E5CN Datasheet
Contents
1. pgo PV SP Display Screen Selection MV Display Selection PV Decimal Point Display PV Status Display Function SV Status Display Function Display Refresh Period Control Output 1 ON OFF Count Monitor Control Output 2 ON OFF Count Monitor Control Output 1 ON OFF Count Alarm Set Value Control Output 2 ON OFF Count Alarm Set Value ON OFF Counter Reset Move to Calibration Level Basic type Digital Temperature Controller E5CN E5CN U 17 Safety Precautions OMRON N CAUTION Do not touch the terminals while power is being supplied Doing so may occasionally result in minor injury due to electric shock Do not allow pieces of metal wire clippings or fine metallic shavings or filings from installation to enter the product Doing so may occasionally result in electric shock fire or malfunction Do not use the product where subject to flammable or explosive gas Otherwise minor injury from explosion may occasionally occur Do not leave the cable for the Support Software connected to the product Malfunction may occur due to noise in the cable Do not use the Temperature Controller or Conversion Cable if it is damaged Doing so may occasionally result in minor electric shock or fire Never disassemble modify or repair the product or touch any of the internal parts Minor electric shock fire or malfunction may
2. oo0000 Di D R o Aleo A KA ca 29 lu D Bll Fr kz g rik 3 Rz un nm mm Di at 3 MB Command Logic Switching PV Change Color PV Stable Band Alarm 1 ON Delay Alarm 2 ON Delay Alarm 3 ON Delay Alarm 1 OFF Delay Alarm 2 OFF Delay Alarm 3 OFF Delay Input Shift Type MV at Stop and Error Addition Auto Manual Select Addition o c gt 39 m o re co ca w 0 oo FE orn HS Alarm Use HS Alarm Latch HS Alarm Hysteresis LBA Detection Time LBA Level LBA Band Control Output 1 Assignment Control Output 2 Assignment Auxiliary Output 1 Assignment Auxiliary Output 2 Assignment Character Select Soak Time Unit Alarm SP Selection po 0000 Manual MV Limit Enable py RP PV Rate of Change Calculation Period A Automatic Cooling Coefficient Adjustment po 0000 1 Heater Overcurrent Use Heater Overcurrent Latch Heater Overcurrent Hysteresis
3. 31 2 max Note A model with finger protection P2CF 11 E is also available Back connecting Socket P3GA 11 Terminal Layout Internal Connections Bottom View Note 1 Using any other sockets will adversely affect accuracy Use only the specified sockets 2 A Protective Cover for finger protection Y92A 48G is also available 14 Basic type Digital Temperature Controller E5CN E5CN U OMRON Operation Setting Levels Diagram This diagram shows all of the setting levels To move to the advanced function setting level and calibration level you must enter passwords Some parameters are not displayed depending on the protect level setting and the conditions of use Control stops when you move from the operation level to the initial setting level Basic Type Power ON Start in manual mode Start in automatic mode Press the O Key or the PF Key for at least 1 s 4 Press the Operation Adjustment Ol c Level Level Press the Keys for at Ol Ce least 1 s Press the Keys for at O Key less than 1 s least 3 s Display will flash after 1st the Ol Key second for at least 3 s while Manual A M is displayed mode A M will flash after 1st second l Press the O Key for at least 3 s Displa
4. 10 Basic type Digital Temperature Controller E5CN E5CN U External Connections OMRON e A voltage output control output for driving SSR is not electrically insulated from the internal circuits When using a grounding thermocouple do not connect any of the control output terminals to ground If the control output terminals are connected to ground errors will occur in the measured temperature values as a result of leakage current e Consult with your OMRON representative before using the external power supply for the ES1B for any other purpose E5CN Controllers Control output Tim Long life relay output Auxiliary outputs relay outputs 250 VAC 3A 250 VAC 3 A resistive load 0 0 resistive load Relay output K ER Control output 1 Auxiliary output 2 a Ta ade oltage output for driving DO NOT A uxiliary outpu 12 VDC 21 mA TE i eee USE i B Current output Li gt gt By lt 0 to 20 mA DC AL I lt I Input power supply 4 to 20 mA DC ponoril gt I ILEI amp OD Load 600 Q max USE I D a I 100 to 240 VAC mA Volt Te Pt 24 VAC VDC no polarity Analog input Temperature input Option Units Control output 2 Voltage output for driving SSR 12 VDC 21 mA ri E53 CNHH03N2 E53 CNHBN2 E53 CNQ03N2 E53 CNPBN2 E53 CNPHN2 Communications Event inputs Communications Event Inputs and E
5. 4 Be sure to wire properly with correct polarity of terminals 5 Use the specified size M3 5 width 7 2 mm or less crimped terminals for wiring To connect bare wires to the terminal block use stranded or solid copper wires with a gage of AWG24 to AWG 14 equal to a cross sectional area of 0 205 to 2 081 mm The stripping length is 5 to 6 mm Up to two wires of the same size and type or two crimp terminals can be inserted into a single terminal 6 Do not wire the terminals that are not used 7 To avoid inductive noise keep the wiring for the product s terminal block away from power cables carry high voltages or large currents Also do not wire power lines together with or parallel to product wiring Using shielded cables and using separate conduits or ducts is recommended Attach a surge suppressor or noise filter to peripheral devices that generate noise in particular motors transformers solenoids magnetic coils or other equipment that have an inductance component When a noise filter is used at the power supply first check the voltage or current and attach the noise filter as close as possible to the product Allow as much space as possible between the product and devices that generate powerful high frequencies high frequency welders high frequency sewing machines etc or surge 8 Use this product within the rated load and power supply 9 Make sure that the rated voltage is attained within two seconds of tu
6. CT input Terminal block models E5CN 15 FS 1 digit max Influence of temperature x2 Influence of voltage x2 Thermocouple input R S B W PL Il Terminal block models E5CN 1 of PV or 10 C whichever is greater 1 digit max Plug in models ES5CN U 42 of PV or 10 C whichever is greater 1 digit max Other thermocouple input 3 Terminal block models E5CN 41 of PV or 24 C whichever is greater 1 digit max Plug in models ES5CN U 42 of PV or 4 C whichever is greater 1 digit max Platinum resistance thermometer input Terminal block models E5CN and plug in models E5CN U 11 of PV or 42 C whichever is greater 1 digit max Analog input Terminal block models E5CN and plug in models ES5CN U 41 FS 1 digit max Input sampling period 250 ms Hysteresis Models with thermocouple platinum resistance thermometer input universal input 0 1 to 999 9 EU in units of 0 1 EU x4 Models with analog input 0 01 to 99 99 FS in units of 0 01 FS Proportional band P Models with thermocouple platinum resistance thermometer input universal input 0 1 to 999 9 EU in units of 0 1 EU x4 Models with analog input 0 1 to 999 9 FS in units of 0 1 FS Integral time I 0 to 3999 s in units of 1 s Derivative time D 0 to 3999 s in units of 1 s 5 Control period 0 5 1 to 99 s in units of 1 s Manual reset value 0 0 to 100 0 in units o
7. 42 4 V peak or 60 VDC 2 A class 2 power supply is one tested and certified by UL as having the current and voltage of the secondary output restricted to specific levels 3 The tightening torque for ESCN U is 0 5 N m Precautions for Safe Use Be sure to observe the following precautions to prevent malfunction or adverse affects on the performance or functionality of the product Not doing so may occasionally result in faulty operation 1 This product is specifically designed for indoor use only Do not use this product in the following places Places directly subject to heat radiated from heating equipment Places subject to splashing liquid or oil atmosphere Places subject to direct sunlight Places subject to dust or corrosive gas in particular sulfide gas and ammonia gas Places subject to intense temperature change e Places subject to icing and condensation Places subject to vibration and large shocks 2 Use and store the product within the rated ambient temperature and humidity Gang mounting two or more Temperature Controllers or mounting Temperature Controllers above each other may cause heat to build up inside the Temperature Controllers which will shorten their service life In such a case use forced cooling by fans or other means of air ventilation to cool down the Temperature Controllers 3 To allow heat to escape do not block the area around the product Do not block the ventilation holes on the product
8. 48 NR Order the Waterproof Packing separately if it becomes lost or Note The E53 COV10 damaged cannot be used The Waterproof Packing can be used to achieve an IP66 degree of protection Deterioration shrinking or hardening of the waterproof packing may SS occur depending on the operating environment Therefore periodic replacement is recommended to ensure the level of waterproofing specified in IP66 The time for periodic replacement depends on the iss operating environment Be sure to confirm this point at your site UP Consider one year a rough standard OMRON shall not be liable for the level of water resistance if the customer does not perform periodic replacement m The Waterproof Packing does not need to be attached if a waterproof 22 structure is not required Lu Current Transformers E54 CT1 E54 CT1 Dad 28 Thru current lo vs Output Voltage pen ssda TT Eo Reference Values 7 5 Maximum continuous heater current 50 A 50 60 Hz Number of windings 400 2 j i Winding resistance 1842 Q 25 3 G OVE So Hz 4 10 5 E Tor i gt A 40 Ss Distortion f u factor 10 Two 3 5 dia o 1 4 S 3 10 c a i 1 5100m Ga i 30 6 10 E54 CT3 i 100 pV 10 1 10 100mA 1 10 100 1 000A Thru current lo A r m s E54 CT3 Thru current lo vs Output Voltage Eo Reference Values
9. Current 2 8 SAK Soak Time H Monitor Si z g8 223 i Press the O and Keys for Press the 0 Key Alarm 4 Type a at least 3 s Press the 0 and lt Keys for at least 1 s l gt ce i less than 1 s et h Wait Band ommunications B H5G7 HSAlarm2 EWE b Eee he Protect Level Level oe SI Note The time taken to move to the protect Note Displayed only for models with communications Hyst f cel ce level can be adjusted by changing the Changes are effective after cycling power or lysteresis Ergo p spo 2 MY 5 MV at Stop Move to protect level time setting after a software reset Bari IDE nn as n ses uu Ig Mal M to Protect Level Sl E PMar Deniaved STA passwort 8 PSE Protocol Setting cal Ee ol amp BC Switches betw ce is set Restricts moving to protec Fan ENF Con tci Ni F SYSWAY joo Nn ompovva B SP 91 g Mi E MEV Ener fee level GFOMP Av Boe ap pees a 00 E Operation Adjustment Protect fees SP used by ce 8 OPE Restricts displaying and B 1 N g Communications Unit No cel multi SP m Modifying menus in operation zs y g 5P P SP2 Be SPRL SP Ramp Set Value adjustment and manual control eae i E iS levels eo z mS ce I ce Eza H art WIJ Initial Setting E Be Communications ta E L PE Communications Protect APS BaudRate MVU men Ea i This protect level restricts movement 2 g6 CompoWay F B SP 3 SP3 Bol H pper Limit Bea to the initial setting communications SA
10. EU is C or F When robust tuning RT is ON the differential time is 0 0 to 999 9 in units of 0 1 s External communications RS 485 and cable communications for the Setup Tool can be used at the same time The E5CN U plug in model is certified for UL listing only when used together with the OMRON P2CF 11 Socket Basic type Digital Temperature Controller E5CN E5CN U 9 OMRON USB Serial Conversion Cable Applicable OS Windows 2000 XP or Vista Current Transformer Order Separately Ratings Applicable software Thermo Mini CX Thermo version 4 0 or higher Applicable models E5AN E5EN E5CN E5CN U E5AN H E5EN H E5CN H USB interface standard Conforms to USB Specification 1 1 DTE speed 38400 bps Connector specifications Computer USB type A plug Temperature Controller Setup Tool port on bottom of Controller Power supply Bus power Supplied from USB host controller Power supply voltage 5 VDC Current consumption 70 mA Ambient operating temperature 0 to 55 C with no condensation or icing Ambient operating humidity 10 to 80 Storage temperature 20 to 60 C with no condensation or icing Storage humidity 10 to 80 Altitude 2 000 m max Weight Approx 100 g Note A driver must be installed in the personal computer Refer to installation information in the operation manual for the Conversion Cable Commun
11. Maximum continuous heater current 120 A 50 60 Hz Maximum continuous heater current for the Temperature Controller is 50 A Number of windings 400 2 Winding resistance 840 8 Q E54 CT3 Accessory 2 100 V E50 Hz Distor i tion e Armature Connection Example 10 i factor 1096 Armature a 3 Approx 3 dia I Plug JA gt 4 1 2 2 e Lead E b C 5100 mv a pale g amp A e Plug ER R ae II t 22 SER 100 pV 10 1 10 100 mA 1 10 100 1 000 A Thru current lo A r m s Basic type Digital Temperature Controller ESCN E5CN U 13 OMRON Adapter Y92F 45 Note Use this Adapter when the panel has already been prepared for the E5B Fixture Accessory 4 7 76 69 6 to 77 6 F g x 72x72 gt sg AAS N fm SER Sp Qa MDD NT 67 x 67 87 Panel 1 to 8 mm 48 x 48 ce LH a A 77 3 to back of E5CN E5CN U Wiring Socket Front connecting Socket Eleven M3 5 x 7 5 P2CF 1 1 sems screws 7 8 Terminal Layout Internal Connections Top View Mounting Holes Two 4 5 dia mounting holes Two 4 5 dia H holes 4040 2 Note Can also be mounted to a DIN track
12. Panel mounting is also possible Precautions when Wiring e Separate input leads and power lines in order to prevent external noise e Use wires with a gage of AWG24 cross sectional area 0 205 mm to AWG14 cross sectional area 2 081 mm twisted pair cable stripping length 5 to 6 mm e Use crimp terminals when wiring the terminals e Tighten the terminal screws to a torque of 0 74 to 0 90 N m however the terminal screws on the ESCN U must be tightened to a torque of 0 5 N m e Use the following types of crimp terminals for M3 5 screws Poe 7 2 mm max 7 2 mm max e Do not remove the terminal block Doing so will result in malfunction or failure 20 Basic type Digital Temperature Controller E5CN E5CN U OMRON Basic type Digital Temperature Controller E5CN E5CN U 21 Warranty and Application Considerations Please read and understand this catalog before purchasing the products Please consult your OMRON representative if you have any questions or comments Warranty and Limitations of Liability WARRANTY OMRON s exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year or other period if specified from date of sale by OMRON OMRON MAKES NO WARRANTY OR REPRESENTATION EXPRESS OR IMPLIED REGARDING NON INFRINGEMENT MERCHANTABILITY OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS DET
13. S 500 0 500 0 500 0 4199 9 to o E 400 0 400 400 0 400 400 0 999 9 400 260 So 120 165 200 mil 100 0 100 0 90 i 100 0 0 0 0 0 0 0 0 0 0 o 0 100 0 Bae 20 0 400 20 0 400 200 499 9 499 9 200 200 199 9 200 200 199 9 200 Setting number 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 24 25 19 20 21 22 23 Shaded settings are the default settings The applicable standards for the input types are as follows K J T E N R S B JIS C 1602 1995 IEC 584 1 L Fe CuNi DIN 43710 1985 U Cu CuNi DIN 43710 1985 W W5Re W26Re ASTM E988 1990 Models with Analog Inputs NEW JPt100 JIS C 1604 1989 JIS C 1606 1989 Pt100 JIS C 1604 1997 IEC 751 PL II According to Platinel II electromotive force charts from BASF previously Engelhard Input Type Current Voltage Input specification 4 to 20mA 0 to 20 mA 1to5V Oto5V 0to10V Setting range Usable in the following ranges by scaling 1999 to 9999 499 9 to 999 9 49 99 to 99 99 or 4 999 to 9 999 Setting number 0 1 2 3 4 Shaded settings are the default settings Basic type Digital Temperature Controller E5CN E5CN U 7 OMRON Alarm Outputs Each alarm can be independently set to one of the following 13 alarm types The default is 2 Upper limit Auxiliary outputs a
14. connector if it does not connect smoothly Using excessive force may damage the connector 25 Do not place heavy object on the Conversion Cable bend the cable past its natural bending radius or pull on the cable with undue force 26 Do not connect or disconnect the Conversion Cable while communications are in progress Product faults or malfunction may occur 27 Make sure that the Conversion Cable s metal components are not touching the external power terminals 28 Do not touch the connectors on the Conversion Cable with wet hands Electrical shock may result 29 Before using infrared communications correctly attach the enclosed Mounting Adapter to the cable for the Support Software When connecting the infrared port on the cable to the Support Software into the Adapter insert the connector to the specified line Communications may not be possible if the connector is not connected properly Precautions for Correct Use Service Life 1 Use the product within the following temperature and humidity ranges Temperature 40 to 55 C with no icing or condensation Humidity 25 to 85 If the product is installed inside a control board the ambient temperature must be kept to under 55 C including the temperature around the product 2 The service life of electronic devices like Temperature Controllers is determined not only by the number of times the relay is switched but also by the service life of internal electronic components C
15. consideration when performing control 17 The number of EEPROM write operations is limited Therefore use RAM write mode when frequently overwriting data during communications or other operations 18 Always touch a grounded piece of metal before touching the Temperature Controller to discharge static electricity from your body 19 D0 not remove the terminal block Doing so may result in failure or malfunction 20 Control outputs for driving SSR that are voltage outputs are not isolated from the internal circuits When using a grounded thermocouple do not connect any of the control output terminals to ground Doing so may result in an unwanted circuit path causing error in the measured temperature 21 When replacing the body of the Temperature Controller check the condition of the terminals If corroded terminals are used contact failure in the terminals may cause the temperature inside the Temperature Controller to increase possibly resulting in fire If the terminals are corroded replace the case as well 22 Use suitable tools when taking the Temperature Controller apart for disposal Sharp parts inside the Temperature Controller may cause injury 23 Before connecting an Output Unit confirm the specifications and thoroughly read relevant information in the datasheet and manual for the Temperature Controller 24 Check the orientation of the connectors on the Conversion Cable before connecting the Conversion Cable Do not force a
16. occasionally occur CAUTION Risk of Fire and Electric Shock a This product is UL listed as Open Type Process Control Equipment It must be mounted in an enclosure that does not allow fire to escape externally b More than one disconnect switch may be required to de energize the equipment before servicing the product c Signal inputs are SELV limited energy 1 d Caution To reduce the risk of fire or electric shock do not interconnect the outputs of different Class 2 circuits 2 If the output relays are used past their life expectancy contact fusing or burning may occasionally occur Always consider the application conditions and use the output relays within their rated load and electrical life expectancy The life expectancy of output relays varies considerably with the output load and switching conditions Tighten the terminal screws to between 0 74 and 0 90 N m 3 Loose screws may occasionally result in fire Set the parameters of the product so that they are suitable for the system being controlled If they are not suitable unexpected operation may occasionally result in property damage or accidents A malfunction in the product may occasionally make control operations impossible or prevent alarm outputs resulting in property damage To maintain safety in the event of malfunction of the product take appropriate safety measures such as installing a monitoring device on a separate line A semiconductor is
17. points SPO to SP3 can be saved and selected using event inputs key operations or serial communications Bank switching Not supported Indication method Multi SP Manual output heating cooling control loop burnout alarm SP ramp other alarm functions heater burnout detection 40 AT 100 AT MV limiter input digital filter self tuning temperature input shift run stop protection functions control output ON OFF counter extraction of square root MV change rate limit logic operations PV SV status display simple program automatic cooling coefficient adjustment Ambient operating temperature 10 to 55 C with no condensation or icing for 3 year warranty 40 to 50 C Other functions Ambient operating humidity 25 to 85 Storage temperature 25 to 65 C with no condensation or icing 6 Basic type Digital Temperature Controller E5CN E5CN U OMRON Input Ranges Thermocouple Platinum Resistance Thermometer Universal Inputs Input Platinum resistance Infrared temperature Analog Type thermometer HE rn ScoUp E sensor input 115 140 60t Name Pt100 JPt100 K J T Ble u elele lvl ipe 120 1 2 ROOS 3 2300 a 1800 1700 1700 1700 1600 1500 eee 1300 1300 1300 1300 1200 Usable rs in the 2 ae following G 000 850 850 850 ranges 900 by 2 ing 5 800 scaling 3 700 1999 to 2 G 600 9999 or
18. used in the output section of long life relays If excessive noise or surge is impressed on the output terminals a short circuit failure is likely to occur If the output remains shorted fire will occur due to overheating of the heater or other cause Take measures in the overall system to prevent excessive temperature increase and to prevent fire from spreading Do not allow pieces of metal or wire cuttings to get inside the cable connector for the Support Software Failure to do so may occasionally result in minor electric shock fire or damage to equipment Do not allow dust and dirt to collect between the pins in the connector on the Conversion Cable Failure to do so may occasionally result in fire Soo 909e OOOOOE When inserting the body of the Temperature Controller into the case confirm that the hooks on the top and bottom are securely engaged with the case If the body of the Temperature Controller is not inserted properly faulty contact in the terminal section or reduced water resistance may occasionally result in fire or malfunction When connecting the Control Output Unit to the socket press it in until there is no gap between the Control Output Unit and the socket Otherwise contact faults in the connector pins may occasionally result in fire or malfunction 1 An SELV circuit is one separated from the power supply with double insulation or reinforced insulation that does not exceed 30 V r m s and
19. when Additional BE oN L Scaling Lower Limit Adjustment Level ES ie SHE Be E g Eg ua Display B 1 Displayed only B S Temperature Input Shift BE cl g 3 Je SL du once when al p k 3 25 Process Value 3 AL Alarm Value 1 3 Eos Bhan Boe E Set Point 8 E 2 p Decimal Point EH tering ess 0 9 B g g S 8 d ca adjustment level ia 4 point shift amp E G For input type of analog x 2 nc y Upper Limit Set either p m Auto ManuarSwitek 3 y ce E HE AT Execute Cancel E NSH Temperature of these 2 A M PID control only B AL IH Alarm Value 11 Temperature Unit Bea OFF E25 0 0 Input Shift Value parameters 0 Added when ae g Upper Limit 1 5 E d u en fara i i Press the auto manual select kj oo r 3 cl A 2 point shift CI Key Cel addition is ON A SS FENA of F MI IL Communications Be NGL Lower Limit fe t Em_ col i gc 3 ge B CMNE Com LIVE for a 2 M SP Multi sP 8 AL I Alarm Value 2 R arr Ying Bs og Input Shift Value least 3 s l g Set Point Setting o oe Cc Si A S Se 1300 Ce y col I ce 8 Bes 1300 8 E I Heater Current 1 FH P Proportional Band E GP M Set Point During FAL o Aave 2 cel Limit me set point 5 an Value Monitor Ee gg E SP Ramp 2 5 g 5L SP Lower Limit 00 ss 8 0 pes a 2 z 200 ce j 4 a ie 5 200 r g fara E Hb IR B 1 Integral Time B TE Heater Current 1 Value 8 AL 2H Alarm Value ce BID NOE Bes Bea 233 oo Mo
20. A N vertical direction Maintain the specified Waterproof ae cae COVER T mounting space between Controllers 0 To mount the Controller so that it is g y 7 T t the Controll that it Accessory Accessory waterproof insert the waterproof packing onto the Controller When two or more Controllers are mounted make sure that the surrounding temperature does not exceed the i allowable operating temperature Note The terminal block cannot be removed specified in the spedi ications E5CN U Panel Cutout Plug in Models ar 84 7 ae Mounted Separately Group Mounted 70 5 mje 48 x number of units 2 5 6 i I 45 36 58 j 44 8 x 44 8 an 60 min i OOOO l 7 Recommended panel thickness is 1 to 5 lo mm J 0 Group mounting is not possible in the Mounting Adapter F 450 vertical direction Maintain the specified Accessory mounting space between Controllers y When two or more Controllers are te mounted make sure that the surrounding m 45 09 mt temperature does not exceed the allowable operating temperature specified in the specifications Accessories Order Separately USB Serial Conversion Cable E58 CIFQ1 2 100 gt 250 1 LED indicator SD i 1 765 22 FN DD Me SS USB connector type A plug ere Serial connector LED indicator RD GE RD 12 Basic type Digital Temperature Controller E5CN E5CN U OMRON Terminal Cover Waterproof Packing E53 COV17 Y92S 29 for DIN 48 x
21. ERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE OMRON DISCLAIMS ALL OTHER WARRANTIES EXPRESS OR IMPLIED LIMITATIONS OF LIABILITY OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL INDIRECT OR CONSEQUENTIAL DAMAGES LOSS OF PROFITS OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS WHETHER SUCH CLAIM IS BASED ON CONTRACT WARRANTY NEGLIGENCE OR STRICT LIABILITY In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY REPAIR OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED STORED INSTALLED AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION ABUSE MISUSE OR INAPPROPRIATE MODIFICATION OR REPAIR Application Considerations SUITABILITY FOR USE OMRON shall not be responsible for conformity with any standards codes or regulations that apply to the combination of products in the customer s application or use of the products Take all necessary steps to determine the suitability of the product for the systems machines and equipment with which it will be used Know and observe all prohibitions of use applicable to this product NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS AND THAT T
22. ERR S Er OFF a x input type the upper limit A D Turn the power OFF then back ON again If the display remains the same the controller must E 333 E333 converter be repaired If the display is restored to normal then a probable cause can be external noise OFF OFF error affecting the control system Check for external noise Memor Turn the power OFF then back ON again If the display remains the same the controller must E l H H E111 error y be repaired If the display is restored to normal then a probable cause can be external noise OFF OFF affecting the control system Check for external noise Note If the input value exceeds the display limit 1999 to 9999 though it is within the control range will be displayed under 1999 and 3333 above 9999 Under these conditions control output and alarm output will operate normally For details on the control range refer to the ES5CN ESAN ES5EN Digital Temperature Controllers User s Manual Basic Type Cat No H156 These errors are displayed only when the PV SP is displayed Errors are not displayed for other displays Basic type Digital Temperature Controller ESCN E5CN U 15 OMRON Parameters Basic Type Some parameters are not displayed depending on the model of the Controller and parameter settings For details refer to the E5CN E5AN E5EN Digital Temperature Controllers User s Manual Basic Type Cat No H156 Power ON Starting in manual mode S
23. HE OMRON PRODUCTS ARE PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM Disclaimers PERFORMANCE DATA Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty It may represent the result of OMRON s test conditions and the users must correlate it to actual application requirements Actual performance is subject to the OMRON Warranty and Limitations of Liability CHANGE IN SPECIFICATIONS Product specifications and accessories may be changed at any time based on improvements and other reasons Consult with your OMRON representative at any time to confirm actual specifications of purchased product DIMENSIONS AND WEIGHTS Dimensions and weights are nominal and are not to be used for manufacturing purposes even when tolerances are shown ALL DIMENSIONS SHOWN ARE IN MILLIMETERS To convert millimeters into inches multiply by 0 03937 To convert grams into ounces multiply by 0 03527 Cat No H04E EN 01 In the interest of product improvement specifications are subject to change without notice OMRON EUROPE B V Wegalaan 67 69 NL 2132 JD Hoofddorp The Netherlands Phone 31 23 568 13 00 Fax 31 23 568 13 88 www industrial omron eu 02 2008
24. Move to Advanced Function Setting Level Displayed when initial setting communications protect is set to 0 Move by setting password 169 EES mm re EJES oe m B n or 3 or Nu fg conn Eon Di ig Advanced Function Setting Level Parameter Initialization Multi SP Uses u SP Ramp Time Unit Standby Sequence Reset Auxiliary Output 1 Open in Alarm Auxiliary Output 2 Open in Alarm un rte lug 0000 Di p Auxiliary Output 3 Open in Alarm 3 dr oO c p OOD DI oo oP fo HB ON OFF 3 xh oO F p Oooo D og og sl or nm a Heater Burnout Latch co OF XT FE ooo Heater Burnout Hysteresis e xe 4 in fr ooo oF OF lt 4 r ppo pp 0000 ST Stable Range AT Calculated Gain AT Hysteresis Limit Cycle MV Amplitude Input Digital Filter Additional PV Display MV Display Automatic Display Return Time Alarm 1 Latch Alarm 2 Latch Alarm 3 Latch Move to Protect Level Time Input Error Output OO 0000 Cold Junction Compensation Method poooo0
25. N 61010 1 IEC 61010 1 Pollution level 2 overcurrent category II EMI EN 61326 Radiated Interference Electromagnetic Field Strength EN 55011 Group 1 class A Noise Terminal Voltage EN 55011 Group 1 class A EMS EN 61326 ESD Immunity EN 61000 4 2 EMC Electromagnetic Field Immunity EN 61000 4 3 Burst Noise Immunity EN 61000 4 4 Conducted Disturbance Immunity EN 61000 4 6 Surge Immunity EN 61000 4 5 Power Frequency Magnetic Field Immunity EN 61000 4 8 Voltage Dip Interrupting Immunity EN 61000 4 11 1 The indication accuracy of K thermocouples in the 200 to 1300 C range T and N thermocouples at a temperature of 400 C max and U and L thermocouples at any temperatures is 22 C 1 digit max The indication accuracy of the B thermocouple at a temperature of 400 C max is not specified The indication accuracy of B thermocouples in the 400 to 800 C range is 3 C max The indication accuracy of the R and S thermocouples at a temperature of 200 C max is 43 C 1 digit max The indication accuracy of W thermocouples is 0 3 of PV or 43 C whichever is greater 1 digit max The indication accuracy of PL II thermocouples is 0 3 of PV or 42 C whichever is greater 1 digit max 2 4 5 7 Ambient temperature 40 C to 23 C to 55 C Voltage range 45 to 10 of rated voltage K thermocouple at 400 C max 10 max EU stands for Engineering Unit and is used as the unit after scaling For a temperature sensor the
26. O NOT i gt gt i gt 4 to 20 mA DC USE I I B Input power supply 0 to 20 mA DC i Load 600 W max mA Volt Te Pt 100 to 240 VAC Analog input Temperature 24 VACIVDG no polarity input Note For the Wiring Socket purchase the P2CF 11 or PG3A 11 separately Basic type Digital Temperature Controller E5CN E5CN U 11 OMRON Nomenclature E5CN E5CN U The front panel is the same for the ESCN and E5CN U Temperature unit S HH PV E M I vi MI AAA NT fa ae a Waa S JALIL A A No 1 display STOP Dra mn vana No 2 display Mode Key Dimensions Unit mm ESCN Panel Cutout Terminal Models Mounted Separately Group Mounted el 91 g 48 x number of units 2 5 5 mm 78 al 01 5 j g 1 kd 45798 58 1448x448 48 8 60 min Group mounting does not 3 1 allow waterproofing 40 6 Recommended panel thickness is 1 to X 450 5 mm 1 Group mounting is not possible in the
27. OMRON Basic type Digital Temperature Controller E5CN E5CN U 48 x 48 mm New 48 x 48 mm Basic Temperature Controller with Enhanced Functions and Performance Improved Indication Accuracy and Preventive Maintenance Function e Indication Accuracy Thermocouple input 0 3 of PV previous models 0 5 Pt input 0 2 of PV previous models 0 5 Analog input 0 2 FS previous models 0 5 pag rill SCR e New E5CN U Models Plug in Models with analog inputs and current outputs e A PV S V status display function can be set to alternate between displaying the PV or SV and the status of the Temperature Controller auto manual RUN STOP and alarms e Preventive maintenance for relays using a Control Output ON OFF Counter A Refer to Safety Precautions on page 18 Main I O Functions Event Inputs 2 line Display PV and SV 4 digit 11 segment display e None ours sie or e Two Auto manual switching Temperature Controller status display LJ Pee p gt 2 Auxiliary Outputs Simple program function Sensor Inputs e Universal thermocouple Pt inputs Models with temperature inputs Analog current voltage inputs Models with analog inputs Control output ON OFF count alarm PV change rate alarm Models optional with RS 485 communications Control Output 2 e None Indication Accuracy Voltage output e Thermocouple input 0 3 of PV for drivin
28. P20 Terminal section IP00 E5CN U Front panel IP50 rear case IP20 terminals IP00 Operating Precautions 1 It takes approximately two seconds for the outputs to turn ON from after the power supply is turned ON Due consideration must be given to this time when incorporating Temperature Controllers ina sequence circuit 2 When using self tuning turn ON power for the load e g heater at the same time as or before supplying power to the Temperature Controller If power is turned ON for the Temperature Controller before turning ON power for the load self tuning will not be performed properly and optimum control will not be achieved 3 When starting operation after the Temperature Controller has warmed up turn OFF the power and then turn it ON again at the same time as turning ON power for the load Instead of turning the Temperature Controller OFF and ON again switching from STOP mode to RUN mode can also be used 4 Avoid using the Controller in places near a radio television set or wireless installing These devices can cause radio disturbances which adversely affect the performance of the Controller Others 1 The disk that is included with the Conversion Cable is designed for a computer CD ROM driver Never attempt to play the disk ina general purpose audio player 2 Do not connect or disconnect the Conversion Cable connector repeatedly over a short period of time The computer may malfunction 3 A
29. SYSWAY only Bos 1050 setting and advanced function setting cal som g ees 105 0 levels wed ce IB 1L L Setting Change Protect 8 LEN Communications Be Ah IS WEPE Protects changes to setups by En nm Data Length B ol 1 MV Lower Limit GFF operating the front panel keys Eee i z ee ees 5 0 ce 1 es Ce B PM 5 K Parameter Mask Enable B She E Saet a a TI Displayed only when a ace 2 E ofL MV Change Rate Limit SE oN parameter mask is set eee B 00 re le AS SAN I A B PRLP password S Meta to Protect Level g PREY Communications Parity g ao EVEN E GRP Extraction of Square Root Ez a EVEN e T Low cut Point ce a B Sd Send Data Wait Time 20 ic 16 Basic type Digital Temperature Controller E5CN E5CN U OMRON ry ml Alh CI Fu g du falh amp ru pp 0000 Press the O Key for at least 1 s Alarm 2 Type Alarm 2 Hysteresis Alarm 3 Type Alarm 3 Hysteresis Transfer Output Type Linear output Transfer Output Upper Limit Transfer Output Lower Limit Linear Current Output Linear output Number of Multi SP Uses Two SPs 1 Four SPs 2 Event Input Assignment 1 Event Input Assignment 2 Extraction of Square F Root Enable
30. al power supply for E53 CNPBN2 Communications RS 485 E53 CN03N2 Communications Control output 2 RS 485 Voltage for driving SSR E53 CNQ03N2 Communications Heater burnout SSR failure Heater RS 485 overcurrent detection E53 CNH03N2 Communications 3 phase heater burnout SSR failure RS 485 Heater overcurrent detection E53 CNHH03N2 Communications External power supply for RS 485 ES1B E53 CNP03N2 Heater burnout SSR failure Heater overcurrent detection Control output 2 Voltage for driving SSR E53 CNQHN2 3 phase heater burnout SSR failure Heater overcurrent detection Control output 2 Voltage for driving SSR E53 CNQHHN2 Heater burnout SSR failure Heater overcurrent detection External power supply for ES1B E53 CNPHN2 Note Option Units cannot be used for plug in models These Option Units are applicable only to models produced after January 2008 Box marked with N6 Basic type Digital Temperature Controller E5CN E5CN U 3 OMRON Model Number Structure Model Number Legend Plug in type Controllers E5CN O020U 1234 1 Output Type 3 Input Type R Relay output T Universal thermocouple platinum resistance thermometer Q Voltage output for driving SSR L Analog Input C Current output 4 Plug in type 2 Number of Alarms U Plug in type 2 Two alarms Ordering Information Plug in type Controllers Size Case color Power sup
31. can be set independently for each alarm type and are expressed as gt and H 2 Set value 1 Upper and lower limit alarm Case 1 Case 2 Case 3 Always ON L H SP SPL H H SP L H lt 0 L gt 0 H gt 0 L lt 0 eiet IHI lt IL IHl gt IL AESP TEIE H gt 0 L lt 0 SPH L H lt L 3 Set value 4 Upper and lower limit range Case 1 Case 2 Case 3 Always OFF L HSP SPL H H SP L H lt 0 L gt 0 H gt 0 L lt 0 H lt 0 L gt 0 H lt ILI IH gt ILI H LSP IH gt ILI H gt 0 L lt 0 SPH L IH lt ILI 3 4 Set value 5 Upper and lower limit with standby sequence For Upper and Lower Limit Alarm Described Above e Case 1 and 2 Always OFF when the upper limit and lower limit hysteresis overlaps e Case 3 Always OFF 5 Set value 5 Upper and lower limit with standby sequence Always OFF when the upper limit and lower limit hysteresis overlaps Basic type Digital Temperature Controller E5CN E5CN U OMRON Characteristics Indication accuracy Thermocouple 1 Terminal block models ESCN 0 3 of indicated value or 1 C whichever is greater 1 digit max Plug in models E5CN U 1 of indicated value or 22 C whichever is greater 1 digit max Platinum resistance thermometer input Terminal block models E5CN and plug in models E5CN U 40 2 of indicated value or 0 8 C whichever is greater 1 digit max Analog input Terminal block models E5CN and plug in models ES5CN U 40 2 FS 1 digit max
32. d 5 V 10 mA Relay output e aes r ae SPDT 250 VAC 3A resistive load electrical life 100 000 operations minimum applicable load E5CN U 5V 10 mA Control Voltage output E5CN Output voltage 12 VDC 15 PNP max load current 21 mA with short circuit protection outputs for driving SSR E5CN U circuit Current output E5CN 4 to 20 mA DC 0 to 20 mA DC load 600 Q max resolution approx 10 000 SPST NO 250 VAC 3 A resistive load electrical life 1 000 000 operations load power supply E5CN voltage 75 to 250 VAC DC loads cannot be connected minimum applicable load 5 V 10 mA leakage current 5 mA max 250 VAC 60 Hz Long life relay output Sh Number of outputs 2 Auxiliary outputs Output specifica Relay output SPST NO 250 VAC 3 A resistive load electrical life 100 000 operations minimum tions applicable load 5 V 10 mA Number of inputs 2 Event External contact Contact input ON 1 KQ max OFF 100 kQ min inputs input specifica Non contact input ON Residual voltage 1 5 V max OFF Leakage current 0 1 mA max tions Current flow Approx 7 mA per contact External power supply for ES1B 12 VDC 10 20 mA short circuit protection circuit provided Setting method Digital setting using front panel keys 11 segment digital display and individual indicators 7 segment display emulation also possible Character height PV 11 mm SV 6 5 mm Up to four set
33. e 2 Heater overcurrent alarm setting range 3 15 FS 1 digit max 0 1 to 49 9 A in units of 0 1 A Minimum detection ON time 100 ms 0 1 to 49 9 A in units of 0 1 A Minimum detection OFF time 100 ms 0 1 to 49 9 A in units of 0 1 A Minimum detection ON time 100 ms 1 For heater burnout alarms the heater current will be measured when the control output is ON and the output assigned to the alarm 1 function will turn ON if the heater current is lower than the set value i e heater burnout detection current value 2 For SSR failure alarms the heater current will be measured when the control output is OFF and the output assigned to the alarm 1 function will turn ON if the heater current is higher than the set value i e SSR failure detection current value 3 For heater overcurrent alarms the heater current will be measured when the control output is ON and the output assigned to the alarm 1 function will turn ON if the heater current is higher than the set value i e heater overcurrent detection current value Electrical Life Expectancy Curve for Relays Reference Values a 500 5 300 oO a o 100 Ra o 50 30 10 SI E5CN 3 250 VAC 30 VDC resistive load coso 1 1 0 1 2 3 4 5 6 Switching current A Note Do not connect a DC load to a Controller with a Long life Relay Output
34. et Make sure that the UP mark is facing up and then attach the E53 COV17 Terminal Cover to the holes on the top and bottom of the Temperature Controller Removing the Temperature Controller from the Case The Temperature Controller can be removed from the case to perform maintenance without removing the terminal leads This is possible for only the E5CN E5AN and E5EN and not for the ESCN U Check the specifications of the case and Temperature Controller before removing the Temperature Controller from the case Tool insertion hole Flat blade screwdriver Unit mm A im 0 4 2 0 Insert a flat blade screwdriver into the two tool insertion holes one on the top and one on the bottom to release the hooks 2 Insert the flat blade screwdriver in the gap between the front panel and rear case and pull out the front panel slightly Hold the top and bottom of the front panel and carefully pull it out toward you without applying unnecessary force 3 When inserting the body of the Temperature Controller into the case make sure the PCBs are parallel to each other make sure that the sealing rubber is in place and press the ESCN toward the rear case into position While pushing the E5CN into place push down on the hooks on the top and bottom surfaces of the rear case so that the hooks are securely locked in place Be sure that electronic components do not come into contact with the case
35. f 0 1 Alarm setting range 1999 to 9999 decimal point position depends on input type Affect of signal source resis tance Thermocouple 0 1 C Q max 100 Q max Platinum resistance thermometer 0 1 C Q max 10 Q max Insulation resistance 20 MQ min at 500 VDC Dielectric strength 2 300 VAC 50 or 60 Hz for 1 min between terminals with different charge Vibration Malfunction 10 to 55 Hz 20 m s for 10 min each in X Y and Z directions resistance Destruction 10 to 55 Hz 0 75 mm single amplitude for 2 hrs each in X Y and Z directions Shock Malfunction 100 m s 3 times each in X Y and Z directions resistance Destruction 300 m s 3 times each in X Y and Z directions Weight E5CN Controller Approx 150 g Mounting Bracket Approx 10 g E5CN U Controller Approx 110 g Mounting Bracket Approx 10 g Degree of E5CN Front panel IP66 Rear case IP20 Terminals IP00 protection E5CN U Front panel IP50 Rear case IP20 Terminals IP00 Memory protection Non volatile memory number of writes 1 000 000 times Setup Tool CX Thermo version 4 0 or higher Setup Tool port Provided on the bottom of the E5CN Use this port to connect a computer to the ESCN when using the Setup Tool An E58 CIFQ1 USB Serial Conversion Cable is required to connect the computer to the E5CN 6 Approved standards x7 UL 61010 1 CSA C22 2 No 1010 1 Standards Conformed E
36. fter connecting the Conversion Cable to the computer check the COM port number before starting communications The computer requires time to recognize the cable connection This delay does not indicate failure 4 Do not connect the Conversion Cable through a USB hub Doing so may damage the Conversion Cable 5 Do not use an extension cable to extend the Conversion Cable length when connecting to the computer Doing so may damage the Conversion Cable Basic type Digital Temperature Controller ESCN E5CN U 19 OMRON Mounting Mounting to a Panel For waterproof mounting waterproof packing must be installed on the Controller Waterproofing is not possible when group mounting several Controllers Waterproof packing is not necessary when there is no need for the waterproofing function Order the P2CF 11 or P3GA 11 Socket separately E53 COV17 Terminal Cover Accessory Adapter Accessory one ae Z EON 1 The Panel Mounting Adapter is also included with the ESCN U There is no waterproof packing included with the ESCN U 2 Insert the ESCN ESCN U into the mounting hole in the panel 3 Push the adapter from the terminals up to the panel and temporarily fasten the E5CN E5CN U 4 Tighten the two fastening screws on the adapter Alternately tighten the two screws little by little to maintain a balance Tighten the screws to a torque of 0 29 to 0 39 N m Mounting the Terminal Cover For Front mounting Sock
37. g SSR e Pt input 0 2 of PV e Analog input 0 2 FS Control Output 1 e Relay output e Voltage output for driving SSR Current output Long life relay output hybrid and other information required for operation before attempting to use the product E5CN E5AN E5EN Digital Temperature Controllers User s Manual Basic Type Cat No H156 E5CN E5AN E5EN Digital Temperature Controllers Communications Manual Basic Type Cat No H158 L Basic type Digital Temperature Controller E5CN E5CN U 1 OMRON Lineup 2 auxiliary outputs 1 control output 2 control outputs Terminal block 1 control output Analog input EVE 2 control outputs Basic Type Temperature input 1 control output Analog input 1 control output Note All models can be used for Heating Cooling and Heating amp Cooling control Temperature input 2 auxiliary outputs 2 auxiliary outputs 2 auxiliary outputs 2 auxiliary outputs 2 auxiliary outputs Model Number Structure Model Number Legend Controllers Option Units E5CN U12 MU U 500 E53 CNUUIN2 12345 6 7 1 23 4 1 Control Output 1 1 Applicable Controller R Relay output CN E5CN Q Voltage output for driving SSR 2 Function 1 C Current output Y L life rel tput hybrid 1 Blank None pee Sa te Q Control output 2 voltage for driving SSR 2 Auxiliary Outputs k2 P Power sup
38. ications Specifications Transmission line connection method RS 485 Multipoint Communications RS 485 two wire half duplex Synchronization method Start stop synchronization Protocol CompoWay F SYSWAY or Modbus Baud rate 1200 2400 4800 9600 19200 38400 or 57600 bps Transmission code ASCII Data bit length 7 or 8 bits Stop bit length 1 or 2 bits Error detection Vertical parity none even odd Frame check sequence FCS with SYSWAY Block check character BCC with CompoWay F or CRC 16 Modbus Flow control None Interface RS 485 Retry function None Communications buffer 217 bytes Communications 0 to 99 ms response wait time The baud rate data bit length stop bit length and vertical parity can Default 20 ms be individually set using the Communications Setting Level Dielectric strength 1 000 VAC for 1 min Vibration resistance 50 Hz 98 m s E54 CT1 Approx 11 5 g E54 CT3 Approx Weight 50g Accessories Armatures 2 E54 CT3 only Plugs 2 Heater Burnout Alarms SSR Failure Alarms and Heater Overcurrent Alarms Models with detection for single phase CT input heaters One input ead EKEN Ce Models with detection for single phase or three phase heaters Two inputs Maximum heater current 50 A AC Input current indication accuracy Heater burnout alarm setting range 1 SSR failure alarm set ting rang
39. nitor a g Upper Limit 2 5 5 i 88 5 ce cal PID settings ce B Ar Heater Overcurrent B Derivative Time o 3 EB oci 5 d TEL 2 Heater Current 2 Value zm 2 Alarm Value 3 gt coo eee Se can Bt Ee Monitor AL EL LowerLimit2 Standard or eal di Es ao Bi a Heating Cooling v ce y r d ce ce a or Heater Current 2 B C 5C Cooling Coefficient 5 ES E Ee Value Monitor Bo S 2 LCR Leakage Current 1 BAL 3 RENS ER T s ee og 00 Ee ag Monitor a a ST Self tuning A i Ees 2 SE r 5 For input type of cel i Sa Hento gcaoind J Ico y Ce a temperature standard EJ per ay DQ control or PID g Nbc seen HEC db Ree ELCRelkaggecumeme FA Hee e Piet Pana ees 09 B 00 amp ooh onor i Upper Limit 3 5 E gt oa Sen ce I Ce I gt PEE When assigning PID or oO control output to ON OFF Be er 5 AF Manual Reset Value 2 OL 2 Heater Overcurrent Bor R Clear the offset during 2 PAS Program Start Alarm Value 3 output ees soo Detection 2 Bs 50 0 stabilization of P or PD Bes PSEL ial mo 500 i EEH 3 control Control Period Heating 3 I FRA Leak Ci t1 B Hysteresis Heating a cI Soak Time Remain a Set the ON OFF B k Ra R en EM HS 2 SKER MV Monitor Heating output cycle Leis Hu GES en Bes a Control Period Cooling J y ce Hysteresis settings A B HE 1 HS Alarm 1 THYS Hysteresis Cooling B ER MV Monitor Cooling gt 500 East ia am Direct Reverse Operation je ye E FR Leakage
40. omponent service life is affected by the ambient temperature the higher the temperature the shorter the service life and the lower the temperature the longer the service life Therefore the service life can be extended by lowering the temperature of the Temperature Controller 3 When two or more Temperature Controllers are mounted horizontally close to each other or vertically next to one another the internal temperature will increase due to heat radiated by the Temperature Controllers and the service life will decrease In such a case use forced cooling by fans or other means of air ventilation to cool down the Temperature Controllers When providing forced cooling however be careful not to cool down the terminals sections alone to avoid measurement errors Measurement Accuracy 1 When extending or connecting the thermocouple lead wire be sure to use compensating wires that match the thermocouple types 2 When extending or connecting the lead wire of the platinum resistance thermometer be sure to use wires that have low resistance and keep the resistance of the three lead wires the same 3 Mount the product so that it is horizontally level 4 If the measurement accuracy is low check to see if input shift has been set correctly Waterproofing The degree of protection is as shown below Sections without any specification on their degree of protection or those with IPLIO are not waterproof Front panel IP66 Rear case I
41. ply for sensor 2 Two outputs 3 Function 2 3 Option Blank None M Option Unit can be mounted H Heater burnout SSR failure Heater overcurrent detection CT 1 HH Heater burnout SSR failure Heater overcurrent detection For 3 phase heater applications 2x CT B Two event inputs 03 RS 485 communications 4 Input Type T Universal thermocouple platinum resistance thermometer L Analog current voltage input 5 Power Supply Voltage H03 Heater burnout SSR failure Heater overcurrent detection Blank 100 to 240 VAC CT1 RS 485 communications D 24 VAC VDC HB Heater burnout SSR failure Heater overcurrent detection CT1 Two event inputs 6 Case Color HHO3 Heater burnout SSR failure Heater overcurrent detection Blank Black For 3 phase heater applications 2x CT W Silver contact your local sales for more information 4 Version 7 Terminal Cover N2 Applicable only to models produced after January 2008 500 With terminal cover Box marked with N6 Note Not all combinations of function 1 and function 2 specifications are possible for Option Units E53 CNUILIN2 1 Always connect an AC load to a long life relay output The output will not turn OFF if a DC load is connected because a triac is used for switching the circuit For details check the conditions in Ratings 2 Auxiliary outputs are contact outputs that can be used to output alarms control or results of logic operations 2 Basic type Digi
42. ply voltage Input type Auxiliary outputs Control output 1 Model Thermocouple Relay output E5CN R2TU or resistance 2 Voltage output for driving SSR E5CN Q2TU thermometer Current output E5CN C2TU 100 to 240 VAC Relay output E5CN R2LU Analog T i 1 16 DIN Black current voltage 2 Voltage output for driving SSR ESCN Q2LU Current output E5CN C2LU Thermocouple Relay output E5CN R2TDU 24 VAC VDC or resistance 2 Voltage output for driving SSR ESCN Q2TDU thermometer Current output E5CN C2TDU Note add power supply voltage to model to complete ordering code ie E5CN R2TU AC100 240 or ESCN R2TDU AC DC24 4 Basic type Digital Temperature Controller E5CN E5CN U Accessories Order Separately USB Serial Conversion Cable Model E58 CIFQ1 OMRON Adapter Connectable models Model Terminal block models Y92F 45 Terminal Cover Connectable models Terminal block models Model E53 COV17 Note The Terminal Cover comes with the E5CN 500 models Waterproof Packing Model Y92S 29 Note Use this Adapter when the panel has been previously prepared for the E5BLI 72x72 mm panel cut out Sockets for Plug in Models Type Model Front connecting Socket P2CF 11 Front connecting Socket with Finger Protection P2CF 11 E Back connecting Socket P3GA 11 Terminal Cover for Back connecting socket with z Finger Protection Y92A 48G Note The Wa
43. re allocated for alarms ON delays and OFF delays 0 to 999 s can also be specified Note For models with heater burnout SSR failure and heater overcurrent detection alarm 1 will be an OR output of the alarm selected from the following alarm types and the alarms for heater burnout SSR failure and heater overcurrent To output only a heater burnout alarm SSR failure alarm and heater overcurrent alarm for alarm 1 set the alarm type to 0 i e no alarm function Set Alarm output operation vares Alarm type When X is When X is positive negative 0 oc function Output OFF 1 Upper and lower on 42 1 limit OFF SP x xX ie 2 Upper limit oN _ 1 an SP SP xX X 3 Lower limit oe Bee SP SP 4 Upper and lower on HEH 3 1 limit range OFF SP 5 Upper and lower on 1 limit with standby OFF SP 4 sequence 5 6 Upper limit with ON 7 oe on X standby sequence OFF SP on SP z Lower limit with o ST ON a standby sequence OFF SP or SP 8 Absolute value ON E ON FE upper limit Or OFF o 9 Absolute value ON ie ON lower limit eT OFF o Absolute value PENER SM lex 10 upper limit with ae I ore standby sequence 0 2 Absolute value lenX le X 1 11 lower limit with ov or EL standby sequence 2 j LBA 7 for alarm 1 only 13 PV change rate E alarm 1 With set values 1 4 and 5 the upper and lower limit values
44. rning ON the power using a switch or relay contact If the voltage is applied gradually the power may not be reset or output malfunctions may occur 10 Make sure that the Temperature Controller has 30 minutes or more to warm up after turning ON the power before starting actual control operations to ensure the correct temperature display 18 Basic type Digital Temperature Controller E5CN E5CN U OMRON 11 When executing self tuning turn ON power to the load e g heater at the same time as or before supplying power to the product If power is turned ON to the product before turning ON power to the load self tuning will not be performed properly and optimum control will not be achieved 12 A switch or circuit breaker must be provided close to the product The switch or circuit breaker must be within easy reach of the operator and must be marked as a disconnecting means for this unit 13 Always turn OFF the power supply before pulling out the interior of the product and never touch nor apply shock to the terminals or electronic components When inserting the interior of the product do not allow the electronic components to touch the case 14 Do not use paint thinner or similar chemical to clean with Use standard grade alcohol 15 Design the system e g control panel considering the 2 seconds of delay that the product s output to be set after power ON 16 The output may turn OFF when shifting to certain levels Take this into
45. tal Temperature Controller E5CN E5CN U Ordering Information OMRON Controllers with Terminal Blocks Size Case color ER Input type Auxiliary outputs Control output 1 Model Relay output E5CN R2MT 500 Thermocouple or Voltage output for driving SSR E5CN Q2MT 500 100 to 240 VAC Resistance thermometer Current output E5CN C2MT 500 Long life relay output hybrid E5CN Y2MT 500 Relay output E5CN R2MTD 500 Thermocouple or 24 VAC VDC Resistance Voltage output for driving SSR E5CN Q2MTD 500 1 16 DIN thermometer Current output E5CN C2MTD 500 48 x 48x 78 Black Wx Hx D Relay output E5CN R2ML 500 Voltage output for driving SSR E5CN Q2ML 500 100 to 240 vac NAIC volt calla goa current voltage Current output E5CN C2ML 500 Long life relay output hybrid E5CN Y2ML 500 Relay output E5CN R2MLD 500 Anal a 24 VAC VDC currentWv llage Voltage output for driving SSR E5CN Q2MLD 500 Current output E5CN C2MLD 500 Note add power supply voltage to model to complete ordering code ie ESCN R2MT 500 AC100 240 or ESCN R2MTD 500 AC DC24 Option Units One of the following Option Units can be mounted to provide the E5CN with additional functions Functions Model Event inputs E53 CNBN2 Event inputs Control output 2 E53 CNQBN2 p Voltage for driving SSR Heater burnout SSR failure Heater Event inputs overcurrent detection E53 CNHBN2 Event inputs Extarn
46. tarting in Press the O Key for at least 3 s automatic Other than the Auto Manual Switch display mode Manual Control Level Press the O Key for at least 1 s Press the O Key for at least 1 s Press the O Key less than 1 s DO O000 L N H Input Type 5 Adjustment Press the Mizz Level IS ML H Scaling Upper Limit a 49 Press the O Key less than 1 s Ee 190 g Process Value RUN STOP Se es El Added
47. terproof Packing is included with the Controller only for models with terminal blocks Current Transformers CTs Hole diameter Model 5 8 dia E54 CT1 12 0 dia E54 CT3 CX Thermo Support Software Model EST2 2C MV4 Basic type Digital Temperature Controller E5CN E5CN U 5 OMRON Specifications Ratings No D in model number 100 to 240 VAC 50 60 Hz D in model number 24 VAC 50 60 Hz 24 VDC Operating voltage range 85 to 110 of rated supply voltage 100 to 240 VAC 7 5 VA max ESCN R2T at 100 VAC 3 0 VA Power supply voltage Power maa 24 VAC VDC 5 VA 3 W max ESCN R2TD at 24 VAC 2 7 VA consump tion E5CN U 100 to 240 VAC 6 VA max 24 VAC VDC 3 VA 2 W max models with current output 4 VA 2 W Models with temperature inputs Thermocouple K J T E L U N R S B W or PL II Platinum resistance thermometer Pt100 or JPt100 Infrared temperature sensor 10 to 70 C 60 to 120 C 115 to 165 C or 140 to 260 C Sensor input Voltage input 0 to 50 mV Models with analog inputs Current input 4 to 20 mA or 0 to 20 mA Voltage input 1 to 5 V 0 to 5 V or O to 10 V Input impedance Current input 150 Q max Voltage input 1 MQ min Use a 1 1 connection when connecting the ES2 HB Control method ON OFF control or 2 PID control with auto tuning SPST NO 250 VAC 3 A resistive load electrical life 100 000 operations minimum applicable E5CN 3 loa
48. xternal Power RS 485 and CT2 and CT RS 485 and External Power Supply Supply and CT Control Output 2 O External En GI power supply eva gt Eva DO NOT USE 14 External 12 VDC CT1 CTIE d T T power supply 20mA CTL E53 CNHO3N2 E53 CNO3N2 E53 CNBN2 E53 CNQHN2 E53 CNQHHN2 Communications Communications Event inputs Control Output 2 Control Output 2 RS 485 and CT RS 485 and CT and CT2 BER D Control output 2 VPN 12 a EV2 Control output 2 A heater burnout alarm heater short alarm heater overcurrent alarm or input alarm is sent to the output to which the alarm 1 function is assigned E53 CNP03N2 Communications RS 485 and External Power Supply E53 CNQBN2 Event Inputs and Control Output 2 DO NOT Pa nor A3 EV2 DO NOT 42 i CT2 USE CTIL Control output 2 DO NOT _ USE a n E5CN U Auxiliary output 250 VAC 3 A resistive load 1 71 Relay outputs Control output 1 et Relay output Control output 1 Auxiliary output 1 three terminals used aq eis e Auxiliary output 2 SPDT 250 VAC 3 A A Control output cooling side resistive load I TONE I PONOT I L f r vind SSH mA I I I B An input error is sent to the or driving I I i output to which the alarm 1 12 VDC 21 mA lg I y a IS 4 l gt t function is assigned Current output D
49. y will flash E 75 after 1st second Manual Control Level Press the O Key for at least 1 s Protect Level Note The time taken to move to the protect SAMLE level can be adjusted tions Setting by changing the Control stops gt pas Move to protect level Press the time setting O Key for less than 1 s Input password while Press the O Key AMay is displayed Set for at least 1 s value 169 Advanced Function Setting Level Input password Calibration Level 1 You can return to the operation level by executing a software reset 2 It is not possible to move to other levels from the calibration level by operating the keys on the front panel It can be done only by first turning OFF the power 3 From the manual control level key operations can be used to move to the operation level only Control in progress Control stopped x2 Not displayed for some models 1900 Level change Error Displays Troubleshooting When an error occurs the No 1 display shows the error code Take necessary measure according to the error code referring the table below T 5 x Status at error No 1 display Meaning Action Control output Alarm output coo Input error Check the wiring of inputs for miswiring disconnections and short circuits and check the Operates as above G