SMC Flex Quick Start

image

Contents

1. TC Programming Notes Aux 1 Set for Normal Aux 4 Set for Up to Speed Start Connection Required for DPI Control SMC Flex Control Terminals PA PA RP 23 24 25 26 27 28 31 32 33 34 ojojojojojo 0 0 9190 Up to Speed x Indication www klinkmann com 10 SMC Flex Quick Start Typical Control Wiring Examples Continued Fig 1 x 3 Wire Control with Option Stopping DPI control Isolation Contactor K1 and Alarm Indication Programming Notes Aux 1 Set for Normal Aux 4 Set fot Alarm Option Stop SMC Flex Control Terminals FA Aux AA Alarm Indication Fig 1 x Start and Stop Control via DPI Communication ONLY with Isolation Contactor K1 Programming Notes Aux 1 Set for Normal Parameter 87 Logic Mask must be set for DPI Control Value of 4 enables HIM control only Value of 32 enables Communication Port control only Value of 44 enables ALL DPI ports for control it 61016 60161010 11 12 13 14 17 19 20 21 22 Hol Aux Co ea SMC Flex Control Terminals FA TRE Aux 23 24 25 26 27 29 31 32 33 34 ojojojojo o ojojojo 6 2011 www klinkmann com SMC Flex Quick Start 11 Step 3 Basic Programming The SMC Flex controller can be programmed with the built in keypad and LCD display or with an optional Bulletin 20 HIM xx LCD human interface module Men
2. 150 FPP135Z B 150 FPP201B 150 FPP201C 150 FPP201Z B 150 FPP251B 150 FPP251C 150 FPP251Z B 150 FPP317B 150 FPP317C 150 FPP317Z B 150 FPP361B 150 FPP361C 150 FPP361Z B 150 FPP480B 150 FPP480C 150 FPP480Z B 150 FPP625B 150 FPP625C 150 FPP625Z B 150 FPP780B 150 FPP780C 150 FPP780Z B 150 FPP970B 150 FPP970C 150 FPP970Z B 150 FPP1250B 150 FPP1250C 150 FPP1250Z Heatsink Fans B 41391 801 03 B 41391 801 03 B 41391 801 01 B 41391 801 02 110 120V AC B 41391 801 04 Control Power 230 240V AC B 41391 801 05 Control Power Base Plate B 41391 803 01 B 41391 803 02 By Pass 110 120V AC B 100 D180ED11 Contactor Control Power B 100 D420ED11 230 240V AC B 100 D180EA11 Control Power B 100 D420EA11 68666 One piece provided per part number Three phase power pole structure provided per part no One phase power pole provided per part no Refer to Appendix D in the SMC Flex User Manual for installation instructions Publication 150 QS001G EN P August 2008 Superecedes Publication 150 QS001F EN P November 2006 40055 217 01 7 Copyright 2008 Rockwell Automation Inc All Rights Reserved Printed in USA Rockwell_Power_Soft_Starters_SMC_Flex_Quick_Start_en_0611 pdf Moscow tel 7 495 641 1616 moscow klinkmann spb ru Helsinki tel 358 9 540 4940 automation klinkmann fi St Petersburg tel 7 812 327 3752 klinkmann klinkmann spb ru www klinkmann com Kiev tel 38 044 495 33 40 klinkmann klin
3. inadvertent contact with terminals Disconnect the main power before servicing the motor controller motor or associated wiring www klinkmann com SMC Flex Quick Start 3 NOTICE The controller contains ESD electrostatic discharge sensitive parts and assemblies Static control precautions are required when installing testing servicing or repairing the assembly Component damage may result if ESD control procedures are not followed If you are not familiar with static control procedures refer to applicable ESD protection handbooks Stopping modes are not intended to be used as an emergency stop The user is responsible for determining which stopping mode is best suited to the application Refer to the applicable standards for emergency stop requirements Pump Stopping may cause motor heating depending on the mechanical dynamics of the pumping system Therefore select the lowest stopping time setting that will satisfactorily stop the pump Slow Speed running is not intended for continuous operation due to reduced motor cooling The fan jumpers have been factory installed for 110 120V AC input Refer to page 9 for 220 240V AC fan wiring 5 480 A devices only Two peripheral devices can be connected to the DPI port The maximum output current through the DPI port is 280 mA When installing or inspecting protective modules make sure that the controller has been disconnected from the power source The protective module shoul
4. 800 option 2 option 4 or use direct dial code 804 Rockwell ALLEN BRADLEY ROCKWELL SOFTWARE Automation www klinkmann com 2 www klinkmann com SMC Flex Quick Start Step 1 Read the General Precautions A az Only personnel familiar with the controller and associated machinery should plan or implement the installation start up and subsequent maintenance of the system Failure to do this may result in personal injury and or equipment damage Hazardous voltage is present in the motor circuit even when the SMC Flex controller is off To avoid shock hazard disconnect main power before working on the controller motor and control devices such as Start Stop push buttons Procedures that require parts of the equipment to be energized during troubleshooting testing etc must be performed by properly qualified personnel using appropriate local safety work practices and precautionary measures Failure of solid state power switching components can cause overheating due to a single phase condition in the motor To prevent injury or equipment damage the use of an isolation contactor or shunt trip type circuit breaker on the line side of the SMC is recommended This device should be capable of interrupting the motor s lock rotor current Hazardous voltages that can cause shock burn or death are present on L1 L2 L3 T1 T2 T3 T4 T5 and T6 Power terminal covers for units rated 108 480 A can be installed to prevent
5. Check for loose connections on line side or motor side of power wires Verify and correct input power quality Internal 24V and 44 45 46 all Low line condition Check the control power verify it is within the specification System Faults 128 209 Excessive load on Check connections and grounding to the SMC control terminals Replace control module Repair Parts Part No Description For units rated 200 600V AC Forunits a 630 100 240V AC 24V AC DC 100 240V AC Control Modules Standard 41391 454 01 S1FX 41391 45 2FX 41391 454 05 S1FZ Pump All 41391 454 01 B1FX 41391 454 02 B2FX 41391 454 05 B1FZ Braking 5 85 A 41391 454 01 D1AX 41391 454 02 D2AX 41391 454 05 D1AZ 108 251A 41391 454 01 D1BX 41391 454 02 D2BX 41391 454 05 D1BZ 317 480 A 41391 454 01 D1CX 41391 454 02 D2CX 41391 454 05 D1CZ 625 780 A 41391 454 01 D1DX N A 41391 454 05 D1DZ 970 1250 A 41391 454 01 D1EX N A 41391 454 05 D1EZ Part No Description Line Voltage 200 480V 200 600V 230 690V Power Poles B 150 FPP5B 150 FPP5C N A B 150 FPP25B 150 FPP25C N A B 150 FPP43B 150 FPP43C N A B 150 FPP60B 150 FPP60C N A B 150 FPP85B 150 FPP85C N A A 41391 800 01 41391 800 02 N A A 41391 800 03 41391 800 04 N A B 150 FPP108B 150 FPP108C 150 FPP108Z B 150 FPP135B 150 FPP135C
6. Minimum horizontal clearance Ocm Din Minimum vertical clearance 15 cm 6 in Controllers rated 625 1250 A Device must be lifted only at the designated lift points identified with labels Lifting Points ne t tA z rat a 5 5 ig 1 p f Ki LA ey 2 J 1 Pi 5 Dimensions For detailed dimensions please refer to the SMC Flex User Manual 6 2011 www klinkmann com SMC Flex Quick Start 5 600 Dimensions are in millimeters inches Controller Rating A Height B Width A Depth C Approximate Shipping Weight 5 85 321 0 12 60 150 0 5 90 203 0 8 00 5 7 kg 12 5 lb 108 135 443 7 17 47 196 4 7 74 212 2 8 35 15 0 kg 33 0 Ib 201 251 560 0 22 05 225 0 8 86 253 8 9 99 30 4 kg 67 0 Ib 317 480 600 0 23 62 290 0 11 42 276 5 10 89 45 8 kg 101 Ib 625 780 1041 1 41 00 596 9 23 50 346 2 13 63 179 kg 395 Ib 970 1250 1041 1 41 00 596 9 23 50 346 2 13 63 224 kg 495 Ib 6 SMC Flex Quick Start www klinkmann com Power Wiring Refer to the product nameplate or the SMC Flex User Manual for device specific information SMC Rating Lug Kit Wire Strip Conductor Max No Lugs Pole Tightening Torque A Cat No Length Range Line Side Load Side Wi
7. QUICK START LISTEN Heys SMC FLEX BULLETIN 150 This guide provides you with the basic information required to start up your SMC Flex controller When reading this document look for this symbol Step x to guide you through the four basic steps required to install start up and program the SMC Flex The information provided in this Quick Start guide does not replace the User Manual which can be ordered or downloaded by visiting www ab com The Quick Start guide assumes the installer is a qualified person with previous experience and basic understanding of electrical terminology configuration procedures required equipment and safety precautions For safety of maintenance personnel as well as others who might be exposed to electrical hazards associated with maintenance activities follow all local safety related work practices for example the NFPA 70E Part II in the United States Maintenance personnel must be trained in the safety practices procedures and requirements that pertain to their respective job assignments For detailed SMC Flex information including set up programming precautions and application considerations refer to the following documentation Title Publication Number Availability SMC Flex User Manual 150 UM008 www ab com literature SMC Flex Application Guide 150 AT002 www ab com literature For product technical support Online Support www ab com support Telephone Support 440 646 5
8. d be inspected periodically for damage or discoloration Replace if necessary An incorrectly applied or installed controller can damage components or reduce product life Wiring or application errors such as under sizing the motor over sizing the controller incorrect or inadequate AC supply excessive ambient temperatures or power quality may result in malfunction of the system The Motor Overload parameter must be programmed by the installer to provide proper protection Overload configuration must be properly coordinated with the motor This product has been designed and tested as Class A equipment for EMC compatibility Use of the product in domestic environments may cause radio interference in which case the installer may need to employ additional mitigation methods Disconnect the controller from the motor before measuring insulation resistance IR of the motor windings Voltages used for insulation resistance testing can cause SCR failure Do not make any measurements on the controller with an Insulation Resistance IR or Megger tester 4 SMC Flex Quick Start www klinkmann com Step 2 Installation Mounting Enclosure Ratings Standard Device Rating IP00 NEMA Open Type Minimum Required Enclosure IP23 NEMA Type 1 Recommended Enclosure IP54 NEMA Type 12 sizing guide in User Manual Enclosure Internal Temperature 5 50 C 23 122 F Orientation and Clearance Mounting Orientation Vertical
9. diagnostics and metering functions which can be accessed through a local or remote LCD display Step 1 Action From any menu Press Esc to get to the MAIN Device display 2 If using the built in display Press Enter and continue to step 3 If using a remote HIM first make sure that the SMC Flex is displayed by going to MAIN MENU DEVICE SELECT SMC FLEX Press Enter and continue to step 3 3 To View or Review the Metering Information Access the metering parameters by selecting PARAMETER MONITORING and then METERING Press enter to view any selected value Viewing and Clearing Faults Step Action 1 Press Esc to acknowledge the fault The fault information will be removed so that you can use the HIM 2 To View or Review the fault information Go to MAIN MENU DIAGNOSTICS FAULTS VIEW FAULT QUEUE Or look at parameters 124 128 3 Address the condition that caused the fault The cause must be corrected before the fault can be cleared 4 After corrective action has been taken clear the fault by one of these methods Press and Hold the ESC key for 3 seconds Cycle control power to the device Press Stop key on an External HIM Program the SMC Flex controller for a CLEAR FAULT which can be found in MAIN MENU DIAGNOSTICS FAULTS Option Input 2 terminal 15 can be configured to clear faults with the use of N O push button 14 SMC Flex Quick Start www klinkmann com Troubl
10. en Set Up This programming group provides a limited parameter set allowing quick start up with minimal adjustment Parameter Name and Description Values Default Parameter 14 SMC Option Standard Pump Control Brake Read Only Displays the type of controller This is factory set and not adjustable Parameter 15 Motor Connection Line or Delta Line Displays the motor type to which the device is being connected Parameter 16 Line Voltage 0 10000 480 Displays the system line voltage to which the unit is connected Parameter 17 Starting Mode Soft Start Current Limit Full Soft Start Allows the user to program the SMC Flex controller for the type of starting that best fits the application Voltage Linear Speed Pump Control Parameter 18 Ramp Time 0 30s 10 This sets the time period during which the controller will ramp the output voltage Parameter 19 Initial Torque 0 90 of locked rotor torque 70 When the Soft Start mode is selected this parameter sets the initial reduced voltage output level for the voltage ramp Parameter 20 Current Limit Level 50 600 FLC 350 When Current Limit mode is selected this parameters sets level of current that is applied for the programmed Ramp Time Parameter 22 Kickstart Time 0 0 2 0s 0 A boost current is provided to the mot
11. er supply with phase Inoperable power module bypass Replace power module indication Check control module TB2 TB4 and TB5 TB7 for securness Check Aux 1 2 3 4 configurations are not set to External Bypass No Load Fault 16 17 18 40 prestart Loss of load side power wiring Check all load side power connections only Start command cycled unexpectedly with motor rotating Check motor windings Line Unbalance 19 running Supply unbalance is greater than the user programmed value Check power system and correct if necessary The delay time is too short for the application Extend the delay time to match the application requirements Overvoltage 20 running Supply voltage is greater than user programmed value Check power system and correct if necessary The delay time is too short for the application Correct the user programmed value Extend the delay time to match the application requirements Undervoltage 21 running Supply voltage is less than user programmed value Check power system and correct if necessary The delay time is too short for the application Correct the user programmed value Extend the delay time to match the application requirements Overload 22 running Motor overloaded Check motor overload condition Overload parameters are not matched to the motor Check values for overload class and motor FLC Verify current draw of the motor Underload 23 running Broken motor shaft belts toolbits etc Check pump system machine drive components and load
12. eshooting Abbreviated Listing For a complete list of fault codes and troubleshooting tips refer to the SMC Flex User Manual Display Fault Fault Code Enabled Possible Causes Possible Solutions Line Fault with 1253 prestart Missing supply phase Check for open line i e blown fuse Phase Indication only Motor not connected properly Check for open load lead Incoming 3 phase voltage instability Verify power quality Shorted SCR 4 5 6 all Shorted power module Check for shorted SCR replace power module if necessary with Phase indication Open Gate with 7 8 9 start or Open gate circuitry Perform resistance check replace power module if necessary Phase Indication stop Loose gate lead Check gate lead connections to the control module PTC Power Pole 10 11 Controller ventilation blocked Check for proper ventilation and SCR Controller duty cycle exceeded Check application duty cycle Overtemp Fan failure Wait for motor to cool or provide external cooling Ambient temperature limit exceeded Replace power module or control module as needed Failed thermistor Replace fan Motor PTC 12 running Motor ventilation blocked Check for proper ventilation Motor duty cycle exceeded Check application duty cycle PTC open or shorted Wait for motor to cool or provide external cooling Check resistance of PTC Open Bypass 13 14 15 running Control voltage is low Check control voltage pow
13. ing Pump cavitation Check settings ncorrect user setting Repair or replace motor Jam 24 running Motor current has exceeded the user programmed jam level Correct source of jam or excessive loading Check programmed time value Stall 25 running otor did not reach full speed by the end of the programmed Correct source of stall or excessive loading ramp time Adjust SMC starting parameters to compensate for load ncorrect user setting Phase Reversal 26 prestart Incoming supply voltage is not in the expected ABC sequence Check power wiring correct if necessary only Network and 30 31 32 all DPI network loss Check communication adapters and verify connection to SMC Comm s Loss 27 28 29 Communication disconnection at the serial port Reconnect each DPI connected device Ground Fault 33 running Ground fault current level has exceeded programmed value Check power system and motor correct if necessary The delay time is too short for the application Check programmed ground fault levels to match application requirements Extend the delay time to match the application requirements Power Loss with 35 36 37 start or Missing supply phase as indicated Check for open line i e blown line fuse phase indication stop Internal CT problem Replace power pole as indicated Line Loss with 41 42 43 start or Incoming 3 phase voltage instability or distortion Check supply voltage for capability to start stop motor phase indication stop High impedance connection
14. kmann kiev ua Samara tel 7 846 273 95 85 samara klinkmann spb ru Yekaterinburg tel 7 343 376 5393 yekaterinburg klinkmann spb ru Minsk tel 375 17 200 0876 minsk klinkmann com Tallinn tel 372 668 4500 klinkmann est klinkmann ee Vilnius tel 370 5 215 1646 post klinkmann lt Riga tel 371 6738 1617 klinkmann klinkmann v
15. ltage A Lvl Overvoltage A Dly Parameter Mgmt Unbalance Unbalance F Lvl Unbalance F Dly Unbalance A Lvl Unbalance A Dly Parameter Mgmt Jam F Lvl Jam F Dly Jam A Lvl Jam A Dly Parameter Mgmt Stall Stall Delay Parameter Mgmt Ground Fault Gnd Fit Enable Gnd Fit Lvl Gnd Fit Dly Gnd Fit Inh Time Gnd Fit A Enable Gnd FIt A Lvl Gnd Fit A Dly Parameter Mgmt PTC PTC Enable Parameter Mgmt Phase Reversal Phase Reversal Parameter Mgmt Restart Starts Per Hour Restart Attempts Restart Delay Parameter Mgmt Comm Masks Language Linear List Logic Mask Parameter Mgmt Language Parameter Mgmt Motor Data Motor FLC Motor ID Parameter Mgmt All Parameters Data Links Data In A1 Data In A2 Data In B1 Data In B2 Data In C1 Data In C2 Data In D1 Data In D2 Data Out A1 Data Out A2 Data Out B1 Data Out B2 Data Out C1 Data Out C2 Data Out D1 Data Out D2 Parameter Mgmt Note Depending on the SMC option additional parameters may appear in some menus eThe external HIM has similar programming operation to the built in HIM however some differences do exist eThe built in HIM can not be used to program other DPI devices i e Device Select 12 SMC Flex Quick Start 6 2011 www klinkmann com Access the Basic set up group by selecting the Parameters menu from the Main Menu and th
16. lue allows the user to define how the overload can reset Parameter 107 Aux1 Config Normal Up to speed Fault Normal Auxiliary 1 contact is located at terminals 19 and 20 and allows the user to configure the operation of the Alarm Network Control Externa contact Bypass N 0 N C Parameter 110 Aux2 Config Normal Up to speed Fault Fault Auxiliary 2 contact is located at terminals 29 and 30 and allows the user to configure the operation of the Alarm Network Control Externa contact Bypass N 0 N C Parameter 108 Aux3 Config Normal Up to speed Fault Alarm Auxiliary 3 contact is located at terminals 31 and 32 and allows the user to configure the operation of the Alarm Network Control Externa contact Bypass N 0 N C Parameter 109 Aux4 Config Normal Up to speed Fault Normal Auxiliary 4 contact is located at terminals 33 and 34 and allows the user to configure the operation of the Alarm Network Control Externa contact Bypass N 0 N C Parameter 115 Parameter Mgmt Ready Load Default Ready Allows the user the ability to recall all Factory default parameter values www klinkmann com SMC Flex Quick Start 13 Step 4 Operation and Troubleshooting Start Up Check List nan Aa U D Verify Input Supply voltage and wiring Check output wiring Check control wiring Apply control power Test local start stop control Monitoring The SMC Flex controller has built in
17. nected to auxiliary contacts 2000 Aux Contact 1 3200 Aux Contact 3 Control power on units rated 625 1250 A is 71 Not Used 3300 Aux Contact 4 pre wired internally from terminal block CP1 22 Not Used 3400 Aux Contact 4 www klinkmann com Control Wiring SMC Flex Quick Start Refer to the product nameplate for additional details Depending on the specific application additional control circuit transformer VA capacity may be required Controllers rated 5 480A Control power is connected to the product through terminals 11 and 12 Conductor Range 0 75 2 5 mm 18 14 AWG Torque 0 6 Nem 5 bein Maximum Number of Wires per Terminal AC Control Voltage Input 2 100 240V AC or 24V AC 10 15 Supply Type 1 phase 50 60 Hz 24V AC Power Requirement 130VA 100 240V AC Power Requirement 75VA DC Control Voltage Input 24V DC 10 15 Inrush Current 5 Inrush Time 250 ms Transient Watts 60 W Transient Time 500 ms Staedy State Watts 24 W Recommended Supply Fan Power Input AC only 1606 XLP5DE separately wired F5 F135 20VA F201 F251 AOVA F317 F480 60VA Controllers rated 625 1250 A Control power is connected to the product through terminal block CP1 at terminals 1 and 4 Conductor Range 0 75 2 5 mm 18 14 AWG Torque 0 6 Nem 5 lbe in Maximum Number of Wires per Terminal 2 Cont
18. or for the programmed time period Parameter 23 Kickstart Level 0 90 of locked rotor torque 0 Adjusts the amount of current applied to the motor during kickstart Parameter 133 Stop Input Coast Stop Option Coast Allows the user to select the operation of terminal 18 Stop Input Parameter 132 Option Input 1 Disable Coast Stop Option Stop Option Allows the user to select the operation of terminal 16 Option Input 1 Fault Fault NC Network Parameter 24 Option Input 2 Disable Slow Speed Dual Ramp Disable Allows the user to select the operation of terminal 15 Option Input 2 Fault Fault NC Network Clear Fault Parameter 32 Stop Mode Soft Stop Linear Speed SMB Soft Stop Allows the user to program the SMC Flex controller for the type of stopping that best fits the application Accu Stop Pump Stop Parameter 33 Stop Time 0 0 120s 0 0 This sets the time period which the controller will ramp the voltage during a stopping maneuver Parameter 44 Overload Class Disable 10 15 20 30 10 Allows the user to enter the desired Overload trip class for the motor Parameter 45 Service Factor 0 01 1 99 1 15 Allows the user to enter the Service Factor of the motor For IEC motors the typical value is 1 0 For NEMA Parameter 46 Motor FLC 1 0 2200 1 0 This is a user entered value that is needed so the device can provide proper motor Overload protection Parameter 47 OL Reset Mode Auto Manual Manual This va
19. re Lug Lug Busbar 1 2 5 85 mm _ _ 11 3Nem E 5 85 8 20 mm 4 3 0 AWG 100 Ibein 4 16 120 mm 31 Nem 23 Nem 108 135 199 LF1 8 20 mm 6250 MCM 1 1 275 Ibein 200 Ibein F 16 120 mm 31 Nem 23 Nem 201 251 199 LF1 8 20 mm 6 250 MCM 2 2 275 Ibe in 200 Ib in 25 240 mm 42 Nem 28 Nem 317 480 199 LG1 8 25 mm 4 500 MCM 2 2 375 Ibe in 250 Ibe in 70 240 mm 45 Nem 68 Nem 625 780 00 DL630 32 mm 64 mm 2 0500 MCM 2 2 400 Ibein 600 Ibein 120 240 mm 45 Nem 68 Nem 970 00 DL860 26 mm 48 mm 4 0 500 MCM 1 1 400 Ibein 600 Ibein 70 240 mm 00 DL630 32 64 1 1 ni mm 64 mm 2 9 500 MCM ee 2 400 Ibein 600 lbein 100 DL860 26 mm 48 mm Nie san UCT 1 5 Control Terminals Terminal Description Terminal Description Footnotes 110 Control Power Input 230 PTC Input 1209 Control Power Common 240 PTC Input 130 Controller Enable Input 25 Tachometer Input Do not connect any additional loads to these 14 Ground 26 Tachometer Input terminas ia loads may cause 15 Option Input 2 270 Ground Fault Transformer Input When set for External Bypass mode the SMC 16 Option Input 1 280 Ground Fault Transformer Input a L Es URLs 1700 Start Input 2900 Aux Contact 2 reaches full speed The SMC Flex overload functionality is disabled in this mode 1809 Stop Input 300 Aux Contact 2 RC Snubbers are required on inductive type 1909 Aux Contact 1 31 Aux Contact 3 loads con
20. rol Voltage Input 110 120V AC or 230 240V AC 10 15 Supply Type 1 phase 50 60 Hz Control Power Input 800VA includes controller bypass and fans 7 8 SMC Flex Quick Start www klinkmann com Typical Wiring Diagrams Typical Power Wiring Examples Diagrams per NEMA Symbology Line Connection with Delta Connection with Isolation Contactor Isolation Contactor Default Mode Optional Mode L1 L2 L3 L1 L2 L3 K1 Diagrams per IEC Symbology Line Connection with Delta Connection with Isolation Contactor Isolation Contactor Default Mode Optional Mode L1 L2 L3 L1 L2 L3 l li l Delta Connection with Shorted SCR Protection Optional Mode R Delta Connection with Shorted SCR Protection Optional Mode L1 L2 L3 www klinkmann com SMC Flex Quick Start 9 Typical Control Wiring Examples Fig 1 x 2 Wire Control No DPI control or Option Stopping with Fault Indication LT L Programming Notes Aux 4 Set for Fault Parameter 132 Set for Diable 2 Wire Device Fan Power Terminations Example Separately Wired for F5 F480 Devices Factory Default Position 110 120 VAC Jumpers Optional Configuration SMC Flex Control Terminals 220 240 VAC PA RE AUX F Supply 7 Jumper Indication Fig 1 x 3 Wire Control With or Without DPI control Isolation Contactor K1 and Up to Speed Indication
21. u Structure Hierarchy Monitoring Power Up and Status Display Motor Protection Main Menu Parameters Diagnostics Preferences Memory Storage Log In See File Structure Below for additional details Alarms Faults Device Revision Change Password User Dspl Line User Dspl Time User Dspl Video Reset User Display Reset to Defaults Enter Password Only Active when a password is used Communications Utility Linear List Metering Volts Phase A B Volts Phase B C Volts Phase C A Current Phase A Current Phase B Current Phase C Watt Meter Kilowatt Hours Elapsed Time Meter Reset Power Factor Mtr Thermal Usage SMC Option Line Voltage Starting Mode Ramp Time Initial Torque Cur Limit Lvl Kickstart Time Kickstart Level Stop Input Option 1 Input Option 2 Input Stop Mode Stop Time Overload Class Service Factor Motor FLC Overload Reset Aux1 Config Aux2 Config Aux3 Config Aux4 Config Parameter Mgt Motor Connection Overload Overload Class Service Factor Motor FLC Overload Reset Overload A Lvl Parameter Mgmt Underload Underload F Lvl Underload F Dly Underload A Lvl Underload A Dly Parameter Mgmt Undervoltage Undervoltage F Lvl Undervoltage F Dly Undervoltage A Lvl Undervoltage A Dly Parameter Mgmt Overvoltage Overvoltage F Lvl Overvoltage F Dly Overvo