Eco-Line Signal Converters User Manual

image

Contents

1. Normally the Eco Line UCV version will be delivered with input and output set to be 4 to 20 mA gi ee z EAE WADNSS 85 Hine de 5 RF Remove the DIP switch covering stickers we do supply spare covering stickers with the unit ne 5 hh al IJ 5 0A Using the table in the Input Range Selection section B oy Mem use DIP Switch SW2 select the input range of TA 4 20 mA this is how it is normally delivered so switches 2 3 and 8 must be ON all others OFF 0 VDC Use DIP Switch SW3 to select an output of O to 10 V From the table in the Output Range Selection you will see that SW3 must have switches 2 and 6 ON and all others OFF The device is normally delivered set up for 4 20 mA output which is SW3 only 1 and 6 are ON Lode g SATEN m s 7 na F b id i At this point you can decide if you wish to have e the Zero and Span trimpots enabled use SW1 switch 1 to do this OFF disabled ON enabled e the Zero and Span set for Normal or Wide range adjustment use SW1 switch 2 to do this OFF normal 10 ON wide 50 e The filtering you desire using SW1 switches 3 and 4 switch 4 ON and 3 OFF 1 second for other selections see the table Filename Filename Eco Line Signal Converters User Manual docx 26 October 2014 Version 1 16 danntech PROCESS INSTRUMENTATION Page 5 of 22 Now you can set up the input 1 Now refer to the table in the section D
2. ccceeeeseeeeeeeeeeeeeeeeeeees 22 POW FO iets rust ovcnces satan cuthanancnshatanansuanoune sats 16 Application Examples ccccccssesseeeeseeees 16 Danntech makes no warranty of any kind with regard to this material including but not limited to the implied warranties of merchantability and fitness for a particular purpose Danntech shall not be liable for errors contained herein or for incidental or consequential damages in connection with the furnishing performance or use of this material This document contains proprietary information which is protected by copyright No part of this document may be photocopied reproduced or translated into another language without the prior written consent of Danntech The information in this document is subject to change without notice Filename Filename Eco Line Signal Converters User Manual docx 26 October 2014 Version 1 16 danntech PROCESS INSTRUMENTATION Page 1 of 22 Configuration As acustomer you can do one of the following A 0 O Order the standard stock part you require from this list below 1 GB SE IA IA C Input 4 20 mA Output 4 20 mA Auxiliary Supply 24 VDC r ji X P 2 GB SE VA IA C Input 0 10 V Output 4 20 mA Auxiliary Supply 24 VDC 3 GB SE IA VA C Input 4 20 mA Output 0 10 V Auxiliary Supply 24 VDC we may add others here depending upon demand and then accept our standard configuration Zero and Span Trimpots enabled Zer
3. The Eco Line Signal Converter provides a way of doing this without the need for you to have an expensive Process Calibrator to simulate the required input voltage All you will need is a basic accurate multi meter and you can use the Eco Line Signal Converter itself to generate the required input signal range or you can use a process signal calibrator if you have one Please note that the product version you receive may not exactly match this picture as we plan to add a few more features early in 2013 These are Alarm and Input Status LED operation and serial communications When you change the input or output ranges you must recalibrate the input and output as exact analogue values are slightly different internally for each range The DIP switches Push Button Link and setup LEDs are accessed by removing the covering stickers Call 011 792 1239 support danntech weeueg EMS Byuog nano g Basic gt Input ranges from 50 mV to 100 V Input ranges from 50 mV to 100 V aie 1 mA up to 10 ADC 1 mAup to 10ADC E cero amp Span Normal gt Output ranges from 0 100mV to from 0 100mV to ON Cero S Wide __ 10 V 0 mA to 22 mA ae Output 10 V 0 mA to 22 mA gt DIP Switch Peel off sticker See Filename Filename Eco Line Signal Converters User Manual docx 26 October 2014 Version 1 16 danntech PROCESS INSTRUMENTATION Page 3 of 22 How it Works A microcontroller forms the central part of the signal
4. a value for approximately 4mA output if the output is set for OFF current otherwise approximately 2 volts then 12 mA 50 output then 20mA 100 output and then 22mA maximum output value then back to following the input step 1 Using the calibrate button you can cycle through these outputs The cycle is repeated as the button is pressed Filename Filename Eco Line Signal Converters User Manual docx 26 October 2014 Version 1 16 danntech PROCESS INSTRUMENTATION Page 15 of 22 Power Up All the LEDs flash twice on power up or when the unit resets for any reason On power up the following is sent to the RS232 port irrespective of the CN2 link Eco line Signal Converter dt331 Copyright Danntech 2012 Firmware V200 Normal power up lf the device has restarted due to a watchdog reset then instead of Normal power up The following will be displayed instead Eco line Signal Converter dt331 Copyright Danntech 2012 Firmware V200 Restarted processor because of watchdog timeout Your unit may not have the COMMS jack socket fitted Application Examples 10V to Servo Controller 24 VDC 0 10 V to data logger 24 VDC to PLC 24 VDC Battery Bank 48 VDC Nominal 0 VDC 0 VDC 0 VDC 4 20 mA from PLC lt Current Shunt 100 mV 100 ADC Typical Results Product Test Report Part Number GB SE_UCVIVG VGAC Supply 24VDC Isolation yes Description Eco Line Signal Conver
5. n he AL Ue c fj al w i st i Zz Hy Vidi k oh cer te a qe e Bie pa i La na bP ae oped 4 TFA i r t ip f Fa i eo er a aa PE a ee MEFE a i FS e d Ji Zeit j j k fe f i 4 oa j I i j r s a A ia i p i Mi a r 5 a kE E j F s E oa i f G 7 b k lil L s re T a a g J 4 PROCESS INSTRUMENTATION a Ai P F EA A OS T na hp i IOA ss 7 S EA ee E The Eco Line range of signal converters has been designed using a low cost powerful microprocessor which enables us to offer flexibility reliability and accuracy at a really good price in a small package Using miniature DIP switches a variety of standard inputs and outputs can be selected and with the one button calibration accurate operation in any configuration is assured Having selected the required input and output ranges these can be adjusted to be anything within the selected range using the one button calibration For example with a O to 100 mV input and 10V output selected one can calibrate the device to have say 0 to 60 mV input where 30 mV input gives an output of 0 V 60 mV an output of 6 V and for 0 mV input and output of 6 V Output inversion is also easily accommodated The Zero and Span trimpots can be disabled or switched to a wider adjustment range using the DIP switches Filtering
6. DIP Switch Selection SW3 _ _ Config 7 LEDs 1 a Ys Push 3 CrTi ma l Button t ii yi Config 4 LD4 PB Link DIP Switch Wy Yy LEDs 2 PB J2 Selection SWw1 E LD5 Filename Filename Eco Line Signal Converters User Manual docx 26 October 2014 Version 1 16 danntech PROCESS INSTRUMENTATION Page 4 of 22 Quick Configuration Guide If you change the input or output ranges from the settings as delivered input 4 20 mA output 4 20 mA you must redo the setup for the changes made So if you change the input then only the input needs to be redone not the output likewise for the output The exact internal analogue values are slightly different for Input mA Output V each range 2 0 10 This step by step procedure will use as an example the setup for an Eco Line Signal Converter with an input of 2 0 mA to 18 0 mA and output of 1 0 V to 5 0 V We will assume that you have a Process Calibrator to inject the desired input range although you could use the Eco Line to generate the mA signal for you In the case where you wish to use the Eco Line to generate the input signal you will need to first of all set up the output to be 2 0 to 18 mA follow the Output Setup procedure Then you connect the output to the input and then set up the input using a multi meter to check and adjust the input Having done that you then 24 ypc redo the setup for output to be what you require
7. converter and after some basic signal conditioning the analogue signal is digitized The Input Signal Conditioning is done in four stages and the various gain and offsets are applied to the input signal The design includes a programmable current source and voltage reference These are not available for the user to access but will be used in our resistance input devices An optional thermocouple amplifier and cold junction temperature sensor are also included for later use Galvanic isolation between input output and power supply is provided using to high quality DC to DC converters with the requisite noise filtering DIP switch 1 SW1 provides selection inputs to the microcontroller DIP switch 2 SW2 switches the various analogue circuit parts to provide the signal conditioning necessary for the various input options DIP switch 3 SWS selects the various output circuit options We have also included an optional isolated RS232 TTL interface which will be used in later versions for configuration purposes data logging and is able to be used for CANBUS COMMS RS232 TTL CANBUS DC Power In INPUT POWER STATUS ALARM IN LED LED LED Current ae Source O Isolated isolated Betas DCtoDC P eaaa ee pote eee ewes Converter Ouinit T i utpu i DIP Switch Conditioning Selection SW2 mmr OoN i lt 2 a il Isolation Input Signal ooo p Micro Conditioning Controller
8. is also DIP switch selectable in four ranges up to 60 seconds We can also make firmware changes if you have a special application that we have not catered for If you have any comments or suggestions which could improve this User Manual please e mail them to me at mailto miked danntech com subject Eco Line User Manual Comment COPTMO UIA OD sie cist ctncrceicndecevics neescscexdesecesedesedxs 2 Typical Results sz sesiicdncrcs ends cecsendsceesicncnczciies 16 HOW It WOFKkS ccccceecceeeeeeeeeeseeeeeeeeeseeeeeees 4 Other Eco Line VersSiOns ccccccseeeeeeees 17 Quick Configuration Guide ccceeeeeees 5 Using the Eco Line Signal Converter as a DIP Switches Push Button PB and Push Preset oignal SOUNC GC eniseiiierirendieniieeiienisesis 17 BOOT EINK era a A 8 Serial COMMUNICATIONS ccccseeeeeeeeeeees 17 Input Range Selection ccccecceeeeeeeeeeeees 9 Setting up without a Process Signal Calibrator Input Setup eee re 9 250585505ESNRNENNENNRNENERNSESNEHNNENENEREHSNENNENEHNEREENENE 18 Output Range Selection ccceeeeeeeeee 10 Opening the Enclosure eseeees 19 Some other interesting things about the Eco Output SetUP cece ceececceeeeeeeeeeeeeeeeeeeees 10 eae P Line Signal Converters cccccseeeeeeeees 20 TSS UT NOGE oes ces eae ee eet 12 oe PEWO onien a Specifications ccceececeececeeeeteeeeteneeeeeeeees 21 a coiiaebs Part Numbering
9. 3 of 22 DIP SW1 Operational Settings Zero and Span Trimpot Enable Enables the operation of the Zero and Span trimpots on the front panel You can enable the trimpots make your adjustments and then when you disable the trimpots the values that you last adjusted are saved and used until the trimpots are enabled again OFF trimpots disabled ON trimpots enabled Zero and Span Normal Wide Range Adjustment Select Provides normal and wide trimpot adjustments for Zero and Span OFF Zero and Span adjustment are normal i e approx 10 over full trimpot range OFF ON Zero and Span adjustment are wide i e approx 50 over trimpot range Note that you may need to adjust zero and span several times to get the best accuracy Filtering Select selects the moving average filter step response time Time seconds No filtering step response approximately 0 1 sec ON Input Calibration Calibrates the input circuit to take into account any component tolerances for the input range selected Using calibrate button to indicate the required input is present at the input You must follow the sequence and carry out all three steps in order Uses three values to fit polynomial to input calibration for highest accuracy operation OFF Inject Minimum Input Value press and hold button until green LED stops flashing and stays on then release button Inject Maximum Input Value press and hold button un
10. IP SW1 Operational Settings on page 14 to set up the input switch SW1 switch 5 ON to select the Input Calibration mode switches 6 7 and 8 must be OFF Now using your Process Calibrator inject the minimum input value 2 mA in this case The state of SW3 does not matter at this point Now you need to press and hold in the Push Button you can do this from the front panel or by closing the PB link next to DIP switch SW1 Hold in until the Push Button until the Red Configuration LED comes on The Green Configuration LED as well as the Status LED will come on for about 1 second to indicate that the minimum input value has been captured Release the button as soon as the RED Configuration LED comes on During the minimum input calibration stage the unit will outout a value set by the Zero trimpot which can be used for input calibration if required Now inject the maximum input value and again press and hold the Push Button as before to capture the maximum input value The internal processor has now recorded and saved these values to use forever switch SW1 switch 5 off to complete the input calibration Now you can set up the output Here you have two choices of how to drive the output you can use the input with your Process Signal Calibrator DIP SW1 switch 6 OFF or the ZERO and SPAN trimpots DIP SW1 switch 6 ON 1 Now refer to the table in the section DIP SW1 Operational Settings on page 14 to set
11. able 4 20 mA 0 20 mA 0 5 V 0 10 V 10 V 3 Isolation 1000 V AC RMS three way isolation between input output and auxiliary power supply 4 Response time approximately 100 mS with filter off 5 Optional filtering selection with DIP switches 0 1 1 10 and 60 seconds step responses to eliminate noise if required 6 Internal trimpot adjustment of output minimum and maximum which can be locked using DIP switch 7 Power On LED indication 8 Microprocessor based latest architecture 9 Smart input and output calibration re ranging using push button switch and LED 10 Linearity better than 0 1 of full scale 11 Auxiliary supplies 12 VDC or 24 VDC 10 must be specified with order Auxiliary supply current 12 VDC at 80mA lout 24 VDC at 45mA lout 12 Operating temperature 10 C to 70 C 13 DIN rail mounting with flame proof high quality enclosure 14 Screw terminal connections for wire diameter 2 5 mm 15 Dimensions 25 x 80 x 85 mm W x H x D ae elma Eco Line Signal Converters User Manual docx 26 October 2014 danntech PROCESS INSTRUMENTATION Page 21 of 22 Part Numbering There are two main types please call us if something is not clear GB SE ko ni ip Eco Line Signal Converter input output aux supply Basic preconfigured version Has labels etc all preconfigured not intended to be configured by the user part number selected as indicated below AND GB SE UCV p User Configura
12. ble Version can specify 24 or 12 VDC auxiliary supply Supplied at 4 20mA 4 20mA setup Uses push button and DIP switches to select various options User can change settings and has overstickers for various options and blanks for user to make up own ranges CURRENT 2 INPUT 20mA CURRENT 5ma OUTPUT 20 4mA ooo amp Selected options red and bold are stock items other versions available within a few days Auxiliary Power Supply C 24 VDC 12 VDC Internal Configuration 9 standard internal configuration can be left out if 9 the standard configuration Standard config Trimpots Enabled Zero and Span Normal Filter Step Response 1 sec Example GB SE IA VA C is Input 4 20 mA Output 0 10 V Auxiliary Supply 24 VDC Standard Internal Config i VOLTAGE INPUT VOLTAGE OUTPUT gt b Lu aa Vv vi Vv Lu W O aa a e V o ss Q O danntech ltd danntech ce Co No 6510211 Reg No CK1986 15338 23 15 College Close Hamble le Rice Tel International 27 11 7921239 Southampton Hampshire Tel National 011 7921239 S031 4QU Fax International 27 11 7924687 United Kingdom Fax National 011 7924687 E Tel 075 9069 1824 e mail sales danntech com e mail sales danntech info P O Box 1023 Fontainebleau 2032 www uk danntech info Republic of South Africa www danntech com Filename Filename E
13. co Line Signal Converters User Manual docx 26 October 2014 Version 1 16 danntech PROCESS INSTRUMENTATION Page 22 of 22
14. d Max lt SW1 6 OFF Ain ON POTs top zero bot span gt Ain 535 VR1 3727 VR2 857 SW1 104 Button 0 m 1 07 c 285 11 DACOut 857 Your unit may not have the COMMS jack socket fitted Filename Filename Eco Line Signal Converters User Manual docx 26 October 2014 Version 1 16 danntech PROCESS INSTRUMENTATION Page 11 of 22 Test Mode There is a test function built in which is activated by switching ON SW1 8 with switches SW1 5 6 amp 7 OFF In Test mode the output can be switched with each press as follows No press yet following the input 1 the minimum possible output value which would can be 0 mA for an output setup of 4 20 mA or 0 3 V for an output setup of 0 10 V 2 the minimum setup output value 0 which would be 4 mA for an output setup of 4 20 mA or 0 V for an output setup of 0 10 V 3 the midrange setup output value 50 which would be 12 mA for an output setup of 4 20 mA or 5 V for an output setup of 0 10 V 4 the maximum setup output value 100 which would be 20 mA for an output setup of 4 20 mA or 10 V for an output setup of 0 10 V 5 maximum possible output value which would be about 21 5 mA for an output setup of 4 20 mA or 10 4 V for an output setup of 0 10 V Using the Push Button PB you can cycle through these outputs The cycle is repeated as the button is pressed The LED will flash once every 2 seconds and the output will be as per normal determined by the inpu
15. etup those which have been changed they operate independently from each other lf you are using the Zero and Span trimpots SW1 switch 1 is ON you will need to inject the minimum and maximum inputs and adjust the Zero and Span trimpots to give the exact outputs you require Do this once to set and a second time to check for best accuracy Filename Filename Eco Line Signal Converters User Manual docx 26 October 2014 Version 1 16 PROCESS INSTRUMENTATION Page 7 of 22 DIP Switches Push Button PB and Push Button Link Alarm LED DIP Switch SW3 Status LED ior detaia wie or ecen GA oia tero and Span Button PB Phe Trimpots Push Button PB Link J2 Communications Swi C a onfiguration Connector Input Status Socket LED LEDs green amp red i hr reel Push Button PB Link J2 Sji m TPS J1 Solder apii PFE Link Configuration LEDs green amp red CN2 f p ae Link OUT aye pa CN2 a tae RS Link IN eS Ga al aT Filename Filename Eco Line Signal Converters User Manual docx 26 October 2014 Version 1 16 danntech PROCESS INSTRUMENTATION Page 8 of 22 Input Range Selection Setup using DIP Switch SW2 and J1 J1 is a solder link accessible only by opening the enclosure you will need to open the enclosure see on page 18 and solder a blob of solder on the pads to close this link DIP Switch SW2 Input Input Setup This is done
16. nal We do have the facility to include an isolated RS232 TTL using the 4 way jack socket This will be used in the future to provide a software configuration feature We can also provide a configuration cable which provides connection from USB to our RS232 TTL Filename Filename Eco Line Signal Converters User Manual docx 26 October 2014 Version 1 16 danntech PROCESS INSTRUMENTATION Page 17 of 22 Setting up without a Process Signal Calibrator The unit is designed to be able to be setup without a Process Signal Calibrator for standard type inputs MY Self Calibration for Voltage Input Self Calibration for Current Input 24 VDC 24 VDC MAINS T ipauuvop 0 VDC 0 VDC The basic process is as follows Set up the output to be able to generate the type of input signal you require Using a multi meter adjust the trimpots to configure the output for the minimum and maximum values you require for your input Now connect up the output to the input including your multi meter as shown in the diagram above for voltage or current input 4 Now calibrate the input and while calibrating the input the output will generate the values you setup previously for the input minimum and maximum values When you have set up the input you need to go back and configure the output to be what you required This avoids the need for an expensive process signal calibrator for basic input types ranges File
17. name Filename Eco Line Signal Converters User Manual docx 26 October 2014 Version 1 16 edanntech PROCESS INSTRUMENTATION Page 18 of 22 Opening the Enclosure The only reasons to open the unit are to install the solder link J1 if you need the 0 30 V input range or to install the CN2 link to enable the COMMS output Both of these are fairly unusual and most users will not need to open the unit GAVE WWOZ 7 1NO ZHXOS 0 NI wae Use a moderately sharp blade not too sharp to With a screwdriver you can get some gently lift up the left side of the front label Be leverage at the bottom of the enclosure careful not to cut the label Run the blade all along between the parts as shown in the photo the left side to free up the left side of the front Gently pry the left side cover apart from the front panel label Using the screwdriver gently pry open the enclosure all around taking care not to damage the plastic parts Filename Filename Eco Line Signal Converters User Manual docx 26 October 2014 Version 1 16 danntech PROCESS INSTRUMENTATION Page 19 of 22 Some other interesting things about the Eco Line Signal Converters This QR code is on the right side of the product and if you download a barcode reader app for your smartphone and scan in this code you will be taken to the latest version of this user manual on our website ole a If you squeeze the enclosure front to back you can press in
18. nd hold the Push Button PB for a few seconds until the red LED flashes and the green LED stays on for approximately two seconds Release the Push Button as the red LED flashes this latches the output value as the minimum output calibration value The green LED will now flash as follows J LILLE J LI UWL 4 If SW1 6 in on you have selected to use the SPAN trimpot to control the output adjust VR1 Span until you get the output desired for the maximum output value lf SW1 6 is off you have selected to use the input to control the output vary the input to adjust the output you require for the maximum output value 5 Press and hold the Push Button PB for a few seconds until the red LED flashes and the green LED stays on for two seconds Release the Push Button as the red LED flashes this latches the output value as the maximum output calibration value The green LED will now flash as follows JL L 6 Switch SW1 7 and 6 off to complete the process While doing the input calibration information can be observed using the RS232 jack socket connection This works at 9600 8 N 1 no flow control Without the link installed between CN2 programming header pins 1 amp 2 only the header line will be sent out To see the internal values you must have this link installed Typically the info displayed will be Eco line Signal Converter dt331 Copyright Danntech 2012 Firmware V200 Output Cal Mode Use Button to capture Output Min an
19. ne Signal Converter at331 Copyright Danntech 2012 Firmware V200 Input Cal Mode Use Button to capture Inout Minimum and Inout Maximum Ain 2955 VR1 3727 VR2 857 SW1 24 Button 0 m 1 06 c 580 20 DACOut 3737 Your unit may not have the COMMS jack socket fitted Output Range Selection Setup using DIP Switch SW3 SW3 PT E Output Setup This is done by using either the Zero and Span trimpots or by injecting a signal into the input to control the output and then latching the minimum and maximum output values desired You can invert the output if you need this making the maximum say 4mA and the minimum 20mA Filename Filename Eco Line Signal Converters User Manual docx 26 October 2014 Version 1 16 danntech PROCESS INSTRUMENTATION Page 10 of 22 Use the following steps 1 SW1 7 is used to activate output calibration mode SW1 8 must be off The green LED will flash twice every 2 seconds in the following way 2 If SW1 6 is off then the input is used to activate the output If SW1 6 is on then the Zero and Span trimpots are used to control the desired output this is the recommended option 3 If SW1 6 is on using the ZERO trimpot to set the output adjust VR2 Zero until you get the output desired for the minimum output value lf SW1 6 is OFF you have selected to use the input to control the output vary the input to adjust the output you require for the minimum output value 7 Press a
20. o and Span Normal Range Adjustment Select and Moving Average Filter Step Response Time 1 second No further configuration is required from you and you can ignore the remainder of this User Manual Or Order the exact part you require using our Eco Line Part Signal Converter Part Numbering guide and fill in the Eco Line Ordering Form sign and send to us and we will configure them for you No further configuration is required from you and you can ignore the remainder of this User Manual Or Order the User Configurable Version UCV and then you can configure it yourself using the Eco Line Signal Converter User Manual this manual You will not be able to configure certain versions as some hardware changes are required for some types User configuration can be done for the following ranges Inputs 0 100 mV 0 1 V 0 10 V 0 100 V 100 mV 1 V 10 V 100 V 0 to 22 mA Outputs 0 100mV 0 1V 0 10V 10 V 0 to 22 mA The User Configurable Version provides a way to configure the device for non standard inputs and outputs within any of the configuration ranges listed above Filename Filename Eco Line Signal Converters User Manual docx 26 October 2014 Version 1 16 danntech PROCESS INSTRUMENTATION Page 2 of 22 For example you can set up the input to be say 200 mV to 800 mV with the output 20 to 4 mA inversion Input Output For 200 mV input you want 20 mA output and m mA 800 mV input you need 4 mA output
21. t without the Zero and Span adjustments The green LED will flash as follows d LE First press output zero Second press output calibrated minimum d OUL T OUL Filename Filename Eco Line Signal Converters User Manual docx 26 October 2014 Version 1 16 edanntech PROCESS INSTRUMENTATION Page 12 of 22 Third press output calibrated maximum calibrated minimum 2 calibrated minimum J WUUL OUUU Fourth press output calibrated maximum Fifth press output maximum sixth press output normal and follows input without Zero and Span adjustments JL LE While doing the input calibration information can be observed using the RS232 jack socket connection This works at 9600 8 N 1 no flow control Without the link installed between CN2 programming header pins 1 amp 2 only the header line will be sent out To see the internal values you must have this link installed the unit is shipped with this link out Typically the info displayed will be Eco line Signal Converter at331 Copyright Danntech 2012 Firmware V200 Use Button to Cycle through outouts gt 0 min max min 2 max 4095 Ain 536 VR1 3727 VR2 858 SW1 136 Button 0 m 1 07 c 285 11 DACOut 859 Tm 1 00 Tc 0 00 Runtime 122 Your unit may not have the COMMS jack socket fitted Filename Filename Eco Line Signal Converters User Manual docx 26 October 2014 Version 1 16 danntech PROCESS INSTRUMENTATION Page 1
22. ter Tested By MD Date 13 Nov 12 Serial Number 125914 A Input Output Units V Units V Min 10 00 Min 10 00 Max 10 00 Max 10 00 ae f Rar of Range a as Load Resistance 4 7kQ Filename Filename Eco Line Signal Converters User Manual docx 26 October 2014 Version 1 16 danntech PROCESS INSTRUMENTATION Page 16 of 22 Other Eco Line Versions Resistance Inputs Thermocouple Inputs Pt100 Pt1000 Inputs 0 10V to Datalogger 24 VDC 24 VDC e 5 4 a 0 VDC 0 VDC 0 VDC Platinum Resistance Thermocouple Temperature Sensor Resist esistance Input Pt100 Pt1000 Input Using the Eco Line Signal Converter as a Preset Signal Source You can configure the desired output type and range for the signal that you require Set the maximum and minimum as per setting the Outout Range Selection section Then you set the unit into Test Mode by switching ON SW1 8 with switches SW1 5 6 amp 7 OFF Now by pressing the Push Button repeatedly cycles through the five possible outputs At starting 0 zero output value Press 1 Minimum Output Calibration value Press 2 Halfway between Minimum and Maximum Output Calibration values Press 3 Maximum Output Calibration value Press 4 Full scale possible output value Press 5 back to starting Serial Communications As delivered the communications socket is left out and connection using RS232 TTL is available internally This is not isolated from the input sig
23. the Push Button So you can get away from using a sharp thin object to press in the switch You can use the Eco Line as a signal source to calibrate itself or use it to generate two output levels which you can switch between by pressing the push button this by using the Input Calibration mode You can also use the Test mode to generate five different outputs which can be switched in sequence using the push button See the section Using the Eco Line Signal Converter as a Preset Signal Source 4 If you order our USB configuration adaptor you can install the internal CN2 link and then get various information to a PC with a Terminal Emulation program there are freeware versions around At some point we will provide a way read from and write to multiple devices using RS232 RS485 USB or Ethernet If you are setting several units it may be easiest to use our auxiliary Push Button switch which you can insert next to DIP m g switch SW1 this makes it a bit easier to work with the DIP switches while setting up A small flat screw driver is also useful if you are using the zero and span trimpots Filename Filename Eco Line Signal Converters User Manual docx 26 October 2014 Version 1 16 danntech PROCESS INSTRUMENTATION Page 20 of 22 Specifications 1 Standard inputs DIP switch selectable 4 20 mA 0 20 mA 0 100 mV 0 1 V 0 10 V 0 100 V 1 V 10 V others possible 2 Standard outputs DIP switch select
24. til green LED stops flashing and stays on then release button Output Calibration Activation Source Select OFF Input is selected as the output activation source oe Filename Filename Eco Line a e a a ao e ee Converters User Manual docx 26 October 2014 Version 1 16 edanntech PROCESS INSTRUMENTATION Page 14 of 22 ON Zero and Span trimpots selected as the output activation source for minimum and maximum output values Output Calibration Calibrates the output circuit to take into account any component tolerances for the input range selected and the output range required Uses the calibrate button to indicate the required output is present at the output You must follow the sequence and carry out both steps in order The output can be set using the input SW1 6 OFF or the values are set using the Zero and Span trimpots SW1 6 ON _ select output activation source Ain or trimpots Set input or Zero trimpot for the minimum output required press and hold button until green LED stops flashing and stays on then release button Set input or Span trimpot for the maximum output required press and hold button until green LED stops flashing and stays on then release button Test Built in test function which is activated by switching on SW1 8 with switches SW1 5 SW1 6 amp SW1 7 off In Test mode the output can be switched in sequence from following the input to minimum possible output value to
25. up the output switch SW1 switch 7 ON to select the Output Calibration mode switch 5 and 8 must be OFF 2 Set DIP SW1 switch 6 to choose your output control OFF uses the input ON uses the ZERO and SPAN trimpots ZERO for minimum output value SPAN for maximum output value this is recommended 3 Now using your Process Calibrator or the ZERO trimpot set the output to produce the minimum output value 1 V in this case 4 Now you need to press and hold in the Push Button you can do this from the front panel or by closing the PB link next to DIP switch SW1 Hold in the Push Button until the Red Configuration LED comes on 5 The Green Configuration LED as well as the Status LED will come on for about 1 second Filename Filename Eco Line Signal Converters User Manual docx 26 October 2014 Version 1 16 danntech PROCESS INSTRUMENTATION Page 6 of 22 to indicate that the minimum output value has been captured Release the button as soon as the RED Configuration LED comes on 6 Now using your Process Calibrator or the SPAN trimpot set the output to produce the maximum output value 5 V in this case 7 Again press and hold the Push Button as before to capture the maximum output value The internal processor has now recorded and saved these values to use forever Switch SW1 switch 7 and switch 6 if used off to complete the output calibration lt is not necessary to setup both the Input and Output you only need to s
26. with the following steps injecting minimum and maximum values 1 SW1 5 is used to activate input calibration mode SW1 6 7 amp 8 must all be off The green LED will flash twice every 2 seconds Inject the minimum input you require Press and hold the Push Button PB for a few seconds until the red LED flashes and the green LED stays on for approximately two seconds Release the Push Button as the red LED flashes this latches the input value as the minimum input calibration value The green LED will now flash as follows Inject the maximum value Press and hold the Push Button PB until the red LED flashes and the green LED stays on for approximately one second Release the Push Button as the red LED flashes this latches the input value as the maximum input calibration value The green LED will now flash as follows JL T Filename Filename Eco Line Signal Converters User Manual docx 26 October 2014 Version 1 16 danntech PROCESS INSTRUMENTATION Page 9 of 22 6 Switch SW1 5 off to complete input calibration process While doing the input calibration information can be observed using the RS232 jack socket connection This works at 9600 8 N 1 no flow control Without the link installed between CN2 programming header pins 1 amp 2 only the header line will be sent out this is the way it is delivered To see the internal values you must have this link installed Typically the info displayed will be Eco li