RXT10 Engineering and commissioning - Quick guide
Contents
1. Master device limits exceeded xxx gt yyy data points Only 889 data points are allowed total 900 data points of which 11 reserved for NIDES RX OK Modify binding template Use fewer network variables Use fewer devices Create a second project 28 32 Building Technologies Building Automation DESIGO RXT10 2 Quick guide Dialog boxes and error handling CM110758en 30 09 2005 Message Cause Action Device xxx has more than yyy network variables bound to the master device Project validation failed You may have loaded the wrong database or are not properly connected to the network If you are absolutely sure that the right database is loaded click Yes Otherwise click No More than 25 network variables per binding template or several binding templates between device and master device The data in the master device does not match the data in the open project An old version of the project is open or the project was modified on another PC OK Modify binding template Yes No If you are sure you are working with the right project click YES to update the master device Clicking NO terminates the network connection One or more remote servers have been found More than one LNS based tool is connected to the network OK Check that only one LNS based tool is connected to the network The master device cannot be the source for a bi
2. 5 1 INTEGRAL automation level with NITEL 19 5 2 INTEGRAL automation level with NCRG 19 5 3 UNIGYR automation level with NIDES RX 20 5 4 VISONIK automation level with NIDES RX 21 6 Migration Utility siririna 22 7 Dialog boxes and error handling sss sees 23 7 1 Tool installation sese eee eee eee 23 7 2 COMMISSIONING ss sese eee eee eee eee ee 24 7 3 Service GrTOTS 27 7 4 Special engineering noes eee eee eee 28 4 32 Building Technologies DESIGO RXT10 2 Quick guide CM110758en Building Automation Contents 30 09 2005 1 About this document This condensed guide briefly describes the engineering and commissioning procedures for DESIGO RX projects It covers both the activities to be carried out with the RXT10 commissioning and service tool and the steps required for integration into the DESIGO building automation and control system Engineering The standard procedure for project engineering normally workflow involves the use of the System Design component of DESIGO TOOLSET In this case the RXT10 is used only for commissioning and service activities 5 32 Building Technologies DESIGO RXT10 2 Quick guide CM110758en Building Automation About this document 30 09 2005 Validity Content and target readership How the contents are structured Faulty product Incomplete documentation Support address 6 32 1 1 Before you start This document is valid for the RXT10
3. Integrate genies and DESIGO INSIGHT engineering super genies CA1Z9130 5 2 INTEGRAL automation level with NCRS Action Step Procedure Tool Generate NCRS 1 Read the NIOPEN ASC and INTEGRAL PLAN database from SAPIM ASC files into Folder M3 SAPIM ASC and INTEGRAL PLAN NIOPEN ASC 2 Create the NCRS database INTEGRAL PLAN and Infolist Folder M3 e g sta_ncrs dbs Load NCRS 3 Database gt Restore NCRS Access database sta_ncrs dbs CA1Z9125 Load Infolist into 4 Database gt NICO Infolist NCRS Access NIDES RX infolstl inf CA1Z9125 19 32 Building Technologies DESIGO RXT10 2 Quick guide CM110758en Building Automation Integration into automation system standard workflow 30 09 2005 Database import 5 Import sta_ncrs dbs DESIGO INSIGHT CA1Z9125 Graphics 6 Integrate genies and DESIGO INSIGHT engineering super genies CA1Z9130 5 3 UNIGYR automation level with NIDES RX Action Step Procedure Tool Create RXC 1 Import UNIGYR Design configuration NIOPEN ASC 2 Generate UNIGYR function blocks and set parameters 3 Update user manual Download to 4 Configuration including UNIGYR Tools RX master transmission of the CA2Z3299 NIDES Infolist CM2Z8021 Download to 5 Transmit Infolist Automatic if NIDES RX different from the last loaded version CA2Z3299 CM2Z8021 Database import 6 UNIGYR DB Import TagTool CA1Y9122 Graphics 7 Integrate genies and DESIGO INSIGHT engineering super ge
4. 2 Processing the To do list RXT10 identifies outstanding tasks automatically The Todo list appears as soon as you select Network gt Connect The check boxes marked with a cross indicate those items in the network which still need to be modified or installed Click Process to start the first step These steps correspond to the steps in the basic Commissioning procedure Building Technologies Building Automation DESIGO RXT10 2 Quick guide CM110758en Commissioning online 30 09 2005 3 3 Loading the project data Refer to Section 8 4 of the User s guide Action Step Procedure Menu Network Install the devices 1 Select the devices to be gt Install with the following installed options 3 Load Settings 4 Set Device Online 5 Update application Device gt Configure gt Application gt Settings Note Both the installation of the master device and the loading of project data can be automated by use of the Connect Wizard 3 4 Disconnecting from the network Refer to Section 8 10 of the User s guide Action Step Procedure Menu 1 Disconnect from network Network Disconnect 2 Select and print the required Project reports gt Print Report 13 32 Building Technologies DESIGO RXT10 2 Quick guide CM110758en Building Automation Commissioning online 30 09 2005 3 5 Commissioning a single device Refer to Section 8 5 of the
5. Project gt Set up project 1 Create a new project New Enter the project 2 Enter project name engineer Properties gt data and comments Overview tab 3 Enter the project version General tab 4 Select the relevant options Network tab 5 Master device network Integration tab interface Notes e One project must be created for each PXR or NIDES RX e f you are using the same RXC devices in succession in different projects for test purposes for example a different domain must be selected for each project 2 1 Configuring the devices Refer to Section 6 of the User s guide Action Step Procedure Menu Device gt Register first device 1 Add a new device Add Configure 2 Location description Summary tab first device 3 Select application Application tab d Select device type Device Type tab 5 Set parameters Settings tab 6 Save configuration OK 7 Select binding to master device Register other 1 Copy device Copy identical devices Paste device s Paste or Paste Special 7 32 Building Technologies Building Automation DESIGO RXT10 2 Quick guide Creating a new project offline CM110758en 30 09 2005 Action Step Procedure Menu Device gt 3 Modify location and description Configure and settings if required gt Overview or Configure gt List view 4 Save configuration OK Register other As Step 1 dissimilar devices Notes on third e Third party devices from the applicati
6. User s guide Action Step Procedure Menu Install devices 1 Connect the PC to the RXC device 2 Connect to network Network gt Connect 3 Select device from the list view View gt List View Define options 4 __ Assign address Device 5 Load settings gt Install 6 Set device online 7 Disconnect from network Network gt Disconnect Third party For a detailed description refer to Section 8 6 of the User s devices with guide LNS plug in 14 32 Building Technologies DESIGO RXT10 2 Quick guide CM110758en Building Automation Commissioning online 30 09 2005 4 Service activities online Refer to Section 9 of the User s guide 4 1 Extending or modifying a project Action Step Procedure Menu Add device s 1 Disconnect the RXT10 from the Network network gt Disconnect 2 Add device s Device gt Add 3 Connect to network Network gt Connect 4 Address the new devices Network gt Assign devices 5 Install the new devices Network gt Install gt Select Changed Devices Replace device 6 Connect to network Network gt Connect 7 Replace device Device gt Replace 15 32 Building Technologies DESIGO RXT10 2 Quick guide CM110758en Building Automation Service activities online 30 09 2005 Caution 4 2 Resetting the project Reset Project Refer to Section 5 10 of the User s guide In the event of a proble
7. project database OK Check that the correct device is being installed Cannot communicate with Master Device Check the cable power supply and battery MD busy no response cable not plugged in correctly Wrong project Bus problems bus overload termination resistance bus connector with loose contact etc Abort Retry Ignore Check for all the suggested causes No project information found in the master device The master device is not installed or there is a communication roblem Power failure with faulty battery Abort Retry Ignore Check the power supply and the battery Re install the master device 25 32 Building Technologies Building Automation DESIGO RXT10 2 Quick guide Dialog boxes and error handling CM110758en 30 09 2005 Message xxx devices are integrated into this project but you can only integrate yyy devices with the selected master device Cause The new master device you have selected PXR cannot accommodate the number of devices already set up change from PXR12 to PXR11 Action OK Integrate fewer devices or select PXR12 as the master device Could not save project The project is write OK under C xx protected because it was Remove the copied from a CD write protection from the project file Could not open LNS LNS will not enable the OK network and or system file db Save project Invalid parameter
8. project has been updated from a previous version If you save the project now you may not be able to open it with the OK To keep the old project save the new project under a new name 27 32 Building Technologies Building Automation DESIGO RXT10 2 Quick guide Dialog boxes and error handling CM110758en 30 09 2005 Message Cause Action old version of the tool Do you want to append data to xxx Network test gt Backup If you click Cancel you will be asked for a new file name Yes No Cancel If you choose not to append the new data then the old data in the file will be overwritten 7 4 Special engineering notes Message Cause Action A template named xxx Warning Existing Yes No already exists If you overwrite this template the changes you made will apply to ALL bindings made with this template Do you want to overwrite it bindings will also be changed Rename the binding if there is any doubt as to whether or not this binding is already being used No space for xxx more device s Paste special More than 150 devices have been created OK Create fewer devices or create a second project Network interface xxx not found Cannot connect Do you want to continue preparing the database A network interface previously installed on this computer is no longer present OK Cancel Select or install a new network interface
9. the User s guide The Commissioning Support option is an efficient tool for commissioning and maintenance of DESIGO RXC systems The following processes can be carried out for several RXC devices at once e Monitor process values e Override outputs e Modify settings Action Step Procedure Menu Connect to network 1 Connect the PC to the LON bus 2 Connect to network Network gt Connect 3 Display commissioning support Tools gt Commissioning support 4 Select devices 5 View process values Select the View check box 6 Override outputs select the Override check box 7 Change settings click Settings 8 Disconnect from network Network gt Disconnect Note Remember to reset the devices to Auto before closing the Commissioning Support dialog box 18 32 Building Technologies DESIGO RXT10 2 Quick guide Building Automation Service activities online CM110758en 30 09 2005 For DESIGO PX 5 Integration into automation system standard workflow Refer to the online help in DESIGO TOOLSET automation level with PXR 5 1 INTEGRAL automation level with NITEL Action Step Procedure Tool Download Infolist 1 Download the Infolist and DESIGO INSIGHT and text into Split asc file CA1Z9125 NIDES RX Import database 2 _ DB Import import the DESIGO INSIGHT Split asc file CA12Z9125 Graphics 3
10. SIEMENS DESIGO RXT10 2 Engineering and commissioning Quick guide ENT Building Technologies 30 09 2005 Building Automation 2 32 Building Technologies CM110758en Building Automation 30 09 2005 Contents 1 About this document sss sese eee eee 5 1 1 Before yOu start asreb rabad eTo chy adaz D 2 Creating a new project Offline sese eee eee ee 7 2 1 Configuring the devices sese ee eee eee 7 2 2 Creating bindings sss eee eee 9 2 2 Creating modifying topologies sss sees eee eee 9 2 4 Creating groups sse eee eee eee eree 10 2 5 Printing the project data saving and closing the sle e Ney eS eA ee 10 2 6 Copying oms see eee ee eee eee eee 11 3 Commissioning online see eee eee eee ee ee 12 3 1 Connecting the PC to the network 00 12 3 2 Processing the To do list seene 12 3 3 Loading the project data sss seene 13 3 4 Disconnecting from the network 13 3 5 Commissioning a single device sese eee 14 4 Service activities online eee ee eee 15 4 1 Extending or modifying a project 15 4 2 Resetting the project Reset Project 16 4 3 Replacing the master deViCe ceceeeeeee 17 4 4 Deleting a deviGe seves sssee esse essere eee 18 4 5 Monitoring and diagnostics sss sees eee eee eee 18 5 Integration into automation system standard WOFKTIOW T 19 3 32 Building Technologies DESIGO RXT10 2 Kurzanleitung CM110758en Building Automation Contents 30 09 2005
11. commissioning and service tool from Version 2 3 The RXT commissioning and service tool is used to engineer install and maintain LON networks incorporating DESIGO RXC and LONMaRk compliant third party devices This document contains basic information and operating instructions and is written for engineering commissioning and service specialists in the field of HVAC All the tables have the same structure The Action and Procedure columns are followed by a Menu column containing the command sequence In addition to cross references within this document chapter x x reference is also made to the relevant section of the User s guide CA110412en where the procedures are described in more detail Should you experience any faults or shortcomings in the product or the product literature please contact the Common Support department of Siemens Building Technologies Building Automation This will help us further improve the product Siemens Switzerland Ltd Building Technologies Group Common Support Entry 5500 Gubelstrasse 22 6301 Zug Switzerland Tel 41 41 724 5500 Fax 41 41 724 5501 E mail fieldsupport zug ch sbt siemens com Building Technologies Building Automation DESIGO RXT10 2 Quick guide About this document CM110758en 30 09 2005 2 Creating a new project offline Refer to Section 5 of the User s guide Action Step Procedure Menu
12. ct 10 Save the project Project gt Save Connect to network 11 Connect to network Network gt gt Connect Install master 12 Install master device Device device gt Install Read network 13 Read network status Network gt Get status status Disconnect from 14 Disconnect from network Network network gt Disconnect Save the project Save the project Project gt Save 4 3 Replacing the master device Refer to Section 6 7 of the User s guide Action Step Procedure Menu Disconnect from 1 Disconnect from network Network network gt Disconnect Delete master 2 Delete master device from Tools gt Clear MD device database image Reset new 3 Remove battery for approx 10 master device seconds NIDES RX only Replace device 4 Replace master device Connect to network 5 Connect to network Network gt Connect Install master 6 Install master device Device device gt Install i Important For technical reasons the RXC devices are reset twice upon connection to the network This can affect lighting and blinds depending on the controller settings 17 32 CM110758en 30 09 2005 Building Technologies Building Automation DESIGO RXT10 2 Quick guide Service activities online 4 4 Deleting a device Notes This process deletes existing bindings The device must also be deleted at the automation level and the management level 4 5 Monitoring and diagnostics Refer to Section 9 1 of
13. en old v1 x project in the DESIGO RXT10 2 V2 3 engineering tool 2 _ Use the report function to save or print full device details 3 Save the project and close it do not make any other changes at this point d Create a new empty project using the v2 x library in the DESIGO RXT10 2 engineering tool This should just include the desired master device and no other controllers or devices 5 Save this new project using a different name and location to the original 6 Start the Migration Utility from the tools menu and select the project to be migrated 7 Make a note of any errors or changes indicated by the utility 8 Save the project 9 Check all configuration details and bindings with the report generated previously to ensure all details are correct 10 Install the NIDES RX interface 11 Install all devices 12 Save the project 22 32 Building Technologies Building Automation DESIGO RXT10 2 Quick guide CM110758en Migration Utility 30 09 2005 7 Dialog boxes and error handling Note For online help in the RXT10 press lt F1 gt in the error view 7 1 Tool installation Message Cause Action The system is not The path entered under OK installed correctly Please System properties Complete the add the directory LonWorks Bin to your Path environment variable and restart the computer gt Environment is not correct System propert
14. ies gt Environment path C Lonworks Bin The files NMSndMsg ocx and LNS_FTP ocx are not in the registry Register NMSndMsg 0cx and LNS_FTP ocx with regsvr32 DOS command regsvr32 NMSndMsg ocx regsvr32 LNS_FTP ocx LNS not installed Check whether the LNS software is installed under Control panel gt Add Remove programs 23 32 Building Technologies Building Automation DESIGO RXT10 2 Quick guide Dialog boxes and error handling CM110758en 30 09 2005 7 2 Commissioning Message Cause Action RXT cannot connect the network interface is being used by xxx The LON network interface is being used by another user Please wait until the other application has finished using the network interface No object selected For networks with several segments you need to specify the segment to which the tool is connected OK Select segment If no segment is selected the connection will be terminated Could not open project file Make sure the file is not being used by another application The project file has been opened by another tool e g MS Access OK Close the program which opened the project file There is already a binding to this project but the LNS database is missing Do you want to create a new database The project has been reset Confirm with YES Instead of creating a backup of the project only the project file was copied N
15. m it is possible to reset the devices in a project i e restore their default values Resetting a project has significant consequences for any devices which have already been addressed These devices must be reinstalled to maintain the consistency of the network Projects should therefore only be reset in extreme circumstances Note Make sure you create a backup first see the User s guide Section 5 8 Action Step Procedure Menu Save the project 1 Create a backup Project gt Backup Disconnect from 2 Disconnect from network Network network gt Disconnect Reset project 3 Reset the project deletes LNS Project Important database gt Reset 4 If the assignment is correct answer No to the prompt Delete Neuron ID De energize PXR B Use reset button do NOT remove battery De energize Remove battery for min 10 s NIDES RX Connect to network 6 Connect to network Network gt 7 Answer No to the prompt aaile Install MD to save time do not install MD until later Reinstall devices 8 Re install devices without Network Application download gt Install Disconnect from 9 Disconnect from network Network network gt Disconnect 16 32 Building Technologies Building Automation CM110758en 30 09 2005 DESIGO RXT10 2 Quick guide Service activities online Action Step Procedure Menu Save the proje
16. nding Tree view Master device is marked as source OK Draw binding from RXC device to master device 29 32 Building Technologies Building Automation DESIGO RXT10 2 Quick guide Dialog boxes and error handling CM110758en 30 09 2005 Message Cause Action The locations are not unique Deleting integration files Locations do not have unique definitions or syntax is faulty Note Unique location strings are only required with VISONIK The check for unique strings can be disabled in the Options menu OK Enter unique locations Some devices routers have been marked in preparation for a move but have not been moved Do you still want to disconnect from the network 30 32 In the engineering process devices were moved to other segments or segments were linked to other routers Yes No These changes must also be carried out in the network If you disconnect from the network now the changes prepared will not be carried out Building Technologies Building Automation DESIGO RXT10 2 Quick guide Dialog boxes and error handling CM110758en 30 09 2005 31 32 Building Technologies DESIGO RXT10 2 Quick guide CM110758en Building Automation Dialog boxes and error handling 30 09 2005 Siemens Schweiz AG Building Technologies Gubelstrasse 22 CH 6301 Zug SWITZERLAND Tel 41 41 724 24 24 Fax 41 41 724 35 22 www sbt siemens com 2005 Siemens Sch
17. nies CA1Z9130 Note Do not create a binding between NIDES RX and RX master 20 32 until the commissioning on the LON side is complete Building Technologies Building Automation DESIGO RXT10 2 Quick guide Integration into automation system standard workflow CM110758en 30 09 2005 5 4 VISONIK automation level with NIDES RX Action Step Procedure Tool Create RXC project The following files are created RXT10 1 Project data CA110412 2 NIOPEN ASC 3 RxNiBps COL containing TSK111 TX project image for BPS TSK110 TX Infolist for NIDES RX Define groups 4 Adapt GroupConfig COL VISOTOOL manually to the project CA2Z8339 General VISONIK 5 Download RX coupling CFE VISOTOOL Editor engineering application to the BPS CA2Z8339 6 Carry out general VISONIK engineering Database import 7 DB Import Import global and DESIGO INSIGHT project specific data CA12Z9125 Graphics 8 Integrate genies and DESIGO INSIGHT engineering super genies CA1Z9130 Note Do not create a binding between NIDES RX and VISONIK BPS until commissioning on the LON side is complete 21 32 Building Technologies DESIGO RXT10 2 Quick guide CM110758en Building Automation Integration into automation system standard workflow 30 09 2005 Action 6 Migration Utility Refer to Section 10 of the User s guide Step Procedure Menu Migration Steps 1 Op
18. o Obtain a backup copy and use this project New gt Connect Master device has a bad magic key Are you sure you want to continue The checksum in the MD does not match the one in the project The MD is corrupt or there is another user working with the project Yes No Ensure that this is the current project Update MD or Clear MD image Invalid Private data file Are you sure you want to continue 24 32 The data in the MD does not match the project Yes No Re install MD Building Technologies Building Automation DESIGO RXT10 2 Quick guide Dialog boxes and error handling CM110758en 30 09 2005 Message Timestamp mismatch Are you sure you want to continue Update master device with selected project Cause The project was not saved after the last connection Old backup The MD has since been changed Action Yes loading current project into MD NO Establishing connection without updating the MD Cancel Connection terminated Validation found that MD data is inconsistent with device with module No xxx Do you want to try to update the MD with the available data If the response to the Incorrect time stamp error was Yes the modules being updated are displayed Yes No Yes to update MD The device with NeuronlD xxx is already in this project Please select a new device An attempt is being made to install a device which already exists in the
19. ocedure Menu Register all the 1 Register the first device Device gt Add devices in a room see chapter 2 1 2 Register remaining devices as Step 1 Create bindings 3 Create bindings see View gt Tree View between registered chapter 2 2 devices 4 Highlight all the devices for this Device gt Copy room and copy including bindings Copy room 5 Paste the copy once Device gt Paste or or more than once gt Paste Special Create bindings 6 Create bindings between View gt Tree View between rooms rooms see chapter 2 2 11 32 Building Technologies Building Automation DESIGO RXT10 2 Quick guide Creating a new project offline CM110758en 30 09 2005 3 Commissioning online 3 1 Connecting the PC to the network Refer to Section 8 of the User s guide Action Step Procedure Menu Connect the PC to 1 Check that the correct LON Tools gt Options the LON bus interface type has been specified Activate the To do list 2 Select the Show Todo dialog Tools gt Options box on connection check box 3 If there are routers on the network specify the segment to which the RXT10 is connected 4 Connect to network Network gt Connect i Important 12 32 If you make an incorrect choice here it will not be possible to install the network At a later stage during installation errors will occur indicating an incorrect channel 3
20. ons library party devices same as RXC devices application 3 party devices e Third party devices with LNS plug ins application type LNS plug in support Devices can only be configured online 8 32 Building Technologies DESIGO RXT10 2 Quick guide CM110758en Building Automation Creating a new project offline 30 09 2005 Action 2 2 Creating bindings Refer to the User s guide Sections 6 1 6 and 7 Step Procedure Menu View gt Create bindings between devices 1 Switch to the tree view 2 Click source device or object and drag mouse pointer to target device or object Binding template It may be necessary to create a binding template if no suitable binding template exists already Menu Tools gt Binding Template Editor Tree view 2 3 Creating modifying topologies Refer to the User s guide Section 6 10 to 6 12 Action Step Procedure Menu Tools gt Define topology 1 Open the relevant topology Device topology offline dialog box or Router topology 2 Adding segments Device topology gt Create or Delete segment Device topology gt Remove 3 Highlight the segment select Device topology gt device s and highlight new Move target segment Modify topology Highlight the device Device topology gt online placeholder Move Create router 1 Highlight router and highlight Router topology offline two new segmen
21. ts Topology 9 32 Building Technologies Building Automation DESIGO RXT10 2 Quick guide Creating a new project offline CM110758en 30 09 2005 Action Step Procedure Menu Tools gt Reconfigure router or Highlight the required Router topology segments Topology gt Change 2 Complete the reconfiguration Router process Topology gt Assign 2 4 Creating groups Refer to Section 6 9 of the User s guide Note Useful for commissioning the plant not to be confused with the Groups in the PXR Action Step Procedure Menu Tools gt Group the devices 1 Display Group Editor Group Editor 2 5 Printing the project data saving and closing the project Refer to the User s guide Section 5 7 to 5 9 Action Step Procedure Menu Project gt Print the 1 Select and print the required Print Report project data report type Save the project 2 Save the project Files willbe Save or generated for system Save as integration Close the project 3 Close the project Close 10 32 If you are ready to commission the RXC devices you can now go to the Commissioning section see chapter 3 without closing the project Building Technologies Building Automation DESIGO RXT10 2 Quick guide Creating a new project offline CM110758en 30 09 2005 2 6 Copying rooms Refer to Section 6 4 of the User s guide Action Step Pr
22. values subsystem NS 44 26 32 Important Reboot the RXT tool LNS will enable the data after the next restart Building Technologies Building Automation DESIGO RXT10 2 Quick guide Dialog boxes and error handling CM110758en 30 09 2005 7 3 Service errors Message Cause Action Replace device Could not initialize the OK Error preparing to replace device new device to be replaced Initialize the device ina test project to check basic operation Check the cable Error replacing device Could not download settings into new device OK Repeat the process If this does not help Test the device by commissioning it ina separate project function test The new device could not be registered in the master device OK Check the master device and then repeat the process No network interface selected Are you sure you want to continue without a network connection No network interface selected in the Tools gt Options menu Yes No This may be intentional to reduce waiting time on the site If not select the network interface under Tools gt Options Do you want to read the device information from the network When re installing the MD the device data needed by the master device can be read from the network or from the database Yes No Read from network The database will be updated again Reading from the database is faster The
23. weiz AG Subject to alteration Building Technologies DESIGO RXT10 2 Quick guide Building Automation CM110758en 30 09 2005