Home
NI PXI-1031/PXI-1031DC User Manual
Contents
1. Voltage 0 50 C 433 3 V 12A 5 V 17A 12 V 2A 12 V 0 8 A Over current protection All outputs protected from short circuit Over voltage protection Active Range Over voltage at Minimum Maximum 3 3 V 3 76 V 4 3 V 5 V 5 74 V 7 0 V 12 V 13 4 V 15 6 V Chassis Cooling Per slot cooling capacity 25W Slot airflow direction P1 to P2 bottom of module to top of module Module cooling System n e e tege ineft Forced air circulation positive pressurization through a 101 1 CFM fan with HIGH AUTO speed selector Intake sett Bottom of chassis NI PXI 1031 PXI 1031DC User Manual A 2 ni com Environmental Appendix A Specifications Exhaust veteres Along rear right side and top of chassis Power supply cooling Forced air circulation through integrated fan Intakes ect renes Front and left side of chassis Exh sti xen Rear side of chassis Operating Indoor use Maximum altitude 2 000 m Measurement Category II Pollution Degree 2 Operating Environment Ambient temperature range 0 to 50 C Tested in accordance with IEC 60068 2 1 and IEC 60068 2 2 Meets MIL PRF 28800F Class 3 low temperature limit and high temperature
2. NI PXI 1031 PXI 1031DC User Manual B 2 ni com Appendix Pinouts Table B 2 P2 J2 Connector Pinout for the System Controller Slot Pin Z A B c D E F 22 GND GA4 GA3 GA2 GA1 GAO GND 21 GND CLK6 GND RSV RSV RSV GND 20 GND CLK5 GND RSV GND RSV GND 19 GND GND GND SMB_SDA SMB_SCL SMB_ALERT GND 18 GND PXI TRIG3 PXI TRIG4 PXILTRIGS GND PXI TRIG6 GND 17 GND PXI TRIG2 GND PRST REQ6 GNT6 GND 16 GND PXI TRIGI PXI TRIGO DEG GND PXI TRIG7 GND 15 GND PXI BRSVAIS GND FAL REQS GNTS GND 14 GND BP I O BP I O BP I O GND BP I O GND 13 GND BP I O GND V I O BP I O BP I O GND 12 GND BP I O BP I O BP I O GND BP I O GND 11 GND BP I O GND V I O BP I O BP I O GND 10 GND BP I O BP I O BP I O GND BP I O GND 9 GND BP I O GND V I O BP I O BP I O GND 8 GND BP I O BP I O BP I O GND BP I O GND 7 GND BP I O GND V I O BP I O BP I O GND 6 GND BP O BP I O BP I O GND BP I O GND 5 GND BP I O 64EN V I O BP I O BP I O GND 4 GND vaso PXI BRSVB4 BP I O GND BP I O GND 3 GND CLK4 GND GNT3 REQ4 GNT4 GND 2 GND CLK2 CLK3 SYSEN GNT2 REQ3 GND 1 GND GND REQI GNT1 REQ2 GND National Instruments Corporation B 3 NI PXI 1031 PXI 1031DC User Manual Pinouts Table B 3 P1 J1 Connec
3. PETER OE RE HE ples aet een 1 5 Handle Eeet Kit j p HE ben ot 1 5 DC Power Cable PXI 1031DC Only eee 1 6 PXI 1031 PXI 1031DC Backplane OVerVieW esee 1 6 Interoperability with CompactPCI pe 1 6 System Controller Slot 2 ett o tet e RS deeds 1 6 Star Trigger Slot so deb ER UC udi niue eet 1 7 Peripheral Slots eer eet ceat tte die 1 7 1 7 Trigger BUS ses 1 8 System Reference ClocK eed esee iet tete e epo ep 1 8 Chapter 2 Installation and Configuration Safety Information aaepe tei ea eei ire ipee rte i rdi 2 1 Chassis Cooling Considerations eese nennen nennen 2 2 Providing Adequate Clearance pe 2 2 Setting Fan Speed oe tet ce pete CR rea uit 2 3 Installing Filler Panels ehe eene 2 3 Rack e 2 4 Connecting Safety Ground eet tee tette I o HR RE ttp ee itn 2 4 Connecting to Power Source nea eaten then 2 4 Connecting to an AC Power Source Ne 2 5 Connecting to a DC Power Source PXI 1031DC Only 2 5 DG Connector e eR vites 2 5 Installing a etit ee did nett aa 2 6 National Instruments Corporation V NI PXI 1031 PXI 1031DC User Manual Contents Installing PXI Modules eese nennen PXI System Configuration with MAX es Basic PXI Syste
4. PXI 1031 PXI 1031DC User Manual December 2010 NATIONAL 3712266 01 INSTRUMENTS Worldwide Technical Support and Product Information ni com National Instruments Corporate Headquarters 11500 North Mopac Expressway Austin Texas 78759 3504 USA Tel 512 683 0100 Worldwide Offices Australia 1800 300 800 Austria 43 662 457990 0 Belgium 32 0 2 757 0020 Brazil 55 11 3262 3599 Canada 800 433 3488 China 86 21 5050 9800 Czech Republic 420 224 235 774 Denmark 45 45 76 26 00 Finland 358 0 9 725 72511 France 01 57 66 24 24 Germany 49 89 7413130 India 91 80 41190000 Israel 972 3 6393737 Italy 39 02 41309277 Japan 0120 527196 Korea 82 02 3451 3400 Lebanon 961 0 1 33 28 28 Malaysia 1800 887710 Mexico 01 800 010 0793 Netherlands 31 0 348 433 466 New Zealand 0800 553 322 Norway 47 0 66 90 76 60 Poland 48 22 328 90 10 Portugal 351 210 311 210 Russia 7 495 783 6851 Singapore 1800 226 5886 Slovenia 386 3 425 42 00 South Africa 27 0 11 805 8197 Spain 34 91 640 0085 Sweden 46 0 8 587 895 00 Switzerland 41 56 2005151 Taiwan 886 02 2377 2222 Thailand 662 278 6777 Turkey 90 212 279 3031 United Kingdom 44 0 1635 523545 For further support information refer to the Technical Support and Professional Services appendix To comment on National Instruments documentation refer to the National Instruments Web site at ni com info and enter the Info Code feedback 2004 2010 National Instruments Corp
5. Figure A 1 PXI 1031 PXI 1031DC Dimensions Front and Side in Inches mm NI PXI 1031 PXI 1031DC User Manual 4 12 ni com Specifications 0 69 in 8 74 in 17 5 mm 222 mm a i mE 0 89 in 22 6 mm e i 4 07 vmi goaa gQ pis 6 49 in MENE 164 85 mm e Figure A 2 PXI 1031 PXI 1031DC Dimensions Bottom in Inches mm National Instruments Corporation 18 NI PXI 1031 PXI 1031DC User Manual Specifications Figure A 3 shows the PXI 1031 PXI 1031DC rack mount kit components 1 PXI 1031 PXI 1031DC Chassis 2 Rack Mount Kit Figure A 3 PXI 1031 PXI 1031DC Rack Mount Kit Components NI PXI 1031 PXI 1031DC User Manual 4 14 ni com Pinouts This appendix describes the P1 and P2 connector pinouts for the PXI 1031 PXI 1031DC backplane Table B 1 shows the P1 J1 connector pinout for the System Controller slot Table B 2 shows the P2 J2 connector pinout for the System Controller slot Table B 3 shows the P1 J1 connector pinout for the star trigger slot
6. National Instruments Corporation A 7 Appendix A Specifications Forced air circulation positive pressurization through a 101 1 CFM fan with HIGH AUTO speed selector Bottom of chassis Along rear right side and top of chassis Forced air circulation through integrated fan Front and left side of chassis Rear side of chassis Indoor use 2 000 m 2 0 to 50 C Tested in accordance with IEC 60068 2 1 and IEC 60068 2 2 20 to 70 C Tested in accordance with IEC 60068 2 1 and IEC 60068 2 2 5 to 9596 noncondensing Tested in accordance with IEC 60068 2 56 NI PXI 1031 PXI 1031DC User Manual Specifications Shock and Vibration Operational shock 30 g peak half sine 11 ms pulse Tested in accordance with IEC 60068 2 27 Test profile developed in accordance with MIL PRF 28800F Random Vibration Operating 5 to 500 Hz 0 3 ga Nonoperating 5 to 500 Hz 2 4 gins Tested in accordance with IEC 60068 2 64 Nonoperating test profile exceeds the requirements of MIL PRF 28800F Class 3 Acoustic Emissions Sound Pressure Level at Operator Position Tested in accordance with ISO 7779 PXI 1031DC Auto fan at 25 C ambient 45 5 dBA High necs 49 4 dBA Sound Power Tested in accordance with ISO 7779 PXI 1031DC Auto fan at 25 C am
7. 3029 eeeeeeeeeeee 00890080000006006 69 OO000O0 00090 CAUTION BOTH POWER iS MUS TO REMOVE FROM E 8 T30VDC 30 0A MAX 50 60 Mz 4 2A 1 Rear Exhaust Vents 5 2 DC Fuse Socket 6 Chassis Ground Screw 3 DC Input 7 4 AC Input 8 Rubber Foot Power Supply Fan Exhaust AUTO HIGH Fan Speed Selector Switch Figure 1 3 Rear View of the PXI 1031DC Chassis NI PXI 1031 PXI 1031DC User Manual 1 4 ni com Chapter 1 Getting Started 1 Power Switch Standby 3 Fan Cover Screw 2 Fan Cover 4 Rubber Foot Figure 1 4 Bottom View of PXI 1031 PXI 1031DC Chassis Optional Equipment Contact National Instruments to order the following options for the PXI 1031 PXI 1031DC chassis EMC Filler Panels Optional EMC filler panel kits are available from National Instruments Rack Mount Kits A rack mount kit option is available for mounting the PXI 1031 or PXI 1031DC chassis into a 19 in instrument cabinet Handle Feet Kit An optional side handle and rubber feet kit is available from National Instruments to pr
8. System Bill Data Neighborhood Devices and Interfaces Traditional NI DAQ Devices NI DAQmx Devices 5 PXI System External PC Jl PXI2 13 1N5TR PXI2 14 1NSTR 9 Ports Serial amp Parallel p AAT VXI System 0 PXI 8320 scales Software 1 Drivers a Remote Systems 3 Show Help Slot Device 1 PX PXI Bridge NI 3 from PXI System External PC 2 PXI2 15 INSTR B PXI2 14 INSTR 4 ZR PXI2 13 INSTR Slot View Figure 2 6 Chassis Configuration in MAX Basic PXI System Configuration Refer to Figure 2 6 while completing the following steps 1 Launch MAX 2 Inthe Configuration tree click the Devices and Interfaces branch to expand it 3 Ifthe PXI system controller has not yet been configured it will be labeled System Unidentified Right click this entry to display the context menu and then select the appropriate controller model from the Identify As submenu 4 Click the PXI System controller and the chassis or multiple chassis in a multi chassis configuration will be listed below it Identify each chassis by right clicking its entry and then selecting the appropriate chassis model through the Identify As submenu Further expanding the PXI System branch will show all of the devices in the system that can be recognized by NI VISA After your controller and all of your chassis have been identified the
9. Specifications Caution Ifthe PXI 1031 PXI 1031DC chassis is used in a manner inconsistent with the instructions or specifications listed by National Instruments the protective features of the chassis may be impaired Note Specifications are subject to change without notice This appendix contains specifications for the PXI 1031 and PXI 1031DC chassis 1031 Chassis Electrical N Caution Overloading the circuits may damage supply wiring Do not exceed the ratings on the equipment nameplate when connecting equipment to the supply circuit AC Input Input voltage 100 240 VAC Operating voltage 90 264 VAC Input frequency 50 60 Hz Operating frequency range 47 63 Hz Input current 4 2 EffICIeBCy eret reet teenies gt 70 at full load normal input voltage The operating range is guaranteed by design National Instruments Corporation A 1 NI PXI 1031 PXI 1031DC User Manual Specifications Power disconnect The AC power cable provides main power disconnect The front panel power switch controls the internal chassis power supply that provides DC power to the backplane DC Output DC current capacity Imp
10. 1 V I O is connected to the 5 V DC power plane so the same specifications apply to V I O and 5 V National Instruments Corporation A 11 NI PXI 1031 PXI 1031DC User Manual Specifications Figure 1 and Figure A 2 show the PXI 1031 PXI 1031DC dimensions The holes shown are for the installation of the optional rack mount kits as shown in Figure A 3 Notice that the front and rear rack mounting holes size M4 are symmetrical 1 10 12 in 1 Pp 257 1 A Next 6 97 in 177 mm ee CEPET 9 y 0 50 in r n 12 7 1 0 88 in dia 22 4 mm 6 6 46 in 164 08 mm gt 172in gt 1 4369 mm M4 x 0 7 0 72in Qi 3 02 in W 0 25 6 35 Max 1 wv 0 25 6 35 mm Max 10x 18 8 mm 76 71 190000000000000000000000000000 0 0 00000000000000600 0000000 00000000 1 000 0 oo o o o9c papers ata UE ne mn E AE i 1 83 in 4 47 in 46 58 mm 113 54 mm LL Lon eet A Front Panel 1 U i 096i 24 38 7 8 43 in 214 2 mm gt
11. 3 1 preparation 3 1 service interval 3 1 static discharge damage caution 3 1 maintenance of PXI 1031DC 3 1 cleaning exterior cleaning 3 2 interior cleaning 3 2 preparation 3 1 service interval 3 1 static discharge damage caution 3 1 National Instruments support and services C 1 0 optional equipment 1 5 P P1 J1 connector peripheral slot table B 6 star trigger slot table B 4 system controller slot table B 2 P2 J2 connector peripheral slot table B 7 star trigger slot table B 5 system controller slot table B 3 peripheral slots overview 1 7 P1 J1 connector pinouts table B 6 P2 J2 connector pinouts table B 7 ni com pinouts B 1 P1 J1 connector peripheral slot table B 6 star trigger slot table B 4 system controller slot table B 2 P2 J2 connector peripheral slot table B 7 star trigger slot table B 5 system controller slot table B 3 power cables table 1 2 power supply connecting to 2 4 connecting to DC 2 5 power switch 2 5 power up testing 2 4 programming examples NI resources C 1 controller installing 2 6 installing in a PXI 1031 chassis figure 2 8 installing in a PXI 1031DC chassis figure 2 8 PXI subsystem star trigger and local bus routing figure 1 8 PXI_CLK10 1 8 PXI_CLK10_IN pin 1 8 1031 backplane interoperability with CompactPCI 1 6 local bus 1 7 overview 1 6 peripheral slots 1 7 star trigger
12. A 12 A 13 electromagnetic compatibility A 9 environmental management A 10 mechanical A 11 rack mount kit dimensions figure A 14 safety 9 system reference clock A 11 specifications PXI 1031 acoustic emissions A 4 sound power 4 sound pressure level at operator position A 4 chassis cooling A 2 electrical AC input A 1 DC output A 2 environmental A 3 specifications PXI 1031DC acoustic emissions A 8 sound power 8 sound pressure level at operator position A 8 chassis cooling A 6 NI PXI 1031 PXI 1031DC User Manual l 4 electrical AC input A 5 DC input A 5 DC output A 6 environmental A 7 star trigger ST slot description 1 7 P1 J1 connector pinouts table B 4 P2 J2 connector pinouts table B 5 star trigger and local bus routing figure 1 8 support technical C 1 system controller slot description 1 6 P1 J1 connector pinouts table B 2 P2 J2 connector pinouts table B 3 system reference clock 1 8 specifications A 1 1 T technical support C 1 testing power up 2 4 DC 2 5 training and certification NI resources C 1 trigger bus 1 8 troubleshooting NI resources C 1 U unpacking PXI 1031 1 1 PXI 1031DC 1 1 Web resources C 1 ni com
13. ST slot 1 7 system reference clock 1 8 trigger bus 1 8 fan speed setting 2 3 filler panel kits 1 5 front view figure 1 3 handle feet kit 1 5 National Instruments Corporation F3 Index installation See installation configuration and operation key features 1 2 maintenance See maintenance of PXI 1031 module cooling air intake figure 2 3 optional equipment 1 5 rack mount kits 1 5 rack mounting 2 4 rear view of chassis 1 4 safety ground connecting 2 4 system controller slot description 1 6 PXI 1031DC backplane interoperability with CompactPCI 1 6 local bus 1 7 overview 1 6 peripheral slots 1 7 star trigger ST slot 1 7 system reference clock 1 8 trigger bus 1 8 bottom view of chassis 1 5 fan speed setting 2 3 installation See installation configuration and operation key features 1 2 maintenance See maintenance of PXI 1031DC module cooling air intake figure 2 3 optional equipment 1 5 rack mount kits 1 5 rack mounting 2 4 rear view of chassis 1 4 safety ground connecting 2 4 R rack mount kit dimensions figure A 14 rack mount kits 1 5 NI PXI 1031 PXI 1031DC User Manual rack mounting 2 4 related documentation viii S safety and caution notices 2 1 ground connecting 2 4 specifications 9 service interval 3 1 setting fan speed 2 3 software NI resources C 1 specifications backplane A 10 CE compliance A 9 dimensions figure
14. FAILURE WOULD CREATE A RISK OF HARM TO PROPERTY OR PERSONS INCLUDING THE RISK OF BODILY INJURY AND DEATH SHOULD NOT BE RELIANT SOLELY UPON ONE FORM OF ELECTRONIC SYSTEM DUE TO THE RISK OF SYSTEM FAILURE TO AVOID DAMAGE INJURY OR DEATH THE USER OR APPLICATION DESIGNER MUST TAKE REASONABLY PRUDENT STEPS TO PROTECT AGAINST SYSTEM FAILURES INCLUDING BUT NOT LIMITED TO BACK UP OR SHUT DOWN MECHANISMS BECAUSE EACH END USER SYSTEM IS CUSTOMIZED AND DIFFERS FROM NATIONAL INSTRUMENTS TESTING PLATFORMS AND BECAUSE A USER OR APPLICATION DESIGNER MAY USE NATIONAL INSTRUMENTS PRODUCTS IN COMBINATION WITH OTHER PRODUCTS IN A MANNER NOT EVALUATED OR CONTEMPLATED BY NATIONAL INSTRUMENTS THE USER OR APPLICATION DESIGNER IS ULTIMATELY RESPONSIBLE FOR VERIFYING AND VALIDATING THE SUITABILITY OF NATIONAL INSTRUMENTS PRODUCTS WHENEVER NATIONAL INSTRUMENTS PRODUCTS ARE INCORPORATED IN A SYSTEM OR APPLICATION INCLUDING WITHOUT LIMITATION THE APPROPRIATE DESIGN PROCESS AND SAFETY LEVEL OF SUCH SYSTEM OR APPLICATION Contents About This Manual CONVEMUONS PIE Related Documentation pt viii Chapter 1 Getting Started Unpack gs C 1 1 What You Need to Get Started niet ee 1 1 E 1 2 Chassis Description eee n a ede d 1 3 Optional Equipment 4 eet e eget HE ER iaai 1 5 EMC Filler Panels sinsnede etre 1 5 Rack Mount
15. GND RSV GND V I O RSV RSV GND 8 GND RSV RSV RSV GND RSV GND 7 GND RSV GND V I O RSV RSV GND 6 GND RSV RSV RSV GND RSV GND 5 GND RSV 64EN V I O RSV RSV GND 4 GND V I O PXI_BRSVB4 RSV GND RSV GND 3 GND PXI_LBR7 GND PXI_LBR8 PXI LBR9 PXI LBRI10 GND 2 GND PXI LBRI1 PXI LBR12 UNC PXI LBL7 PXI 8 GND 1 GND PXI LBL9 GND PXI LBL10 PXI LBL11 PXI LBL12 GND National Instruments Corporation B 7 NI PXI 1031 PXI 1031DC User Manual Technical Support and Professional Services Visit the following sections of the award winning National Instruments Web site at ni for technical support and professional services National Instruments Corporation Support Technical support at support includes the following resources Self Help Technical Resources For answers and solutions visit ni com support for software drivers and updates a searchable KnowledgeBase product manuals step by step troubleshooting wizards thousands of example programs tutorials application notes instrument drivers and so on Registered users also receive access to the NI Discussion Forums at ni com forums NI Applications Engineers make sure every question submitted online receives an answer Standard Service Program Membership This program entitles members to direct access to NI Applications Engineers via phone and email for one to one technical support as well as exclusive acces
16. Instruments and have no agency partnership or joint venture relationship with National Instruments Patents For patents covering National Instruments products technology refer to the appropriate location Help Patents in your software the patents txt file on your media or the National Instruments Patent Notice at ni com patents WARNING REGARDING USE OF NATIONAL INSTRUMENTS PRODUCTS 1 NATIONAL INSTRUMENTS PRODUCTS ARE NOT DESIGNED WITH COMPONENTS AND TESTING FOR A LEVEL OF RELIABILITY SUITABLE FOR USE IN OR IN CONNECTION WITH SURGICAL IMPLANTS OR AS CRITICAL COMPONENTS IN ANY LIFE SUPPORT SYSTEMS WHOSE FAILURE TO PERFORM CAN REASONABLY BE EXPECTED TO CAUSE SIGNIFICANT INJURY TO A HUMAN 2 IN ANY APPLICATION INCLUDING THE ABOVE RELIABILITY OF OPERATION OF THE SOFTWARE PRODUCTS CAN BE IMPAIRED BY ADVERSE FACTORS INCLUDING BUT NOT LIMITED TO FLUCTUATIONS IN ELECTRICAL POWER SUPPLY COMPUTER HARDWARE MALFUNCTIONS COMPUTER OPERATING SYSTEM SOFTWARE FITNESS FITNESS OF COMPILERS AND DEVELOPMENT SOFTWARE USED TO DEVELOP AN APPLICATION INSTALLATION ERRORS SOFTWARE AND HARDWARE COMPATIBILITY PROBLEMS MALFUNCTIONS OR FAILURES OF ELECTRONIC MONITORING OR CONTROL DEVICES TRANSIENT FAILURES OF ELECTRONIC SYSTEMS HARDWARE AND OR SOFTWARE UNANTICIPATED USES OR MISUSES OR ERRORS ON THE PART OF THE USER OR APPLICATIONS DESIGNER ADVERSE FACTORS SUCH AS THESE ARE HEREAFTER COLLECTIVELY TERMED SYSTEM FAILURES ANY APPLICATION WHERE A SYSTEM
17. JIS C8303 If you are missing any of the items listed in Table 1 1 or if you have the incorrect AC power cable contact National Instruments You have the option of powering the PXI 1031DC chassis with a DC power cable through the DC input connector on the rear panel of the chassis Refer to Figure 1 3 for the location of the DC connector Key Features The PXI 1031 PXI 1031DC combines a 4 slot PXI backplane with a structural design that has been optimized for maximum usability in a wide range of applications The key features of the chassis include the following Accepts 3U PXI and CompactPCI PICMG 2 0 R 3 0 modules 4 slot chassis with universal AC input and automatic voltage frequency ranging DC power input PXI 1031DC only On Off Standby power switch on the front panel for easy access AUTO HIGH temperature controlled fan speed based on air intake temperature to minimize audible noise Optional Carrying handle for portability Rack mountable NI PXI 1031 PXI 1031DC User Manual 1 2 ni com Chassis Description Chapter 1 Getting Started Figure 1 1 Figure 1 2 and Figure 1 3 show the key features of the PXI 1031 PXI 1031DC chassis front and rear panels Figure 1 1 shows the front view of the PXI 1031 the PXI 1031DC front panel is identical except for the chassis name stenciled on the face plate Figure 1 2 shows the rear view of the PXI 1031 Figure 1 3 shows the rear panel of the PXI 1031DC Fi
18. Specifications PXI 1031DC Chassis Electrical Caution Overloading the circuits may damage supply wiring Do not exceed the ratings on the equipment nameplate when connecting equipment to the supply circuit AC Input Input voltage 100 240 VAC Operating voltage 90 264 VAC Input frequency 50 60 Hz Operating frequency range 47 63 Hz Input current 4 2 Over current protection 6 3 A fuse in power supply no user serviceable components inside chassis 65 minimum Power disconnect The AC power cable provides main power disconnect The front panel power switch controls the internal chassis power supply that provides DC power to the backplane DC Input Input voltage 18 30 VDC Input current 30 10 A Etf ciency e tre 65 typical The operating range is guaranteed by design National Instruments Corporation A 5 NI PXI 1031 PXI 1031DC User Manual Specifications Power disconnect The DC power cable provides main power disconnect The front panel power switch controls
19. VISA Virtual Instrument System Architecture I O standard NI VISA provides support for the VISA API and also provides VISAIC a utility for instrument configuration and I O function execution Nanosecond one billionth of a second 10 9 Parts per million PCI eXtensions for Instrumentation PXI is an implementation of CompactPCI with added electrical features that meet the high performance requirements of instrumentation applications by providing triggering local buses and system clock capabilities 10 MHz PXI system reference clock Root mean square Seconds Deviation in signal transmission times An assembly installed into an empty slot to improve the airflow in adjacent slots Star trigger The backplane is unpowered off but the chassis is still connected to AC power mains NI PXI 1031 PXI 1031DC User Manual Glossary star trigger slot system reference clock TTL UL VAC pp This slot is located at slot 2 and has a dedicated trigger line between each peripheral slot Use this slot for a module with ST functionality that can provide individual triggers to all other peripherals A 10 MHz clock also called PXI_CLK10 that is distributed to all peripheral slots in the chassis as well as a BNC connector on the rear of chassis labeled 10 MHz REF OUT The system reference clock can be used for synchronization of multiple modules in a measurement or control system The 10 MHz REF IN and OUT BNC connectors o
20. left local bus signal lines on slot 2 are used for star trigger and do not connect to slot 1 The right local bus signal lines on slot 4 are not routed anywhere Each local bus is 13 lines wide and can pass analog signals up to 42 V between cards or provide a high speed TTL side band digital communication path that does not reduce the PXI bus bandwidth Initialization software uses the configuration information specific to adjacent peripheral modules to evaluate local bus compatibility National Instruments Corporation 1 7 NI PXI 1031 PXI 1031DC User Manual Chapter 1 Getting Started Star Triggers x Local Local a o Bus Bus c 5 5 9 5 a 2 2 5 g S a c 9 5 5 5 2 gt n PCI Arbitration and Clock Signals Figure 1 5 Star Trigger and Local Bus Routing Trigger Bus All slots share eight PXI trigger lines You can use these trigger lines in a variety of ways For example you can use triggers to synchronize the operation of several different PXI peripheral modules In other applications one module located in slot 2 can control carefully timed sequences of operations performed on other modules in the system Modules can pass triggers to one another allowing precisely timed responses to asynchronous external events the system is monitoring or controlling Syst
21. limit Relative humidity range 20 to 8096 noncondensing Tested in accordance with IEC 60068 2 56 Storage Environment Ambient temperature range 20 to 70 C Tested in accordance with IEC 60068 2 1 and IEC 60068 2 2 Meets MIL PRF 28800F Class 3 limits Relative humidity range 10 to 9596 noncondensing Tested in accordance with IEC 60068 2 56 National Instruments Corporation A 3 NI PXI 1031 PXI 1031DC User Manual Specifications Shock and Vibration Operational shock 30 g peak half sine 11 ms pulse Tested in accordance with IEC 60068 2 27 Meets MIL PRF 28800F Class 2 limits Random Vibration Operating insect ee aaah 5 to 500 Hz 0 3 Sims Nonoperating 5 to 500 Hz 2 4 gins Tested in accordance with IEC 60068 2 64 Nonoperating test profile exceeds the requirements of MIL PRF 28800F Class 3 Acoustic Emissions Sound Pressure Level at Operator Position Tested in accordance with ISO 7779 Meets MIL PRF 28800F requirements 1031 Auto fan at 25 C ambient 35 0 dBA High iiec 51 7 dBA Sound Power Tested in accordance with ISO 7779 PXI 1031 Auto fan at 25 C ambient 43 4 dBA High 59 5 dBA NI PXI 1031 PXI 1031DC User Manual A 4 ni com
22. required pxisys ini file will be complete NI PXI 1031 PXI 1031DC User Manual 2 10 ni com Chapter 2 Installation and Configuration 5 Apply the chassis number labels shown in Figure 2 7 included with your kit to each chassis in your PXI system and write in the chassis number accordingly in the white space Chassis EE Number Figure 2 7 Chassis Number Label Trigger Configuration in MAX Each chassis has one or more trigger buses each with eight lines numbered 0 through 7 that can be reserved and routed statically or dynamically Static reservation pre allocates a trigger line to prevent its configuration by a user program Dynamic reservation routing deallocation is performed on the fly within a user program based upon National Instruments APIs such as NI DAQmx Static reservation of trigger lines can be implemented by the user in MAX through the Triggers tab Reserved trigger lines will not be used by PXI modules dynamically configured by programs such as NI DAQmx This prevents the instruments from double driving the trigger lines possibly damaging devices in the chassis Complete the following steps to reserve these trigger lines in MAX 1 Configuration tree click the PXI chassis branch you want to configure 2 Click the Triggers tab at the bottom of the right hand pane Select which trigger lines you want to statically reserve 4 Click the Apply button Note For more information about rout
23. the answers you need contact your local office or NI corporate headquarters Phone numbers for our worldwide offices are listed at the front of this manual You also can visit the Worldwide Offices section of ni com niglobal to access the branch office Web sites which provide up to date contact information support phone numbers email addresses and current events NI PXI 1031 PXI 1031DC User Manual C 2 ni com Glossary Symbol Prefix Value 10 12 109 micro 10 6 m milli 10 3 k kilo 103 M mega 106 G giga 10 T tera 102 Symbols Degrees IV lA AC ANSI AUTO AWG Equal or greater than Equal or less than Percent Ohms Amperes Alternating current American National Standards Institute Automatic fan speed control American Wire Gauge National Instruments Corporation G 1 NI PXI 1031 PXI 1031DC User Manual Glossary backplane cfm CFR cm CompactPCI CSA D daisy chain DC DoC E efficiency EIA An assembly typically a printed circuit board with connectors and signal paths that bus the connector pins Celsius Cubic feet per minute Code of Federal Regulations Centimeters An adaptation of the Peripheral Component Interconnect PCI Specification 2 1 or later for industrial and or embedded applications requiring a more robust mechanical form factor than desktop PCI It uses industry standard m
24. 1 GND 17 GND 3 3 V SDONE SBO GND PERR GND 16 GND DEVSEL GND V I O STOP LOCK GND 15 GND 3 3 V FRAME IRDY GND TRDY GND 12 14 Key Area 11 GND AD 18 AD 17 AD 16 GND 2 GND 10 GND AD 21 GND 33V AD 20 AD 19 GND 9 GND C BE 3 IDSEL AD 23 GND AD 22 GND 8 GND AD 26 GND V I O AD 25 AD 24 GND 7 GND AD 30 AD 29 AD 28 GND AD 27 GND 6 GND REQ GND 33V CLK AD 31 GND GND 5 5 RST GND GNT GND 4 GND 4 GND V I O INTP INTS GND 3 GND INTA INTB INTC 5V INTD GND 2 GND TCK 5V TMS TDO TDI GND 1 GND 5V 12 V TRST 12 V 5V GND NI PXI 1031 PXI 1031DC User Manual B 6 ni com Appendix Pinouts Table B 6 P2 J2 Connector Pinout for the Generic Peripheral Slot Pin Z A B F 22 GND GA4 GA3 GA2 GAO GND 21 GND PXI_LBRO RSV PXI LBRI PXI LBR2 PXI LBR3 GND 20 GND PXI LBRA PXI LBR5 PXI LBLO GND PXI LBL1 GND 19 GND 1812 RSV PXI LBL3 PXI LBLA PXI LBLS5 GND 18 GND PXI TRIG3 4 5 GND PXI TRIG6 GND 17 GND PXI TRIG2 GND RSV PXI STAR PXI_CLK10 GND 16 GND PXI TRIGI PXI_TRIGO RSV GND PXI TRIG7 GND 15 GND PXI BRSVAIS GND RSV PXI LBL6 PXI LBR6 GND 14 GND RSV RSV RSV GND RSV GND 13 GND RSV GND V I O RSV RSV GND 12 GND RSV RSV RSV GND RSV GND 11 GND RSV GND V I O RSV RSV GND 10 GND RSV RSV RSV GND RSV GND 9
25. 1 PXI 1031DC Module Cooling Airflow Side View Install the chassis so that you can easily access the bottom panel Setting Fan Speed The AUTO HIGH fan speed selector switch is on the rear panel of the PXI 1031 and PXI 1031DC Refer to Figure 1 2 Rear View of the PXI 1031 Chassis or Figure 1 3 Rear View of the PXI 1031DC Chassis to locate the fan speed selector switch Select HIGH for maximum cooling performance recommended or AUTO for quieter operation The fan speed is determined by chassis intake air temperature when set to AUTO Installing Filler Panels To improve module cooling performance install filler panels provided with the chassis in unused or empty slots Secure with the captive mounting screws provided National Instruments Corporation 2 3 NI PXI 1031 PXI 1031DC User Manual Chapter 2 Installation and Configuration Rack Mounting Rack mount applications require the optional rack mount kits available from National Instruments Refer to Figure A 3 PXI 103I PXI 1031DC Rack Mount Kit Components and the instructions supplied with the rack mount kits to install your chassis in an instrument rack Note You may want to remove the feet from the chassis when rack mounting To do so remove the screws holding the feet in place Connecting Safety Ground UN Caution The PXI 1031 PXI 1031DC chassis is designed with a three position inlet that connects the cord set ground line to the chassis ground To minimize
26. Considerations The chassis is designed to operate on a bench or in an instrument rack Determine how you want to use the chassis and follow the appropriate installation instructions Providing Adequate Clearance Apertures in the top bottom front rear and along the right and left sides of the chassis facilitate power supply and module cooling Air enters through the fan inlet in the bottom of the chassis for module cooling It then exits through the upper sections at the right side back and through the top as shown in Figure 2 1 Air cooling the power supply enters the front and left side of the chassis which is shown in Figure 1 1 Front View of the PXI 1031 Chassis then exits through the rear of the chassis which is shown in Figure 1 2 Rear View of the PXI 1031 Chassis and Figure 1 3 Rear View of the PXI 1031DC Chassis Place the chassis on a bench top or in an instrument rack so that the fans air inlets and the air outlet apertures along the right and left sides the top and the back of the chassis have adequate ventilation Provide at least 44 5 mm 1 75 in clearance above behind and on the sides of the unit for adequate venting High power applications may require additional clearance NI PXI 1031 PXI 1031DC User Manual 2 2 ni com Chapter 2 Installation and Configuration 1 Air Outlets 2 Air Intake Figure 2 1 PXI 103
27. ND PXI STARI GND 19 GND PXI STAR2 RSV PXI STAR3 PXI_STAR4 PXI STARS GND 18 GND PXI TRIG3 PXI TRIG4 PXI TRIGS GND PXI TRIG6 GND 17 GND PXI TRIG2 GND RSV PXI CLK10 IN PXI CLK10 GND 16 GND PXI PXI TRIGO RSV GND PXI TRIG7 GND 15 GND PXI BRSVAIS GND RSV PXI STAR6 PXI LBR6 GND 14 GND RSV RSV RSV GND RSV GND 13 GND RSV GND V O RSV RSV GND 12 GND RSV RSV RSV GND RSV GND 11 GND RSV GND V I O RSV RSV GND 10 GND RSV RSV RSV GND RSV GND 9 GND RSV GND V O RSV RSV GND 8 GND RSV RSV RSV GND RSV GND 7 GND RSV GND V I O RSV RSV GND 6 GND RSV RSV RSV GND RSV GND 5 GND RSV 64EN V I O RSV RSV GND 4 GND V 1 O PXI BRSVB4 RSV GND RSV GND 3 GND PXI LBR7 GND PXI LBR8 PXI LBR9 PXI_LBR10 GND 2 GND PXI LBR11 PXI_LBR12 UNC PXI_STAR7 PXI_STAR8 GND 1 GND PXI STAR9 GND PXI_STAR10 5 PXI STAR12 GND National Instruments Corporation B 5 NI PXI 1031 PXI 1031DC User Manual Pinouts Table B 5 P1 J1 Connector Pinout for the Generic Peripheral Slot Pin Z A B F 25 GND 5 REQ64 ENUM 3 3 V 5 GND 24 GND AD 1 5V V I O AD 0 ACK64 GND 23 GND 3 3 V AD 4 AD 3 5V AD 2 GND 22 GND AD 7 GND 3 3 V ADI6 5 GND 21 GND 33V AD 9 AD 8 M66EN C BE 0 GND 20 GND AD 12 GND V O AD 11 AD 10 GND 19 GND 3 3 V AD 15 AD 14 GND AD 13 GND 18 GND SERR GND 3 3 V C BE
28. Table B 4 shows the P2 J2 connector pinout for the star trigger slot Table B 5 shows the P1 J1 connector pinout for the peripheral slots Table B 6 shows the P2 J2 connector pinout for the peripheral slots Note signals are shown in bold National Instruments Corporation B 1 NI PXI 1031 PXI 1031DC User Manual Pinouts Table B 1 P1 J1 Connector Pinout for the System Controller Slot Pin Z A B F 25 GND 5 REQ64 ENUM 3 3 V 5V GND 24 GND AD 1 5 V I O AD 0 ACK64 GND 23 GND 3 3 V AD 4 AD 3 5V AD 2 GND 22 GND AD 7 GND 3 3 V AD 6 AD 5 GND 21 GND 3 3 V AD 9 AD 8 M66EN C BE 0 GND 20 GND AD 12 GND V I O AD 11 AD 10 GND 19 GND 3 3 V AD 15 AD 14 GND AD 13 GND 18 GND SERR GND 33V PAR C BE 1 GND 17 GND 33V SDONE SBO GND PERR GND 16 GND DEVSEL GND V I O STOP LOCK GND 15 GND 33V FRAME IRDY GND TRDY GND 12 14 Key Area 11 GND AD 18 AD 17 AD 16 GND C BE 2 GND 10 GND AD 21 GND 3 3 V AD 20 AD 19 GND 9 GND C BE 3 IDSEL AD 23 GND AD 22 GND 8 GND AD 26 GND V O AD 25 AD 24 GND 7 GND AD 30 AD 29 AD 28 GND AD 27 GND 6 GND REQ GND 3 3 V CLK AD 31 GND 5 GND 5 5 RST GND GNT GND GND BRSVP1A4 GND V I O INTP INTS GND 3 GND INTA INTB INTC 5V INTD GND 2 GND TCK 5V TMS TDO TDI GND 1 GND 5V 12 V TRST 12 V 5V GND
29. User Manual Viii ni com Getting Started This chapter describes the key features of the NI PXI 1031 and PXI 1031DC chassis and lists the kit contents and optional equipment you can order from National Instruments Unpacking Carefully inspect the shipping container and the chassis for damage Check for visible damage to the metal work Check to make sure all handles hardware and switches are undamaged Inspect the inner chassis for any possible damage debris or detached components If damage appears to have been caused during shipment file a claim with the carrier Retain the packing material for possible inspection and or reshipment What You Need to Get Started Q Q D CO DO LU National Instruments Corporation NI PXI 1031 or NI PXI 1031DC chassis Filler panels Power cable either AC power cable refer to Table 1 1 for AC power cables DC power cable NI PXI 1031 PXI 1031DC User Manual Read Me First Safety and Electromagnetic Compatibility Driver CD ROM containing NI PXI chassis software Chassis number labels 1 1 NI PXI 1031 PXI 1031DC User Manual Chapter 1 Getting Started Table 1 1 AC Power Cables Power Cable Reference Standards Standard 120 V USA NEMA 5 15 Switzerland 220 V SEV Australia 240 V AS C112 Universal Euro 230 V CEE 7 IV IEC83 North America 240 V NEMA 6 15 United Kingdom 230 V BS 1363 IEC83 Japan 100 V
30. bient 54 3 dBA High 58 2 dBA NI PXI 1031 PXI 1031DC User Manual 8 Specifications Common Specifications Safety This product is designed to meet the requirements of the following standards of safety for information technology equipment e 61010 1 EN 61010 1 e UL61010 1 CSA 61010 1 Note For UL and other safety certifications refer to the product label or the Online Product Certification section Electromagnetic Compatibility This product meets the requirements of the following EMC standards for electrical equipment for measurement control and laboratory use e EN 61326 IEC 61326 Class A emissions Basic immunity e EN 55011 CISPR 11 Group 1 Class A emissions e AS NZS CISPR 11 Group 1 Class A emissions e FCC 47 CFR Part 15B Class A emissions e ICES 001 Class A emissions Note For the standards applied to assess the EMC of this product refer to the Online Product Certification section Note For EMC compliance operate this device with shielded cabling CE Compliance C This product meets the essential requirements of applicable European Directives as follows e 2006 95 EC Low Voltage Directive safety e 2004 108 EC Electromagnetic Compatibility Directive EMC National Instruments Corporation A 9 NI PXI 1031 PXI 1031DC User Manual Specifications Online Product Certification Refer t
31. ctPCI Specification PICMG 2 0 3 0 for details regarding V I O System Controller Slot The system controller slot is slot 1 of the chassis as defined by the PXI specification It has three controller expansion slots for system controller modules that are wider than one slot As defined in the PXI specification these slots allow the controller to expand to the left to prevent the controller from using peripheral slots NI PXI 1031 PXI 1031DC User Manual 1 6 ni com Chapter 1 Getting Started Star Trigger Slot The star trigger ST slot is slot 2 This slot has dedicated equal length trigger lines between slot 2 and peripheral slots 3 and 4 refer to Figure 1 5 Slot 2 is intended for modules with ST functionality that can provide individual triggers to all other peripheral modules However if you do not require advanced trigger functionality you can install any standard peripheral module in this slot The star trigger slot can also be used to provide a PXI_CLK10 signal to the backplane For more information regarding PXI_CLK10 refer to the System Reference Clock section Peripheral Slots There are three peripheral slots including the star trigger slot Local Bus The PXI backplane local bus is a daisy chained bus that connects each peripheral slot with adjacent peripheral slots to the left and right refer to Figure 1 5 For example the right local bus of slot 2 connects to the left local bus of slot 3 and so on The
32. echanical components and high performance connector technologies to provide an optimized system intended for rugged applications It is electrically compatible with the PCI Specification which enables low cost PCI components to be utilized in a mechanical form factor suited for rugged environments Canadian Standards Association A method of propagating signals along a bus in which the devices are prioritized on the basis of their position on the bus Direct current Declaration of Conformity Ratio of output power to input power expressed as a percentage Electronic Industries Association NI PXI 1031 PXI 1031DC User Manual G 2 ni com embedded system controller EMC EMI F FCC filler panel G GPIB amp rms IEC TEEE National Instruments Corporation G 3 Glossary A module configured for installation in slot of a PXI chassis This device is unique in the PXI system in that it performs the system controller functions including clock sourcing and arbitration for data transfers across the backplane Installing such a device into any other slot can damage the device the PXI backplane or both Electromagnetic Compatibility Electromagnetic Interference Federal Communications Commission A blank module front panel used to fill empty slots in the chassis 1 grams 2 a measure of acceleration approximately equal to 9 8 m s General Purpose Interface Bus IEEE 488 A measure of random vibratio
33. em Reference Clock The PXI 1031 PX1 1031DC supplies the PXI 10 MHz system clock signal PXI CLK10 independently to each peripheral slot An independent buffer having a source impedance matched to the backplane and a skew of less than 250 ps between slots drives the clock signal to each peripheral slot You can use this common reference clock signal to synchronize multiple modules in a measurement or control system You can drive CLK10 from an external source through the PXI_CLK10_IN pin on the P2 connector of the star trigger slot Refer to Table B 4 P2 J2 Connector Pinout for the Star Trigger Slot You must manually switch S2 on the chassis backplane to enable or disable routing an external clock to peripheral slots NI PXI 1031 PXI 1031DC User Manual 1 8 ni com Installation and Configuration This chapter describes how to install configure and use the PXI 1031 and PXI 1031DC chassis Before connecting the chassis to a power source read this chapter and the Read Me First Safety and Electromagnetic Compatibility document included with your chassis Safety Information Caution Before undertaking any troubleshooting maintenance or exploratory procedure carefully read the following caution notices This equipment contains voltage hazardous to human life and safety and is capable of inflicting personal injury e Chassis Grounding The chassis requires a connection from the premise wire safety ground to t
34. environment rohs china For information about China RoHS compliance go ni com environment rohs_china Backplane SIZE E 3U sized system slot with three system expansion slots and three peripheral slots Compliant with IEEE 1101 10 mechanical packaging Hardware Specification Revision 2 2 compliant Accepts both PXI and CompactPCI 3U modules NI PXI 1031 PXI 1031DC User Manual A 10 ni com Specifications VO 5 V Backplane bare board material UL 94 V 0 recognized Backplane connectors Conform to IEC 917 and IEC 1076 4 101 and are UL 94 0 rated 10 MHz System Reference Clock 10 MHz REF Maximum clock skew between slots 250 ps Built in 10 MHz clock Pure M 25 ppm guaranteed over the operating temperature range Mechanical Overall dimensions standard chassis sop 177 mm 6 97 in Note 12 7 mm 0 50 in is added to height when feet are installed 257 1 mm 10 12 in ei 212 8 mm 8 38 in Weight iicet heer as 5 kg 11 0 165 Chassis 5 Sheet Aluminum Extruded Aluminum Cold Rolled Steel Nylon Clear Chromate Conversion Coat on Aluminum Electrodeposited Nickel Plate on Cold Rolled Steel Polyester Urethane Powder Paint
35. eration or maintenance instructions owner s modification of the product owner s abuse misuse or negligent acts and power failure or surges fire flood accident actions of third parties or other events outside reasonable control Copyright Under the copyright laws this publication may not be reproduced or transmitted in any form electronic or mechanical including photocopying recording storing in an information retrieval system or translating in whole or in part without the prior written consent of National Instruments Corporation National Instruments respects the intellectual property of others and we ask our users to do the same NI software is protected by copyright and other intellectual property laws Where NI software may be used to reproduce software or other materials belonging to others you may use NI software only to reproduce materials that you may reproduce in accordance with the terms of any applicable license or other legal restriction Trademarks LabVIEW National Instruments NI ni com the National Instruments corporate logo and the Eagle logo are trademarks of National Instruments Corporation Refer to the Trademark Information at ni com trademarks for other National Instruments trademarks Other product and company names mentioned herein are trademarks or trade names of their respective companies Members of the National Instruments Alliance Partner Program are business entities independent from National
36. first placing the module card edges into the front module guides top and bottom as shown in Figure 2 5 Slide the module to the rear of the chassis making sure that the injector ejector handle is pushed down as shown in Figure 2 3 3 When you begin to feel resistance push up on the injector ejector handle to fully inject the module into the chassis frame Secure the module front panel to the chassis using the module front panel mounting screws NI PXI 1031 PXI 1031DC User Manual 2 8 ni com Chapter 2 Installation and Configuration 1 2 PXI 1031 PXI 1031DC Chassis 3 Injector Ejector Handle 5 NI PXI Controller Injector Ejector Rail 4 PXI Module Figure 2 5 Installing PX or CompactPCI Modules System Configuration with MAX Configuration of the PXI system is handled through Measurement amp Automation Explorer MAX included on the NI Driver CD ROM packaged with your kit MAX creates the pxisys ini file that defines the layout and parameters of your PXI system After installing the software on the NI Driver CD ROM the MAX icon will be present on the desktop The configuration steps for single or multiple chassis systems are the same National Instruments Corporation 2 9 NI PXI 1031 PXI 1031DC User Manual Chapter 2 Installation and Configuration File Edit View Tools Help Chassis 1 PXI 1031 Measurement amp Automation Explorer nj x Configuration
37. gure 1 4 shows the bottom of the chassis both types of chassis will be identical on the bottom NI PXI 1031 p 9 0 NATIONAL INSTRUMENTS o CA oooopooopooocoooo Fu m 000000 7 Backplane Rubber Foot RON Expansion Slots Controller Expansion Slots ONO Star Trigger Peripheral Slot Embedded Controller Slot Power Switch Standby Power Supply Airflow Intake Vents Figure 1 1 Front View of the PXI 1031 Chassis National Instruments Corporation 1 3 NI PXI 1031 PXI 1031DC User Manual Chapter 1 Getting Started 1 OD OO DD De 2099 OOOOOOOCOOOOOOOOOOO e6069008000000600600090 eA tLe P A G T 1 Rear Exhaust Vents 2 AC Input 4 Chassis Ground Screw 5 Fan Speed Selector Switch 3 Power Supply Fan Exhaust 6 Rubber Foot Figure 1 2 Rear View of the PXI 1031 Chassis A eoo
38. he AC inlet The power switch allows you to power on the chassis or place it in standby mode Press the power switch to the On position if not already on Observe that all fans become operational Connecting to DC Power Source PXI 1031DC Only Table 2 1 DC Power Requirements Electrical Element Requirement Voltage 18 30 VDC DC Input Current 30 10A For full chassis power the DC source must be capable of providing a minimum of 300 watts of continuous power per feed pair to the P1 connector on the PXI 1031DC power supply DC Connector Figure 2 2 shows the DC connector P1 that appears on the rear panel of the PXI 1031DC power supply Positive Negative Figure 2 2 The P1 DC Input Connector National Instruments Corporation 2 5 NI PXI 1031 PXI 1031DC User Manual Chapter 2 Installation and Configuration To build custom DC cable be sure to note the positive and negative terminals shown in Figure 2 2 Use the following components or their equivalents to mate to the P1 port Positronic connector part number CBD7W2F0000 Positronic hood part number D15000GEO e Two Positronic contacts part number FS4008D choice of solder cup or crimp terminals Use of UL listed AWG 10 wire is recommended maximum length 216 in Install an F30A 500 VDC 600 VAC 1 5 in x 41 in 10 mm x 38 mm Midget fast acting fuse on the positive wire of the custo
39. he Read Me First Safety and Electromagnetic Compatibility document shipped with the product for precautions to take Bold text denotes items that you must select or click in the software such as menu items and dialog box options Bold text also denotes parameter names Italic text denotes variables emphasis a cross reference a hardware label or an introduction to a key concept Italic text also denotes text that is a placeholder for a word or value that you must supply Text in this font denotes text or characters that you should enter from the keyboard sections of code programming examples and syntax examples This font is also used for the proper names of disk drives paths directories programs subprograms subroutines device names functions operations variables filenames and extensions National Instruments Corporation vii NI PXI 1031 PXI 1031DC User Manual About This Manual Related Documentation The following documents contain information that you may find helpful as you read this manual e NI PXI 1031DC DC Cable Kit Installation Guide e CompactPCI Specification PICMG 2 0 3 0 e PXI Hardware Specification e PXI Software Specification e IEEE 1101 1 1991 JEEE Standard for Mechanical Core Specifications for Microcomputers Using IEC 603 2 Connectors e IEEE 1101 10 ZEEE Standard for Additional Mechanical Specifications for Microcomputers Using IEEE 1101 1 Equipment Practice NI PXI 1031 PXI 1031DC
40. he chassis ground The earth safety ground must be connected during use of this equipment to minimize shock hazards Refer to the Connecting Safety Ground section for instructions on connecting safety ground Live Circuits Operating personnel and service personnel must not remove protective covers when operating or servicing the chassis Adjustments and service to internal components must be undertaken by qualified service technicians During service of this product the mains connector to the premise wiring must be disconnected Dangerous voltages may be present under certain conditions use extreme caution Explosive Atmosphere Do not operate the chassis in conditions where flammable gases are present Under such conditions this equipment is unsafe and may ignite the gases or gas fumes National Instruments Corporation 2 1 NI PXI 1031 PXI 1031DC User Manual Chapter 2 Installation and Configuration e Part Replacement Only service this equipment with parts that are exact replacements both electrically and mechanically Contact National Instruments for replacement part information Installation of parts with those that are not direct replacements may cause harm to personnel operating the chassis Furthermore damage or fire may occur if replacement parts are unsuitable e Modification Do not modify any part of the chassis from its original condition Unsuitable modifications may result in safety hazards Chassis Cooling
41. ii NI resources C 1 related documentation viii drivers NI resources C 1 E electromagnetic compatibility specifications A 9 EMC filler panel kit 1 5 environmental management specifications A 10 examples NI resources C 1 F fan setting speed 2 3 filler panel installation 2 3 G ground connecting 2 4 H handle feet kit 1 5 help technical support C 1 NI PXI 1031 PXI 1031DC User Manual installation configuration and operation chassis initialization file 2 11 configuration in MAX figure 2 10 connecting safety ground 2 4 filler panel installation 2 3 installing a PXI controller 2 6 module installation 2 7 2 8 CompactPCI or PXI modules figure 2 9 injector ejector handle position figure 2 7 configuration in MAX 2 9 trigger configuration 2 11 controller installed in a PXI 1031 chassis figure 2 8 controller installed in a PXI 1031DC chassis figure 2 8 rack mounting 2 4 setting fan speed 2 3 site considerations 2 2 testing power up 2 4 DC 2 5 unpacking PXI 1031 1 1 PXI 1031DC 1 1 instrument drivers NI resources C 1 interoperability with CompactPCI 1 6 K key features 1 2 KnowledgeBase C 1 L local bus routing figure 1 7 star trigger and local bus routing figure 1 8 NI PXI 1031 PXI 1031DC User Manual l 2 maintenance of PXI 1031 3 1 cleaning exterior cleaning 3 2 interior cleaning 3 2 DC fuse replacement
42. ing and reserving triggers refer to KnowledgeBase 3TJDONDS at ni com support Using System Configuration and Initialization Files The PXI specification allows many combinations of PXI chassis and system modules To assist system integrators the manufacturers of PXI chassis and system modules must document the capabilities of their products The minimum documentation requirements are contained in ini files which consist of ASCII text System integrators configuration utilities and device drivers can use these ini files National Instruments Corporation 2 11 NI PXI 1031 PXI 1031DC User Manual Chapter 2 Installation and Configuration The capability documentation for the PXI 1031 PXI 1031DC chassis is contained in the chassis ini file on the software media that comes with the chassis The information in this file is combined with information about the system controller to create a single system initialization file called pxisys ini PXI System Initialization The system controller manufacturer either provides a pxisys ini file for the particular chassis model that contains the system controller or provides a utility that can read an arbitrary chassis ini file and generate the corresponding pxisys ini file System controllers from National Instruments use MAX to generate the pxisys ini file from the chassis ini file Device drivers and other utility software read the pxisys ini file to obtain system information De
43. m Configuration Trigger Configuration in MAX Using System Configuration and Initialization Files Chapter 3 Maintenance DC Fuse Replacement PXI 1031DC Only Service Interval oem Ra qe RA AR e See NES Preparation siete ER e EPI UEM RR ERU ERN MR Cleaning nh P dete eret tees Interior Cleaning sisisi Exterior Cleaning uinea eR DERE Appendix A Specifications Appendix B Pinouts Appendix C Technical Support and Professional Services Glossary Index NI PXI 1031 PXI 1031DC User Manual vi ni com About This Manual Conventions The NI PXI 1031 PXI 1031DC User Manual contains information about installing configuring using and maintaining the NI PXI 1031 and PXI 1031DC chassis bold italic monospace The following conventions are used in this manual The symbol leads you through nested menu items and dialog box options to a final action The sequence Options Settings General directs you to pull down the Options menu select the Settings item and select General from the last dialog box This icon denotes a note which alerts you to important information This icon denotes a caution which advises you of precautions to take to avoid injury data loss or a system crash When this symbol is marked on the product refer to t
44. m cable as close to the power source as practical Ferraz Shawmut FEB 81 81 fuse holder with Ferraz Shawmut FSB1 insulating boots and an ATM30 fuse is recommended Refer to the NJ PXI 1031DC DC Cable Kit Installation Guide for information on fuse installation iyi Note You can purchase an optional DC cable from National Instruments that incorporates an in line fuse and the mating connector for the P1 port Installing a PXI Controller This section contains general instructions for installing a PXI controller in the chassis Refer to your PXI controller user manual for specific instructions and cautions Complete the following steps to install a controller 1 Connect the AC or DC power source to the PXI chassis before installing the controller The AC power cord grounds the chassis and protects it from electrical damage while you install the controller For DC powered applications make sure the chassis is properly grounded through the chassis ground screw Make sure the chassis power switch is in the Off Standby position N Caution To protect both yourself and the chassis from electrical hazards leave the chassis off until you finish installing the controller NI PXI 1031 PXI 1031DC User Manual 2 6 ni com Chapter 2 Installation and Configuration Install the controller into the system controller slot slot 1 indicated by the red card guides by first placing the controller edges into the front controller guides to
45. n the root mean square of acceleration levels in a random vibration test profile Hours Hertz cycles per second International Electrotechnical Commission an organization that sets international electrical and electronics standards Institute of Electrical and Electronics Engineers Mainframe peak current NI PXI 1031 PXI 1031DC User Manual Glossary in inhibit jitter kg L Ib load regulation MAX MHz NEMA NI Inches To turn off A measure of the small rapid variations in clock transition times from their nominal regular intervals Units seconds RMS Kilograms Kilometers Pounds The maximum steady state percentage that a DC voltage output will change as a result of a step change from no load to full load output current Meters NI Measurement amp Automation Explorer the utility that allows you to configure and test your PXI system Megahertz One million Hertz one Hertz equals one cycle per second Millisecond one thousandth of a second 10 3 National Electrical Manufacturers Association National Instruments NI PXI 1031 PXI 1031DC User Manual G 4 ni com NI DAQmx NI VISA ns ppm PXI PXI_CLK10 R RMS S S skew slot blocker ST standby National Instruments Corporation G 5 Glossary National Instruments driver that controls the operation of National Instruments data acquisition DAQ devices National Instruments implementation of the
46. n the rear of the chassis can be used to synchronize multiple chassis to one reference clock The PXI backplane specification defines implementation guidelines for CLKI10 Transistor transistor logic Underwriter s Laboratories Volts Volts alternating current or Vins Peak to peak voltage Watts NI PXI 1031 PXI 1031DC User Manual G 6 ni com Index A AC power cables table 1 2 backplane interoperability with CompactPCI 1 6 local bus 1 7 overview 1 6 peripheral slots 1 7 specifications A 10 star trigger ST slot 1 7 system reference clock 1 8 trigger bus 1 8 cables power table 1 2 calibration certificate NI resources C 2 CE compliance specifications A 9 chassis initialization file 2 11 chassis number label figure 2 11 CompactPCI installing modules figure 2 9 interoperability with PXI 1031 backplane 1 6 interoperability with PXI 1031DC backplane 1 6 configuration See installation configuration and operation conventions used in the manual vii cooling air cooling of PXI 1031 2 2 air cooling of PXI 1031DC 2 2 air intake figure 2 3 filler panel installation 2 3 setting fan speed 2 3 National Instruments Corporation D DC fuse replacement 3 1 power cable 1 6 power up testing 2 5 Declaration of Conformity NI resources C 2 diagnostic tools NI resources C 1 dimensions figure A 12 A 13 documentation conventions used in manual v
47. o the product Declaration of Conformity DoC for additional regulatory compliance information To obtain product certifications and the DoC for this product visit ni com certification search by model number or product line and click the appropriate link in the Certification column Environmental Management Dt NI is committed to designing and manufacturing products in an environmentally responsible manner NI recognizes that eliminating certain hazardous substances from our products is beneficial to the environment and to NI customers For additional environmental information refer to the NI and the Environment Web page at ni com environment This page contains the environmental regulations and directives with which NI complies as well as other environmental information not included in this document Waste Electrical and Electronic Equipment WEEE EU Customers At the end of the product life cycle all products must be sent to WEEE recycling center For more information about WEEE recycling centers National Instruments WEEE initiatives and compliance with WEEE Directive 2002 96 EC on Waste and Electronic Equipment visit com environment weee ChE QL PERA National instruments RoHS National Instruments RoHS ni com
48. oration All rights reserved Important Information Warranty The NI PXI 1031 PXI 1031DC chassis is warranted against defects in materials and workmanship for a period of one year from the date of shipment as evidenced by receipts or other documentation National Instruments will at its option repair or replace equipment that proves to be defective during the warranty period This warranty includes parts and labor The media on which you receive National Instruments software are warranted not to fail to execute programming instructions due to defects in materials and workmanship for a period of 90 days from date of shipment as evidenced by receipts or other documentation National Instruments will at its option repair or replace software media that do not execute programming instructions if National Instruments receives notice of such defects during the warranty period National Instruments does not warrant that the operation of the software shall be uninterrupted or error free A Return Material Authorization RMA number must be obtained from the factory and clearly marked on the outside of the package before any equipment will be accepted for warranty work National Instruments will pay the shipping costs of returning to the owner parts which are covered by warranty National Instruments believes that the information in this document is accurate The document has been carefully reviewed for technical accuracy In the event that technical o
49. ovide a handle for portability National Instruments Corporation 1 5 NI PXI 1031 PXI 1031DC User Manual Chapter 1 Getting Started DC Power Cable PXI 1031DC Only An optional DC power cable is available from National Instruments to provide power through the DC input connector on the rear panel of the chassis PXI 1031 PXI 1031DC Backplane Overview Interoperability with CompactPCI The PXI 1031 PXI 1031DC backplane is interoperable with 5 V and universal PXI compatible products and standard CompactPCI products This is an important feature because some PXI systems may require components that do not implement PXI specific features For example you may want to use a standard CompactPCI network interface card in a chassis The signals on the backplane P1 connectors meet the requirements of the CompactPCI specification for both peripheral and system modules Refer to Appendix B Pinouts for pinout information The PXI specific signals are on the backplane P2 connectors and are found only on those signal lines reserved or not used in the CompactPCI 64 bit specification Therefore all modules that meet the requirements of the CompactPCI 64 bit specification will function in the PXI 1031 PXI 1031DC Refer to Appendix B Pinouts for pinout information Note The PXI 1031 backplane is 32 bit PCI 64 bit CompactPCI cards will operate in 32 bit mode in this chassis The chassis backplane has 5 V I O Refer to the Compa
50. p and bottom Slide the controller to the rear of the chassis making sure that the injector ejector handle is pushed down as shown in Figure 2 3 National Instruments Corporation Figure 2 3 Injector Ejector Handle Position during Controller or Peripheral Module Insertion When you begin to feel resistance push up on the injector ejector handle to inject the controller fully into the chassis frame Secure the controller front panel to the chassis using the controller front panel mounting screws Connect the keyboard mouse and monitor to the appropriate connectors Connect devices to ports as required by your system configuration Power on the chassis Verify that the controller boots If the controller does not boot refer to your controller user manual 2 7 NI PXI 1031 PXI 1031DC User Manual Chapter 2 Installation and Configuration Figure 2 4 shows a PXI controller installed in the system controller slot of PXI 1031 PXI 1031DC chassis You can place CompactPCI or PXI modules in any other slot 1 PXI 1031 PXI 1031DC Chassis 3 NI PXI Controller 2 Injector Ejector Rail Figure 2 4 NI PXI Controller Installed in a PXI 1031 PXI 1031DC Chassis Installing PXI Modules Complete the following steps to install a module 1 Make sure the power switch is in the Off Standby position 2 Install a module into a chassis slot by
51. r typographical errors exist National Instruments reserves the right to make changes to subsequent editions of this document without prior notice to holders of this edition The reader should consult National Instruments if errors are suspected In no event shall National Instruments be liable for any damages arising out of or related to this document or the information contained in it EXCEPT AS SPECIFIED HEREIN NATIONAL INSTRUMENTS MAKES NO WARRANTIES EXPRESS OR IMPLIED AND SPECIFICALLY DISCLAIMS ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE CUSTOMER S RIGHT TO RECOVER DAMAGES CAUSED BY FAULT OR NEGLIGENCE ON THE PART OF NATIONAL INSTRUMENTS SHALL BE LIMITED TO THE AMOUNT THERETOFORE PAID BY THE CUSTOMER NATIONAL INSTRUMENTS WILL NOT BE LIABLE FOR DAMAGES RESULTING FROM LOSS OF DATA PROFITS USE OF PRODUCTS OR INCIDENTAL OR CONSEQUENTIAL DAMAGES EVEN IF ADVISED OF THE POSSIBILITY THEREOF This limitation of the liability of National Instruments will apply regardless of the form of action whether in contract or tort including negligence Any action against National Instruments must be brought within one year after the cause of action accrues National Instruments shall not be liable for any delay in performance due to causes beyond its reasonable control The warranty provided herein does not cover damages defects malfunctions or service failures caused by owner s failure to follow the National Instruments installation op
52. rist strap or equivalent while servicing the chassis National Instruments Corporation 3 1 NI PXI 1031 PXI 1031DC User Manual Chapter 3 Maintenance Cleaning Caution Always disconnect the AC power cable and the DC power cable if you are working with a PXI 1031DC chassis before cleaning or servicing the chassis Cleaning procedures consist of exterior and interior cleaning of the chassis Refer to your module user documentation for information on cleaning individual CompactPCI or PXI modules Interior Cleaning Use a dry low velocity stream of air to clean the interior of the chassis Use a soft bristle brush for cleaning around components Exterior Cleaning UN Cautions Avoid getting moisture inside the chassis during exterior cleaning especially through the top vents Use just enough moisture to dampen the cloth Do not wash the front or rear panel connectors or switches Cover these components while cleaning the chassis Do not use harsh chemical cleaning agents they may damage the chassis Avoid chemicals that contain benzene toluene xylene acetone or similar solvents Clean the exterior surfaces of the chassis with a dry lint free cloth or a soft bristle brush If any dirt remains wipe with a cloth moistened in a mild soap solution Remove any soap residue by wiping with a cloth moistened with clear water Do not use abrasive compounds on any part of the chassis NI PXI 1031 PXI 1031DC User Manual 3 2 ni com
53. s to on demand training modules via the Services Resource Center NI offers complementary membership for a full year after purchase after which you may renew to continue your benefits For information about other technical support options in your area visit ni com services or contact your local office at ni com contact Training and Certification Visit ni com training for self paced training eLearning virtual classrooms interactive CDs and Certification program information You also can register for instructor led hands on courses at locations around the world System Integration If you have time constraints limited in house technical resources or other project challenges National Instruments Alliance Partner members can help To learn more call your local NI office or visit ni com alliance C 1 NI PXI 1031 PXI 1031DC User Manual Technical Support and Professional Services Declaration of Conformity DoC A DoC is our claim of compliance with the Council of the European Communities using the manufacturer s declaration of conformity This system affords the user protection for electromagnetic compatibility EMC and product safety You can obtain the DoC for your product by visiting ni com certification e Calibration Certificate If your product supports calibration you can obtain the calibration certificate for your product at ni com calibration If you searched ni com and could not find
54. shock hazard make sure the electrical power outlet you use to power the chassis has an appropriate earth safety ground For DC powered applications or if your power outlet does not have an appropriate ground connection you must connect the premise safety ground to the chassis grounding screw located on the rear panel Refer to Figure 1 2 Rear View of the PXI 1031 Chassis or Figure 1 3 Rear View of the PXI 1031DC Chassis to locate the chassis grounding screw Complete the following steps to connect the safety ground 1 Connect a 10 AWG 2 6 mm wire to the chassis grounding screw using a grounding lug The wire must have green insulation with a yellow stripe or must be noninsulated bare 2 Attach the opposite end of the wire to permanent earth ground using toothed washers or a toothed lug Connecting to Power Source Cautions Do not install modules prior to performing the following power on test To completely remove power you must disconnect the AC power cable and DC power if applicable If both AC and DC power cables are connected the chassis will draw power from both sources NI PXI 1031 PXI 1031DC User Manual 2 4 ni com Chapter 2 Installation and Configuration Connecting to an AC Power Source Attach input power through the rear AC inlet using the appropriate AC power cable supplied Refer to Figure 1 2 Rear View of the PXI 1031 Chassis or to Figure 1 3 Rear View of the PXI 1031DC Chassis to locate t
55. the internal chassis power supply that provides DC power to the backplane DC Output DC current capacity Imp Voltage 0 50 3 3 V 12A 5 V 17A 12 V 2A 12 V 0 8 3 Notes The output power is derated 5 W C above 45 The combined loading on 5 VDC and 3 3 VDC must not exceed 112 W For AC powered applications the combined loading must not exceed 145 6 W Overcurrent All outputs protected from short circuit and overload Overvoltage protection All outputs protected from overvoltage Cycle the primary power and front power switch to restart Chassis Cooling Per slot cooling capacity 25W Slot airflow direction P1 to P2 bottom of module to top of module NI PXI 1031 PXI 1031DC User Manual A 6 ni com Module cooling Tinta ke sai estes cesses EXha st 25 deett Power supply cooling Environmental Operating Maximum altitude Installation Category Pollution Degree Operating Environment Ambient temperature range Storage Environment Ambient temperature range Relative humidity range
56. tor Pinout for the Star Trigger Slot Pin Z A B F 25 GND 5 REQ64 ENUM 3 3 V 5 GND 24 GND AD 1 5V V I O AD 0 ACK64 GND 23 GND 3 3 V AD 4 AD 3 5V AD 2 GND 22 GND AD 7 GND 3 3 V ADI6 5 GND 21 GND 33V AD 9 AD 8 M66EN C BE 0 GND 20 GND AD 12 GND V O AD 11 AD 10 GND 19 GND 3 3 V AD 15 AD 14 GND AD 13 GND 18 GND SERR GND 3 3 V C BE 1 GND 17 GND 3 3 V SDONE SBO GND PERR GND 16 GND DEVSEL GND V I O STOP LOCK GND 15 GND 3 3 V FRAME IRDY GND TRDY GND 12 14 Key Area 11 GND AD 18 AD 17 AD 16 GND 2 GND 10 GND AD 21 GND 33V AD 20 AD 19 GND 9 GND C BE 3 IDSEL AD 23 GND AD 22 GND 8 GND AD 26 GND V I O AD 25 AD 24 GND 7 GND AD 30 AD 29 AD 28 GND AD 27 GND 6 GND REQ GND 33V CLK AD 31 GND GND 5 5 RST GND GNT GND 4 GND 4 GND V I O INTP INTS GND 3 GND INTA INTB INTC 5V INTD GND 2 GND TCK 5V TMS TDO TDI GND 1 GND 5V 12 V TRST 12 V 5V GND NI PXI 1031 PXI 1031DC User Manual B 4 ni com Appendix Pinouts Table B 4 P2 J2 Connector Pinout for the Star Trigger Slot Pin Z A B F 22 GND GA4 GA3 GA2 GAO GND 21 GND PXI_LBRO RSV PXI_LBR1 LBR2 PXI_LBR3 GND 20 GND PXI_LBR4 PXI LBR5 PXI STARO G
57. vice drivers should have no need to directly read the chassis ini file For detailed information regarding initialization files refer to the PXI specification at www pxisa org NI PXI 1031 PXI 1031DC User Manual 2 12 ni com This chapter describes basic maintenance procedures you perform on the PXI 1031 and PXI 1031DC chassis N Caution Disconnect the power cables prior to servicing the chassis DC Fuse Replacement PXI 1031DC Only The PXI 1031DC is protected against over current by a 30 A fuse on the rear of the chassis as shown in Figure 1 3 Rear View of the PXI 1031DC Chassis The fuse should only be replaced with a Wickmann 162 6385 530 Littlefuse 257 030 or equivalent To remove the fuse pull straight out from the chassis Service Interval Clean dust from the chassis exterior and interior as needed based on the operating environment Periodic cleaning increases reliability Preparation The information in this chapter is designed for use by qualified service personnel Read the Read Me First Safety and Electromagnetic Compatibility document included with your kit before attempting any procedures in this chapter UN Caution Many components within the chassis are susceptible to static discharge damage Service the chassis only in a static free environment Observe standard handling precautions for static sensitive devices while servicing the chassis Always wear a grounded w
Download Pdf Manuals
Related Search
Related Contents
Cryltane AC Primer VHA MCAD Connector for Pro/Engineer User Manual 西大寺教室 CAMIP7N - FuturaShop ASUS VB199T LED display InstallatIon InstructIons Function Formed Fl oil spout WK210 - Support manuale dell'utento Manual de Usuario Scribd Cómo usar Scribd Fusion Shell User Manual Copyright © All rights reserved.