1. SAFETY DEVICE SETTING Device Set point Differential Differential Control thermostat summer C 20 2 Control thermostat Domestic hot water C 40 2 Control thermostat winter C 40 2 ui Anti freeze thermostat C 4 6 MANUAL Electric heater thermostat C 4 6 MANUAL High pressure switch Bar 28 T MANUAL Low pressure switch Bar 0 7 1 MANUAL Water safety valve Optional Bar 6 ELECTRIC DATA Power supply VI IHz 230 1 50 Sizes 06 08 10 400 3 N 50 Sizes 10T 14 21 26 31 41 Control board VI IHz 2411150 Auxiliary circuit VI IHz 230 1 50 Fans power supply VI IHz 230 1 50 Electric data may change for updating It is therefore necessary to refer always to the wiring diagram inside the units WARNING All this operation described in next chapters MUST BE DONE BY TRAINED PEOPLE ONLY Before every operation of servicing on the unit be sure that the electric supply is disconnected INSPECTION When installing or servicing the unit it is necessary to strictly follow the rules reported on this manual to conform to all the specifications of the labels on the unit and to take any possible precautions of the case Not observing the rules reported on this manual can create dangerous situations After receiving the unit immediately check its integrity The unit left the factory in perfect condition any eventual damage must be questioned to the carrier and recorded on the Delivery Note before it is signed MAX
2. CONDITIONING R R407c 00 029 L80 LLOITUIN SIS TTE RASSE TVNNVUN NOLL L 4 E e NOLL VITV LSNI sapaesiadns aosinyijso ainysoig Hojejeyanboyejeg obojeje 90 HVMH nyjuonip3 euorssiug eueg aueg seueg auog HIGH EFFICIENCY AIR TO WATER HEAT PUMPS SCROLL COMPRESSORS WITH DOMESTIC HOT WATER PRODUCTION HWAR High efficiency air to water heat pumps MUI0111081520 00 HWAR High efficiency air to water heat pumps INDEX Declaration of conformity Aim and contents of this manual How to keep this manual Graphic symbols Safety laws General safety guidelines Workers health and safety Protective equipment Safety signs Unit description Operation limits Corrections tables Sound Data Safety Device Setting Electric data Inspection Lifting and handling Location and minimum technical clearances Installation of the hoods Hydraulic connections Basic version hydraulic components Domestic hot water hydraulic connections Electrical connections Start up Controls during operation Maintenance and periodic checks Refrigerant circuit repair Environment protection Unit out of service Fault finding Dimensions MUI0111081520 00 3 page3 page 6 page 6 page 6 page 7 page 7 page 8 page 8 page 8 page 9 page 10 page 11 page 11 page 12 page 12 page 12 page 12 page 13 page 14 page 15 page 16 page 17 page 18 page 18 page 19 page 19 page 20
3. WARNING Never switch off the unit for temporary stop by opening the main switch this component should be used only to disconnect the unit from power supply when the current is not passing through ie when the unit is in OFF mode Moreover with no supply to crankcase heater at the unit start up compressor could be seriously damaged WARNING Do not modify internal wiring of the unit otherwise warranty will terminate immediately WARNING The summer winter operation must be selected at the beginning of the related season Frequent change over of the seasonal operation mode must be avoided in order to prevent severe damage to compressors HWAR High efficiency air to water heat pumps An Lcn CONTROLS DURING UNIT OPERATION e Check the fans rotation If the rotation is incorrect disconnect the main switch and change over any two phases of the incoming main supply to reverse motor rotation only for units with three phase fan motors e Check that water temperature at evaporator inlet is near to the set point of the control thermostat e For A version units units with pumps and storage tank if the motor driven pump should be noisy slowly close discharge shut off valve until normal working conditions are restored This trouble may occur when system pressure drop is quite different from pump available pressure Refrigerant charge checking e After few hours the unit is working check that sight glass shows a green colour core if the cor
4. 2 wires of 2 5 mm section Power supply cables must be separated by remote control wires Maximum distance 50 metres WARNING The remote control panel can not be installed in area in with strong vibrations corrosive gases excess of dirtiness or high humidity level Leave free the area near the cooling openings START UP Before start up Check that all power cables are properly connected and all terminals are hardly fixed The voltage at the phase R S T is the one shown in the unit labels Check that there is not any refrigerant leakage Check that crankcase heaters are powered correctly Check that all water connections are properly installed and all indications on unit labels are observed The system must be bleed off in order to eliminate any air Before start up check that all the cover panel are re located in the proper position and locked with fastening screws WARNING Crankcase heaters must be powered at least 12 hours before start up by closing the main switch heaters are automatically supplied when main switch is closed The crankcase heaters are working properly if after some minutes the compressor crankcase temperature is about 10 15 C higher than ambient temperature Start up and switch off Push Fo 5 seconds to run the unit in heating mode Push the same key for 5 seconds to switch off Push for 5 seconds to run the unit in cooling mode Push the same key for 5 seconds to switch off A MUI0111081520 00 18
5. DATA HWAR SL LOW NOISE VERSION Octave bands Hz Lw Lp Mod 63 125 250 500 1K 2K 4K 8K dB dB dB dB dB dB dB dB 9H dB A dB A 06 08 80 9 72 3 66 2 64 7 63 6 58 2 54 8 45 7 81 9 68 0 40 0 10 10 80 9 72 3 66 2 64 7 63 6 58 2 54 8 45 7 81 9 68 0 40 0 14 81 9 73 3 67 2 65 7 64 6 59 2 55 8 46 7 82 9 69 0 41 0 21 86 9 78 3 72 2 70 7 69 6 64 2 60 8 51 7 87 9 74 0 46 0 26 91 9 83 3 77 2 75 7 74 6 69 2 65 8 56 7 92 9 79 0 51 0 31 91 9 83 3 77 2 75 7 74 6 69 2 65 8 56 7 92 9 79 0 51 0 41 91 9 83 3 77 2 75 7 74 6 69 2 65 8 56 7 92 9 79 0 51 0 HWAR SL LOW NOISE VERSION WITH SUPPLY RETURN SOUND ATTENUATION HOODS Octave bands Hz Lw Lp Mod 63 125 250 500 1K 2K 4K 8K dB dB dB dB dB dB dB dB MB dB A 06 08 76 1 67 3 61 2 59 7 58 6 53 2 49 8 40 7 76 9 63 0 35 0 10 10T 76 1 67 3 61 2 59 7 58 6 53 2 49 8 40 7 76 9 63 0 35 0 14 77 1 68 3 62 2 60 7 59 6 54 2 50 8 41 7 77 9 64 0 36 0 21 82 1 73 3 67 2 65 7 64 6 59 2 55 8 46 7 82 9 69 0 41 0 Lw Sound power level according to ISO 3746 Lp Sound pressure level measured at 10 mt from the unit in free field conditions direction factor Q 2 according to ISO 3746 MUI0111081520 00 WARNING The sound pressure level of the STANDARD VERSIONS without compressor jackets and compressor vane insulation is approx 1 5 dB A higher than the equivalent low noise versions LS HWAR High efficiency air to water heat pumps ARNAN
6. HWAR High efficiency air to water SCHEMA DIMENSIONALE HWAR 06 08 10 10T oe ee ee ee D 1 oT HWAR High efficiency air to water HWAR High efficiency air to water HWAR High efficiency air to water heat pumps An Lcn HWAR High efficiency air to water heat pumps An Lcn MUIO111081520 00 26 HWAR High efficiency air to water heat pumps An Lcn NOTE MUI0111081520 00 27 AIR CONDITIONING Via Gettuglio Loc La Macia 37040 Arcole Verona Italy Tel 39 045 76 36 585 r a Fax 39 045 76 36 551 r a www maxa it e mail maxa maxa it The data indicated in this manual is purely indicative The ma nufacturer reserves the right to modify the data whenever it is considered necessary
7. exchangers are made of AISI 316 stainless steel braze welded plates type The use of these kind of heat exchangers allows a massive reduction of the refrigerant charge of the unit compared to the traditional shell in tube evaporators and also a reduction of the overall dimensions of the unit The user heat exchangers are factory insulated with flexible close cell material and can be equipped with antifreeze heater optional Each heat exchanger is provided with a temperature sensor as antifreeze protection Electric box The electric box is made according to electromagnetic compatibility norms CEE 73 23 and 89 336 The accessibility to the board is possible after removing the front panel of the unit The protection degree is IP55 In all HWAR units are installed standard the compressors sequence relay who disable the operation of the compressor in case the power supply phase sequence is not the correct one scroll compressors in fact can be damaged if they rotate reverse wise The following components are also standard installed main switch magnetic thermal switches as a protection of pumps and fans compressors fuses control circuit automatic breakers compressor contactors fan contactors pump contactors The terminal board is supplied with voltage free contacts for remote ON OFF winter summer change over and general alarm Microprocessors All HWAR units are supplied standard with microprocessor controls The microprocessor controls the foll
8. m dari Vitae Phares Pisas alge S pannong Prmen requena Patron epp nig F Tera Cuts ancien C C Ld Cam mre rere arua inb Crsnerie mmr cdi Mypcrbed curent shaving Manufachieed by BV ITA 40 02 1236 Macarius Mais GRRE TINA del 23 magi TET PE D I Curae da m n m m D X Jl Tipa ci nedeigesachs Carica celrigerante peer circula type GPa gee per Kateri Typ n Type de nord je de ceca che Grog Taratura peesaoshato di alta Presi radaima curae Ma Prize rez pipt praebuit Mas Deeds avi E renal Vr adegen mdi zs cud rarae MUIO111081520 00 9 HWAR High efficiency air to water heat pumps ANXN OPERATION LIMITS Heating mod 10T 14 21 26 31 41 only Outlet water temperature C Ambient temperature C User heat exchanger water flow rate The nominal water flow rate given by MAXA is referred to a Dt of 5 C Maximum flow rate allowed is the one that presents a Dt of 3 C higher values may cause too high pressure drop The minimum water flow rate allowed is the one presenting a Dt of 8 C Insufficient values cause too low evaporating temperatures with the action of safety devices which would stop the unit User hot water temperature winter opera
9. page 20 page 20 page 20 page 22 HWAR High efficiency air to water heat pumps An Lcn The HWAR manual contains any information that is needed for a correct use of the equipment while safeguarding operator safety according to what indicated from Council Directive 98 37 CE and following changes AIM AND CONTENTS OF THIS MANUAL This manual provides basic information on the installation operation and maintenance off the HWAR unit It is addressed to machine operators and it enables them to use the equipment efficiently even if they do not have any previous specific knowledge of it This manual describes the characteristics of the equipment at the time it is being put on the market therefore it may not capture later technological improvements introduced by MAXA as part of its constant endeavour to enhance the performance ergonomics safety and functionality of its products HOW TO KEEP THIS MANUAL The manual must be always with the unit it refers to It must be stored in a safe place away from the dust and moisture It must be accessible to all users who shall consult it any time they are in doubt on how to operate the equipment MAXA reserves the right to modify its products and related manuals without necessarily updating previous versions of the reference material The customer shall store any updated copy of the manual or parts of it delivered by the manufacturer as an attachment to this manual MAXA is available to give any detailed informat
10. the connection labelled USER WATER IN otherwise the heat exchangers may freeze WARNING It is compulsory to install on the USER WATER IN connection a metallic filter with a mesh not larger than 1 mm The presence of the filter is to be considered mandatory the warranty will no longer be valid if it is removed The filter must be kept clean so make sure it is clean after the unit has been installed and then check it periodically WARNING All units are factory supplied with the flow switch it is factory installed in the A versions supplied loose in the standard versions The flow switch MUST BE INSTALLED on the water outlet connection labelled USER WATER OUT If the flow switch is altered removed or the water filter should not be present on the unit the warranty will be invalidated Please refer to the wiring diagram for flow switch electric connections MUI0111081520 00 15 HWAR High efficiency air to water heat pumps ARNAN BASIC VERSION HYDRAULIC COMPONENTS E j l E D DAL LU Ww rd A System filling group L Water pump B Thermometer M One way valve C Flexible connection N Evaporator D Ball shut off valve Flow switch E Water strainer P User Water tank F Expansion vessel Q Water manometer G Safety valve R Domestic hot water accumulator H Vent valve S Domestic hot water feeding Water tank Drainage valve MUI0111081520 00 16 HWAR High efficie
11. A must be informed within 8 days of the extent of the damage The Customer should prepare a written statement of any severe damage LIFTING AND HANDLING When unloading the unit it is highly recommended to avoid any sudden Pan move in order to protect al i refrigerant circuit copper Pad R tubes or any other unit E i ay component Units can be cr 1 duy lifted by using a forklift or in alternative using belts being sure that the method of lifting does not damage the lateral panels b P and the cover It is M i important to keep the unit horizontal at all time to avoid damages to the A internal components MUIO111081520 00 12 HWAR High efficiency air to water heat pumps Ane PDHSBIF IDASHEH LOCATION AND MINIMUM TECHNICAL CLEARANCES HWAR units are designed for external installation any cover over the unit and location near trees even if they partially cover the unit must be avoided in order to prevent air by pass It is advisable to create a proper basement with a size similar to unit foot print Unit vibration level is very low it is advisable however to fit a rigid rubber band between basement and unit base frame If it is the case it is possible to install anti vibration mounts spring or rubber to keep vibrations at a very low level Absolute care must be taken to ensure adequate air volume to the condenser Re circulation of discharge air must be avoided failure to observe this p
12. an thermal m Manual the event expires then proceed with A11 Digital input active protection alarm manual reset Automatic with next proper defrost cycle A12 Defrost error alarm Max defrost time Proceed reset A13 Running hour gt 14 Manual Proceed with the hour reset procedure A14 m bald Running hour CO15 Manual Proceed with the hour reset procedure A15 mainenange Running hour warning Manual Proceed with the hour reset procedure rtC Clock alari Ne dito setthe clock time Manual Set the clock and then proceed with manual reset Manual Proceed with manual reset if nothing rtF Clock alarm Faulty clock control happens change the clock Manual Proceed with manual reset if nothing EE EEPROM error alarm Possible data losing happens the controller is locked no regulation available ACF1 Configuration alarm Heat pump winot Automatic After parameter proper debu 9 reversing valve p 9 without condensing probe ACF2 Configuration alarm control configuration Automatic After parameter proper debug ACF3 Configuration alarm Tao digra inputs Automatic After parameter proper debug same function FErr Functioning alarm Two digital inputs activated at Manual after the alarm event expires proceed the same time with manual reset AFr The frequency of power supply Frequency alarm is out of range Automatic After the frequency becomes normal MUI0111081520 00 21
13. connected from electric and pneumatic power source and after its pneumatic system has been discharged Do not put your hands or insert screwdrivers spanners or other tools into moving parts of the equipment their tasks in safety Operators must know how to use personal protective devices and must know the accident prevention guidelines contained in national and international laws and norms A The equipment supervisor and the maintenance man must receive training suitable for the performance of MUI0111081520 00 5 HWAR High efficiency air to water heat pumps ARNAN WORKERS HEALTH AND SAFETY The European Community has adopted a number of directives on workplace health and safety which include directives 89 391 CEE 89 686 CEE 89 655 CEE 86 188 CEE and 77 576 CEE Every employer shall implement such provisions and ensure that workers respect them Donot tamper with or replace parts of the equipment without the specific consent of the manufacturer The manufacturer shall have no responsibility whatsoever in case of unauthorised operations JP Using components expendable materials or spare parts that do not correspond to those recommended by the manufacturer and or listed in this manual may be dangerous for the operators and or damage the equipment The operator s workplace must be kept clean tidy and free from objects that may camper free movements Appropriate lighting of the work place shall be provided so as to allo
14. d MUI0111081520 00 10 HWAR High efficiency air to water heat pumps CORRECTION TABLES Operation with glycol Glycol percentage Freezing point IPCF WFCF PDCF 10 3 2 0 985 1 1 02 1 08 20 7 8 0 98 0 99 1 05 1 12 30 14 1 0 97 0 98 1 09 1 22 40 22 3 0 965 0 97 1 14 1 25 50 33 8 0 955 0 965 1 2 1 33 CCF Capacity correction factor IPCF Input power correction factor WFCF Water flow correction factor PDCF Pressure drops correction factor The water flow rate and pressure drop correction factors are to be applied directly to the values given for operation without glycol The water flow rate correction factor is calculated in order to maintain the same temperature difference as that which would be obtained without glycol The pressure drop correction factor takes into account the different flow rate obtained from the application of the flow rate correction factor CORRECTION TABLES different DT Water temperature diff C 3 5 8 CCCP 0 99 1 1 02 IPCF 0 99 1 1 01 CCCP Cooling capacity correction factor IPCF Input power correction factor CORRECTION TABLES Different Fouling factors Fouling factor 0 00005 0 0001 0 0002 CCCP 1 0 98 0 94 IPCF 1 0 98 0 95 CCCP Cooling capacity correction factor IPCF Input power correction factor SOUND
15. d a vapour injection system used to enlarge the working range The compressors are all supplied with crankcase heater and thermal overload protection by a klixon embedded in the motor winding They are mounted in a separate chamber in order to be separated from the air stream The crankcase heater is always powered when the compressor is in stand by The inspection is possible through the frontal panel of the unit that allow the maintenance of the compressors even if the unit is working Source heat exchanger The source heat exchangers are made of copper pipes and aluminium fins The diameter of the copper pipes is 3 8 and the thickness of the aluminium fins is 0 1 mm The tubes are mechanically expanded into the aluminium fins to improve the heat exchange factor The geometry of these condensers guarantee a low air side pressure drop and then the use of low rotation and low noise emission fans The source heat exchangers can be protected by a metallic filter to be installed on request Fans The fans are axial type with aluminium aerofoil blades They are statically and dynamically balanced and supplied complete of the safety fan guard according to EN 60335 They are mounted on the unit frame by interposition of rubber vibration dampers The electric motors are all at 6 poles about 900 rpm The motors are directly driven with an integrated thermal overload protection The protection class of the motors is IP 54 User heat exchangers The user heat
16. d the water pipes plus an armoured electric heater fitted inside the water tank This device is controlled by the microprocessor and it is used in the version A1 with integrated hydraulic kit INTEGRATION ELECTRIC HEATER To be installed in the water tank can be used to integrate the water in case the heat pump can not reach the set point due to very critical ambient conditions The device can be installed in the water tank A1 versions only to integrate the user hot water temperature or supplied separately to integrate the domestic hot water temperature circuit MUI0111081520 00 8 HWAR High efficiency air to water heat pumps UNIT DESCRIPTION fff This chapter contains a general description of main unit characteristics together with those of its principal standard and optional components IDENTIFICATION Unit identification The unit can be identified throug the plats attached on the frame and in the electrical box This label contains the following information Manufacturer s name Manufacturer s address Description of the series and type of unit Series number Year of construction Type and quantity of refrigerant liquid Max Allowable pressure Pressure switch set point EC certification symbol Electrical characteristics Wiring diagram identification bey Env TTA AUD 1 20 Magie tl sett A Pee Mace hee aac uer Temiri Fim mpera Termin anis
17. e is yellow moisture would be present in the circuit In this case it is necessary circuit dehydration to be carried out by qualified people only Check that at the sight glass there is no continuous vapour bubbles presence In this case additional refrigerant charge could be required It is however allowed the presence of few vapour bubbles e Few minutes after the start up working on summer operating mode cooling check that condensing temperature is approximately 15 C higher than condenser inlet air temperature Check moreover that evaporation temperature is bout 5 C lower than the evaporator outlet temperature e Check that refrigerant superheat on the evaporator is about 5 7 C e Check if refrigerant sub cooling on the condenser is about 5 7 MAINTENANCE AND PERIODIC CHECKS WARNING All this operation described in this chapter MUST BE DONE BY TRAINED PEOPLE ONLY Before every operation of servicing on the unit be sure that the electric supply is disconnected The top shell and discharge line of compressor are usually at high temperature level Be very careful when operating in their surroundings Aluminium coil fins are very sharp and can cause serious wounds Be very careful when operating in their surroundings After servicing operation close the unit with cover panels fixing them with locking screws Itis a good rule to carry on periodic checks in order to verify the correct working of the unit e Check that safety and control dev
18. eat exchanger used as condenser for the domestic hot water that is independently from the operation mode of the unit The activation of the additional heat exchanger is done automatically by the microprocessor control when the domestic hot water temperature measured by the sensor is lower than the required set point This unit allow the production of cold and hot water at the same time independently This version is supplied with return supplied domestic hot water sensors and advanced control panel with specific software able to manage the operation priorities HWAR A1 HIGH EFFICIENCY HEAT PUMP WITH INTEGRATED HYDRAULIC KIT The HWAR heat pumps can be delivered as option with a built in hydraulic kit that includes Water tank in different sizes depending on the size of the unit factory insulated with flexible close cell material and prepared for the installation of antifreeze kit option The water tank is installed on the hot water outlet water side to minimize the inevitable fluctuations in the water temperature due to the compressors starts and stops The installation of the water tank on the hot water outlet water side keeps constant for a period of time the user water temperature when the compressors are Off while this can not be obtained if the water tank is installed on the hot water inlet water side Water pump centrifugal type suitable for chilled water operation The pump is directly controlled by the microprocessor that controls its co
19. harged with nitrogen using a gas bottle with a pressure reducing valve until 15 bar pressure is reached Any eventual leakage must be searched with a bubble leak finder In case bubbles appear discharge the circuit before welding with proper alloys WARNING Never use oxygen instead of nitrogen explosions may occur ENVIRONMENT PROTECTION According to European norms dealing with the use of depleting stratospheric ozone substances it is forbidden to release refrigerants fluids in the atmosphere They must be redelivered to the seller or to proper gathering points at the end of their operating life Refrigerant R407C is mentioned among controlled substances and for this reason it must be subjected to the mentioned norms A particular care is recommended during service operations in order to reduce as much as possible any refrigerant loss UNIT OUT OF SERVICE Once the unit is arrived at the end of its life and needs to be removed or replaced the following operations are recommended e the unit refrigerant has to be recovered by trained people and sent to proper collecting centre e compressor lubricating oil has to be recovered and sent to proper collecting centre e frame and various components if not usable any longer have to be dismantled and divided according to their nature particularly copper and aluminium which are present in conspicuous quantity in the unit These operations allow easy material recover and recycling process reduci
20. ices work correctly as previously described monthly Check all the terminals on the electric board and on the compressor are properly fixed Check and clean the sliding terminals of the contactors Check refrigerant charge by sight glass check leakages from compressor monthly Check water leakages in the hydraulic system monthly If the unit is to be expected to be stopped for a long period unit hydraulic circuit should be emptied from all the tubes and heat exchanger This operation is compulsory if during seasonal stop ambient temperature is expected to go down below the freezing point of employed mixture typical seasonal operation e Check flow switch proper working clean metallic filters on water piping monthly e Check compressor crankcase heater proper supply and functioning monthly e Clean finned coils metallic filters with compressed air in the opposite direction of the air flow If filters should be fully clogged clean them with a water jet monthly e Check mounting of fan blades and their balancing every 4 months e Check the colour of the sight glass core green no moisture yellow moisture present if it has a yellow colour change the refrigerant filter every 4 months MUI0111081520 00 19 HWAR High efficiency air to water heat pumps ARNAN REFRIGERANT CIRCUIT REPAIR In the case that refrigerant circuit should be discharged all the refrigerant must be recovered with proper machines The system must be c
21. ion about this manual and to give information regarding the use and the maintenance of its own units GRAPHIC SYMBLS Indicates operations that can be dangerous for people and or disrupts the correct operation of the equipment EN Indicates prohibited operations Indicates important information that the operator must follow in order to guarantee the correct operation of the equipment in complete safety MUI0111081520 00 4 HWAR High efficiency air to water heat pumps An Lcn SAFETY LAWS MAXA equipment and their component parts have been designed in compliance with the harmonised EC norms in force and other European and national norms as required by the Council Directive 98 37 and later amendments The equipment i salso compliant with Norms EN 292 1 e 292 2 Norma EN 294 Norms EN 378 1 378 2 378 3 e 378 4 Norma EN 418 Norma EN 953 Norma EN 1050 Norma EN 60204 1 Norma EN 61000 6 2 Norma EN 61000 6 4 Community Directives 98 37 CE 97 23 CE 93 68 CEE 89 336 CEE 73 23 CEE GENERAL SAFETY GUIDELINES Before beginning to operate on HWAR units every user must be perfectly knowledgeable about the functions of the equipment and its controls and must have read and understood the information container in this manual It s strictly forbidden to remove and or camper with any safety device Any routine or not routine maintenance operation shall be carried out when the equipment has been shut down dis
22. ly WARNING Before any service operation on the unit be sure that the electric supply is disconnected WARNING Inside the unit some moving components are present Be very careful when operating in their surroundings even if the electric supply is disconnected WARNING The top shell and discharge line of compressor are usually at high temperature level Be very careful when operating in their surroundings WARNING Aluminium coil fins are very sharp and can cause serious wounds Be very careful when operating in their surroundings WARNING After servicing operation close the unit with cover panels fixing them with locking screws HYDRAULIC CONNECTIONS Unit water pipe work must be installed in accordance with national and local regulation pipes can be made either in steel galvanized steel or PVC Pipes have to be designed depending on the nominal water flow and the hydraulic pressure drops of the system All pipes must be insulated with closed cell material of adequate thickness The chillers have to be connected to the piping by using flexible joints Piping should include Temperature and pressure gauges for the ordinary maintenance or servicing operations Shut off manual valves to separate the unit from the hydraulic circuit Metallic filters to be mounted on the inlet pipe with a mesh not larger than 1 mm Vent valves expansion tank with water filling discharge valve WARNING Unit water inlet must be in correspondence with
23. ncy air to water heat pumps DOMESTIC HOT WATER HYDRAULIC CONNECTIONS SA VERSIONS ONLY 010111081 520 00 17 HWAR High efficiency air to water heat pumps ELECTRICAL CONNECTIONS It must be verified that electric supply is corresponding to the unit electric nominal data tension phases frequency reported on the label in the front panel of the unit Power connections must be made in accordance to the wiring diagram enclosed with the unit and in accordance to the norms in force Power cable and line protection must be sized according to the specification reported on the form of the wiring diagram enclosed with the unit N A A WARNING The line voltage fluctuations can not be more than 5 of the nominal value while the voltage unbalance between one phase and another can not exceed 2 If those tolerances should not be respected please contact our Company WARNING Electric supply must be in the limits shown in the opposite case warranty will terminate immediately Before every operation on the electric section be sure that the electric supply is disconnected WARNING The Flow switch must be connected following the indication reported in the wiring diagram Never bridge the flow switch connections in the terminal board Guarantee will be invalidated if flow switch connections are altered or not properly made WARNING The remote control panel is connected to the water chiller by
24. ng environmental impact FAULT FINDING Cod Meaning Cause Origin Reset Missing faulty probe or resistance exceeding value P1 Pb1 probe alarm Automatic if the probe value recovers Missing faulty probe or P2 Pb2 probe alarm resistance exceeding value Automatic if the probe value recovers Missing faulty probe or P3 Pb3 probe alarm resistance current exceeding Automatic if the probe value recovers value Missing faulty probe or resistance exceeding value P4 Pb4 probe alarm Automatic if the probe value recovers Digital input for high pressure Manual after the alarm event expires proceed AM Hight pressure activated with manual reset Digital input for low pressure Manual after the alarm event expires proceed A02 Low pressure switch alarm activated with manual reset MUIO111081520 00 20 HWAR High efficiency air to water heat pumps Cod Meaning Cause Origin Reset A07 Anti freeze alarm so Meee Manual proceed with manual reset A08 Water flow alarm Digital input active for AL06 Automatic It turns to manual after 3 events in 1 duration hour A09 Compressor 1 thermal Digital input active Manual the event expires then proceed with protection alarm manual reset A10 Compressor 2 thermal Digital input active Manual the event expires then proceed with protection alarm manual reset Condenser f
25. oint will result in poor performance or activation of safety controls For these reasons it is necessary to observe the following clearances E T MOD A B C D E 06 800 500 500 500 500 08 800 500 500 500 500 B 10 101 800 500 500 500 500 14 1000 500 500 500 500 D E 21 1000 500 500 500 500 Lu 06 500 500 500 500 500 08 500 500 500 500 500 10 10T 500 500 500 500 500 14 500 500 500 500 500 21 500 500 500 500 500 MUI0111081520 00 13 HWAR High efficiency air to water heat pumps i gt H 1 uu D 22 C o Pd MOD A B C D E 26 1000 800 800 800 3000 31 1000 800 800 800 3000 41 1000 800 800 800 3000 INSTALLATION OF THE HOODS FSH PI Pia eine The sound attenuation hoods are supplied loose they have to be mounted on the unit by Self screwing screws M3 5 x 16 supplied in the installation kit MUI0111081520 00 14 HWAR High efficiency air to water heat pumps WARNING The equipment should be installed so that maintenance and or repair services be possible The warranty does not cover costs due to lifting apparatus and platforms or other lifting systems required by the warranty interventions WARNING All the maintenance operation must be done by TRAINED PEOPLE on
26. owing functions regulation of the water temperature antifreeze protection compressor timing compressor automatic starting sequence alarm reset The control panel is supplied with display showing all operational icons The microprocessor is set for automatic defrost in case of operation in severe ambient conditions and for summer winter domestic hot water change over SA versions only Upon request any microprocessor can be connected to a BMS system for the remote control and management The technical department is available to study together with the customer different solutions using MODBUS LONWORKS BACNET or TREND protocols MUI0111081520 00 7 HWAR High efficiency air to water heat pumps An Lcn Control and protection devices All units are supplied with the following control and protection devices Return user water temperature sensor antifreeze protection sensor installed on the user outlet water temperature return and supply domestic hot water sensors SA versions only high pressure switch with manual reset low pressure switch with automatic reset high pressure safety valve compressor thermal overload protection fans thermal overload protection pressure transducer used to optimize the defrost cycle and the fan speed depending on the ambient conditions flow switch OTHER VERSIONS HWAR SA UNIT WITH DOMESTIC HOT WATER PRODUCTION This version is suitable to produce domestic hot water the unit is supplied with an additional h
27. rrect operation In the hydraulic circuit are also present the expansion vessel the safety valve and the eventual manual valves with fittings HWAR SL LOW NOISE VERSION This version includes the complete acoustic insulation of the unit compressor heat exchangers vanes with compressor jackets and insulating material made with high density media and the interposition of heavy bitumen layer ACCESSORIES SOUND ATTENUATION HOODS mod 06 08 10 10T 14 21 only These devices are installed on the units to minimize the sound level they are made from hot galvanised thick sheet metal painted with polyurethane powder enamel at 180 C to ensure the best resistance against the atmospheric agents The hoods are internally insulated with PU foam material with the interposition of high density non toxic bitumen free barrier They are mounted on the unit by stainless steel screws REMOTE CONTROL PANEL It allows the remote control of all parameters of the unit RUBBER VIBRATION DAMPERS To be installed beneath the unit base and the ground to avoid the transmission of vibrations and the noise to the building EVAPORATOR ANTIFREEZE HEATER It is made by a self heating electric cable mounted around the evaporator in order to avoid dangerous freezing of the water inside it It is controlled by the microprocessor It can be used in the units without hydraulic kit ANTIFREEZE KIT It is made by a self heating electric cable mounted around the evaporator an
28. they can operate down to 15 C ambient temperature All models are supplied standard with reverse cycle valve for cold water production Frame All HWAR units are made from hot galvanised thick sheet metal painted with polyurethane powder enamel at 180 C to ensure the best resistance against the atmospheric agents The frame is self supporting with removable panels All screws and rivets for outdoor installations are in stainless steel The colour of the units is RAL 7035 Refrigerant circuit The refrigerant gas used in these units is R407C The refrigerant circuit is made by using international primary brands components and according to ISO 97 23 conceming welding procedures The refrigerant circuit includes sight glass filter drier double thermal expansion valves one for cooling mode one for heating mode with external equalizer 4 way reverse cycle valve one way valves liquid receiver Schrader valves for maintenance and control pressure safety device according to PED regulation Models starting from 10T are also supplied with an AISI316 stainless steel heat exchanger used as economizer and additional expansion valve for refrigerant vapour injection Compressors The compressors used are high performance scroll type supplied with a special scroll design who enhance the efficiency of the refrigerant cycle at low ambient conditions Units starting from model 10T are also supplied with an additional heat exchanger used as economizer an
29. tion Once the system is on temperature user hot water temperature at the user heat exchanger inlet does not have to be less than 30 C lower values could cause incorrect working operation of the compressor and compressor failure may occur The maximum user water temperature can not exceed 60 C sizes 10T 14 21 26 31 41 or 55 C sizes06 08 10 higher values may call the action of safety devices with unit stop Cold water temperature summer operation The minimum temperature allowed at the evaporator outlet is 5 To work below this limit the unit should need some structural modifications In this case contact our company The maximum temperature allowed at the evaporator outlet is 15 Ambient air temperature The units are designed and manufactured to operate In winter operation heating mode from 15 C to 25 C In cooling mode the units can operate with ambient air temperatures from 20 to 43 WARNING All units are supplied standard with evaporation condensing pressure control This device allows unit operation in heating mode over 15 and in cooling mode under 20 ambient temperature The device modulates the airflow measured by a pressure transducer obtaining in this way correct operating parameters This device can be used as well to reduce unit sound level emission in cooling mode when ambient temperature is decreasing i e during night time Fan speed control is factory pre set The values must never be modifie
30. w the operator to carry out the required operations safely Poor or too strong lighting can cause risks Ensure that work places are always adequately ventilated and that aspirators are working in good condition and in compliance with the requirements of the laws in force gt gt gt PERSONAL PROTECTIVE EQUIPMENT When operating and maintaining the HWAR unit use the following personal protective equipment Protective clothing Maintenance men and operators must wear protective clothing that complies with the basic safety requirements currently in force In case of slippery floors users must wear safety shoes with non slip soles Gloves During maintenance or cleaning operation protection gloves must be used GO J Mask and googles Respiratory protection mask and eye protection goggles should be used during cleaning and maintenance operations SAFETY SIGNS The equipment features the following safety signs which must be complied with General hazard Electric shock hazard gt gt MUI0111081520 00 6 HWAR High efficiency air to water heat pumps An Lcn TECHNICAL CHARACTERISTICS The high efficiency HWAR heat pump series have been especially designed for application with radiant floor heating systems or in those applications where it is necessary to have the highest maximum efficiency in heating mode The units have been optimized for heating mode they are able to produce water up to 60 C and