Figure 45 Parameter Snsr Cal Zio H Of Figure 47 Parameter Wm Config Type ZIO H OF Displays and allows modification of Zio TYPE Displays and allows modification of type for humidity offset Its value ranges from 100 to wall module to be used as NONE TR20 ZIO 100 UNDEFINED Default configuration UNDEFINED Configuration settings in program are as follows 0 NONE No wall module 1 TR20 Conventional wall module TR20 2 ZIO ZIO TR71 TR75 255 UNDEFINED 31 STRYKER CVAHU ZIO CONFIGURATION GUIDE Figure 48 Parameter Wm Config Cntr Sp Figure 50 Parameter Wm Config Cntsp Lo CNTR SP Displays and allows modification of centre CNTSP LO Displays and allows modification of setpoint as FALS TRUE UNDEFINED This centre setpoint low limit lts value ranges from 10 to parameter defines whether centre Setpoint is to be CNTSP HI used or not Default configuration UNDEFINED Configuration settings in program are as follows 0 FALS 1 TRUE 255 UNDEFINED Figure 49 Parameter Wm Config Cntsp Hi Figure 51 Parameter Wm Config Byps Min CNTSP HI Displays and allows modification of centre BYPS MIN Displays and allows modification of wall setpoint high limit Its value ranges from CNTSP LO module bypass time setpoint in minutes Its value to 100 ranges from 0 to 1092 32 STRYKER CVAHU ZIO CONFIGURATION GUIDE Figure 52 Param
16. laca irrealidad eels 46 Parameter Ent OUL GIO SIO2 a a ada scinetauies sieves 46 Parameter Gata Out Clg SiGe a a ees 47 Parameter Ent QUE EA bal 47 Parameter Eng QUA dd eine cle 48 Parameter Cno Qui Alli di land 48 Parameter Ent QUO SIS si ida 49 Parameter Chg QUEEN DUE e e o dol loo 49 Parameter CO OUt Dampers serari id 50 Parameter TME CMO iria 50 Parameter Set Mme HOUS ai das 51 Parameter Set Time MIN rieien a ea a a a eaa ai 51 Parameter oet Date Ye rt A als 51 Parameter Set Date Monsanto PANER 51 Parameter Set Date Daycare E A A EEr E R ES 52 Parametros ds 53 Parameter Schedule Monday aestas iia 53 Parameter Schedule Monday Mon Ed occccccnccncccccnnccccnnnnnccnnncnnonnnnnnnnnnonononnnnnnnnnnnnnnnnnnnnnnnonnnnnnnnnnonnnnnnos 53 Tenantimode nome screen irse la dsd dato tias 54 Tenantmode Fan ALO mcsir eE Ea tenants peasenacbcaadedavbangpas 55 Tenant Mode Fan Oran aaa 55 Tenant Mode Fan Olinda tata tal 55 TenantOvernide rected et theca ot acter e oi 56 Tenant System and View More SYS MOE ccccccccsseeseececeeeeeeeeeeeeeeeeseeseeeeeceeeesseaeeeeeeesesaeaeeeeeeeeesaas 57 Tenant Mode ROOM TEM Dacor e in is ea den 57 Tenant mode Riann O 57 Tenant mode Dit o tn eos o a 58 lios AAA eee elie E E E ti leat 58 Tenantmode Cnt SP o ree tad ies 58 TENA mode A it 58 Tenant Mode HOU att 59 Tenant Moge Mierne E E E oca eodaoa 59 TenantMode Year ii 59 Table 1 Table 2 Table 3 Table 4 Table 5 Table 6 Table 7 Table 8
17. parameters e Ability to access and adjust most parameters in the programmable controller e R75 can access and adjust the controller schedule e Ability to balance the VAV system from the wall module e Home screen can display one out of three following parameters temperature setpoint room temperature room humidity outdoor humidity outdoor temperature and time or virtually any one of parameters in the controller e Network bus jack e Simple 2 wire terminal connection to the programmable controller includes power and an optional 2 wire terminal connection for the network All connections are polarity insensitive e Permanent retention of user configuration including Setpoints after a power outage For more information refer below mentioned documents as shown in Table 2 Table 2 Zio reference documents Croma w Zio Zio Plus LCD Wall Modules Wall Module Specification Data 63 1322 02 62 0271 07 Zio Zio Plus LCD Wall Modules Wall Module Installation Instructions 63 2719 LCD Wall Modules Wall operating guide Control Application Stryker CVAHU systems in commercial buildings typically incorporate a packaged air handler system that delivers a constant volume of air at preconditioned temperatures to the zone being served Each zone is usually serviced by a separate AHU however sometimes two or more AHUs service the same zone The Stryker CVAHU can control staged or modulating heating and
18. range configuration Figure 80 Parameter AO2 Range RANGE Displays and allows modification of analog output2 range This can be changed as 0D10 10D0 2D10 10D2 0A20 20A0 0A22 22A0 4A20 2044 DIG and UNDEFINED Default Parameter setting UNDEFINED Configuration settings in program are as follows O 5 8 9 10 209 0D10 Analog voltage 0 to 10VDC direct output 10D0 Analog voltage 0 to 10VDC reverse output 2D10 Analog voltage 2 to 10VDC direct output 10D2 Analog voltage 2 to 10VDC reverse output 0A20 Analog current O to 20 mA direct output 20A0 Analog current 0 to 20 mA reverse output 0A22 Analog current 0 to 22 mA direct output 22A0 Analog current 0 to 22 mA reverse output 4A20 20A4 Analog current 4 to 20 mA reverse output Analog current 4 to 20 mA direct output DIG Analog as binary output UNDEFINED AO3 Analog output3 range configuration Figure 81 Parameter AO3 Range RANGE Displays and allows modification of analog output3 range This can be changed as 0D10 10DO 2D10 10D2 0A20 20A0 0A22 22A0 4A20 20A4 DIG and UNDEFINED Default Parameter setting UNDEFINED Configuration settings in program are as follows O 0D10 Analog voltage O to 10VDC direct output 1 10D0 Analog voltage 0 to 10VDC reverse output 2 2D10 Analog voltage 2 to 10VDC direct output 3 10D2 Analog voltage 2 to 10VDC revers
19. up the controller connecting a Zio and then configuring the parameters available After configuration is done via the Zio an Integrator perform an upload and the LCD PANEL configuration is added to the WEBs AX station database Since Stryker has the capability to utilize Zio an installer uses a conventional sensor on all installed a Stryker units and then uses a single Zio to configure mr oe as many Stryker s as desired Since the Zio s program n and configuration are stored in the Stryker each time pus the Zio is connected to a new Stryker it gets its s SG program from that device _ o This document serves as a configuration guide for an installer who is configuring a Stryker CVAHU NETWORK BUS PORT ON BOTTOM OF CASE F arin controller via a TR71 or TR75 wall module Parameters are grouped into logical categories rather than on a large list To access the contractor mode for configuration press the up down and middle keys simultaneously During this time the model number Figure 5 Key position of wall module and firmware revision of the TR71 75 are displayed Contractor mode allows advanced options such as You are then prompted to enter a password default modifying configured parameters using the soft keys 0000 Contractor mode also allows for customizing the tenant s view including setting the tenant s Home screen and controlling the tenant s view more access which can provide
20. 5 Figure 56 Figure 57 Figure 58 Figure 59 Figure 60 Figure 61 Figure 62 Figure 63 Figure 64 Figure 65 Figure 66 Figure 67 Figure 68 Figure 69 Figure 70 Figure 71 Figure 72 Figure 73 Figure 74 Figure 75 STRYKER CVAHU ZIO CONFIGURATION GUIDE Parameter Alame Ol OM ai 28 Parameter Alann FO Oir a 29 Parameter Alarms Fan OVO ciar a E E O E E 29 Rarameletr Alanis Frost E 29 Parameter Alamo ad Alii eien E ica 29 Parameter Alaris NV O Dani e a e a a aa AA 30 Parameter Alame opc Tem Diesre n a aa 30 Parameter onsr Cal ZO TOR eRe a a e E 31 Parameter Sns Caza 31 Parameter Wm Conio UNS sii dt a a tai 31 Parameter Wm Contig A a ae ee lk N 31 Parameter Witt Contig Catral ias 32 Parameter Win Cong CNED Tal vecbe ne Siete cate eg cicada tela eee ta 32 Parameter Wm Contig CntSp LO ince eel e e td a 32 Parameter Wm Config BypS Min cccccccsseeeecceceeceaeeeeeeeceeeceeeeseeeeeeessaeeeeeeeeeseeeeeeseeeesssaaeaeeeeeessaaeasses 32 Parameter Wi Conta FIGS piloto ii 33 Parameter Wmi Conio Hosp LO id 33 Parameter Wm Contig CIOS Al di a di 33 Parameter Win Conti CIS Lia A E 33 Parameter Wim Conti End ld utili io idad 34 Parameter Wm Config Efhtg LO occccccccccnconnccnnncconononcnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnos 34 Parameter Win Config Etc locas srt rico 34 Parameter Wm GontigElcla Loera 34 Parameter Chig CIAD TYDE sprint dera lia iria 35 Parameter Cno CICIO TYP
21. ATION GUIDE Neuron LONWORKS LONMARK are registered trademarks of Echelon Corporation Automation and Control Solutions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 http www customer honeywell com Honeywell U S Registered Trademark 2013 Honeywell International Inc C G 11 2013 Printed in U S A on recycled 31 00023 01 E paper containing at least 10 Printed in United States post consumer paper fibers 60
22. DEFINED Default Parameter setting UNDEFINED Configuration settings in program are as follows O AO1 AO 2 IN U U Ug O O gt gt O N 2 J Q es Il J O WO N J O O O ON OO KR WwW PD Il Il J J O O 0 gt de Go J J O O J ES II II U U O O JJ JJ D i G _ aa an O O 00 al gt O wo 255 UNDEFINED STRYKER CVAHU ZIO CONFIGURATION GUIDE Figure 84 Parameter Cnfg Out Clg Stg3 Figure 85 Parameter Cnfg Out Hp Chang CLG STG3 Displays and allows modification of HP CHANG Displays and allows modification of logical output configuration terminal assignment for logical output configuration terminal assignment Heat Cooling or Heat Pump stage 3 Command This can Pump change over relay command This can be be changed as AO 1 AO 2 DOC1 DOA1 DOA2 changed as AO 1 AO 2 DOC1 DOA1 DOA2 DOA3 DOB1 DOB2 DOB3 DOB4 AO 3 and DOA3 DOB1 DOB2 DOB3 DOB4 AO 3 and UNDEFINED UNDEFINED Default Parameter setting UNDEFINED Default Parameter setting UNDEFINED Configuration settings in program are as follows Configuration settings in program are as follows O AO1 O AO1 1 AO2 1 AO2 2 DOC1 DO1 2 DOC1 DO1 3 DOA1 DO2 3 DOA1 DO2 4 DOA2 DO3 4 DOA2 DO3 5 DOA3 DO4 5 DOA3 DO4 6 DOB1 DO5 6 DOB1 DOS 7 DOB2 DO6 7 DOB2 DO6 8 DOB3 DO7 8 DOB3 DO7 9 DOB4 DO8 9 DOB4 DO8 10 AO3 10 AO3 255 UNDEFINED 255 UNDEFINED 47
23. E era td dl 35 Parameter Ena CUGO Tiers E EEN 35 Paramete Ging Gila onir an adi iia 36 Parameter Gre i ERO TYDE tia aida leia a a 36 Parameter cmo CIPRO Tis o td lirio 37 Parameter Cata CU HO aid a a cons taenseealted 37 Parameter cho Gils Fan Mode a a a a E 38 Parameter Grig C il OC SNOM osare a ede ee DO 38 lc a a a A a E EA a 39 Parameter le DD T er 5 e nie ea hl ele aie a 39 Parameter Gntg Spe TEM Pu ee e d aaa ed aa aaa ai eda aaa E 40 Parameter Crig lit SPS Rienie E E E aa 40 Parameter Cotg M SpE GCO cenite ieia a e a E e 41 Parameter Cnfg In Dischaliaiciai 2a conassdeondde dense badeed cee Asasndaeatacess ddansctacededenddcasasateeedeaneteddeasscacaca 41 Parameter Onon MING lorca 42 STRYKER CVAHU ZIO CONFIGURATION GUIDE Figure 76 Figure 77 Figure 78 Figure 79 Figure 80 Figure 81 Figure 82 Figure 83 Figure 84 Figure 85 Figure 86 Figure 87 Figure 88 Figure 89 Figure 90 Figure 91 Figure 92 Figure 93 Figure 94 Figure 95 Figure 96 Figure 97 Figure 98 Figure 99 Figure 100 Figure 101 Figure 102 Figure 103 Figure 104 Figure 105 Figure 106 Figure 107 Figure 108 Figure 109 Figure 110 Figure 111 Figure 112 Figure 113 Figure 114 Parameter Gnig MOC TOD alas 42 Parameter Grit Quin OCG OTS an iio 43 Parameter conto lin Window ectie a 43 Paame AMB eta iiO 44 Parameter AO2 RAS A ainda A A O age ems 44 Parameter AOS Rand e dd o ee aa E ee 45 Parameter Cia OU CI SiO
24. Honeywell STRYKER CVAHU ZIO CUL6438SR CV1 CONFIGURATION GUIDE Nov 2013 31 00023 01 STRYKER CVAHU ZIO CONFIGURATION GUIDE Table of Contents PTE OC UG TOI recess cs ee seces ee eee ee eee eens eee eae are ease ea ele a caesar etd 9 PSSM PMON Ol OGIO sinc Aaah cece hes dde linea deis 9 Stryker Lon Configurable CVAHU Conltroller oocccccoccococonnncocononoconnnconanonconanonononononanonnnnos 9 General ssn a E EAN 9 EOI Sree E ie rito rito a AT 9 Zio Zio Plus LCD Wall MoOdU ES oooooooonncccccnnononoccnnnnonononnnnnnnccnnnnnnnnnnononnnnnnnnnnncnnnnnnnnnnnnnnnnos 10 General scr seh er r buleeatie Gecce deeds eneen eseden eats 10 A e scaisaniedecetuo e a steak re N 10 CONtTOLAPPIC IUO asata aa dl di e lO E 10 Control Provided cast e eee eee 11 Products Over io edit aldo 12 OrganizalionorMantlal sis acrilico 12 Applicable USAS A Sout ae tela ie eee 12 Product NAMES si ais 12 AJENO ISA OS a 13 A AO 14 Constructions of Controller and Wall Module oocccccnnnncccccnnnncoccncccnncnnnnnnononononoonononannnnnnnnnnnnnnnnnos 14 Stryker CVAHU configuration by Zio wall module cccccceeesseeeeeeeneeeseeenneeeseeenseeeeeeesneeeseeneeeseonenseeseoeeneeesees 15 Contractor Mode INtWOCUCU OM seis dees arth A a 15 Nal Owen dd 16 Contractor Mode Configuration StepS ccccccccccccconccnnnncconononononnnonononanenonnnononnnnnnnnnonnnnannnnnnnnnnnnnnos 17 Set Home OCl COM PP y 17 O S56 ae gates ae asa ac
25. Unoccupied Tenant when scheduled to be unoccupied and the occupancy sensor is active switch to occupied for the comfort of the tenant 255 UNDEFINED Note 1 If an occupancy sensor is configured and the space is scheduled for occupied and the occupancy sensor is inactive the mode switches to standby Manual override commands have priority over the schedule and the occupancy sensor 3 Occupancy Sensor Behavior a 1 No occupancy detected inactive b 0 Occupancy detected active Cnfg Ui Configuration of CVAHU universal inputs Figure 69 Parameter Cnfg Ui Ui 1 Ul 1 Displays and allows modification of input type for universal input 1 This can be changed as NTC TR T TRAB TRRL DGNO and DGNC Default configuration NTC Configuration settings in program are as follows O NTC 20 KNTC 1 TR T TR2x 20KNTC 2 TRAB TR2x Setpoint Absolute 3 TRRL TR2x Setpoint Relative 14 DGNO Digital Normally Open 15 DGNC Digital Normally Closed Clicking NEXT the following parameters are available with configuration settings similar to UI1 Ul2 Universal Input2 UI3 Universal Input3 Ul4 Universal Input4 UI5 Universal Input5 UIG Universal Input6 39 STRYKER CVAHU ZIO CONFIGURATION GUIDE Cnfg Di Configuration of CVAHU digital inputs Figure 70 Parameter Cnfg Di Di 1 DI 1 Displays and allows modification of input type for digital input 1 This can be cha
26. adjust the fan settings depending on the fan options It has three possible positions 2 3 or 5 position configured Click the FAN soft key to change the fan icon to the following three positions as shown in Figure 101 1 AUTO Figure 103 Tenant mode Fan Off e Click the FAN softkey to toggle the fan icon between ON and AUTO If the fan is at 2 positions then each click on the FAN soft key changes the fan icon display between ON and AUTO e At position number 5 Fan icon display changes Figure 101 Tenant mode Fan Auto to one of the following two options o OFF Description Fan has three modes of operation o AUTO e AUTO Operates in Auto mode Refer Figure 101 e And Fan speed indicator is in one of the following e ON Operates in manual ON mode Refer Figure states 102 a o Low e OFF Operates in manual OFF mode Refer Figure 103 o Medium o High 2 ON Figure 102 Tenant mode Fan On 55 STRYKER CVAHU ZIO CONFIGURATION GUIDE Override Override allows the tenant to override the occupancy settings see Figure 104 Figure 104 Tenant Override Description Override is used to make CVAHU ON before or after occupied schedule or time Override remaining displays duration left in hours and minutes for the override For example if occupied duration is 9 00 AM to 6 00 PM and override operation is configured for one hour and if override is applied at 6 PM then override remaining will be 25
27. ant adjustable parameters e Click DONE soft key to save configuration changes e Click the CANCEL soft key to exit the display without saving any changes When the contractor configures a parameter and selects the Editable by tenant check box this enables the tenant to adjust the parameter s value e Click NEXT to access parameters in following sequence Figure 107 Tenant mode Rh RH Displays room humidity and is an input to the Sbus wall model function block STRYKER CVAHU ZIO CONFIGURATION GUIDE Figure 108 Tenant mode Oat Figure 110 Tenant mode Cntr Sp OAT Displays outside air temperature and is an input CNTR SP Displays and allows modification of centre to the Sbus wall model function block setpoint It is both an input and output to the Sbus wall model function block Figure 109 Tenant mode Eff Sp Figure 111 Tenant mode Time EFF SP Displays effective setpoint and is an input to TIME Displays controller time in HH MM format the Sbus wall model function block 58 STRYKER CVAHU ZIO CONFIGURATION GUIDE Figure 112 Tenant Mode Hours Figure 114 Tenant Mode Year MIN Displays and allows modification of time in YEAR Displays and allows modification of date in minutes lts value ranges from 0 to 59 years lts value ranges from 2008 to 2099 Figure 113 Tenant Mode Min HOURS Displays and allows modification of time in hours lts value ranges from 0 to 11 59 STRYKER CVAHU ZIO CONFIGUR
28. cooling coils mixed air economizer dampers and the system fan Control of heat pump units where the compressor s is used for both cooling and heating is also provided The zone the Stryker CVAHU services can use a TR71 75 for space temperature sensing and an S bus and LON bus network access for users via Zio and front end graphics respectively STRYKER CVAHU ZIO CONFIGURATION GUIDE Figure 3 shown below is typical Stryker CVAHU control application Q ies oe I WINDOW CONTACT Cn sep OCCUPANCY e Figure 3 Typical Stryker CVAHU control application Control Provided The Stryker CVAHU Controller is designed to control a single air handler to maintain the unit s space temperature at the current Setpoint Heating and cooling control are provided for either staged or modulating equipment Up to three stages of mechanical cooling and up to three stages of heating are allowed Modulating outputs can be either floating type such as a series 60 control or pulse width modulated PWM control The economizer dampers can be controlled directly with floating or PWM outputs or indirectly using a digital output as an enable disable signal to a packaged economizer controller The economizer enable function determines when to allow outdoor air for free cooling can be configured to one of the Strategies based on the inputs When the economizer position is controlled from the Stryker CVAHU the minimum position setting
29. e output 0A20 Analog current 0 to 20 mA direct output 20A0 Analog current 0 to 20 mA reverse output 6 0A22 Analog current 0 to 22 mA direct output 22A0 Analog current 0 to 22 mA reverse output 4A20 20A4 Analog current 4 to 20 mA reverse output Analog current 4 to 20 mA direct output 10 DIG Analog as binary output 255 UNDEFINED 45 STRYKER CVAHU ZIO CONFIGURATION GUIDE STRYKER CVAHU ZIO CONFIGURATION GUIDE Cnfg Out Configuration of CVAHU analog and digital outputs Figure 82 Parameter Cnfg Out Clg Stg1 CLG STG1 Displays and allows modification of logical output configuration terminal assignment for Cooling or Heat Pump stage 1 command This can be changed as AO 1 AO 2 DOC1 DOA1 DOA2 DOA3 DOB1 DOB2 DOB3 DOB4 AO 3 and UNDEFINED Default Parameter setting UNDEFINED Configuration settings in program are as follows O AO1 AO 2 Hol J Q Oo 0 N O Ol Bb W N ll J O gt OO J O X II U O gJ D U O 00 II II U g O O gt gt N L U O Go Il J O 2 Il J O WO N J O O Il J O 00 de J O J Il gt O wm 10 255 UNDEFINED 46 Figure 83 Parameter Cnfg Out Clg Stg2 CLG STG2 Displays and allows modification of logical output configuration terminal assignment for Cooling or Heat Pump stage 2 Command This can be changed as AO 1 AO 2 DOC1 DOA1 DOA2 DOA3 DOB1 DOB2 DOB3 DOB4 AO 3 and UN
30. eeeeeeessaageeeeeeeseeeessaneeees 15 Figure 6 TR70 Series Wall Module LCD screen oooccccncccnccccnnccnnncccononnnnnnnnnonnnnnnnnnnnnnonnnannnnnononnnnnnnnnnnnnnnnnnnnnnnnnns 16 Figure 7 Model number and Sylk DUS AUUTESS ooocccccccccccconncnnnccccnnonnncnnnnonononnnnnnnnnonnnnnnnnonnnononnnnnnnnnnnnnnnanannnnnns 16 Figure 8 Contractor mode default NOME SCreenN oooccccnnccccccconnccnnncccononnnnnnnnnonnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnns 17 Figure 9 OMe screen HOONMMEMD ei wrt a eaS 17 Figure 10 Home screen Room Setpoint ROO0MteMp ccccccccncccncnnnccccnnnnnncnnnncnonononnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnannnennnnns 17 Figure 11 Home screen Outside ROOM Temperature ooocccnccccccccncccnoncnnncononcnnnnonannnnnnnnnnrnnnnnnnnrncnnnnnrnnnnnnnnrnnnnnnnnos 18 Figure 12 Home screen Room Room Setpoint Temperature ccccccoocccncccconcnnnccnonnnnnonnnncnnnononaronnnnnnnnnnnnonnnonennannnss 18 Figure 13 Set View More FirSt SCTeen ooooocccccnccccccoonccnnnccnnnnonncnnnnnonnnnnnnnnnnnnnnnnnrnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnennnnnnns 18 Figure 14 Parameter Grou A a aa 20 Figure 15 Parameters Sensors Zio TOM srania e a a a a a ana a 20 Figure 16 Parameters Sensors Zio A iia 21 Figure 17 Parameter Status Htg Out cccccccccseseeccceeeeeeeeeeceeeeeeeeeseceeeeeeseeeceeeeeeeseeeeeeeeeeessseeeseeeeesseaaaeeeeeeeeesags 22 Figure 18 Parameter Status Clo OUt orn aid 22 Figure 19 Parameter Status
31. er eel VAV CVAHU Controller gene ene dial Senan econ Q7752A B Serial interface adapter 63 1322 02 Zio Zio Plus LCD Wall Modules Wall Module Specification Data 209541B Termination module 62 0271 07 Zio Zio Plus LCD Wall Modules Wall Module Installation Instructions 63 2719 LCD Wall Modules Wall operating guide 209541B LONW ORKS Bus Wiring Guidelines Termination Module Installation Instructions 12 STRYKER CVAHU ZIO CONFIGURATION GUIDE Agency Listings Table 4 Agency listing Tested and listed under UL916 Standard for open energy management equipment with plenum rating File number E87741 Listed E87741 LR95329 3 listed Meets FCC Part 15 Subpart B Class B radiated emissions controller Meets Canadian standard C108 8 radiated emissions Zio Zio Plus LCD wall modules TR70 TR71 TR75 with Sylk bus ar losa Conforms to the following requirements per European Consortium standards EN 61000 6 1 2001 EU immunity EN 61000 6 3 2001 EU emissions ul cu O csa foo ll E STRYKER CVAHU ZIO CONFIGURATION GUIDE Abbreviations AHU Air Handling Unit The central fan system includes the blower heating equipment cooling equipment ventilation air equipment and other related equipment CO Carbon Monoxide Occasionally used as a measure of indoor air quality CO Carbon Dioxide Often used as a measure of indoor air quality CPU Central Processin
32. eter Wm Config Htgsp Hi Figure 54 Parameter Wm Config Clgsp Hi HTGSP HI Displays and allows modification of CLGSP HI Displays and allows modification of heating setpoint high limit lts value ranges from cooling setpoint high limit Its value ranges from HTGSP LO to 100 CLGSP LO to 100 Figure 53 Parameter Wm Config Htgsp Lo Figure 55 Parameter Wm Config Clgsp Lo HTGSP LO Displays and allows modification of CLGSP LO Displays and allows modification of heating setpoint low limit Its value ranges from 0 to cooling setpoint low limit Its value ranges from 0 to HTGSP HI CLGSP HI 33 STRYKER CVAHU ZIO CONFIGURATION GUIDE Figure 56 Parameter Wm Config Efhtg HI Figure 58 Parameter Wm Config Efclg HI EFHTG HI Displays effective heating high setpoint EFCLG HI Displays effective cooling high setpoint Figure 57 Parameter Wm Config Efhtg Lo Figure 59 Parameter Wm Config Efclg Lo EFHTG LO Displays effective heating low setpoint EFCLG LO Displays effective cooling low setpoint 34 STRYKER CVAHU ZIO CONFIGURATION GUIDE Cnfg Ctl mm CVAHU configuration for control 1 Modulating cooling not compatible with Econo_ Type 1 Packaged Modulating compressor is not Supported for heat pump control Automatic Gain Selection feature is enabled when Throttling Range TR is O Default TR is O Figure 60 Parameter Cnfg Ctl Hp Type HP TYPE Displays and allows modification of heat pump type selection as CON GSHP
33. fication Data Stryker Lon Configurable 62 2029 02 VAV CVAHU Controller Installation Instructions STRYKER CVAHU ZIO CONFIGURATION GUIDE Zio Zio Plus LCD Wall Modules AP Figure 2 Zio Zio Plus LCD Wall Modules General The TR70 Series Zio TR70 TR70 H TR71 TR71 H and Zio Plus TR75 TR75 H are 2 wire non polarity sensitive and Sylk bus communicating wall modules for use with Spyder and Comfort Point programmable controllers All models have a space temperature sensor network bus jack and an LCD panel with three soft keys and two Up Down adjustment keys The TR7 H TR71 H and TR75 H models include an on board humidity sensor Refer to the Zio Zio plus LCD Wall Modules Operating Guide form 63 2719 for information about customizing the wall module configuration in the WEBs AX Workbench such as modifying the default Home screens or creating your own application Features The TR7O Series wall modules include e Ability to control tenant access to controller parameters via password protection e Ability to assign labels for enumerated values e Customized parameter access by using the Honeywell WEBs AX Workbench tool e Ability to link setpoint limits to a network variable e Programmable for home screen options tenant access contractor access optional password protection to contractor mode 10 access to controller parameters Setpoint override fan and other
34. g Unit cUL Underwriters Laboratories Canada CVAHU Constant Volume Air Handling Unit refers to a type of air handler with a single speed fan that provides a constant amount of supply air to the space it serves Echelon The Company that developed the LON bus and the Neuron chips used to communicate on the E bus Economizer Mixed air dampers that regulate the quantity of outdoor air that enters the building In cool outdoor conditions fresh air is used to supplement the mechanical cooling equipment Since this action saves energy the dampers are often referred to as economizer dampers EMI Electromagnetic Interference Electrical noise that can cause problems with communications signals EMS Energy Management System refers to the controllers and algorithms responsible for calculating optimum operational parameters for maximum energy savings in the building Enthalpy The energy content of air measured in BTUs per pound Kilojoules per Kilogram Firmware Software stored in a nonvolatile memory medium such as an EPROM Floating Control Floating Control utilizes one digital Output to pulse the actuator open and another digital output to pulse it closed FTT Free Topology Transceiver IAQ Indoor Air Quality lt refers to the quality of the air in the conditioned space as it relates to occupant health and comfort 14 I O Input Output the physical sensors and actuators connected to a controller R
35. he space heating PID control Table 7 TR values used by the space heating pid Table 8 IT values used by the space heating pid control control 37 STRYKER CVAHU ZIO CONFIGURATION GUIDE Figure 67 Parameter Cnfg Ctl Fan Mode FAN MODE Displays and allows modification of fan mode to be used for CVAHU This can be changed as CONT AUTO FAN and UNDEFINED Default configuration UNDEFINED Configuration settings in program are as follows O CONT Fan runs continuously when the effective occupancy is OC OCCUPIED or OC BYPASS The fan cycles on and off with demand for cooling and may cycle with heating if FanOnHeat is TRUE during OC UNOCCUPIED or OC STANDBY modes AUTO Fan cycles on and off with demand for cooling and may cycle with heating if FanOnHeat is TRUE This is known as the intermittent mode of operation FAN Enable local fan switch 255 UNDEFINED 38 Figure 68 Parameter Cnfg Ctl Oc Snorp OC SNORP Displays and allows modification of occupancy sensor operation status This can be changed as CLN CONF TNNT and UNDEFINED Default configuration UNDEFINED Configuration settings in program are as follows 1 CLN Unoccupied Cleaning Crew when scheduled to be unoccupied and the occupancy sensor is active switch to standby for the comfort of the cleaning crew CONF Conference Room when scheduled to be unoccupied stay unoccupied independent of the occupancy sensor activity TNNT
36. ings in program are as follows 0 FALS 1 TRUE 255 UNDEFINED 29 STRYKER CVAHU ZIO CONFIGURATION GUIDE Figure 40 Parameter Alarms Frost FROST Displays frost override status as TRUE FALS or UNDEFINED Configuration settings in program are as follows 0 FALS 1 TRUE 255 UNDEFINED Figure 41 Parameter Alarms laq Alm IAQ ALM Displays IAQ alarm override status as TRUE FALS or UNDEFINED Configuration settings in program are as follows 0 FALS 1 TRUE 255 UNDEFINED STRYKER CVAHU ZIO CONFIGURATION GUIDE Figure 42 Parameter Alarms Invid Sp INVLD SP Displays invalid setpoint override status as TRUE FALS or UNDEFINED Configuration settings in program are as follows 0 FALS 1 TRUE 255 UNDEFINED Figure 43 Parameter Alarms Spc Temp SPC TEMP Displays space temperature override status as TRUE FALS or UNDEFINED Configuration settings in program are as follows 0 FALS 1 TRUE 255 UNDEFINED 30 STRYKER CVAHU ZIO CONFIGURATION GUIDE Snsr Calibration Wm Config CVAHU sensor calibration CVAHU wall module configuration Figure 44 Parameter Snsr Cal Zio T Of Figure 46 Parameter Wm Config Units ZIO T OF Displays and allows modification of Zio UNITS Displays and allows modification of units to temperature offset lts value ranges from 100 to be displayed for temperature parameters as C F 100 UNDEFINED Default configuration UNDEFINED Configuration E
37. ion of logical input configuration terminal assignment for discharge air temperature This can be changed as SPC CO Displays and allows modification of logical input configuration terminal assignment for space CO This can be changed as UI 1 UI 2 UI 3 UI 4 UI 1 UI 2 UI 3 UI 4 UI 5 UI 6 SB8 SB9 SB10 UI 5 UI 6 and UNDEFINED SB11 SB12 and UNDEFINED Default Parameter setting UNDEFINED Default Parameter setting UNDEFINED Configuration settings in program are as follows ae pe Hing enh PIOo emai a tQUOn 0 Uli 1 Ul2 3 Ul4 2 Ul3 4 UI5 3 Ul4 5 UI6 4 UI5 21 SB8 C7400s temperature bus Address 8 5 U6 22 SB9 C7400s temperature bus Address 9 23 SB10 C7400s temperature bus Address 10 255 UNDEFINED 24 SB11 C7400s temperature bus Address 11 25 SB12 C7400s temperature bus Address 12 255 UNDEFINED Note 1 Up to 5 Sbus sensor are supported The Sbus address is fixed and the configuration enables addresses 8 through 12 2 Bus address DIPswitchVal 8 3 Sbus address is fixed Sensor Bus Address DIP SW 123 41 STRYKER CVAHU ZIO CONFIGURATION GUIDE Figure 75 Parameter Cnfg In Mixedair MIXEDAIR Displays and allows modification of logical input configuration terminal assignment for mixed air temperature This can be changed as UI 1 UI 2 UL 3 UI 4 UI 5 UI 6 SB8 SB9 SB10 SB11 SB12 and UNDEFINED Default Parameter setting UNDEFINED Co
38. ist for the selected category It displays the first 17 Set Date parameter in that category For example ZIO 18 Schedule TEMP parameter in the SENSORS category as shown in Figure 15 Figure 15 Parameters Sensors Zio Temp e If the parameter is configured as adjustable by the tenant the up and down arrow keys adjust the value of the parameter e Click NEXT soft key to display the next parameter or category e Click DONE soft key to save configuration changes e Click CANCEL soft key to the exit PARAMETER group or PARAMETER without saving any changes 20 Sensors CVAHU sensor value display Click the PARAMETERS soft key to display the first configured category SENSORS Within this category one sample Zio display is shown for reference and the remaining parameters are available for view only as per the following order Following is the path to access the screen as shown in Figure 16 CONTRACTOR gt PARAMETERS gt SENSORS gt 2ZI0 TEMP Figure 16 Parameters Sensors Zio Temp e Click CANCEL to return to SENSORS SENSOR is parameter group for this parameter e Click NEXT to access parameters in the following sequence ZIO TEMP Display Zio temperature which corresponds to the onboard temperature sensor and is an output of the Sbus wall module function block ZIO HUMIDITY Displays Zio humidity sensor from wall module ROOMTEMP Displays room temperature and is an input to the Sbus wall module func
39. le Stryker LON CVAHU controller is available as one model Organization of Manual CUL6438SR CV1 Constant volume air handling unit controller from Stryker LON family This manual is divided into two basic parts introduction and configuration The Introduction provides information for Stryker LON configurable CVAHU controller and TR7O e TR7O series Zio Zio Plus LCD wall modules control application control provided product covered and e TR7OH abbreviations e TR71 Configuration steps provide information for the The TR7O series Zio wall module is available in four models engineering of Stryker LON configurable CVAHU e TR IH controller by TR70 series Zio Zio Plus LCD wall The TR70 series Zio Plus wall module is available modules using its various function keys in two models The organization of the manual assumes a project e TR75 is being engineered from installation to finish e TR75H Applicable Literature List of documents containing information related to the configurable lighting controllers as shown in All models have a space temperature Table 3 sensor network bus jack and an LCD Table 3 List of applicable literature panel with three soft keys and two up down adjustment keys The TR70 H TR71 H and TR75 H models include an onboard 63 4529 03 Stryker Lon Configurable VAV CVAHU Controller l Specification Data Other products 62 2029 02 Stryker Lon Configurable Q7751A B Router configured as a repeat
40. me and changing the occupancy state i e OCC UNOCC STANDBY 3 Use the up down arrows to change occupancy state 4 Click DONE soft key to apply changed time and occupancy state settings 5 Click CANCEL soft key to exit the MON E1 screen display without saving any changes Figure 97 Parameter Schedule 6 Click NEXT and follow above mentioned steps 1 to step 6 to view or edit next three events I e Step 2 Use the EDIT soft key to move to the next ea ene iat MON E4 screen e g Monday a y To remove a programmed event use the up down arrow keys to scroll the time to either 12 00 p m or 12 00 a m Just before reaching 12 00 the time changes to four dashes Click the DONE soft key at this point to remove a programmed event In the 5 2 or 5 2 1 schedule options e 5 means Monday to Friday and Monday s events are shown on the Zio e 2 means Saturday and Sunday and Saturday s events are shown on the Zio e 1 means holiday When Monday is changed the TR75 copies that event to Tuesday and so on till Friday It updates this Figure 98 Parameter Schedule Monday schedule into the controller for Monday through Friday The same occurs for Saturday and Sunday when a change is made on Saturday When a holiday is modified it is also updated into the controller 53 STRYKER CVAHU ZIO CONFIGURATION GUIDE Tenant Mode ntrod ucti on Tenant mode default home screen may be in any o
41. minutes at 6 35 PM e Depending on the occupancy override configuration click the OVERRIDE soft key The occupancy icon changes to one of the following three modes o Standby o Occupied o Unoccupied e f an override is set by the tenant the OVERRIDE soft key changes to CANCEL OVERRIDE e Click the CANCEL OVERRIDE soft key to cancel the override 96 System View More Click the system amp view more key to change the system state and view adjust configured parameters see Figure 105 Figure 105 Tenant System and View More Sys mode e Click the key The first click displays the system information Click the up and down arrow keys The system state can assume one of the following states o Off o Auto o Cool o Heat e lf the contractor enables tenants access to a parameter then the tenant can use the up and down arrow keys to adjust the parameter s value otherwise the tenant is able to only view the parameter and its value e Click DONE soft key to save configuration changes e Click the CANCEL soft key to exit the display without saving any changes e Click VIEW MORE soft key to display each viewable parameter 97 STRYKER CVAHU ZIO CONFIGURATION GUIDE For example Figure 106 Tenant mode Room Temp ROOM TEMP Displays room temperature and is an input to the Sbus wall model function block e Use the UP DOWN arrow keys on Zio module to increase or decrease the value or state for ten
42. ne of out of above mentioned four home screen set by the contractor The tenant using the soft keys and arrow keys may Refer Set H E vet nome ocreen change following features if these are configured 1 Setpoints Fan speed HOME SCREEN label ROOMTEMP 2 3 System mode heat cool o Description Displays system status and room 4 Initiate override temperature e The tenant can change the Occupancy By referring to Figure 100 Tenant mode home Override parameter to Occupied screen has the following three soft keys They Unoccupied or Standby And the override provide the following options which are explained can be timed in minutes days or be below in detail continuous 1 Fan Note 2 Override Following parameters home screen s in 3 System and view mode Tenant view adjust mode are for reference only and may change as per configuration done in contractor mode Note 1 The fan and override settings are optional for home screen setup lf the system command option is not Te nant Mode View enabled then the SYSTEM soft key does not display on the tenant s home screen Steps lf there are no parameters configured for tenant s access the VIEW MORE soft key l does not display on the tenant s home Figure 100 for reference screen Tenant mode default home screen is as shown Figure 100 Tenant mode home screen 54 STRYKER CVAHU ZIO CONFIGURATION GUIDE Fan 3 OFF The tenant uses Fan to
43. nfiguration settings in program are as follows O UI1 1 Ul2 2 UI3 3 UI4 4 UI5 5 UI6 21 SB8 C7400s temperature bus Address 8 22 SB9 C7400s temperature bus Address 9 23 SB10 C7400s temperature bus Address 10 24 SB11 C7400s temperature bus Address 11 25 SB12 C7400s temperature bus Address 12 255 UNDEFINED 42 Figure 76 Parameter Cnfg In Od Temp OD TEMP Displays and allows modification of logical input configuration terminal assignment for outside air temperature This can be changed as UI 1 UI 2 UI 3 UI 4 UI 5 Ul 6 SB8 SB9 SB10 SB11 SB12 and UNDEFINED Default Parameter setting UNDEFINED Configuration settings in program are as follows O UI1 1 Ul2 2 UI3 3 Ul4 4 UI5 5 UI6 21 SB8 C7400s temperature bus Address 8 22 SB9 C7400s temperature bus Address 9 23 SB10 C7400s temperature bus Address 10 24 SB11 C7400s temperature bus Address 11 25 SB12 C7400s temperature bus Address 12 255 UNDEFINED STRYKER CVAHU ZIO CONFIGURATION GUIDE Figure 77 Parameter Cnfg In Occ Snsr Figure 78 Parameter Cnfg In Window OCC SNSP Displays and allows modification of WINDOW Displays and allows modification of logical logical input configuration terminal assignment for input configuration terminal assignment for window occupancy sensor This can be changed as UI 1 UI contacts This can be changed as UI 1 UI 2 UI 3 UI 2 UI 3 UI 4 UI 5 UI6
44. nged as DGNO DGNC and UNDEFINED Default configuration UNDEFINED Configuration settings in program are as follows 14 DGNO Digital Normally Open 15 DGNC Digital Normally Closed 255 UNDEFINED Clicking NEXT the following parameters are available with configuration settings similar to DI1 DI2 Digital Input2 DIS Digital Input3 DI4 Digital Input4 STRYKER CVAHU ZIO CONFIGURATION GUIDE Cnfg In Configuration of CVAHU inputs Figure 71 Parameter Cnfg In Spe Temp SPC TEMP Displays and allows modification of logical input configuration terminal assignment for space temperature This can be changed as Ul 1 Ul 2 UI 3 UI 4 UI 5 UI 6 ZIO and UNDEFINED Default Parameter setting UNDEFINED Configuration settings in program are as follows 0 Uli 1 Ul2 Ul3 Ul4 UI5 Ul6 ZIO 255 UNDEFINED N A A O N Il 40 Figure 72 Parameter Cnfg In Spe Rh SPC RH Displays and allows modification of logical input configuration terminal assignment for space relative humidity This can be changed as UI 1 UI 2 UI 3 Ul 4 Ul 5 UI 6 ZIO and UNDEFINED Default Parameter setting UNDEFINED Configuration settings in program are as follows 0 Uli 1 Ul2 2 Ul3 3 Ul4 4 UI5 5 UI6 7 ZIO 255 UNDEFINED STRYKER CVAHU ZIO CONFIGURATION GUIDE Figure 73 Parameter Cnfg In Spe CO Figure 74 Parameter Cnfg In Dischair DISCHAIR Displays and allows modificat
45. on of time in YEAR Displays and allows modification of date in hours lts value ranges from 0 to 11 years lts value ranges from 2008 to 2099 Figure 93 Parameter Set Time Min Figure 95 Parameter Set Date Month MIN Displays and allows modification of time in MONTH Displays and allows modification of date in minutes lts value ranges from 0 to 59 months lts value ranges from 0 to 12 51 STRYKER CVAHU ZIO CONFIGURATION GUIDE Figure 96 Parameter Set Date Day DAY Displays and allows modification of date in days lts value ranges from 0 to 31 52 STRYKER CVAHU ZIO CONFIGURATION GUIDE Schedule Step 3 Use the EDIT soft key to move to the next screen e g MON El The Schedule option lets you modify the schedule and change CVAHU Stryker s time The desired scheduling option 8 day 7 days etc is setup in the Configuration Wizard refer 63 2719 LCD Wall Module Wall Operating Guide The option screens vary based on that selection Following example illustrates the steps for viewing editing a schedule for Monday You can similarly view edit schedule for Saturday and any other holiday Step 1 To access schedule parameter group refer section Parameters Figure 99 Parameter Schedule Monday Mon E1 Click the EDIT soft key to change the time and occupancy state for this event 1 Use the up down arrows to change the time 2 When editing an event use the NEXT soft key to toggle between editing the ti
46. orkbench tool and the WEBs AX JACE Controller for programming It can download to any brand of the Niagara Workbench or JACE controller Controllers are used in VAV Variable Air Volume and CVAHU Constant Volume Air Handling Unit control applications Each controller contains a host microcontroller to run the main HVAC application and a second microcontroller for LONWORKS network communications Each controller provides flexible universal inputs for external sensors digital inputs and a combination of analog outputs and digital outputs STRYKER CVAHU ZIO CONFIGURATION GUIDE Features e Uses the Echelon LONW ORKS network protocol e Free Topology Transceiver FTT high speed 78 kilobits communications network e Capable of stand alone operation but may also use LONWORKS bus network communications e Sylk bus for use with Sylk enabled sensors e 120 controllers per Q7751A B router when configured as a repeater e Field configurable for control input and output functions using the NAGARA FRAMEWORK software Built in zone control functions include a remote wMarkall module interface and a scheduler e All wiring connections are made to removable terminal blocks to simplify controller installation and replacement For more information refer below mentioned documents as shown in Table 1 Table 1 Stryker reference documents Stryker Lon Configurable 63 4529 03 VAV CVAHU Controller Speci
47. res vices nat deere code crak a teva cence a a ta ae eee aetna 18 A O 20 o A E 21 EILE e E E E EE E E ENEE a T E E EE E EE E 22 A ener ei ceke ene neers reenter ee eee een ee eee eee oe 25 OVE MOG irp ER 28 AAN Soa a a a ats cota uniter a E 28 nn a Senora erry 31 WCG ONO cerat eta ciatteod cate eaahancnnsaii inline eaianctedl dade tetendaatanatecu Aen aaatedtosaiadsecats 31 A eee a oC nee eee one a oe eee 35 A eer etch TAE ce eters eet eon ec ener se meer cee eee ae 39 MO Drs cia 39 a 40 O A mee ee 44 STRYKER CVAHU ZIO CONFIGURATION GUIDE OA o A A 44 DS A A o O A ees eee 45 A A E 46 TWN Cisse hase wie estate baaa 50 o 51 A a ae re eee nee ee 51 A a N 53 Tenant Mode Introducir ii 54 Tenant Mode View StS ii E 54 A o e dele 55 y A on 56 SYSTEMS VEW MOTE sales 57 STRYKER CVAHU ZIO CONFIGURATION GUIDE List of Figures Figure 1 Stryker Lon Configurable CVAHU Controller ooccccccoconccnnccconnconcononccnnononnncnncononncnnononnnnnnonannnnncnnannons 9 Figure 2 Zio Zio Plus LCD Wall Modules 02 le ddciad 10 Figure 3 Typical Stryker CVAHU control applicatiON ooccccccccccoconnncnnnnccononnncnnnnncnnnnancnonnnononannnnnnnnnnnnnnnnnnnnons 11 Figure 4 Stryker CVAHU configuration by Zio wall module occcoocccncccconccnncnoncconnnonancnnnnnnnnnnnnnonannncononnnnnonnnnnons 15 Figure 5 Key position of wall MOUIC ccccccsseeeeecceeeeceeceeeeeceeeeeeeseeeeeeueeeeeseeeeeeesseeeeeeess
48. s from OCC Space freeze protection setpoint Its value ranges HTG to UNOC HTG from 30 to 70 The space heating setpoint is shifted to this value when a window is opened 26 STRYKER CVAHU ZIO CONFIGURATION GUIDE Figure 34 Parameter Temp Sp Eff Sp EFF SP Displays room temperature effective setpoint lts value ranges from 40 to 100 27 STRYKER CVAHU ZIO CONFIGURATION GUIDE Override Alarms CVAHU override used for fan CVAHU parameter alarms Figure 35 Parameter Override Fan Ovrd Figure 36 Parameter Alarms Emrg Ovrd FAN OVRD Displays and allows modification of EMRG OVRD Displays smoke detector status as supply fan override command as ON OFF or TRUE FALS or UNDEFINED UNDEFINED Configuration settings in program are as follows Default configuration UNDEFINED 0 FALS 1 TRUE 255 UNDEFINED Configuration settings in program are as follows 0 OFF 1 ON 255 UNDEFINED Figure 37 Parameter Alarms Clg Ovrd CLG OVRD Displays cooling override status as TRUE FALS or UNDEFINED Configuration settings in program are as follows 0 FALS 1 TRUE 255 UNDEFINED 28 Figure 38 Parameter Alarms Htg Ovrd HTG OVRD Displays heating override status as TRUE FALS or UNDEFINED Configuration settings in program are as follows 0 FALS 1 TRUE 255 UNDEFINED Figure 39 Parameter Alarms Fan Ovrd FAN OVRD Displays fan override status as TRUE FALS or UNDEFINED Configuration sett
49. saving any changes 17 STRYKER CVAHU ZIO CONFIGURATION GUIDE Figure 9 Home screen Roomtemp Home screen ROOMTEMP Description Default home screen displays room temperature setpoint is not adjusted from this home screen as shown in Figure 10 ROOM SETPOIN TEMPERATURE IONE Figure 10 Home screen Room Setpoint Roomtemp Home screen ROOM SETPOINT ROOMTEMP Description Displays room temperature and effective room temperature setpoint setpoint is not adjusted from this home screen STRYKER CVAHU ZIO CONFIGURATION GUIDE JUTSIDE TEMPERATURE JOHE Figure 11 Home screen Outside Room Temperature Home screen OUTSIDE ROOMTEMPERATURE Description Displays outside air temperature and room temperature setpoint is not adjusted from this home screen ROOM SETPOINT TEMPERATURE 1 Te ta T E a E m HE A CANCE Figure 12 Home screen Room Room Setpoint Temperature Home Screen ROOM ROOM SETPOINT TEMPERATURE Description Displays room temperature and room setpoint temperature setpoint is adjusted from this home screen 18 Set View More SET VIEW MORE allows the contractor to provide parameter access view only or adjustable to the tenant s VIEW MORE soft key Click SET VIEW MORE soft key to display the first configured parameter as shown in Figure 13 Figure 13 Set View More First screen The soft keys changes to DONE CANCEL and
50. tes with any onboard sensor display such as temperature The TR71 TR75 also display the firmware revision number model number and Sylk bus address as shown in Figure 7 Figure 7 Model number and Sylk bus address On power up screen displays revision and Zio model number 16 Contractor Mode Configuration Steps The Contractor Mode screen as shown in Figure 8 Figure 8 Contractor mode default home screen The three soft keys on the contractor home screen provide the following three options 1 Set home screen 2 Set view more 3 Parameters Set Home Screen SET HOME SCREEN allows the contractor to choose among multiple home screen options for the tenant The tenant s home screen choices are created by the configuration wizard and downloaded to the wall module Each wall module may have different home screen choices The contractor using the soft keys may choose which home screen is to be used He may configure the Tenant view to show a subset or none of the configured parameters When the contractor clicks the SET HOME SCREEN soft key the display changes as shown in the Figure 9 to Figure 12 The soft keys change to DONE CANCEL and NEXT as per configuration requirement e Click NEXT soft key to cycle through the configured home screens e Click DONE soft key when the desired home screen to be set as default home screen for Tenant view e The CANCEL soft key exits the home screen display without
51. the tenant with a view of the configured parameters 15 STRYKER CVAHU ZIO CONFIGURATION GUIDE Controller features not supported by Zio In Itial Powe r U p configuration e Network functionality IMPORTANT 1 Make sure the TR70 Series wall module is properly mounted and properly wired and connected to the programmable controller e Accessory loops e Custom sensors Refer to the Zio LCD wall modules TR70 e Local sensor UI 1 4 calibration Series with Sylk bus installation CVAHU controller default configuration instructions form no 62 0271 for specific installation requirements e Wall module Zio e Center setpoint source Zio mac yeep ogi ly Conter setpoint disable controller ignores i center setpoint value display status as PLEASE LOAD As shown in j Figure 6 the startup screen of the wall module where e Center setpoint high limit 100 the status is displayed And also illustrates all the possible LCD Wall Module display elements Only those elements pertinent to e Room temperature source Zio TR71 75 the current configuration and status actually display e Center setpoint low limit 10 LABEL ROOM SETPOINT HUMIDITY OUTSIDE VALUE ii A O O OO OT 8 CHAR i NASO DaS Dan PA DSA DT MT Mt l ES OVERRIDE ROOMSETPOINTTEMPERAJURE ENGINEERING REMAINING i PPM y VALUE i i PHILS e Se a Figure 6 TR70 Series Wall Module LCD screen This phrase alterna
52. tion block RH Displays room relative humidity and is an input to the Sbus wall module function block CO Displays room CO PPM and is an input to the Sbus wall module function block STRYKER CVAHU ZIO CONFIGURATION GUIDE DISCHRG Displays discharge air temperature and is an input to the Sbus wall module function block OAT Displays outside air temperature and is an input to the Sbus wall module function block OAH Displays outside air humidity and is an input to the Sbus wall module function block OCC SNSR Displays occupancy sensor and is an input to the Sbus wall module function block Status is displayed as follows OCC UNOC BYPS STBY UNDEFINED Configuration settings in program are as follows 0 OCC Occupancy Mode 1 UNOC UN occupancy Mode 2 BYPS Bypass Mode 3 STBY Standby Mode 4 UNDEFINED WINDOW Displays window open closed contact status and is an input to the Sbus wall module function block Status is displayed as follows CLOS OPEN UNDEFINED Configuration settings in program are as follows 0 CLOS Window close status 1 OPEN Window open status 2 UNDEFINED MON SWTH Displays monitory switch and is an input to the Sbus wall module function block Status is displayed as follows OFF ON UNDEFINED Configuration settings in program are as follows 0 OFF 1 ON 255 UNDEFINED MON MODU Displays mon modulation and is an input to the Sbus wall module

Download Pdf Manuals

image

Related Search

Related Contents

Kicker S18X Owner's Manual  企業における 自律的な安全衛生管理の 進め方検討会  Manuale dell`utente Master ATX new v 1_0  User Manual IDK-2108 Series    User guide for casual work delegators – allocate and amend roles in  DCM Series - QSC Service  P95-002-00057-002 EN-ES 3D+_3D30 ROAD  "CAS-3300BT"  HP All in One Printer 3380 User's Manual  