PlantScape integration with Honeywell recorder/controllers using

image

Contents

1. definition Baud Rate 19200 or 38400 Must match that in Main tab s Port parameter definition Number of Data Bits 8 Stop Bits 1 Parity NONE Checksum NONE XON XOFF NONE RS 232 All boxes unchecked RS 485 All boxes unchecked 11 3 99 Revision 1 1 Page 3 of 6 CONTROLLER CONFIGURATION Controller parameters must be configured such that the PlantScape system recognizes the device as a generic Modbus RTU device Note that when setting up the device parameters it must match the parameters of the physical device being configured Follow the steps below to properly set up the Controller configuration 1 Select the Controller tab card in the Quick Builder main window 2 Select the button in the tool bar to bring up the Add Items window 3 Select the Generic device type from the list and click the OK button A configuration window will be shown for the new controller Configure the parameters in the Main tab card as follows MAIN TAB Parameter Data Name User chosen text string defining name of controller ThisController for example Description User chosen text description of controller optional Channel Name Select the desired channel name configured for use with this controller from the pull down menu Definition Example followed by field definitions 0 name ThisController marg 25 fail 50 id 1 devtype generic F01 96 F02 96 F03 127 F04 127 BDCAP 1F
2. 7 FLAGS 1B DIAG 1800 name is a user defined text string defining name of controller This string must be the same as Name parameter immediately above marg defines when communication to the controller becomes marginal 25 is a common value fail defines when the communication to the controller has failed and halts operation 50 is a common value id is device s Modbus RTU Address Integer value configured on physical device Must be unique to device where multiple devices are present on a single physical port 11 3 99 Revision 1 1 Page 4 of 6 POINT CONFIGURATION Points fall into two major categories based on data type Analog points are characterized by having real values and are represented by the IEEE floating point numerical format Status points are characterized by having discrete values in two states represented by either a zero or one While these points differ in format their configuration in terms of being displayed by the PlantScape Vista system is the same Both types will have available a Display tab card that must be configured in order for the points to be displayed on the PlantScape screens To display a point s data on a PlantScape Vista Station screen the user must fill in the Display tab card with trend and or group number and position information ANALOG POINT TYPE Analog point types include Analog Inputs Calculated Values Constants Totalizers Alarm Set Points etc The basis of configuring a p
3. Honeywell PlantScape Vista UMB Modbus RTU Interface Application Bulletin by Glenn Heidel INTRODUCTION This document is intended for use as a guide to connecting Honeywell recorder controller devices such as UDC DR DPR UMC VPR or VRX products to a PlantScape Vista system using the Modbus RTU communication protocol This document covers the configuration of the parameters in the PlantScape system related to monitoring or controlling Modbus RTU devices and their associated points It does not discuss hardware configurations wiring or any specifics for devices to be connected In order to monitor and or control points within a Modbus RTU device one must configure a project channel controller and points on the PlantScape Vista system This bulletin serves as an aide to configuring the required information especially regarding the addressing of the different entities to be configured REFERENCE DOCUMENTS 1 Modbus RTU Serial Communication User Manual 51 52 25 66 11 3 99 Revision 1 1 Page 1 of 6 Modbus RTU Serial Communications Link PlantScape Vista PROJECT CONFIGURATION The Quick Builder tool will be used to perform the necessary configurations starting with the project file that contains the configuration data for the generic interface Upon creating a new project file qdb the Quick Builder tool will present a set of tab cards in a window titled Setup Data needs to be entered in three t
4. ab cards for a generic Modbus RTU device Channels Controllers and Points Follow the steps below to properly set up the Project configuration 1 Inthe Channel tab card the Generic channel type selection box must be checked This will allow for configuration of generic channels using the Modbus RTU protocol 2 Inthe Controller tab card the Generic controller type selection box must be checked This will allow for configuration of generic controllers using the Modbus RTU protocol 3 In the Points tab card both the STATUS and ANALOG point types selection boxes must be checked These selections will allow for configuration of all the point types required to monitor control points supported in the Modbus RTU protocol 4 Once the tab cards in the Setup window are configure and the OK button is selected the configurations will be accepted and the Quick Builder main window will be exposed The Project tab card should be selected and in this tab card the user can enter a user defined Project Name and optional project Description 11 3 99 Revision 1 1 Page 2 of 6 CHANNEL CONFIGURATION The channel used by PlantScape Vista must be configured to use the Modbus RTU protocol with the correct data communications parameters Note that when setting up channel protocol parameters they must match the parameters of the physical device being configured Follow the steps below to properly set up the Chann
5. b Parameter Data Setpoint SP Dest Address Must be identical to the Main tab s PV Source Address field This applies to all of the analog point types Setpoint SP Source Address Must be left blank PV Scan Period Must be non zero Setpoint SP Low Control Limit _ Enter the engineering unit low limit of the point to be controlled Setpoint SP High Control Limit Enter the engineering unit high limit of the point to be controlled 11 3 99 Revision 1 1 Page 5 of 6 STATUS POINT TYPE Status point types include Discrete Inputs Discrete Outputs Alarm Status Calculated Value Status and Totalizer Status The basis of configuring a point with a Status Data type is as follows 1 Select the Points tab card in the Quick Builder main window 2 Select the button in the tool bar to bring up the Add Items window 3 Select the Status point type from the list and click the OK button A point configuration window will be shown for the new point The Main tab must be filled out for all status points There are three different configurations required depending on whether the point is a Discrete Input Discrete Output or a status bit status bits generally represent the output status OS parameter from an analog point An example of each of the three status point types is shown in the table below DI 1 DO1 and AL 1 OS will be used in the examples below Configuration of any oth
6. ed by subtracting one from point number PV Scan Period Must be non zero Scanning Enabled Box must be checked 11 3 99 Revision 1 1 Page 6 of 6
7. el configuration 1 Select the Channel tab card in the Quick Builder main window 2 Select the button in the tool bar to bring up the Add Items window 3 Select the Generic device type from the list and click the OK button A configuration window will be shown for the new channel Configure the parameters in the Main and Port tab cards as follows MAIN TAB Parameter Data Name User chosen text string defining name of channel ThisChannel for example Description User chosen text description of channel optional Port SERIAL port com1 baud 38400 data 8 parity none stop 1 write 3 Example port can also be com2 etc Peed ney baud may also be 19200 write should be set to 5 if baud 19200 or 3 if baud 38400 NOTE If the communications link contains a UDC2300 UDC3300 DR4500 ver 57 58 or a DR4300 Ver 4 the write delay must be set to 20 Definition UMB name ThisChannel marg 25 fail 50 Example name is a user chosen text string defining name of channel This string must be the followed by field same as Name parameter immediately above ealinitions marg defines when communication channel s condition becomes marginal 25 is a common value fail defines when the communication channel has failed and halts operation 50 is a common value PORT TAB Parameter Data Port Type Serial Serial Port Name COM1 or COM2 Must match that in Main tab s Port parameter
8. er status point of the same type DI DO or status bit is the same as shown in the examples with the exception of entering the correct hex address in the PV Source Address parameter for the point being configured Main Tab Parameter Data Point ID User chosen text string defining name of point Description User chosen text description of the point PV Source Address AL 1 OS One example for each of the three different status point types followed by field definitions DI 1 DO 1 ThisController 4 0x1BFO 0 ThisController Example of the point s Controller Name parameter 4 Function Code Identifier always 4 for status bit types 0x1BFO Hex address of Alarm 1 s Output Status OS status bit 0 bit position for Alarm 1 s Output Status OS status bit ThisController 1 0x0 ThisController Example of the point s Controller Name parameter followed by a space 1 Function Code Identifier always 1 for Discrete Input points 0x0 Hex address of DI 1 s Output Value OV ThisController 0 0x0 ThisController Example of the point s Controller Name parameter followed by a space 0 Function Code Identifier always 0 for Discrete Output points 0x0 Hex address of DO 1 s Output Value OV 1 Reference Modbus RTU Serial Communications User Manual See Appendix A for the hex address of the actual point being configured 2 Dl and DO addresses are always determin
9. oint with an Analog Point type is as follows 1 Select the Points tab card in the Quick Builder main window 2 Select the button in the tool bar to bring up the Add Items window 3 Select the Analog point type from the list and click the OK button A point configuration window will be shown for the new point The Main tab must be filled out for all analog points Optionally the Control tab must be filled out if control of a point is required Example Alarm 1 will be detailed in the following tables including monitoring and control of its set point Configuration of any other analog point type is the same with the exception of entering the correct hex address in the PV Source Address parameter for the point being configured Main Tab Parameter Data Point ID User chosen text string defining name of point Description User chosen text description of the point PV Source Address ThisController 4 0x1C00 IEEEFP Example followed ThisController Example of the point s Controller Name parameter pyar definitan 4 Function Code Identifier always 4 for analog point types 0x1C00 Hex address of Alarm 1 s Set Point SP IEEEFP Data format entered literally 1 Reference Modbus RTU Serial Communications User Manual See Appendix A for the actual hex address of the point being configured PV Scan Period Must be non zero Scanning Enabled Box must be checked Control Ta

Download Pdf Manuals

image

Related Search

Related Contents

Color television window expansion and overscan correction for high    Shure T Series Wireless User Guide Portuguese  Philips SWV2742T User's Manual  Gigabyte GA-F2A88XM-DS2 motherboard  Whitehaus Collection WHQ536-SBLU Installation Guide  FY-08PPR7 の取付工事説明書  RCA RCR804BR User's Manual  Mac OS X Server Einführung  Newsletter-06 - tennis club de croissy sur seine  