Single Zone VAV Systems

image

Contents

1. K 12 classrooms Retail Stores Slide 5 Potential Benefits of SZVAV e Potential Benefits e Lower Energy Use e Better Dehumidification at Part Load e Less Fan Generated noise 2014 Trane a business of Ingersoll Rand All rights reserved TRACE 700 Single Zone VAV Systems Traditionally the system has been found in larger rooftops and air handlers used to serve large densely occupied zones that have variable cooling loads such as gymnasiums and auditoriums However smaller rooftops air handlers and terminal units like blower coils and water source heat pumps have been designed with variable speed supply fans and necessary controls so single zone VAV is starting to be used in many different space types Compared to a constant volume system some of the potential benefits of using a Single Zone VAV system include lower energy use better dehumidification at part load and less fan generated noise Of course the extent of these benefits will depend on the climate building layout and operating hours of the specific building Since the fan is able to modulate airflow to the space during part load conditions there can be considerable fan energy savings However it is important to look at the application to determine expected savings For instance if a space consistently has high internal loads the system will be running more hours in cooling mode with higher airflow and probably see less energy savings than if th
2. will gradually be reset upward to avoid overcooling the zone At some point no mechanical cooling is needed to maintain temperature When this happens the compressors turn off and the zone temperature is allowed to float within the set deadband If the zone temperature falls below the heating temperature set point the zone will demand heating When there is a demand for heating the supply airflow will remain at the min stop and the supply air temperature is increased If the supply air temperature reaches a maximum temperature limit the supply airflow is increased to match space load until heating design supply conditions are met left hand side of the chart So let s talk about how to model this system in TRACE 700 By default TRACE sets the min stop at 30 of the design supply airflow This value can be overridden to meet requirements for your system To change the minimum cooling airflow go to the Create Rooms screen and select the Airflows Tab Under VAV control set the cooling VAV min to the desired value The heating VAV max control is the maximum airflow that can be supplied during heating mode once the maximum supply temperature has been reached By default if this field is left blank it is set equal to the cooling min airflow Trane C D S eLearning Series Slide 8 How to model SZVAV in TRACE 700 Create Systems Eo 1 Select Single Zone Variable Volume system ii 2 Temp Humidity tab By default Su
3. Trane C D S eLearning Series Slide 1 Q ma TRACE 700 Slide 2 T Learning objectives e What is Single Zone VAV SZVAV e Basic calculation methodology e How to model SZVAV in TRACE 700 e Classroom example of SZVAV Slide 3 Simple Single Zone VAV System Supply airflow modulated based on loads in zone Controller Space Varies cooling heating capacity to Coils and fan maintain supply air temperature at serve a single zone set point 2014 Trane a business of Ingersoll Rand All rights reserved TRACE 700 Single Zone VAV Systems Hello my name is Audra Benzschawel and am a Marketing Engineer in the C D S group at Trane Today am going to talk about Single Zone VAV in TRACE 700 We will start with today on what is single zone VAV basic calculation methodology how to model it in TRACE and then finish it off with a classroom example with setting up the system Single Zone VAV consists of a variable volume fan cooling coil and heating coil that typically serve a single zone In this system a single zone sensor is used to directly vary the supply fan Like a traditional multiple zone VAV system the cooling capacity is varied to maintain the discharge air temperature Because only one zone is served no VAV boxes are needed Trane C D S eLearning Series Slide 4 Typical SZVAV Applications Large densely occupied zones with variable cooling loads Gymnasiums auditoriums etc
4. ber the Single Zone VAV system has a zone level coil so it very important to use the Zone Checksums report since not all zones will necessarily peak at the same time The System Component Selection Report is extremely useful for sizing equipment It is important to remember that the system will not necessarily be sized differently than a constant volume system The true benefit of Single Zone VAV will be seen in the energy analysis results Having a comparison between the SZVAV and CV system and looking at the Equipment Energy Consumption Report will show the real benefit of the system 2014 Trane a business of Ingersoll Rand All rights reserved Trane C D S eLearning Series ide 11 M aag Additional resources PDF of this presentation TRACE 700 User s Manual Online F1 help Trane Engineers Newsletter Understanding Single Zone VAV Systems vol 42 2 Engineers Newsletter Live program Single Zone VAV Systems www trane com ContinuingEducation Slide 12 contact us phone 608 787 3926 fax 608 787 3005 email cdshelp trane com Web www tranecds com 2014 Trane a business of Ingersoll Rand All rights reserved TRACE 700 Single Zone VAV Systems Additional resources can be found in the CDS Help eLibrary including links to Engineers Newsletter article and an on demand program on Single zone VAV systems Thanks and hope you enjoyed this presentation Good luck modeling
5. e system operates more hours in heating mode with lower airflow Dehumidification is better at part load conditions because even at part load the system will always supply the same cool dry air It is the amount of air supplied to the zone that is modulated Just like in a traditional VAV system Less noise is generated by the fan when operating at part load conditions The actual sound level depends on specifics of the fan but in general when the fan is operating at a slower speed the noise level also decreases Trane C D S eLearning Series Slide 6 Slide 7 Modeling SZVAV in TRACE 700 Creates Rooms 1 Airflows Tab e By default e Min Cooling Airflow set 30 of supply airflow Ba m e Max Heating Airflow Min Cooling Airflow a pre To change min stop e Adjust Clg VAV min and Htg VAV max 2014 Trane a business of Ingersoll Rand All rights reserved TRACE 700 Single Zone VAV Systems When the zone is at the design sensible cooling load right hand side of chart the system delivers 100 supply airflow to the zone at the design supply air temperature for cooling As the load in the zone decreases the supply airflow is decreased to maintain the room temperature set point Eventually the load decreases to the point where minimum airflow limit or min stop is reached typically 30 of the design supply airflow If the load continues to decrease after reaching min stop the supply air temperature
6. library Okay now let s walk through setting up the system We will use a School example set up using the New File Wizard All default inputs will be used Trane C D S eLearning Series TRACE 700 Single Zone VAV Systems Slide 10 So we already created this building using the new file wizard E gt We first need to go into the templates and verify SCREENCAST the correct Clg VAV min and Htg VAV max is Jeee ee being applied In this case we will leave those te fields set to the default values of 30 When setting these values it is important to remember that all rooms applied to the same system should have the same min stop values Any changes made in the templates will filter down into the Rooms Now we will take a look at the systems We can go ahead and select the Single Zone Variable Air Volume system type from the list in the selection tab Next we move on to the Temp Humidity tab Again we will leave the Cooling Supply Design Temperature alone and allow TRACE to calculate the supply temperature Before we leave the Create Systems we need to select the Fan On the Fans tab we will select the 90 1 07 Min VAV FC Centrifugal fan for the Primary Fan type and use a Static pressure of 2 in wg We then have to assign our rooms to the system and then we can calculate the file Two useful reports for SZVAV will be the Zone Checksums and System Component Selection Reports Remem
7. pply Air Temperature set 55 degrees e To change specify a Min Max Cooling supply temp 3 Fans tab Select a VAV fan for primary fan Assign Rooms to Zone 1 Apply proper zoning rules to drag and drop room onto the system Slide 9 Classroom Load Example H at 1 stories 30 glass 100 ft x 100 ft per floor area 12 foot floor to floor height 3 ft plenum height perimeter depth of 15 feet Single Zone VAV 2014 Trane a business of Ingersoll Rand All rights reserved TRACE 700 Single Zone VAV Systems Next enter the Create Systems section and select Single Zone Variable Air Volume system type found under Variable Volume Category Next move over to the Temp Humidity tab If the Design Cooling Supply Air Temperature is left blank TRACE will calculate the supply air temperature psychrometrically to satisfy the room conditions For system design it is best to allow TRACE to calculate this value however if working with an existing system or if this temperature specified the values can be defined in these fields To specify the cooling supply air temperature enter Create Systems and select Temp Humidity Tab Finally on the Fans tab select a VAV fan for the Primary Fan and enter a Static Pressure and full load energy consumption rate Once the system is created continue on to Assign Rooms to Zone section For information how to appropriately set up zoning see Room and Zone Assignment video in the eLearning