1. No of Zone Q C 1 Engineer INsyiN Peace of Mind Round the Clock Fire Alarm Panel Moldel IFP 02 04 User Manual Insyin Electronics Private Ltd New No 2 5th Street Narasingapuram Extn Guindy CHENNAI 600 032 Phone 044 2244 3405 4478 E mail insyin vsnl net sales insyin com Website www insyin com INsyiN Peace of Mind Round the Cloch MICRO CONTROLLER BASED FIRE ALARM CONTROL AND INDICATING PANEL Fire Alarm Panel User Manual
2. CONTENTS SYSTEM INTRODUCTI ON DESIGN AND PLAN GENERAL FEATURES MECHAN CAL CONSTRUCTION NSTALLAT ON AND COMMISSIONING NSTALLATION COMMISSIONING OPERATION POWER CONDITION ZONE LOOP CONDITION KEY FUNCTI ONS TECHNI INSTRUCT CAL ONS TO BE FOLLOWED DATA SOME DO S AND DON T S TROUBLESHOOTING DIAGRAM 2 ZONE PANEL ABBREV AT 4 ZONE PANEL ONS Page No A A N N O O O 4 Fire Alarm Panel User Manual Fire Alarm Panel User Manual FIRE ALARM PANEL MODEL IFP 02 04 1 INTRODUCTION This manual intended as a complete guide to the model 02 04 Conventional Fire Alarm Control and Indicating panel First part of this manual guides the user about the panel Installation and Commissioning and then it is describing User Instruction Operation with full technical details 2 SYSTEM DESIGN AND PLAN This panel is designed to meet the general requirements of IS 2189 3 GENERAL The microcontrller based Automatic Fire Alam control and indication panel is designed to detect the fire in its earliest practicable moment through the detector and developed with the state of art technology It provides high reliable
3. Y CERTIFICATE Model No Serial Insyin Electronics Private Ltd warrants each instrument to be free from defects in material and workmanship This obligation is limited to servicing or part returned to the campany for that purpose and making good any parts their of which shall be within warranty period Returned to be company under a written intimation and which to the company s satisfaction to be found defective The company reserves the right for decide the workplace for the repair work The fright for defective material will have to be bore by the purchaser and the transit risk for such material will rest with the purchaser This warranty will last for a period of 12 months from the date of dispatch of the instrument fromthe factory The warranty is applicable only if the instrument is used within its specifications The warranty for the replaced components will lapse along with that the main instrument THIS WARRANTY IS VALID UP TO 12 Months from the date of billing Authorised Signatory Insyin Electronics Private Ltd New No 2 5th Street Narasingapuram 1 Guindy CH ENNAI 600 032 Phone 044 2244 3405 4478 TEST CERTIFICATE Extn This is to certify that the following items are tested and checked 1 Micro Controller Based Conventional Fire Alarm Control Panel Model No Serial No For Insyin Electronics Private Ltd Production Engineer
4. gulation b The Indian Standard of fire detection and alarm for building Care should be taken not to install cable in the proximity of high voltage cables or in areas likely to induce electrical interference Fire Alarm Panel User Manual Fixthe panel in its mounting position using the key slots and fix the panel to the wall using the screws Ensure the enclosure and the inner parts of the panel are given sufficient protection during installation pericd All external cables are to be glanded via the 20mm dia performed knockouts located at the top of the panel When the installation of all the cables has been completed clean the interior of the enclosure ensuring all masonry debris and drilling sword are removed 6 2 COMMISSIONING Check all the entered wiring is correctly identified and also check the cables are free fram fault conditions using a multimeter Connect the extemal wiring into their respective terminals and replace the END OF LINE resistor to the last device inthe circuit Prior to the initial powerup of the panel conduct the following preliminary checks Check for any external signs of damage caused during installation h Check all the PCBS are secure in its monitory position Check the cables are secure and correctly connected d Check all the cable termination is tight amp secure Connect the batteries ensuring the correct p
5. h dog LED would glow stable manner Tomove to the second zone again press the silence key 4 X After selecting the zone press the ISOLATE key to isolate that zone 5 Now the particular zone is ISOLATED with the glowing ISOLATE LED and every 4 second once Beep sound will be enabled and also the voltage to the loop is cut off Fire Alarm Panel User Manual To bring back the isolated zone to the normal monitoring condition follow the steps below Follow the above steps 1 to 3 to select a particular zone After selecting the zone press the ISOLATE key to bring back the zone to normal condition Now the particular zone comes to normal condition with the ISOLATI IED goes off HOOTER LOOP SENSE The Hooter loop is monitored through an external END OF LINE EOL 4k7 Resistor for open short circuit If an open circuit is occurred in the hooter loop the hooter loop fault LED would blink If short circuit is occurred in the Hooter loop the hooterloop fault LED would continuously glow with intermittent fault tone in the panel buzzer Press the SILENCE key to silence the panel buzzer The visual indication will remain till the fault conditions are rectified KEY FUNCTIONS LAMP TEST KEY This key is provided to test whether all the LED S available are in good conditions o
6. ing necessary actions to restore the panel to normal operating conditions press the RESET key In case of open Short fault Green Yellow LED of respective Zone will glow with Intermittent Panel buzzer sound To silence the Intermittent buzzer Sound press the SILENCE key When the Fault is cleared or corrected the panel goes to the operating conditions autamatically Fire Alarm Panel User Manual TECHNICAL DATA Panel Operating Condition Operating Voltage AC power Standby power Operating Temperature Operating Humidity Quiescent Current Zone Operating Condition Normal loop voltage Open Threshold Current Short Threshold Current Fire Threshold Current Standby Threshold Current EOL Detector Current Alarm outputs Sounder Output Remote Outputs Fire Contact 1 C NO NC Fire Contact 2 C NO NC 10 220V AC 50HZ 10 24V DC 0 C to 49 2 C 95 Non Condensing 35mA 20 8V 0 mA 40mA 15 35 mA 4 4mA 2 5mA 0 5A 24V DC 220V AC 30V DC 1A 220V AC 30V DC 1A General Weight Colour Fire Alarm Panel User Manual 5 Kgs Approximate 350 x 263 x 103 mm Width x Height x Depth Black with Siemens Grey Structure finish Dual colour Some DO S and DON T S The panel and Detectors should be within the temperature rang of 0 C to 49 C 2 C We strongly recommend to check the panel o
7. is occurred in the Zone loops in any of the zone the open short LED in the corresponding zone will glow with intermittent fault tone in the panel buzzer Fire Alarm Panel User Manual Press the SILENCE KEY to silence the panel buzzer The visual indication will remain till the fault onditions are recti fied 2 FIRE CONDITIONS In case of Fire in any of the zone the corresponding RED TWIN LEDS will flash In this condition the panel Buzzer will give wailing fire tone The Press the SILENCE key to silence the panel buzzer and all the external sounders The TWIN LEDS will glow steadily and the panel buzzer generat a intermittent tone In this condition SILENCE key cannot respond to silence the panel buzzer The conditions of the visual indications Auxiliary relays and panel buzzer will remain till the panel is reset Before pressing the silence key If any subsequent fire in the second zone comes it will be indicated by the corresponding flashing of TWIN RED LEDs and the previous indication will go to steady state 3 ZONE ISOLATION To isolate the zone loops for maintenance purpose and bring back to the normal operating condition follow the procedure as below To Isolate a particular zone perform the following steps 1 Holdthe SILENCE key for 3 seconds 2 Zone 1 ISOLATE start blinking and watc
8. monitoring of protected area The panel operates on 220V AC mains with 24V DC battery as a standby power The built in circuit provides constant voltage charging to maintain the battery capacity 4 FEATURES 1 Rugged sheet with powder coated finish 1 Operates on 220V AC supply 1 Battery backup with built in charging i Error free fire fault status in unanbiguous colored LED indication 3 Fire Alarm Panel User Manual 1 Low battery visual warning with audible tone i Watchdog system on AC on Battery on Charger on indications 1 Relay output for actuators 1 Lamptest facility 1 Campatiable to all types of Conventional detectors 1 TwinREDLED indication for fire 1 Zaeisolatim facility i 24VDC Axillary output extemal notification devices sander Bell etc Hooter logo monitoring facility 1 Hootertest facility 5 MECHANICAL CONSTRUCTION The enclosure is constructed of CRCA sheet with powder coated finish The panel enclosures are designed to affored the degree of protection as per IP 54 The cable entry is via performed 20m dia knockouts located at the top of the cabinet The panel also has a built in battery provision to accommodate 2 No s of 12V 7AH batteries 6 INSTALLATION AND COMMISSIONING 6 1 INSTALLATION Note The installation of the fire detection and alarm camply with a The IEEwiring re
9. n daily basis and the detectors on weekly basis Ensure 220V AC 10 of the input Voltage level befor switching ON the panel If the voltage fluctuation is more than 10 use UPS supply or voltage 11 Don t fix the panel Detector in high range of vibrating area Don t put the panel cables near to the high voltage area Don t fix the panel in highly moisture surrounded area Improved wiring will void the warranty There is indication on the panel If there is any false alarm from the Detector Detector OPEN is not detected by the panel Hooter fault indication Fire Alarm Panel User Manual TROUBLESHOOTING No Power to the panel May be the detector failure or low loop voltage Total zone loop current Check Ac and Standby supply Ensure the AC supply within 220V 10 or Change the faulty detector Check number of detectors exceed the rated valu There is no proper connection in the hooter or loop fault connected in the loop Total nos of detector current should not go above 2 5mA If there is no hooter connected in the output Check resistor EOL is connected there or not Check loop wiring for short open using meter If hooter is non polarized then ensure each hooter ve connected to 1N 4007 diode cathode and the anode connected with hooter loop ne CONNECTION DETAILS FOR NON POLARIZED SOUNDER Sounder 12 Fire Alarm Panel Use
10. olarity All damages Fault must be rectified before proceeding Switch on the panel The panel will indicate the following in the IED indicating section WATCHDOG W D a b SYSTEM ON d CHARGER ON Fire Alarm Panel User Manual OPERATIONS POWER CONDITIONS A C FAIL During AC mains fail the A C ON LED goes off and charger on LED also goes off with intermitted panel buzzer fault tone Battery ON LED lights on To silence the fault tone press the SILENCE key If A C mains resumes then the panel would automatically go to the nomal condition BATTERY LOW If the Battery voltage goes down less than 20V then the Battery ON LED blinks with intermitted panel Buzzer fault tone till the Battery voltage goes low to 18 5V If the voltage goes below 18 5V Panel buzzer generates continuous tone In this condition SILENCE key cannot respond to silence the panel buzzer and there is no response from input actions Such as fire open fault short fault amp sounder loop fault In this case the user can Switch off the panel or change the battery If battery voltage cross above 18 5V 20V Panel automatically goes to normal mode To silence the fault tone press the SILENCE KEY ZONE LOOP CONDITIONS FAULT CONDITIONS The zone loops are monitord through an external END OF LINE EOL 4k7 Resistor for qpen short circuit If an qpen short circuit
11. r Manual d O inva Hd d O 4414 23t HOLGIS3H INI 40 0N3 703 H2d 8S HIASNI zo 441 GoW TANYA INOZ S IIv130 TONINGIL l3 Fire Alarm Panel User Manual d O Lea d O 4414 3414 OY 02 EE ear HOLSIS3H ANT 40 ON3 703 Hal2a313U0 d TIT SS RRR d O HIONNOS yo 41 dew TANYd INOZ t STIYLIO 3 1 a E 14 Fire Alarm Panel User Manual ABBREVIATIONS The short forms which are given in this manual are abbreviated below IEP 15 2189 DC CRCA LED O P IP 54 m m no s Ah EOL PCB CPU MCP S Nos mA Kgs C NO NC Insyin Fire Parel Indian Standard 2189 Alternating Current Direct Current Cold Rolled Carbon Alloy Light Emitting Diode Output Industrial Protection millimeter number s volts Ampere per hour Institute of Electrical Engineering End of Line Printed Circuit Board Central Processing Unit Manual Call Point Serial Numbers milli Ampere Kilo grams Common Normally Open Normally Close 16 Fire Alarm Panel User Manual Insyin Electronics Private Ltd New No 2 5th Street Narasingapuram Extn Guindy CHENNAI 600 032 Phone 044 2244 3405 4478 Email insyin vsnl net sales insyin om Website www insyin com WARRANT
12. r not When the key is pressed all the LED S will glow with continuous tone in the panel buzzer until the key is in pressed condition and the previous condition is retained after releasing the key SILENCE KEY This key is provided to silence the panel buzzer and the external scunders during the fire Conditions If the key is pressed panel buzzer and external sounders are silenced Similarly during the fault conditions the panel buzzer is silenced by this key Fire Alarm Panel User Manual RESET KEY This key is provided to reset the panel to normal conditions ISOLATE KEY This key is provided to isolate and de isolate the selected zone HOOTER TEST KEY When the key is pressed the external sounder and internal panel buzzer will be activated until the key is in pressed Condition and the previous conditions retained after releasing the key INSTRUCTIONS TO BE FOLLOWED In normal condition the following visual indications are available on front side of the panel L WATCHDOG W D in blinking condition Red LED 2 SYST 1 ON indication Green LED 3 indication Yellow LED 4 CHARGER ON Indication Red LED In case of Fire the FIRE RED of respective Zone will flash with alam Sound To silence the alarm press the SILENCE key After tak