VACON NX QUICK HELP Start-up wizard

image

Contents

1. Input line supervision 11 Output phase supervision 12 Brake chopper supervision 13 Frequency converter under temperature 14 Frequency converter overtemperature 15 Motor stalled 16 Motor overtemperature 17 Motor underload 22 EEPROM checksum fault 24 Counter fault NOTE Different All in One applications 25 Microprocessor watchdog fault embody more monitoring values 26 Start up prevented 29 Thermistor fault IGBT temperature hardware Fan cooling CAN bus communication Control unit Device change Device added Device removed Device unknown 41 IGBT temperature 42 Brake resistor overtemperature Encoder fault Device change default param Device added default param 50 Analogue input lin lt 4mA selected signal range 4 20 mA 51 External fault 52 Keypad communication fault 53 Fieldbus fault 54 Slot fault 56 PT100 temperature fault Multimonitoring items Actual value special display The Actual value special display parameters are used to convert and display the actual value signal in a form more informative to the user The Actual value special display parameters are available in P D Control Application and Pump and Fan Control Application ParID Parameter name Parameter code in Parameter code in PID ctrl applic Pump amp Fan ctrl applic ID1033 Actual value special display minimum 2 2 46 2 9 29 ID1034 Actual value
2. VACON NX QUICK HELP Start up wizard The Start Up Wizard is activated when the power to the drive is turned on for the first time or if the Start Up Wizard is activated from the System menu P6 5 3 AND the power is turned OFF and back ON The Start up Wizard is a feature on the control keypad to facilitate the commissioning of the fre quency converter If selected active default the Start up Wizard prompts the operator for the lan guage and application of his her choice plus for the values for a set of parameters common to all applications as well as for a set of application dependent parameters Always accept the value with the Enter button scroll options or change values with the Browser buttons up and down arrows More information on the use of the control panel in Chapter 7 of the User s Manual Startup wizard Press enter Language English Application Standard Setup starts Press enter Repeat setup lt No Yes gt Min Frequency 0 00 Hz Monitoring values Faults and fault codes Signal name Output frequency Frequency reference Motor speed Motor current Motor torque Motor power Motor voltage DC link voltage Unit temperature Motor temperature Voltage input Current input DIN1 DIN2 DIN3 DIN4 DIN5 DIN DO1 RO1 RO2 Analogue output current Overcurrent Overvoltage Charging switch Emergency stop Saturation trip System fault 9 Undervoltage 10
3. ontrol place by keeping the D pushed down for 3 seconds when the motor is running The keypad will become the active control place and the current frequency reference and direction will be copied to the keypad Select the keypad as the active control place by keeping the e button pushed down for 3 seconds when the motor is stopped The keypad will become the active control place and the current frequency reference and direction will be copied to the keypad Copy the frequency reference set elsewhere 1 0 fieldbus to the panel by keeping the button pushed down for 3 seconds Note that if you are in any other than M3 menu these functions will not work If you are in some other than M3 menu and try to start the motor by pressing the START button when the keypad is not selected as the active control place you will get an error message Keypad Control NOT ACTIVE NOTE 2 By default the motor can be stopped at all times by pushing the e button regardless of the selected control place This default setting can be inactivated by giving parameter Stop Button Activated P3 4 or P3 6 menu M3 the value 0 With this value given to the parameter pushing the STOP button stops the motor only when the keypad has been selected as the active control place
4. special display maximum 2 2 47 2 9 30 ID1035 Actual value special display decimals 2 2 48 2 9 31 ID1036 Actual value special display unit 2 2 49 2 9 32 Example The actual value signal sent from a sensor in mA represents the amount of waste water pumped from a tank per second The signal range is 0 4 20mA Instead of receiving the level of the actual value signal in mA on the display you wish to receive the amount of water pumped in m s You then set a value for par ID1033 to correspond to the minimum signal level 0 4 mA and another value for par ID1034 to correspond to the maximum signal level 20 mA The number of decimals needed can be set with par ID1035 and the unit m s with par ID1036 The level of the actual value signal is then scaled between the set min and max values and displayed in the selected unit The following units can be selected par ID1034 0 NotUsed Lo 1 A O o 2 Pp 3 m a E 48 ee pw Sms m3 min NOTE The maximum number of characters that can be shown on keypad is 4 This means that in p qe F 18 gal s 19 gal min some cases the display of the unit on the keypad does not comply with the standards Selection of language Find the System Menu M6 Enter the Language selection page S6 f Push the Menu button rightto make the name of language blink Browse through the languages with the Browser buttons and select ano
5. ther language with the Enter button foe Donc For closer information on language selection see Chapter 7 3 6 READY PREADY Mc ED se Gb System Menu Language gt 19S11 English REA o5 GE Language English Selection of application Find the System Menu M6 Enter the Application selection page S6 2 Push the Menu button rightto make the name of application blink Browse through the applications with the Browser buttons and select another application with the Enter button Feba ma For closer information on application change see Chapter 7 3 6 stop READY M5 o5 GE System Menu Application 19S11 Standard cD Shc Gp Application Application Standard Multi step Control panel menus Za dc c1 D i Expander boards A NXOPTA1 G129G5 gt G1236G1 Mo m Sh Gm Change System Menu p Language value 912959 English READY wo m HG m Fault history lt p gt 11 Output phase H12H3 aad qa M4 dms Active faults FO Cr M3 m PI ip Keypad control lt P gt Control Place P19P3 gt I O Terminal n READY READY wo dw t X75 Pe LET Parameters Basic parameters Min Frequency G13G9 P19P15 13 95 Hz A Browse Change value DA DA Mi ui G5 Monitor p Output frequency No editing V12V15 13 95 Hz NOTE There are some special functions that can be performed when in the M3 menu Select the keypad as the active c