Home
iSeries User Manual
Contents
1. 4 1 2 2 Calibration Curve INIt gt INPt gt Rtd gt A CRV ZIG Navigate to the desired setting Settings include the following e 385 1 European and most common standard at the conventional resistance of 100 Q factory default e 385 5 European curve for 500 Q e 385 t European curve for 1000 Q e 392 Old US standard rarely used at 100 Q only e 3916 Japanese standard at 100 O only Omega Engineering www omega com PLATINUM ym Series User s Guide Reference Section Initialization Mode INIt Select the indicated option 4 1 3 Thermistor Input Type Configuration INIt gt INPt gt tHRM Select Thermistor tHRM as the input type This sets up the unit for thermistor based temperature measurement and then the specific thermistor type can be specified If no thermistor type is specified the last selected type is used EI d X Navigate to the correct setting Settings include the following e 2 25k 2 2500 thermistor factory default e bk 5 0000thermistor e 10k 10 0000 thermistor Select the indicated option 4 1 4 Process Input Type Configuration INIt INPt PRoC Select Process PRoC as the input type Then select the process input range and scale it If you stop after selecting the PRoC input type the last selected input range and scaling is used 12 Navigate to the voltage or current range of the process input Any signal input outside of the specified hardware input range will result in an
2. 4 2 5 Normal Color INIt RdG NCLR Select the Normal Color NCLR parameter This controls the default display color which can then be overridden by Alarms EI Jd Navigate to the desired setting Settings include the following e GRN Green factory default e REd Red e AMbR Amber Select the indicated option 4 2 6 Brightness INIt RdG bRGt Select the Brightness bRGt parameter EI d Navigate to the desired setting Settings include the following e HIGH High display brightness factory default e MEd Medium display brightness e Low Low display brightness Select the indicated option 4 3 Excitation Voltage INIt ECtN Select the Excitation Voltage ECtN parameter EI g Navigate to the correct setting Settings include the following e 5V bVoltexcitation voltage factory default e 10V 10 Volt excitation voltage e 12V 12 Volt excitation voltage e 24V 24 Volt excitation voltage e OV Excitation turned off Select the indicated option Omega Engineering www omega com PLATINUM ym Series User s Guide Reference Section Initialization Mode INIt 4 4 Communication INIt gt COMM Select the Communication Type COMM to configure Only installed communications options show up for configuration USB is always present If more than one communications option is installed any or all of them can be configured for simultaneous operation 12 Navigate to the correct option Options include the f
3. CONDITIONS Equipment sold by NEWPORT is not intended to be used nor shall it be used 1 as a Basic Component under 10 CFR 21 NRC used in or with any nuclear installation or activity or 2 in medical applications or used on humans Should any Product s be used in or with any nuclear installation or activity medical application or used on humans or misused in any Way NEWPORT assumes no responsibility as set forth in our basic WARRANTY DISCLAIMER language and additionally purchaser will indemnify NEWPORT and hold NEWPORT harmless from any liability or damage whatsoever arising out of the use of the Product s in such a manner Return Reguests Inquiries Direct all warranty and repair requests inquiries to the NEWPORT Customer Service Department BEFORE RETURNING ANY PRODUCT S TO NEWPORT PURCHASER MUST OBTAIN AN AUTHORIZED RETURN AR NUMBER FROM NEWPORT S CUSTOMER SERVICE DEPARTMENT IN ORDER TO AVOID PROCESSING DELAYS The assigned AR number should then be marked on the outside of the return package and on any correspondence The purchaser is responsible for shipping charges freight insurance and proper packaging to prevent breakage in transit FOR WARRANTY RETURNS please have the FOR NON WARRANTY REPAIRS consult NEWPORT following information available BEFORE for current repair charges Have the following contacting NEWPORT information available BEFORE contacting NEWPORT 1 P O number under which the product was 1 P
4. Display Peak Reading 0PER gt PEAK Select Display Peak Reading PEAk to change the process value displayed to the highest reading since PEAk was last cleared Clear the PEAk reading buffer Return to RUN Mode or to displaying RUN depending on the Operating Safety parameter setting 4 5 2 Operating Mode Confirmation INIt SFty oPER Note Using the other buttons to navigate away from PEAk does not clear the PEAk reading buffer Standby Mode oPER gt Stby Select Standby Mode Stby to disable outputs and Alarm conditions Stby is displayed until navigating elsewhere Navigate to any desired initialization or programming settings to change them or to adjust the process Return to RUN Mode or to displaying RUN depending on the Operating Safety parameter setting 4 5 2 Operating Mode Confirmation INIt SFty oPER Omega Engineering www omega com Reference Section Operating Mode oPER PLATINUMrm Series User s Guide Specifications 7 Specifications 7 1 Inputs Input Types Current Input Voltage Input Thermocouple Input ITS 90 RTD Input ITS 90 Configuration Polarity Accuracy Resolution Input Impedances Temperature Stability A D Conversion Reading Rate Digital Filter CMRR Excitation Setpoint Adjustment Warm Up to Rated Accuracy Tid Action Autotune Adaptive Tune Control Modes Control Cycle Time Ramp and Soak Thermocouple RTD Thermistor Analog Voltage Ana
5. oFF Output does nothing Pld PID Control Mode oN oF Off when gt SP1 on when lt SP1 dRCt Off when lt SP1 on when gt SP1 dEAd Deadband value default 5 S PNt SP1 Either Setpoint can be used of on off default is SP1 SP2 Specifying SP2 allows two outputs to be set for heat cool ALM 1 Output is an Alarm using ALM 1 configuration ALM 2 Output is an Alarm using ALM 2 configuration RtRN Rd1 A Process value for oUt1 oUt1 Output value for Rd1 Rd2 A Process value for oUt2 OUt2 Output value for Rd2 RE oN Activate during Ramp events Omega Engineering PLATINUMrm Series User s Guide Level Level Level Level Level 2 3 4 5 6 SE ON CV CES Mies RNGE 0 5 0 20 4 20 0 24 oUt2 oUt3 dRCt A to LLL AUto StRt GAIN A o LO _ HI _ AdPt dSbL RM SP oN Complete Menu Structure Notes Activate during Soak events PWM pulse width in seconds Analog Output Range 0 10 Volts 0 5 Volts 0 20 mA 4 20 mA 0 24 mA oUt2 is replaced by output type oUt3 is replaced by output type 1 8 DIN can have up to 6 Increase to SP1 i e heating Decrease to SP1 i e cooling Set timeout time for autotune Initiates autotune after StRt confirmation Manual Proportional Band setting Manual Integral Factor setting Manual Derivative Factor setting Low clamping limit for Pulse Analog Outputs High clamping limit for Pulse Analog Outputs Enable fuzzy logic adaptive tuning Disable fuzzy logic a
6. 57 600 Baud e 115 2 115 200 Baud Select the indicated option 4 4 3 3 Parity INIt gt COMM gt SER gt C PAR gt PRty Select the Parity PRty parameter Navigate to the desired setting Settings include the following e odd Odd parity used to verify communications factory default e EVEN Even parity used to verify communications e NoNE Parity is not used to verify communications Select the indicated option 4 4 3 4 Data Bits INIt gt COMM gt SER gt C PAR gt dAtA Select the number of Data Bits dAtA Omega Engineering www omega com PLATINUM ym Series User s Guide Reference Section Initialization Mode INIt 4 5 EIL 12 Navigate to the desired setting Settings include the following e 8blt 8 bits used per data character factory default e 7blt 7 bits used per data character Select the indicated option 4 4 3 5 Stop Bits INIt COMM SER C PAR StoP Select the number of Stop Bits StoP EIEg Navigate to the desired setting Settings include the following e l1bit 1 stop bit factory default 2bit 2 stop bits provides a force 1 parity bit Select the indicated option Safety Features INIt SFty Select Safety Features SFty Navigate to the desired parameter Parameters include the following e PwoN Requires confirmation before running automatically at startup e OPER User must select RUN when exiting from the Stby PAUS or StoP Modes e SP LM Setpoint limits c
7. F 0 5 C 0 9 F 1 0 C 1 8 F 0 5 C 0 9 F 1 0 C 1 8 F 0 5 C 0 9 F 0 4 C O 7 F 1 0 C 1 8 F 0 4 C 0 7 F 0 3 C O 5 F 0 3 C O 5 F 0 3 C O 5 F 0 2 C 0 35 F 0 2 C 0 35 F 0 2 C 0 35 F Omega Engineering www omega com PLATINUM Series User s Guide Approvals Information 8 Approvals Information C This product conforms to the EMC directive 89 336 EEC amended by 93 68 EEC and with the European Low Voltage Directive 72 23 EEC Electrical Safety EN61010 1 2010 Safety requirements for electrical equipment for measurement control and laboratory Double Insulation Pollution Degree 2 Dielectric withstand Test per 1 min e Power to Input Output 2300 Vac 3250 Vdc e Power to Input Output 1500 Vac 2120 Vdc e Power to Relays SSR Output 2300 Vac 3250 Vdc e Ethernet to Inputs 1500 Vac 2120 Vdc e Isolated RS232 to Inputs 500 Vac 720 Vdc e Isolated Analog to Inputs 500 Vac 720 Vdc e Analog Pulse to Inputs No Isolation Measurement Category Category includes measurements performed on circuits not directly connected to the Mains Supply power Maximum Line to Neutral working voltage is 50Vac dc This unit should not be used in Measurement Categories Il Ill and IV Transients Overvoltage Surge 1 2 50uS pulse e Input Power 2500 V e Input Power 1500 V e Ethernet 1500 V e Input Output Signals 500 V EMC EN61326 1997 and A1 1998 A2 2001 Immunity and Emi
8. gt ALM 1 ALM 2 gt dE OF seeeeeeeernnnnnnennnenn nnns 41 5 4 Output Channel 1 3 Configuration PROG gt oUt 1 oUt 3 ceeseccecceeesecceeeeeeseceeeeaeeeeeess 42 5 4 1 Output Channel Mode PROG gt oUt1 oUt3 gt ModE ss 42 5 4 2 Output Cycle Pulse Width PROG gt OUt1 OUt3 gt CyCL Rs 45 5 4 3 Analog Output Range PROG gt OUt1 OUt3 gt RNGE nnne 45 5 5 PID Configuration PROG gt PIC S cssccccsssssesccssecssecccseeensecssseeesecesseeeeessssseessesessecuesesesseenees 45 5 91 Action Response PROG gt Pid gt ACEN sisaveiacdscsnseenvonsensdsarannacansinwsdooanssannouaeescaebannsnansenacdeonws 46 5 5 2 Autotune Timeout PROG gt Pld gt A to eeeeessseeeenenn emen nnne nnne nnns 46 5 5 3 Autotune PROG gt Pld gt AUtO ccc sccsssssersccrcauserscctcaussrsesteauserseateauserseateaussrsesteausersenteaues 46 5 5 4 PID Gain Settings PROG gt Pld gt GAIN nnne 47 5 5 5 Low Output Clamping Limit PROG gt PId gt LO eeeseecccceeeseeceeeeeeeceeeteeeeeeeeeeeneneeess 47 5 5 6 High Output Clamping Limit PROG gt PId gt HI eee eeeesssseeceeceeceeeeeseeeceeeeeseaaaeeeeeeeees 47 5 5 7 Adaptive Tuning PROG gt Pld gt ACPt sise 48 5 6 Remote Setpoint Configuration PROG gt RM SP cccccccsssssecccseesssecceeseeseecceseeeeeceseeeeeeeceeeeeeeees 48 5 6 1 Cascade Control using Remote Setpoint sisi 49 5 7 Multi Ramp Soak Mode Parameters PROG gt
9. EI d Navigate to the desired setting Settings include the following e OFF Alarm is off factory default e AboV Alarm is triggered when the process value exceeds ALR H Absolute Mode or the specified Setpoint plus ALR H Deviation Mode e bELo Alarm is triggered when the process value is less than ALR L Absolute Mode or the specified Setpoint minus ALR L Deviation Mode e Hi Lo Alarm is triggered when the process value is outside the ALR L ALR H range Absolute Mode or the range defined by the band around the specified Setpoint as determined by ALR L and ALR H Deviation Mode e bANd Alarm is triggered when the process value is within the ALR L ALR H range Absolute Mode or within the band around the specified Setpoint as determined by ALR L and ALR H Deviation Mode Note Table 5 1 compares the Alarm range options and Figure 5 1 represents the Alarm range options graphically Select the indicated setting Omega Engineering www omega com PLATINUMru Series User s Guide Reference Section Programming Mode PRoG Setting Absolute AbSo Deviation d SP1 Deviation d SP2 AboV gt ALR H gt SP1 ALR H gt SP2 ALR H bELo lt ALR L SP1 ALR L SP2 ALR L HI Lo lt ALR L or gt ALR H lt SP1 ALR L or gt SP1 ALR H lt SP2 ALR L or gt SP2 ALR H bANd gt ALR L and lt ALR H gt SP1 ALR L and lt SP1 ALR H gt SP2 ALR L and lt SP2 ALR H Table 5 1 Alarm Range Option Comparis
10. Every unit comes standard with USB communications for firmware updates configuration management and data transfer Optional Ethernet and RS 232 RS 485 Serial communications are also available The Analog Output is fully scalable and may be configured as a proportional controller or retransmission to follow your display The universal power supply accepts 90 240 Vac The low voltage power option accepts 24 Vac or 12 36 Vdc Additional features usually found only on more expensive controllers make these the most powerful products in their class Some additional standard features are remote Setpoint for cascaded control setups High high Low low Alarm functionality external latch reset external Ramp and Soak program initiation combination Heat Cool Control Mode configuration save and transfer and configuration password protection Omega Engineering www omega com PLATINUM m Series User s Guide Introduction PB 1 2 Using This Manual This initial section of the manual will cover the back panel connections and wiring instructions A quick overview of how to navigate the PLATINUM Series menu structure follows in Section 2 This is followed in Section 3 by the complete PLATINUM yy Series menu tree Remember not all commands and parameters in that menu tree will show up on your unit as those that are not available with your configuration are automatically hidden Repetitive menu structures are highlighted in gray and only shown once but are used
11. IN 2 Input signal corresponding to RD 2 In Manual Mode IN 1 and IN 2 are entered manually for scaling in Live Mode IN 1 and IN 2 activate a read of the input signal for scaling Select the scaling parameter to change BI For manual inputs set the selected scaling parameter to the desired value Confirm the value for the selected scaling parameter in Manual Mode MANL or read and accept the input signal for either IN 1 or IN 2 in Live Mode LIVE 4 2 Display Reading Formats INIt gt RdG Select Reading Formats RdG to configure the front panel display EI d Navigate to the desired setting Settings include the following e dEC P Decimal point format entry point e FC Temperature units e FLtR Filter readings displayed per second e ANN 1 Annunciator 1 setting e ANN 2 Annunciator 2 setting e NCLR Normal color default display color e bRGt Display brightness Select the indicated setting 4 2 1 Decimal Point Format INIt RdG dEC P Select Decimal Point dEC P and then select the desired decimal point format Only the FFF F and FFFF formats work for temperature inputs but all four can be used with process inputs While this parameter sets the default format the numeric display will autorange automatically shift the decimal point if necessary 12 Navigate to the desired setting Settings include the following e FFF F One decimal place factory default e FFFF Zero decimal places e FF FF Two d
12. M RMP nn 50 5 7 1 Multi Ramp Soak Mode Control PRoG gt M RMP gt R CtL 50 5 7 2 Select Program PROG gt M RMP gt S PRG cccccccccssssecceeeeeseececeeeeeseceseeeeseeeeeseeeseeeeeeeenes 51 5 7 3 Multi Ramp Soak Tracking PROG gt M RMP gt M tRK eeeeeeeeeeeennnn nnne 51 5 7 4 Time Format PROG gt M RMP gt tIM F sssccccccssssecccseeessecceeeeeeeccseeeeeseccesseeeaeeeseeaeenseess 51 5 7 5 Program End Action PROG gt M RMP gt E ACT cccccccsseccceeseccsceesecsceenecsseeeeeseeeuceseseuneess 51 5 7 6 Number of Segments PROG gt M RMP gt N SEG cccccccecccccesesceceeeessceenecseeeeeeseeeuessseeneess 52 5 7 7 Segment Number for Editing PROG gt M RMP gt S SEG rss 52 5 7 8 More on Multi Ramp Soak Programming ii nnne nnns 53 6 Reference Section Operating Mode OPER inner nennen 54 6 1 Normal Rum Mode ToPER RUN annees EE 54 6 2 Change Sstpolnt HOPER SPI SR a ad a en den 55 Omega Engineering www omega com PLATINUM m Series User s Guide Introduction 6 6 3 Change Setpoint 2 OPER gt SP2Z crcivscsonssconsepaawsdtanandeosesatiinataneaceusaneutndsanatsyounnedesetaneaceusasednctanatevones 55 6 4 Manual Mode OPER gt MANL c cccsssccocecececescscecescscessscscecacecacaceesacscsacacessacaceetaceecacacessaceeseacens 55 6 5 Pause Mode OPER gt PAUS a a aa ene ees VIEN a nan 55 6 6 Stop Process TOPER gt STOP a de sant as ae re 56 6 7 Clear katched Al
13. MoDE RE oN for an enabled ramp event to actually do anything e MSP H Setpoint value for Soak cycle e MSt H Time for the Soak cycle the default is 10 See MRT H for more info e MSE Determine whether to activate Soak event enabled outputs o OFF Disable Soak events for this segment factory default ON Enable Soak events for this segment At least one output must be set to MoDE RE oF for an enabled soak event to actually do anything Select the indicated setting Navigate to the correct setting or set the desired value Select the indicated setting or confirm the value Omega Engineering www omega com PLATINUMru Series User s Guide Reference Section Programming Mode PRoG 5 7 8 More on Multi Ramp Soak Programming 5 7 8 1 Overview A key feature of the Ramp and Soak mechanism is provided by the ability to link ramp soak segments together to create a chain of sequences This allows sequences of up to 792 Ramp Soak pairs to be defined A Ramp Soak segment is defined as a specified increase or decrease Ramp of the process variable over a set period of time followed by holding Soak the process variable at a fixed level for a Target Setpoint fixed period of time These controllers provide a multi segment multi profile Ramp and Soak mechanism with the additional ability to link multiple profiles together to implement extended sequences Although the term RAMP is used to indicate the process va
14. firmware will then be read from a thumb drive connected to the USB port 4 11 Resetto Factory Default Parameters INIt F dFt Select the Reset to Factory Default Parameters F dFt function The LED display shows ok and requires confirmation Confirm the parameter reset 4 12 Password Protect Initialization Mode Access INIt I Pwd Select the Password Protect Initialization Mode Access I Pwd function EI d Navigate to the desired setting Settings include the following e No Donotrequire a password for INIt Mode factory default e yES Require a password for INIt Mode users will be prompted for this password when selecting INIt Select the indicated setting ZIO fyES set the numeric password from the range 0000 9999 Confirm the password 4 13 Password Protect Programming Mode Access INIt P Pwd Select the Password Protect Programming Mode Access P Pwd function Omega Engineering www omega com PLATINUM Series User s Guide Reference Section Programming Mode PRoG EI d Navigate to the desired setting Settings include the following e No Do not require a password for PROG Mode factory default e yES Require a password for PRoG Mode users will be prompted for this password when selecting PRoG Select the indicated setting FIC fyES set the numeric password from the range 0000 9999 Confirm the password 5 Reference Section Programming Mode PRoG Use Programming Mode to set the following parameters a
15. for 8DPt 16DPt Models External power source must meet Safety Agency Approvals Units can be powered safely with 24 Vac power but no certification for CE UL is claimed e 12 36 Vdc 3 W power for 8Pt 16Pt 32Pt e 20 36 Vdc 4 W power for 8DPt 16DPt e NEMA Ax Type 4x IP65 front bezel 32Pt 16Pt 16DPt e NEMA 1 Type 1 front bezel 8Pt 8DPt e 8Pt Series 295 g 0 65 Ib e 16Pt Series 159 g 0 35 Ib e 32Pt Series 127 g 0 28 Ib No CE compliance above 60 Hz Omega Engineering www omega com PLATINUMrm Series User s Guide Input Type Process Process J Type T C K Type T C T Type T C E Type T C R Type T C S Type T C B Type T C C Type T C N Type T C RTD RTD RTD Thermistor Thermistor Thermistor Description Process Voltage Process Current lron Constantan CHROMEGA ALOMEGA Copper Constantan CHROMEGA Constantan Pt 13 Rh Pt Pt 10 Rh Pt 30 Rh Pt 6 Rh Pt 5 Re W 26 Re W Nicrosil Nisil Pt 0 00385 100 Q 500 Q 1000 Q Pt 0 003916 100 Q Pt 0 00392 100 O 2252 Q 5K O0 10K O Range 100 mV 1 10 Vdc Scalable within O to 24 mA 210 to 1200 C 346 to 2192 F 270 to 160 C 454 to 256 F Specifications C Accuracy 0 03 FS 0 03 FS 0 4 C 0 7 F 1 0 C 1 8 F 160 to 1372 C 256 to 2502 F 0 4 C 0 7 F 270 to 190 C 454 to 310 F 190 to 400 C 310 to 752 F 270 to 220 C 454 to 364 F 220 to 1000 C 364 to 1832 F 50 to 40 C 58 t
16. frequently changed They include Setpoints Control Modes Alarms etc These settings can be password protected P Operating Mode This mode allows users to switch between Run Mode Standby Mode Manual Mode etc Omega Engineering www omega com PLATINUMrm Series User s Guide PLATINUMTM Series Navigation 2 4 Circular Flow of Menus The following diagram shows how to use the LEFT and RIGHT buttons to navigate around a menu Press the ENTER button on oPER to select and enter RUN Press the UP button to Mode 2 D i 4 navigate back up a level Press the LEFT and RIGHT It is possible to cycle through buttons to navigate around any menu in both directions the Operating Mode options Figure 2 2 Circular Flow of Menus Omega Engineering www omega com PLATINUM rm Series User s Guide Complete Menu Structure 3 Complete Menu Structure 3 1 Initialization Mode Menu INIt The following table maps the Initialization Mode INIt navigation Level Level Level Level Level Level Level 2 3 4 5 6 7 8 INPt t C Type K thermocouple Type J thermocouple Notes Type T thermocouple Type E thermocouple Type N thermocouple Type R thermocouple Type S thermocouple Type B thermocouple Type C thermocouple Z E AJ Rtd 3 wl 3 wire RTD 4 wl 4 wire RTD 2 wl 2 wire RTD A CRV 385 calibration curve 100 Q 385 5 385 calibration curve 500 Q 385 t 385 calibration curve 1000 Q 392 392 calibratio
17. multiple times examples include scaling process inputs for the different process input ranges setting up the data communications protocol for each of the communications channels configuration for multiple outputs etc This manual is optimized for online use Therefore the blue entries in the Section 2 menu tree are hyperlinks that take you straight to the corresponding reference section entry when you click on them The Reference Section encompassing Initialization Mode in Section 4 Programming Mode in Section 5 and Operating Mode in Section 6 will provide more detail on what parameter and command choices you have how they operate and why you might want to choose a specific value There are also blue cross references embedded in the Reference Section the blue section headers however are not hyperlinks In addition the Table of Contents on pages 3 through 6 is hyperlinked to all of the entries throughout the manual that are listed in it Omega Engineering www omega com PLATINUM m Series User s Guide Introduction Oo 1 3 Safety Considerations This device is marked with the international caution symbol It is important to read this manual before installing or commissioning this device as it contains important information relating to Safety and EMC Electromagnetic Compatibility This instrument is a panel mount device protected in accordance with EN 61010 1 2010 electrical safety requirements for electrical equipment for measurem
18. out of range error code E009 Input range choices include the following e 420 4mAto 20 mA factory default e 0 24 OmAto24 mA e 1 10 10 V to 10 V e 41 1Vto 1V e 0 1 1mVto 1 mV Select the desired range EI g Choose either manual or live scaling The scaling functions translate process values to engineering units and are available for all process input ranges The defaults for each input range are the hardware minimum and maximum Scaling methods include the following e MANL User manually enters all four scaling parameters e LIVE User manually enters the low and high display values RD 1 and RD 2 but reads the input signal directly to set the low and high input values IN 1 and IN 2 Using either MANL or LIVE to set up scaling scaled values are then calculated as Scaled Value Input Gain Offset where Gain Rd 2 Rd 1 IN 2 IN 1 Offset Rd 1 Gain IN 1 Therefore scaling can be done over a subset of the applicable range as this scaling calculation linearly extrapolates in both directions Select the scaling method to be used Omega Engineering www omega com PLATINUM ym Series User s Guide Reference Section Initialization Mode INIt BI Navigate to the desired scaling parameter Options include the following e Rd 1 Reading low value corresponding to IN 1 signal e IN 1 Input signal corresponding to RD 1 e Rd 2 Reading high value corresponding to IN 2 signal e
19. than the Proportional factor and potentially result in more overshoot This factor is sometimes referred to by its reciprocal Reset e d Derivative Factor The derivative term sometimes referred to by its recipricol Rate senses the rate of rise or fall of the input measurement and throttles the PID algorithm accordingly A higher value for this factor can speed up or slow down the response of the system even faster than an increase in the Integral Factor will Select the indicated setting EI J Setthe desired value Confirm the value 5 5 5 Low Output Clamping Limit PRoG gt PId gt Lo Select the Low Output Clamping Limit 96Lo parameter 0 to 100 This parameter sets the lower limit of Power applied to an analog output or On time for PWM pulse width modulated control used with the other output types The default setting is 000 096 EI Setthe desired value Confirm the value 5 5 6 High Output Clamping Limit PRoG gt PId gt HI Select the High Output Clamping Limit 96HI parameter O to 10096 This parameter sets the upper limit for power to analog outputs or on time for PWM control with the other output types The default setting is 100 096 Set the desired value Confirm the value Omega Engineering www omega com PLATINUM Series User s Guide Reference Section Programming Mode PRoG ESS 5 5 7 Adaptive Tuning PRoG gt PId gt AdPt Select the Adaptive Tuning AdPt parameter F1 Navigate
20. the number 1 99 corresponding to the Ramp Soak profile to be loaded for use or editing The default is 1 Confirm the value 5 7 3 Multi Ramp Soak Tracking PRoG gt M RMP gt M tRk Select the Multi Ramp Soak Tracking M tRk parameter This parameter has three settings that allow for different ways to manage ramp and soak program tracking BI Navigate to the desired setting Settings include the following e RAMP Guaranteed Ramp Mode If the soak setpoint is not reached within the specified Ramp Time the Ramp and Soak cycle will terminate the outputs are disabled and a failure message E008 will be displayed e SoAK Guaranteed Soak Mode If the soak setpoint is not reached within the specified Ramp Time the system will continue to Ramp and not transition to the Soak Mode until the Soak point is reached The full specified Soak time is preserved e CYCL Guaranteed Cycle Mode If the soak setpoint is not reached within the specified Ramp Time the unit will continue to ramp until that setpoint is reached The additional ramp time required is subtracted from the soak time so that the specified cycle time ramp time soak time is preserved If the soak setpoint is still not reached at the end of total cycle time the ramp and soak program will terminate the outputs are disabled and the failure message E0008 will be displayed Select the indicated setting 5 7 4 Time Format PRoG gt M RMP gt tIM F Select the default Ram
21. to the desired setting When adaptive tuning is enabled the PID parameters are continually optimized based on the process input changes caused by the current output control parameters This is the easiest way to optimize the PID algorithm for a wide variety of systems Settings include the following e ENbL Enables fuzzy logic adaptive tuning factory default e dSbL Disables fuzzy logic adaptive tuning Select the indicated setting 5 6 Remote Setpoint Configuration PRoG gt RM SP Select the Remote Setpoint Configuration RM SP parameter Navigate to the desired setting A remote signal can then be used to set and or change the Setpoint value using an analog input This function can be used for a variety of applications where direct access to the controller for Setpoint manipulation is a problem hazardous environments lack of proximity etc It can also be used to configure the controller in a cascaded control scheme Settings include the following e oFF Do not use a remote Setpoint factory default e oN Remote Setpoint replaces Setpoint 1 Note oFF has no sub parameters but ON requires scaling of the remote Setpoint input Select the indicated setting If oN navigate to the desired input range Options include the following e 4 20 4 00 20 00 mA input signal range e 0 24 0 00 24 00 mA input signal range e 0 10 0 00 10 00 V input signal range e 0 1 0 00 1 00 V input signal range Select the desired input si
22. uses dual displays the current Setpoint value is displayed in the secondary display With the unit remaining active the oPER menu selections can be navigated to using the LEFT and RIGHT buttons Omega Engineering www omega com PLATINUM Series User s Guide Reference Section Operating Mode oPER 6 2 Change Setpoint 1 oPER gt SP1 Select the Change Setpoint 1 SP1 parameter This function allows Setpoint 1 to be changed while remaining in Run Mode Pressing the ENTER button after changing a Setpoint while in RUN Mode returns you to RUN Mode with no interruption in monitoring control or communications operations If remote Setpoint is enabled Setpoint 1 cannot be changed here and the display will flash Set the desired value for Setpoint 1 When changing the setpoints from the operating mode menu the left arrow decreases the value with acceleration and the right arrow increases the value with acceleration This is different from the decimal place switching numeric change control in other places as changes made here are usually limited Confirm the value 6 3 Change Setpoint 2 oPER gt SP2 Select the Change Setpoint 2 SP2 parameter This function allows Setpoint 2 to be changed while remaining in RUN Mode The current value for Setpoint 2 flashes in the main display Setpoint 2 is only used for Alarms and as the cooling Setpoint in Heat Cool Control Mode See 6 2 Change Setpoint 1 OPER gt SP1 for additional information 12 Set
23. 488 www newportuk co uk e mail sales newportuk co uk Newport Electronics B V Benelux Managed by the United Kingdom Office TEL 31 20 3472121 FAX 31 20 6434643 Toll Free 0800 0993344 www newport nl e mail info newport nl Newport Electronics spol s r o Frystatska 184 33 01 Karvin Czech Republic TEL 420 59 6311899 FAX 420 59 6311114 Toll Free 0800 1 66342 www newport cz e mail info newport cz Newport Electronics GmbH Daimlerstrasse 26 D 75392 Deckenpfronn Germany TEL 49 7056 9398 0 FAX 49 7056 9398 29 Toll Free 0800 6397678 www newport de e mail sales newport de Newport Electronique S A R L France Managed by the United Kingdom Office TEL 01 57 32 48 17 FAX 01 57 32 48 18 Toll Free 0805 541 038 www newport fr e mail sales newport fr Mexico and Latin America FAX 001 203 359 7807 TEL En Espa ol 001 203 359 7803 NEWPORTnet On Line Service Internet e mail www newportUS com info newportUS com M5451 N 1115
24. LATINUMru Series User s Guide Reference Section Programming Mode PRoG 5 3 Alarm Mode Configuration PRoG gt ALM 1 ALM 2 Select Alarm Configuration 1 ALM 1 or Alarm Configuration 2 ALM 2 in order to set up change enable or disable Alarms Either or both Alarms can be assigned to trigger display color changes annunciators and or outputs Either or both Alarm configurations can be assigned to multiple outputs The ALM 1 and ALM 2 configuration menus have all of the same settings and function in the same manner F1 Navigate to the Alarm setting you want to change Settings include the following e tyPE Alarm type absolute or deviation e Ab dV Alarm references values ALR H and ALR L or deviation from SP1 or SP2 e ALR H Alarm high parameter used for Alarm trigger calculations e ALR L Alarm low parameter used for Alarm trigger calculations e A CLR Alarm color indication e HLHI High High Low Low offset value e LtCH Alarm latching e CtCL Alarm action normally open or normally closed e A P oN Alarm power on behavior e dE oN Time delay for Alarm trigger unless the condition persists default 1 0 s e dE oF Time delay for cancelling Alarms after being triggered prevents Alarm chatter default 0 0 s Select the indicated setting 5 3 1 Alarm Type PRoG gt ALM 1 ALM 2 gt tyPE Select the Alarm Type tyPE parameter This parameter will control the basic behavior of the selected alarm
25. MEd Medium display brightness Low Low display brightness ECtN Excitation voltage 5 V 10V 10V 12V 12V 24 V 24 V OV Excitation off CoMM USb Configure the USB port Note This PRot submenu is the same for USB Ethernet and Serial ports PRot Waits for commands from other end CoNt Transmit continuously every sec dAtF StAt No yES Includes Alarm status bytes Omega Engineering www omega com PLATINUMrm Series User s Guide Complete Menu Structure Level Level Level Level Level Level Level 2 3 4 5 6 7 8 pote RdNG yES Includes process reading No PEAK yES Includes highest process reading yES Includes lowest process reading UNIt yES Send unit with value F C V mV mA LF yES Appends line feed after each send ECHo yES Retransmits received commands No Carriage Return separator in CoNt SPCE Space separator in CoNt Mode M bUS RtU Standard Modbus protocol ASCI Omega ASCII protocol AddR USB requires Address EtHN Ethernet port configuration AddR Ethernet Telnet requires Address Serial port configuration Single device Serial Comm Mode 485 Multiple devices Serial Comm Mode bAUd Baud rate 19 200 Bd 9600 9 600 Bd 4800 4 800 Bd 2400 2 400 Bd 1200 1 200 Bd 57 6 57 600 Bd 115 2 115 200 Bd PRty Odd parity check used EVEN Even parity check used NoNE No parity bit is used oFF Parity bit is fixed as a zero dAtA 8 bit data format 7bit 7 bit data format StoP 1 stop bit 2blt 2 stop bits gives a force 1 p
26. O number to cover the COST of PURCHASED the repair 2 Model and serial number of the product under 2 Model and serial number of product and warranty and 3 Repair instructions and or specific problems relative 3 Repair instructions and or specific problems to the product relative to the product NEWPORT s policy is to make running changes not model changes whenever an improvement is possible This affords our customers the latest in technology and engineering NEWPORT is a registered trademark of NEWPORT Electronics Inc Patent pending Copyright 2015 NEWPORT Electronics Inc All rights reserved This document may not be copied photo copied reproduced translated or reduced to any electronic medium or machine readable form in whole or in part without prior written consent of NEWPORT Electronics Inc N NEWPORT 1 800 NEWPORT Newport Electronics Inc 2229 South Yale Street Santa Ana CA 92704 U S A TEL 714 540 4914 FAX 203 968 7311 Toll Free 1 800 639 7678 www newportUS com e mail info newportUS com ISO 9001 Certified Newport Technologies Inc 976 Bergar Laval Quebec H7L 5A1 Canada TEL 514 335 3183 FAX 514 856 6886 Toll Free 1 800 639 7678 www newport ca e mail info newport ca Newport Electronics Ltd One Omega Drive River Bend Technology Centre Northbank Irlam Manchester M44 5BD United Kingdom Tel 44 161 777 6611 FAX 44 161 777 6622 Toll Free 0800 488
27. PUTS side not visible here 8 Pin Power Base Outputs Connector 10 Pin Input Connector Figure 1 1b CN8Pt Models Back Panel Connections With Isolated Output Expansion Board Omega Engineering www omega com PLATINUM rm Series User s Guide Introduction 8 Pin Power Outputs Connector 10 Pin Input Connector EC Sears LIP rp al e wo A UC Up x3 Ethernet Connector if EIP Ethernet Communications Status USB Connector on side Option Installed LEDs if EIP Option Installed cable stub shown Figure 1 2 CN16Pt and CN32Pt Models Back Panel Connections 1 4 2 Connecting Power Connect the main power connections to pins 7 and 8 of the 8 pin power output connector as shown in Figure 1 1 EQUIVALENT AC POWER DC POWER 90 240 Vac 110 375 Vdc AIAIAIAIAIAIAIA 8 7 6 5 4 3 2 1 D 5 4 3 SW Fuse 1 9r Use copper conductors only LOW VOLTAGE POWER OPTION for power connections Fuse 2 4 24 Vac 12 36 Vdc Caution Do not connect power to your device until you have completed all input and output connections Failure to do so may result in injury Figure 1 3 Main Power Connections For the low voltage power option maintain the same degree of protection as the standard high N voltage input power units 90 240 Vac by using a Safety Agency Approved DC or AC source with the same Overvoltage Category and pollution degree as the standard AC unit 90 240 Vac The Saf
28. Temperature amp Process Controllers Pt32 Pt16 Pt16D PtsPt PtsD Operator s Manual CE us m PLATINUM Series MX NEWPORT www newportUS com manuals Additional products from N NEWPORT Counters Rate Meters Frequency Meters Timers PID Controllers Totalizers Clock Timers Strain Gauge Printers Meters Process Meters Voltmeters On Off Multimeters Controllers Soldering Iron Recorders Testers Relative pH pens Humidity pH Controllers Transmitters pH Electrodes Thermocouples RTDs Thermistors Thermowells Wire Flow Sensors Wireless For Immediate Assistance In the U S A and Canada 1 800 NEWPORTe In Mexico 95 800 NEWPORTs Or call your local NEWPORT Office The information contained in this document is believed to be correct but NEWPORT Electronics Inc accepts no liability for any errors it contains and reserves the right to alter specifications without notice WARNING These products are not designed for use in and should not be used for patient connected applications TRADEMARK NOTICE M X NEWPORT NEWPORT and newportUS com are trademarks of NEWPORT Electronics Inc AGE device is marked with the international caution symbol It is important to read the Setup Guide before installing or commissioning this device as it contains important information relating to safety and EMC Newport Electronics Inc www newportUS com 2229 South Yale Street info newportUS com Santa Ana CA 92704 PLATINUM
29. Wire 4 Wire Ther Remote Number Voltage Current couple RTD RTD RTD mistor Setpoint 1 Rtn did RTD2 RTD2 Rtn 2 Vin I T C RTD1 RTD1 RTD1 TH 3 l T C RTD2 TH 4 RTD1 RTD1 RTD1 5 V I In For Remote Setpoint with an RTD Pin 1 on the Output Connector must be used for the RtN instead of Pin 1 on the Input Connector Remote Setpoint is not available if you are using an RTD sensor and you have an SPDT Type 3 Output installed Requires external connection to pin 4 Table 1 2 Interfacing Sensors to the Input Connector Omega Engineering www omega com PLATINUMru Series User s Guide Introduction ERESERESEREAEJ AAA t IT RTD 100 Q 4 WIRE RTD 100 Q 3 WIRE RTD 100 Q 2 WIRE requires pin 1 to be jumpered to pin 4 S E E Figure 1 4 RTD Wiring Diagram 0 24 mA Internal ledeisbepel ele is isle AIAIAIAIAIWIAINIANIA AAABABAAAE WW Va 1 a 1 Va Pa 1y Ey Jumper Excitation Figure 1 5 Process Current Wiring Hookup with Internal and External Excitation 1 4 4 Connecting Outputs The PLATINUM Series supports 7 different types of outputs with the model number numeric designations summarized in Table 1 3 Your unit comes preconfigured with up to 3 outputs up to 6 outputs with 1 8 DIN models Table 1 4a shows the base output connector connections for the different configurations offered Your base output configuration is the 3 numeric digits follo
30. an be set to limit the values that can be entered e LPbk Loop break enable disable and timeout value e O CRk Open circuit detection enable disable Select the indicated option 4 5 1 Power On Confirmation INIt gt SFty gt PwoN Select Power On Confirmation PwoN Navigate to the desired setting Settings include the following e dSbL Program runs automatically at startup factory default e ENbL The unit powers on and then displays RUN press the ENTER button to run the program Select the desired setting 4 5 2 Operating Mode Confirmation INIt gt SFty gt oPER Select the Operating Mode Confirmation OPER parameter Navigate to the desired setting Settings include the following e dSbL Pressing the ENTER button in Stby PAUS or StoP Modes will start running the current program immediately factory default e ENbL Pressing the ENTER button in any Operating Menu Mode will display RUN pressing the ENTER button again will start running the current program Select the desired setting 4 5 3 Setpoint Limits INIt SFty SP LM Select Setpoint Limits SP LM to set limits on the values that can be used for the all Setpoints Omega Engineering www omega com PLATINUM ym Series User s Guide Reference Section Initialization Mode INIt EI g Navigate to the desired setting Settings include the following e SP lo Set the minimum possible Setpoint value e SP HI Set the maximum possible Setpoint value Selec
31. arameters and sub parameters include the following e ModE Choose the Mode for initiating ASCII data transfer o CMd Datais sent after receiving a prompt command from the connected device factory default o CoNt Datais sent as it is collected you can set the seconds between data sends default 001 0 In Continuous Mode sending a CTRL Q to the unit suspends transmission and sending a CTRL S restarts transmission e dAt F Data Format select yES or No for the following settings o StAt Alarm status bytes are sent with the data o RdNG Sends the process reading o PEAk Sends the highest process reading so far o VALy Sendsthe lowest process reading so far o UNIt Sends the unit with the value F C V mV mA e _LF_ Select yES or No yES sends a line feed between each data block to format the output in a more readable fashion e ECHo Select yES or No yES echoes each received command to allow verification e SEPR Determines the separation character between each data block o CR Acarriage return sent between data blocks factory default o SPCE A space character is sent between each data block Select the indicated option and manage submenus and parameters as required 4 4 2 Address INIt CoMM USb EtHN SER AddR Select the Address AddR parameter 812 Set the Address value The Modbus protocol requires an address field to correctly identify the selected device The Omega protocol supports an
32. arity bit AddR Address for 485 placeholder for 232 Omega Engineering www omega com PLATINUMru Series User s Guide Complete Menu Structure Level Level Level Level Level Level Level NN 2 3 4 5 6 7 8 SFty RUN s automatically on power up ENbL Power on oPER Mode ENTER to run RUN M ENTER in Stby PAUS StoP runs ENbL ENTER in modes above displays RUN SP LM Low Setpoint limit SP HI High Setpoint limit LPbk Loop break timeout disabled ENbL Loop break timeout value MM SS o CRk Open Input circuit detection enabled dSbL Open Input circuit detection disabled t CAL Manual temperature calibration 1 PNt Set offset default 0 2 PNt R Lo Set range low point default 0 R HI Set range high point default 999 9 ICE P ok Reset 32 F 0 C reference value SAVE Download current settings to USB LoAd EN Upload settings from USB stick VER N Displays firmware revision number VER U ENTER downloads firmware update F dFt ENTER resets to factory defaults Pwd No required password for INIt Mode Set password for INIt Mode P Pwd No password for PRoG Mode Set password for PRoG Mode 3 2 Programming Mode Menu PRoG The following table maps the Programming Mode PROG navigation Level Level Level Level Level 2 3 4 5 6 nots Process goal for PID default goal for oN oF Setpoint 2 value can track SP1 SP2 is an absolute value dEVI SP2 is a deviation value ALM 1 Note This submenu is the same for all other Alarm configurat
33. arms OPER 5L RSE ccicscccssiccestvseispotsdeastnhescbramuensivscs beivbapatsieasenbsesivanssanwsenbaseoaseteas 56 6 8 Display Valley Reading OPER gt VALY ccccccsecccccceeeccceenececeeeeceseeueeesseuecsseeuecsseeueeseeeueeseseunssss 56 6 9 Display Peak Reading OPER gt PEAK Sanaa aus vensieueveearnanesoabeeesvavenwavanooneuess 56 6 10 Standby Mode OPER gt Stby cccccccececcccssecceceeseccceececsceenecsseeuseseeausessseeueesseeueesseeueseeeeneseseenes 56 Te SCC CALI ONS TNT 57 7 1 BEVIS cere 57 7 2 Sog TE 57 7 3 egi 58 7 4 Communications USB Standard Optional Serial and Ethernet 58 7 5 KONTO nat een da da be dr D de todo ral me dou 58 7 6 Slc Mee 58 8 Approval ITA AIO a ad seed mem dM ia UIN de 61 Omega Engineering www omega com PLATINUM m Series User s Guide Introduction 1 Introduction 1 1 Description The PLATINUM Series controller offers unparalleled flexibility in process measurement While the controller is extremely powerful and versatile great care has gone into designing a product that is easy to set up and use Automatic hardware configuration recognition eliminates the need for jumpers and allows the unit s firmware to automatically simplify itself eliminat
34. choose a value between 0 1 and 199 0 The default is 0 1s For mechanical relays choose a value between 1 0 and 199 0 The default is 5 05 Confirm the value 5 4 3 Analog Output Range PRoG oUt1 0Ut3 RNGE Select the Output Range RNGE parameter This menu choice is only available for analog outputs The RNGE parameter is used for both Control and Retransmission Modes and generally must be matched to the input range for whatever device the analog output is driving ZIG Navigate to the desired setting Settings include the following e 0 10 Oto 10 Volts factory default e 0 5 Otob Volts e 0 20 Oto 20mA e 4 20 4to20mA e 0 24 Oto24 mA Select the desired range setting 5 5 PID Configuration PRoG gt PId S Select Pld S to configure the PID control settings These settings apply to all outputs that have had their Control Mode set to PID 5 4 1 2 PID Control Mode PRoG gt oUt1 oUt4 gt ModE gt PId PID control can be optimized in a variety of ways The suggested way is to initiate an autotune command 5 5 3 Autotune PRoG gt PId S gt AUto and then enable adaptive tuning 5 5 7 Adaptive Tuning PRoG gt Pld S gt AdPt The PID parameters may also be set manually or manually adjusted after an autotune command has been executed Omega Engineering www omega com PLATINUM Series User s Guide Reference Section Programming Mode PRoG ECS F1 Navigate to the desired setting Settings include the foll
35. daptive tuning Use SP1 not remote Setpoint Remote analog Input sets SP1 range 4 20 mA Note This submenu is the same for all RM SP ranges SL IN Lo RS HI IN HI M RMP yES RMt SPRG M tRk SoAk CYCL tIM F Min Setpoint for scaled range Input value for RS Lo Max Setpoint for scaled range Input value for RS HI 0 24 mA 0 10 V 0 1 V Multi Ramp Soak Mode off Multi Ramp Soak Mode on M RMP on start with digital input Select program number for M RMP program options 1 99 Guaranteed Ramp soak pnt must be reached in ramp time Guaranteed Soak soak time always preserved Guaranteed Cycle ramp can extend but cycle time can t Minutes Seconds default time format for R S programs Omega Engineering www omega com PLATINUMru Series User s Guide Complete Menu Structure Level Level Level Level Level 2 3 4 5 6 OMS HH MM Hours Minutes default time format for R S programs E ACt Stop running at the end of the program HOLd Continue to hold at the last soak setpoint at program end LINK EE Start the specified ramp amp soak program at program end 1 to 8 Ramp Soak segments 8 each 16 total Select segment number to edit entry replaces below Time for Ramp number default 10 Ramp events on for this segment Ramp events off for this segment MSP Setpoint value for Soak number MSt Time for Soak number default 10 MSE Soak events off for this segment oN Soak events on for this se
36. e 1 0 05s e 2 O 1s e 4 02s Select the indicated option 4 2 4 Annunciator Settings INIt RdG ANN 1 ANN 2 Select the Annunciator 1 ANN 1 parameter This controls which Alarm or output status activates the 1 annunciator on the front display In general the default values for both annunciators should be used status for Alarm configuration 1 for annunciator 1 and status for Alarm configuration 2 for annunciator 2 However it can be useful during troubleshooting to map the on off status of one or two outputs to the annunciators The ANN 1 and ANN 2 parameters work the same way except that they control the 1 and the 2 front display annunciators respectively and have different default values Omega Engineering www omega com PLATINUM ym Series User s Guide Reference Section Initialization Mode INIt BI Navigate to the desired setting Settings include the following e ALM 1 The configuration defined by PRoG gt ALM 1 determines the state of the annunciator The annunciator turns on when the Alarm condition exists factory default for ANN 1 e ALM 2 The configuration defined by PRoG gt ALM 2 determines the state of the annunciator factory default for ANN 2 e oUt oUt is replaced by a list of the names of all outputs that are not analog outputs For example the output choices dtR 1 and dC 1 are listed for a 145 configuration and ANG 1 is not listed Select the indicated option
37. ecimal places not a choice with temperature inputs e F FFF Three decimal places not a choice with temperature inputs Select the indicated format 4 2 2 Temperature Units INIt gt RdG gt F C Select the Temperature Units F C parameter and the current temperature unit selection is then displayed Omega Engineering www omega com PLATINUM ym Series User s Guide Reference Section Initialization Mode INIt BI Navigate to the desired setting Settings include the following e C Degrees Celsius factory default C annunciator turned on e F Degrees Fahrenheit F annunciator turned on e NoNE Default for INPt PROC both temp unit annunciators turned off if the process level input signal corresponds to a temperature temperature transmitters for example the appropriate temperature type annunciator can be chosen Select the indicated option 4 2 3 Filter INIt gt RdG gt FLtR Select the Filter FLtR parameter Filtering averages multiple input analog to digital conversions which can suppress noise in the input signal This should be set to an appropriate value depending on the response time of the input EI J Navigate to the desired setting corresponding to the number of readings per displayed value Settings include the following calculated times between display value updates are shown for each setting as well e 8 0 4s factory default e 16 0 85 e 32 1 65 e 64 32s e 128 64s
38. ennen 33 4 5 3 Setpoint Limits INIt gt SFty gt SRM sen ae rien 33 4 5 4 Loop Break Timeout INIt gt SFty gt LPbk ceeecccccceseecceseeeeecceeeeeeeccesteeeeeeeeseeeneess 34 4 5 5 Open Circuit INIt gt SEDy gt 70 CRK eisirean a E E EES 34 4 6 Manual Temperature Calibration INIt gt t CAL ssl 34 4 6 1 No Manual Temperature Calibration Adjustment INIt gt t CAL gt NONE 35 4 6 2 Manual Temperature Calibration Offset Adjustment INIt gt t CAL gt 1 PNt 35 4 6 3 Manual Temperature Calibration Offset and Slope Adjustment INIt gt t CAL gt 2 PNt 35 4 6 4 Temperature Ice Point Calibration INIt gt t CAL gt ICE P J URL 35 4 7 Save Current Configuration for All Parameters to a File INIt gt SAVE eee 35 4 8 Load a Configuration for All Parameters from a File INIt gt LoAd eeeeernnn 36 4 9 Display Firmware Revision Number INIt gt VER N eeeeeeennnnnnnnnnnnennnnnnnn nnns 36 4 10 Update Firmware Revision INIt gt VER U cccccecccccsescsceeseceseeeecsseeeeeseeeeessseeeeseeeneeeeeeneeeeeen 36 4 11 Reset to Factory Default Parameters INIt gt F dFt ss 36 4 12 Password Protect Initialization Mode Access INIt gt I Pwd 36 4 13 Password Protect Programming Mode Access INIt gt P Pwd 36 5 Reference Section Programming Mode PROG ccc cssssccccecessseccceceeeseccceeeeesccseseeeeeesseseueeceseeeeeees 37 5 1 Set
39. ent control and laboratory use Installation of this instrument should be done by qualified personnel A In order to ensure safe operation the following instructions must be followed and warnings observed This instrument has no power on switch An external switch or circuit breaker must be included in the building installation as a disconnecting device It must be marked to indicate this function and it must be in close proximity to the equipment within easy reach of the operator The switch or circuit breaker must comply with the relevant requirements of IEC 947 1 and IEC 947 3 International Electrotechnical Commission The switch must not be incorporated in the main supply cord Furthermore to provide protection against excessive energy being drawn from the main supply in case of a fault in the equipment an overcurrent protection device must be installed e Do not exceed the voltage rating on the label located on the top of the instrument housing e Always disconnect the power before changing the signal and power connections e Do not use this instrument on a work bench without its case for safety reasons e Do not operate this instrument in flammable or explosive atmospheres e Do not expose this instrument to rain or moisture e Unit mounting should allow for adequate ventilation to ensure that the instrument does not exceed the operating temperature rating e Use electrical wires with adequate size to handle mechanical strain and
40. ety European Standard EN61010 1 for measurement control and laboratory equipment requires that fuses must be specified based on IEC127 This standard specifies the letter code T for a Time lag fuse Omega Engineering www omega com PLATINUM rm Series User s Guide Introduction 1 4 3 Connecting Inputs The 10 pin universal input connector assignments are summarized in Table 1 0 Table 1 2 provides detail for the specific types of sensors supported All sensor selections are firmware controlled see 4 1 Input Configuration INIt gt INPt and no jumper settings are required when switching from one type of sensor to another Figure 1 4 provides more detail for connecting RTD sensors Figure 1 5 shows the connection scheme for process current input with either internal or external excitation Pin No Code Description 1 ARTN Analog return signal analog ground for sensors and remote Setpoint 2 AIN Analog positive input 3 AIN Analog negative input 4 APWR Analog power currently only used for 4 wire RTDs 5 AUX Auxiliary analog input for remote Setpoint 6 EXCT Excitation voltage output referenced to ISO GND 7 DIN Digital input signal latch reset etc Positive at gt 2 5V ref to ISO GND 8 ISO GND Isolated ground for serial communications excitation and digital input 9 RX A Serial communications receive 10 TX B Serial communications transmit Table 1 1 10 Pin Input Connector Wiring Summary Pin Process Process Thermo 2 Wire 3
41. eueeseseueseseensess 27 4 3 Excitation Voltage INIC gt ECIN da de ee ee 29 4 4 Communication INIt gt COMM cccccccssecsccssecsccesccsceececsseesesseeueessseueeseseeueceeseueseseeueseseeneeeeeas 30 4 5 Safety Features INIT gt SF UY canscatencsoteeuneacnoesnssonssannoumatunssanannessuasensevarconntean sua Ud TRI PINO NN OF iquE PUES 33 4 6 Manual Temperature Calibration INIt gt t CAL rss 34 4 7 Save Current Configuration for All Parameters to a File INIt gt SAVE eee 35 4 8 Load a Configuration for All Parameters from a File INIt gt LOA eeeeneenn 36 4 9 Display Firmware Revision Number INIt gt VER N ccccccccssecsscesscsseeeeeseeeeecsseeeeeeeeeneeseeeuness 36 4 10 Update Firmware Revision INIt gt VER U cccccceccccccssecsseescceseeneesseeeecsseeeeeeeseeeseeeeneseeeaneses 36 4 11 Reset to Factory Default Parameters INIt gt F dFt 36 4 12 Password Protect Initialization Mode Access INIt gt I Pwd 36 4 13 Password Protect Programming Mode Access INIt gt P Pwd 36 4 1 Input Configuration INIt gt INPt Select the Input parameter INPt to configure the input EICJ Navigate to the correct setting Settings include the following e tC Thermocouple Temperature Sensor entry point e Rtd Resistance Temperature Detector RTD e tHRM Thermistor Temperature Sensor e PRoC Process Voltage or Current Input Select the indicated setting 4 1 1 Thermocoup
42. fication This WARRANTY is VOID if the unit shows evidence of having been tampered with or shows evidence of being damaged as a result of excessive corrosion or current heat moisture or vibration improper specification misapplication misuse or other operating conditions outside of NEWPORT s control Components which wear are not warranted including but not limited to contact points fuses and triacs NEWPORT is pleased to offer suggestions on the use of its various products However NEWPORT neither assumes responsibility for any omissions or errors nor assumes liability for any damages that result from the use of its products in accordance with information provided by NEWPORT either verbal or written NEWPORT warrants only that the parts manufactured by it will be as specified and free of defects NEWPORT MAKES NO OTHER WARRANTIES OR REPRESENTATIONS OF ANY KIND WHATSOEVER EXPRESSED OR IMPLIED EXCEPT THAT OF TITLE AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED LIMITATION OF LIABILITY The remedies of purchaser set forth herein are exclusive and the total liability of NEWPORT with respect to this order whether based on contract warranty negligence indemnification strict liability or otherwise shall not exceed the purchase price of the component upon which liability is based In no event shall NEWPORT be liable for consequential incidental or special damages
43. fied by S PRG which can provide for cycling through a series of linked programs Specifying 100 will restart the last program run in a sequence of linked programs Select the indicated setting 5 7 6 Number of Segments PRoG M RMP N SEG Select the Number of Segments N SEG parameter ZIQ Setthe number of segments 1 8 The default is 1 Confirm the value 5 7 7 Segment Number for Editing PRoG gt M RMP gt S SEG Select the Segment Number for Editing S SEG Set the segment number to edit for the Program Number This segment number selection will replace the digit in all of the ramp and soak control parameters for that segment listed below MRt MSt etc as you view it on the unit s display This will help you keep track of where you are when programming multiple ramp and soak segments from the front panel Confirm the segment number F1 Navigate to the desired setting Settings include the following e MRt Time for Ramp number the default is 10 Ramp and Soak times can be as long as either 99 minutes and 59 seconds or 99 hours and 59 minutes The default format is controlled by the tIM F parameter setting for this program The default can be overridden for any segment time as described under tIM F e MRE 4 Determine whether to activate Ramp event enabled outputs o OFF Disable Ramp events for this segment factory default o ON Enable Ramp events for this segment At least one output must be set to
44. gment 3 3 Operating Mode Menu oPER The following table maps the Operating Mode oPER navigation I n E Pte Normal Run Mode process value displayed SP1 in optional secondary display EM Shortcut to change Setpoint 1 current Setpoint 1 value in main display SP2 EE Shortcut to change Setpoint 2 current Setpoint 2 value in main display MANL M CNt Manual Mode the RIGHT and LEFT buttons control output displays M M INP Manual Mode the RIGHT and LEFT buttons simulate the input for testing PAUS Pause and hold at current process value display flashes StoP Stop controlling turn off outputs process value rotating flash Alarms remain L RSt Clears any latched Alarms Alarms menu also allows digital input reset VALy Displays the lowest input reading since the VALy was last cleared PEAK Displays the highest input reading since the PEAK was last cleared Stby Standby Mode outputs and Alarm conditions disabled displays Stby Omega Engineering www omega com PLATINUMru Series User s Guide Reference Section Initialization Mode INIt 4 Reference Section Initialization Mode INIt Use Initialization Mode to set the following parameters and perform the following functions 4 1 Input Configuration INIt gt INPt cccccccccsssseccccccesseccceeeeseccceseeeecceseeeeeeeeeseeeeeeeesseeeneeeeetegenss 24 4 2 Display Reading Formats INIt gt RdG ccc ccccccccesecccceesecsceesecseceeecesseueseseeuecsse
45. gnal range to proceed to the scaling parameters starting with RS Lo EI g Navigate to the desired setting Settings include the following e RS Lo Minimum Setpoint value entry point Setpoint 1 is set to this value when the analog input signal is IN Lo e IN Lo Input value in mA or V for RS Lo e RS HI Maximum Setpoint value Setpoint 1 is set to this value when the analog input signal is IN HI e IN HI Input value in mA or V for RS HI Select the indicated setting 12 Setthe desired value Confirm the value Omega Engineering www omega com PLATINUM Series User s Guide Reference Section Programming Mode PRoG ECS 5 6 1 Cascade Control using Remote Setpoint The remote Setpoint feature of the PLATINUM Series controllers can be used in a variety of applications where Setpoints can be sent to the controllers from remote devices such as a manual pots transmitters computers etc This feature can also be used to set up a cascade control system where the remote Setpoint input is generated by another controller Figure 5 3 shows a generic diagram of a cascade control system and Figure 5 4 shows a typical example in this case a heat exchanger application Disturbances Cascaded Controbar Output Temperature l Inner Loop Od on Manipulate d Controlled ontroller Cascaded Flow Controller Variable EE FT Primary Secondary Measurement Measurement 1 Heat Exchanger Primary i Cont
46. he Alarm Color A CLR parameter F1 Navigate to the desired option Options include the following e REd Alarm conditions are displayed in red factory default e AMbR Alarm conditions are displayed in amber e GRN Alarms conditions are displayed in green e dEFt Alarms do not affect the default display color Select the desired option 5 3 6 Alarm High High Low Low Offset Value PRoG ALM 1 ALM 2 gt HLHI Select the Alarm Offset Value HI HI parameter This parameter allows an offset to be added to the Alarm trigger point s which will flash the display when exceeded Depending on the Alarm type the offset can apply above the trigger point below it or both This is illustrated in Figure 5 2 HI HI works with both absolute and deviation Alarms F1 Navigate to the correct option Options include the following e oFF High High Low Low function disabled factory default e ON Display will flash in the color determined by the A CLR parameter when the Process Value is greater than the HI HI offset value away from the Alarm condition settings in either direction Select the indicated option 12 For ON set the offset value Confirm the value Lo Lo HI HI ALR L ALR H bELo HI Lo bANd HI Lo M P Lower Higher Figure 5 2 Alarm HI HI parameter 5 3 7 Alarm Latching PRoG gt ALM 1 ALM 2 gt LtCH Select the Alarm Latching LtCH parameter EI d Navigate t
47. ing parameters and perform the following functions 6 1 Normal Run Mode OPER gt RUN ccccccsseccccesecccccesecseeenecsseeecseeeueeesseuessseeecsseeueeseeeueesesauneess 54 6 2 Change Setpoint HOPER ica 55 6 3 Change Se DO 2 TOPER SP2 aaen EA AE 55 6 4 Manual Mode OPER gt MANL c cccssescsceseccecescsceccecscessecsceecaceccacaceecacscsacacessacaceesacsecataceasacecacacen 55 6 5 PAUSE Mode OPER PAUS TK 55 6 6 SEDD PEOCOESS TOPER SCO caesarean a a te 56 6 7 Clear Latched Alarms OPER gt L RSt 0scocsscoscsssvoscesavessesassovensnvevcesaveevecansosceeavescavassesssanseveass 56 6 8 Display Valley Reading OPER SV ALY sccivsivssssssenvnaioesasaaaaionasaiwsneseinevenvesiaoeesasaveeiarseosnweinavereesavsins 56 6 9 Display Peak Reading OPER gt PEAK eese nnne nnne nennen nennen nnns 56 6 10 Standby Mode OPER gt Stby cccccccceeccccssecscceeecceceuceceeeeeeeseeeueessseueeseeueceseeueesseeueesseuneeeseeees 56 6 1 Normal Run Mode oPER gt RUN Select Normal Run Mode RUN The ENTER button starts the unit operating according to the current input output and communications settings Run Mode will automatically be entered and activated at unit power on if the Power on Confirmation 4 5 1 Power On Confirmation INIt gt SFty gt PwoN parameter is set to dSbL The process value is displayed in the main display and if the unit
48. ing all menu options that do not apply to your configuration Each unit allows the user to select the input type from 9 thermocouple types J K T E R S B C and N Pt RTDs 100 500 or 1000 Q with a 385 392 or 3916 curve thermistors 2250 Q 5K Q and 10K Q DC voltage or DC current The analog voltage inputs are bidirectional and both voltage and current are fully scalable to virtually all engineering units with a selectable decimal point that is perfect for use with pressure flow or other process inputs Control is achieved using the PID on off or heat cool control strategy PID control can be optimized with an autotune feature and in addition a fuzzy logic Adaptive Tuning Mode allows the PID algorithm to be continuously optimized The instrument offers up to 16 Ramp and Soak segments per Ramp and Soak program eight each with auxiliary event actions available with each segment Up to 99 Ramp and Soak programs can be stored and multiple Ramp and Soak programs can be chained creating unmatched ramp and soak programming capability Multiple Alarms can be configured for above below hi lo and band triggering using either absolute or deviation Alarm trigger points The PLATINUM rm Series controller features a large three color programmable display with the capability to change color every time the Alarm is triggered Various configurations of mechanical relay SSR DC pulse and analog voltage or current outputs are available
49. ing flow control loop a more predictable robust and tighter control scheme results Omega Engineering www omega com PLATINUMru Series User s Guide Reference Section Programming Mode PRoG 5 7 Multi Ramp Soak Mode Parameters PRoG gt M RMP Select Multi Ramp Soak Mode M RMP for activation and configuration You can configure store and load up to 99 Ramp Soak programs Each program can have up to 8 Ramps and 8 Soaks including the ability to activate auxiliary non control outputs during any or all Ramp and Soak segments Any segment soak setpoint can be an increase or a decrease from the previous soak setpoint and the unit will automatically determine the control direction reverse or direct for the associated ramp The end action E Act can be defined as StOP HOLd or LINk By using LINk one program can be specified to start at the end of the previous program creating an absolute capability to set up a program with 8 99 or 792 ramps and 792 soaks In addition a program can be linked to itself to create a continuously cycling profile Configuration settings files can be edited on a PC in Excel and this can be especially useful when creating editing complex ramp and soak programs See INIt gt SAVE for further information on this For an overview of Ramp and Soak programming including examples see Section 5 7 8 Note When setting up multidirectional ramp and soak programs only one direction can use PID control as PID contro
50. ings include the following e Rd1 Process reading 1 the process reading that corresponds to the output signal oUt1 e OoUt1 The output signal that corresponds to the process value Rd1 e Rd2 Process reading 2 the process reading that corresponds to the output signal oUt2 e OUt2 The output signal that corresponds to the process value Rd2 Select the indicated setting F1 Setthe desired value Confirm the value Omega Engineering www omega com PLATINUM Series User s Guide Reference Section Programming Mode PRoG 5 4 1 7 Set Output to Ramp Event Mode PRoG gt oUt1 oUt3 gt ModE gt RE oN Activate Output to Ramp Event Mode RE oN during Ramp segments in Ramp and Soak programs when the Ramp Event flag is set for that Ramp segment This can be used to turn on auxiliary devices such as fans or stirrers secondary heaters etc 5 4 1 8 Set Output to Soak Event Mode PRoG gt oUt1 oUt3 gt ModE gt SE oN Activate Output to Soak Event Mode SE oN during Soak segments in Ramp and Soak programs when the Soak Event flag is set for that Soak segment This can be used to turn on auxiliary devices such as fans or stirrers 5 4 2 Output Cycle Pulse Width PRoG gt oUt1 oUt3 gt CyCL Select the Output Cycle Pulse Width CyCL parameter This parameter is used to set the control signal pulse width in seconds for DC pulse mechanical relay and solid state relay SSR outputs BI Seta value Note For DC pulse and SSR outputs
51. ion Initialization Mode INIt Confirm the SAVE command This saves the configuration to the file number specified If the SAVE operation fails the failure code w004 is displayed If the SAVE operation is successful doNE is displayed 4 8 Load a Configuration for All Parameters from a File INIt gt LoAd Select the Load a Configuration LoAd command If no thumb drive is present the failure code E010 is displayed Otherwise a numeric designation for the file to be loaded is then specified and confirmed before the LoAd command executes BI Select a numeric file name from the range 0 99 Confirm the LoAd command This loads the configuration from the file number specified If the LoAd operation fails the failure code w003 is displayed If the LoAd operation is successful doNE is displayed 4 9 Display Firmware Revision Number INIt VER N Select the Display Firmware Revision Number VER N function The currently installed version number is displayed in the format 1 23 4 where 1 is the major revision number 23 is the minor revision number and 4 is the bug fix update number 4 10 Update Firmware Revision INIt VER U Select the Update Firmware Revision VER U function Note that updating your firmware will reset the unit to factory defaults as well If you want to keep you configuration settings save them before installing new firmware The LED display shows ok and requires confirmation Confirm the firmware update New
52. ions ALM 1 is not used for display or outputs AboV Alarm process value above Alarm trigger bELo Alarm process value below Alarm trigger HI Lo Alarm process value outside Alarm triggers bANd Alarm process value between Alarm triggers Omega Engineering www omega com PLATINUM rm Series User s Guide Complete Menu Structure Level Level Level Level Level 2 3 4 5 6 Notes Ab dV Absolute Mode use ALR H and ALR L as triggers d SP1 Deviation Mode triggers are deviations from SP1 d SP2 Deviation Mode triggers are deviations from SP2 ALR H __ Alarm high parameter for trigger calculations ALR L Alarm low parameter for trigger calculations A CLR REd Red display when Alarm is active AMbR Amber display when Alarm is active GRN Green display when Alarm is active dEFt Color does not change for Alarm HI HI OFF High High Low Low Alarm Mode turned off ON Offset value for active High High Low Low Mode LtCH Alarm does not latch yES Alarm latches until cleared via front panel botH Alarm latches cleared via front panel or digital input RMt Alarm latches until cleared via digital input CtCL Output activated with Alarm N C Output deactivated with Alarm A P oN yES Alarm active at power on No Alarm inactive at power on dE oN Delay turning off Alarm sec default 1 0 dE oF Delay turning off Alarm sec default 0 0 ALM 2 Alarm 2 oUt1 oUt1 is replaced by output type Note This submenu is the same for all other outputs
53. l is set to reverse heating or direct cooling action for any and all outputs assigned to MoDE gt PID PID Autotuning of your system under control will tune only for the PID action direction as the optimum PID parameters for the other action direction may be completely different On Off control must be used to set up any output s for the other action direction EI d Navigate to the desired setting Settings include the following e R CtL Activate Multi Ramp Soak Mode e PRG Program number e M tRk Multi Ramp Soak tracking setting e tiM F Time format for Ramp Soak programs e N SEG Number of segments e S SEG Segment number for editing e EAct Determines what happens at the end of a program Select the indicated setting 5 7 1 Multi Ramp Soak Mode Control PRoG gt M RMP gt R CtL Select the Multi Ramp Soak Mode Control R CtL parameter EI g Navigate to the desired setting Settings include the following e No Multi Ramp Soak Mode off e yES Multi Ramp Soak Mode on must be started from front panel e RMt Multi Ramp Soak Mode on front panel or digital input to start Select the indicated setting Omega Engineering www omega com PLATINUMru Series User s Guide Reference Section Programming Mode PRoG 5 7 2 Select Program PRoG gt M RMP gt S PRG Select the Select Program S PRG parameter The current profile for the selected program number will be loaded and can be used as is or modified ZIQ Set
54. lay SPDT Relay SSR Isolated DC Pulse Isolated Analog 7 4 Connection USB Ethernet Serial Protocols 7 5 Isolation Approvals Power to Input Output Power to Relays SSR Outputs Relays SSR to Relay SSR Outputs RS 232 485 to Inputs Outputs 7 6 General Display Specifications Non isolated programmable for control or retransmission Voltage Output O 10 V output 500 Ohms Min Accuracy 0 1 U Current Output 0 20 mA output 500 Ohms Max Accuracy 0 196 0 Step response time 100 ms Non Isolated 10 Vdc at 20 mA Single pole single throw mechanical relay 250 Vac or 30 Vdc at 3 A Resistive Load Single pole double throw mechanical relay 250 Vac or 30 Vdc at 3 A Resistive Load 20 265 Vac at 0 05 0 5 A Resistive Load continuous 1 5 kV Isolation 10 Vdc at 20 mA 1 5 kV Isolation programmable for control or retransmission Voltage Output 0 10 V output 500 Ohms Min Accuracy 0 1 Current Output 0 20 mA output 500 Ohms Max Accuracy 0 196 2 Step response time 100 ms 1 At 25C 2 Output scaling required for stated accuracy Refer to Platinum Current Output Application Note 3 Filter setting of 1 4 Isolated outputs share common return Communications USB Standard Optional Serial and Ethernet USB Female Micro USB Ethernet Standard RJ45 Serial Screw terminals USB 2 0 Host or Device Standards Compliance IEEE 802 3 10 100 Base T Auto switching TCP IP ARP HTTPGET Software Selec
55. le Input Type INIt gt INPt gt t C Select Thermocouple t C as the input type factory default Then specify a specific type of thermocouple or the last selected type will be used Omega Engineering www omega com PLATINUM ym Series User s Guide Reference Section Initialization Mode INIt BI Navigate to the installed thermocouple type Supported types are as follows e k Type K factory default e J Type J e t TypeT e E TypeE e N TypeN e R TypeR e S Types e b TypeB e C TypeC Select the indicated type 4 1 2 Resistance Temperature Detector RTD Input Type INIt gt INPt Rtd Select Rtd as the input type Factory default configuration settings are three wire 100 O using the European standard 385 curve Note that the 392 and 3916 curves are only available for 100 Q RTDs If Rtd is selected and a specific configuration is not changed the last saved configuration will be used 12 Navigate to the desired configuration parameter e N wIR Firmware selection of the number of wires for RTD connection no jumpers needed e A CRV Calibration curve covering both the international standard and the resistance of the RTD Select the option 4 1 2 1 Number of RTD Wires INIt INPt Rtd N wIR ZIG Navigate to the desired setting Settings include the following e 3wl Three wire RTD factory default e Awl Four wire RTD e 2wl Two wire RTD Select the indicated option
56. log Current 4 to 20 mA 0 to 24 mA Scalable 100 to 100 mV 1 to 1 V 10 to 10 Vdc Scalable K J T E R S B C N 100 500 1000 Q Pt sensor 2 3 or 4 wire 0 00385 100 Q only 0 00392 100 Q only or 0 003916 100 Q only curves Differential Bipolar Refer to Table 7 1 0 1 F C temperature 10 uV process Process Voltage 10 MQ for 100 mV Process Voltage 1 MQ for other voltage ranges Process Current 5 Q Thermocouple 10 KO max e RTD 0 04 C C e TCat 25 C 77 F 0 05 C C cold junction compensation e Process 50 ppm C 24 bit Sigma Delta 20 samples per second Programmable from 0 05 seconds filter 1 to 6 4 seconds filter 128 120 dB Firmware selectable no jumpers to set to 5 10 12 and 24 Vdc 25 mA 9999 to 9999 counts 30 min Reverse heat direct cool or heat cool Operator initiated from front panel User selectable fuzzy logic continuous PID tuning optimization On off or the following time amplitude Proportional Control Modes selectable Manual or Auto PID Proportional Proportional with Integral Proportional with Derivative 0 1 199 seconds e Upto 99 Saved Ramp and Soak programs e Upto 8 Ramp and 8 Soak segments with individually selectable events per program e Definable End Actions include program linking e Ramp and Soak segment times 00 00 to 99 59 for HH MM and MM SS Omega Engineering www omega com PLATINUMrm Series User s Guide 7 3 Outputs Analog DC Pulse SPST Re
57. ly adjusted this setting can be set to NoNE to disable the manual adjustment resetting to factory defaults will remove any manually adjustment factors EI J Navigate to the desired setting Settings include e NoNE No manual calibration factory default e 1 PNt Manually create a 1 point calibration e 2 PNt Manually create a 2 point calibration e CEP Manually create a 1 point calibration at 0 C Select the indicated option Omega Engineering www omega com PLATINUMrm Series User s Guide RICA 4 6 1 No Manual Temperature Calibration Adjustment INIt gt t CAL gt NoNE Select NONE to use the standard temperature sensor calibration curves This mode will be used by most users 4 6 2 Manual Temperature Calibration Offset Adjustment INIt gt t CAL gt 1 PNt Select 1 PNt to manually adjust the offset of the calibration curve base on the current reading Set the Manual Thermocouple Calibration Offset value in degrees Confirm the Offset value and pair it with the current input reading 4 6 3 Manual Temperature Calibration Offset and Slope Adjustment INIt gt t CAL gt 2 PNt Select 2 PNt to use 2 points to manually adjust both the offset and slope of the calibration curve Navigate to the desired setting Settings include the following e R Lo Set low point in degrees default 0 and associate with input reading e R HI Set high point in degrees default 999 9 and associate with input reading Selec
58. m PLATINUMrm Series User s Guide 6 6 6 7 6 10 Return to RUN Mode or to displaying RUN depending on the Operating Safety parameter setting 4 5 2 Operating Mode Confirmation INIt gt SFty gt oPER Stop Process 0PER gt StoP Select the Stop Operating Mode StoP to turn off all control outputs The current process value remains with flashing digits in this mode Alarm conditions are maintained Return to RUN Mode or to displaying RUN depending on the Operating Safety parameter setting 4 5 2 Operating Mode Confirmation INIt SFty oPER Clear Latched Alarms oPER L RSt Select the Clear Latched Alarms command L RSt to clear currently latched Alarms Alternatively use digital input to activate the L RSt command if configured in the PRoG menu as explained in 5 3 4 Alarm Latching PRoG gt ALM 1 ALM 2 gt LtCH Return to RUN Mode or to displaying RUN depending on the Operating Safety parameter setting 4 5 2 Operating Mode Confirmation INIt SFty oPER Display Valley Reading 0PER VALy Select Display Valley Reading VALy to change the process value displayed to the lowest reading since VALy was last cleared Clear the VALy reading buffer Return to RUN Mode or to displaying RUN depending on the Operating Safety parameter setting 4 5 2 Operating Mode Confirmation INIt SFty oPER Note Using the other buttons to navigate away from VALy does not clear the VALy reading buffer
59. m Series User s Guide Introduction Contents Deg O ROME RETO ETE 7 Ld Deser Os TT T HER H 7 1 2 Jome TNA a see enemansenaeecinesnenanadeenee eae 8 1 3 Sale e nile E E EE E D TT 9 1 4 WENEI VUCO oran E A ie a lee On A 10 1 4 1 Back Panel CONNECTIONS annees snnenneceerr E TS 10 1 4 2 Connec tine POW CM ae E E Tm 11 1 4 3 Connecting IMPULS e ace do me a on 12 1 4 4 Connecting OS ed de tom at de A 13 2 PLATINUM Series NAMIBATIONE ss cenixesestviaanncbyicateaceidetedrwsactaatrivaiectueindaanredereanveaeteatvennsmalacants T5 2 1 Description of Button ACTIONS nreosense nsc cols bbes sec tie donnee donnes sente cssn noie 15 2 2 Menu SSI US er sem ttn ss 15 2 3 OVE tT N E ee io a 15 2 4 CIF RON OMIS mmm 16 9e COMO US MES DOC ann cutee nce aa ae ni e IDEE 17 3 1 initialization Mode Menu UNIES anne a ae Cote 17 3 2 Programming Mode Menu PROG eese nne nnne nnne nnn nnns 20 3 3 Operating Mode Menu OPER ccccccccssssecccccessecccceeeesecceeeeeeececeeeuseceseseuesecesssseeeceeeeaueeeeeteas 23 4 Reference Section Initialization Mode INIt inner 24 4 1 Input Configuration TINIE gt INPI susce tes ibus cese umtagiiers ves Dm M PR esse a qo DUE CaE S DUMP ET ies tasa IU tbv rds 24 4 1 1 Thermocouple Input Type INIt gt INPE gt t C ss 24 4 1 2 Resistance Temperature Detector RTD Input Type INIt gt INPt gt Rtd 25 4 1 3 Thermisto
60. mpletes successfully the unit displays the message doNE ua Omega Engineering www omega com PLATINUM Series User s Guide Reference Section Programming Mode PRoG 5 5 4 PID Gain Settings PRoG gt PId gt GAIN Select Gain GAIN to manually adjust the PID factors Setting I to zero sets the controller for PD control setting d to zero sets the controller for PI control and setting both I and d to zero sets the controller for proportional control Most of the time you are better off using autotune and adaptive tuning and letting the system optimize its own PID factors The P I and d factors are used to calculate output power according to the following equation On P e I SUM e d de dt e On Power for Analog Outputs or On Width for PWM Outputs e e Error Function Setpoint Process Value e SUM e A summation of the Error Function over time e de dt The rate of change of the Error Function over time The P I and d factors can initially be set using the autotune function and then fine tuned BI Navigate to the desired manual parameter Parameters include the following e P Proportional Factor The proportional factor amplifies the error function process value minus Setpoint to accelerate progress towards to the Setpoint The default value is 001 0 e Integral Factor The integral term amplifies the integrated error function over time and can increase the acceleration towards the Setpoint faster
61. n curve 100 Q 3916 391 6 calibration curve 100 Q tHRM 2250 O thermistor 5k 5000 Q thermistor 10k 10 000 Q thermistor PRoC Process input range 4 to 20 mA Note This Manual and Live Scaling submenu is the same for all PROC ranges MANL Low display reading IN 1 De Manual input for Rd 1 Rd 2 E High display reading IN 2 EN Manual input for Rd 2 LIVE EE Low display reading IN 1 Live Rd 1 input ENTER for current Rd 2 AE High display reading IN 2 EN Live Rd 2 input ENTER for current 0 24 Process input range O to 24 mA 10 Process input range 10 to 10 V 1 Process input range 1 to 1 V 0 1 Process input range 0 1 to 0 1 V Omega Engineering www omega com PLATINUMru Series User s Guide Complete Menu Structure Level Level Level Level Level Level Level NN 2 3 4 5 6 7 8 RdG Reading format 999 9 to 999 9 FFFF Reading format 9999 to 49999 FF FF Reading format 99 99 to 499 99 F FFF Reading format 9 999 to 49 999 F C Degrees Celsius annumciator E Degrees Fahrenheit annunciator NoNE Turns off for non temperature units FLtR Readings per displayed value 8 16 16 32 32 64 64 128 128 1 2 2 3 4 4 ANN 1 Alarm 1 status mapped to 1 ALM 2 Alarm 2 status mapped to 1 oUt Output state selections by name ANN 2 Alarm 2 status mapped to 2 ALM 1 Alarm 1 status mapped to 2 oUt Output state selections by name NCLR GRN Default display color Green REd Red AMbR Amber bRGt High display brightness
62. nd N O Com V Gnd V C Gnd N O Com N O Com NO Com N O Com V Gnd N O Com N O Com V C Gnd V Gnd V Gnd V Gnd V Gnd V Gnd V Gnd V Gnd V C Gnd Table 1 4a 8 Pin Output Power Connector Wiring Summary by Configuration Config 006 776 Output Expansion Board Pin Number Description 6 5 Isolated Analog IDC IDC Isolated Analog V Gnd 4 3 2 1 V C Gnd V Gnd V C Gnd Table 1 4b 6 Pin Output Expansion Board Connector Wiring Summary by Configuration Code N O Com N C Gnd V V C Definition Code Normally open relay SSR load AC Relay Common SSR AC power AC Normally closed relay load DC DC Ground DC Load for DC pulse Load for analog Table 1 5 Definitions for Abbreviations in Table 1 4 Definition AC power neutral in pin AC power hot in pin Negative DC power in pin Positive DC power in pin Omega Engineering www omega com PLATINUMI Series User s Guide PLATINUMTM Series Navigation 2 PLATINUM Tw Series Navigation Alarm Annunciators 7X Negative Sign i F pamm Process Value Temperature Units i Setpoint Value gt o Program Buttons J i NM BEEN Figure 2 1 PLATINUM Series Display CN8DPt Shown 2 4 Description of Button Actions The UP button moves up a level in the menu structure Pressing and holding the UP button navigates to the top level of any menu OPER PRoG or INIt This can be a useful way of reorienting yourself if you get l
63. nd perform the following functions 5 1 Setpoint 1 Configuration PROG gt SP1 esssessssssrresesrrrssrrrresrrrssrrrrsrtresrrtresreresrreresrtreserereerrreeens 37 5 2 Setpoint 2 Configuration PROG gt SPA denses dessertes O Ear ENa ENEs 37 5 3 Alarm Mode Configuration PROG gt ALM 1 ALM 2 cccccccccssecccceeseceseenecsseeeesseeuseseseeneseeeeees 38 5 4 Output Channel 1 4 Configuration PROG gt oUt 1 oUt 4 cecccccceesseceeeeeeeeeeeeeeeeeeeeeeeeas 42 5 5 PID Conneuration PROG P m 45 5 6 Remote Setpoint Configuration PROG gt RM SP cccccccsssssecccccesssecccseeeseecceseeeseeeeeseeeeeeeeeeeeenes 48 5 7 Multi Ramp Soak Mode Parameters PROG gt M RMP Re 50 5 1 Setpoint 1 Configuration PRoG gt SP1 Select the Setpoint 1 SP1 parameter BI Setthe process goal value for Pld or oN oF control Confirm the value 5 2 Setpoint 2 Configuration PRoG gt SP2 Select the Setpoint 2 SP2 parameter SP2 is used with Alarm functions and with on off control when setting up for Heat Cool Control Mode 12 Navigate to the desired setting Settings include the following e ASbo The value for SP2 is specified in Absolute Mode factory default e dEVI The value specified for SP2 indicates an offset positive or negative from SP1 this allows SP2 to track any changes to SP1 automatically Select the indicated setting EI d Set the correct value Confirm the value Omega Engineering www omega com P
64. number 3 e ANG1 Analog output number 1 e dC1 Isolated DC Pulse output number 1 e dC2 Isolated DC Pulse output number 2 e AN1 Isolated Analog output number 1 Note All output channels have the same menu structure However only those parameters that apply for the type of output being configured appear in that output s menu Select the indicated output channel F1 Navigate to the desired submenu Submenus include the following e ModE Allows the output to be set up as a control Alarm retransmission or Ramp Soak event output the output can also be turned off e CyCL PWM pulse width setting for DC pulse mechanical relay and solid state relay outputs e RNGE Sets the voltage or current range for analog outputs Select the indicated setting 5 4 1 Output Channel Mode PRoG oUt1 0Ut3 ModE Select Output Channel Mode ModE to configure the specified output Omega Engineering www omega com PLATINUMru Series User s Guide Reference Section Programming Mode PRoG F1 Navigate to the desired setting Settings include the following e OFF Turn off the output channel factory default e Pid Set the output to Proportional Integral Derivative PID Control Mode e oON oF Set the output to On Off Control Mode e ALM 1 Set the output to be an Alarm using the ALM 1 configuration e ALM 2 Set the output to be an Alarm using the ALM 2 configuration e RtRN Set up the output for Retransmission e REON Turn on the
65. o 104 F 40 to 1788 C 104 to 3250 F 50 to 100 C 58 to 212 F 100 to1768 C 212 to 3214 F 100 to 640 C 212 to 1184 F 640 to 1820 C 1184 to 3308 F O to 2320 C 32 to 4208 F 250 to 100 C 418 to 148 F 100 to 1300 C 148 to 2372 F 200 to 850 C 328 to 1562 F 200 to 660 C 328 to 1220 F 200 to 660 C 328 to 1220 F 40 to 120C 40 to 248F 30 to 140C 22 to 284F 20 to 150C 4 to 302F Table 7 1 Ranges and Accuracies for Supported Inputs Code E001 E002 E003 E004 E005 E006 E007 E008 E009 E010 E011 E012 E013 E014 E015 E016 E017 Error Code Descriptions File not found during load operation Bad file format during load operation File read error during load operation File write error during save operation Device not found for read or write operation Loop break timeout Autotune timeout Ramp and Soak program tracking error Input signal out of range Communications device not ready USB Serial etc Communications install error Failed attempt to open a communications device Failed attempt to read from a communications device Failed attempt to write to a communications device Bad reboot attempt to reboot from an unknown source Signal too unstable to perform autotune Can t autotune because input signal is on wrong side of setpoint Table 7 2 Error Code Descriptions 1 0 C 1 8 F 0 4 C O 7 F 1 0 C 1 8 F 0 4 C O 7 F 1 0 C 1 8
66. o the desired option Options include the following e No Alarm does not latch factory default the Alarm turns off when the Process Value returns to a non Alarm condition e yES Alarm latches even if the Process Value returns to a non Alarm condition the Alarm condition remains active and must be unlatched using oPER L RSt e botH Alarm latches and can be unlatched either by using oPER gt L RSt from the front panel or via the digital input e RMt Alarm latches and can be unlatched only via the digital input Select the indicated option Omega Engineering www omega com PLATINUM Series User s Guide Reference Section Programming Mode PRoG 5 3 8 Alarm Normally Closed Normally Open PRoG gt ALM 1 ALM 2 gt CtCL Select the Alarm Normally Open or Normally Closed CtCL parameter F1 Navigate to the desired option Options include the following e N o Normally open output is activated when the Alarm condition is met factory default e N C Normally closed output is activated in normal conditions but turned off in the Alarm condition Select the indicated option 5 3 9 Alarm Power On Behavior PRoG gt ALM 1 ALM 2 gt A P oN Select the Alarm Power On Behavior A P oN parameter EI d Navigate to the desired option Option include e yES Alarms are active at power on and do not require crossing the Setpoint factory default e No Alarms are inactive at power on the process reading must cross the Alarm condi
67. ollowing e USb Universal Serial Bus USB communications e EtHN Ethernet communications configuration e SER Serial either RS232 or RS485 communications configuration Select the indicated option PI Navigate to the desired parameter submenu Options include the following e PRot Protocol e AddR Address Note The serial communications SER option above also includes the following parameter e C PAR Communications parameters only applicable to serial communications Select the indicated option 4 4 1 Protocol INIt CoMM USb EtHN SER PRot Select the Protocol PRot parameter EI g Navigate to the desired setting Settings include the following e oMEG factory default Omega s Protocol using standard ASCII encoding Further detail on this format is covered in the Communications Manual e M bUS Modbus protocol available as Modbus RTU RtU default or Modbus ASCII ASCI The Ethernet option supports Modbus TCPIP More detail on using this protocol can be found in the Communications Manual Select the desired setting Omega Engineering www omega com PLATINUM ym Series User s Guide Reference Section Initialization Mode INIt 4 4 1 1 ASCII Parameters INIt gt COMM gt USb EtHN SER gt PRot gt oMEG Select OMEG to configure Omega ASCII mode communications parameters These configuration settings are the same for USB Ethernet and Serial communications PI Navigate to the desired parameter P
68. on ALR L ALR H Absolute Mode AbSo PELO HI Lo bANd AboV HI Lo Lower Higher SP1 SP2 bANd SP2 has the same alarm options bELo HI Lo AboV HI Lo pov Deviation Mode dEVI Lower Higher Figure 5 1 Alarm Range Option Diagram 5 3 2 Absolute or Deviation Alarm PRoG gt ALM 1 ALM 2 gt tyPE gt Ab dV Select the Absolute or Deviation Alarm Ab dV parameter 12 Navigate to the correct setting Settings and subsettings include the following e AbSo Alarm is triggered using calculations based on the absolute values of ALR H or ALR L used as specified by the tyPE parameter e d SP1 Alarm is triggered using calculations based on values relative to SP1 as specified by the tyPE parameter e d SP2 Alarm is triggered using calculations based on values relative to SP2 as specified by the tyPE parameter Select the desired setting 5 3 3 Alarm High Reference PRoG ALM 1 ALM 2 tyPE ALR H Select the Alarm High Reference ALR H parameter EIEdg Set the Alarm High Reference value Confirm the value 5 3 4 Alarm Low Reference PRoG gt ALM 1 ALM 2 gt tyPE gt ALR L Select the Alarm Low Reference ALR L parameter EI d Setthe Alarm Low Reference value Confirm the value Omega Engineering www omega com PLATINUM Series User s Guide Reference Section Programming Mode PRoG CSS 5 3 5 Alarm Color PRoG gt ALM 1 ALM 2 gt A CLR Select t
69. optional address field which is required for Serial channels configured for RS485 Accept the entered value 4 4 3 Serial Communications Parameters INIt COMM SER gt C PAR Select C PAR Then select individual parameters to configure the serial communications Omega Engineering www omega com PLATINUM ym Series User s Guide Reference Section Initialization Mode INIt BI Navigate to the correct setting Settings include the following bUS F Specify RS232 or RS485 serial communications bAUd Baud rate transmission rate PRty Parity used for transmission error checking dAtA Number of bits per data point StoP Number of stop bits between data points Select the desired setting EIL 4 4 3 1 Serial Bus Format INIt gt COMM gt SER gt C PAR gt bUS F Select the Bus Format bUS F parameter Navigate to the desired setting Settings include the following e 232C Allows one to one serial communications factory default e 485 Allows multiple devices to operate on a single pair of wires Select the indicated option 4 4 3 2 Baud Rate INIt gt COMM gt SER gt C PAR gt bAUd Select the Baud Rate bAUd parameter The device being communicated to determines how fast you can set the Baud Rate Navigate to the desired setting for Baud rate bits per second e 19 2 19 200 Baud factory default e 9600 9 600 Baud e 4800 4 800 Baud e 2400 2 400 Baud e 1200 1 200 Baud e 57 6
70. ost in the menu structure The LEFT button moves across a set of menu choices at a given level up in the Section 4 menu structure tables When changing numerical settings press the LEFT button to make the next digit one digit to the left active The RIGHT button across a set of menu choices at a given level down in the Section 4 menu structure tables The RIGHT button also scrolls numerical values up with overflow to 0 for the flashing digit selected The ENTER button selects a menu item and goes down a level or it enters a numerical value or parameter choice MMA E 2 2 Menu Structure The menu structure of the PLATINUM Series is divided into 3 main Level 1 groups which are Initialization Programming and Operating They are described in Section 2 3 The complete menu structure for levels 2 8 for each of the three Level 1 groups is detailed in Section 3 1 3 2 and 3 3 Levels 2 through 8 represent sequentially deeper levels of navigation Values with a dark box around them are default values or submenu entry points Blank lines indicate user provided information Some menu items include links to reference information elsewhere in this user manual The information in the Notes column defines each menu choice 2 3 Level 1 Menu Initialization Mode These settings are rarely changed after initial setup They include transducer types calibration etc These settings can be password protected Programming Mode These settings are
71. output during Ramp events e SE oN Turn on the output during Soak events Select the indicated setting 5 4 1 1 Turn Off Output Channel PRoG gt oUt1 0Ut3 gt ModE gt oFF Turn off this output OFF 5 4 1 2 PID Control Mode PRoG gt oUt1 0Ut3 gt ModE gt Pld Select PID Control Mode Pld for this output factory default PID parameters are set outside the specific output submenus as more than one output can be used for PID control at a time See 5 5 PID Configuration PRoG gt PID 5 4 1 3 On Off Control Mode PRoG gt oUt1 oUt3 gt ModE gt oN oF Select On Off Control Mode oN oF for this output More than one output can be set up for oN oF control For Heat Cool control set the output connected to the heater with ACtN equal to RVRS and the output connected to the cooling device with ACtN set to dRCt 12 Navigate to the desired setting Settings include the following e ACtN Determines the action direction for control e dEAd Sets the deadband value the deadband value is applied in the same units as the process variable to one side of Setpoint as determined by the ActN direction e SPNt Allows either Setpoint 1 or Setpoint 2 to be specified as the target value Setpoint 2 can be set to track Setpoint 1 using the deviation dEVI option 5 2 Setpoint 2 PRoG SP2 a useful feature when setting up for heat cool operation Select the indicated setting Omega Engineering www omega com PLATINUM Se
72. owing e ACtN Action direction allows you to move up or down to SP1 e A to Autotuning Timeout sets a maximum amount of time for autotuning e AUto Initiates autotuning e GAIN Select the proportional integral and derivative factors for manual tuning e 96Lo Low clamping limit for Pulse and Analog outputs e 96HI High clamping limit for Pulse and Analog outputs e AdPt Fuzzy logic adaptive tuning Select the desired parameter 5 5 1 Action Response PRoG PId ACtN Select the ction Direction ACtN parameter BI Navigate to the desired setting Settings include the following e RVRS Reverse Action Increase to SP1 such as heating factory default e dRCt Direct Action Decrease to SP1 such as cooling Select the indicated setting 5 5 2 Autotune Timeout PRoG gt PId gt A to Select the Autotune Timeout A to parameter BI Setthe amount of time before the autotune process gives up and times out in Minutes and Seconds MM SS Slowly responding systems should have a longer time out setting Select the indicated setting 5 5 3 Autotune PRoG PId AUto Select the Autotune AUto command The unit displays StRt Confirm Autotune activation The unit attempts to optimize the P I and d settings by stimulating the system and measuring the response If the A to time out period expires before the autotune operation can complete the unit displays a failure message E007 If the autotune operation co
73. p and Soak Time Format tIM F parameter for the current program The default format can be overridden to create mixed time mode Ramp and Soak programs EI g Navigate to the desired setting Settings include the following e MM SS Time specified in minutes and seconds factory default e HH MM Time specified in hours and minutes Indicated by turning on the negative sign to differentiate from MM SS format when adjusting the MRT and MST parameters for a given segment Select the indicated option Note that the default time format can be overridden for any given segment time by pressing the left arrow with that time showing until it sequences through each digit and then the entire time flashes Pressing the right arrow at that point will change the setting for that segment to the other time format 5 7 5 Program End Action PRoG gt M RMP gt E ACT Select the End Action E ACT parameter Omega Engineering www omega com PLATINUMru Series User s Guide Reference Section Programming Mode PRoG F1 Navigate to the desired setting Settings include the following e StOP Enter standby mode displaying RUN at the completion of this program e HOLd Hold at the final soak setpoint at the completion of this program e LINK Link to another stored ramp amp soak program at the completion of this program o dH Specify the Program Number to start at the completion of this program 1 to 99 Specifying O will repeat the program speci
74. point 1 Configuration PROG gt SP1 ccc cccccccceeseceseeecseceecesseeeecsseeueesseeueeseeeueseseenessseeees 37 5 2 Setpoint 2 Configuration PROG gt SP2 rss nennen sese snae sanas 37 5 3 Alarm Mode Configuration PROG gt ALM 1 ALM 2 ccccccscssscccccesecseeesecsseeeseeeeeuseseseeneseseeees 38 5 3 1 Alarm Type PRoG gt ALM 1 ALM 2 gt tyPE cccccccccccccecccceseececsceeeeecesesseeeeeeseeeeeeeeeseeeeess 38 9 3 2 Absolute or Deviation Alarm PRoG gt ALM 1 ALM 2 gt tyPE gt Ab dV eene 39 5 3 3 Alarm High Reference PRoG gt ALM 1 ALM 2 gt tyPE gt ALRH ccccccececssseeeeseseeeeeeseeees 39 5 3 4 Alarm Low Reference PROG gt ALM 1 ALM 2 gt tyPE gt ALR L c cccccccesesceseceseseecsceseseeseceeess 39 5 3 5 Alarm Color PROG gt ALM 1 ALM 2 gt A CLR eese nnne nnne nnne 40 Omega Engineering www omega com PLATINUM m Series User s Guide Introduction 5 3 6 Alarm High High Low Low Offset Value PRoG gt ALM 1 ALM 2 gt HI HI 40 5 3 7 Alarm Latching PRoG gt ALM 1 ALM 2 gt LtCH ou cceccccceesecseeeeecseeeeseseeeeeseseenessseenes 40 5 3 8 Alarm Normally Closed Normally Open PRoG gt ALM 1 ALM 2 gt CtCL eeeee eens 41 5 3 9 Alarm Power On Behavior PROG gt ALM 1 ALM 2 gt A P OoN nnne 41 5 3 10 Alarm On Delay PRoG gt ALM 1 ALM 2 gt E ON cccccccesseccceeeecsseeeceseeeeeseseeeeeeeeeeeeeeas 41 5 3 11 Alarm Off Delay PRoG
75. power requirements Install this instrument without exposing the bare wire outside the connector to minimize electrical shock hazards A EMC Considerations e Whenever EMC is an issue always use shielded cables e Never run signal and power wires in the same conduit e Use signal wire connections with twisted pair cables e Install Ferrite Beads on signal wires close to the instrument if EMC problems persist A Failure to follow all instructions and warnings is at your own risk and may result in property damage bodily injury and or death Omega Engineering is not responsible for any damages or loss arising or resulting from any failure to follow any and all instructions or observe any and all warnings Omega Engineering www omega com PLATINUM m Series User s Guide Introduction 1 4 Wiring Instructions 1 4 1 Back Panel Connections Ethernet Connector if EIP Option Installed Ethernet Communications Status LEDs if EIP Option Installed USB Connector on side HEXGNE TR shown with cable stub 8 Pin Power Base Outputs Connector 10 Pin Input Connector Figure 1 1a CN8Pt Models Back Panel Connections No Isolated Output Expansion Board Installed Optional Isolated Output Expansion Ethernet Connector if EIP Option Installed Connector POWER mi m ETHERNET Tlo Ethernet Communications Status l LEDs if EIP Option Installed z 8 7 STATUS jee mp USB Connector on 7 G outputs 1 IN
76. r Input Type Configuration INIt gt INPt gt tHRM nne 26 4 1 4 Process Input Type Configuration INIt gt INPt gt PROC 26 4 2 Display Reading Formats INIt gt RdG ins nennen nnne senes 27 4 2 1 Decimal Point Format INIt gt RdG gt dEC P se 27 4 2 2 Temperature Units INIt gt RdG gt CFPC cccccccccccscecsseceeseeceseeeeeeesseeeeeeeseeeeeueesseuaeneeess 27 4 2 3 PANIERS Mh E 28 4 2 4 Annunciator Settings INIt gt RAG gt ANN 1 ANN 2 eeeeennnn nennen nnns 28 4 2 5 Normal Color INIt gt RAG gt NCER nas dessertes aies 29 4 2 6 BRIS CMe SS dE FROG gt DROE ae ee en 29 Omega Engineering www omega com PLATINUM m Series User s Guide Introduction 4 4 3 Excitation Voltage INIt gt ECEN s cccsccsnessnsnscusisamansaeeaned veaatesausatasaneedianatdacsesaseneteseodentapesadbanatsnorss 29 4 4 Communication UNIES COMM iassa 30 4 4 1 Protocol INIt gt COMM gt USb EtHN SER gt PROt serre 30 4 4 2 Address INIt gt COMM gt USb EtHN SER gt ACOR ccccccecececcececcscecescscececcscescasscescaceceesacen 31 4 4 3 Serial Communications Parameters INIt gt COMM gt SER gt C PAR sssssercssrrrreerrrsern 31 4 5 Safety Features INIt SPORE dde dan a de a ee ne Cu 33 4 5 1 Power On Confirmation INIt gt SFty gt PWON ccccccccsseeccceessesseeesecsseeecsseeeeeeseeueeeeseeneess 33 4 5 2 Operating Mode Confirmation INIt gt SFty gt OPER n
77. riable change there is no restrictions on the direction of change The Target Setpoint may be above or below the Current process variable for each Soak 1 Ramp 1 Ramp 2 Soak 2 The Ramp and Soak times are provided in 1 second increments and may span from 1 second to 99 hours cycle within a sequence Current Process Variable 59 minutes 59 seconds Internally the time values are tracked within 0 1 second intervals The Ramp and Soak function attempts to provide a controlled increase to the process variable such that the target setpoint is reached within the specified time Options are provided to track the specified RAMP time the specified SOAK time or the overall CYCLE time Omega Engineering www omega com PLATINUM Series User s Guide Reference Section Operating Mode oPER 5 7 8 2 Ramp Soak Program Linking LINK parameter Where N is the number of Allows continuous cycling of a single program the current program Reload the S PRG program Allows continuous process cycling using multiple linked programs Load the specified program Allows linking to a specified program 100 Reload the current program Allows cycling of the last program in a linked chain of programs 6 Reference Section Operating Mode oPER Operating Mode is used to activate the unit s monitoring and controlling functions It also allows shortcut access to the Setpoint parameters while still running Use Operating Mode to set the follow
78. ries User s Guide Reference Section Programming Mode PRoG ESS ZIG For ACtN select the correct setting Settings include the following e RVRS Off when Process Value is gt Setpoint and on when Process Value is lt Setpoint e g heating deadband is applied below Setpoint factory default e dRCt Off when Process Value is lt Setpoint and on when Process Value is Setpoint e g cooling deadband is applied above Setpoint For dEAd set the desired value The default is 5 0 Select the indicated ACtN setting or confirm the dEAd value 5 4 1 4 Output as Alarm 1 PRoG gt oUt1 oUt3 gt ModE gt ALM 1 Select this Output to be an Alarm using the Alarm 1 ALM 1 configuration 5 4 1 5 Output as Alarm 2 PRoG gt oUt1 0Ut3 gt ModE gt ALM 2 Select this Output to be an Alarm using the Alarm 2 ALM 2 configuration 5 4 1 6 Retransmission PRoG gt oUt1 0Ut3 gt ModE gt RtRN Select Retransmission RtRN as the Operating Mode for the output This option is only available for analog outputs Scaling is performed using absolute values not calculated counts The retransmission signal type voltage or current and range is set for this output using the 5 4 3 Analog Output Range PRoG gt oUt1 oUt3 gt RNGE parameter The retransmission signal is then scaled using the following 4 parameters The unit will display the first scaling parameter Rd1 after RtRN is selected EI g Navigate to the desired setting Sett
79. roller Disturbance Process Flow Setpoint Condensate Figure 5 3 Generic Cascade Control Diagram Figure 5 4 Heat Exchanger with Cascade Control Cascade control schemes can provide tighter control of a process when you have two linked variables one of which has a much slower typically 4X or more response than the other The slower responding variable is used as the input to the primary or master controller and the faster responding variable is used as the input to the secondary or slave controller The output of the primary controller is scaled to be used as the Setpoint for the secondary controller In the heat exchanger application in Figure 2 the primary goal of the application is to control the temperature of the effluent Therefore the desired effluent temperature becomes the Setpoint for the primary controller which is a temperature controller TC The process input for the temperature controller is the measured temperature of the effluent TT The output of the temperature controller is the flow Setpoint for the secondary controller which is a flow controller FC The process input for the secondary flow controller is the flow rate of the steam that is used to heat the process flow through the heat exchanger FT The output of the secondary flow controller is a control signal for the proportional valve controlling the flow of the steam By isolating the slowly changing effluent temperature control loop from the rapidly chang
80. ssions requirements for electrical equipment for measurement control and laboratory are as follows e EMC Emissions Table 4 Class A of EN61326 e EMC Immunity Table 1 of EN61326 UL File Number E209855 2 Low voltage DC power option Units configured for external low power DC voltage 12 36Vdc 3 Ibid O signal and control lines require shielded cables and these cables must be located on conductive cable trays or in conduits The length of these cables should not exceed 30 meters Omega Engineering www omega com Warranty Disclaimer NEWPORT Electronics Inc warrants this unit to be free of defects in materials and workmanship for a period of one 1 year from the date of purchase In addition to NEWPORT s standard warranty period NEWPORT Electronics will extend the warranty period for four 4 additional years if the warranty card enclosed with each instrument is returned to NEWPORT If the unit should malfunction it must be returned to the factory for evaluation NEWPORT s Customer Service Department will issue an Authorized Return AR number immediately upon phone or written request Upon examination by NEWPORT if the unit is found to be defective it will be repaired or replaced at no charge NEWPORT s WARRANTY does not apply to defects resulting from any action of the purchaser including but not limited to mishandling improper interfacing operation outside of design limits improper repair or unauthorized modi
81. t the desired setting BI Setthe Setpoint limit value Confirm the value 4 5 4 Loop Break Timeout INIt gt SFty gt LPbk Select the loop break LPbk parameter When enabled this parameter specifies the amount of time in Run Mode without a change in input value that would signify a sensor malfunction For example if there were a problem in a thermocouple the input would not change over time BI Navigate to the desired setting Settings include the following e dSbL No loop break timeout protection factory default e ENbL Set loop break timeout value Select the indicated setting QIO fENbL Set the loop break timeout value in minutes and seconds MM SS Confirm the value 4 5 5 Open Circuit INIt SFty o CRk Select the open circuit o CRk parameter When o CRk is enabled the unit will monitor Thermocouples RTD and Thermistors for an open circuit condition BI Navigate to the desired setting Settings include the following e ENbL Open circuit conditions will stop the program and display oPEN factory default e dSbL No open circuit protection may be necessary when using high impedance infrared thermocouples or thermistors Confirm the value 4 6 Manual Temperature Calibration INIt gt t CAL Select the Manual Temperature Calibration t CAL submenu This parameter allows you to manually adjust the thermocouple RTD or Thermistor calibration curves provided with the unit Once a curve has been manual
82. t the indicated setting Set the Temperature for R Lo or R HI Confirm the value and pair it with the current input reading 4 6 4 Temperature Ice Point Calibration INIt gt t CAL gt ICE P Select ICE P to calibrate the zero point for the temperature sensor This function basically operates the same as a 1 PNT offset adjustment restricted to a measurement at the freezing point of water The LED display shows ok and requires confirmation Confirm the Ice Point reset Save Current Configuration for All Parameters to a File INIt SAVE Select Save Current Configuration Settings SAVE as the command to execute If no thumb drive is present the failure code E010 is displayed Otherwise a numeric designation for the save file is then specified and confirmed before the SAVE command executes Important Note The configuration file is a tab separated text file with a TXT extension It can be loaded onto a PC read into Excel then modified there Once modified save it back as a tab separated TXT file and it can then be loaded back into the unit using the INIt LoAd command This capability can be especially useful for editing complex multi ramp and soak programs For more information on the configuration file format see the Load and Save File Format Manual Select a numeric file name from the range 0 99 Omega Engineering www omega com Reference Section Initialization Mode INIt PLATINUM ym Series User s Guide Reference Sect
83. table RS 232 or RS 485 Programmable 1200 to 115 2 K baud Omega ASCII Modbus ASCII RTU UL C UL and CE 8 Approvals Information e 2300 Vac per 1 min test e 1500 Vac per 1 min test Low Voltage Power Option 2300 Vac per 1 min test 2300 Vac per 1 min test 500 Vac per 1 min test 4 digit 9 segment LED red green and amber programmable colors for process variable Setpoint and temperature units e 10 2 mm 0 40 32Pt 16Pt 16DPt Dual Display e 21mm 0 83 8Pt e 21mm 0 83 and 10 2 mm 0 40 8DPt Dual Display Omega Engineering www omega com PLATINUM rm Series User s Guide Specifications Dimensions Panel Cutout Environmental Conditions External Fuse Required Line Voltage Power Low Voltage Power Option Protection Weight e 8Pt Series 48H x 96 W x 127 mm D 1 89 x 3 78 x 5 e 16Pt Series 48 H x 48 W x 127 mm D 1 89 x 1 89 x 5 e 32PtSeries 25 4 H x 48 W x 127 mm D 1 0 x 1 89 x 5 e 8Pt Series 45 H x 92 mm W 1 772 x 3 622 1 8 DIN e 16Pt Series 45 mm 1 772 square 1 16 DIN e 32Pt Series 22 5 H x 45 mm W 0 886 x 1 772 1 32 DIN All Models 0 50 C 32 122 F 9096 RH non condensing Time Delay UL 248 14 listed e 100mA 250V e 400 mA 250 V Low Voltage Option Time Lag IEC 127 3 recognized e 100mA 250V e 400 mA 250 V Low Voltage Option e 90 240 Vac 10 50 400 Hz e 110 375 Vdc equivalent voltage e 4W power for 8Pt 16Pt 32Pt Models e 5 W power
84. the desired value for Setpoint 2 Confirm the value 6 4 Manual Mode oPER gt MANL Select the Manual Operating Mode MANL This mode allows for control output levels or the process input value to be manually changed FIX Navigate to the desired Manual Operating Mode The choices are as follows e M CNt Manually vary the control output s e M INP Manually simulate change in the process input Select the desired Manual Operating Mode EIId Varythe Output or Input manually with the left and right arrows For M CNt the On value is displayed instead of the process input value With analog outputs the On value specifies the output current or voltage as a percentage of the total scaled range With DC Pulse and Relay outputs the On value controls the width of the PWM pulse width modulated signal For M INP the process input value continues to be displayed but the value can be changed up or down using the RIGHT and LEFT buttons respectively This is a simulated value and it can be used to test out Alarm configurations retransmission scaling etc Exit Manual Mode and return to Run Mode 6 5 Pause Mode oPER gt PAUS Select the Pause Operating Mode PAUS to pause the controller and hold the process input at its current value If in a Multi Ramp Soak program the timer for the current Ramp or Soak segment is paused as well The current process value display will flash while in pause mode Omega Engineering www omega co
85. tion before being activated Select the indicated option 5 3 10 Alarm On Delay PRoG ALM 1 ALM 2 dE oN Select the Alarm On Delay dE oN parameter BI Set the number of seconds to delay triggering the Alarm The default is 0 This setting can be used to prevent false Alarm triggering when the Process Value only briefly enters an Alarm condition Confirm the value 5 3 11 Alarm Off Delay PRoG gt ALM 1 ALM 2 gt dE oF Select the Alarm Off Delay dE oF parameter ZIQ Set the number of seconds to delay cancelling the Alarm The default is 0 This setting can be used to prevent Alarm chatter Confirm the value Omega Engineering www omega com PLATINUM Series User s Guide Reference Section Programming Mode PRoG 5 4 Output Channel 1 6 Configuration PRoG gt oUt 1 0Ut 6 12 Navigate to the desired output channel The number and type of output channels on the PLATINUM Series are automatically recognized by the device The following output names are what you can see on the panel display replacing the generic oUt 1 through oUt 3 references used in this document e StR1 Single Throw Mechanical Relay number 1 e StR2 Single Throw Mechanical Relay number 2 e dtR1 Double Throw Mechanical Relay number 1 e dtR2 Double Throw Mechanical Relay number 2 e SSR1 Solid State Relay number 1 e SSR2 Solid State Relay number 2 e dC1 DC Pulse output number 1 e dC2 DC Pulse output number 2 e dC3 DC Pulse output
86. wing the first dash in your model number The optional isolated output expansion board offered on 1 8 DIN models can add 1 or 3 additional isolated outputs with the numeric codes and connection positions shown in Table 1 4b Table 1 5 defines the abbreviated codes used in Tables 1 4a and 1 4b Please note that the SPST and SPDT mechanical relays have snubbers built in but only on the normally open contact side Omega Engineering www omega com PLATINUMrm Series User s Guide Code YO UW BB WN HP Introduction Output Type 3A Mechanical single pole single throw SPST mechanical relay 1A Solid state relay SSR 3A Mechanical single pole double throw SPDT mechanical relay DC pulse for connecting to an external SSR Analog current or voltage Isolated Analog current or voltage only on output expansion board for 1 8 DIN models Isolated DC pulse IDC only on output expansion board for 1 8 DIN models Table 1 3 Output Type Designations for Base Output Connector Config 330 304 305 144 145 220 224 225 440 444 445 Power Description 8 7 SPDT SPDT SPDT DC pulse SPDT analog SPST DC pulse DC pulse SPST DC pulse analog AC AC SSR SSR or or SSR SSR DC pulse DC DC SSR SSR analog DC pulse DC pulse DC pulse DC pulse DC pulse DC pulse DC pulse analog Output Pin Number 6 5 4 3 2 1 N O Com N C N O Com N C N O Com N C V Gnd N O Com N C V C Gnd N O Com V Gnd V G
Download Pdf Manuals
Related Search
Related Contents
3.活力みなぎる元気な街 ANEXO I Philips SoundShooter Portable speaker SBA3010BLU NT TURBINE KM-JETs エンジン NT70 / NT140 / NT170 取扱説明書 Ficha Técnica SHT-3006 / CW610E 1MB ZUV-H Instrucciones Hotpoint FFUG 20xx x O3 Refrigerator User Manual USER`S MANUAL - Power Drive Services Samsung M197DNR Инструкция по использованию Copyright © All rights reserved.
Failed to retrieve file