1. meters Temperature sensing range 0 55 C Resolutions 1 V for voltage 0 1 A for Current amp 0 1 degree C for Temperature Auto Controller Bypass Switch is used to bypass the controller i e A C 1 amp A C 2 will remains ON irrespective of temperature demands if both switches are in ON condition Indications a Supply ON for A C 1 amp A C 2 Colour Yellow b Auto Mode for A C 1 amp A C 2 Colour Green c Manual Mode for A C 1 amp A C 2 Colour Red d A C 1 amp A C 2 ON Colour Green e A C 1 amp A C 2 Fault Colour Red f Room High Colour Red g Healthy Colour Green Keys four keys for parameter settings a SET Key To enter into SET Mode To View next set point b UP Arrow Key To increment the set point To view next menu To view next set point in the menu c Down Arrow Key To decrement the set point To view previous menu To view previous set point in the menu d Enter Key To come out of SE mode To enter into menu To accept the password Mounting Wall mounting Size 230 mm H X 225 mm W X 100 mm D Sr Modes Description No 1 Run Mode Sr no_ Display Message Description 1 t C Room Temperature 2 VoL1 AC 1 Voltage 3 VoL2 AC 2 Voltage 4 Curi AC 1 Current 5 Cur2 AC 2 Current 6 bAL Balance Cycle Time 7 Hr 1 AC1 Hour 8 Hr 2 AC2 Hour 9 r Hi High Temperature Alarm 10 oV 1 AC 1 O
2. 93 4 rSet Factory set 9992 User settable default 9992 SET Menu To display SET Menu parameter press SET Key display will show the message Set Mod amp then display Set then press ENTER key controller will ask for password by showing Message Entr PASS amp then display 0000 Now enter password with the help of arrow keys amp press ENTER key If the password is correct controller show message PASS Corr amp will show the set point Now user can view change Set menu set points by pressing SET key again amp again to see next parameters If password not correct controller show error message Sr Display Description No Set point Message 1 AC 1 AC1 cut in set point on Default value 23 0 C Range 20 0 C to 40 0 C 2 AC 1 AC1 cut off set point OFF Default value 3 0 C Range 20 0 C to 40 0 C 3 AC 2 AC2 cut in set point on Default value 24 0 C Range 20 0 C to 40 0 C 4 AC 2 AC2 cut off set point OFF Default value 3 0 C Range 20 0 C to 40 0 C 5 r Hi Room High cut in set point on Default value 25 0 C Range 25 0 C to 37 0 C 6 r Hi Room High cut in set point OFF Default value 25 0 C Range 25 0 C to 37 0 C 7 uVSt Under Voltage set point Default value 160V Range 100 to 200V ON Hysteresis 10V 8 oVSt Over Voltage set point Default value 270 V Range 240 to 300 V ON Hysteresis 10V 9 uLSt Under Load set point Default v
3. I wae VAC ASPI FF c No aas AIC2 SUPPLY 230 VAC AIC FAIL ALARM ROOM HIGH ALARM
4. USER MANUAL PROTON POWER CONTROL PVT LTD PUNE ONS ooN 11 12 13 14 15 16 17 DUAL A C CONTROLLER m O Salient Features Controls Two Air Conditioners Separate Phase Supply for each AC Bright RED 4 digit LED Display Accurate Temperature sensing by precise temperature sensor Time sharing for Compressors to share load equally Voltage amp Current Protections for each compressor Separate alarm relay contacts for AC Fail Separate alarm relay contacts for Room High Hour counters for Compressor ON period to check its reliability Display of all the A C Parameters amp fault messages if any fault present in a scrolling on display Display Hold feature by using ENTER Key Press it again to release the hold Various set points are settable through the following menus a SET b DLAY c OFST d RSET Password Protection for all the settings Cyclic ON amp Operations of both ACs on Sensor fail mode Auto with all protections manual without protection Modes Controller Bypass features by provision of switch on front panel LED Indications to observe the status Technical Specifications Supply Voltage 230 V AC 50 Hz 15 separate for each A C Contact rating 30 A at 230 V AC for compressor Live Outputs amp 5 A at 250 V AC Alarm Potential free outputs C N O Temperature Sensor Thermistor sensor NTC 10K 25 C metal body with clamp Sensor cable length 2 75
5. alue 3 0 A Range 0 8 to 3 0 A 10 oLSt Over Load set point Default value 15 0 A Range 12 0 to 30 0 A 11 AC1 AC1 Auto Manual Selection Default Auto Auto AC1 have all protection Man AC1 Protections Bypass 12 AC2 AC2 Auto Manual Selection Default Auto Auto AC2 have all protection Man AC2 Protections Bypass 13 AC SeL Machine selection i e Window Win Split Default Window AC Selected For Window AC Selection AC1 amp AC2 restart delays are 180 amp 190 Seconds respectively For Split AC Selection AC1 amp AC2 restart delays are 5 amp 10 Seconds respectively 14 SET Default 9995 PASS Range 0000 to 9999 dLAY Menu To enter into Delay menu the password selection process is same for all menu as mention in SET Menu Sr Display Description No Message 1 CYCL Cycle time to swap AC1 amp AC2 Temperature set point Default 360 minutes Range 5 to 9995 Minutes 2 InTr Inter AC ON Delay ACon Default 10 Seconds Range 2 to 300 Seconds 3 oV Over Voltage trip delay triP Default 5 Sec Range 3 to 180 Seconds 4 uV Under Voltage trip delay triP Default 5 Sec Range 3 to 180 Seconds 5 oL Over Load trip delay triP Default 5 Sec Range 3 to 180 Seconds 6 uL Under Load trip delay triP Default 300 Sec Range 10 to 180 Seconds 7 SnFL AC Sensor fail ON delay on Default 60 Minutes Range 5 to 995 minutes 8 SnFL AC Sensor fail Off delay off Default 15 Minutes Range 5 to 995 minutes 9 dLAY D
6. efault 9994 Range 0000 to PASS 9999 ofSt Menu To enter into Offset menu the password selection process is same for all menu as mention in SET Menu Sr Display Description No Message 1 V1 P AC1 Voltage Offset Default OV Range 0 to 50 V 2 V1 AC1 Voltage Offset Default 0 V Range 0 to 50 V 3 V2 P AC2 Voltage Offset USER MANUAL PROTON POWER CONTROL PVT LTD PUNE Default OV Range 0 to 50 V AC2 Voltage Offset Default 0 V Range 0 to 50 V Working Sr Description No AC1 Current Offset Default 0 0 A Range 0 0 to5 0A AT AC1 Current Offset Default 0 0 A Range 0 0 to5 0A 1 After power ON delay over if room temperature demands with respective to AC1 ON set point amp Ac2 ON set point AC 1 amp AC2 will be ON Which of the AC becomes ON first after Inter AC ON delay over other AC will be allowed to ON A2 P AC2 Current Offset Default 0 0 A Range 0 0 to5 0A 2 AC 1 will be ON after its ON Delay of 180 s for window AC amp 5 sec for split AC AC2 Current Offset Default 0 0 A Range 0 0 to5 0A 3 AC 2 will be ON after its ON Delay of 190 sec Inter AC ON delay 10 sec for window AC amp 10 sec Inter AC ON delay 10 sec for split AC 4 If Room temperature decreases below AC1 ON set point AC1 OFF set point AC1 will be OFF Room Temperature Offset Default 0 0 C Range 0 0 to 5 0 C 5 If Room tem
7. perature decreases below AC2 ON set point AC2 OFF set point AC2 will be OFF 10 Room Temperature Offset Default 0 0 C Range 0 0 to 5 0 C 6 AC 1 amp AC 2 set point will get interchanged after cycle time for the purpose of load sharing 11 oFSt PASS Default 9993 Range 0000 to 9999 7 If any fault occurs to one machine there will be cycle changeover if that machine AC ON set point is lower than other So now other machine will operate with full load rSet Menu To enter into Reset menu the password selection process is same for all menu as mention in SET Menu 8 All faults are auto reset fault 9 After temperature cut in fault recovery AC will be ON after their restart delays Sr No Display Message Description 10 In Manual mode foe AC1 amp AC2 will not be protected by uv ov ul ol faults rSet FALt Reset AC1 amp AC2 Faults rSet HoUr Reset AC1 amp AC2 Hour 11 In sensor fail condition one of the AC will remain ON foe AC sensor fail ON time amp will remains OFF for AC sensor fail OFF Time TM ie S PROTON POWER CONTROL PVT LTD S NO 28 JAGTAP DAIRY PIMPLE NILAKH PUNE 411027 TEL 020 27270800 27276777 TEL FAX 020 27270100 MOBILE 9764885010 9422009655 E MAIL rdpawar protonpowercontrol com accounts protonpowercontrol com Terminal Layout act SUPPLY E 20vae TE AC
8. ver Voltage 11 oV 2 AC 2 Over Voltage 12 uV 1 AC 1 Under Voltage 13 uV 2 AC 2 Under Voltage 14 oL 1 AC 1 Over Load 15 oL 2 AC 2 Over Load 16 uL 1 AC 1 Under Load 17 uL 2 AC 2 Under Load 18 SnFL Sensor Fail 19 PFL1 AC 1 Power Fail 20 PFL2 AC 2 Power Fail 2 Key Operation Sr Display Message Description No 1 SET Key To enter into SET mode To save the changes 2 ENTER Key To save the changes amp to come out of SET Mode 3 UP Arrow Key To Increment the value 4 Down Arrow Key To Decrement the value USER MANUAL PROTON POWER CONTROL PVT LTD PUNE Sr Modes Description No 3 SET Mode User can view change the set point in this mode Sr Display Description no menu 1 Set User can view change the Temperature UV OV UL OL Auto set points amp AC selection i e Window Split 2 dLAY User can view change delay set point 3 ofSt User can view change the offset set points for AC1 AC2 voltages currents amp Room Temperature 4 rSet To reset the Faults Hours Counters Passwords User can enter into menus by entering the correct passwords Sr Display Password No Menu 1 Set Factory set 9995 User settable default 9995 2 dLAY Factory set 9994 User settable default 9994 3 ofSt Factory set 9993 User settable default 99