INSTALLATION MANUAL - Zeta Alarm Systems
Contents
1. amp Next Keys Options are Simplicity 126 Simplicity 64 Simplicity 252 Infinity ID2 2 Zone Infinity ID2 4 Zone Infinity ID2 6 Zone Infinity ID2 8 Zone Select repeater number with buttons 1 to 8 Each repeater on a system must have a different number 3 Activity Selects which commands the repeater will send to the main panel 1 Start sounders 2 Stop Sounders 3 Reset Panel 4 Silence All A means the option is selected If Silence all has a it will silence its own buzzer the panel s buzzer and any other repeaters connected If silence is not marked with a it will just silence it s own buzzer 7 GENERAL FAULT FINDING The Infinity ID2 repeater panel does not have any input or output circuits so any General faults reported should be investigated at the main panel There are 2 possible faults which can be generated by the repeater itself 7 1 Communication fault Communication fault means that the repeater cannot see the communications from the main panel The possible causes for this are Communication cable reverse polarity It should be connected A to A and B to B Communication cable loose connection or cable break Damaged repeater PCB Damaged panel PCB To check a PCB Disconnect the data cable Then check the DC voltage between B and A with a DVM It should be around 1 5V 7 2 System fault A system fault is an abnormal microprocessor running condition due to various unexpected phenomena This w
2. be in the language entered The repeater shows Alarms and faults from the fire panel It does not show disablements or test mode events The repeater can be configured to start panel sounders stop panel sounders Silence panel Buzzers and reset the panel The repeater can not interrogate panel configuration or device status The repeater can not select disablements or test mode 3 Repeater Access Levels The Infinity ID2 active repeater has the following access levels Access Level Access Available functions Code N A View panel indications Silence fault buzzer Scroll between multiple event messages 123 Start Alarm Sounders Evacuate Stop Alarm Sounders Reset panel 69 AL3 3 Select Repeater Panel Language Select Panel the repeater connects to Select Repeater Number Configure repeater response Start Sounders Stop Sounders Reset Panel Silence All Approved Document No GLT 221 7 1 Issue 1 0 Author NRPJ Date 29 11 2013 PAGE 4 INFINITY ID2 ACTIVE REPEATER MANUAL Software Versions 0 H 8682 4 MOUNTING THE FIRE ALARM PANEL The Infinity ID2 Active Repeater comes with many cable entry holes If another entry hole is required it is strongly recommended that the the termination PCBs should be removed and stored in a safe place This would also help while fixin the back box to the wall 4 1 FIXING THE BACK BOX TO THE WALL Figure 2 Plan view inside the enclosure without PCBs Side view for surface instal
3. main panel To do this enter the repeater setup Menu and select option 2 The menu gives 4 options Start sounders Stop sounders Reset panel amp silence All The currently selected options are marked with a Press the buttons 1 to 4 to toggle the required options on or off Eg to set a repeater so that it can stop sounders but not to start them or reset the system set as Each repeater could have different settings if required 5 3 Configuring the Repeater panel onto the Fire panel The ID2 panel configures the repeaters as part of the loop configuration routine If a repeater has been added or removed the loop should be relearned from the main panel 5 4 Check Software Version To view the software version of the repeater panel press the LED test button This needs to be done at access level 2 The screen will show the Type of panel the repeater is configured for and the software version Approved Document No GLT 221 7 1 Issue 1 0 Author NRPJ Date 29 11 2013 PAGE 7 INFINITY ID2 ACTIVE REPEATER MANUAL Software Versions 0 H 8682 6 Menu Structure To help locate the different features available the menu structure of the Infinity ID2 Active repeater panel is shown here MENU LAYOUT 1 Language Choose between English Spanish Portuguese French Italian Hungarian Serbian Lithuanian with prev amp next keys Press enter to select 2 Panel Type Select the panel this repeater is connected to with the Prev
4. INFINITY ID2 ACTIVE REPEATER MANUAL Software Versions 0 H 8682 INFINITY DZ ACTIVE REPEATER by GLT Exports Ltd MADE IN THE UK START STOP ZONAL INDICATIONS ACCESS SOUNDERS SOUNDERS S ON m E ZONE FIRE ZONE FIRE ZONE FIRE ZONE FIRE GHI JKL BUZZER PQRS TUV WXYZ al condition Pi Norm ower LED on Ee cone tong Fits LED on and zone red LED on ault condition Faul on Evacuation Enter code then paa start stop sounders CANCEL 0 ENTER LED TEST REFER TO MANUAL LCD REPEATER PANEL POWER FIRE FAULT SYS FLT INSTALLATION MANUAL yeta ea Approved Document No GLT 221 7 1 Issue 1 0 Author NRPJ Date 29 11 2013 PAGE 1 INFINITY ID2 ACTIVE REPEATER MANUAL Software Versions 0 H 8682 CONTENTS 1 GENERAL INFORIVIATION criniera eusaciateresidoeieeaane 3 Dd Safety IMMORAL OM scerna aea a EE 3 1 2 Product Disposal At The End Of Its Working Life acsee 3 L EAVronmental INTONMAtIO ass T 3 1A EQUIDIMERE Guarantee 6 wadicccicesidauin se nn AEREE 3 2 Overview of the Infinity ID2 Active Repeater ccccccceccescceseeeeeeseeseseesseees 4 3 Repeater Access Levels ciresarii a a aa E a N 4 4 MOUNTING THE FIRE ALARM PANEL ccccsecccsecescceneceseceenseenseenceeeeeeeuss 5 4 1 FIXING THE BACK BOX TO THE WALL ccccccceeseesseenseeneeeeectenseenseeneees 5 42 Repeater connecteren E A T 6 5 CONFIGURING INFINITY ID2 REPEATER ccccscccseccseceeeceeseceneceeeeeeecee
5. eeeens 7 5 1 Configuring the Language sicsicccsicvinscessdvanadinaiuscacaudeatedaleaabdsedeimaddevelvs tecee bandas 7 5 2 Configuring the Repeater Type and ID ccc cecceccesceeseeseeseecenseeeeeeseees 7 5 3 Configuring the Repeater Activity RESPONSE cecceeccesceeseeseeeeeesenseees 7 5 3 Configuring the Repeater panel onto the Fire panel ccccesceeseeeeees 7 5 4 Check SOTEWANE V CLS OI rane a r unedeseanaaseevanousiavan nidedasedas 7 IVI TILE SU A UNC ai snsaisica tive assoc eiee spd owe dante someirachiassinwanisted cesta to anedsacid posal ween E 8 7 GENERAL FAULT FINDING sinccdacetccasetesevestsenasatevavercBias A eaaaestoaa vente beeess 8 7 SCOMIMUMIC ATION Tates T 8 Toe SSC CMa WU a E E E E AEE 8 8 PCB TERMINATION CONNECTIONS cc ccccceccssecessccseceeecenecenseeeeeeeeeeeseens 9 I SPECIFICATIONS arrisera n N 10 JLENCIOSUreESpecNiCaHONS rearea EE EN 10 92 Electricals peccato S orioa E T 10 Approved Document No GLT 221 7 1 Issue 1 0 Author NRPJ Date 29 11 2013 PAGE 2 INFINITY ID2 ACTIVE REPEATER MANUAL Software Versions 0 H 8682 1 GENERAL INFORMATION 1 1 Safety Information Please consult the Infinity ID2 Installation manual for safety information relating to the ID2 System 1 2 Product Disposal At The End Of Its Working Life Like all electronic equipment at the end of its working life this unit should not be disposed of in a refuse bin It should be taken to a local reprocessin
6. g site as per the guidelines of the WEEE directive for correct disposal sd 1 3 Environmental Information It will operate in ambient temperatures of 5 to 40 C It will operate in a relative humidity of up to 95 non condensing It will withstand vibrations between 5 amp 150 Hz The repeater should be maintained as described in section 3 of the Infinity ID2 User Manual Maintenance Guide amp Log Book 1 4 Equipment Guarantee If this equipment is not fitted and commissioned according to our guidelines and the relevant National Standards by an approved and competent person or organisation the warrantee may become void Approved Document No GLT 221 7 1 Issue 1 0 Author NRPJ Date 29 11 2013 PAGE 3 INFINITY ID2 ACTIVE REPEATER MANUAL Software Versions 0 H 8682 2 Overview of the Infinity ID2 Active Repeater The Infinity ID2 active repeater is used on an Infinity ID2 Panel It is powered from the ID2 Panel so is connected via 4 cores 2 x power and 2 x data Op to 8 repeaters can be connected The first 2 repeaters can be powered from the panel Subsequent repeaters would need an external power supply Each repeater can be selectively configured to determine which commands it will send to the network EG to allow some repeaters to reset the system and others to not reset the system Each Repeater can also be configured to run in a different language Although any device labels entered by the installer will just
7. ical specifications SUPPLY VOLTAGE 29V DC Nominal 19 to 30V DC OPERATING CURRENT 40mA typical AUXILIARY FAULT OUTPUT 1 x FAULT RELAY SELV 1A NORM ENERG MAX NUMBER OF REPEATERS PER SYSTEM REPEATER CONNECTION RS485 Approved Document No GLT 221 7 1 Issue 1 0 Author NRPJ Date 29 11 2013 PAGE 10 INFINITY ID2 ACTIVE REPEATER MANUAL Software Versions 0 H 8682 Installation Manual Modification History ISSUE DATE CHANGES 1 0 29 11 2013 Initial Release Approved Document No GLT 221 7 1 Issue 1 0 Author NRPJ Date 29 11 2013 PAGE 11
8. ill result in the panel attempting to correct itself Should this fault occur the System Fault LED General Fault LED General Fault relay and fault internal buzzer will be constantly active until the control panel is reset Disconnect the power to the repeater Wait for 10 seconds then turn power back on This should cause the system fault condition to clear If not it is likely that the PCB is damaged Consult your supplier Approved Document No GLT 221 7 1 Issue 1 0 Author NRPJ Date 29 11 2013 PAGE 8 INFINITY ID2 ACTIVE REPEATER MANUAL Software Versions 0 H 8682 8 PCB TERMINATION CONNECTIONS ZONAL INDICATIONS kal 23 START STOP Ce Eee Eee Cee pe COME FIRE ZONE FIRE ZOHE FIRE ZONE FIRE GH JEL G Mac BUZZER fa Bae tet ied sone ed LED ce e Laer cons Inet n AG DRAN E es REFER TO MANUAL i TEND Ble ABC E CEF SOUNDERS SOUNDERS WARMED RESET Se INTELLIGENT 2 WIRE FIRE ALARA CONTROL PANEL EHSA amp ENS4 4 POWER FIRE FAULT oS FLT FUSE mA AUX 28V SPARE FUSES THERM gy RS485 Data Connection from ID2 panel 24VDC Input Power Connection from ID2 panel No other connections are used Approved Document No GLT 221 7 1 Issue 1 0 Author NRPJ Date 29 11 2013 PAGE 9 INFINITY ID2 ACTIVE REPEATER MANUAL Software Versions 0 H 8682 9 SPECIFICATIONS 9 1 Enclosure specifications DESCRIPTION VALUE ENCLOSURE SIZE 364 x 302 x 90 mm TOP CABLE ENTRIES 15 x 19mm DIA ENTRIES 9 2 Electr
9. lation 15 x 20mm knock out cable entries KLOOO000000 TT T T TT T TN 38mm 244mm 302mm Wall Mount Flush Mount Fix the enclosure to the wall using the three mounting holes provided Check the build amp condition of the wall to decide a suitable screw fixing The mounting holes are designed for No 8 roundhead or countersunk woodscrews or similar Remove any debris from the enclosure Take care not to damage the FACP during installation Approved Document No GLT 221 7 1 Issue 1 0 Author NRPJ Date 29 11 2013 PAGE 5 INFINITY ID2 ACTIVE REPEATER MANUAL Software Versions 0 H 8682 4 2 Repeater connection The Infinity ID2 Plus Active repeater has an RS485 connection to an ID2 Repeater The repeater has full control Up to 2 repeaters can be powered from the Aux 24V DC output on the panel If 3 or more are to be connected then they must be powered from external 24V power supplies The panel supports up to 8 repeaters NERAL SABLEWENT JENERAL ST i conio Power LED J Fire condition Fig LED on and zone rod LED ce hut condton Faut tED on Fauteondnon FauttEDon onn rA sess ndoa Eracar Ere cedo ten manies REFER TO MANUS REFERTO MANDAG aop mm MORE INTELLIGENT 2 WIRE FIRE ALARM CONTROL PANEL DATA EN54 2 amp EN54 4 BAT SPARE FUSES THERM Iii PEHE Eed ID2 PANEL ID2 REPEATER ID2 Panel ID2 Repea
10. ter AUX 28V 24V DC IN Power for repeater AUX 28V 24V DC IN Power for repeater RS485 B RS485 B RS485 A RS485 A RS485 GND RS485 GND Approved Document No GLT 221 7 1 Issue 1 0 Author NRPJ Date 29 11 2013 PAGE 6 INFINITY ID2 ACTIVE REPEATER MANUAL Software Versions 0 H 8682 5 CONFIGURING INFINITY ID2 REPEATER 5 1 Configuring the Language From the system Normal screen press enter and type the engineer access code 369 Select Option 1 from the repeater set up menu The panel now shows the language selection screen Use Prev amp Next Buttons To select the desires language and press enter The languages available are English Spanish Portuguese French Italian Hungarian Serbian Lithuanian 5 2 Configuring the Repeater Type and ID For the repeater to function correctly it needs to be set to the correct panel version To do this enter the repeater setup Menu and select option 2 Select the correct panel type by using the prev Next buttons If there will be more than one repeater on the system each repeater should be given a different ID repeater number Select a new repeater ID by pressing the relevant number 1 to 8 on the keypad If there is only one repeater it can be left at the default ID of 1 Press enter to save the changes 5 3 Configuring the Repeater Activity Response It is possible to configure which commands the repeater will send to the