1. Brief instruction TOPLON PRIO WAGO TOPLON WAGO TOPLON INNOVATIVE CONNECTIONS WAGE 5th step Create a binary hex file and test the project e After finishing the program please check in the menu project options if Dump symbol entries in symbol configuration is activated e Activate also Hex file not available in the demo version in C 6X compiler output e Following this check the program by using Project Check and save the program after st WAGO 9900 12 Test pru PLC_ RG PIG Fay 6th step Create Configuration variables The value of a variable that is declared as a configuration variable is permanently saved thus still available even after a power failure Configuration variables e g timer setpoints etc which shall be modified via LON network are entered as follows gt Choose a marker variable e g ncil MD1792 from the variable list template on the upper part of the screen gt If necessary rename the variable in the declaration part e g change nci 1 to stairway time_1 and copy the name to the corresponding input of the function block The name Stairway time_ 1 will appear in the configuration window of the TOPLON PRIO Plugin later on Brief instruction TOPLON PRIO e 9 maca INNOVATIVE CONNECTIONS 7th step Load application software First of all connect the PC and the LON controller with the serial cable
2. In order not to loose the original project rename the file and save it The renamed project can be used then in a standard way Variables in that project which shall be connected to the LON network should be used from the predefined variable list Rename the variables which shall be used in the project for inputs and outputs directly in the variable list and copy paste the variables to the operators and function blocks Please notice that it is important to pay attention to the type and direction of the variable The declaration of the variables is as follows e g _W1 direction Input type WORD number 1 e g O_Byte3 direction Output type Byte number 3 As explained above copy the renamed variable to the input or output of the operator or function block With it these variables including its new names and types are available for a network access in WAGO I O PRO 32 In order not to loose the overview it is recommended to deleted the unused variables before compiling the final project 14 Appendix Brief instruction TOPLON PRIO WAGO TOPLON
3. e Check in the menu Online communication parameters if the channel Local is selected Baudrate 19200 Parity Even Stop bits 1 Motorola byt no If not select this channel e By using the menu online Login select the LON controller 750 819 and confirm with OK e After the download of the application start the application in the menu Online Start e It is also possible to download the application hex file via the LON network from the Plug in TOPLON PRIO Use the HEX file generated in the 5 step For further information please refer to the TOPLON PRIO manual 8 step Start the Plug in WAGO TOPLON PRIO e Start the network management tool software Register the Plug in TOPLON PRIO and create a node with the device template PRIO_26 26 01 e Start the Plug in TOPLON PRIO depending on the network management tool gh step Import symbol file e Import the symbol file in TOPLON PRIO by using the menu WAGO I O PRO Open sym file Please find the sym file sym in the directory where the original WAGO I O Pro project is stored 10 e Brief instruction TOPLON PRIO WAGO TOPLON WAGO TOPLON Ae CONNECTIONS 10 step Baot_OUTs Vor_OUTs Bocl Ns Vars_INS Assign Standard Network Variable Types SNVTs to network variables Open the Software configuration using the menu Configuration Software Open the configurati
4. eivable measure has been taken to ensure the correctness and completeness of this documentation However as errors can never be fully excluded we would appreciate any information or ideas at any time We expressively point out that the software and hardware designations and brand names of individual companies used in this manual are subject to general trade name protection trade mark protection or patent protection 2 Brief instructions WAGO TOPLON WAGE INNOVATIVE CONNECTIONS Brief instruction for WAGO TOPLON IF Ist step Invoking Starting the network management software e Start the network management software using Start Program or by double clicking on the icon of the NMT 2nd step Create and open a new project e Create a new project according to the manual of your NMT e Select the project name of your choice For Online operation select Project interface e Open the new project 3rd step Register the Plug In s e Register the required Plug In e g WAGO T OPLON IF e Following this select the device template e g 24 24V03 For further information please refer to the TOPLON IF user manual Chapter Device template details 4th step Changing to Online operation optional Only if a network interface is installed e If it is not possible to access the network read the network interface operating instructions for diagnostic possibilities or contact the network interface suppl
5. ess gt MD1792 in the PLC program maximum 128 Click on the cell Type and assign an SCPT or SNVT type to the variable e You can rename the UCPT variable in the field CP Name The new name will then also be used in the network management tool software which makes it easier to assign the UCPT variable e A numerical value that is appropriate for the chosen data type has to be entered in the field Value After clicking on the Accept button the values are transferred to the controller e Ifrequired the configuration values can be read out of the controller by clicking on the Controller Update button i TELC_PRG nciGW _Temp_sussen PLC_PRG neHyat_ Temgp_sus en TPLCPRG nciTveinTemparanur PLC_PRG nciTveus Temperstur FPLUC_PRG naa Soana Ost PLC PPG nciTveinSome PUC_PRG nciTveusSone PLC_PRG nciG 1_Sonne_Sued IPLE PRG ncityetl_Sonne_Sued P CPRO nc Doemmenng IPLE PRG ncihyst Daommonng PLC PAG nciTen_Dssmmenng PLC_PRG nciTaus Doeemenng PLC_PRG nciTvein_ Regen FPUC_PRG nciTaus_Peges PLC_PRG nciTvaus_Windesberwachung SCPT delayTia 2 Byes SNVT_temp_p 2 Bys SNVT_tmmp_p 2 Bytes SCPTdeteyTime 2 Bes SNVT_See_sec 2 Bytes SCPTIudSetpoint 2 Bes SCPTdoleyTime 2 Bes SCPTdeleyTime 2 Bss SNT Jux 2 Bytes SNVT_Ju 2 Bytes SNVT Jux 2 Bytes SNVT_jux 2 Bytes ISNVT_Sme_sec 2 Bytes SNVT_tee_sec 2 Bytes SNVT_ me_sec 2 Bytas SNVT_tme_sec 2 Bytes 12 e Appendix Br
6. function test Only in On line mode Only if the Extras Make contact to LonWorks menu of the Online mode is activated Test the digital inputs and outputs via the View Digital I Os menu light green LED ON dark green LED OFF Test the network input and output variables via the View Browser menu Read the output variables by marking the individual control boxes and the attendant variables Following this click on the Read value symbol Set the input variables by entering a value in the input window and then clicking on the Accept value symbol 10 step Node configuration documentation optional Rename the product specific standard name using the selection menu Documentation and selecting via the menu point Digital input Digital output Analog inputs Analog outputs Network inputs Network outputs Select the required print data in the Documentation Print menu and print Brief instruction TOPLON IF 5 maca INNOVATIVE CONNECTIONS 6 e Brief instruction TOPLON IF WAGO TOPLON maco INNOVATIVE CONNECTIONS Brief instruction WAGO TOPLON PRIO 1st step Invoking Starting the WAGO I O PRO 32 software e Start the WAGO I O PRO 32 software using Start Program or by double clicking on the icon WAGO I O PRO32 on your desktop 2nd step Create a new project e Open the file Template 750 819 by selecting the menu File Open P
7. ief instruction TOPLON PRIO eciTveusWind T 05 nciGW Temperatar 7 00 105 ncttyiterseTemp 100 6 nciTveinTame m0 107 o nciTvausTemo 200 E INSO 20 eciTveinSome U 0 I __rciCTvwutSorne 300 793 MaWi 40000 179 nohtSonneS d 2000 79 eo anemmer 7000 173 nct4ysteammer 00 107 onciTemDoemmer 300 107 sciTausDeerener 300 10 onciTveinReger 200 107 nciTveurFeges 200 WAGO TOPLON maco INNOVATIVE CONNECTIONS Template WAGO I O PRO 32 Input parameter Data type Comment Function description WAGO I O PRO project variables with different types are predefined for connection with the network The template includes the following enlistments Input variables e 2 REAL e 10 WORD e 10 INTEGER e 15 BYTE e 20 BOOL Output variables e 2 REAL e 10 WORD e 10 INTEGER e 15 BYTE e 20 BOOL Configuration variables e 20 DWORD expandable to 128 WAGO TOPLON Appendix Brief instruction TOPLON PRIO 13 maca INNOVATIVE CONNECTIONS The template can be extended at any time The maximum limits are Input variables e 20 REAL e 100 WORD e 100 INTEGER e 100 BYTE e 496 BOOL Output variables e 20 REAL e 100 WORD e 100 INTEGER e 100 BYTE e 496 BOOL Configuration variables e 128 DWORD How to use the template Open the WAGO I O PRO project Template_750_819
8. ier Sth step Create unit node e Create a node device according to the manual of your NMT e Enter the required device names and select the device template e g 24 24V03 Only in On line mode e For commissioning a device press the Service Pin with the designation SRQ on the bus coupler to read in the Neuron ID of the node e Incase of fault messages The entered device template with the program ID does not match with the received program ID Click on the Yes button e Click on the OK button when error messages appear like The Programld of the device does not match the device template Please load an matching application program into the device e For downloading an APB file refer to the manual of your NMT e Select the APB file having the highest version number for the required device template WAGO TOPLON Brief instruction TOPLON IF e 3 INNOVATIVE CONNECTIONS WAD 6th step Select Plug In Start the Plug in TOPLON IF like described in the manual of your NMT 7th step Configure hardware e Start the hardware configuration using the Configuration Hardware menu in the main TOPLON IF window Online mode e The field bus coupler is automatically read for documentation purposes specify by double clicking on the individual modules Offline mode e Take over the modules to be used in the project one at a time by selecting in the left hand window and clicking on
9. lease find the file in the directory english software programming template on the TOPLON CD template description in the supplement e Save the file using File Save as under a name of your choice 3rd step optional Insert an additional library e Copy the required library from the TOPLON CD into the directory C Programms WAGO IO PRO 32 LIB2 Please find the libraries in the directory X english software applications Open the menu Window Library Manager Insert the selected library in the library manager by using the menu Insert additional library WAGD 10 PRO I2 Test pro Library Mana BOE Ble Ed Poon piot Eyoss Qilsa Window Help laix Diza amosa tae SSS rl braen OO T r WAGO TOPLON Brief instruction TOPLON PRIO e 7 maca INNOVATIVE CONNECTIONS 4th step Create a program Note The following example is done in the programming language FBD e Change the view from Library Manager to PLC PRG by using the menu Window PLC_PRG PRG FBD e Insert an operator a function or a function block by using Insert Operator The operator AND will be inserted in the program Clicking on F2 on the keyboard opens the help manager for the selection of different FBD or conversion operators e The required operator will be inserted in the program by double clicking on it e Assign variables to the inputs and outputs of the function blocks or operat
10. maco INNOVATIVE CONNECTIONS Brief instructions WAGO TOPLON for TOPLON IF und TOPLON PRIO Quickstart These brief instructions for TOPLON IF and TOPLON PRIO show the general procedure from creating a project to the start up of a WAGO TOPLON fieldbus node in a few steps They are correct but not complete and for this reason do not replace the manual The intention is to assist you to realize your first applications with WAGO TOPLON IF and with WAGO TOPLON PRIO in a short time and to form a guideline for further projects It has been assumed the tools any LNS compliant network management tool NMT Lonworks LNS database and WAGO TOPLON IF and or TOPLON PRIO PlugIn have been correctly installed An interface to the bus system such as for example a LONDONGLE is required on the PC parallel port to allow online access to the nodes WAGO TOPLON Brief instructions 1 WAGE INNOVATIVE CONNECTIONS Copyright 2001 by WAGO Kontakttechnik GmbH All rights reserved WAGO Kontakttechnik GmbH HansastraBe 27 D 32423 Minden Phone 49 0 571 8 87 0 Fax 49 0 571 8 87 1 69 E Mail info wago com Web http www wago com Technical Support Phone 49 0 571 8 87 5 55 Fax 49 0 571 8 87 4 30 E Mail support wago com Information on TOPLON Phone 49 0 571 8 87 0 Fax 49 0 571 8 87 8 528 E Mail toplon wago com Web http www wagotoplon com Every conc
11. on screen NVIs by clicking on the icon on the left hand side In order to select the appropriate SNVT click in the row with nvi00 the column Type Choose from the appearing pull down menu the type SNVT_ switch Contigurntion Subsystem 1 Dreg e column header hare to group by hat coluen f d g g g g o g g o Oo g g d g q g al g o g g a o g g g g a 11 step Assign WAGO I O PRO variables to network variables Open the configuration screen Bool OUTs by clicking on the icon on the left hand side Click in the first row on the column Connected to and select from the pull down menu the network variable input_ext_1 Choose from the appearing pull down menu the network variable nvi00 that you defined before Click on the suited structure element of the SNVT e After a Click on OK insert the upper and lower bound This values serve to the signal accommodation of the WAGO I O PRO variables and the network variables Before closing the window confirm the configuration with Apply or OK Brief instruction TOPLON PRIO e 11 maco INNOVATIVE CONNECTIONS 12 step Write and read the configuration variables e Open the window with the configuration variables under WAGO I O PRO Configuration IEC 61131 e Inthe column Variables are all variables that have been declared as markers with the addr
12. ors Therefore a variety of pre defined variables template with 2 double words 10 words 10 integers 15 bytes and 20 bits per direction are displayed on the upper part of the screen For local variables gt Attention Before defining a variable click with the mouse pointer at the bottom of the variable list once to make sure that the next variable is inserted at the right place gt Enter the appropriate names for inputs and outputs by clicking on Return gt Press Enter for getting the declaration window gt Select the right type for the variable and press OK For external variables gt Choose one of the variables with an appropriate type from the predefined variable list at the top by just clicking on it gt Rename this variable to a name of your choice e g I Bit1 to input ext 1 and copy and paste the name by using Edit Copy and Edit Paste to the input or output of the operator or function block The choosen name in this case input_ext_1 will be displayed in the Plug In TOPLON PRIO e Mark the output area of an operator by clicking right beside the block Add an Assignment to the function block by using the menu Insert Assign Type in the address of a channel of a module e g QX2 0 for the first digital output if a 2 channel analog output module is installed For further information please refer to the chapter Addressing in the WAGO I O PRO 32 manual 8 e
13. the top arrow in the right hand window The hardware configuration is graphically displayed in the lower window e Terminate hardware configuration with Continue 8th step Configure software e Start the software configuration using the Configuration Software menu in the main TOPLON IF window e Select required register gt Basic initialization e Enter the number of latching relay functions if digital inputs and outputs are available on the nodes e Click on the Initializing button Common building functions e Open the function type selection window for each function number scroll down arrow and define the function type e Select hardware as well as network inputs and outputs e For further functions select the next function number scroll right arrow gt Central functions optional e Open the function type selection window for each function number scroll down arrow and select the function type e Click on the required subscriber of the central function in the control box e Select the digital or network input which the central function is to activate gt Additional functions optional e Configure the connected light sensor Terminate the software configuration with OK For more information please refer to the TOPLON IF manual Software configuration and Functions chapter 4 e Brief instruction TOPLON IF WAGO TOPLON WAGO TOPLON INNOVATIVE CONNECTIONS WAGE gh step Perform

Download Pdf Manuals

image

Related Search

Related Contents

ブレーキホースキット 取扱説明書  Service des enseignants et référentiel horaire  Day & Night High-definition Color Camera User`s Manual  Chapter 1  Voice Service Optimization and Troubleshooting AMR failures in a  Origin Storage KB-4FW6W notebook spare part  OBJECTIFS Maîtriser la RTex*, réglementation thermique de l  