1. 150A Peak w an error due to CF of 3 Working Voltage 600Vrms Common Mode Voltage 600Vrms Influence of Adjacent Conductor lt 15mA A at 50Hz Influence of DC on AC signal 2A Range DC Current lt 1A lt 3 150A Range DC Current lt 10A lt 10 Influence of Conductor Position in Jaw 0 5 of mV output 50 60Hz Influence of Frequency 2A Range 40Hz to 1kHz 10 of mV output 1kHz to 10kHz 10 of mV output 150A Range 40Hz to 1kHz 5 of mV output 1kHz to 10kHz 15 of mV output Influence of Temperature lt 200 ppm K or 0 2 of mV output per 10 K Influence of Humidity 10 90 RH lt 0 2 of mV output per 10 K 18 to 28 C MECHANICAL SPECIFICATIONS Operating Temperature 14 to 131 F 10 to 55 C Storage Temperature 40 to 158 F 40 to 70 C Operating Relative Humidity 10 to35 C 85 RH without roll off above 35 C Maximum Cable Diameter One 0 78 20mm bus bar 20 x 5 mm Case Protection IP 40 IEC 529 Drop Test Test per IEC 68 2 32 1 0 m drop on 38mm of Oak on concrete Shop for AEMC products online at www PowerMeterStore ca Mechanical Shock Test per IEC 68 2 27 Vibration Test per IEC 68 2 6 Dimensions 5 47 x 2 00 x 1 18 139 x 51 x 30mm Weight 180g 6 50z Polycarbonate Material Jaws Polycarbonate with 10 fiberglass charge Red UL 94 VO Case Polycarbonate 920A Gray Opening Operations Life gt 50 000 Outpu
2. AC Current Probe Model MN373 User Manual DESCRIPTION The MN373 Catalog 2116 28 is the latest in compact AC current probes Designed to meet the most stringent demands in industry and electrical contracting it also meets the latest safety and performance standards The probe has a measurement range up to 240Arms a range and resolution capable of displaying 10mV of output per amp of measured current a voltmeter accuracy of 0 75 or better to take full advantage of the accuracy of the probe and an input impedance of gt 1MQ WARNING The safety warnings are provided to ensure the safety of personnel and proper operation of the instrument Read the instruction completely Use caution on any circuit potentially high voltages and currents may be present and may pose a shock hazard Do not use the probe if damaged Always connect the current probe to the measuring device before it is connected around the conductor Do not use on non insulated conductor with a potential to ground greater than 600V CAT III pollution 2 Use extreme caution when clamping around bare conductors or bus bars Before each use inspect the probe look for cracks in housing or output cable insulation Do not use clamp in wet environment or in locations that hazardous gases exist Do not use the probe anywhere beyond the tactile barrier INTERNATIONAL ELECTRICAL SYMBOLS 0 This symbol signifies that the current probe is protected by double or reinforce
3. TS 2 56 65 mm 73 83 21 mm 18 5 mm an x Tactical pan Barrier keep hands below this barrier ww 61 y s 2 00 51 mm ELECTRICAL SPECIFICATIONS Nominal Range 2A 150A 150A Range Accuracy Measurement Range 2A 0 01 to 2 4A 0 1 to 1A lt 3 Reading 200V 150A 0 1 to 200A 1 to 20A lt 2 Reading 200V 20 to 80A lt 1 Reading Transformation Ratio Voltage output 80 to 150A lt 3 Reading Output Signal 2A 1000mV A 150 to 200A Not specified 150A 10mV A 150A Range Phase Shift 0 1 to 1A Not specified Accuracy and Phase Shift 1 to 20A lt 3 2A Range Accuracy 0 01 to 0 1A lt 5 Reading 2mV ee lt er 0 1to1A lt 3 Reading 1mV 80 to 150A lt 3 1 to 2A lt 1 Reading 150 to 200A lt 4 2 to 2 4A lt 1 Reading Reference conditions 18 C to 28 C 20 to 75 RH external magnetic field lt 40 A m 48 to 65Hz sine wave Phase Shift Not specified distortion factor less than 1 no DC component no external current carrying conductor test sample centered Shop for AEMC products online at www PowerMeterStore ca 1 877 766 5412 Overload 240A for 10 min ON 30 min OFF Frequency Range 40 to 10kHz Limit Operating Conditions 200A permanently to 1kHz Derating above 3kHz 200A x 1 0 333F F in kHz Crest Factor 2A 3 2A Peak w an error due to CF of 3 150A 3
4. d insulation Use only factory specified replacement parts when servicing the instrument M This symbol signifies CAUTION and requests that the user refer to the user manual before using the instrument This is a type A current sensor This symbol signifies that application around and removal from HAZARDOUS LIVE conductors is permitted DEFINITION OF MEASUREMENT CATEGORIES CATI For measurements on circuits not directly connected to the AC supply wall outlet such as protected secondaries signal level and limited energy circuits CAT Il For measurements performed on circuits directly connected to the electrical distribution system Examples are measurements on household appliances or portable tools CAT Ill For measurements performed in the building installation at the distribution level such as on hardwired equipment in fixed installation and circuit breakers CAT IV For measurements performed at the primary electrical supply lt 1000V such as on primary overcurrent protection devices ripple control units or meters RECEIVING YOUR SHIPMENT Upon receiving your shipment make sure that the contents are consistent with the packing list Notify your distributor of any missing items If the equipment appears to be damaged file a claim immediately with the carrier and notify your distributor at once giving a detailed description of any damage Shop for AEMC products online at www PowerMeterStore ca 1 877 166 541 2 AEMC INSTRUMEN
5. e range which corresponds to the measured current If the current magnitude is unknown start with the probe in the 10mV A position and if the current is lt 2 amps the probe can be switched to the 1000mV A position for the higher resolution Clamp the probe around the conductor With the probe in the 10mV A position take the reading on the meter and multiply it by 100 to obtain the measured current e g 160mV reading 160 x 100 16 000mA or 16A e For best accuracy avoid if possible the proximity of other conductors which may create noise Tips for Making Precise Measurements e When using a current probe with a meter it is important to select the range that provides the best resolution Failure to do this may result in measurement errors e Make sure that probe jaw mating surfaces are free of dust and contamination Contaminants cause air gaps between the jaws increasing the phase shift between primary and secondary It is very critical for power measurement MAINTENANCE Warning e For maintenance use only original factory replacement parts e To avoid electrical shock do not attempt to perform any servicing unless you are qualified to do so e To avoid electrical shock and or damage to the instrument do not get water or other foreign agents into the probe Cleaning To ensure optimum performance it is important to keep the probe jaw mating surfaces clean at all times Failure to do so may result in error in readings To clean t
6. he probe jaws use very fine sand paper fine 600 to avoid scratching the jaw then gently clean with a soft oiled cloth REPAIR AND CALIBRATION You must contact our Service Center for a Customer Service Authorization number CSA This will ensure that when your instrument arrives it will be tracked and processed promptly Please write the CSA on the outside of the shipping container If the instrument is returned for calibration we need to know if you want a standard calibration or a calibration traceable to N I S T includes calibration certificate plus recorded calibration data Chauvin Arnoux Inc d b a AEMC Instruments 15 Faraday Drive e Dover NH 03820 USA Tel 800 945 2362 Ext 360 603 749 6434 Ext 360 Fax 603 742 2346 or 603 749 6309 repair aemc com Or contact your authorized distributor Costs for repair standard calibration and calibration traceable to N I S T are available NOTE All customers must obtain a CSA before returning any instrument TECHNICAL AND SALES ASSISTANCE If you are experiencing any technical problems or require any assistance with the proper use or application of this instrument please call our technical hotline 800 343 1391 508 698 2115 Fax 508 698 2118 Chauvin Arnoux Inc d b a AEMC Instruments tanhaumnnartAanama nnam Shop for AEMC products online at www PowerMeterStore ca 1 877 766 5412 99 MAN 100161 v8 04 11
7. t Double reinforced insulated 5 ft 1 5m lead with safety 4mm banana plug SAFETY SPECIFICATIONS ce o us LISTED Electrical E192383 Double insulation or reinforced insulation between the primary or secondary and the outer case of the handle conforms to IEC 1010 2 32 Common Mode Voltage 600V Category III Pollution Degree 2 Dielectric Strength 5550V 50 60Hz between primary secondary and the outer case of the handle Electromagnetic Compatibility EN 50081 1 Class B EN 50082 2 Electrostatic discharge IEC 1000 4 2 Radiated field IEC 1000 4 3 Fast transients IEC 1000 4 4 Magnetic field at 50 60Hz IEC 1000 4 8 ORDERING INFORMATION AC Current Probe MN373 Cat 2116 28 Includes a user manual and a product warranty and registration card Accessories Banana plug adapter to non recessed plug ce eee Cat 1017 45 1 877 766 5412 OPERATION Please make sure that you have already read and fully understand the WARNING section on page 1 Making Measurements with the AC Current Probe Model MN373 Connect the black lead of the current probe to common and the red lead to the AC voltage input on your DMM or other voltage measuring instrument The AC current probe has an output of 10mV A and 1000mV A This means that with the probe in the 10mV A position for 200A AC in a conductor around which the probe is clamped 2V AC will come out of the probe leads to your DMM or instrument Select th
Download Pdf Manuals
Related Search
aemc_instruments_mn3..
Related Contents
Dale Tiffany TA70112 Instructions / Assembly ficha técnica - J. ROMA, Lda. Télécharger le dépliant, La pilule, mode d`emploi Manuale installatore- Installer guide Manuel installateur User Manual μRS1000/μRS1800記録形用 RS-422 CIRA X2 I/O Quick Start Guide PRECAUCIÓN Admission Module HP ProLiant SL270s Gen8 Server User Guide Copyright © All rights reserved.