Home
SCS-SCS gateway
Contents
1. or several interfaces as applicable It is possible to select one of two modes using the Virtual Configurator application as indicated in the software User Manual pressing the interface pushbutton for at least 2 seconds Any other interfaces in MOD 6 installed in the system will automatically acquire the configuration of the devices Before performing this operation check that all system interfaces and actuators have their addresses configured MN 2 0870018 YMN 2 0820014 7 Use of interfaces with different modes For home automation systems of a certain complexity several systems may be integrated with interfaces configured in different modes For example it is possible to create a system with three interfaces for the connection of two Automation systems and one Burglar alarm system to one single riser Example N 1 Gi F422 If necessary each of these can be expanded physical expansion mode or interfaced with the Video Door Entry System or the Sound System using other interfaces For example in case of a villa consisting of several large floors U T 230 Vac o OUT OO OUT c Mh OOOO h OOOO fr 7 4 c E WOO 2 IN Example no 2 system with logic expansion A PL 01 gt
2. sections individually powered The scenario module the memory module the IR emitter for the control of air conditioning units and the devices that can be configured in self learning mode must be installed on the BUS section corresponding to the own local address e g if the scenario module is configured as A 0 PL 1 it will have to be placed on system no 1 see system example The web server and the scenario programmer must be installed on the BUS line with the lowest addresses system 1 in the drawing All the control devices configured to send Point point Room Group and General controls can be connected on either branch of the system 1 or 2 regardless of their addresses in A and PL positions This is also true in the case of actuators configured in the slave operating mode Interface item F422 allows the transit between the various systems of the Point Point Group Room and General controls As an example install a control configured with A 1 and PL 5 in system 2 to control actuator A 1 and PL 5 installed in system 1 Within the system no device must be configured with the same address as the interface 2 Logic expansion operating mode MOD 2 configurator This mode enables separation of control systems with each of them therefore capable of using all the addresses available It is therefore possible to connect several systems to an automation BUS with each system having all t
3. 31 la OUT Wy uy uy ya Main riser A PL 33 gt 53 1b OUT O DUT hi hk iB 23 or MOD 1 IN 8 OUT A PL 55 gt 175 1c OUT 22 OUT MM 2 prsg 4 4 MOD 1 IN Wey uy ey fu F422 yN 2 087z0014 MN 2 0820014 Example no 3 system without logic expansion A PL 33 53 OUT Wy yal yt Slr eti A PL 01 31 la 22 OUT O e zZ etcma Scs Fag OOO OOO OUT 1b A PL 55 gt 175 1c sljal A OUT Wy uy yt F422
4. SCS SCS gateway Description The SCS SCS gateway is an interface that provides communication among BUS systems with SCS technology even if they perform different functions The interface has two BUS clamps IN and OUT On the front is a C key for virtual configuration and a LED for the notification of correct power supply and configuration ON steady BUS not detected OFF configuration not detected or incorrect configuration flashing The device may operate in six different modes Physical expansion for MY HOME and Lightingh Management can increase the total BUS length or exceed the absorption limit of 1200 mA for the individual power supply Logical expansion for MY HOME can increase the number of devices of a system which is 175 max 11 in rooms defined with A 0 to 10 and 16 light points with PL 0 to 15 Address A 0 PL 0 is not permitted Burglar alarm automation interface for MY HOME it allows communication between these two systems Public riser it provides alarm event supervision for the common parts of the video door entry system Galvanic separation for MY HOME can interface two different functions ex Sound system with Automation Separazione fisica raggruppa le caratteristiche della modalita Espansione fisica e della modalita Separazione galvanica Utilizzabile per impianti con dispositivi predisposti per la configurazione virtuale NOTE regardless of the interface mode of use i
5. connected to the main riser must be connected to the OUT clamp of the interface The main riser must consist of an Automation system in which in addition to the corresponding control devices and actuators it will also be possible to install the Energy management central unit temperature central unit and the MH200N scenario programmer In this mode up to nine interfaces may be connected to the main riser it is possible to manage up to ten systems as if they were a single one Each system connected to the riser can have all 81 addresses allowed The web server and the scenario programmer must be installed on the BUS line with the lowest addresses system 1 in the drawing From the main riser IN clamp arrive the general controls rolling shutters and lights group controls this allows a minimum centralisation of the controls using standard devices of the control system and power management controls to allow positioning of the power management central unit on the riser On the other hand point point controls are stopped by the interface and therefore remain inside the individual system including the riser The controls of all systems other than automation including AUXILIARY controls travel in the two directions without any processing In order to send controls from one system to the other the special controls H4651M2 14651M2 and AM5831M2 may be used in extended control mode The interface address cannot be the
6. he 175 addresses available The BUS to which all others are connected therefore operates as main riser This BUS must necessarily belong to an automation system It is recommended that this mode is used for systems installed in large villas or in the service industrial sector Installation example A PL 01 99 BO OUT etcma ISCS F2 OO OO OO OO z F422 A typical example may be a large villa on several floors A system may be installed for each floor all connected to each other through another system operating as a riser The positions identified with 11 12 and 13 must not be configured while in the 14 position the address of the interface 14 from 1 to 9 connected to the riser must be configured 1 A PL 01 gt 99 2 A PL 01 gt 99 3 EEEE loccoad DE D E OUT OUT A l IEE 2 2 B B 141 4 2 5 MOD 2 MOD 2 7 IN IN Main riser Note maximum number of addresses available with physical configuration Maximum 175 addresses may be managed with virtual configuration Installation rules Configure 14 to give a number from 1 to 9 to the Buses connected to the riser 11 I2 and 13 must not be configured The BUS of the individual system
7. independent power supplies F422 Installation rules Each individual system connected to the IN or OUT clamps of the interface must be powered by its own power supply Itis possible to use up to 4 interfaces in MOD 6 for the connection of the Automation and or Energy Management and Temperature Control systems to each other n case of cascade connection of several Automation and or Energy management and Temperature Control systems each individual system must be connected to the OUT clamp of one interface and the IN clamp of the other Therefore do no connect the system to the two interfaces only using the OUT clamps Do not configure positions 11 and 12 In positions 13 and 14 address 13 0 to 9 and 14 1 to 9 of the interface must be specified This address may also correspond to that of other actuator devices installed in the connected systems If several interfaces are installed these must have different addresses The interface does not use any addresses of the Automation system The scenario module and the devices that can be configured in self learning mode can be connected to any branch of the system no 1 or no 2 The memory module must be connected to the system connected to the OUT clamp of the last interface All control devices configure for sending Point point Room Group and General controls may be connected to any branch of the system no 1 or no 2 without limita
8. input BUS IN the addresses must go from A 0 PL 1 and A 3 PL 1 On the output BUS OUT the addresses must be beween A 3 PL 3 and A 9 PL 9 or the address of the next interface As it can be seen from the example all the automation BUS 1 addresses are lower than that of the interface while all the automation BUS 2 addresses are higher the interface address therefore separates all the addresses of which the complete system might be made up of into two or more blocks MN 2 0870018 MN 2 0820014 Installation example APL 33 53 F422 2 APL 78 gt 175 4 Wy uy uy fu Jnlwli Wyn yu pu fu slul APL 01 31 1 APL 55 76 Note maximum number of addresses available with virtual configuration of the devices Installation rules Configure both 13 and 14 with configurators from 1 to 9 to set the separation between the two BUSES 11 and 12 must not be configured If several interfaces are installed in series the addresses of the devices between one interface and the other must be within those of the two interfaces see system example In this mode it is not possible to install two interfaces in parallel on the same BUS It is possible to install up to four interfaces in series which subdivide the system in 5 separate
9. not use any addresses of the Automation system F422 5 Operating mode Galvanic separation configurator MOD no configuration This configuration enables keeping the power supplies of the two buses separate allowing interfacing of different MY HOME functions e g sound system and automation In some cases the use of this interface is necessary for example when the sound system is installed In other cases installation alternatives are possible for example it will be possible but not compulsory to install Temperature Control on a separate BUS and interface it with Automation using an interface in Galvanic Separation mode The positions identified with 11 12 and 13 must not be configured while in the 14 position the address of the interface 14 from 1 to 9 must be configured Installation example o OUT Qe OUT o l QQQ 2 OOOO B IN 4 1 olr Ino gl Installation rules Configure 14 with configurators from 1 to 9 11 I2 and 3 must not be configured The Automation BUS must be connected to the IN clamp The other systems must be connected to the OUT clamp e g Sound System Itis not possible to connect several Automation systems to the same Sound System Thanks to this mode using the Web Server A V it is possible to control a one family system a video door entry system and an Automation system at the most subdivided i
10. nto lines following the physical and or logic expansion mode procedure The interface does not use any addresses of the Automation system M0 2 0820018 YMN 2 0820014 6 Physical separation mode MOD 6 configurator This mode brings together the features of the physical expansion mode and the galvanic separation mode Each system may be connected to both the OUT and the IN clamps of the interface and differently from what is required for physical expansion MOD 1 the addresses of the devices of the two systems may be selected freely F422 In view of the above it will no longer be necessary to indicate the system separation address in positions 13 and 14 therefore the interface will have to be configured by assigning any address from 01 to 99 including any address already used by actuator devices installed in the connected systems If several interfaces are used these must have different addresses A PL 15 A PL 26 A PL 48 A PL 27 A PL 35 A PL 78 OUT OUT ila DO OUT OUT M gt c fi OOOO R BE OOOO R z 4 1 2 4 2 MOD 6 MOD 6 IN IN A PL 11 A PL 35 A PL 62 The use of the interface with this mode may be useful to keep the Automation system and the Temperature control system separate for example when using
11. ry channels these must be connected to the IN clamp of interface item F422 Use a free address of the video handset 4 Interface between burglar alarm and automation video door entry system sound system mode MOD 4 configurator This mode can be used to interface the Automation system to the burglar alarm system to facilitate interaction and exchange of information between the two BUS Thanks to this function it is possible to remotely control the automation system using the telephone communicator The positions identified with 11 12 and 13 must not be configured while in the 14 position the address of the interface 14 from 1 to 9 must be configured Installation example o OUT 22 OUT F 1 OOOO R OOOO B IN 4 1 Installation rules Configure 14 with configurators from 1 to 9 11 I2 and 13 must not be configured The BUS of the Burglar Alarm system must be connected to the OUT clamp of the interface Itis not possible to connect other interfaces to the Burglar Alarm system to physically extend the BUS or to increase the maximum number of devices Only one interface may be connected to the Burglar Alarm system It is therefore not possible to connect together two Automation systems through the Burglar Alarm system Installation of the Automation system actuators within the Burglar Alarm system is not allowed The interface does
12. same as that of other devices e g configure the interface 11 12 13 4 1 and MOD 2 if a scenario module is configured with A and PL 1 MN 2 0870018 MN 2 0820014 F422 3 Burglar alarm automation interface mode MOD 3 configurator This mode is indicated when display of burglar alarms and technical alarms are required generated within the common sections using a switchboard item 346310 installed on the backbone or the riser of the video door entry system Simple diagram for the display of alarms on common parts Riser 1 Riser 2 Riser 3 OUT o N e eke m e E Mi ba en mine cen l I OUT imi l re l l I Il l ee 1 l OUT nn 11 pS l l Ei l l I l ooo l I c B se imi oo l l 0000 4 _ 11 ooo EH l i Q000 MOD 3 it 000 i I 2e EKE I I I I S keza ll l l Io l i l Forthe electric diagram see the switchboard I 1 Common system section 1 i technical sheet l Installation rules On the common sections it is possible to connect contact interfaces or technical alarms gas water leak up to a total of 9 auxilia
13. t must be taken into account that the two Buses connected constitute at all effects two systems and as such they must be subjected to all existing sizing and installation rules Technical data Power supply from SCS BUS 27 Vdc Operating power supply with SCS BUS 18 27 Vdc IN clamp absorption 25mA OUT clamp absorption 5mA Dissipated power with max load 1W Dimensional data Size 2 DIN modules Configuration 1000 11 12 13 14 MOD 0000 Sockets 11 12 13 and 14 are used to uniquely identify using numerical configurators the addresses of the interfaces inside the system The interface may also be configured using the Virtual Configuration application as indicated in the software User Manual 1 Operating mode Physical expansion configurare MOD 1 With the interface configured in this mode it will be possible to extend the physical limit of the maximum length of the BUS or exceed the limit of 1200 mA delivered by the individual power supply but not the maximum number of actuators max 175 The positions identified with 11 and 12 must not be configured The separation address between the two buses connected to the interface must instead be defined in positions 13 and 14 Supposing as in the example that 13 3 14 2 1 F422 Legend Configurator socket BUS Signalling LED Pushbutton for virtual configuration OUT clamp WE e e On the
14. tion irrespective of their respective addresses in the A and PL positions The above also applies to actuators configured in slave operating mode Interface f422 allows Point point Group Room and General controls to travel through the various systems It is therefore possible to install for example in system no 2 a control configured as A 1 and PL 5 that will control actuator A 1 and PL 5 installed in system no 1 Configuration For correct operation the interface must be configured to define its address within the system acquire the address of the devices of the systems connected to the IN and OUT clamps Configuration of the interface address The device may be configured in 3 different modes using numerical configurators 0 to 9 in positions 13 and 14 using the Virtual Configurator application as indicated in the software User Manual using the self configuration procedure as indicated below 1 press the interface pushbutton for a few instants the LED flashes slowly 2 press the pushbutton again the LED flashes quickly and the device starts the self configuration procedure 3 Once the configuration procedure has been completed correctly the LED comes on steady Repeat this operation for all the interfaces in MOD 6 of the system Acquisition of the addresses of the connected devices This procedure must only be carried out after the configuration of the interface address
Download Pdf Manuals
Related Search
Related Contents
フルパワ 一 軽量リングトランス Maya Rendering: Troubleshooting User's Manual データシート - Elcometer Dynacord LittleMax1 User's Manual StrongHold User Manual Telegärtner MP8 FS 500 LSZH 0.25m [ 富士ドライケムスライド Hb-WII ] ≫PDF Danby SBWC033A1S User's Manual Apple Loops Utility 3 User Manual (en) Copyright © All rights reserved.
Failed to retrieve file