RIM 600 TECHNICAL DATASHEET 60000
Contents
1. Note Use bracket P N 60075 710 for rack mounting Smoke Detector Monitor for the presence of high heat and smoke e Sensitivity 2 0 37 to 39 ft e Contact Rating 2 Amp 28 VDC or 120 VAC resistive e Heat Sensor rating Fixed 135 F 57 C rate of rise gt 15 F min 8 3 C min e Operating voltage 8 5 VDC to 33 VDC 10 max ripple e Maximum ambient temperature 100 F 37 8 C e Power up time 15 seconds e Housing white plastic 6 1 155 mm diameter x 1 9 48 mm high e Mounting wall flat surface or single gang box Smoke Detection Sensors Description Shipping Weight 60062 007 Smoke Detector with 7 L 2 1 m Cable 3 Ib 1 4 kg Power Monitoring Sensor Monitor voltage levels on power circuits e Range 0 VAC to 250 VAC 50 60 Hz e Accuracy 2 e Power connector IEC 60320 C 14 power inlet e Includes a 6 L 1 8 m C 13 to NEMA 5 15P or C 13 to C 14 power cord e Connector RJ 45 e Housing black plastic with mounting ears Power Monitoring Sensors Power Monitoring Sensor with C 13 to NEMA 5 15P Power Cord Lies Power Monitoring Sensor with C 13 to C 14 Power Cord Note Use sensor mounting panel P N 60075 720 for rack mounting 1 Ib 0 5 kg PRODUCT DATA SHEET SENSORS Motion Sensor Monitor for movement in the room e Sensing method infrared e Sensor passive dual element e Connector RU 45 includes 7 L 2 1 m cord e Housing white plastic e Adjustments for sensitivity LE
2. outlet Maximum power output is 10A on outlets 1 and 5 and 4A on all other outlets Each PowerGate includes a 6 L 1 8 m null modem cable 2 PRODUCT DATA SHEET REMOTE INFRASTRUCTURE MANAGEMENT RIM 600 SENSORS Room Temperature Sensors Monitor temperature in the room or cabinet e Range of measurement see order table e Humidity 5 to 90 RH e Sensor type solid state IC e Accuracy 3 e Connection RJ 45 e Housing white plastic e Mounting wall flat surface or single gang box e Indoor use only e Display digital two digit select models Room Temperature Sensors 60010 001 Range 5 F to 122 F No Display 1 Ib 0 5 kg 60010 002 Range 15 C to 50 C No Display 1 Ib 0 5 kg 60011 001 Range 32 F to 95 F With Display 1 Ib 0 5 kg 60013 001 Range 0 C to 50 C With Display 1 Ib 0 5 kg Note Use bracket P N 60075 710 for rack mounting Humidity Sensor Monitor humidity in the room or cabinet e Range of measurement 0 100 RH e Temperature 32 F to 122 F 0 C to 50 C e Accuracy 5 e Connector RJ 45 e Housing white plastic e Mounting wall flat surface or single gang box e Indoor use only e No display Humidity Sensor With Display Monitor humidity in the room or cabinet e Range of measurement 5 95 RH e Temperature 32 F to 158 F 0 C to 70 C e Accuracy 3 e Connector RJ 45 e Housing white plastic e Mounting wall flat surface or single gang box e Indoor use o
3. sensor for equipment cabinets e Magnetic reed switch e Connects directly to a host or node module e Single door sensor includes one door sensor a 7 L 2 1 m RJ 45 cable and a 25 L 7 6 m sensor cable e Dual door sensor includes two door sensors a 7 L 2 1 m RJ 45 cable and 2 10 L 3 m sensor cables Door Open Closed Sensors 1 Ib 0 5 kg 1 Ib 0 5 kg 60052 001 Single Door Sensor Magnetic Reed 60052 002 Dual Front Rear Door Sensor Magnetic Reed CHATSWORTH PRODUCTS INC REMOTE INFRASTRUCTURE MANAGEMENT RIM 600 Cables and Accessories Use patch cables to attach sensors to the RIM 600 Host and Node Module Use null modem cables to attach PowerGate Modules to the RIM 600 Host and Node Modules Optional mounting brackets let you attach sensors to 19 EIA racks or cabinets Cables and Accessories Part Number Description Patch Cable RJ 45 7 L 2 1 m Patch Cable RJ 45 14 L 4 3 m Patch Cable RJ 45 25 L 7 6 m RJ 45 F F Coupler Kit 4 Null Modem Cable 6 L 1 8 m Host Node Wall Mount Kit Temp Humidity Sensor Rack Mount Bracket sensor Mounting Panel 19 W x 1 RMU User Solutions Manual Shipping Weight 1 Ib 0 5 kg 1 Ib 0 5 kg 1 Ib 0 5 kg 1 Ib 0 5 kg 1 Ib 0 5 kg 2 b 0 9 kg 1 Ib 0 5 kg 2 b 0 9 kg 1 Ib 0 5 kg 1 Ib 0 5 kg 60070 007 60070 014 60070 025 60074 001 60071 006 60075 001 60075 710 60075 720 60087 001 60088 002 Note Sensor mounting pa
4. D display and Pulse count e Indoor use only e Mounting flat surface Motion Detection Sensors Part Number Description Shipping Weight 1 Ib 0 5 kg Normally Open Normally Closed Dry Contact Bridge Monitor a device equipped with a relay output that functions as an alarm Senses a definite yes no input from a normally open or normally closed output and sends an alarm when the yes or no condition is sensed e Input normally open or normally closed switchable e Source sense voltage 14 VDC e Source sense current 10 mA e Connector RJ 45 e Temperature 32 F to 122 F 0 C to 50 C e Housing black plastic with mounting ears e Indoor use only e No display Dry Contact Sensors 60050 001 Dry Contact Bridge N O N C 1 Ib 0 5 kg Note Use sensor mounting panel P N 60075 720 for rack mounting 60061 007 Passive Infrared with 7 L 2 1 m cord RIM 600 4 20 mA Dry Contact Bridge Monitor a maximum or minimum threshold for example the amount of fuel or water in a tank Senses a range of inputs from a corresponding 4 20 mA Transducer and sends an alarm when a specific threshold is reached between 0 4 mA and 100 20 mA 4 20 mA Dry Contact Bridge Description Dry Contact Bridge 4 20mA Note Use sensor mounting panel P N 60075 720 for rack mounting Shipping Weight 1 Ib 0 5 kg Door Open Closed Sensors Check door open or closed status e Single and dual door version e Use dual door
5. Monitor Shelf e CPI Keyboard Tray CHATSWORTH PRODUCTS INC REMOTE INFRASTRUCTURE MANAGEMENT RIM 600 M ce RIM p0D iin ra en Erem l nii a RIM 600 Host Module RIR ETN L A a mm m gt mn mgl at i RIM 600 Node Module RIM 6090 PowerGate1 Module PowerGate2 Module The Remote Infrastructure Management RIM 600 System gives you the ability to remotely monitor record and analyze environmental conditions in your data center and equipment rooms Each RIM 600 Host and Node supports up to eight external sensors and will automatically poll up to 64 IP addresses using a scheduled network ping and port service tests HTTP FTP email etc You can monitor temperature power or humidity check for the presence of smoke or water and use motion detectors IP cameras and door sensors for added security No special wiring is required Sensors have an RJ 45 connection and patch together with standard Category 5 network cabling The RIM 600 automatically recognizes and configures sensors and will notify you If sensors are disconnected or not reporting You can set alarm thresholds for each sensor and schedule when where and how you or members of your team are to be contacted The RIM 600 Host Module includes an Ethernet and a phone connection and can contact you by voice call text pager email SNMP or fax You can also check the status of equipment at any time through a voice call two way email you email RIM 600 re
6. PRODUCT DATA SHEET KEY FEATURES e Remote monitoring of environmental conditions in your data center or equipment room with up to eight external sensors temperature humidity etc and the capability to automatically monitor up to 64 IP addresses per Host or Node Module e Includes an Ethernet and phone connection so you can be contacted even if the network is down e Includes battery backup and non volatile data storage so you won t lose monitoring capability if the power goes out e Sensors are automatically recognized and configured when connected Attach sensors with standard network cabling using RJ 45 connectors Connection loss is automatically detected and reported e An integrated web server makes it easy to set up monitoring thresholds and to analyze collected data through a web browser e An easy to use scheduling tool lets you assign multiple points of contact and specific sequences of contact per events for you and each member of your team up to 64 users eight contacts each e Set limits and be notified by phone pager email fax or SNMP when thresholds are crossed APPLICATIONS e Continuous environmental power and security monitoring in the data center and equipment rooms USE WITH e CPI Cabinet and Enclosure Systems e CPI Rack Systems e CPI Wall Mount Systems RELATED ACCESSORIES e CPI Thermal Management Solutions e CPI Cable Management Products e CPI Power Management Products e CPI LCD
7. d RIM 600 Node Module e Supervised by RIM 600 Host e Monitoring same as RIM 600 Host Module e External connections Sensor connections 8 RJ 45 568B Ethernet connection RJ 45 10 100 Base T 10 100 Mbps RS 232 connection DB9 9600 bps DTE External microphone 3 5 mm jack electret condenser Power inlet external transformer NEMA 5 15P plug e Power operation Power supply see order table Power consumption 10 Watts Backup battery 1 6V 3 4AH Sealed Gel Cell Backup run time 3 5 hours Operating temperature 32 F 0 C to 122 F 50 C Operating humidity 5 90 RH non condensing e Size 19 EIA x 1 RMU x 7 D 178 mm e UL Listed and CE approved PowerGate Modules e Monitor and reset power remotely e Attaches to RIM 600 Host or Node Module e Monitoring power use reset status for each outlet e External connections RS 232 connection DB9 9600 bps DTE Power inlet Attached power cord 1 NEMA 5 15P plug PowerGate2 also has 8 IEC 60320 C 14 1 outlet Use power cord 60078 010 with PowerGate2 Power outlets 8 NEMA 5 15R e Power operation Power supply 120 VAC 60Hz Over current protection circuit breaker s Operating temperature 32 F 0 C to 95 F 35 C Operating humidity 5 90 RH non condensing e Size 19 EIA x 1 RMU x 10 D 254 mm e UL Listed CONNECTIONS INDICATORS RIM 600 Node Module PowerGate 15 A M R PowerGate Modul
8. e 1 DB9 Serial Port Used for initial setup of the RIM 600 10 The RIM 600 includes a standard PC type grounded unit and to connect to from the RIM 600 PowerGate power cord Module 11 Internal battery backup holds operation for several 2 Ethernet Port connects your RIM 600 to your network hours after utility power has been interrupted 3 Telephone jack connects your RIM 600 Host to the 12 Identifies your RIM 600 unit as the main Host Node telephone network The yellow phone status LED shows or PowerGate Modules if the phone line interface is in use 13 Rack mountable 1 RMU high 19 EIA mounting 4 Eight environmental inputs support all of the RIM 600 sensors with standard RJ 45 connectors 5 Red and green lights show the real time alarm status of configuration The RIM 600 can also be mounted on a wall with the RIM 600 Host Node Wall Mount Kit purchased separately the environmental inputs 14 Built in mic and external microphone jack in Node 6 Battery alarm indicator shows the status of the internal Module are for detecting sound level alarms battery backup system 15 Power on off switch and green LED power indicator 7 AC power alarm indicator shows the status of the AC on the Node Module power line into which the RIM 600 is plugged 16 Circuit breaker on the PowerGate Module 8 Internal microphone for sound level alarming and 17 Eight power outlets on the back of the PowerGate remote listen in Module 9 Microphone
9. jack for attachment of a remote microphone 18 Eight LEDs indicating the on off status of each outlet for sound level alarming and remote listen in 19 LED indicates that the PowerGate Module is plugged in and receiving power ORDERING INFORMATION Remote Infrastructure Management RIM 600 System Part Number 60000 001 Description Host 100 250 VAC 50 60 Hz International Host 100 250 VAC 50 60 Hz shipped without power cord 14 Ib 6 4 kg 60001 001 Node 120 VAC 60 Hz 7 Ib 3 2 kg 60001 002 Node 100 240 VAC 50 60 Hz with power cord 7 Ib 3 2 kg 60001 102 International Node 100 240 VAC 50 60 Hz 7 Ib 3 2 kg shipped without power cord 60075 001 Wall Mount Kit 2 b 0 9 kg Note Host Module includes a users manual and configuration software CD Node module 60001 002 includes an auto sensing power transformer with an IEC 320 C 14 power inlet and detachable power cord with a NEMA 5 15P plug PowerGate Module Part Number Shipping Weigh 60045 001 14 Ib 6 4 kg 60046 001 14 Ib 6 4 kg 60078 010 1 Ib 0 5 kg Shipping Weight 14 Ib 6 4 kg 60000 102 PowerGate 1 Power Connection 8 Outlets PowerGate2 9 Power Connections 8 Outlets PowerGate2 Power Cord IEC to NEMA 5 15P 10 L 3 m Note PowerGates allow you to reset power to each outlet Power connections are 120 VAC 60 Hz PowerGate shares power across all outlets Maximum combined UL approved power output is 12A PowerGate2 has 1 power connection per
10. nel P N 60075 020 supports three sensors ConsoleView Software CD Remote Infrastructure Management RIM 600 Solution Bundle Everything you need to begin monitoring humidity and temperature for up to four cabinets Includes 1 Remote Infrastructure Management RIM 600 Host Module 3 Miniature Temperature Sensors 1 Room Temperature Sensor with F display 1 Humidity Sensor 1 Temp Humidity Sensor Rack Mount Bracket 4 7 L 2 1 m RJ 45 Patch Cables and 1 RU 45 F F Coupler Kit For more detailed information on the RIM 600 Solution Bundle see the application sheet at www chatsworth com rim600 Remote Infrastructure Management Solution Bundle Par Number Description Shipping Weight 25 Ib 11 3 kg F600 0 Environmental Monitoring Solution Bundle International Environmental Monitoring Solution F600 1 Bundle includes C Temp sensors and shipped without power cords 25 Ib 11 3 kg 2012 Chatsworth Products Inc All rights reserved CPI CPI Passive Cooling MegaFrame Saf T Grip Seismic Frame SlimFrame TeraFrame GlobalFrame Cube iT Plus Evolution OnTrac QuadraRack and Velocity are federally registered trademarks of Chatsworth Products Inc Simply Efficient is a trademark of Chatsworth Products Inc All other trademarks belong to their respective companies Rev 8 02 12 MKT 60020 326
11. nly e Display digital two digit Humidity Sensors Room Humidity Sensor No Display 1 Ib 0 5 kg Room Humidity Sensor with Display 1 Ib 0 5 kg Miniature Temperature Sensor Monitor temperature in a cabinet e Range of measurement see order table e Humidity 5 to 90 RH e Sensor type solid state IC e Available preset to F or C e Accuracy 3 e Connection RJ 45 includes 7 L 2 1 m cable e Housing black plastic e Mounting flat surface via included double back tape e Size 2 2 W x 1 4 H x 6 D 56 mm x 36 mm x 15 mm e Indoor use only e No display Miniature Temperature Sensor 60012 007 Range 5 F to 140 F 1 Ib 0 5 kg 60012 057 Range 15 C to 60 C 1 Ib 0 5 kg Water Detection Sensor Monitor for the presence of water e Sensing method Conductivity e Sensor polymer core cable with sensing wire 10 L 3 m e Connector RJ 45 daisy chain up to three sensors e Housing black plastic with mounting ears Water Detection Rope 10 L 3 m e Extend the reach of the water detection sensor e Add up to 10 ropes in line with each Water Detection Sensor Water Detection Sensors Water Detection Sensor with 10 L 3 m Water Detection Rope 1 Ib 0 5 kg 60072 001 Additional 10 L 3 m Water Detection Rope 1 Ib 0 5 kg Note Expand sensor capability by daisy chaining up to three sensors or adding up to 10 ropes Use sensor mounting panel P N 60075 720 for rack mounting 60032 010
12. plies with status or with a web browser over a web wireless web or remote dial in connection The separate phone connection keeps you connected if your network connection goes down Each RIM 600 monitors input power and has an internal battery backup so it will keep working if the power goes out Add a separate PowerGate Module to remotely reboot up to eight pieces of equipment or monitor power on a specific circuit with the Power Monitoring Sensor Reduce cost in large networks by combining Host and Node Modules Host Modules include an Ethernet and phone connection Node Modules include Ethernet connections and are supervised by a Host Module Connect up to 31 Nodes to each Host through your network and monitor up to 256 environmental sensors and 2 048 IP addresses and ports anywhere in your network Additionally one PowerGate Module can be connected to each Host or Node Module to provide remote reboot capability for up to 256 outlets See reverse for product details or contact CPI Technical Support for configuration assistance 1 800 834 4969 techsupport chatsworth com www chatsworth com PRODUCT DATA SHEET REMOTE INFRASTRUCTURE MANAGEMENT RIM 600 SPECIFICATIONS RIM 600 Host Module e Provides remote automated environmental and network monitoring e Supervises up to 31 RIM 600 Nodes Monitoring Eight external sensors any mix of temperature etc 64 IP addresses scheduled network ping port service tests Power reset stat
13. us when attached to a PowerGate Module Sensor connection status connected reporting Sound level in dB with built in microphone Source power on off True RMS Voltage on Host Backup battery charge level e Record keeping Keeps 62 500 records can be downloaded Website displays sensor status history and sample plots e Notification 64 user profiles with eight contacts each Integrated contact scheduling tool Sends alarms by voice call with custom messages alpha pager numeric pager fax email or SNMP trap Check status by voice dial in Website network log in SNMP get set and two way email External connections Sensor connections 8 RJ 45 568B Category 5 UTP cable 1000 L 304 8 m max Ethernet connection RJ 45 10 100 Base T 10 100 Mbps Integrated web server SNMP V1 2 3 complete MIB and Get Set support Modem connection RJ 11 33 6 Kbps Fax Group 3 14 4 Kbps Integrated voice processor RS 232 Connection DB9 9600 bps DTE External microphone 3 5 mm jack electret condenser Power inlet IEC 60320 C 14 Includes 6 L 1 8 m cord with NEMA 5 15P plug Power operation Power supply 100 250 VAC 50 60H7z 1 6 A Power consumption 25 Watts Backup battery 12V 2 9AH Sealed Gel Cell Backup run time 3 5 Hours Operating temperature 32 F 0 C to 122 F 50 C Operating humidity 5 90 RH non condensing e Size 19 EIA x 1 RMU x 9 6 D 244 mm e User Manual and software CD included e UL Listed and CE approve