VF03 FULL - HyControl
Contents
1. Flange Connector Cable 54 FEP coated o o e i 3 Diam 28 Twin cable Connector Diam 102 e les Flange Cable Weight Hycontrol VF SERIES Installation and operating instructions Page 18 10 00 7 3 Replacement of the signal converter Always disconnect power before assembling the signal converter Hazardous duty systems Before replacing the signal converter instrument head in a hazardous location make absolutely certain that there is no explosion hazard gas free certificate 1 Disconnect all cables from the instrument See Section 7 6 2 Remove the 4 Allen screws M Allen key size 4 mm 0 16 and lift off the signal converter The flange system will remain sealed DANGER On pressurised tanks do not in any case remove the 4 screws H connecting the VF SERIES flanges with
2. 2 character T J Z 3 character I T U 4 character Q F V CISIEIN ___5 character R E U 6 character R E U 7 character Q F V 8 character R E U 9th character Q F V QSS lt The above table can be used to decode the password Hycontrol VF SERIES Installation and operating instructions 8 5 16 WATCH STATUS Displays the status of the device Tank Full Tank Empty Level Lost EEPROM Error RAM Error ROM Error Digitising Error Gain Error Offset Error Positive Voltage Error Negative Voltage Error VCO1 Voltage Error VCO2 Voltage Error Checksum Error Bank Customer 0 Checksum Error Bank Factory 0 Checksum Error Bank Customer 1 Checksum Error Bank Factory 1 Delay out of limits Reference Not Found Flange Not Found Reference Lost First Start Error reprogramming FPGA Error Parity FPGA Each status is explained in sections 8 2 and 8 3 8 5 17 Display of the PC program PC STAR 2 Language of displayed texts Choose one of the following languages for the display e GB USA English e D German e F French 8 5 18 Hardware test At each start up the VF SERIES executes automatically a hardware test Several voltage values as well as other tests of the audio signal are performed During normal operation the VF SERIES performs real time tests in order to guarantee a correct and reliable operation In case of an unlikely problem
3. 5 4 Repeatability Repeatability is equal to half the value of the error of measurement 5 5 Measured value resolution Measured value resolution is 1 mm 0 04 5 6 Transient recovery time The transient recovery time is determined by the setting parameter time constant 1 100 s The transient recovery time relative to 1 deviation from the steady state value is approx 4 6 times the time constant However in the case of unusual rapid changes in level the transient recovery time may deviate from this figure 5 7 Turn on characteristics turn on drift After the VF SERIES has been switched on the current output is fixed to 22 mA during 15 seconds Next the current output is driven to probe length until a product reflection is detected The current output will then rise to the measured value Full measuring accuracy is obtained after 23 seconds operating time with default parameters time constant 5 seconds Hycontrol VF SERIES Installation and operating instructions Page 10 10 00 Typical turn on drift example Current mA 25 15 10 Time sec 0 5 10 15 20 30 Startup Research Measurment Current output value Variable duration depending on probe length for a probe of 24 meters the research can take up to 40 secondes The long term drift is within the specified error of measurement Temperature coefficient signal output Current output with HART signal lt 0 01 K typical
4. REFLEX VF SERIES Process connection or flange Sensor material d Sada Viton Kalrez Other Sensor type Power supply 24V DC Standard 124 V DC Exi Brand Sensor length CONNECTION sise DIN connector M16 Connector Special items Additional calibration OIE en Sessa cheat cae 12 External standards codes and directives EN 500014 1977 VDE 0170 0171 part 1 1 87 Electrical apparatus for potentially explosive atmospheres General requirements EN 500020 1977 VDE 0170 0171 part 7 4 92 Electrical apparatus for potentially explosive atmospheres Intrinsic Safety i DIN VDE 0170 0171 part 13 11 86 Requirements for equipment of Zone 10 in German DIN EN 50081 1 VDE 0839 part 81 1 1993 03 Electromagnetic compatibility EMC General emission standard Part 1 Residential commercial and light industry EN 50082 2 1995 03 Electromagnetic compatibility generic immunity standard Part 2 industrial environment NAMUR Recommendation for the interference immunity of electronic devices EMC 18 05 1999 in English DIN EN 61010 1 VDE 0411 part 1 1993 04 Safety requirements for electrical equipment for measurement control and laboratory use General requirements in German Directive 89 336 EEC CE marking
5. Fct 1 2 6 2 CONVERSION FACTOR The conversion factor reference is the millimeter If the conversion factor is equal to 10 then the new unit is equivalent to centimeter 10 mm If the conversion factor is equal to 0 1 the new unit is equivalent to one tenth of millimeter 0 1mm 8 5 5 Analogue Output Fct 1 3 1 FUNCTION Use this function to select the measured variable LEVEL DISTANCE VOLUME ULLAGE VOLUME Fct 1 3 2 RANGE I Use this function to define the current output value during error condition E Error at 22 mA e 4 20 mA hold last measured value when error occurs e 4 20 mA E 22 mA drift to 22 mA in case of error Fct 1 3 3 SCALE l min 4 mA e This function is used for Imin 4 mA to define the lower value for level distance volume or ullage volume scaling 4 mA e Setting LEVEL or DISTANCE in Fct 1 3 1 Unit for SCALE 4 mA same as in Fct 1 1 1 TANKHEIGHT Value must be smaller than SCALE 20 mA Hycontrol VF SERIES Installation and operating instructions e Setting VOLUME or ULLAGE VOLUME under Fct 1 3 1 Unit for SCALE 4 mA same as in Fct 1 2 5 VOLUME UNIT But Value must be smaller than the maximum value in the conversion table and smaller than the SCALE 20 mA Fct 1 3 4 Fct 1 3 4 SCALE 20 mA e This function is used for 20 mA to define the upper value for level distance volume or ullage volume e Setting LEVEL or DISTANCE in Fct 1 3 1 Unit for SCALE 20 mA as
6. Special 2 Special 3 Options 1 Product 1 Level 2 Products 1 Level 2 3 1 3 2 3 1 4 EPSILON R 2 3 2 0 APPLICATION 2 3 2 1 VOLTAGES VALUES APPLICATION TYPE 1 Product 1 Level Min value 0 8 1 0 Max value 99 0 2 3 2 2 WATCH PULSES 2 3 2 3 MEAS STAT HIST 2 3 2 4 PROBLEM HISTORY 2 3 3 0 CALIBRATION 2 3 3 1 CURRENT OUTPUT 2 3 3 2 ELEC CALSPEED Min value 0 7 Max value 3 0 1 5189 2 3 3 3 MECH CALSPEED Min value 0 7 Max value 9 999 2 3 3 4 OFFSET ELECTRONIC Min value 250 mV Max value 250 mV 0 mV 2 3 3 5 AUTO OFFSET MEASURE 2336 _ SET REF N 00 Hycontrol VF SERIES Installation and operating instructions Page 26 Correction for time the pulse takes to travel from the elec tronics to the flange Your VF SERIES has been ordered with one of these probe types This probe type can be changed only in the service menu Process configuration 1 or 2 liquids Note for the specification of 2 liquids the top liquid must have an e lt 5 and be always at the flange This menu is available if application type is 2 products 1 Level Enter the Epsilon R value of the product above the surface to be measured This menu is not valid for the reverse probe type This function displays the voltage values within the device Power supply 3 Volts Time base supply VCO This function displays information about ea
7. 2 Mode of operation and system structure 2 1 Measuring principle REFLEX TDR TDR Time Domain Reflectometry The converter electronics sends an electromagnetic pulse to the probe system That electromagnetic pulse travels at the speed of light down to the product surface Here the pulse gets partially reflected and travels back to the converter electronics The distance between the converter flange and product surface is therefore directly proportional to time For a distance of 1m the pulse s travel time is 6 7ns 6 7 10 seconds They are defined by two plausibility Windows one for the emitted pulse and one for the reflection radar The polarity and the amplitude of the partially pulse reflected REFLEX pulse depends on the epsilon r of the two mediums which are above and below the reflecting surface Under normal circumstances the medium above the surface is a gas with an e close to 1 0 and the medium below is the process medium with an higher The figure on the right shows a typical pulse reflection of such a standard application The advantage of the TDR measuring principle is that the travel time of the pulse and therefore the accuracy of the level measurement is completely independent of the and the density of the process medium One of the front end electronics main tasks is to sample the complete measurement signal at the upper probe end As the signal is too fast to get sample
8. 4 mm conductor cross section at neck of signal converter Cable entries M25x1 5 PG11 Standard cable gland cable clamping area 8 10 mm IP65 Signal cable shielding No shielding needed Power supply 1 Remove the screw P and lift off the connector from the signal converter 2 Put a screwdriver in F and separate N from R 3 Connect the current loop to terminal 1 and 2 there s no polarity to respect Use ferrules to protect cable ends The terminal 3 and E remain non connected Re assemble N and R 5 Put the seal in place connect R to the signal converter tighten and screw P The terminal E is not connected with the signal connector housing or with the flange system of the instrument For standard and Ex applications only the intrinsically safe 2 wire loop must be connected to the terminals 1 and 2 The terminal E as well as terminal 3 remains non connected Hycontrol VF SERIES Installation and operating instructions Page 21 10 00 N LA dek E S O e F 2 1S016 Terminals Wire cross section max 1 5 mm
9. 6000 cm e Tank height 60000 mm e Tank height 2362 2 inch e Tank height 196 85 ft e The tank height setting is also the max limit for the following function Scale max 20 mA Fct 1 3 4 e The tank height must be greater or equal to the probe length 8 5 3 Dead zone Time constant Probe length Fct 1 1 2 DEAD ZONE e Measurements near the flange may not be precise or reliable Therefore the Dead zone prevents measurements in this area The minimum value is equal to those shown in the table below Measurement may not be precise in an area less than this recommended value The factory default value is 0 40 m e Unit and setting range same as Fct 1 1 1 TANKHEIGHT Probe type Top Dead zone Top Dead zone for an lt 10 for an e gt 10 400 mm 15 75 300 11 81 Pa ARO mm 11 81 150 5 9 Mono Cable 400 mm 15 75 300 11 81 anae ee 1450 5 9 Fct 1 1 3 TIME CONSTANT e The measurement is filtered with the time constant so as to avoid abrupt changes in measured values and thus also in the current output value e Range 001 100 Sec Default value and recommended setting 5 Sec Fct 1 1 6 PROBE LENGTH e This value has to equal to the exact length of the probe The only situations for changing this value is if the probe length has been changed e Selection of unit see Sect 8 5 1 e Setting ranges for the probe length VF SERIES O to 27 00 m 0 to 2700 cm 0 to 27000 mm 0 to 1063 inch
10. 80mm 3 1 A Generally respect B gt A B 6 1 1 4 Interference between two VF SERIES There must be 2 meters mini between 2 m mini two VF series if we want no interference Hycontrol VF SERIES Installation and operating instructions Page 13 10 00 6 1 1 5 Mounting inside side mounted vessel or stilling well Here we have an optimal mounting inside vessel or stilling well Take care of fixing or centering the probe end to prevent this one from touching the vessel wall In case of the rod or cable type process T probe end for rods or large dimensions height are advised 6 1 1 6 Preferential mounting in agitated tank FILLING FIXING AT THE BOTTOM AGITATOR 6 1 1 7 Shortening of probe Screw A4 70 HC M6 10 DIN 913 Loosen the screws take out the cable shorten the length of the cable and enter the cable in the weight and tighten the screws Reduce probe length in the parameter setting of the device 7 only for liquid applications Hycontrol VF SERIES Installation and operating instructions Page 14 10 00 6 1 1 9 Sunshade In case of direct exposure to sunshine a sunshade is recommended 6 2 Ambient conditions 6 2 1 Hazardous locations Approvals 1G EEx ia IIC T6 T3 1G EEx ia IIB T6 T3 1 2 D T 100 C EEx ia 6 2 2 Ambient temperature of signal converter and process temp
11. Conversion unit any text 20 30 V DC Typically lt 70 mW Page 52 10 00 Annex B Type code nameplates Type code See nameplate on signal converter blanks and slashes may be omitted N m 5 E a a ee 5 6 7 8 910 11 1213 14 Order code of VF SERIES Probe type of instrument without single rod single cable 4 mm coax twin cable revers single cable 8 mm double tige Material of probe without 316 316L HC276 C22 FEP coated 7 PVC non Ex Process connection without 1 G 1 NPT 1 Y NPT DN50 PN40 DN80 PN16 DN100 PN16 DN150 PN16 2 150 Ibs 2 150 Ibs 3 150 Ibs 4 150 Ibs 6 150 Ibs SMS DN38 DN 11851 DN40 NOO P 0N ajo O O1 P N AO 2E DIZIMIDIOIDI gt Y AAWwIN o R Tri clamp DN40 Probe length meter 0 without 1 1 2 2 3 3 4 4 o 9 6 6 7 7 8 8 A 9 B 10 C 11 D 12 E 13 F 14 G 15 H 16 K 17 L 18 M 19 N 20 P 21 Hycontrol VF SERIES Installation and operating instructions R 22 S 23 T 24 6 Probe length 100 mm 0 without 1 100 2 200 3 300 4 400 5 500 6 600 7 700 8 800 A 900 7 Pressure without 1 16 bar 2 40 bar 8 Sealing 0 without max 4bar 1 Viton 2 Kalrez 9 Counter weight 0 without 1 Standard 2 Twin cable 3 Powder weight 4 Hastelloy weight 276 5 Turnbuckle 6 Ring i Hastelloy 22 10 Cable gland 0 without 1 DIN 2 M16 3 M16 1 2 NPT 11 Application 0 without 1 Liquids 2 Po
12. 0 to 88 594 ft e The probe length is at the same time the min limit of the range for the following function Tank height Fct 1 1 1 e The probe length is at the same time the max limit of the range for the following function Dead zone Fct 1 1 2 Note When tank is empty it is possible with software PC STAR 2 function F11 to execute an automatic calculation of the probe length from the dynamic configuration window Page 34 10 00 8 5 4 Display with the PC program PCSTAR 2 Fct 1 2 4 LENGTH UNIT Use this function to select the unit for displaying level and distance e m e cm e mm e inch Ft e optional unit If you want to select the optional unit you have to initialise the name of the new unit 4 character max fct 1 2 6 1 the conversion factor fct 1 2 6 2 The conversion factor reference is the millimeter If the conversion factor is equal to 10 then the new unit is equivalent to centimeter 10 mm If the conversion factor is equal to 0 1 the new unit is equivalent to one tenth of millimeter 0 1mm Fct 1 2 5 VOLUME UNIT Use this function to select the unit for volume display e m3 e litres e US Gal e GB Gal Gal gallons e ft3 e bbl petroleum barrels e m3 h e ft h e metric tons e US tons e Kg Fct 1 2 6 NEW LENGTH UNIT Appears only if new unit is chosen in fct 1 2 4 Length Unit Fct 1 2 6 1 NAME OF NEW LENGTH UNIT Name of new unit max 4 characters
13. 13 Quality assurance HYCONTROL LTD is certified to e DIN ISO 9001 EN 29001 Hycontrol VF SERIES Installation and operating instructions Page 51 10 00 Annex A Technical specifications 6 1 6 2 6 3 Hycontrol VF SERIES Installation and operating instructions Range of application Mode of operation system structure Input Measured variable Measuring range Rate of change in level Output Ex ia current output HART Measuring accuracy Error of measurement Repeatability Measured value resolution Effect of ambient temperature Operating conditions Installation conditions Ambient conditions Hazardous locations CENELEC Ambient temperature at signal converter Product temperature Environment class Protection category Shock resistance Vibration endurance limit EMC Product conditions Physical properties Relative permitivity Limitations Operating pressure Electrical connection User language Units of measurement Design User interface Power supply 24 V DC Power consumption Distance level volume and reflection measurement of liquids slurries solids and particulate material on storage and process tanks or containers and also in stilling wells Micropulse TDR with digital signal processing compact device modular design Primary variables distance reflection derived variables level volume Min tank height 0 15 m Max measuring range 24 m lt 10 min Type Passiv
14. ASCII characters can be written Fct 1 4 9 PROBE TYPE Probe type attached to the flange as specified in the order Fct 1 4 10 CHECKSUM ROM Checksum Identifies the software version of the device It allows also to detect problems with the micro controller A test of this checksum is performed in the factory 8 5 7 Threshold Distance input Search Probe End Dynamic Configuration The amplitude and the amplification of the level pulse give an indication whether the device is following the correct pulse For a product with amp gt 80 the amplification factor should be 0 or 1 depending on the probe type For lt 10 the amplification factor should be 2 or 3 gain 2 or 3 Normally the threshold does not need to be adapted In some applications where reflections occur due to nozzles etc a higher threshold setting can be necessary Note It is recommended to not have a full or empty tank when setting the threshold To understand the principal use of this parameter it is important to study the measuring principle Hycontrol VF SERIES Installation and operating instructions Initial Pulse Threshold Level wm Fla nge Non valid reflection The threshold filters non valid reflections example heating tube The VF SERIES measures only those pulses with an amplitude above the threshold The amplitude of the reflections is related to the dielectric constant of the product To set the threshold correct
15. Section Current output HART Passive HART protocol Ex ia current output HART Intrinsically safe Passive HART protocol All versions with HART protocol can be operated with the PC STAR 2 PC program see Section 8 11 Overview of digital communication possibilities VF SERIES PC STAR 2 PC STAR ly or HART specific software and operating devices HART Master Point to point Multidrop 4 2 HART communication The HART communications protocol can in accordance with the Rosemount Standards be used with a VF SERIES Electrical connection see Section 7 6 There are two ways of using the HART communication a As a point to point connection between the VF SERIES and the HART Master equipment 4 20 mA Hycontrol VF SERIES Installation and operating instructions Page 7 10 00 b As a multipoint connection multidrop with up to 5 devices VF SERIES or other HART equipment in parallel on a 2 wire bus Theoretically we can plug up to 15 instruments But in practice we do only 5 When configuring instruments in multidrop mode all instruments must have previously been configured with addresses different from each other address must be other than 0 because 0 is an address solely used for point to point mode 4 20 mA output valid Before switching to multidrop mode one has to make an address configuration for each instrument in point
16. converter Calibration of reference frequency is done only during manufacturing factory set 2340 EEPROM RESET SS 2 3 4 1 USER RESET This function allows a reset of the user parameters to their default values This can be used in case the service engineer wants to reprogram the default parameter settings A forgotten password can be disabled by this method 2 3 4 2 FACTORY RESET Note Before using this function contact a HYCONTROL Service Department This function resets all the factory parameters It is essential to record the Offset of measure the electronic offset Electronics Speed Calibration and Mechanical Speed Calibration values and reference frequency value before this function is activated These values can be then re entered after the reset After a reset the current output must be calibrated again 2 3 4 3 IDENTIFICATION French and German command numbers 3 0 ACCESS RIGHTS AAA 3 1 MAINTENANCE PSW Disables the access lock on the configuration menu The password must contain exactly 9 characters E R or U are used only The password is displayed in a scrambled format It allows HYCONTROL to decode the password in case it was forgotten 3 2 SPECIALIST PSW Specialist access to the Service Parameters 4 0 WATCH STATUS This function allows displays the status of the device 5 0 HART VARIABLES 5 1 MANUFACTURER HYCONTROL Read only menu VF SERIES Read only menu AAA 52 MODEL Read only menu 5 4 SOFT
17. instruments works correctly The parameter was measured during the assembly process of the instrument and cannot be determined without special equipment 8 5 14 EEPROM RESET Fct User Reset Allows to set all user parameters to their default values This can be useful to reconfigure completely a device which also disables the maintenance password in case it was forgotten Fct Factory Reset Note Before using this function contact the HYCONTROL Service Department This function resets all the factory parameters It is essential to record the Offset of Measure the Electronic Offset Electronics Speed Calibration and Mechanical Speed Calibration values and Reference Frequency value before this function is activated These values can be then re entered after the reset After a reset the current output must be calibrated again 8 5 15 ACCESS RIGHTS Fct Maintenance Password The maintenance password is a customer password It allows to protect the access of the device configuration menu Read only values can only then be accessed like the measurement values and the status without the password The password must contain exactly 9 characters and these characters must be E R or U The password is displayed in a scrambled format It allows HYCONTROL to decode the password in case it was forgotten The password must contain exactly 9 characters and the only usable characters are E R or U RE U Astcharacter_ I T U
18. measurement e All possible failures are listed in this section with a corrective action e Please read this section before contacting HYCONTROL Service Fault Symptom Current Output value lt 4 mA The calibration of the current output Execute the calibration if you have the is incorrect specialist access or contact Hycontrol Service Connection of the device is Check the connection between the device and incorrect the power supply No power supply fe Reads 22 M An error has occurred This happens in case the range 4 20 M error 22 M is selected Check the status of the device by selecting the status window F8 or enter the status 4 0 menu of the HART communicator The device is in its start up phase Wait 50 seconds If the current value drop to a value between 4 and 20 mA and goes immediately back to 22 mA consult HYCONTROL Service The value at the current output Settings of the current output are Configure output as described in Sect 8 6 8 does not correspond to the value incorrect Fct 1 3 0 at the display PC STAR 2 or HART communicator digital interface is not working the computer are set incorrectly Current output value is 22 mA VF SERIES is in its start up phase wait 50 seconds and try again If the problem persists then contact Hycontrol Service The VF SERIES indicates an The VF SERIES measures a non In the case the indicated level is close to the incorrect level value val
19. of the device when this 2 1 6 1 ADDRESS Options Address from 0 to 15 latter is connected on a HART Multidrop networks The current output drifts to 4 mA 2170 STRAPTABLE 2 1 7 1 VOLUME UNIT Options Liter Unit for conversion values volume table The selected unit is used to define the strapping table values Metric Tons US Tons INPUT TABLE Options 0 point No volume This function defines the strapping table Contains from 0 to 20 table The maximum number of points is 20 The points 4 mA current output in volume is the first value in the table Each subsequent value must be greater than the previous one The length and volume units can be changed later without affecting the settings in the table Calculations are done automatically in the instrument 2 1 7 3 DELETE TABLE o This function deletes the strapping table 2 2 1 TEST OUTPUT Options This function allows the current output to 4 mA be tested 12mA The output can be set to one of the listed 20 mA values With a reference ammeter the Other calibration of the current output can be verified 2 3 0 SERVICE 23 1 0 BASIS Na VNS NES Hycontrol VF SERIES Installation and operating instructions Page 25 10 00 PARAMETERS E 2 3 1 1 OFFSET OF Min value O 263 mm 10 4 MEASURE Max value 24000 mm 1448 2 3 1 2 i PROBE TYPE Twin Rod Cable Cable counterweight Twin Cable Twin Cable counterweight Coax Special 1
20. ratio remains the same along the probe following the same attenuation curve as the level pulse In the case the probe is short lt Q 3m the reduction of the threshold amplitude is not very significant The factory threshold setting will be suitable in all normal applications Adjustment is only necessary in situations where the e is very low and installation conditions are difficult Plot 6 Initial Pulse How to use the Threshold The smaller the e of the product is the more important the correct threshold setting will be In order to adjust the threshold level it is absolutely necessary to know the product level reflection amplitude inside the tank The ideal point where to make a threshold adjustment is when the product covers about 50 cm the probe end If the level is to high the product will mask the non valid reflection And if the product doesn t reach the probe end one won t manage to evaluate the ratio of the level pulse and the non valid pulses In this case The easiest way to adjust the threshold level is to capture a complete trace of the probe signal trace from the initial pulse down to the probe end with the oscilloscope function F7 of the PC STAR 2 software The threshold level is adjusted correctly so that all non valid reflections are below and the product surface pulse is above the threshold level If possible the threshold level should be half way between the non valid signal and level signal If the
21. specific volumes In the case of non symmetrical tanks e g tanks with dished bottom the accuracy of volume measurement will depend on the number of entered level volume pairs The maximum number of pairs points that can be set is 20 the volume is linearly determined interpolated between 2 points e The table is generally used for volume but can be used for mass or volume flow too e In the following example 4 sets of data have been programmed previously calculated or measured Unit volume Fct 1 2 5 m Input table PC STAR 2 i Volume m 0 66 ft 0 5 m3 17 6 ft m 2 46 ft 1 0 m3 35 3 ft m 3 28 ft 1 5 m3 53 ft m 18 4 ft 16 80 m 593 3 ft Volume table Tank height Fct 1 1 1 6 00 m 19 7 ft Probe length Fct 1 1 6 5 80 m 19 3 ft Dead zone Fct 1 1 2 0 40 m 1 31 ft Maximum measurable level tank height dead zone tank height probe length 6 00 m 0 40 m 6 00 m 5 80 5 40 m 17 7 ft equivalent to a volume of 16 30 m Note The real level can be measured between 0 20 m to 5 60 m When the level of the product is lower than the probe end the VF SERIES indicates tank empty The VF SERIES is programmed on the basis of a level range between 0 m and 5 60 m but it can only give a measuring value between 0 2 m 0 44 ft and 5 60 m 18 4 ft The size of the Dead Zone 0 m to 0 2 m depends of the installation and the probe type of the VF SERIES Function Fct 1 3 1 VOLUM
22. the probe length has been changed 5 seconds 1 1 6 PROBE LENGTH Min value 0 mm 0 Max value Tank height and lt 27000 mm 1063 12 0 DISPLAY NA 1 2 4 LENGTH UNIT Options m mm Millimeter Length unit of displayed value level distance 6000 mm 236 The selected unit is only valid for the length values The optional unit allows the user to define a new unit name and factor see menu 2 1 2 1 3 Optional Unit 1 2 5 VOLUME UNIT Options Liter I Unit for conversion values volume table US Gal Ft3 The selected unit is only used to display bbl the conversion value M3 h Ft3 h kg Metric Tons US Tons 1 2 6 DEFINE NEW UNIT fT 1 2 6 1 UNIT NAME 4 ASCII characters unit Optional unit name User has to enter the unit name before to use it in the menu LENGTH UNIT 1 2 6 2 UNIT FACTOR Min value gt 0 0 Optional unit factor User has to enter the Unit Factor before using it in the menu LENGTH UNIT Max value 100000 With a factor 1 0 the unit is equivalent to one millimeter With a factor 1000 0 the unit is equivalent to one meter 13 ANALOS OUR Od OOOO 1 3 1 FUNCTION I Options Level Current output function measured value to Level Distance Volume Ullage Volume 1 3 2 RANGE I Options 4 20 mA Current output range 4 to 20 mA 1 4 20 mA choice 4 20 mA When the VF SERIES is in error mode the current output is frozen except if the 22 mA if Error second choice is sele
23. the total loop resistance Ampere meter resistance Rmeter plus wiring resistance He plus HART communication resistance Rharre has to be taken in consideration for the calculation of the minimum power supply voltage Function B gives an example of a voltage drop caused by a 250 Q resistance The voltage of the power supply has to be at a loop current of 20 mA at least V supply min20 20 mA 250 Q Vinput min20 5V 10V 15V In order to cover the full current range of 4 to 22 mA the voltage drop at 4 mA has to be verified V supply mind 4 mA 250 Q V input mind 1V 18V 19V This means that with a loop resistance of 250 Q a power supply voltage of 19 V will be sufficient to cover the 4 to 20 mA range of the instrument 9 2 4to 20 mA converters V input Barrier supply Reter ER Function A in the graph above chapter 9 1 can be also used to find out whether a certain 4 to 20 mA converter is adequate for the operation with the VF SERIES Most of the converters are specified to deliver a minimum output voltage at 20 mA loop current Vout min2o This voltage must be above function A at 20 mA loop current means greater than 10 V The second condition for the converter is the output voltage at 4 mA Either it is specified too or it can be calculated with the value of the internal series converter resistance It is important to use only converters which are equipped with a SMART function Neither the PCSTAR soft
24. these level gauges rests solely with the user Improper installation and operation of our level gauges may lead to loss of warranty In addition the General conditions of sale forming the basis of the purchasing contract are applicable If you need to return the level gauge to the manufacturer or supplier please refer to the information given in Annex D Items supplied e Signal converter bolted to sensor Factory settings sheet for the signal converter Documentation supplied e Installation and operating instructions this manual detailed user manual and reference book including description of special versions and functions This documentation is structured on lines similar to those given in the DIN V 19259 Standard e Approval documents unless reproduced in the installation and operating instructions Software history Mth Yr Hardware Firmware Hardware Operating Software Device User system program 04 00 VF 1 10 Win 3 x v0 42a Online help RE P C Win 95 98 PC STAR 2 07 00 VF v0 43a Online help SERIES Hycontrol VF SERIES Installation and operating instructions Page 3 10 00 1 Range of application The VF SERIES REFLEX level gauging system is designed to measure the distance level and volume of liquids slurries solids and particulate materials It can be operated on storage process tanks and also on stilling wells Because of the low power output the microwaves are not harmful to humans
25. value dead zone This function forces the instrument not to analyse reflections in a zone directly below the flange The entered value of the detection delay must be smaller than the dead zone value 1 6 0 SERIAL I O 1 6 2 POLL ADDRESS Options Address from 0 to 15 Sets the device address of each instrument on HART Multidrop mode In this mode the current output is fixed to 4 1 7 0 STRAP TABLE 1 7 2 INPUT TABLE Options Contains from 0 to 20 The maximum number of points is 20 The points 4 mA current output in volume is the first value in the table Each subsequent value must be greater than the previous one The length and volume units can be changed later without affecting the settings in the table Calculations are done automatically in the instrument DYNAMIC CONFIGURATION TF O ooo S S THRESHOLD Ebbe LEVEL PULSE GAIN Read only value Dynamic value Amplification of level pulse gain 0 1 2 or 3 LEVEL PULSE AMP Read only value Dynamic value Amplitude of level pulse in millivolts LEVEL PULSE DISTANCE Read only value Distance of the level pulse DISPLAY AND SET 200 mV Threshold of the level pulse in millivolts THRESHOLD VALUE amplification The threshold is always displayed in terms factor 3at 1 of the same gain amplification factor as the meter product pulse DISTANCE INPUT The function forces the VF SERIES to search for the product surface in a Hycontrol VF SERIES Installation and o
26. within the electronics the VF SERIES records into a non volatile memory The function watch status can be used to access this memory Page 39 10 00 8 6 Warning and error messages during configuration Applied process too high Message appears when the PV range values are not adapted method Apply values Not in proper current mode Appears if the current output is not fixed when we execute method DAC Trim Cannot change active password Appears in the case the password is incorrect Lower range value too low Lower range value must be bigger Applied process too low Message appears when the PV range values are not adapted method Apply values Table non dull Appears if the volume table is not dull Appears in multidrop mode when wanting to fix a value on the current output In this mode it is not possible to set the current output to certain value The characters of the passed password are incorrect They must be E R or U Invalid units code Access restricted This message appears when trying to modify a parameter and the customer password is enabled Invalid range units code Appears if the unit of the range is incorrect Appears when the device is in search mode or if it is executing a function Not implemented Appears if the command sent to the device is not implemented in the device Some parameters are handled in pairs The two items are updated at the First Parameter too high same time when one of the following messages a
27. 1 LENGTH UNIT Options Length unit of displayed value level dis tance The optional unit allows the user to define a new unit name and factor see menu Optional Unit 2 1 2 1 3 2 1 2 1 2 DISPLAY FORMAT Options number of 2 decimal places Defines the displayed length values format decimal places option of the HART communicator H275 2 1 2 1 3 0 DEFINE NEW UNIT 2 1 2 1 3 1 UNIT NAME 4 ASCII characters unit Optional unit name User has to enter the unit name before using it in the menu LENGTH UNIT 1 0 2 1 2 1 3 2 UNIT FACTOR Min value gt 0 0 Optional unit factor User has to enter the Hycontrol VF SERIES Installation and operating instructions Page 23 10 00 Max value 100000 Unit Factor before using it in the menu LENGTH UNIT With a factor 1 0 the unit is equivalent to one millimeter With a factor 1000 0 the unit is equivalent to one meter yi 21 220 VOLUME IIA PERA as 2 1 2 2 1 VOLUME UNIT Options m3 Liter I Unit for conversion values volume table US Gal Ft3 The selected unit is only used to display bbl the conversion value from the strapping M3 h table Ft3 h kg Metric Tons US Tons 2 1 2 2 2 DISPLAY FORMAT Options number of 2 decimal places Defines the displayed volume value decimal places format Option of the HART communicator H275 2 1 3 0 ANALOG OUTPUT LSO 2 1 3 1 FUNCTION I Options Level Current output function measured value to Level be display
28. 4 ULLAGE VOLUME A A Ullage Volume value if a strapping table is programmed 1 2 0 Inputs Outputs Primary Variable 21 Cuentoutput value MA 123 PercemtageofPvrange S O ES CC PE 2110 BASISPARAMETER OT COTOOCOCOCOCCS 2 1 1 1 TANK HEIGHT Min value Probe Length 6000 mm 2362 Tank height Max value 60000 mm The tank height is defined as the distance between the bottom of the tank and the lower flange surface 2 1 1 2 PROBE LENGTH Min value 0 mm 6000 mm 2362 This value has to be equal to the exact Max value Tank height length of the probe The only situations for and lt 27000 mm changing this value is if the probe length has been changed 2 1 1 3 TIME CONSTANT Min value 1 second 5 seconds The time constant allows to filter possible Max value 100 seconds signal fluctuations when the product surface is turbulent 2 1 1 4 DEAD ZONE Min value 0 mm 400 mm 15 8 Measurements near the flange may not be Max value Probe length precise or reliable Therefore the Dead Zone prevents measurements in this area Measurement may not be precise in an area less than this recommended value depending on the probe type 2115 Sensor ino IN VA VEN 2 1 1 5 1 Sensor upper limit 0000000 Read only Menu Upper sensor limit 2 1 1 5 2 Sensor lower limit Read only Menu Lower sensor limit 2 1 1 5 3 Sensor min span Read only Menu Sensor minimum span 2120 DISPLAY INS VE VEN 2121 LENGTH A 2 1 2 1
29. AWG 16 Ex equipotential bonding U clamp terminal max 4 mm conductor cross section at neck of Signal converter Cable entries M16x1 5 With standard cable gland cable clamping area 8 10 mm IP65 Signal cable No shielding needed Power supply 1 Remove the 4 screws T and open the terminal compartment 2 Connect the current loop to the terminal U there s no polarity to respect Use ferrules to protect cable ends 3 Close the terminal compartment The terminal E is not connected with the signal connector housing or with the flange system of the instrument For standard and Ex applications only the intrinsically safe 2 wire loop must be connected to the terminals 1 and 2 The terminal E remains non connected e D We Hycontrol VF SERIES Installation and operating instructions Page 22 10 00 8 User interface 8 1 HART Communicator No local display is available for the installation and configuration of the VF SERIES Configuration can be carried out with a HART communicator or the PC STAR 2 program 8 2 Description of functions via HART Communicator HC 275 Version 1 00 Function Fct Default value Description 1 0 PROCESS VAR 1 1 0 MEASUREMENTS 1 1 1 LEVEL Level value 1 1 2 DISTANCE Distance value 1 1 3 VOLUME Volume value if a strapping table is programmed 1 1
30. E Range Fct 1 3 2 4 20 mA Scaling 4 mA Fct 1 3 3 0 50 rr corresponds to 4 mA Scaling 20 mA Fct 1 3 4 16 80 m corresponds to 20 mA Current output I m cubic meter Unit conversion Fct 1 2 5 Hycontrol VF SERIES Installation and operating instructions Page 33 10 00 8 5 Description of functions NOTE The menu structure is of the structure of the PC program PC STAR 2 refered to 8 5 1 Choice of units Level distance units Select Fct 1 2 4 Length Unit e m e cm mm e inch MIEL Optional unit The selected unit is then used for the following functions Dead zone Fct 1 1 2 Probe length Fct 1 1 6 Scaling 4 mA value current output Fct 1 3 3 Scaling 20 mA value current output Fct 1 3 4 The optional unit can only be used as a function of length Before selecting this unit in Fct 1 2 4 it is necessary to enter the new unit parameters The name of the unit 4 characters Fct 1 2 6 1 The factor of the unit Fct 1 2 6 2 The reference of the factor is the millimeter If the factor is 10 the optional unit is equivalent to the centimeter 10 mm If the factor is 0 1 the optional unit is equivalent to one tenth of a millimeter 0 1 mm Conversion units The conversion unit can be used to convert the level measurement into a different unit usually volume It is possible to realise a non linear function as a factor of the level Options under Fct 1 2 5 VOLUME UN
31. Elect Iss 01 Installation and operating instructions Level TDR REFLEX VF03 SERIES TDR Continuous level measurement for Liquids Powders and Granular products Hycontrol VF SERIES Installation and operating instructions Page 1 10 00 CONTENTS General advice on safety p3 Product liability and warranty p3 Items included with supply p3 Documentation supplied p3 Software history p3 1 Range of application p 2 Mode of operation and system structure p 2 1 Measuring principle p4 2 2 Signal processing p5 2 3 Modularity p5 3 Input p 3 1 Measured variable p6 3 2 Measuring range p6 3 3 Dead zone p6 3 4 Out of range performance p6 4 2 HART communication p7 4 3 Service information pS 5 Measuring accuracy p9 5 1 Reference conditions p9 5 2 Current output accuracy p9 5 3 Error of measurement p9 5 4 Repeatability p10 5 5 Measured value resolution p10 5 6 Transient recovery time p10 5 7 Turn on characteristic turn on drift p10 5 8 Long term drift pll 5 9 Effect of ambient temperature pll 6 Operating conditions p12 6 1 Installation conditions p12 6 2 Ambient conditions p15 6 3 Product conditions p16 7 Design p17 7 1 Models p17 7 2 Dimensions weights p17 Hycontrol VF SERIES Installation and operating instructions 7 3 Replacement of the signal converter p19 7 4 Selection of sensor type p19 7 5 Materials of construction p21 7 6 Electrical connection p21 8 User interface p23 8 1 HART co
32. IAL I O Gain 3 HART PROTOCOL The HART protocol is a communications protocol of the HART Communication Foundation In addition to the universal commands and common practice commands there are device specific commands to access all the rest of the parameters and functions of the VF SERIES Furthermore ask for the device description DD for the VF SERIES which can be used for universal HART control units such as the HART Communicator or SIPROM The standard hardware platform for HART is the current The threshold can not output 4 20 mA with superimposed FSK signals For decrease anymore than HART Multidrop max 15 devices on one bus the current Minimum value output is automatically set to a constant 4 mA Level 50 mV gain 3 Fct 1 6 2 ADDRESS e This function is used for entering valid addresses from 0 to 15 HART protocol e If several devices are operated on one digital bus or via HART Multidrop each device must be set to an individual address under which it can then be addressed on the bus 2 e The default value is the address 0 o This function of the device allows the threshold to remain in the same proportion as the reflection amplitudes Non valid reflection 8 5 9 STRAPPING TABLE See Volume Measurements section 8 5 10 TESTS Fct Test Output This function tests the current output It forces the output to a certain value while the accura
33. IT e m liter e US Gal Ft3 e bbl petroleum barrels e metric Tons US Tons e Kg m h e Ft3 h The selected unit is also valid for the following functions Scaling 4 mA value current output Fct 1 3 3 Scaling 20 mA value current output Fct 1 3 4 e Display range 0 00 30000 00 m O 9999999 Liter O 7925161 US Gal O 6599265 GB Gal 0 0 999999 9 Ft3 0 0 99999 9 bbl petroleum barrel Conversion measurement requires a conversion table entered with the PC STAR 2 program or HART communicator By means of this table a conversion value is allocated to each level value level conversion pairs The values are linearly interpolated between 2 points Examples of application and setting see Sect 8 4 2 8 5 2 Tank height Fct 1 1 1 TANK HEIGHT The entered value is a fundamental variable for the calculation of level measurement and its equivalent current value The tank height is defined as the distance between the bottom of the tank and lower flange surface The value must be greater or equivalent to the probe length The minimum Hycontrol VF SERIES Installation and operating instructions and maximum values are 0 and 60 m 200 ft respectively The factory default value is per your sales order NOTE The VF SERIES does not measure beyond its probe length e Selection of unit see Sect 8 5 1 e Setting ranges for the tank height VF SERIES e Tank height 60 00 m e Tank height
34. Rod Probe type attached to the flange Twin Rod Cable Hycontrol VF SERIES Installation and operating instructions Page 24 10 00 Cable counterweight Twin Cable Twin Cable counterweight Coax Special 1 Special 2 Special 3 2 145 CHECKSUM 2 1 5 0 APPLICATION 2 1 5 1 0 THRESHOLD 2 1 5 1 1 LEV PULSE AMP Read only value Dynamic value Amplitude of level pulse in millivolts Read only value Dynamic value Amplification of level pulse gain 0 1 2 or 3 2 1 5 1 3 THRESHOLD Threshold of the level pulse in millivolts amplification The threshold volutes in terms of gain factor 3 at 1 amplification factor changing by the electronic converter 2 1 5 1 2 LEV PULSE GAIN Read Only menu Similar to the release number This parameter allows to identify the software version of device IN A 2 1 5 2 DISTANCE INPUT This function allows forcing the VF SERIES to search for the product surface in a particular zone other than the actual measuring zone If there is no level signal you can enter an estimated value 2 1 5 3 DETECTION DELAY This function forces the instrument not to analyse reflections in a zone directly below the flange The entered value of the detection delay must be smaller than the dead zone value AAA AAA 2 1 5 4 SEARCH PROBE Measures automatically the probe length END 2 1 5 5 RESET VF SERIES Restarts the VF SERIES 2 1 6 0 SERIAL I O Sets the address
35. S indicates that the product level is in the dead zone Tank Empty The VF SERIES indicates that the level is bellow the probe end The VF SERIES cannot measure down to the tank bottom but only down to the end of the probe Level Lost The VF SERIES indicates when it loses the level reflection This can occur in case there is no reflection with an amplitude higher than the threshold value Measuring values are frozen If the mode 4 20 mA error 22 mA is selected then the current output is fixed to 22 mA after the selected delay time Hycontrol VF SERIES Installation and operating instructions Page 41 10 00 8 8 Error messages during start up or measurement The following list table all error messages that can trigger the current output to be set 22 mA if the mode 4 20 Error22 is selected Measuring values are then frozen EEPROM Error This message can occur during start up of the device after Hardware A tests If it occurs there is a problem with the non volatile memory Please contact HYCONTROL Service This message can occur during the start up of the device after Hardware tests If it occurs there is a problem with the internal micro controller memory Please contact HYCONTROL Service ROM Error This message can occur during the start up of the device after Hardware tests If it occurs there is a problem with the internal micro controller memory Please contact HYCONTROL Service Checksum Error Bank Customer 0 This message c
36. WARE REV 1 0 Software revision A SS Cru EE EAS 5 6 DEVICE ID Read only menu The device ID is also the ME Pr 52 bytes of ASCII characters 5 8 DESCRIPTOR __ 16 bytes of ASCII characters 5 9 DATE Month Day Year xx xx xx 5 10 NUM RESP PREAM EC frame of the device BA TAG lt Lag name ge VF SERIES 512 POLL ADDRESS gt Addressofthedevie Hycontrol VF SERIES Installation and operating instructions Page 27 10 00 8 3 Table of settable functions of PC STAR 2 Version 1 00 1 0 0 OPERATION 1 1 0 BASIS PARAMETER A 1 1 1 TANK HEIGHT Min value Probe Length 6000 mm 236 Tank height Max value 60000 mm The tank height is defined as the 2362 distance between the bottom of the tank and lower flange surface 1 1 2 DEAD ZONE Min value Omm 0 Max value Probe length Measurements near the flange may not be precise or reliable Therefore the Dead 1 1 3 TIME CONSTANT Min value 1 second Max value 100 seconds 400 mm 15 8 Zone prevents measurements in this area Measurement may not be precise in an area less than this recommended value The time constant allows to filter possible signal fluctuations when the product surface is turbulent The minimum and maximum values are 1 and 100 seconds respectively The factory default value is 5 seconds This value has to be equal to the exact length of the probe The only situation for changing this value is if
37. acceptable The level reflections of the coax probe can move up to the top of the flange without being disturbed by the flange pulse The signal plots of both probe types show how the level reflection amplitude changes with two different amplification factors gain 1 and gain 2 Remark that only the amplitude of the level reflections changes but not the amplitude of the initial neither the flange reflections Amplification is only applied in the measuring zone In certain application the signal along the probe contains non valid reflections as shown in the following plot The reflections can have various origins but have always the characteristic of a real product surface pulse This means that the non valid reflections get amplified like real level reflections Hycontrol VF SERIES Installation and operating instructions Page 44 10 00 What is the use of the Threshold Plot 5 Typical signal Non valid reflections The purpose of the threshold level of the VF SERIES is to mask such non valid reflections The threshold level as shown in plot 6 is not a constant level along probe signal but an exponentially falling function If the amplitude of the threshold level was set at 1 m to 400 mV it will be reduced to 250 mV at 10 m probe length The exponentially falling function was chosen because the amplitude of the level pulse as well as the amplitude of the non valid reflections decrease with the same kind of function and the amplitude threshold
38. an occur during the start up of the device after Hardware tests If it occurs there is a problem with the EEPROM or with the function which recalls the parameters saved in the EEPROM Parameters are saved in a non volatile memory EEPROM There are 4 banks 2 for each type of parameters customer or factory If there is a problem with the first bank 0 then the VF SERIES gets the parameters values from the second bank 1 If the VF SERIES indicates only a problem with the first bank it means that it succeeded in getting all the parameters thanks to the second bank In this case the device can measure Checksum Error Bank Factory 0 This message can occur during start up of the device after Hardware tests If it occurs there is a problem with the EEPROM or with the recalling of the parameters saved in EEPROM Parameters are saved in a non volatile memory EEPROM There are 4 banks 2 for each type of parameters customer or factory If there is a problem with the first bank 0 then the VF SERIES tries to get the parameters values from the second bank 1 If the VF SERIES indicates only a problem with the first bank it means that it succeeded in getting all the parameters thanks to the second bank In this case the device can measure Checksum Error Bank Customer 1 This message can occur at the start up of the device after Hardware A tests Refer to Bank 0 and re start the device several times If the problem remains then contac
39. ange mm r Dielectric constant of first medium under the flange normally 1 00 DeltaT Calspeeds Ve Offset Distance Level Tank Height Distance The measured time between the initial pulse and the level pulse is translated into length by the Calspeeds product This primary distance is corrected by the offset and is thus standardised to the reference point flange This primary distance is divided by the square root of x if there is only one product in the tank the Er is 1 00 air The level is calculated as the difference between tank height and distance All items of information excepted Delta T can be accessed via the digital communication Hycontrol VF SERIES Installation and operating instructions Page 47 10 00 9 Power supply 9 1 Technical data AA nominal power supply voltage Vinout 24 VDC 35 VDC see graph below Input voltages above 35 VDC may damage the instrument Furthermore input voltages above 35VDC or below the specified voltage may cause a faulty measurement or may trigger the instrument to reset cyclicly loop resistance Rig Ryarto Reable Rmeter D minimum Rios 0 750 Q HART communication resistor Riarte 250 Q recommended A Doi DH Hycontrol VF SERIES Installation and operating instructions Page 48 10 00 The function A in the diagram above specifies the minimum voltage at the terminals of the VF SERIES The voltage drop over
40. ary to record this before an EEPROM Factory Hycontrol VF SERIES Installation and operating instructions Page 30 10 00 eee Sa reset so that it can be re entered 2 5 MECH CALSPEED Min value 0 7 Mechanical speed constant This is the Max value 9 999 correction factor relating to the actual probe type and the pulse propagation speed This is factory calibrated and needs to be recalibrated only if the probe is changed or extended 2 6 SET REF FREQUENCY Min value 0 Reference frequency setting for the digital Max value 255 to analogue converter Factory set Change only with the agreement of a Hycontrol Service Engineer 30 EEPROM RESET O O O O 3 3 SERIAL NUMBER Read only menu Unique serial number of the device and device ID Each device has therefore it s individual address HART protocol 3 4 FRENCH COMMISSION Read only menu NUMBER This number is factory set Refer to this number in case of warranty or service claims 3 5 GERMAN COMMISSION Read only menu NUMBER This number is factory set Refer to this number in case of warranty or service claims 3 6 HARDWARE RELEASE Release number of the instrument NUMBER DYNAMIC CONFIGURATION AAA VOLTAGES VALUES This function displays the voltage values within the device Power supply 3 Volts Time base supply VCO WATCH PULSES This function displays information about each pulse Reference pulse flange pulse and level pulse For each pulse there a
41. ble max 20 points The strength of the reflected signal can be measured for qualitative assessment of the tank product or its surface Only available with HART communication 3 2 Measuring range 0 15 24 m 0 50 72 ft Minimum tank height 0 15 m 0 5 ft The useful range will depend on the sensor type the reflection properties of the tank product the installation position and the presence of interfering reflections 3 3 Dead zone The dead zone distance is the minimum measured distance between the mounting flange reference point and surface of the tank product For twin cable gt 10 150 mm 5 9 For twin cable e lt 10 300 mm 11 8 For mono cable e lt 10 400 mm 15 8 PP These are min values Default For mono cable gt 10 300 mm 11 8 value 400mm 15 8 For coax system 0 for all e Recommended minimum values see following sketches Nozzle height To set the right dead zone and detection delay add the height of the nozzle to the E A A values mentioned in the table 3 4 Out of range performance When the level measuring range is exceeded including flooding the output value will stay at the adjustable dead zone see Sect 8 5 3 lf the measured value drops below the level range the output will stay at the set lower range limit distance tank height Hycontrol VF SERIES Installation and operating instructions Page 6 10 00 4 1 Variants Variants Remarks Described in
42. cal Calspeed These two constants are calibration factors which convert the measured time between the reference pulse and the level pulse into a distance length There are 2 calibration factors One because the pulse crosses the electronic board before entering the probe and the other one because there are several probe types and each probe type geometry has an influence on the propagation of the wave Each electronic block has its own electronic factor Each probe type has his own mechanical factor Hence each device is calibrated with its specific probe Fct 2 1 Electronic Offset This parameter allows to move the signal vertically Says to add or to substract an offset to the signal zero reference lt allows to hide non valid signal noise because only positive signals are measured In the example below the amplitude of the non valid pulse is about 30 mV Increasing the offset by 30 mV maskes the noise completely The non valid signal disappeared but the amplitude of the level pulse decreased too 10 00 Page 38 Normally for standard application this parameter should not be modified This parameter should be only modified under supervision of HYCONTROL Service Fct Auto Offset Measure See Section Fct 1 1 2 Fct 2 6 Set Ref Frequency The function allows to re enter the frequency reference parameter after a factory reset The value must be recorded before the reset and re entered to make sure that the
43. ch pulse Reference pulse flange pulse and level pulse For each pulse there are set values For example window number pulse amplitude position of the pulse inside the window etc This function indicates the 24 last process status Markers Level Normal Full Tank Empty Tank Level Lost This function indicates the last 24 device errors This function allows to calibrate the current output Factory set Electronics speed constant Not necessary to change in any circumstance This is factory set and is specific to each electronics lt is always necessary to record this before an EEPROM Factory reset so that it can be re entered Mechanical speed constant This is the correction factor relating to the actual probe type and the pulse propagation speed This is factory calibrated and needs to be recalibrated only if the probe is changed or extended Electronic offset Signal offset This parameter Sets the offset value of the audio signal This parameter alllows to adjust the level of signal amplitude to mask non valid pulses VF SERIES uses this value to control electrically the level of signal amplitude The higher this value is the higher the non valid signal amplitude is This function calculates automatically the offset Parameter 2 3 1 1 After having used this function a manual calibration is possible This parameter sets a value for the digital 10 00 FREQUENCY Max value 255 analogue
44. cted and then the current output is fixed at 22 mA TT Ne eine Jane o a Or e orant Max value Scale max output 4 mA 20 mA Max value tank Height output 20 mA be displayed 1 3 5 ERROR DELAY Options No delay This function is available in case the range No delay menu is set to 4 20 mA with error 22 M 10 seconds This parameter sets the delay before the 20 seconds current output goes to 22 MA after the Hycontrol VF SERIES Installation and operating instructions Page 28 10 00 30 seconds error mode occurred 1 minute 2 minutes 5 minutes 15 minutes 1 4 0 USERDATA 1 4 0 USER DATA 1 4 4 TAG 1 4 5 SERIAL NUMBER 1 4 6 FRENCH COMMISSION NUMBER Read only menu Unique serial number of the device ID Each device has therefore its individual address HART protocol Read only menu This number is factory set Refer to this number in case of warranty or service 1 4 7 GERMAN COMMISSION Read only menu This number is factory set Refer to this number in case of warranty or service 1 4 8 OPTION Up to 15 bytes of ASCII characters permitted 1 4 9 PROBE TYPE Options Read only menu Rod Release number of the device Software Twin Rod and Hardware version Probe type Cable attached to the flange Cable counterweight Twin Cable Twin Cable counterweight Coax Special 1 Special 2 Special 3 ss AN AAA Sa NUMBER 15 0 APPLICATION IIA 1 5 1 DETECTION DELAY Min value O mm Max
45. cy can be checked with a reference ammeter Refer to the annexe for further information on how to adjust the threshold Fct Distance Input It is not recommended to use this function in normal circumstances Only in case of problems it is to be used This function forces the VE SERIES to search for the product in a certain area along the probe For instance if e An ammeter must be connected to the loop for this test The VF SERIES probe is mounted on a tank while this latter is switched on it may display permanently a full tank To e Select a current value for PC STAR 2 resolve such a problem two way exist A mA 1 switch off the VF SERIES and then switch it on 8 mA 2 Enter in a distance value where the product is 12 mA supposed to be 16 mA 20 mA 22 mA Fot Detection Delay e The connected ammeter shows the measured current Allows to define a zone below the flange in order to mask valve noise This value has to be smaller or equal to the value of the dead zone set in 1 1 2 The detection delay is especially useful for eliminating reflections due to the nozzle Fct Search Probe End The probe length can be measured automatically This is necessary when the probe length was modified cut If the VF SERIES does not succeed in finding automatically the probe length there are three possibilities 1 The threshold is not set correctly Follow instructions to set it to a lower value 2 The electronic offset is incorrect Se
46. d with a sufficient resolution in time the electronics sends continuous electromagnetic pulses down the probe and samples each signal a fraction of time later than the previous signal sampling The so generated audio signal is a direct copy of the real time measuring signal with a 228 000 times slower time base This means that 1m of distance between converter flange and process surface is not anymore equivalent to a time of 6 7ns but to a time of 1 5ms This time transformed audio signal is now sufficiently slow and can be directly processed In order to save electrical power the converter samples the measuring signal only in the relevant areas Hycontrol VF SERIES Installation and operating instructions measuring windows pulse reflection transformed signal j Page 4 10 00 2 2 Signal processing digital The figure below shows the digital signal processing of the VF SERIES It can be split up into two main blocks The function of the first block with its pulse generator sample circuit and digital PLL Phase Locked Loop time base that was already referred to in the previous chapter It is linked via the audio signal to the second block that completes the signal processing of the electronics An analogue to digital converter samples the audio signal before the microprocessor processes the data with different filter and measurement algorithms In a final step the processor calculates the product level and sends
47. detection delay and dead zone Fct 1 1 2 Fet 1 5 1 Non measurable zone 150 mm B Dead zone at the end of the probe Refer to a representation of the physical dimensions of the probe ends cable twin cable coax etc see BM 100A Manual Level configuration example Fct 1 3 1 Level 0 1 2 3 4 current output range is smaller than the measuring range current output range is equal to the measuring range min scale 4 mA fct 1 3 4 tank height probe length B max scale 20 mA fct 1 3 5 tank height dead zone current output range is larger than the measuring range min scale 4 mA fct 1 3 4 0 0 max scale 20 mA fct 1 3 5 tank height dead zone current output range is larger than the measuring range min scale 4 mA fct 1 3 4 tank height probe length B max scale 20 mA fct 1 3 5 tank height current output range is larger than the measuring range min scale 4 mA fct 1 3 4 0 0 max scale 20 mA fct 1 3 5 tank height Please note For distance measurement the reference point is the bottom surface of the flange Hycontrol VF SERIES Installation and operating instructions Page 32 10 00 8 4 2 Volume measurement example In order to be able to measure volume with the VF SERIES a conversion table strapping table needs to be entered via the PC STAR 2 program or HART communicator see Sect 8 3 By means of the strapping table level values are allocated to
48. e current sink Current range 4 20 mA error 22 mA 4 mA constant for HART Multidrop lt 0 02 K 0 05 rel 20 mA 25 C 20 30 V terminals 1 and 2 see 9 Power supply 0 750 Q see certificates Temperature drift Accuracy linearity Supply voltage 2 Load impedance Max electrical values Same characteristic Reference conditions and error curves see Sect 5 1 and 5 2 lt 0 5 x error of measurement VF SERIES 1 mm No significant effect on measured value 1 ppm K see also signal output accuracy Avoid interference reflections and multiple reflections Approvals for 1G EEx ia IIC T6 T3 1G EEx ia IIB T6 T3 1 2 D T 100 C EEx ia 20 C to 55 C 50 C to 90 C Higher on request Locations exposed direct to open air climate D1 Severity in conformity with EN 60654 1 signal converter IP65 Impact test according to EN 61010 Sect 8 2 with 0 5 J energy drop test to prEN 50178 IEC 68 2 6 and prEN 50178 10 57Hz 0 075mm 57 150 Hz 1g EN 50081 1 EN 50082 2 No effect on measurement results to ensure reliable measurements the relative permitivity e should have the following minimum values E gt 1 5 for coax probes E gt 1 8 for twin cable probes gt 2 3 for mono cable probes Sticky products Standard max 4 bar higher on request DIN Connector PG 13 5 German English French Length m cm mm inch ft Volume mf Liter US Gal GB Gal ft3 bbl
49. e of the product is low it is possible that the pulse of the probe end is visible too on the screen This pulse does not have to be masked by the threshold level as it will be seen moving further away in time as the product level increases Adjust now the threshold level according the different pulse amplitudes lt is advised to keep a margin between the threshold level and the pulse amplitudes in order to cope with possible fluctuations in terms of amplitude The amplitude of the product reflection increases with increasing level and vice versa In case the threshold level was adjusted to a value higher than the product pulse the VF SERIES will not find the pulse even after changing the amplification factor In case the threshold level was adjusted too low below non valid pulse amplitude level the VF SERIES will find a non valid pulse next time the product level drops below the probe end The minimum threshold is 50 mV at gain factor 3 Hycontrol VF SERIES Installation and operating instructions Page 45 10 00 45000 Hycontrol VF SERIES Installation and operating instructions 8 12 Calculation of the measured value VF SERIES measures the time between reflections and converts it into a distance or a level value with the following formulas Delta T Time between Initial Pulse and Level Pulse 2 uS Calspeeds Electronic Calspeed Mechanic Calspeed uS mm ffset Distance between Initial pulse and bottom surface of the fl
50. e end It helps in analysing incorrect measurements by visualising the threshold and pulse together In case of a measurement problem do not hesitate to use this function It visualises all pulses along the probe including the initial pulse flange and level pulses if not empty and non product reflections The signal function of PC STAR 2 helps to adapt measurement related settings like the detection delay or the threshold level Moreover it helps to understand how the VF SERIES works A screen plot of this function will help in understanding the instrument s application The signal can be printed or saved as an Excel file and sent by Email How to use the Signal Function The plots below show typical measurement signals recorded with the PC STAR 2 oscilloscope function Plot 1 is a signal captured with a rod or a cable probe and an amplification factor of 1 gain 1 Plot 2 shows the same probe with an amplification factor 2 gain 2 Plot 3 and 4 are traces recorded with a coaxial probe and the same amplification factors as plot 1 and 2 Plot 1 Plot 2 EN Gain 1 Rod or Cable Probes Flange signal Level signal Plot 3 Plot 4 Gain 1 Coax Probe Level signal The difference between the coax probe and the other probe types is the missing flange pulse The missing pulse explaines why it is advantageous to use a coax probe for applications where a certain dead zone at the top of the probe is not
51. ed Distance Volume Ullage Volume 2 1 3 2 RANGE I Options 4 20 mA Current output range 4 to 20 mA 1 4 20 mA choice 4 20 mA When the VF SERIES is in error mode the 22 mA if Error current output is frozen except if the second choice is selected and then the current output is fixed at 22 mA 2 1 3 3 ERROR DELAY Options No delay This menu is available in case the range delay menu is set to 4 20 mA with error 22 M seconds This parameter sets the delay before the seconds current output goes to 22 mA after the seconds error mode occurred minute minutes minutes minutes 2 1 3 4 SCALE Min value 0 Input the lower range value corresponding min 4 mA Masate Soo mer to 4 mA depending of the parameter 2 1 3 1 choosen 2 1 3 5 SCALE I Min value Scale min 6000 mm 236 Input the upper range value max 20 mA Wiel corresponding to 24 mA depending of the parameter 2 1 3 1 choosen AAA 2147 TAG VE SERIES OO Tag number ofdevicg a cr Each device has its proper serial number 2 143 FRENCH Read only menu COMMISSION NUMBER This number is factory set Refer to this number in case of warranty or service claims 2 144 GERMAN Read only menu COMMISSION NUMBER This number is factory set Refer to this number in case of warranty or service claims 2 145 RELEASE NUMBER Read only menu Release number of the device Software and Hardware version 2 145 PROBE TYPE Options Read only menu
52. electric constant of the upper medium between the flange and the lower product level is not 1 0 In this second case the function 1 1 4 can be used to specify the e of the upper product 8 5 12 APPLICATION Fct Voltages values The voltage values are Power supply 3 volts Time Base supply Voltage Control Oscillator These values are used only by the Hycontrol Service Department Fct Watch Pulses This function can be only used by the Hycontrol Service Department This function gives additional information on the captured signal It is useful in analysing if the VF SERIES is tracking the right level reflection Fct Histories These two functions record the status history of the device The two functions store the last 24 status or error messages in a special non volatile memory Hycontrol VF SERIES Installation and operating instructions 8 5 13 CALIBRATION Fct Current Output This function is used to calibrate the current output First a reference ammeter has to be connected to the VF SERIES in order to measure the actual loop current The function fixes the current to 4 0 mA Enter the actual current value measured with the ammeter e g 4 01 mA The VF SERIES then calibrates automatically the current output Repeat this operation in case the accuracy of the displayed current output value is not satisfactory As a final step repeat the same procedure for the 20 mA value Fct 2 4 and 2 5 Electronical Mechani
53. en channel measurement replacement threat con nection installation Hycontrol VF SERIES Installation and operating instructions 1 Cement limestone flyash alumna etc 2 Acids 3 Liquid sugar honey sirops 4 For very high temperature 1 Tank farm 2 LPG LNG NH3 spheres beer alcohol with single cable construc tion Page 20 10 00 7 5 Materials of construction Check that the materials of the sensor extension flange gaskets Viton Kalrez and PTFE contained in all versions are compatible with the product 7 5 1 Signal converter Housing Aluminium with epoxy or powder coating 7 5 2 Flange system 1 G Standard all other flanges on request 7 5 3 Materials in contact with the product Stainless steel 316 for the cable Hastelloy optional Stainless steel 316 L standard for all the process connections others on request PTFE Viton O Ring Kalrez optional 7 6 Electrical connection The electrical connection for the power supply is made in the terminal compartment of the signal converter Observe requirements specified in VDE 165 D D gg D J In case of installation in hazardous areas only certified intrinsically safe equipment may be connected to the VF SERIES Two kinds of electrical connection are available 1 DIN Connector Terminals 3 poles ground Wire cross section max 1 5 mm AWG 16 Ex equipotential bonding U clamp terminal max
54. erature For the VF SERIES the max and min temperature of the converter and the flange are linked Minimum converter temperature 30 C 22 F lt gt Minimum product temperature 50 C 58 F Maximum converter temperature 55 C 131 F lt gt Maximum flange temperature 90 C 195 F 6 2 3 Storage temperature 40 C lt T lt 80 C 22 F lt T lt 195 F 6 2 4 Environmental class Installation in free air level DI according EN60654 1 6 2 5 Protection category IP65 6 2 6 Shock resistance Resist to shocks according EN61010 8 2 0 5J 6 2 7 Vibration endurance limit IEC 68 2 6 and pr EN50178 10 57 Hz 0 075 mm 57 150 Hz 1G 6 2 8 EMC Electromagnetic Compatibility The devices satisfy the requirements of EN 50081 1 EN 50082 2 Hycontrol VF SERIES Installation and operating instructions Page 15 10 00 6 3 Product conditions 6 3 1 Physical properties of the products Physical properties such as density viscosity conductivity relative permitivity magnetic properties etc have no effect on measurement results The relative permitivity is merely required to have a minimum value in order to ensure reliable measurements see Section 6 3 2 6 3 2 Relative permitivity The relative permitivity of the product Epsilon R determines the strength of the reflected signal Measurement results are not affected so long as the reflected signal is strong enough Reliability and the maximum measu
55. id reflection nozzle increase the detection delay and the dead zone with the same ratio or increase the threshold level if the full measurement range is essential In any case use the PC STAR 2 oscilloscope function to visualise and to analyse the application The threshold level must be adjusted so that it masks the disturbances It permits also to give enough margin for the level pulse Very large pulses along the measurement signal same amplitude as the initial pulse can be caused by a probe which is touching the nozzle or the tank side see mounting guideline section The tank is empty and the VF In case the VF SERIES indicates a Analyse the signal with PC STAR 2 Simply SERIES indicates a level level a valid pulse was found adjust the threshold dynamic configuration Check the probe for disturbances window See section 8 5 7 such as heating tubes or product build up clogging The tank is full and the VF The threshold is not adapted See section 8 5 7 to adjust it SERIES indicates a level or oe empty tank The tank is not empty nor full See section 8 5 7 to adjust it and the VF SERIES indicates an empty or full tank Hycontrol VF SERIES Installation and operating instructions Page 43 10 00 8 11 Oscilloscope Function of PC STAR 2 and Threshold What s the purpose of the signal oscilloscope of PC STAR 2 This function analyses the position and amplitude of each pulse between the initial pulse and the prob
56. in Fct 1 1 1 TANKHEIGHT The value set has not to be greater than the tank height Fct 1 1 1 e Setting VOLUME OR ULLAGE VOLUME in Fct 1 3 1 Unit for SCALE 20 mA same as in Fct 1 2 5 VOLUME UNIT The value set must be greater than the SCALE 4 mA Fct 1 3 3 otherwise error during Parameter Check Application and programming examples see Sect 8 5 Fct 1 3 5 ERROR DELAY This function is available on the HART communicator when 4 20 mA E 22 mA is chosen The delay defines the amount of time in the event of an error before the VF SERIES goes to 22 mA After the problem occurs and before the end of the delay the measurement value and also the current value is frozen Page 35 10 00 8 5 6 User Data Fct 1 4 4 TAG Tag name of the device can be displayed 8 ASCII characters Note Not all the characters can be used Tag name descriptor and message are recorded in a special format Packed ASCII Only the characters in the following table can be used CIA A O E E A CO a A A ASA d Fct 1 4 5 SERIAL NUMBER Identifies each VF SERIES Can not be changed This number defines the Device ID of the HART Long Address Fct 1 4 6 FRENCH COMMISSION NUMBER This number is factory set Refer to this number in case of warranty or service claims Fct 1 4 7 GERMAN COMMISSION NUMBER This number is factory set Refer to this number in case of warranty or service claims Fct 1 4 8 Optional Up to 15 optional
57. l liquid contained in this level gauge BEI SIG EE Companies stamp Hycontrol VF SERIES Installation and operating instructions Page 55 10 00 Annex D Tables on documentation of device configuration Device No COMM No Location Contact person Menu item Configuration parameters customer A E EEN D ad ZO ages eee eet lis TIMe CON SAM SN PR eii Prob eng nee nest E E A O A A CIE RAME ssa eet E E ene ea cs ls ln BL Cel Ce Semen ent we mn E E TERE REED Volume UNT Se E E E EHF CHE C ireht output range error eege eelere li Min scale for Current E E idoneidad l Max Scale Tor CUE ii a eege e lg 2 OA rt E E i Ta el TEE dos Dio AAA Te eo ea e a mn AA AAOS SS y tin A EE eee esser Configuration parameters factory POD VDO E E E SN E EE EE E E Application VDS sd E tan den nina Dante ie no EDSON Bee e D Set value of electronic offset D 1 l Electronic Calspeed 53 588 680 ee Mechanic Calspeed EE aa aa RS a a fe ins E Relerence The due e EE E oe ener neo ee eee cease Hycontrol VF SERIES Installation and operating instructions Page 56 10 00 Fct Strap table configuration 20 points Point 0 OVAL eo ce Volume Point 1 eelere EE ege Volume Point 2 Level A Volume Point 3 ee ene ae eee ee ae eee on Volume Point 4 Level den Volume Point 5 LV iii cion Volume Point 6 RE Volume P
58. ly 0 003 K The temperature has no effect on the measured value as the device carries out a regular self calibra tion The temperature effect of the atmosphere above the liquid product results theoretically in 1ppm K for air In respect of reference measurements in liquid tanks it needs to be borne in mind that liquids generally have a high coefficient of thermal expansion organic liquids typically 0 15 K Hycontrol VF SERIES Installation and operating instructions Page 11 10 00 6 Operating conditions 6 1 Installation conditions Refer to Section 7 4 for selection of the optimal sensor type 6 1 1 First mounting of device Before installing the device please refer to the following guidelines E E TL C J ag e y 100 mm 3 9 MIN 0 mm 0 MIN 300 mm 11 8 MIN Twin rod cable Coax cable Mono rod cable 6 1 1 1 Excessive bending of the cable BE CAREFULL DON T BEND CABLES TOO MUCH Hycontrol VF SERIES Installation and operating instructions Page 12 10 00 6 1 1 2 No penetrating nozzle Penetrating nozzle is forbiden Ideally the VF series is mounted without a nozzle and directly mounted in a 1 G welding socket this gives the best measuring results at the lowest installation cost 6 1 1 3 Mounting on a nozzle Avoid nozzle size higher than 150 mm 5 9 especially when B lt
59. ly it is necessary to know approximately the amplitude of all reflections along the probe level reflection and also non valid reflections An oscilloscope function which gives a view of all the reflections along the probe Default value for threshold is 200 mV in amplification factor 3 gain 3 The minimum threshold is 50 mV Gain 3 The maximum threshold is 2500 mV Gain 0 Amplification OO The gain stage is assigned according to the strength of the reflection With amplification factor 0 gain 0 the reflection is not amplified With gain 3 the reflection is amplified nearly by 9 The VF SERIES automatically changes the gain In order to ensure that the processed reflection is maintained within a range of values that the electronics can most efficiently track The threshold is recorded with the same amplification factor as the reflection If the reflection level gets smaller the VF SERIES will increase the gain and the reflection will be amplified The threshold level will be equally amplified Threshold Same reflection The example shows that when the reflection level gain changes the threshold in both cases rises approximately to a level of 50 signal amplitude As the distance between the flange and the product surface rises the amplitude of the reflected pulse gets smaller The threshold adapts automatically in the same manner Page 36 10 00 The level in the tank is between 2 and 4 meters 8 5 8 SER
60. mmunicator 23 8 2 Table of settable functions of HARTS Communicator HC250 23 8 3 Table of settable functions of HART Communicator PC STAR 2 p28 Configuration examples p32 Description of functions p34 Warning and error messages during Configuration p40 Warning messages during measurement __ p41 Error messages during start up or measurement p42 Start up p43 0 Faults and symptoms during start up and measurement p43 8 11 Signal function of PC STAR 2 and Threshold p44 8 12 Calculation of the measured value p47 00 0 90 90 00 OO Ch UN E OO OO MO 9 Power supply p48 9 1 Technical data p48 9 2 4to 20 mA converters p49 9 3 Sunshade p49 9 4 Ex Applications p49 10 Certificates and approvals p51 10 1 CE manufacturer s declaration p51 11 Order information p51 12 External standards codes and directivesp52 13 Quality assurance p51 Annex p52 Annex A Technical specifications p52 Annex B Type code nameplates p53 Annex C Declaration p55 Annex D Tables on documentation of device configuration p56 Page 2 10 00 General advice on safety When handling the VF SERIES avoid hard shocks jolts impacts etc Product liability and warranty The VF SERIES level gauge is designed solely for measuring the distance level and volume of liquids solids and particulate materials Special codes and regulations apply to its use in hazardous areas Responsibility as to suitability and intended use of
61. o return a device for inspection or repair please pay strict attention to the following points Due to statutory regulations concerning protection of the environment and the health and safety of our personnel Hycontrol may only handle test and repair returned level gauges that have been in contact with products which do not pose a risk to personnel and environment This means that Hycontrol can only service your unit if it is accompanied by a certificate in line with the following model confirming that the device is safe to handle If the unit has been operated on toxic caustic flammable or water endangering products you are kindly requested to check and ensure if necessary by rinsing or neutralising that all cavities are free from such dangerous substances to enclose a certificate with the level gauge confirming that it is safe to handle and stating the product used HYCONTROL regret that they cannot service your level gauge unless such a certificate accompanies it SPECIMEN certificate COMPA Rs eeler Beier EE Kl RN e GE The enclosed level gauge YF SERIES rs rige o HYCONTROL Order No or Series No Because this liquid is water endangering toxic caustic flammable We have Checked that all cavities in the unit are free from such substances Flushed out and neutralised all cavities in the unit delete where not applicable We confirm that there is no risk to man or environment through any residua
62. oint 7 RE Volume Point 8 KEE Volume Point 9 CI CY H RER EE Volume Point 10 Level ee Volume Point 11 OVS E Volume Point 12 A A Volume Point 13 LOVE Sa anna Volume Point 14 Level EE Volume Point 15 RE Volume Point 16 Level cei eee Volume Point 17 OV nes Volume Point 18 ESO aie eters Volume Point 19 LOV L ee ee Volume Hycontrol VF SERIES Installation and operating instructions Page 57 10 00
63. ounterweight Twin Cable Twin Cable counterweight Coax Special 1 Special 2 Special 3 1 1 2 OFFSET OF MEASURE Min value O 263 mm 10 35 Correction for time the pulse takes to Max value 24000 mm travel from the electronics to the flange 944 9 1 1 3 APPLICATION TYPE Options 1 Product 1 Level Process configuration 1 or 2 liquids 1 Product 1 Level Note for the specification of 2 liquids the 2 Products 1 Level top liquid must have an e lt 5 and be always at the flange 1 1 4 EPSILON R Min value 0 8 1 0 This menu is available if application type Max value 99 0 is 2 products 1 Level Enter the Epsilon R value of the products above the surface to be measured This menu is not valid for the reverse probe type probe type 5 20 CALIBRATION RES WE 2 1 ELECTRONIC OFFSET Min value 250mV Sets the offset value of the audio signal Max value 250mV Allows to hide non valid pulses This parameter sets the value of the electronic offset The VF SERIES uses this value to control electronically the level pulse amplitude As higher the level pulse amplitude is as higher the non valid pulses amplitude will be too This parameter allows adjusting the level pulse amplitude in order to hide non valid pulses 2 4 ELEC CALSPEED Min value 0 7 Electronics speed constant Not necessary Max value 3 0 to change in any circumstance This is factory set and is specific to each electronics It is always necess
64. perating instructions Page 29 10 00 particular zone Therefore if there is no level signal you can enter an estimated value If you are sure of what your indication should be and there is still no reading contact HYCONTROL about decreasing the Level Threshold value CAUTION Use of this function is not recommended except for trained HYCONTROL service representatives SEARCH PROBE END Leck Allows to calculate automatically the probe length ADD POINT TO VOLUME Options 0 point No volume This function defines the strapping table TABLE Contains from 0 to 20 The maximum number of points is 20 The points 4 mA current output in volume is the first value in the table Each subsequent value must be greater than the previous one The length and volume units can be changed later without affecting the settings in the table Calculations are done automatically in the instrument DELETE POINT OF THE This function deletes the strapping table VOLUME TABLE TEST CURRENT OUTPUT Options This function allows the current output to 4 mA be tested 8 mA The output can be set to one of the listed 12 mA values With a reference ammeter the 16 mA calibration of the current output can be 20 mA verified 22 mA RESET VF SERIES Key CTRL ALT R RestartstheVF SERIES SERVICE 1 1 BASIS PARAMETERS ISSO 1 1 1 PROBE TYPE Options Probe type specification as mounted to the Rod flange per the purchase order Twin Rod Cable Cable c
65. ppears and one of the first member of the pair too high items is incorrect These pairs are e Tank height Probe length First Parameter too low Dead zone Detection delay first member of the pair too low Threshold value Threshold distance Optional unit name Optional unit factor Second Parameter too high Offset of measure Period of measure Second member of the pair too high Electronics Calspeed mechanical calspeed Epsilon R Set value of Electronic offset Second Parameter too low psilon R Set value of Electronic offse second member of the pair too low Hycontrol VF SERIES Installation and operating instructions Page 40 10 00 8 7 Warning messages during measurement Configuration Changed Configuration parameter was changed More Status Available Command 48 must be executed to detail the status better menu Watch Status Primary Variable Analog Output Fixed Is displayed when e Device is set in Multidrop Mode Polling Address 0 e Fixed Current Mode is entered during Loop Test and DAC Trim Analog Output Saturated During normal operation the maximum value for the analogue output is 20 mA The analogue output saturation error flag is set in case the measurement exceeds the signal current output range First Start This message appears only when the serial number is 0 or 16777215 IS Normally this message can occur only in production before the calibration of the device Tank Full The VF SERIE
66. re set values For example window number pulse amplitude position of the pulse inside the window etc AUTO OFFSET MEASURE This function calculates automatically the offset parameter 2 3 1 1 After having used this function a manual calibration is possible USER RESET This function allows a reset of the user parameters to their default values This can be used in case the service engineer wants to reprogram the default parameter settings A forgotten password can be disabled by this method FACTORY RESET Note Before using this function contact a HYCONTROL Service Department This function resets all the factory parameters It is essential to record the Offset of measure the electronic offset Electronics Speed Calibration and Mechanical Speed Calibration values and reference frequency value before this function is activated These values can be then re entered after the reset After a reset the current output must be calibrated again Hycontrol VF SERIES Installation and operating instructions Page 31 10 00 8 4 Configuration examples NOTE The menu items e g Fct 1 1 3 of the examples refer to the menu structure of the PC program PC STAR 2 8 4 1 Level measurement example tank height Fct parameter number probe length E Fct A 15 A Measuring range zone Www evel reference point tank height Current output measuring range A Minimum recommended distance between
67. ring range are dependent upon the relative permitivity The minimum permitivity depends on the type of probe being used recommendation Mono gt 2 3 Twin 21 8 Coax gt 1 5 6 3 3 Product limitations TDR based level measuring devices are not suitable for products with severe deposit characteristics This with the limitation mentioned in 6 3 2 are the only limitations of the device 6 3 4 Maximum allowable operating pressure max 40 bar The maximum allowable operating pressure for the standard version is 16 bar 58 psig Option 40 bar 580 psig 6 3 5 Maintenance Maintenance is not necessary in standard applications however when the sensor is heavily contaminated this can lead to measurement errors Hycontrol VF SERIES Installation and operating instructions Page 16 10 00 7 1 Models VF SERIES coax VF SERIES rod VF SERIES cable 7 2 Dimensions weights SENSOR TYPE Weight converter Extra Weight 1 m probe Per m Twin cable 2 kg 4 4 Ib 0 28 kg m Connector 102 Tube 228 316L 926 7 ALLOY C276 Hycontrol VF SERIES Installation and operating instructions Page 17 10 00 Mono rod Twin rod Connector
68. ring start up That explain the use of S With that design we can grant good liability of our instruments Hycontrol VF SERIES Installation and operating instructions Page 8 10 00 4 3 Service information Service information can be called up via the following interfaces e Current output 22 mA in case of error signal e Digital interfaces interrogation of error flags E D 10 i ih an 4 S 3 10 E ua Crctance do Range crested STANTA De inn EE only cable im ono er tems 5 Measuring accuracy 5 1 Reference conditions Temperature 20 C 68 F Pressure 1013 mbar abs 14 5 psia Air humidity 65 Highly reflecting product e g water with calm surface Tank diameter gt 1 m 3 28 ft Mounted at least 300 mm 12 away from tank wall Mounted flat on the tank no nozzle 5 2 Current output accuracy The accuracy of the 4 20 mA output is 0 01 of measured value 5 3 Error of measurement Since the measuring process primarily determines distance measuring accuracy can only be specified as a function of the distance For that reason all figures given in this Section 5 refer to the measured distance Hycontrol VF SERIES Installation and operating instructions Page 9 10 00 Accuracy mm 30 20 20 30 5 10 15 20 24m Distance to flange coax rod mono or twin ia only cable mono or twin or cable mono or twin
69. rvice Menu 3 The probe type selected is incorrect Service Menu 4 The tank is not empty Contact the Service Department in case of an unsuccessful auto measurement of the probe Fct Reset VF SERIES Restarts the device Hycontrol VF SERIES Installation and operating instructions e When exiting the test the current output will return to the measured or previous value Page 37 10 00 8 5 11 SERVICE Fct 1 1 2 Measurement Offset Function for manual zero adjustment Reference point for all measurements is the lower flange surface of the instrument It is not recommended to modify this parameter except for Hycontrol Service Personnel Level reflection For calibration you can modify the offset in order to adjust value supplied by VF SERIES If the value indicated by the VF SERIES is for example 2505 mm 98 6 and the true value is 2500 mm 98 43 then 5 mm 0 2 2505 2500 has to be added to the offset An automatic measurement of the offset can be performed with the dynamic configuration function This automatic function does not give an accurate value lt has to be adjusted manually Fct 1 1 3 Application Type Sets the process configuration A 1 product 1 level B 2 products 1 level Option A is the standard mode Only one product is in the tank and the dielectric constant of the upper medium between the flange and the lower product level is 1 0 air The second option is used in case the di
70. ry low e y liquids 10 Foam applications 1 Crystallising liquids 2 High deposal product application 3 Powders For all fine powder applications For high silos or tanks with liquids or granules 1 For all fine powder applica tions gt 6 metres 2 For all very viscous liquids like liquid sugar 3 For building a coaxial version with an existing stillwell Calibration required 4 Very corrosive liquids with FEP coating 5 Crystallising acids with FEP coating 1 Same as rods but up to 24 meters and over 6 me ters 2 For smaller tanks with no clearance for rigid probes coax or rod 3 For side installations with allowed probe max 6m 20ft on liquids only 1 Small connection flange 1 Long and small diameter with nozzle nozzle installation min re 2 Agitated tank without commended flange 4 or anchoring mounted with 2 flange 1 Max nozzle height base on its diameter calcu lation is h Lxd 140mm 4xa L Probe length mm d Nozzle diameter mm a Flange eccentricity from tank center mm Main Applications are Tanks lt 6 meters gt 6 meters under request Viscous fluid for very high viscosity use single probe All application NH3 solvents oil LPG etc For OEM integration molded in plastic liner or welded in the tank For multifluids storage tank 1 Tanks lt 6 meters 2 LPG LNG Solvent NH3 Fuel oil Foam Alcohol Displacer op
71. t HYCONTROL Service This message can occur at the start up of the device after Hardware tests Refer to Bank 0 and re start the device several times If the problem remains then contact HYCONTROL Service Digitizing Error This message occurs in case of a problem during sampling the audio emeng signal The electronics doesn t get a valid image of the audio signal The measurement may be incorrect Please contact HYCONTROL Service This message occurs in case of Hardware problems with the signal front end amplifier The error occurs in case one of the 4 amplifications do not work correctly Please contact HYCONTROL Service Offset Error As with the sampling and the Gain errors this message occurs in case of a problem with the electronic offset of the audio signal Please contact HYCONTROL Service HYCONTROL Service HYCONTROL Service HYCONTROL Service HYCONTROL Service HYCONTROL Service HYCONTROL Service Flange Not Found Occurs in the case of a problem with the time base The error indicates a mechanical problem bad contact between the converter s electronic block and the flange connection Please contact the HYCONTROL Service Department Update failure Warning message to indicate that the VF SERIES is not able to measure Hycontrol VF SERIES Installation and operating instructions Page 42 10 00 8 9 Start up Please refer to following table in case of problems 8 10 Faults and symptoms during start up and
72. the tank Install the new VF SERIES signal converter take care of the signal contact tip 3 4 Screw the 4 Allen screws M Allen key size 4 mm 0 16 6 Check power voltage 7 Reconnect all cables in the terminal compartment as described in Sect 7 6 Important Ensure that the O sealing of the signal converter is well greased Hycontrol VF SERIES Installation and operating instructions Page 19 10 00 4 Selection of sensor type Probe selection guide MONO ROD COAX TWIN CABLES MONO CABLE Recommended when For liquid powder or granules level lt 6 m small distance 1 To be used complemen tary to coaxial for all others applications For contactless measu rement through the plastic wall of tanks or in a sheath plastic tube for high corrosive fluids or crystallisation problems high dielectric For exotic application material as tantalum For specific probe shape with angles For minimum bottom dead zone in small tanks For full measurement level Contact inside the tank Temperature gt 240 C Only for clean liquids level 1 Connection size is lt DN80 mm 3 2 Liquid agitated acting like stillwell 3 Liquid or vapours spray near the probe 4 High flow inside vessel For example oil water separators 5 Can be heat traced 6 Contact with metallic part or tank wall possible 7 High magnetic field in tank 8 CE approval in plastic tanks 9 Ve
73. this information to the output circuit pulse micro generator digital processor time output gg base Hl circuit amp emm window en sample management AD i circuit converter oop A audio signal o De digital time transformation digital signal conversion 2 3 Modularity signal converter 1 G NPT probe system The measuring system consists of the sensor system and the signal converter The flange system is made up of the probe support the sealing system with signal contact and the process connection The compact signal converter contains the TDR measuring circuit and the entire signal processing system including the provision of a standardised output signal 4 20 mA or digital interface The signal converter can be separated from the sensor system under process conditions without compromising tank integrity Converter OS Flange or 1 G connection with pressure tight signal feed through Probe Hycontrol VF SERIES Installation and operating instructions Page 5 10 00 3 1 Measured variable distance level volume The primary measured variable is the distance between a reference point as standard tank mounting flange and a reflecting surface surface of the liquid Level is calculated from the measured distance value and the tank height Volume output is possible by entering a conversion ta
74. to point mode On multidrop mode only digital information is used 4 20 mA output been not valid in this case the current output of each instrument is set to 4 mA Step 1 We fix the address of the device different from 0 Step 2 Multidrop connection of 5 devices VF SERIES or other HART equipment in parallel or on a 2 wire bus Address 1 2 3 4 5 HART MASTER 4 4 4 mA d other other HAR HART device device During start up on multidrop mode it should be noticed that each instrument needs a current value of 22 mA see section 5 7 After this start up the instruments comes back to a fixed value of 4 mA in multidrop mode After the instruments are powered on for instance VF SERIES the current output remains fixed to 22 mA during 15 seconds Then it changes to 4 mA If we look at the example of the start up assuming that we have connected 5 Instruments That means that we need a current of 5 22 mA That it to say 110 mA during 15 seconds Re 250 O l O ccc o a e Vs 24V E HART MASTER 4 mA 4 mA 4 mA 22 mA 22 mA 22 mA ou Taking account of the Resistor load 25002 and the constant power supply 24 V we notice that the power supply is not sufficient enough Voltage drop within the resistor 110 mA 250Q 27 5 V Hence it appears that it is necessary to make a short circuit of the resistor of 250 Q du
75. ware nor the HART communication run when the converter is not equipped with this option 9 3 Sunshade If the device is exposed direct sun exposition a sunshade is recommended 9 4 Ex Applications Ex approved VF SERIES instruments must be used with certified Ex equipment only The maximum electrical safety values of the VF SERIES that are listed on the data plate must be respected in any circumstances The minimum voltage supply values that are described in 9 1 must be respected for the proper functionality of the VF SERIES Furthermore the connected equipment must be HART compatible in order to use communication software or the HHC communicator Hycontrol VF SERIES Installation and operating instructions Page 49 10 00 10 Certificates and approvals 10 1 CE Manufacturer s declaration DECLARATION OF CONFORMITY We HYCONTROL LTD Larchwood House Orchard Street Redditch Worcs B98 7DP United Kingdom declare on our own responsibility that the product REFLEX VF SERIES 24V DC to which this declaration refers is in conformity with the following standards EN 50081 1 1993 3 EN 50082 2 1995 3 pr EN 50178 1994 8 EN 61010 1 1993 4 in accordance with the provisions of Directives 89 336 EEC and 73 23 EEC February 2000 Signed Company Management Hycontrol VF SERIES Installation and operating instructions Page 50 10 00 11 Order information Technical information relevant to the order
76. wders 12 Approval 0 without 1 CENELEC zone 0 and 2 2 FM 3 CSA 13 Precision 0 without 1 Standard 2 5 mm 14 Temperature 0 without 1 standard 90 C 2 135 C Page 53 10 00 Information on nameplates example Version Type MANUF ACT N comm COMM Na N Rep TAG No N Fab Sem SERIAL Na Wiring instruction Alimentation POWER SUPPLY Pas de polarit Manufacture Lo lt E por les bornes 1 el2 NO POLARITY TO BE RESPECTED FOR POWER TERMNALS 1 AND 2 Pression Maxi MAX W PRESSURE Degr de protection PROTECT CLASS Const m canique MECHANICAL CONST Temp ambiante AMBIANT TEMP Temp Maxi la bride MAX TEMP AT FLANGE O Hycontrol VF SERIES Installation and operating instructions Page 54 European conformity Date of applied norm According to Type code see above date of manufacture Commission no Tag no customer option Serial no Power supply voltage Maximum process pressure Protection class of instrument Mechanical constant Min and max Ambient temperature Min and max Allowed flange temperature 10 00 Annex C Signed declaration to accompany a device returned to HYCONTROL If you need to return level gauges for testing or repair to HYCONTROL If installed and operated in accordance with these operating instructions your level gauges will rarely present any problems Should you nevertheless need t
Download Pdf Manuals
Related Search
Related Contents
PRB BELLE ÉPOQUE Sous Couche Wiko Lubi 2 Getting Started Guide TPL-410AP Punto de acceso wireless 500 AV Powerline Volkswagen The New Touran User's Manual South Shore Furniture 4379678 Instructions / Assembly Manuel d`Utilisation fire machine color - rgb - pt Safety and operating instructions Knoll Systems HT200 User's Manual 001 - Medium Voltage Enclosed Switchgear Copyright © All rights reserved.