1. pres postaa Figure 20 Room pressure switch joint view The differential pressure switch can be mounted in several ways Mounting the body of the pressure switch in the room figure 21 Mounting the body of the pressure switch in the surrounding room figure 21 Mounting the body of the pressure switch in the false ceiling of the room figure 22 r gt Handbook code 75802206A 0204 TECNAIR LB Sheet 41 of 82 CONTRO ERS Figure 21 Mounting the differential pressure switch in the room Figure 22 Mounting the differential pressure switch in the surrounding environment Figure 23 Mounting the body of the pressure switch in the false ceiling of the room Anywhere you decide to install the differential pressure switch it is essential that The tube with free end is connected with the positive outlet of the differential pressure switch the free end must jut some centimetres out of the wall or false ceiling di d Handbook code 75802206 0204 TECNAIR LB Sheet 42 of 82 CONTRO ABI ERS The pressure switch is installed not less than two metres over the floor so as to be more protected against possible deposits of dust Concerning the electrical connections the pressure switch receives two terminals the feeding one 24V and the outgoing signal 4 20mA The cable AWG24 screened type not supplied by Tecnair LB shall be connected wit
2. Verification of the air cooled condensers only OHA OWA models Verification of the electric connections to the condenser switch Verification that the switch is in on position feeded condensor Verification that the frigorific connections of the condenser are in opposite streamdirection between the refrigerant and the air Verification of the correct positioning of the condenser away from walls and or other condensers so to avoid air recirculation which would not allow for it s good functionment r gt Handbook code 75802206A 0204 TECNAIR LB Sheet 47 of 82 AB OTC ERS Verification electrical feeding Verification of the connection of the three phases neutral and ground connection Verification that the feeding line has a tension tolerance of 10 Verification of the hydraulic connections POSTIIVE NEGATIVE Verification the conformity of the entrance and exit of the cold and hot feeding With the arrows on the connections to the unit and as shown in the installation manual of the unit Verification that the feeding tubes are fitted with hand valves outside the unit Verification that the condensing discharge tube does not have valves or counterpendences p Verification that the feeding water hardness is between 10 and 40 French degrees Verification that the connections for the feeding of the humidifier connected to the sanitary water Verification that the cond
3. This system allows a modulation of the cooling capacity between 5 and 100 of the nominal one therefore also with a great reduction of the absorbed power at the same time The injection valves opening is controlled by the microprocessor by a 0 10V signal proportional to the percentage shift of the sensed temperature to the set point one in relationship the proportional band The expansion valve is controlled by the over heating of the refrigeration gas exiting the evaporator r gt Handbook code 75802206A 0204 TECNAIR LB Sheet 15 of 82 CONTROL ERS microprocessor activates the first compressor the injection one when the room temperature equals the set point plus 50 of the proportional band For example if the proportionate band is of 2 C and the set point is of 20 the first compressor starts when the room temperature feeler measures a 21 temperature ref figure 3 In case of a single compressor will startup at 10096 of the proportionate band If the room temperature is above 50 of the proportional band the microprocessor will also start the second compressor if present This being without regulations will always work at 100 of its capacity whilst the first compressor modulates itself as seen above to ensure a perfect temperature regulation 2 6 AIR CONDITIONERS WITH CHILLED WATER COIL OWA STANDARS FOR BOTH OHU AND OWU SERIES The hydraulic circuits of the chill
4. units come with The present manual for the unit description installation and maintenance The installed Microprocessor manual pCO for the start up operating parameter modification and the unit control operations Wiring diagram Manufacturers conformity and testing declarations Instruction for moving and lifting the unit sticked out of the packing r gt Handbook code 75802206A 0204 TECNAIR LB Sheet 11 of 82 CONTROL CUPREHTICHS ERS 2 COMPONENTS DESCRIPTION AND OPERATION 2 1 MICROPROCESSOR ADJUSTMENT All the air conditioners are equipped with microprocessor which controls the temperature humidity air flow and overpressure depression in the controlled room with regard to the surrounding environment All working parameters can be modified directly by the Customer through the user interface Moreover the air conditioner can be remote controlled Installed on the unit Remote display for wall installation Figure 2 describes the functions and other components supported by the micro pCO2 Functions Temperature control YES Humidity control OH YES OW ACCESS Stand by YES Remote control ACCESSORY Supported components 3 points valves YES Modulating valves YES 2 compressors YES 2 step heater YES 3 step heater YES Modulating heater YES Modulating humidifier YES Inverter on one compressor YES Invert
5. 2 13 HEAT RECOVERY SECTION Only for OH HR series air conditioners The heat recovery system is based on heat exchange between the fresh air and the return one from the environment to control The heat transfer between the two coils in the red circle of Figure 7 occurs through an appropriate circulation pump and expansion tank and uses water as exchange fluid According to the current heating cooling condition setting the system gives or takes heat from the air being supplied to the unit We suggest mixing glycole with the water charge in the heat recovery circuit to prevent it from freezing during winter functioning Exaustair External air suction Supply air T Suction from controlled room Figure 7 Heat recovery system r7 Handbook code 75802206A 0204 TECNAIR LB Sheet 26 of 82 CATRO OMT ERS The functioning of the heat recovery system depends on the value of temperatures outdoor air gt return air and supply SUMMER FUNCTIONING The condition outdoor airl gt supply air is normally verified If the condition outdoor T gt return is verified too where A is a parameter that can be set from 2 through 5 the water circulation pump is working and cools the incoming fresh air down freely WINTER FUNCTIONING The condition outdoor lt supply is normally verified If the condition outdoor lt return T A is also verified the wate
6. MECHANICAL BREAKAGE DISCHARGED DEFECTUOUS LOW AIR FLOW IN COOLING CIRCUIT THERMOSTATIC THE EVAPORATOR CONDENSATION PRESSURE SEARCH THE REPLACE THE CHECK THE LEAKAGE THEN BELLOW CONDENSATION RESTORE CONTROL SYSTEM DISCONNECT THE COMPRESSOR AND REPLACE CLEAN AIR CHECK THE AIR CHECK FAN FILTERS CIRCUIT THEN SETTING RESTORE THE ORIGINAL CONDITIONS r gt Handbook code 75802206A 0204 TECNAIR LB Sheet 74 ot 82 ABE CTIMEHTICH ERS CONTR 8 2 U AIR CONDITIONERS HYDRAULIC CIRCUIT PROBLEMS AIR IN THE CIRCUIT CHECK AND ELIMINATE THE AIR IN THE CIRCUIT c 2 TECNAIR LB CHECK THE ELECTRONIC CARD NON COOLING NON OPENING THE THREE WAY TOO HIGH WATER TEMPERATURE AT THE EVAPORATOR OUTLET CHECK THE CHILLER AND BRING THE TEMPERATURE BACK TO DESIGN CONDITIONS CHECK THE SERVOMOTOR GOOD FUNCTIONING Handbook code 75802206A 0204 VALVE CHECK THE OPENING SYSTEM FOR MECHANICAL BLOCKS Sheet 75 of 82 8 3 HEATING SECTION PROBLEMS HEATING HOT GAS REHEATIN G NON REHEATING NON HEATING NON FUNCTIONING OF THE SERVOCONTRO MAGNETOTHERMIC THERMOSTATIC SWITCH SWITCH INTERVENTION INTERVENTION CHECK FEEDING AND MODULATING SIGNAL SHORT CIRCUITOR i HIGH TOO LOW VALVE NON EARTH HEATER Pd TEMPERATURE H WATER H OPENING Pd DUE TOLOW i TEMPERATURE AIRFLOW CHECK SERVOCONTROL FUNCTIONING DISCO
7. Mainly in case of presence of a double floor the use of the Water alarm option is recommended so to have the possibility to close two solenoid valves installed on the hydraulic pipes and avoid room flooding due to an emergency or a break down of any component of the installation Otherwise the installation of two manual shut off valves in a very accessible position is mandatory 3 7 HYDRAULIC CONNECTIONS COLD OR HOT WATER COILS As for the units fitted with chilled water coil U as the third character or with an hot water one you shall also need to connect the feeding lines with them The tubes diameter is indicated in the technical documentation the inlet and outlet conenctions are shown on both the following drawing documentation and the appropriate self sticking labels on the connections themselves valvola 3 vie threway valve uscita acqua water outlet Ingresso acqua T E water inlet 8 attacco femmina pollice gas female connection gas Handbook code 75802206A 0204 Sheet 33 of 82 TECNAIR LB Mainly in case of presence of a double floor the use of the Water alarm option is recommended so to have the possibility to close two solenoid valves installed on the hydraulic pipes and avoid room flooding due to an emergency or a break down of any component of the installation Otherwise the installation of two manual shut off valves in a very accessible position is mandatory 3 8
8. aria la camera o Filtre FT tierna Filtre 4 di mandata Ripresa aria dalla camera bianca Filtra Ga Figure 7 clean room air conditioners r7 Handbook code 75802206A 0204 TECNAIR LB Sheet 20 of 82 CATRO OTC ERS 2 11 CONTROLLING THE AIRFLOW QUANTITY TO THE ROOM 2 11 1 Surgical room air conditioners OH series The regulation of the airflow is entrusted through the microprocessor to an inverter that controls the number of revolutions of the air discharge fan based on two parameters set airflow and filter clogging level The required airflow can be set directly in the manufacturer branch see use handbook of the pCO microprocessor from a minimum to a maximum as a function of the air conditioner model in question When shipping the unit the airflow is pre set at the corresponding rating requested by the Customer To guarantee the requested air flow the microprocessor uses a calculation algorithm based on the pressure difference between the propeller of the air discharge fan and a given dead point before it in which the air have speed almost at zero Based on the pressure difference and on the type of the fan the microprocessor calculates the current air flow and corrects it as necessary sending a tension signal 4 20 mA to the inverter The inverter receives the signal from the microprocessor and varies the feeding frequency of the air discharge fan in order to increase or
9. press the Enter key This writes the new value to memory The Program Mode Indicator will stop flashing and the display will flash once indicating that the new value has been accepted If at any time while in the program mode you wish to abort the editing process press the ESCape key The original value of the parameter will remain unchanged and you will be exited from the Program mode NOTE In addition power must be cycled or P56 Reset Function must be set to 2 for the change to take effect If you reset to factory defaults you cannot use the Program Keypad Module for start or reverse control until it is selected using P46 setting 2 7 1 5 DISPLAY GROUP PARAMETERS READ ONLY This group of parameters consists of commonly viewed drive operating conditions such as output frequency output voltage output current and frequency command All parameters in this group are read only The last user selected Display Group parameter is saved when power is removed and is displayed by default when power is reapplied Par Parameter name Description Min Max Units 01 Output Frequency Displays the output frequency at TB2 terminals U V amp W T2 amp T3 0 0 240 0 Hz 02 Output Voltage Displays the output voltage present at TB2 terminals U V amp W T1 T2 amp T3 0 Max Voltage 03 Output Current Displays the output current present at TB2 terminals U V amp W T2 am
10. CHEE CONTROL ERS valve at 80 then the microprocessor regulates it in proportional way so to get a modulating dehumidification 2 16 DIFFERENTIAL PRESSURE SWITCHES FOR CLOGGED FILTER INDICATION The air conditioners produced by Tecnair LB are all equipped with differential pressure switches for measuring the pressure difference before and after the suction discharge and return filter The microprocessor gives a signal when the pressure difference exceeds the set value see Table 8 This type of alarm does not stop the unit as it only has a signalling function The calibration of the clogged filter pressure switches is normally executed by the Manufacturer during the testing In any case the values of intervention of each pressure switch can certainly be calibrated according to the requirements of the Customer according to whether this one wishes the filter clogging signalling to be more or less timely To change the intervention pressure value of a pressure switch just unscrew the cover and turn the wheel toward the pressure drop value desired TYPE OF FILTER POSITION VALUE Pa Filter G4 Air suction 180 Filter G4 Air return 180 Filter F9 Air discharge 450 Figure 11 summarises the default calibrations executed during the unit testing at Tecnair s 2 17 SOUND ABSORBERS The high LWS sound power level of the electro fans makes the installation of sound absorbers mandatory at least in the s
11. CYLINDER CYLINDER DUE DISCHARGING DISCHARGIN ERMIC CYLINDER MAGNETOTHERMIC TO LOW WATER VALVE DISC G VALVE DISC SWITCH SWITCH CONDUCTIVITY INTERVENTIO INTERVENTION MANUALLY DISCONNECT AND DISCHARGE AND REPLACE THE RESTORE THE CYLINDER MAGNETOTHERMIC SWITCH MANUALLY MANUALLY PUT SALT IN THE CLEAN SOLENOID DISCHARGE AND DISCHARGE THE FILLING BAC AND FILLING BAC RESTORE THE CYLINDER MAGNETOTHERMIC SWITCH CHECK WATER CLEAN FILTER AND CLEAN SOLENOID TAPS WATER AND DISCHARGING DISCHARGING VALVE VALVE VERY SMALL DISCONNECT AND DISCHARGING REPLACE THE PIPELINE PIPELINE THE WATER RUN OVER THE BAC CLEAN AND CLOGGED AND COUNTERINCLINED ELIMINATE THE DISCHARGING COUNTER PIPELINE 1 INCLINATION r gt Handbook code 75802206A 0204 TECNAIR LB Sheet 78 of 82 AB COREHTICHS ERS 8 5 DEHUMIDIFICATION PROBLEMS NON DEHUMIDIFICATIO N DIRECT EXPANS THE COMPRESSOR DOESN T START UP HIGH WATER FLOW HIGH WATER TEMPERATURE THE VALVE DOESN T OPEN AIRFLOW BRING BACK TO CHECK FEEDING ON CHECK DESIGN THE HUMIDIFIER S SERVOMOTOR CONDITIONS ELECTRONIC CARD FUNCTIONING CHECK THE BRING BACK TO CONSENTS ON THE DESIGN ELECTRONIC CARD CONDITIONS ELIMINATE POSSIBLE MECHANICAL BLOCKS IN THE CLOSING SYSTEM r gt Handbook code 75802206A 0204 TECNAIR LB Sheet 79 of 82 AB COREHTICHS ERS CONTR THE
12. FAULT INFORMATION Keypad Module Fault Display Figure 33 Ready Fault Indicating Panel L r TECNAIR LB PTHQTRCN ABE OF METH ERS Handbook code 75802206A 0204 Sheet 69 of 82 When fault occurs the cause must be corrected before the fault be cleared After corrective action has been taken any of the following actions will clear the fault Press the Program Keypad Module s Stop button Disconnect power to the drive wait one minute reapply power Cycle the input signal at TB3 8 to the drive Set P54 Clear Fault to 1 Included is a list and description of drive faults and problems that may occur Fault num Fault name Fault description Corrective action The DC Bus voltage remains below 85 nominal Monitor the incoming AC line for low voltage or line 03 Power Loss Fault power up for longer than 5 seconds power interruptions The DC Bus voltage fell below the minimum rated voltage For 200 240V AC input drives the under voltage trip occurs at a bus voltage of 210VDC Monitor the incoming AC line for low voltage or line 04 UnderVoltage Fault equiv alent to a 150VAC incoming line voltage For Power 380 460V AC rated drives the undervoltage trip interruptions occurs at a bus voltage of 390VDC equivalent to a 275 incoming line voltage The maximum DC Bus voltage has been exceeded For 200 240
13. HYDRAULIC CONNECTIONS STEAM HUMIDIFIER The humidifier shall be feeded with tap water as indicated in par 2 14 through the relevant conenction in its bottom part The sole connection to be made is the feding one as indicated in the following drawing with arubebr pipe whose diameter is indicated in the order confirmation The discharge connection is already carried ouside the unit by Tecnair uscita vapore Tecnair steam supply Tecnair 0 umidificatore humidifie 8 uscita acqua water discarge Tecnair o entrata acqua tubo interno 6mm linstallatore water inlet connection to be made by the installer with a tube internal 96mm 3 9 CONNECTIONS THE NETWORK STEAM DISTRIBUTOR The Condair steam flow regulator must be connected to the sterile network through stainless steel tubes from the relevant hole in its upper part as indicated in the following drawing The distributor resists to a pressure of 5 Bar though it is selected for it to be feeded 2 Bar This is the sole connection to be made inside the unit because the discharge one is syphoned and carried outside from Tecnair The installation upstream of the steam distributor of a pressure reducer with manometer to guaranty that the feeding pressure is of two bars absolute is mandatory collegamento entrata v
14. SELect key enables editing of a parameter value when the Program mode is active When you press this key the Program Mode Indicator flashes Up Down Arrow Keys Use the Up Down Arrow keys to scroll through a list of parameters or increase and decrease parameter values Press and hold either key to increase scrolling speed Real time frequency adjustment can be achieved when using P58 Internal Frequency and P59 Frequency Select Refer to Chapter 5 for further information Enter Pressing this key causes the current value displayed to be entered into memory only while in the Program mode When you press this key the Program Mode Indicator remains on but stops flashing Direction LEDs Indicators The appropriate LED will illuminate continuously to indicate the commanded direction of rotation If the second LED is flashing the drive has been commanded to change direction but is still decelerating IMPORTANT Actual motor rotation could be different if motor leads are not connected properly Reverse Mode change direction c 2 TECNAIR LB Sheet 63 of 82 CATRO OTC ERS Handbook code 75802206A 0204 This function is only active when 46 Input Mode is set to 2 When active pressing this key causes the motor to ramp down to 0 Hz and then ramp up to its set speed in the opposite direction When the motor is running pressing this key causes the currently illuminated LED to flash indicating mot
15. a function of the size of the different units expressed by the coding numerical order r gt Handbook code 75802206A 0204 TECNAI R LB Sheet 38 of 82 CONTRO ABI C DRENCH ERS The table considers only two equivalent lengths for pipelines for a more accurate dimensioning you can certainly use the diagrams above which are generally valid se Ree Pipelines up to 15 equiv m Pipeline 15 to 30 equiv m ome Ue Buen 21 2 6 12 14 10 12 16 18 14 16 10 12 20 22 __ M 3 14 16 10 12 20 22 16 18 10 12 20 22 S m 2625 2 qe 2528 n esm 168 102 2628 2022 146 3335 amp 75m 25 202 vane 2628 2628 rane 3335 am zaon 230 22022 241416 2 33 35 2 2628 216 28395 ag 2 2h 246 22528 2 2022 2 3335 20628 22022 2533 38 32 25 245 22528 22022 233135 20628 22002 2439 42 Figure 17 Inside outside diameters of cooling lines Indeed the columns relating to equivalent length up to 30m are true for longer sections as well however where this is possible we suggest to lay the unit out in such a way as to not have any excessive lengths resulting in a considerable flow resistance and consequent reduction of the exchanged cooling capacity NOTE in case of heat pump units the frigorific lines to be selected are the liquid and the suction ones Line
16. air cooled condenser fan panel and is allowing a constant condensing pressure also during night and winter In case the air conditioner is supplied without the relevant condenser the revolution number variator for the condenser can be ordered as accessory and installed inside the electric panel The device is already factory set but should you need to change it due to a blink or only to reset it internally the cover a setting screw is provided Turn this screw anti clock wise to increase the fan revolution number reduce the condensing pressure turn it clock wise to reduce the revolution number and consequently increase the condensing pressure On the modulating pressure switch on the liquid line sending the transformer the signal proportional to the condensation pressure there is a screw Turn this screw clockwise anticlock wise to decrease increase the pressure in the circuit 4 2 4 Sucked gas overheating control Gas leaving the evaporator and arriving to the compressor is at the evaporating pressure but overheated For a good operating of the frigorific circuit the difference between sucked gas temperature and the temperature corresponding to the evaporating pressure must be around 4 7 C this difference is called overheating If overheating is more than 7 C it means that Thermostatic valve is too close or defective To open the thermostatic valve you have to remove the cap placed on the lower part of the valve then rotate ant
17. and the directly proportional cooling capacity of the air conditioner The cooling capacity regulation through inverter on the compressor is only used on heat pump air conditioners The inverter is controlled by the microprocessor with a OVdc 10 Vdc signal The inverter therefore varies continuously the feeding frequency of the compressor between the minimum value 30 Hz equal OVdc and maximum value 60 HZ equal 10 Vdc allowed The maximum and minimum frequencies are indicated by the compressors Manufacturer Particualrly the minimum frequency cannot be lower than 30 Hz So to avoid gripping the compressor due to insufficient oil return because of the too low refrigerant speed in the pipes The microprocessor starts the first compressor the one equipped with the inverter when the room temperature equals the set point plus 5096 of the proportional band For example if the proportional band is 2 and the set point is 20 then the first compressor will start up when the feeler in the room senses 21 cfr Figure 3 gt Handbook code 75802206A 0204 TECNAIR LB Sheet 14 of 82 CONTROL CTIMEHTI HA ERS If the total capacity of the first compressor is enough to work off the room heat the microprocessor will decrease the output signal to the inverter and therefore the inverter will adjust down to the minimum frequency set point If the room temperature equals the set point plus 10096 of the proportional band the micropro
18. any interruption or connection The magnetotermic switch mandatory to protect the feeding line against overcurrents according to the European Rules par 7 2 1 and 7 2 6 CEI EN 60204 1 must be placed by the Installer as close as possible to the unit The magnetotermic switch shall have a differential block from 30 to 300 mA to assure in addition to the magnetotermic protection the operators protection against direct or indirect contacts too The differential bock protects the of the air conditioner against insulation faults too The earthling shall be made using a cable with section as indicated in the wiring diagram To prevent the microprocessor from suffering any working problem no utility not even if it is part of the plant itself such as pumps condensers etc shall be connected after the external magnetotermic differential switch of the air conditioner this is indispensable suitable anti interference devices C shall be parallel connected with the relay coils of such utilities 3 5 HYDRAULIC CONNECTIONS CONDENSATE DISCHARGE All air conditioners with either direct expansion or chilled water coil need the waste pipe to be connected with the central water trap which canalises the condensate from the direct expansion coil The humidifier waste water discharge tube shall be connected too The connections must be made on the relevant fittings on the lower part of the right hand side panel The connections al
19. by an anti freeze thermostat by which it is possible to guaranty a raise in the temperature of at least four degrees so to reduce the humidity and avoid the risk of freezing the humidity which accumulates in the pre filter We suggest that this system is made with plain tubes because the possible fins are dirtied too quickly by the fresh air which in that point is not yet filtered We empathise that for temperatures lower than 20 C the possibility to install the air conditioner externally is excluded Units without heat recovery system temperature minimum 22 C maximum 38 C humidity lower 10 maximum 100 Units with heat recovery system temperature minimum 40 maximum 48 humidity lower 1096 maximum 100 1 6 2 Direct expansion air conditioners W series R407C 1 6 2 1 Internal unit operating limits the indicated temperature and humidity limits of the treated air external air mixture plus re circulation entering into the unit are valid for operating after the first transitory span with nominal air flow and a prevalence of 800 pa For lower air flow up to 10 the mentioned limits must be raised by one degree centigrade so to avoid too low evaporating temperatures We empathise that for external winter temperatures regularly lower than 5 it is necessary to install in the fresh air duct a system for the pre heating of the fresh air controlled by an anti freeze thermostat by which it is po
20. care and cost hepa filters by each vent or air diffuser to the room The cleaning operations relating to the air conditioners series H used for conditioning operating theatres shall be executed by personnel previously and duly trained to this end by the hospital s maintenance service in order to prevent the air conditioners themselves from being contaminated by proliferations of bacteria Only in this way the health of the cleaning operators medical staff and of the patients entering in the rooms conditioned by these units in the future will be protected 5 2 OUTFIT TO USE FOR EXECUTING CLEANING OPERATIONS Unless otherwise specified by the physician in charge of the surgical room the personnel entrusted with the cleaning operations should wear the clothes listed below in order to both protect their health and safeguard the result of the operations they carry out on the unit r7 Handbook code 75802206A 0204 TECNAIR LB Sheet 54 of 82 CONTROL ERS A clean overall Protection goggles Latex gloves during cleaning and disinfections operations on the operating compartment the gloves shall be replaced as soon as they get dirty Antiseptic half mask respirator Top footwear Once the cleaning operations have been terminated all the clothes used for these activities shall be disposed of as contaminated waste with the exception of the overall which may be re used after appropriate washing and disinf
21. conductivity and hardness REMARK We suggest treating water with hardness exceeding 30 fH even if lower than 40 fH The maximum softening allowed is 40 of the initial hardness value For example if you start from hardness of 50 fH do not exceed 30 in this case 40 of the initial value equals 20 fH If water conductivity is higher than 1250 5 we suggest treating water appropriately and taking it back to the limits allowed The two cases with grey background refer to conditions that occur very rarely as they concern water very rich in scale and poor in the other dissolved salts Figure 10 r gt Handbook code 75802206A 0204 TECNAIR LB Sheet 28 of 82 CONTROL ERS 2 14 2 Condair ESCO steam distributor The microprocessor controls the humidification by controlling the servomotor of a valve through a 0 10Volt signal Based on the signal from the microprocessor the servomotor opens or closes the valve in proportion to the deviation of the ambient humidity value with respect to the set point For example if the band is 10 and the set point is 50 then the valve will close completely at 5096 while it will is completely opened at 40 Figure 11 illustrates the above said A top humidity humidostat located in the fan compartment and connected with a solenoid valve placed before the steam distribution regulator makes sure that the steam flow to the room is promptly stoppe
22. differential pressure transducer installed in the room As a function of the current value sensed the microprocessor increases or decreases the output tension signal to the inverter so as to vary the frequency of the fan until the pressure difference between the room and the reference environment falls again within the 0 5 Pa from set point The regulation with depression set point follows the same principle unless on starting the unit up the microprocessor forces a 10Volt tension to the inverter which corresponds to the maximum revolving frequency 2 12 2 CONTROL OF THE CAPACITY WITH THE CONSTANT PRESSURE METHOD As an alternative to the control method of constant air capacity to the controlled room described above the same air can be controlled by maintaining a constant pressure inside the supply ducts This system is mandatory if one single unit must feed more than one room The ducts infact are normally intersected by motorised dampers which are closed partially night stand by or totally sterilization in case of non operability of the room itself To do this type of regulation Tecnair LB provides a differential pressure stat with the unit 0 1000 pa which is installed by the installer in the air supply duct towards the rooms closer to the unit and anyway after the F9 filter and before each connection to the different rooms The pressure stat is wired electrically to the electric panel s relative clamps as indicated in
23. filter on the fresh air suction it is possible to install a F9 filter On the air discharge towards the controlled room it is possible to install a F9 filter 2 10 2 Surgical room air conditioners without heat recovery OH The fans and filters are located as shown in Fig 5 When a partial recircultion is requested the by pass damper accessory allows mixing the return air from the environment to the fresh one The opening of the damper in opposed to the fresh one and is controlled by the microprocessor r gt Handbook code 75802206A 0204 TECNAIR LB Sheet 19 of 82 DUAE CONTRO OMT ERS Supply alr ta Exaus air controlled room _ FF filter Exaust fan G4 filter fram controlled Hecirculatian damper Supply air fan External air Suction G4 Alter Cooling coil Figure 5 surgical room air conditioners without heat recovery Alternative filters In alternative to the G4 filter on the fresh air suction it is possible to install a F5 or an F7 filter On the air discharge towards the controlled room it is possible to install a F9 or an H12 filter In case of an H12 the maximum capacity will be a bit smaller 2 10 3 Clean room air conditioners OW The fresh air opening is always placed on the top panel whilst the one for recalculating the air can be above on the front the back or on the left hand side of the unit Mandat aria waaro
24. hours as a function of the hardness and conductivity of the feeding water For a correct functioning of the humidifiers we recommend the following Always supply city water with a mechanical filter 50 um Never use demineralised water The conductivity of the feeding water to the humidifier shall be 125 to 1250 uS cm The hardness of the feeding water to the humidifier shall be 15 to 40 F D D D O With harder water use NO water softener but a de scale r gt Handbook code 75802206A 0204 TECNAIR LB Sheet 27 of 82 CONTROL CTIMEHTI HA ERS The frequency of cylinder replacement is direct proportion to the water hardness because of the increase in scale therefore we suggest monitoring constantly the condition of the cylinders and make sure that all the operations described in chapter Houtine maintenance are executed The following table provides a merely QUALITATIVE description of what may happen when the water conductivity and hardness are not within the recommended limits CONDUCTIVITY uS cm HARDNESS H 350 350 800 800 1250 Water subject to softening 15 Probable foaming Strong problems with Slow in gaining speed corrosion jump sparks foam corrosion and jump spark Foaming problems 15540 OPTIMUM CONDITION probably treated water and corrosion problems Many scales gt 40 Probable foaming Figure 8 behaviour of the humidifier based on the water
25. power must be 0 cycled or P56 must set to 2 for the change to take effect 47 Output Configure Determinestheon offpointforthe TB3 0 10 0 9 Determinestheon offpointforthe TB3outputrelaywhen P47 is set to 6 7 8 and 48 OutputThreshold 10 0 815 0 0 Settings 6 from 0 to 240 Hz 7 0 180 8 0 815 Volt 10 0 180 49 PWM Frequency Carrier frequency for the PWM output waveform 2 0 8 0 kHz 4 0 kHz 4 0 Maximum number of times the drive will attempt to reset fault i Faults 03 20 will automatically reset according to this parameter setting 02 51 RestartTime Time between restart attempts 0 0 300 0 10 seconds 10 0 seconds Enables disables external dynamic braking 07100 DB Enable This parameter cannot be programmed while the drive is running 53 Curve S Enables a fixed shape S Curve 0 10 0 0 Setting this parameter to 1 performs fault reset When the fault reset 54 Clear Fault S on 0 0 is complete the value is automatically set back to 0 This parameter cannot be programmed while the drive is running 55 Memory Probe Address Used by Rockwell Automation field service personnel Drive parameters and their associated defaults are reset according to the following descriptions 0 Idle State 56 Reset Functions 1 Reset defaults restores all parameter settings to factory defaults 0 2 0 0 2 Update Input Mode restores the drive to most recent programmed After the reset update function is c
26. the unit s wiring diagramwith a cable of belden type Of maximum length of 10 meters When this damper closes the pressure inside the duct raises The pressure stat informs the microprocessor that confronts it with the setpoint and adjusts the revolution speed with the fans inverter This system guaranties a good control of the capacity even if the number of rooms to be controlled varies and acts as a correction of the reduction of capacity due to the progressive dirtying of the filters upstream the measuring point the ones inside the unit It is not anyway able to control the dirtying of the filters downstream the measuring point It is therefore necessary that the filters upstream the measuring point are maintained in an optimum state so that the dirtying of the absolute filter is slower and gradual in time With this system there is no direct control of the capacity the parameter which we must control but indirectly by the pressure in the supply ducts which is proportional to the capacity r gt Handbook code 75802206A 0204 TECNAIR LB Sheet 23 of 82 CONTROL ERS The regulating system for the installation is therefore bit more complicated because of this need to act indirectly It is therefore suggested to proceed as follows Hypotise a loss of capacity for the system downstream the unit with all the units operating and with clean filters nsert as pressure set point this value Verify room
27. to consult this manual for further details 7 1 2 GENERALITIES L inverter 160 SSC can be controlled by Program Keypad Module DeviceNet Communication Module RS 232 Communication Module For proper applications Tecnair uses the programming keyboard with which it is possible to visualise and modify the units parameters The Program Keypad Module provides the following features 6 digit 7 segment LED display Nine keys for programming QUI sui Two directional LED indicators Moon con 3 T2 ri inia con De VERTS 1 Bienen course Duncan kar Bitten d ripunan bapa PTS TE ES 1 Modum con mahari eget rh DOC Figure 29 frontal view of the inverter ar ail d Handbook code 75802206A 0204 TECNAIR LB Sheet 62 of 82 K Li SIB OOREHTICH ERS kal 3 gui D Figure 30 Program Keypad Module Parameter Number Display Indicates which Display or Program Group parameter is active Program Mode Flashes when in program mode Parameter Value Fault Number Displays the parameter value or fault code number Escape The ESCape key allows you to toggle between the Display and Program modes When the Program mode is active this key will disable the editing of a parameter Select The
28. torque at low frequency Settings 9 12 are used to reduce 12 2 12 energy consumption 39 Skip Frequency Works in conjunction with P40 creating a range of frequencies at which the 0 240 Hz 240 Hz 240 drive will not operate continuously Determines the band around the P39 parameter The actual band width will be 2 40 Skip Frequency Band times P40 1 2 the band above and 1 2 the band below A value of zero will 0 30 Hz 0 Hz 0 disable the skip frequency 4 Bulletin 160 provides Class 10 overload protection Settings 0 2 select the otor Overload Select derating factor for the I 2 t overload function Set to motor nameplate Full Load Amps FLA ricalcolare assorbimento del 42 Motor Overload Current Motore alla frequenza massima impostata 0 1 200 115 115 Valore impostato in percentuale della corrente nominale di uscita dell inverter 43 Current Limit Maximum output current allowed before current limiting occurs Value set in 1 180 150 150 percent of drive rated output current 44 DC Hold Time The time that P45 will be applied to the motor when P34 is set to 0 2 0 3 4 0 0 seconds 0 45 DC Hold Voltage Voltage level applied to the motor during braking when P34 is set to 0 2 o 0 115 V 0 0 Configures the TB3 control inputs for various 3 wire or 2 wire control schemes Also enables disables the Program Keypad Module This parameter is Input Mode cannot be programmed while the drive is running In addition
29. use of the apparatus Whenever any operation that may give rise to the propagation of pathogenic microorganisms is executed in the surgical room Before washing and cleaning the unit it is absolutely necessary to empty the pre heating if any as otherwise the efficacy of the washing of the chilled water coil would be very low To empty the coil you need to close the manual valves on the hot water input and output ducts mounted on the framework of the unit by the installer The coil is connected with the ducts by appropriate vents So isolated from the water ducts the coil can be removed from the frame by unscrewing the 4 screws and sliding it on the special guide Now the coil can be washed and sterilised like all the other parts The washing and disinfections procedure is the following Make sure you have all the necessary material and spare filters Stop the unit and disconnect the electricity by turning the main shutter blocking switch off Put a notice on it saying that the unit is under maintenance Dismount and replace if necessary the pre filter on the outdoor air intake These filters can be disposed of as standard solid waste as they should not be subject to bacterial contamination Dismount and replace the filter after the shut off damper on the air return from the surgical room The dismounted filter shall be put into a hermetically sealed container and then disposed of following the same procedure as for the septic waste of the
30. 4 ELECTRICAL CONNECTIONS 3 5 HYDRAULIC CONNECTIONS CONDENSATE DISCHARGE 3 6 HYDRAULIC CONNEC TIONS WATER COOLED CONDENSERS 3 7 HYDRAULIC CONNECTIONS COLD OR HOT WATER COILS OO L lt O 2 Z O Z lt L lt GD oO CONNECTIONS TO THE NETWORK STEAM DISTRIBUTOR FRIGORIFIC CONNECTIONS LINES LAYOUT FOR FRIGORIFIC CONNECTIONS 3 12 LINES DIAMETERS FOR COOLING CONNECTIONS COMPLETING THE REFRIGERANT CHARGE SeT EATE ONENE OO O OS 3 15 INSTALLING THE DIFFERENTIAL PRESSURE SWITCH IN THE ENVIRONMENT MES o INSTALLING FOR THE AIR CONDITIONER REMOTE CONTROL INTERFACE P SEDA BEAN 7 5 5 5 5 NIN 3 18 DISASSEMBLE AND DISPOSAL Handbook code 75802206A 0204 TECNAIR LB Sheet 2 of 82 DUAE CONTRO 4 FIRST START UP 47 4 2 CONTROLS OF REFRIGERATION CIRCUIT OPERATION 49 5 3 DISPOSING THE WASTE MATERIALS USED FOR CLEANING OPERATIONS 55 MAINTENANCE HUMID R MAIN NAN 160 55 62 B TROUBLE ANALYSIS 72 1 8 2 U AIR CONDITIONERS HYDRAULIC CIRCUIT PROBLEMS 75 8 3 HEATING SECTION PROBLEMS L1 U L Lo DP OB 8 5 DEHUMIDIFICATION PROBLEMS 8 6 PROBLEMS Handbook code 75802206 0204 TECNAIR LB Sheet 3 of 82 17 4 Al MTC ERS 1 GENERAL INFORMATIONS 11 CE DECLARATION OF CONFORMITY The series H and W air conditioners that
31. 5802206A 0204 TECNAIR LB Sheet 10 of 82 CONTROL ERS We empathise that for external winter temperatures regularly lower than 5 it is necessary to install the fresh air duct a system for the preheating of the fresh air controlled by an anti freeze thermostat by which it is possible to guaranty a raise in the temperature of at least four degrees so to reduce the humidity and avoid the risk of freezing the humidity which accumulates in the pre filter We suggest that this system is made with plain tubes because the possible fins are dirtied too quickly by the fresh air which in that point is not yet filtered We empathise that for temperatures lower than 20 C the possibility to install the air conditioner externally is excluded Version L units low air flow temperature minimum 22 maximum 38 humidity lower 1096 maximum 100 Version H units high air flow temperature minimum 40 maximum 48 humidity lower 1096 maximum 100 1 7 SPARE PART LIST The spare part list available under request to our Commercial Offices emphasises the parts which don t have easy local reparability Static parts such as heat exchangers closing panels and others Rare faults are therefore not listed Universally retrievable parts such as electrical motors contactors automatic switches refrigerating gasses are also not listed 1 8 DOCUMENTS INCLUDED IN THE UNIT
32. 7 Run Forward Run Reverse 1 int Freq Select 0 8 Run Forward Run Reverse 1 0 9 Run Forward E Run Reverse 1 Sel freq int Status of Bit 3 for Input Mode 8 is TB3 2 is 0 Open 1 Closed 13 Power Factor Angle Displays the angle in electrical degrees between motor voltage and motor current 0 0 180 0 Degrees 14 nas Probe Used by Rockwell Automation field service personnel Numeric Value Displays the open 0 and closed 1 state of TB3 inputs SW1 SW2 and SW3 in binary coded format Bit 0 SW 1 15 Preset Status Bit 1 Sw 2 0000 0011 Bit 2 SW 3 1 Bit 3 Not used Displays the analog input as a percent of full scale Used in setting P60 Zero Offset P75 Analog Input Minimum and P76 Analog Input Maximum 16 Important On initial set up of the drive apply a OV or 4 mA analog command to 156071500 E 2 Analog Input the drive Once applied if the value of this parameter displays something other than 1500150 Zero program that value into P60 Zero Offset Please note that the value of Zero Offset will be subtracted from the value of this parameter 17 Fault Buffer 0 This parameter stores the last fault that occurred 0 48 18 Fault Buffer 1 This parameter stores the second most recent fault that occurred 0 48 19 Fault Buffer 2 This parameter stores the third most recent fault that occurred 0 48 1 Questo ingresso vale s
33. CAL COMPARTMENT containing the control systems and the compressors No air circulation occurs in this compartment so it normally doesn t require any disinfection Anyway every three r gt Handbook code 75802206A 0204 TE CNAIR LB Sheet 55 of 82 CICAE CATRO ERS month when washing disinfecting the operating compartments or any time it is opened for maintenance operations this compartment shall be cleaned following the specific procedure described in this handbook OPERATING COMPARTMENTS containing the parts in which the air treatment occurs This area is licked by both the outdoor air which is treated and then supplied to the surgical room and the air flow coming from the surgical room Despite the filtering systems adopted for the air suction return and distribution systems and the unit bacteria may nest in these parts of the air conditioner in the long run and proliferate during inactivity periods which would make the later use of the unit unsafe from a hygienic standpoint Such compartments shall be washed and disinfected according to the methods specified hereafter at least once a month and always in case of surgical operations involving a risk of propagation of harmful bacteria Anyway as the frequency and mode of use of the surgical rooms are various and different the responsibility of deciding about the need for a washing and disinfections of such compartments pertains exclusively to the Physician in c
34. E CIRCUITO AERAULICO E SENSO ROTAZIONE VENTILATORE VERIFICARE CONDIZIONI TESTARE BLOCCO VERIFICARE FUNZIONAMENTO AVVOLGIMENTO MECCANICO O TARTURA E LA ESPANSIONE SE LA MISURA GRIPPAGGIO FUNZIONALITA CONDENSAZIONE RISULTA FUORI DEL MECCANISMO CONTROLLARE LA CONTROLLARE EVENTUALMENTE TBSIONE DI CONTINUITA DEI SOSTITUIRE IL SOSTITUIRLO ALIMENTAZIONE SINGOLI COMPRESSORE AVVOLGIMENTI r gt Handbook code 75802206A 0204 TECNAIR LB Sheet 82 of 82 ATE COCTSEHTICHS ERS
35. Heat pump operation 10 HR Integrated heat recovery system Figure 1 example of unit coding reading 1 6 OPERATING LIMITS 1 6 1 Direct expansion air conditioners H series R407C 1 6 1 2 Unit operating limits The indicated temperature and humidity limits of the treated air external air mixture plus re circulation entering into the unit are valid for operating after the first transitory span with nominal air flow and a prevalence of 800 pa For lower air flow up to 10 the mentioned limits must be raised by one degree centigrade so to avoid too low evaporating temperatures We empathise that for external winter temperatures regularly lower than 5 C it is necessary to install in the fresh air duct a system for the pre heating of the fresh air controlled by an anti freeze thermostat by which it is possible to guaranty a raise in the temperature of at least four degrees so to reduce the humidity and avoid the risk of freezing the humidity which accumulates in the pre filter We suggest that this system is r gt Handbook code 75802206A 0204 TECNAIR LB Sheet 7 of 82 CONTROL CUPREHTICHS ERS made with plain tubes because the possible fins are dirtied too quickly by the fresh air which that point is not yet filtered We empathise that for temperatures lower than 20 C the possibility to install the air conditioner outdoor is excluded Units without heat recovery system version L low a
36. NNECT CHECK AND BRING AND REPLACE BACK TO DESIGN CONDITIONS CLEAR AIR CHECK AIR CIRCUIT CHECK FAN FILTERS AND BRING BACK TO CONNECTIONS AND DESIGN CONDITIONS FUNCTIONING CHECK CHECK FEEDING CHECK THE OPENING SERVOMOTOR AND MODULATING SYSTEM FOR FUNCTIONING SIGNAL MECHANICAL BLOCK r gt Handbook code 75802206A 0204 TECNAIR LB Sheet 76 of 82 TRC ATE CIIMEHTI CHN ERS 8 4 HUMIDIFIER PROBLEMS NON WATER CHARGING LACK OF TENSION FAILURE OF THE TOO CONDUCTIVE IN CHARGING CHARGING VALVE SOLENOID SOLENOID CHE CK THE DISCONNECT AND PROVIDE A HUMIDIFIER S REPLACE THE SOFTENER ELECTRONIC SOLENOID ACCORDING TO CARD THE ACCEPTED VALUES CHECK THE CONTACTOR S CONSENT PRESENCE OF POLYPHOSPHATE MEASURING DEVICES CHECK WATER CLEAN PRESSURE CLEAN WATER ELIMINATE TAPS REDUCER AT CHARGING VALVE MEASURING CHARGING VALVE FILTER DEVICES OUTLET MAGNETOTHERMI LOW WATER C SWITCH CONDUCTIVITY INTERVENTION MANUALLY DISCHARGE AND RESTORE NON WATER DISCHARGE DEFECTIVE LACK OF TENSION DISCHARGING i IN DISCHARGING VALVE SOLENOID H SOLENOID DISCONNECT THE CHECK THE SOLENOID AND HUMIDIFIER S REPLACE IT ELECTRONIC CARD c 2 TECNAIR LB CONTR Handbook code 75802206A 0204 Sheet 77 of 82 CONTINUOUS LACK OF BOIL WATER DISCHARGE TOO FULL FOAM IN THE TOO FULL OPEN OPEN MAGNETOTH RUN DOWN CYLINDER DUE TO
37. Ow Clean Room units the supply fan comes standard with inverter so to guaranty a very constant airflow In the same way the expulsion fan has its own standard inverter so to control the rooms over and under pressure only in OH series The inverter is controlled by the standard microprocessor pco under the information of a differential pressostat applied internally the unit between the fan propeller and an area upstream of it where the airflow speed is close to zero When the microprocessor feels the pressure difference between the two points is different from the one it calculates on the basis of the required air capacity it intervenes on the fan speed so to correct all anomalies For further information about the inverter refer to chapter 7 gt Handbook code 75802206A 0204 TECNAIR LB Sheet 18 of 82 CONTROL ERS For both series OH and OW units the fans internal to the front panels are protected by a safety grille for the safety of the operator 2 10 AIR FILTRATION 2 10 1 Surgical room air conditioners with heat recovery system OH HR The fans and the filters are located as shown in fig 4 External alr Supply alr to Exausl air suction centalled mem tar Exausi fan GA filter Supply Fan Section air from coetredlad mom V coll for recovery 2 Cueling call Figure 4 surgical rooms air conditioner with heat recovery Alternative filters In alternative to the G4
38. RMOSTATIC VALVE FUNCTIONING DIRECT EXPANS TOO LOW EXPANSION TEMPERATURE CHECK BLOCKED FAN CHECK THE COOLING CIRCUIT FOR RUN DOWN STATE c 2 TECNAIR LB EXCESSIVE DEHUMIDIFICATION TOO LOW AIRFLOW CHECK THERMAL FAN PROTECTION INTERVENTION CHECK ELECTRIC FAN CONNECTION CHECK FOR TOO LOW CONDENSING PRESSURE TOO LOW EXPANSION TEMPERATURE CLEAN THE FILTERS CHECK THE AIR CIRCUIT BRING BACK TO DESIGN CONDITIONS Handbook code 75802206A 0204 Sheet 80 of 82 8 66 FAN PROBLEMS LACK OF AIRFLOW THERMAL PROTECTION INTERVENTION DUE TO HIGH ABSORPTION FUNCTIONING WITH OPEN SHUTTERS THERMAL PROTECTION INTERVENTION CLOGGED FILTERS CLOSE THE CLEAN THE FILTERS SHUTTERS Yo LOW FEEDING TENSION HIGH AIRFLOW CHECK THE TENSION FOR GOOD REGULATION BY MEASURING IT REDUCE THE REDUCE THE SPEED BY THE SPEED BY SELECTOR IF MODIFYING THE PRESENT ELECTRIC PRESSURE IN THE CONNECTION c 2 TOO LOW HIGH AIR i AIRFLOW TEMPERATURE CREATE ADDITIONAL LOSSES OF AIR CIRCUIT Handbook code 75802206A 0204 TECNAIR LB Sheet 81 of 82 AB CTIMKIHTI HQ ERS PROTEZIONE TERMICA VENTILATORE BLOCCO DEL FLUSSOSTATO i ROTTURA AVVOLGIMENTO MECCANICA i MANCANZA ARIA IN E E CORTOCIRCUITO ELEVATO ASSORBIMENTO FUNZIONAMENTO MONOFASE VERIFICAR
39. V AC input drives the overvoltage trip Motor regeneration has caused a bus overvoltage 05 OverVoltage Fault occurs at a bus voltage of 400VDC For 380 460VAC Monitor the Incoming AC line for voltage input drives the overvoltage trip occurs at a bus Extend the decel time or install a dynamic brake voltage of 800VDC module or external capacitor module 06 Motor Stall Fault The motor has stalled due to an excessive motor load 07 Motor Overload Fault An internal electronic overload trip has occurred Reduce the motor load until the drive output current excessive motor load exists does not exceed the current set by P42 Reduce P38 Over Temperature s Clear blocked or dirty heat sink fins Check ambient a Fault Excessive hiat has been detected temperature Check for a blocked or non operating 11 Operator Fault The keypad has been removed while the drive is Clear the fault Do not remove the keypad under powered power An overcurrent has been detected the hardware trip Check for a short circuit at the drive output or for 12 Overcurrent Fault EA circuit excessive load conditions at the motor 13 Software Over Current Motor current exceeded value set in parameter 79 A longer acceleration time reduced oad or removal Fault of motor shaft blockage is required Clear blocked or dirty heat sink fins Check ambient 20 Drive Overload Fault An internal electronic overload trip has occurred The
40. a 6 pin plug the other one in the second card of the microprocessor MEDIUM CARD or CARD 2 placed inside the electric panel this connection is better explained on the user manual of the pCO microprocessor The connection cable r gt Handbook code 75802206A 0204 TECNAIR LB Sheet 43 of 82 CONTRO ABE COCHSENTICHS ERS is not provided by Tecnair At the two ends of the cable even the ferrite provided with the unit must be applied with the 2 terminal refer also to the PCO2 manual The second terminal can be either wall or panel mounted see figures 25 e 26 As to the panel installation the dimensions of the drilling jig shall be 167x108mm the maximum thickness of the panel shall be 6mm Conversely concerning the wall installation you shall need a mounting bracket and a 3 section standard wall box for the switches in order to allow the cables to pass In case the second interface for remote control is to be installed inside the surgical room it is warmly suggested to protect it from sterilisation effects putting it in an IP54 box with transparent front panel dima di foratura 187 108mm Figure 26 Wall mounting of the user interface 3 17 TEMPERATURE AND HUMIDITY FEELERS POSSIBLE POSITIONINGS The standard supplied feelers are always wall type Should you like to install them in a duct the specific ones must be requested The connection cable of coxial type is not provided by Tecnair 3 17 1 Surgical room air c
41. al will be equal to 0 V when the measured temperature will be of 20 it is equal 10V when the temperature is of 18 2 7 1 2 Electric heater heating capacity regulation The microprocessor sends a 0 10 Vdc tension signal to the electronic PWM regulator The tension value is directly proportional to the temperature shifts from the set point For example if the proportional band is 2 C and the set point is 20 C the microprocessor s exit tension value will be equal to is equal 10V if the room temperature reaches 18 2 7 1 3 Steam coil capacity regulation The regulations made by the three way modulating valve specific for steam and its functioning is identical to those for hot water We therefore must remember that steam coils can work until these conditions Entrance steam temperature 150 a Entrance steam pressure 6 Bar 2 7 1 4 Heat pump heating capacity regulation Functioning is identical reversed to the one for direct expansion cooling only that here the four way valve inserted in the circuit sends the refrigerant to condensate inside the units internal coil therefore giving to the air its condensing heat r gt Handbook code 75802206A 0204 TECNAIR LB Sheet 17 of 82 CONTROL CTIMEHTI HA ERS We evidence the fact that the condensing heat is overabundant for the treatment of all fresh air therefore in this case its necessary to provide the accessory for the regulation o
42. alternatively inside the surgical room or in the air return ducts the microprocessor shall start either the cooling or heating capacity Finally according to the humidity in the environment again sensed by the previously mentioned feeler the microprocessor shall start either the humidification or dehumidification 2 2 2 OW Series starting up Start up procedures are function of the installed components therefore after the supply fans start up the temperate and humidity feeler which is supplied loose and must be installed on the suction duct or in the controlled room automatically activates through the microprocessor the standard cooling and if present also the re heating and humdification r gt Handbook code 75802206A 0204 TECNAIR LB Sheet 13 of 82 CONTROL ERS 2 3 DIRECT EXPANSION AIR CONDITIONERS OWA The direct expansion coil air conditioners are all provided with two cooling circuits with the exception of models OHA 41 and 51 and OWA 41 and 51 which are mono circuit type The standard units have an ON OFF regulation of the cooling capacity therefore the pco microprocessor starts up the compressor with its proportional or proportional integral logic and stops it at the meeting of the set point This regulation is valid in case of units working with a small fresh air flow and high recircultion In case of 100 or high fresh air flow or of very rigorous temperature an humidity control th
43. apore attacco femmina pollice gasl a carico dell installatore steam inlet female connection gas to be made by the installer distributore vapore Condair Condair steam distributor 7 uscita condensa Tecnair condensate discharge Tecnair r gt Handbook code 75802206A 0204 TECNAIR LB Sheet 34 of 82 CHEE CONTROL ERS 3 10 FRIGORIFIC CONNECTIONS Type copper for diameters up to 26 28 hard drawn Gelidus type copper for larger diameters To prevent copper dust or off cuts from getting into the pipes they shall not be cut with an arm saw but only with a link pipe cutter then the pipe ends shall be thoroughly cleaned If the pipe ends need to be welded they shall be cleaned with a 00 type emery cloth in order to eliminate any possible trace of oxidation or dirt Afterwards the pipe shall be inserted into the joint and evenly heated until it reaches the stock melting point so that it may easily come into the joint to weld 3 10 1 Lines connecting a unit with a remote air or water cooled condenser DISCHARGE HOT GAS LINE It is located between the compressor output and the air condenser To make the connection easier inside the air conditioner a pipe section long approx 20 cm is connected with the compressor output cock that is pinched and then welded to the free end After having made sure that the compressor valve is close
44. are the object of this declaration shall be installed and used according to the terms provided for in this Installation and maintenance handbook which are supplied together with the unit UNDER THESE CONDITIONS ONLY Shall we the undersigned take full responsibility for declaring that the units making the object of the present Declaration comply with the provisions set forth in the following Directives 89 392 EEC 93 68 EEC 73 23 EEC 89 336 EEC Uboldo February 19th 2001 1 Concerning the air conditioners series W with remote condensing unit the Declaration of Conformity shall be valid only if the condensing unit is supplied by Tecnair LB together with the air conditioner If the air conditioner is supplied by Tecnair LB without condensaers unit the Manufacturer s Declaration of conformity shall be valid Tecnair LB r gt Handbook code 75802206A 0204 TECNAIR LB Sheet 4 of 82 CONTROL CTIMEHTI HA ERS 1 2 DECLARATION OF THE MANUFACTURER The series Hand W air conditioners that are the object of this Declaration shall be installed and used according to the terms provided for in this Installation and maintenance handbook which are supplied together with the unit UNDER THESE CONDITIONS ONLY Shall we the undersigned take full responsibility for declaring that the units making the object of the present declaration comply with the provisions set fort
45. ation too is described in the aforesaid drawing 3 2 UNIT ACCEPTANCE ON SITE Unless otherwise agreed upon specifically with the Customer TECNAIR LB delivers the units ex works standard packaged with a wooden pallet and a polyethylene protection sheet As the Carrier is always responsible for any damage the goods entrusted to him may suffer during the transport before signing the delivery slip for acceptance always check the packaging for integrity and the unit for possible visible damages of oil or refrigerant leakage If any evident damage is detected or if you have the slightest doubt that the air conditioner may have suffered some hidden damages during transportation you shall make your qualification to the carrier himself in writing and at the same time inform Tecnair LB s Sales Department as well If the unit does not need to be installed immediately after the arrival on site it shall be left in its original packaging and stored indoors in a non humid and heated if possible place having temperature 15 in winter If the storage extends for a long period the Customer shall ask Tecnair LB s Sales Department for the procedures for executing the necessary routing checks on the unit condition 3 3 CLEARANCE ANTIVIBRATION SUPPORT AND POSITIONING To prevent the unit from suffering any problem and damage during transportation we suggest taking the packaging off only when it has reached the place of installation Moreover it
46. aximum accepted pressure drop because an excessive diameter may lower too much the refrigerant speed which would result in bad oil entrainment ASPIRAZIONE R407c di pressions max consigliata 20 L TTIZ 1 1 f am Caduta di pressione per metra Potenzialit frigorifera kW Figure 14 diagram for suction pipeline dimensioning r gt Handbook code 75802206A 0204 TECNAIR LB Sheet 37 of 82 DE CONTRO OMT ERS LIQUIDO R407c Cait di pressone max consgiata 10 BOkP a e EF T B T M LL Set LE E EL Li mf e ll P ile sp Te bel pilli u 20 29 L prs aH j L Poo qe ammi Pi 1 0 1 4 7 i 7 1 10 100 1000 Potenzialit frigorifera kW Figure 15 diagram for refrigerant pipeline dimensioning MANDATA R407c dzkPa 100 H 10 Caduta di pressione per metro kP a m 1 10 100 1000 Potenzialita frigorifera kW Figure 16 diagram for discharge line dimensioning Anyway the following table can be use instead of the previously described method It illustrates the diameters suggested for discharge refrigerant and suction pipelines as
47. by room the reached air capacity the reached capacity is not the desired one raise for example of 30 Pa the pressure set point and continue regulating it until the desired capacity is reached 2 12 3 Controlling overpressure for OW series air conditioners Clean room air conditioners are built to make air conditioning in rooms where no dangerous substance is handled therefore they work and control only the overpressure of the controlled room in relationship to the external conditions According to the precision of the overpressure tolerance demanded its possible to use two different systems 2 12 3 1 Static control of the overpressure This is obtained by two manual dampers not provided by Tecnair placed one on the suction mouth of the air from the room and the other on the mouth of the fresh air suction During the start up of the conditioning installation the installer will measure through a differential pressostat the pressure difference between the controlled environment and another external reference one Therefore regulatates the two dampers raising the fresh air flow if the desired overpressure is not yet met and diminishing it in the opposite case With this system simple and useful in environments which don t have frequent changes in conditions such as doors and windows which open frequently the overpressure of nearly 15 Pa can be controlled with a tolerance of 8 10 Pa The overpressure level must be verified periodically s
48. cal lowering of the re circulated air flow so that the total capacity towards the controlled room is constant in r gt Handbook code 75802206A 0204 TECNAIR LB Sheet 25 of 82 CONTROL ERS time This is in fact necessary condition for a good control of the air quality within the controlled room To do this it is therefore necessary that the two motorized dampers are of identical sizes On the extracted air mouth a modulating motorized damper is installed dimensioned for 2596 of the total capacity of the unit On the air re circulation mouth where an air flow higher than the fresh one close to 75 90 of the total passes two parallel dampers are installed damper motorized and modulating is counter placed to the fresh air one and is identical to it for approximately the 2596 of the units air flow whilst a second damper is dimensioned at 75 and with manual regulation The two parallel dampers are placed on the re circulation mouth of the unit and are flanged together so that the installer can connect to them a single suction duct It is up to the installer to forward think of a manual damper for precision regulations in case the ducts the fresh air and the re circulated one have two different pressure drops i e direct re suction from the room and long duct for fresh air which would make a prevalent air flow of one of the two and therefore consequent difficulties in controlling the overpressure
49. cessor will start the second compressor up This one being without inverter works at its maximum whilst the other reduces its revolution speed as we have already seen to match the requested cooling capacity To assure the correct entrainment of the oil in the refrigerant under any working condition at fixed time intervals the microprocessor forces the compressor with inverter to top revolving speed for a fixed time The stay time and frequency at top speed can be set by the user cfr User handbook and depends on the corresponding duct length The microprocessor is default programmed to start the compressor at the maximum frequency for 5 minutes every 60 minutes 2 5 COOLING CAPACITY REGULATION WITH ELECTRONIC HOT GAS INJECTION The cooling capacity regulation is made by an electronic system always controlled by the pCO microprocessor of hot gas injection and refrigerant expansion see following drawing The hot gas injection downstream the expansion valve reduces the cooling capacity proportionately to the regulating demand whilst part of the refrigerant expansion in the relative valve allows the suction temperature not to become too high therefore compromising the good functioning of the compressor condensatore condenser lt valvola di espansione expansion valve compressore compressor valvola contrallo by pass bypass control valve evaporatore evaporator
50. charge line connecting the internal and the external units over the horizontal sections shall be tipped down by 2 at least in the refrigerant flow direction Ifthe discharge pipeline needs to rise over 3 meters a trap with the lowest bending radius shall be installed immediately before each rising section A counter trap as high as the highest part of the condensing coil shall be installed next to the condenser joint All pipelines shall be clamped every 2 metres The support fastening to the pipes shall be made so that no vibration is passed on and so as to allow the normal thermal expansion of the pipes due to temperature changes during the working charging valve shall be installed on both pipelines as close as possible to the external unit in order to allow discharging and charging the circuit Q The refrigerant input and output connections on the air condenser are identified by appropriate self adhesive labels In any case we point out that the heat exchange between air and refrigerant shall work in counter current This means that the gas refrigerant input connection in the condenser is the farthest from the air inlet to the coil that is the closest to the fans Vice versa the refrigerant liquid output connection from the condenser is the farthest from the fans REMARK The drawing below shows only the discharge pipeline as that of the liquid does not require any special precautions Fundenzs minima 186 C
51. cut it off Drain and remove the cylinder D DO D D Install the spare cylinder The worn cylinder shall be disposed of as described below Cut the plastic shell along its circumference using a hacksaw Unscrew the electrode nuts on the cylinder Remove the metal electrodes and separate them from the plastic crosspiece if any The plastic part of the cylinder is made of polypropylene and therefore it can be recycled completely the metal part is made of plate and therefore it can be recycled as ferrous material 6 2 FAN MAINTENANCE We recommend checking the fan fins for cleanliness on a regular basis and removing any dirt or fouling mark which may in the long run compromise the balancing the runner and damage the bearings Moreover we recommend checking the fan motor cooling fins for cleanliness If during the operation any anomalous noise is produced identify the defect stop the unit and solve the anomaly replacing the fan or the motor if necessary 6 4 COOLING CIRCUIT MAINTENANCE The cooling circuit does not need any maintenance operation but only periodical checks which shall be executed as indicated in chapter Starting the unit up starting from searching possible leakages shown by bobbles in the liquid flow indicator Check the condition of the cooling coil and clean it if necessary with hot water and soap by means of a brush with long and soft bristles Compressed air may be used as well provided that i
52. d the installer shall cut the pipe 5 cm before the welded end and welds the pipe that runs up to the air condenser The pipe diameter shall be selected as a function of the section of the connection to execute During its operation the pipeline reaches 70 80 C temperature as regards the good functioning of the unit this pipeline does not need to be thermally insulated as the loss of heat along this section is conducive to the good functioning of the cooling cycle Pipe insulation is required for safety reasons only where people may accidentally touch the pipeline or when this one runs under floor in direct contact with the conditioned air LIQUID RETURN LINE This pipeline connects the output of the condenser with the air conditioner input valve It is weld connected with the condenser and the unit input valve Its working temperature is approx 40 and does not require any thermal insulation but with conditioning units that need to work in winter as well at temperatures below zero IMPORTANT In case of installation with cooling lines longer than 10 meters with vertical sections and condenser installed in a higher position than the internal unit two non return valves or check valve shall be installed The fisrt one on the supply line of the refrigerant liquid as close as possible to the compressor outlet This serves to prevent the refrigerant from going back through the discharge pipeline up to the compressor due to the compressor
53. d in case of regulation failures DL Qm S c m zo See Figure 10 Regulation of the humidification with mains steam Steam limits Entrance steam temperature lt 152 C Entrance steam pressure lt 5 Bar 2 15 DEHUMIDIFICATION Standard on both Series OH and OW The dehumidification can be executed through 2 15 1 Compressorized Unit In this case the dehumidification start up the compressor with inverter if present This way the compressor provides all the cooling capacity necessary to take the air below the saturation curve and thus the drops of water are worked off so decreasing the humidity in the air If the compressor is equipped with inverter accessory the regulation of the dehumidification is modulating In this case the pCO starts up the frigorific circuit at 80 of it s capacity and then modulates 2 15 2 Chilled water unit The dehumidification is obtained by first opening at 80 the chilled water valve this valve is modulating type and is fed by a 0 10V signal from the microprocessor This way the water provides all the cooling capacity necessary to take the air below the extreme saturation curve and thus the drops of water are worked off so decreasing the humidity in the air The dehumidification is switched on by opening the r gt Handbook code 75802206A 0204 TECNAIR LB Sheet 29 of 82
54. decrease the air flow to the surgical room On starting the air conditioner up the microprocessor forces a tension value corresponding to the required airflow towards the inverter Every 10 seconds the microprocessor carries out a new reading of the pressostat and based on the current value it senses it increases or decreases the voltage signal to the inverter by a step corresponding to 1096 of the working span so as to keep the set value The progressive clogging of the three filters brings an airflow reduction To maintain the airflow to the surgical room at the set value the microprocessor increases the output signal to the inverter which in turn increases the revolutions of the fan 2 11 2 CONTROL OF THE CAPACITY TO THE CONTROLLED ROOM WITH THE CONSTANT PRESSURE METHOD IN THE SUCTION DUCT As an alternative to the control method of constant air capacity to the controlled room described above the same air can be controlled by maintaining a constant pressure inside the suction ducts This system is mandatory if one single unit must feed more than one room The ducts infact are normally intersected by motorised dampers which are closed partially night stand by or totally sterilization in case of non operability of the room itself To do this type of regulation Tecnair LB provides a differential pressure stat with the unit 0 500 pa which is installed by the installer in the air suction duct towards the rooms closer to the unit and a
55. during the normal operation of the unit and the analysis can be visualised on the display Cfr Use handbook However we suggest to perform chemical sampling analyses on a regular basis to make sure that the water conductivity and hardness values fall within the limits indicated above The member of the humidifier that require annual checks are the following Intake discharge solenoid valve remove solid scales if any use no compressed air Hydraulic circuit remove scales if any from the whole water route of the water intake valve to the steam production cylinder check it for leaks or dripping Q Steam supply duct check it for clogging along the route r gt Handbook code 75802206A 0204 TE CNAIR LB Sheet 60 of 82 CICAE CATRO ERS Humidity feeler re adjust it as necessary Do not use any compressed air solvents for cleaning the feeler sensor If the unit is disabled we suggest draining all the water in the cylinder The steam production cylinder must be replaced whenever the lime scales inside the cylinder itself prevent the water to pass sufficiently As previously said the frequency of the replacements depends on the feeding water conditions the more the water is rich with salts and or impurities the more frequently the cylinder shall be replaced The worn cylinder shall be replaced as explained below Make sure that the automatic no tension drain function is set see Use handbook Stop the unit and
56. e TECNAIR LB CLOSE CONTROL AIR CONDITIONERS AIR CONDITIONERS FOR SURGICAL ROOMS AND FOR CLEAN ROOMS a mme wa 8 g 8 4 4 a 4l INSTALLATION USE AND MAINTENANCE HANDBOO r gt Handbook code 75802206A 0204 TECNAIR LB Sheet 1 of 82 CHE CATR OMICS ERS 1 GENERAL INFORMATIONS CE DECLARATION CONFORMITY 2 DECLARATION OF THE MANUFACTURER WARRANTY E APPLICATION OF THE PRESENT MANUAL UNIT CODING 6 OPERATING LIMITS 27 SPARE PART LIST 8 DOCUMENTS INCLUDED IN THE UNIT p COMPONENTS DESCRIPTION AND OPERATION 12 oO 1 N 2 1 MICROPROCESSOR ADJUSTMENT 12 2 2 START UP AND FUNCTIONIG LOGIC OF THE UNITS 13 2 4 OOLIN APA Y REGULATION WITH INVERTER ON TH OMPR 2 5 COOLING CAPACITY REGULATION WITH ELECTRONIC HOT GAS INJECTION 1 2 6 AIR CONDITIONERS WITH CHILLED WATER COIL OHA OWA 16 2 7 PREHEATING SECTIONS 16 2 8 REHEATING SECTION 18 DO AN ON 2 10 AIR FILTRATION 19 2 11 CONTROLLING THE AIRFLOW QUANTITY TO THE ROOM 21 2 12 OVERPRESSURE DEPRESSION 22 2 13 HEAT RECOVERY SECTION 26 2 14 HUMIDIFICATION standard for OH series accessory for OW 27 2 15 DEHUMIDIFICATION 29 2 16 DIFFERENTIAL PRESSURE SWITCHES FOR CLOGGED FILTER INDICATION 30 2 17 SOUND ABSORBERS 30 INSTALLATION OO s TRANSPORT 3 2 UNIT ACCEPTANCE ON SITE 3 3 CLEARANCE ANTIVIBRATION SUPPORT AND POSITIONING 3
57. e for this parameter depends on the dynamics of the process being controlled as well as the desired response This parameter is active when P46 0 10 00 0 01 0 01 82 Integral Gain Integral Gain used by the PI regulator This parameter is scaled so that when it is set to 1 0 the process response is 10 Hz sec when the process error is 196 The correct value for this parameter depends on the dynamics of the process being controlled as well as the desired response This parameter is active when P46 setting 9 is used 0 10 00 0 01 0 01 83 1 PI Process Reference The PI control will regulate to this set point value It represents a percentage of the analog input This parameter is active when P46 setting 9 is used This parameter along with P72 also activates PI control in drives using Firmware Version FRN 7 06 See page 5 17 for PI Control Setup and Activation instructions ATTENTION Hazard of personal injury or equipment damage exists due to unpredictable changes in motor speed Do not use P72 and P83 to disable PI control while the drive is running Disable PI control only when the drive is stopped 0 100 96 0 0 96 0 0 84 1 PI Dead Band The PI control will ignore errors less than this value This parameter is active when 46 setting 9 is used 0 10 0 0 0 96 0 0 1 This parameter applies only to the Analog Signal Follower model 2 9 1 7
58. e guarantee of the machine After this to start up the unit first open the taps placed on the suction and discharge line of the compressors on the exit of the liquid receiver if present and all the other valves present on the frigorific circuit at this point you can energize the unit pushing the ON button on the microprocessor or the selector on the units with electronic control After 15 20 minutes of continuous operation of the machine it is necessary to check the good operation of the frigorific circuit to do this you have to control the following operating point r gt Handbook code 75802206A 0204 TECNAIR LB Sheet 49 of 82 CICE CONTROL ERS refrigerant charge of the circuit Evaporating pressure Condensing pressure Overheating of the suction line 1 2 3 4 5 Sub cooling of the liquid line 6 unclogging if clogged of the fluid line filter 7 Compressors power input 8 High pressure switch good operation 9 Low pressure switch good operation 1 0 Operating temperature of the compressor As normally used by the air conditioning serviceman here below we express condensing and evaporating pressures using the relevant temperatures 4 2 1 Refrigerant charge control This is the first control to be made on a frigorific circuit in fact if the charge is not correct the control of all the operating parameters is without any sense To control the charge it is enough to check at the liq
59. e use of a frigorific capacity regulation device is warmly suggested Each circuit consists of an hermetic scroll compressor a thermostatic expansion valve and two pressure switches each The low pressure one with automatic reset but to be reset by the microprocessor keyboard too doesn t stop definitely the cooling circuit The high pressure one for clear safety motifs is with manual reset and stops the cooling circuit In both cases the conditioner continues to function displaying the trip of the high or low pressure alarm A drier filter with sight glass is forecat on the refrigerant liquid line The compressor is scroll type with built in integral electric protection to avoid any excessive electrical input and is equipped with a crankcase heater and welding type connections to the supply pipe The direct expansion coil is 4 6 or 8 rows coil with copper tubes expanded into the aluminium fins A stainless steel condensate discharge back is always installed under the coil and is connected with a central water trap with non return valve The discharge from the humidifier is independent from the other one and is carried toward the right hand side panel of the unit The discharge condensate bac always has a slight downwards inclination so to guarantee that it always remains empty 2 4 COOLING CAPACITY REGULATION WITH INVERTER ON THE COMPRESSOR On request an inverter can be installed on one compressor to control optimally the feeding frequency
60. ections 5 3 DISPOSING THE WASTE MATERIALS USED FOR CLEANING OPERATIONS Cleaning these units originates both solid waste replaced filters operator clothing worn out belts if any etc and sewage washing fluid and rinsing water residue The solid waste shall be put into hermetically sealed containers and shall be disposed of together with the septic solid waste of the hospital Conversely the sewage can be discharged into the drain of the condensate discharge back fitted on the apparatus These bacs shall be previously connected with the septic sewage system of the hospital 5 4 CLEANING METHOD As the air conditioners contain electric components electric motors terminal boards feelers etc that cannot bear plenum water jets or high temperature and a cooling system that cannot undergo high pressure when executing any cleaning operation the operators shall not use Any jets of steam Any jets of plenum water The disinfectant and the water necessary for disinfecting and rinsing the apparatuses shall be used only in atomised form and then be disposed of as septic sewage You can obtain the atomised solution for cleaning the air conditioners using appropriate manual atomisers The cleaning and washing operations shall be executed using only water plus 496 ammonium chloride solution or a chemically equivalent commercial solution to atomise with a manual atomiser Each air conditioner can be divided into three sections TECHNI
61. ed water units is made essentially of a big surface direct expansion cooling coil with copper tubes expanded into aluminium fins and a three way modulating valve All internal tubes are copper made and are provided with thermal insulation The microprocessor controls the modulating valve with an analogic 0 10 output signals The opening of the valve is proportional to the value of the signal sent by the microprocessor On its turn the voltage value is proportional to the required thermal or humidity load from the required set point Verifying on the display the level of the valve s opening is always possible With the machine switched off the valve returns in a totally closed position whilst in case of a lack of feeding tension the valve remains in the previous position For example if the indicated proportionate band is of 2 C and the set point is of 20 C the exit tension value should be equal to 0 V when the measured temperature is of 20 C and will equal 10 V when the temperature is of 22 C All this is shown on fig 3 lov il 20 220 set a Figure 3 2 7 PREHEATING SECTIONS The heating system is defined as preheating when the heat source is positioned upstream the cold source reheating when its placed downstream In case of cold water coils it s necessary to preheat the air to avoid freezing In case of direct expansion cold coils the only hot source can be a single water or electric coil r gt Handbo
62. ensing discharged from the humidifier is connected to the drainage network without valves or counterpendances Verification of the system for heat recovery accessory Verification that the system has been charged with water and glycol in relationship to the forecasted minimum temperatures Verification of the aeraulic connections and of the air filters Verifcation that the air ducts are connected in conformity to the instructions Verification of the installation of the sound dampers at least twords the controlled room Verification that the air ducts are insulated externaly Verification that the air filters on the supply and that terminal in the room are not installed so to avoid that they become dirty during the systems testing Verification of the differential pressostat for the control of the rooms pressure Verfication of the connections ot the pressure plugs as descirbed in the installation manual h min 1700 mm Verifcation of the electrical connection from the pressostat to the electric pannel as described in the wiring diagrams and the installation manual Verification of the temperature and humidity feelers Verification of the positioning as forecasted in the installation manual h min 21700 mm Verifcation of the electrical connections of the feelers to the elctrical pannel as described by the wiring diagram or the installation manual Verification of the second interface for remote control o
63. ent by turning the appropriate key With the end piece of the vacuum cleaner remove any trace of dust from the internal components and walls This operation shall be executed from the top to the bottom r gt Handbook code 75802206A 0204 TE CNAIR LB Sheet 56 of 82 CICAE CATRO ERS Clean the internal walls with an alcoholic solution avoiding moistening the shutter washer This operation shall be executed from the top to the bottom Clean the shutter washer with a wet cloth Dry scrupulously the internal walls and washer with a dry and clean cloth Close the shutter taking care not to damage the washer If the operating compartments do not need to be washed and disinfected connect the electricity again by turning the main shutter blocking switch on At this point the unit is ready to be set at work again 5 4 2 Procedure for washing and disinfecting the inside of the oparting compartment The inside of the operating compartments is licked by the outdoor air and by the airflow from the surgical room This is why they can be subjected to accumulation and proliferation of pathogenic microorganisms even if appropriate filters are installed both on the unit and on the air suction and discharge networks Therefore they must be washed and disinfected on a regular basis Unless otherwise specified by the Physician in charge of the Ward in question they shall be washed and disinfected At least once a month regardless of the
64. er on exaust air YES Inverter on discharge air YES Accessories Remote alarm board ACCESSORY Serial RS422 board NO r gt Handbook code 75802206A 0204 TECNAIR LB Sheet 12 of 82 CONTRO AJ Serial RS485 board ACCESSORY Storage extension ACCESSORY Programming key ACCESSORY Figure 2 functions and components supported by pCO As for the modes of operation of microprocessor PCO2 please refer to the relevant user manual code 75802307A 0109 containing all the instructions for the start up modification of the working parameters and management of the equipment itself 2 2 START UP AND FUNCTIONIG LOGIC OF THE UNITS 2 2 1 OH Series starting up On starting the unit up the microprocessor opens the motorised dampers installed on the duct entry This operation takes about 90 seconds after which it starts up the fan for air discharge to the environment and that for air return and expulsion if present The air discharge fan controls the airflow evenness as required in spite of the increased pressure drop due to progressive filter clogging The air expulsion fan controls the overpressure or depression of the air conditioned environment compared to any reference surrounding environment Afterwards according to the temperature of the environment to treat which is sensed by the temperature and humidity feeler installed in the air expulsion section or
65. erinisiena Figure 13 External unit higher than the internal unit 1 r gt Handbook code 75802206A 0204 TE CNAIR LB Sheet 36 of 82 ABE OF METH 3 12 LINES DIAMETERS FOR COOLING CONNECTIONS The following diagrams relating to 5 C evaporation temperature and 45 condensation temperature allow easily dimensioning the suction fluid and discharge cooling pipelines Given the cooling capacity of the plant and the equivalent length of the line in question the graphs permit to go back to the pressure drop per metre and therefore to the total pressure drop which must always be lower than the peak marked in the top right hand corner of the diagram For instance if you want to calculate the diameter of a suction pipe having equivalent length equalling 24 metres in a plant with cooling capacity equivalent to 28kW we can draw 3 possible diameters from the diagram at the following page lines intercepted by the vertical line at 24kW 228 235 242 If we choose 228 the diagram provides ordinate of point A a 1 05 kPa m unit drop and therefore a 25 2 kPa total drop along the line which is higher than the suggested peak 20 kPa Conversely if we choose the next greater diameter 35 we shall have a 0 4 kPa m unit loss and a 9 6 kPa total loss which acceptable You are advised against using the greatest suggested diameter 42 even if this is in accordance with the m
66. f the cooling circuits capacity In case of nearly total recirculation max 20 2596 fresh air as in the majority of cases of clean room air conditioners OW series the heat pump heating can be used even without the capacity regulations 2 7 2 OW series clean room air conditioners A standard reheating coil is not forecasted In case of necessity both electrical coils or hot water coils can be applied both modulating controlled by the 2 8 REHEATING SECTION Electrical modulating heater standard for series OH units accessory for OW units 2 8 1 OH series surgical room air conditioners The standard coil is electrical with modulating regulations and thermal protection at 70 For further information refer to chapter 2 5 1 2 Alternatively to the standard electrical coil its possible to install a water reheating coil with three way modulating valve For further information refer to chapter 2 5 1 1 2 8 2 OW series clean room ari conditioning A standard reheating coil is not forecast In case of necessity both hot water coil and the electric one can be installed as option 2 9 FAN SECTION Installed fans are plug fan type directly connected to the 2 poles frequency variable electrical motors They have a characteristic very steep curve therefore with a small air flow loss they can provide a higher static pressure so to compensate the progressive clogging of the filters Never the less in the both OH surgical room and
67. h in the following Directives 89 392 EEC 93 68 EEC 73 23 EEC 89 336 EEC Uboldo February 19th 2001 Tecnair LB r gt Handbook code 75802206A 0204 TE CNAIR LB Sheet 5 of 82 CICAE CATRO ERS 1 3 WARRANTY The air conditioners described in this manual are subject to the present warranty terms which intended as accepted and automatically subscribed by the Customer when placing the order with TECNAIR LB The supplier hereby guarantees the correct construction and good quality of the product object of the supply committing himself during the warranty period specified herein to repair or supply spares for at his sole discretion in the shortest period the parts and or components that should present any material or construction or working defect invaliding them for their intended use provided that the defect is not due to the purchaser s negligence to any routine wear and tear to the User s negligence or unskillfullness to any damages by third parties to Acts of God or Force Major or to any other cause not ascribable to the original manufacturer of the equipment and the Manufacturer shall not be held responsible for any direct or indirect damages of any kind and for any reason Defected parts substitution is held in the Uboldo factory and all transport costs is made by the Commissioners The warranty term is of 1 one year from the delivery date The warranty term shall be au
68. h the unit according to the respective terminals It is essential that the cable be screened and be not as far as possible inserted in any runways or tube along the route to the unit avoiding any angle route and or too small bending radius Figure 24 terminal board of the differential pressure switch IMPORTANT THE DIFFERENTIAL PRESSURE SWITCH SHALL NOT BE CALIBRATED 3 16 INSTALLING FOR THE AIR CONDITIONER REMOTE CONTROL INTERFACE All the air conditioners produced by Tecnair are equipped with a user interface mounted on the unit A second user interface can be installed inside or near the room to control the air conditioner directly from inside the room This interface allows to Fix the temperature and humidity set point Modify the capacity of the air conditioner Read the alarms intervened if any Stop or put the unit in stand by The second interface is connected with the microprocessor on the unit as a local network shared terminal So a 6 way flat telephone type cable shall be brought in the environment up to the point of connection The maximum length of the connection cable is 50m Should you need to connect the second interface at a distance longer than 50m the use of a shielded cable type AWG22 is mandatory This cable must be connected to the two T derivation cards from the microprocessor card and the remote terminal are connected One end of the cable must be entered in the rear of the terminal through
69. harge of the Ward in question EXTERNAL FRAMEWORK OF THE UNIT The external framework of the unit is made of enamelled plate so it only needs to be cleaned according to the criteria and following the specific procedure described in this handbook However if the unit is installed directly in the surgical room or in any room in which any septic contamination may occur it should be cleaned whenever the operating compartments are washed and disinfected or even more frequently to the sole discretion of the Physician in charge of the Ward in question Each section shall be cleaned with a different method as each method applies to specific areas Further the following order shall be observed Cleaning the inside of the technical compartment Washing and disinfecting the operating compartments Cleaning the external framework of the unit 5 4 1 Procedure for cleaning the inside of the technical compartment The inside of the technical compartment shall be cleaned with a vacuum cleaner equipped with an interchangeable paper filter using a soft brush Unless otherwise specified by the charge Physician the filters of the vacuum cleaner do not require necessarily to be disposed of as septic waste The cleaning procedure to apply is the following Stop the unit and disconnect the electricity by turning the main shutter blocking switch off Put a notice on the switch saying that the unit is under maintenance Open the shutter of the technical compartm
70. he pipelines being used and on their length Table 7 below features for convenience the refrigerant weight kg per metre for the liquid refrigerant discharge and suction lines the refrigerant is question is 407 Weight kg per m length R407C Diameters 210 12 214 16 220 22 226 28 033 35 239 42 Liquid line 0 09 0 17 0 35 0 58 0 94 1 31 Discharge line 0 02 0 05 0 09 0 16 0 26 0 36 Figure 18 weight of the refrigerant in the lines So to obtain the charge corresponding to each pipeline you just have to multiply the data in the table by the actual length of the contemplated pipelines The sum of all the replenishments calculated e g refrigerant discharge condenser in case of units with direct expansion coil gives the total charge to replenish We recommend the use of SUNISO 3 GS for units charged with R22 and MOBIL EAL ARTIC 22 BC and equivalent polyesters for units with 407 3 14 CHARGE OF THE HEAT RECOVERY CIRCUIT The heat recovery circuit is normally not filled in by Tecnair as the percentage of glycols to put in the water vary according to the place of installation of the air conditioner as well as to the capacity of the circuit It is essential to always use glycol water if the outdoors temperature is expected to fall below freezing While filling in the circuit first put the glycol and then the water If the plant is stably connected with the water network install a disconnector befo
71. he compressor control Temperature of the top of the scroll compressor must be about 60 70 temperature of the bottom must be about 25 30 If temperatures are colder and you can notice that the top of the compressor is covered by condensate water it means that temperature of the refrigerant is too low and therefore liquid refrigerant tends to return to the compressor as a result of an insufficient level of overheating ensured by the thermostatic valve Proceed as seen at paragraph sucked gas overheating control If the compressor head is too hot 50 C or more it means that the thermostatic valve does not allow a sufficient refrigerant to pass to the evaporator and that the overheating of the refrigerant is too high therefore proceed as per paragraph sucked gas overheating control This phenomenon can also be due to a defectuous compressor r gt Handbook code 75802206A 0204 TE CNAIR LB Sheet 53 of 82 ERS 5 WASHING CLEANING AND DISINFECTION 5 1 WARNINGS Before initiating any cleaning operation it is indispensable to read carefully the following preliminary instructions and fully understand their content All cleaning operations shall be executed observing such directions as any improper procedure may cause serious damages to the equipment and or harm the operator The air conditioners series H and W contain live and pressurised parts Therefore to avoid any possible hazard i
72. hospital Great care shall be taken in cleaning the room between the airs return damper and the filter seat where dirt is likely to deposit Dismount and replace the hepa filters before the vents and or air diffusers to the room The dismounted filters shall be put into hermetically sealed containers and then disposed of following the same procedure as for the septic waste of the hospital r gt Handbook code 75802206A 0204 TECNAIR LB Sheet 57 of 82 CONTROL ERS Dismount the shutters of the operating compartments by turning the appropriate key Dismount the filters on the unit G4 class filter on the air return G4 class post filter on the outdoor air suction and G7 class post filter on the air discharge The dismounted filters shall be put into hermetically sealed containers and then disposed of following the same procedure as for the septic waste of the hospital The spare filters shall be mounted later as otherwise they may get damaged during the washing and disinfections Dismount the drops eliminator if present Wash and disinfect the left hand operating compartment with a 496 ammonium chloride solution to atomise by means of a hand atomiser in following order until all the components are completely washed On the overpressure damper of the air expulsion On the return air fan turning the runner by hand until it is completely washed On the heat recovery coil if any on the return airside The co
73. iclockwise the control shaft that is under the cap by one turn and after 30 minutes to allow the circuit to stabilise recontrol the overheating if this is not enough turn an other turn refrigerant charge is not complete bubbles on the liquid indicator Q Air inlet is too hot r gt Handbook code 75802206A 0204 TECNAIR LB Sheet 51 of 82 CONTROL ERS If the overheating is less than 4 C it means that Thermostatic valve is too open or defective to close it proceeds as already seen by rotating clockwise the control shaft Air filter is dirty or the coil is clogged Fans are defective wrong revolution 4 2 5 LIQUID REFRIGERANT SUBCOOLING CONTROL Liquid refrigerant leaving the condenser is at the condensing pressure but sub cooled compared with the temperature corresponding to the condensing pressure Normally sub cooling ought to be between 2 and 7 If sub cooling is less than 2 C it means that the condenser cannot get rid of all the heating produced If sub cooling is more than 7 it means that the refrigerant charge is too high 4 2 6 Filter liquid line clogging control The filter on the refrigerating liquid line is of great importance in the units with refrigerating lines to be completed in the factory to avoid allowing the circulation of eventual dirt impurities or other leftovers from the selling due to bad execution of the same lines which could therefore damage the compress
74. il shall be sprinkled abundantly with the solution from the top of its upper face until the solution comes out of the bottom side On all the pipelines running inside the compartment On the circulation pump of the heat recovery circuit if provided On the blades of the return air damper In the room produced by the thickness of the panel between damper and filter On the framework of the return air post filter On the internal walls of the compartment acting from the top On the bottom bac Rinse abundantly the internal parts of the left side operating compartment by atomising sterilised water with a manual atomiser The rinsing operation shall be executed following the same sequence described at previous point i Wash and disinfect the central operating compartment with a 496 ammonium chloride solution to atomise with a hand atomiser in the order specified below until all components are completely washed On the levers and blades of the outdoor air damper In the room produced by the thickness of the panel between damper and filter On the framework of the outdoor air filter On the heat recovery coil if present on the outdoor airside The coil shall be sprinkled abundantly with the solution from the top of its upper face until the solution comes out of the bottom side On all the pipelines running inside the compartment a On the bac beneath the heat recovery coil if present b On the assembly consisting of the pre heating c
75. ince an accidental modification of the damper position could delete it and therefore produce great damages to the environments production 2 12 3 2 Automatic control of the overpressure accessory Clean rooms have to always be maintained in overpressure so to guaranty that the pollution cannot enter from doors or small openings The overpressure has to be kept so that in no case it can be cancelled by external causes therefore it has to be well above the tolerance of the system which is approximately calculated to 5Pa The overpressure must not be excessively high so not to create difficulties in opening the doors even though these are mostly sliding type or other problems It is thought that the optimal level is of 15Pa this is the Tecnair LB default value Overpressure control is obtained by controlling accurately the fresh air flow which is supplied to the environment on the basis of the information released by the differential pressostat provided by us and r gt Handbook code 75802206A 0204 TECNAIR LB Sheet 24 of 82 CONTROL CTIMEHTI HA ERS installed by the client between the controlled environment and a reference one The microprocessor compares the received signal from the pressostat with the previously set pressure set point and if the overpressure is not reached acts according to the unit type like we are going to explain 2 12 3 2 1 Overpressure control for totally fresh air operating clean room air cond
76. ir flow temperature minimum 22 C maximum 38 C humidity lower 10 maximum 100 Q Units without heat recovery system version H high air flow temperature minimum 10 C maximum 30 C humidity lower 10 maximum 100 Units with heat recovery system version L low air flow temperature minimum 40 maximum 46 humidity lower 1096 maximum 100 Units with heat recovery system version H high air flow temperature minimum 32 maximum 40 humidity lower 10 maximum 100 1 6 1 2 Operating limits for air cooled condensers 1 6 1 2 1 Minimum operating limit minimum outdoor air temperature Axial or radial air condenser with switch and speed variator minimum external air temperature 20 Axial or radial air condenser with switch and without speed variator The speed variator can be installed in the internal electric panel of the unit minimum external air temperature 25 Axial or radial air condenser without switch and without speed variator This solution is not in conformity with the safety standards since the operator is not certain that the condenser is not remotely switched on whilst he is doing maintenance work is therefore mandatory that the switch installed away from the condenser and inside the building is of lockable type minimum outdoor air temperature 40 1 6 1 2 2 Maximum operating limit maximum outdoor air temperature It is sugges
77. is essential to check the floor where the unit is to be positioned it must be such as to bear the weight of the unit which can be easily drawn from the related commercial documentation or read directly on the identification plate inside the unit itself During the installation take care to leave enough room around the unit for routine and extraordinary maintenance operations as indicated in the drawing attached to the confirmation of order In general it is absolutely necessary to provide for approx 80cm clearance all before the unit and 80cm on the right side The units OHA 242 and OHU 308 need a further 80cm clearance behind the machine If the unit is to be installed on the floor you shall need to place rubber or spring anti vibration supports right under the unit 4 pieces or the models 41 and 51 and 6 pieces for the other models chosen as a function of the unit weight and fixed to appropriate holes in the base r gt Handbook code 75802206A 0204 TECNAIR LB Sheet 31 of 82 CONTROL ERS 3 4 ELECTRICAL CONNECTIONS The external electrical connections of the air conditioner must fulfil the following requirements Q They shall be sized to support the maximum load Ampere indicated in the electric wiring diagram and on the identification label placed inside the control section of the unit The feeding line shall arrive to the unit directly from the external magnetotermic differential switch without
78. itioners Clean room air conditioners with totally fresh air treatment are marked by the letter L low air flow after the numeric part of their code and have a single mouth opening for the air on which as an option a modulating motorized damper can be installed for controlling the room overpressure This opening is dimensioned according to the units nominal air flow For these very tough conditions the air treatment components are selected and therefore the chilling coils are of 6 or 8 row type and even the humidifier is very large Unless in very rare cases in parallel to these units for the treatment of fresh air only others are installed only for the recirculation for a capacity five or more times superior of that of the fresh air unit The microprocessor receives the information on the actual overpressure state of the environment from the differential pressostat compares it with the set point previously set and raises the dampers opening if the overpressure in the environment is not reached reduces it if it s too much The units air flow therefore varies in first approximation in relationship to the level of air tightness in the controlled room higher the air tightness of the room is lower is the amount of fresh air necessary to overpressurise the environment To guaranty the air flow external re circulated necessary for the demanded air quality in the room the re circulation air conditioners are used 2 12 3 2 2 Overpressure contr
79. k that the compressor valve is open r gt Handbook code 75802206A 0204 TE CNAIR LB Sheet 50 of 82 CICAE CATRO ERS For good operation of the frigorific circuit the condensing pressure must be as constant as possible A low condensing pressure causes low evaporating pressure with a consequent high dehumidification too high condensing pressure is causes a low efficiency of the frigorific circuit and high electric power input Therefore normally we try to keep in summer and winter a condensing pressure as close as possible to 45 In order to do this it is mandatory that condensers are selected to have the capacity to dissipate the heat rejection of the unit cooling capacity plus compressor power input with a difference of temperature of 15 20 C between air entering temperature to the condenser and condensing one So when the external temperature is 30 the condensing temperature will be 45 50 Of course when the air temperature is higher than 30 the condensing temperature will be higher than 45 50 but this cannot be avoided and is not reasonably creating problems to the frigorific circuit Tecnair air cooled condensers are provided with an electronic device made of a modulating pressure switch connected with a regulator to reduce the revolution speed of the condenser fan when the condensing pressure is reduced due to the low ambient temperature This device water proof protection IP55 is placed on the
80. least two hours before the arrival of the technician do to allow for the carter oil resistance of the compressor to arrive to the temperaturefor the refrigerant to evaporate and so to guaranty the correct functionment of the compressor POS OPERATIVE DESCRIPTION POSITIVE NEGATIVE Visual verification of the hot gas supply ducts only H amp W Conformity verification of the supply tube diameter with what forecasted in the installation manual Verification of the slope of the horizontal hot gas supply tubes in the direction of the refrigerant flow of at least 196 Verification of the presence of the siphon at the base of each mounting tube and every 3 m and of a counter siphone in the highest point of it Verification of the presence in the nearest point to the compressor of a non return valve opening in the direction of the refrigerant s flow Verification of the presence of the insulation of the tubes in the pieces of points where an occasional contact is possible by the operator Temperature of the tubes works at approx 70 80 C Verification fo the settings of the brackets on the supply tubes not to be too rigid every 3 m so to allow for dilatation Visual verification of tubes for the frigorific return liquid only OHA OWA Verification of the conformity of the diameter for the liquid tubes with what requested Verification of the presence of the brackets every 3 m
81. lied with the unit If the absorption of one phase or of all the phases of a motor is higher than the limit it should be checked that the fan is operating in normal mechanical conditions and eventually substitute the motor When the compressors will be started up it is necessary to control that their absorption is within the fixed limits For units with scroll compressor only therefore with A or W as the third letter of the coding The units with scroll compressors are standard equipped with devices controlling the feeding phases sequencer This device installed in the electric board is equipped with two LEDs green and red marked electric connection OK and invert phase connection respectively When the red LED is on the unit is not started up for avoiding damages to the compressor 4 2 CONTROLS REFRIGERATION CIRCUIT OPERATION About four hours before starting up the compressors it is necessary to insert the general feeding switch so as to give voltage to the carter oil heater in order to minimize the concentration of the refrigerant present in the oil and the consequent involving of the same when the compressors are switched on to avoid to damage them This operation must be repeated every time it is necessary to start up the compressors after an idle period during which the voltage has been taken away by opening the general feeding switch This procedure is so important that the non observance of it is voiding th
82. loss of capacity for the system upstream the unit with all the units operating and with clean filters es 500 Pa Insert as depression set point this value es 250 Verify room by room the reached air capacity f the reached capacity is not the desired one raise for example of 5 Pa the pressure set point and continue regulating it until the desired capacity is reached 2 12 OVERPRESSURE DEPRESSION 2 12 1 Controlling overpressure for OH series Conditioners The regulation of the overpressure or depression in the environment is entrusted to an inverter that controls the revolutions of the direct driven fan for air return and exaust based on the following parameters Set value for overpressure or depression in the environment Changes in the environment condition The regulation of the pressure in the room is based on the principle that to keep an overpressure depression in an isolated environment you just need to extract less more air than you put in Thanks to the inverter on the air return fan the air conditioners manufactured by Tecnair LB can reach the overpressure depression set point with F5 Pa tolerance The value of the overpressure of the room with regard to a given reference environment this value can be set by the user see user handbook of the microprocessor pco is expressed in Pa and must fall within a 20 20 Pa range Of course if the set point is negative this means that depressi
83. ne maintenance However there are some inner points that still present a risk of cut for the user water drain bac coil fins etc So it is fundamental for the operator to be very careful on removing and then re inserting the air filters to not cutting his her hands The G4 class filters normally installed on the outdoor air suction and on the expulsion air from the surgical room cannot be clean and must be replaced Their average life is about one month Also the F7 class filter that is normally installed on the air supply to the surgical room cannot be clean and must be replaced Its average life is about three months A sticker shall be put on the spare filters marking the date of the replacement in order to have a reference of the residual life of the filters at all times The filters shall be disposed of together with the special waste of the hospital The air conditioners can absolutely not work without the filters so you are strongly recommended to purchase a series of spare filters from Tecnair to ensure the continuative functioning of the air conditioners 6 1 HUMIDIFIER MAINTENANCE All the air conditioner series H are equipped with an electronic modulating humidifier for controlling the relative humidity in the environment As previously mentioned it is necessary to monitor very carefully the steam production cylinder and to analyse as much carefully the feeding water The microprocessor generally analyses the water conductivity
84. nitoring of the air conditions whilst air conditioners for white r gt Handbook code 75802206A 0204 TECNAIR LB Sheet 6 of 82 OTC ERS rooms which be for complete outside air or partially re circulated air are standard in cooling only version and as accessory have heating coil humidifier and regulating inverters for ventilation In the following chapters indications of standard components to the machines and add ons are always specified For the exact composition of the units reference is made to the order confirmation 1 5 UNIT CODING Your unit belongs to Tecnair s catalogue of air conditioners for surgical rooms The different models are coded by letters and numerals indicating the unit s power and type of functioning and the heat recovery system if present The coding shall be read as follows 05 1 R407C HP HR 1121314 51617 8 9 10 1 Air supply direction Upflow air supply 2 H Series H For surgical rooms 2 W For clean rooms 3 A Typology of the cold generator A Direct expansion coil with remote condenser 3 E Direct expansion coil with remote condensing unit 3 U water coil with remote water chiller 4 5 5 Size Nominal horsepower Number of cooling circuits or number of rows of the cooling coil for water units a Modify index R of refrigerant fluid HP
85. nly if present Verification of the positioning as forecasted in the installation manual h min 21700 mm Verifcation of the electrical connection of the interface to the electrical pannel as seen on the wiriing diagram or the installation manual NOTES FOR POSSIBLE ANOMALIES ENCOUNTERED DURING THE VERIFICATION PHASE Handbook code 75802206A 0204 TECNAIR LB Sheet 48 of 82 ATRO AE 41 ELECTRIC CONTROLS Before proceeding with the operations it is necessary to check that power connections have been carried out correctly and that their operational level are in optimal conditions Then it is recommended to control that every screw of the terminals are accurately tightened down both as regard the connections effected on the terminal block and on the individual devices By mean of a voltmeter make sure that the line voltage corresponds to that of the label with a 1096 allowance It is necessary also to check direction of the fans starting them up without energizing the compressor If the rotation of fans is not correct it is sufficient to change the connections on the terminal board of two out of three phases of the feeding line of the machine Before staring up the compressor it is necessary to proceed to a control of the current absorption of the various fans by an amperometric wrench on each phase to be sure that they do not exceed the limits indicated on the electric wiring diagram supp
86. nning c 2 TECNAIR LB CONTRO ARB Handbook code 75802206A 0204 Sheet 68 of 82 78 Compensation 0 No compensation 1 Some drive motor combinations have inherent instabilities which are exhibited as non sinusodial motor currents This setting attempts to correct this condition 2 Some motor load combinations have mechanical resonances which can be excited by the drive current regulator This setting slows down the current regulator response and attempts to correct this condition 0 2 79 Software Current Trip This provides a software instantaneous current trip similar to the 30096 hardware current trip This value is the percent above the P43 at which the drive trips immediately A setting of zero disables the Software Current Trip 80 Stall Fault Time This selects the amount of time the drive must be in a stall condition before it causes a stall fault 0 Normal stall time approximately 60 seconds 1 2 times normal stall time 2 4 times normal stall time 3 6 times normal stall time 4 8 times normal stall time 5 Stall fault disabled ATTENTION Continuous operation at high currents caused by a stall can cause motor damage 0 50 0 5 0 96 81 1 PI Proportional Gain Proportional gain used by the PI regulator This parameter is scaled so that when it is set to 1 0 the process response is 1 Hz when the process error is 1 The correct valu
87. nt has been detected between these Check the motor and external wiring to the drive two drive output terminals output 43 VW Short Fault Excessive current has been detected between these Check the motor and external wiring to the drive two drive output terminals output terminals for a shorted condition Intermittent Phase Check wiring between the drive and the motor 46 An external short red whil ing di tics Fault externa short occurred wane Tunning diagnostics Check for more than one shorted output 48 Reprogram Fault Occurs when the drive parameters are reset to default Clear the fault These faults have an auto reset feature This feature automatically clears overvoltage undervotage and overtemperature faults 1 second after the fault condition is removed Refer to P51 TECNAIR gt TRAN Handbook code 75802206A 0204 Sheet 71 of 82 8 TROUBLE ANALYSIS The following chapter aims at assisting the operator in searching possible troubles in the unit equipment Starting from the type of problem in question indication is given of the possible sequential causes of the trouble itself and the possible remedies The description of the causes is general so it takes into consideration the most complete possible versions of the units the operator shall take care to identify from time to time only the matters of interest and or the functions actually featured in the unit in question Any in
88. nyway after the F9 filter and before each connection to the different rooms The pressure stat is wired electrically to the electric panel s relative clamps as described in the unit s wiring diagram with a Belden type cable of a maximum length of 10 meters When this damper closes the pressure inside the duct raises The pressure stat informs the microprocessor that confronts it with the setpoint and adjusts the revolution speed with the fans inverter r gt Handbook code 75802206A 0204 TECNAIR LB Sheet 21 of 82 CONTROL CTIMEHTI HA ERS This system guaranties a good control of the capacity even if the number of rooms to be controlled varies and acts as a correction of the reduction of capacity due to the progressive dirtying of the filters upstream the measuring point the ones inside the unit It is not anyway able to control the dirtying of the filters downstream the measuring point It is therefore necessary that the filters upstream the measuring point are maintained in an optimum state so that the dirtying of the absolute filter is slower and gradual in time With this system there is no direct control of the capacity the parameter which we must control but indirectly by the pressure in the suction ducts which is proportional to the capacity The regulating system for the installation is therefore a bit more complicated because of this need to act indirectly It is therefore suggested to proceed as follows Hypotise
89. ok code 75802206A 0204 TECNAIR LB Sheet 16 of 82 CHE CONTROL CETRSEHTICHN ERS installed downstream the cold one with winter heating functions and summer post heating Obviously case of water coils its necessary that the hot water is retrievable both in summer and in winter The preheating water coil comes standard in the OH series as an accessory in the OW series 2 7 1 OH series surgical room air conditioners In all the types of air conditioners the standard heating section is made of a 2 row hot water coil with a microprocessor controlled three way motorised valve The coil like every other coil in the unit is designed in such a way as to favour sterilisation thanks to a minimum 2 5mm fin spacing and is epoxy painted Alupaint Alternatively a fully microprocessor controlled modulating electric heater can be installed as heating source with a thermal protection set to 70 or a modulating steam heating coil can be installed Both are controlled by the pCO microprocessor which comes standard with the units Heat pump units use the frigorific circuit as a heating source 2 7 1 1 Hot water coil heating capacity regulation standard The regulation is entrusted to a three way modulating valve that is directly controlled by the microprocessor The valve opens and closes in direct proportion to the set proportional band For example if the set proportional band is 2 C and the set point is 20 C then the exit tension sign
90. ol for air conditioners for clean rooms operating with fresh air plus recirculation The air conditioners for clean room for treatment of fresh air plus re circulation or only re circulation are characterised by the letter H high air flow after the numerical part of the unit s code and have two independent suction mouths Normally in these units the fresh air flow if present is at maximum equal to 10 2596 of the total one the rest is re circulated Under these conditions the components are selected and therefore the chilling coils are of 4 rows whilst the humidifiers are smaller This unit serves alone one room or can be set parallel to other units as stated in the previous point Units for total re circulation cannot take up the function of controlling the overpressure since they don t have the necessary quantity of fresh air they don t even have the relative mouth In this case installation of the motorized damper is useless When the unit handles fresh air too the overpressure control is obtained by two motorized dampers modulating and counter placed on the mouth for the entrance of fresh air and on the re circulation one The two dampers are controlled by the microprocessor with the information of the usual differential pressostat The microprocessor controls the overpressure raising or diminishing the fresh air dampers opening and therefore the relative air flow totally automatically To a raise in fresh air corresponds an identi
91. ol only when the drive is stopped When this parameter is set to a 1 reverse is disabled The reverse command 73 Reverse Disable may come from the analog input TB3 5 the keypad or a serial command 0 1 0 1 This parameter cannot be programmed while the drive is running 74 Settings 0 unipolar analog input 0 to 10V 1 bipolar analog input 10 to Analog Select 10V 0 1 0 0 9 This parameter cannot be programmed while the drive is running Minimum analogic input Sets the percent of analog input used to represent P32 If the minimum analog input equals minimum frequency no action is needed 75 If it is desired to adjust the analog input to equal P32 use 16 to adjust the Analog Input Minimum analog input to the desired level using P60 and then enter this value into P75 0 0 I Analog inversion can be accomplished by setting this value larger than P76 Do not adjust this parameter until setting P60 This parameter cannot be programmed while the drive is running Sets the percent of analog input used to represent P33 If the maximum analog input equals maximum frequency no action is needed If it is desired to adjust 76 the analog input to equal P33 use 16 to adjust analog input to the desired 4 Analog Input Maximum level using P60 and then enter this value into P76 0 0 150 0 100 0 100 Analog inversion be accomplished by setting this value smaller than P75 This parameter cannot be programmed while the drive is ru
92. olamente per il modello a velocit prestabilita 2 This parameter applies only to the Analog Signal Follower model 71 6 PROGRAM GROUP PARAMETER This group contains parameters whose values can be programmed Par Parameter Name Description Min Default Fan 30 Accel Time 1 Time for the drive to ramp from 0 0 Hz to P33 0 0 600 0s 10 0s 20 31 Time 1 Time for the drive to ramp from P33 to 0 0 Hz The rate is linear for any 0 0 600 0s 110 05 20 decrease in command frequency unless P53 Seconds 32 Minimum Frequency Lowest frequency that drive will output continuously 0 240 Hz 0 Hz 10 20 33 Maximum Frequency Highest frequency the drive will output 0 240 Hz 60 Hz 4 and TEC c 2 8 Handbook code 75802206 0204 Sheet 66 of 82 34 Stop Mode Select Determines stopping mode used by the drive when a stop is initiated 0 3 0 1 35 Base Frequency Set value to rated nameplate frequency of motor 10 240 Hz 50 Hz 50 380400 36 Base Voltage Set value to rated nameplate voltage of motor 230 460 V a dipende linea voltage 20V 37 Maximum Voltage Sets the highest voltage that the drive will output P37 must be greater than or 230 460 V Nominal Same value equal to P36 units input P 36 voltage Sets the boost voltage and redefines the Volts per Hz curve Settings 0 8 can 38 Boost Select provide increased
93. omplete this parameter will set itself to 0 57 Program Lock When set to 1 all parameters will be protected against change by unauthorized 0 1 0 0 personnel c 2 TECNAIR OLE CONTRO Orie Handbook code 75802206A 0204 Sheet 67 of 82 When 59 is set to a 1 this parameter will provide the drive frequency command This parameterwillchangethe frequencycommandin Real time using the up down arrow keys Maximum value is set in P33 0 0 240 0 58 Internal Frequency Once the desired command frequency is reached the Enter key must be Hz 60 Hz 60 pressed to store this value to EEPROM memory If the ESC key is used before the Enter key the frequency will return to the original value following the normal accel decel curve 59 Frequency Select Selects the source of the frequency command for the drive 0 1 0 0 60 Used to add or subtract any system offset to the analog input 50 0 4 Zero Offset m 0 0 1 This parameter cannot be programmed while the drive is running 50 0 96 0 0 240 0 61 Preset Frequency 0 The programmed value sets the frequency that the drive outputs when selected Hz 3 0 Hz 3 0 0 0 240 0 62 Preset Frequency 1 The programmed value sets the frequency that the drive outputs when selected Hz 20 0 Hz 20 0 63 0 0 240 0 2 Preset Frequency 2 The programmed value sets the frequency that the drive outputs when selected H
94. on must be kept in the surgical room with regard to the reference environment The value of the pressure difference between the room and the reference environment is measured by a differential pressure switch cfr Chap Installing the differential pressure switch in the room and then sent to the microprocessor with a 4 20mA signal Based on the pressure difference the microprocessor to correct it as necessary sends a tension signal 4 20 mA to the inverter The inverter receives the signal from the microprocessor and varies the feeding r gt Handbook code 75802206A 0204 TECNAIR LB Sheet 22 of 82 CONTROL CTIMEHTI HA ERS frequency of the air exaust fan in order to increase decrease the pressure of the surgical room inverter varies the feeding frequency of the fan in direct proportion to the tension signal from the microprocessor increasing decreasing tensions correspond to increasing decreasing frequencies and therefore pressures If you need to maintain the overpressure in the surgical room on starting the unit up the microprocessor forces a OVolt signal outgoing to the inverter of the air return fan This OVolt signal corresponds to the minimum Hz value set on the inverter and therefore to the minimum revolving speed of the fan which corresponds to an airflow extraction equalling about 10 of that supplied by the unit Afterwards every 15 seconds the microprocessor reads the mA signal coming back from the
95. onditioners OH series According to the necessary installation type different positionings of the humidity and temperature feelers are possible Tecnair LB has a standard solution but also other solutions can be possible r gt Handbook code 75802206A 0204 TECNAIR LB Sheet 44 of 82 OLE CONTRO AIR CI 3 17 1 1 Standard positioning Temperature and humidity feeler positioned in the suction section directly downstream the G4 filter This position has the advantage of being installed in the factory wired and tested with the unit The feelers also are well protected from possible damages The inconvenient is that it feels the average of the temperature and humidity of the various controlled environments If these have as often occurs endogenous thermal heat different for both entity and timing 1 a surgical room and a sterilization room that don t work simultaneously the shifts in the temperature and humidity are very high In case of a single surgical room the solution is valid acceptable in case of surgical room plus awakening room even if this is always cold since it doesn t have endogenous heat Therefore the installation in the auxiliary environments of the re heating water or electrical coils with automatic regulation is necessary This also obliges to insulate the suction ducts since otherwise the temperatures retrieved by the feelers could be different from the actual ones and is in difficulty when the d
96. oners must be disassembled by skilled technicians The following points must anyway be respected Switch off the air conditioner directly from its microprocessor and then open the door lock main switch of the unit Open the magnetotermic difefrential external switch to insulate the unit from the electric net Remove the electric conenction from the eletcric panel of the unit Remove the refrigerant charge if present from the unit according to the local Rules for the ozone protection Disconenct the frigorific lines fromthe unit Disconenct the hidraulic lines and the condenssate discharge The unit disposal is subject to the local Rules We suggest to contact a disassembling specialised Company The air conditioners are essentially made by aluminium copper and steel c 2 Handbook code 75802206A 0204 TECNAIR LB Sheet 46 of 82 CICE CONTROL ERS 4 FIRST START UP Before proceeding to the commissioning madae by Tecnair LB s technicians it is mandatory to follow the instructions indicated in the following sheet direct expansion units Surgical rooms and clean rooms with frigorific circuit OHA and OWA models or with chilled water coil models OHU and OWU Start up date Operator name and signature Start up location Client name and signature Test to be done before calling our technician for the start up The start up of the units with frigorific circuit OHA OWA forecasts that the unit are fed for at
97. ooling and reheat coil The assembly shall be sprinkled abundantly with the solution from the pre heating coil side until the solution comes out of the reheat coil out on the right hand operating compartment Afterwards the solution shall be sprinkled through the reheat coil until it comes out of the pre heating coil c On all the blades and levers of the by pass damper if present d On the internal walls of the compartment acting from the top e On the bottom bac r gt Handbook code 75802206A 0204 TE CNAIR LB Sheet 58 of 82 CICAE CATRO ERS Clean and disinfect the supply air fan turning the runner by hand until it is completely washed On the humidification system On all the pipelines running inside the compartment On the condensate discharge bac On the internal walls of the compartment acting from the top On the bottom bac Rinse abundantly the internal parts of the right hand operating compartment by atomising sterilised water with a hand atomiser The rinsing shall be followed by the operations listed at previous point m taking into account that between stage m4 And stage m5 The reheat coil needs to be rinsed it was washed previously in order to eliminate any accidental trace of solution from its surface Wash and rinse the components of the drops eliminator dismounted beforehand Mount the hot water heating coil back Mount the discharge adjusting damper back on the duct following the specific ins
98. oors stay open and therefore the microprocessor reduces to the minimum the extraction air flow 3 17 1 2 Fixed point regulation Temperature feeler positioned in the supply van immediately upstream of the air filter Humidity feeler in the re suction van in the same position as above mentioned The temperature feeler regulates the hot and cold coils of the units so to have a constant supply temperature both in summer and in winter i e 14 In this condition the relative humidity will be of nearly 9096 whilst the absolute one will be maintained by the microprocessor the same as the desired one in the environment excluding the endogenous humidity due to the presence of people The unit can be supplied without the re heating coil It is therefore necessary to install a hot water or electrical re heating coil complete with each one of the ducts to the controlled rooms This system allows a good regulation in each environment the only inconvenient being the necessity of re heating each room at the expenses of the installer The humidity tolerance is less good since the re suction feeler feels the average of the various humidity s in the various served environments 3 17 1 3 Combined Temperature and humidity feeler loose provided and installed in the room This allows an optimum control of the conditions of the main room and of the auxiliary ones by local re heating coils with regulation This type of installation has difficulties if the sys
99. or The clogging of the filter causes a pressure loss of the refrigerant and therefore a partial re vaporization with the presence of bubbles in led and a slightly noticeable loss in the temperature of the tube upstream and downstream of the filter 4 2 7 Compressor power input control The compressor power input must be measured by an amperometric wrench on each single phase on the electric line from the relevant contactor to the compressor and compared with the one indicated on the testing declaration of the unit 4 2 8 High pressure switch control Connect a pressure gauge with scale end 30 bar with the servicing valve 1 4 on the cock of the compressor and stop the fans of the air condenser At 24 bars the high pressure gauge must stop the compressor If at 25 bar the pressure switch has not intervened stop immediately the unit and replace it 4 2 9 Low presure switch control Connect a pressure gauge with scale end 8 bar with the servicing valve 1 4 and close the suction cock of the compressor At 1 bar the low pressure gauge must stop the compressor and start it up r gt Handbook code 75802206A 0204 TECNAIR LB Sheet 52 of 82 CONTROL ERS automatically when the pressure is 2 5bar If at 0 7 the pressure switch has not intervened stop immediately the unit and replace it NOTE On starting the compressor the low pressure switch is delayed by 180 seconds 4 2 10 Temperature of t
100. or rotation while decelerating to zero The other LED will illuminate indicating the commanded direction Start This function is only active when P46 Input Mode is set to 2 When active pressing this key initiates a start command Stop om Pressing the Stop key will cause the motor to stop using the selected stop mode Refer to the P34 Stop Mode parameter If the drive has stopped due to a fault pressing this key will clear the fault Important The Stop key is always active in all control modes 1 Display parameters are read only they cannot be programmed 2 Program parameters can be changed to fit your motor control requirements Following is an example of the programming steps required to change a Program Group parameter setting To program the value of a Program Group parameter enter the Program Group by pressing the ESCape key The Program Mode Indicator will illuminate cfr Figure 31 Press the Up Down keys until the desired parameter displays Press SELect The Program Mode Indicator flashes indicating that you can use the Up Down keys to change the parameter value cfr Figure 32 r gt Handbook code 75802206A 0204 TECNAIR LB Sheet 64 of 82 CORE ABE OF METS ERS Cambiare il valore del parametro selezionato con i tasti freccia su freccia git Tenendo continuamente premuto uno dei due tasti il valore aumenta o diminuisce pi velocemente When the desired value displays
101. p T3 bu 04 Output Power Displays the output power present at TB2 terminals U V amp W T1 T2 amp T3 KW 05 Bus Voltage Displays the DC Bus Voltage level iip 0 800 460 V 06 Frequency Command Displays the frequency that the drive is commanded to output 0 0 240 0 Hz 07 Active Fault Displays the coded active fault number 0 48 08 Heatsink Temperature Displays the temperature of the drive heatsink 69 150 C Displays the status of the drive in a binary coded format Important 0 Inactive 1 Active Bit 0 Running 09 Drive Status Bit 1 0000 1011 Bit2 Accel Bit3 Decel 10 Drive Type Used by Rockwell Automation field service personnel Numeric Value 11 Firmware Version Visualizza la versione firmware dell inverter Fixed Value B Input Status Hip ip T 0 and closed 1 state of the inputs to TB3 in binary coded 0000 1111 Input Bit 3 Bit 2 Bit 1 Bit 0 Mode Polarity TB3 6 TB3 8 TB3 5 7 Handbook code 75802206A 0204 TE CNAIR LB Sheet 65 of 82 AIR C TSESTICHS ER 0 Start Stop Run Reverse 1 Run Forward Stop Run Reverse 2 N P Stop N P 3 Run Forward Stop Run Reverse Accel 2 Decel 2 4 Run Forward Run Reverse 0 2 Accell 0 Positive Det 5 analog input Run Forward Coast to Rest Stop Run Reverse 0 TB3 control 6 1 Negative Run Forward 1 Key pad or Run Reverse analog input Comm 0 Anal Freq Select
102. r pump is functioning If outdoor air lt 1 the pump is always working in order to prevent the water of the heat recovery system from freezing Concerning how to fill the heat recovery system see the related paragraph in chapter nstallation 2 14 HUMIDIFICATION standard for OH series accessory for OW 2 14 1 Immersed electrodes humidifier The humidifier installed in Tecnair LB s air conditioners works by Joule effect by heating up the water comes to the boil and thus evaporates All the air conditioners for surgical rooms can be equipped with one standard or two accessory cylinders of similar or different size The electrodes humidifiers can modulate between 30 and 100 of their own capacity In same case the 30 is to much and the best solution is to install two of them in serie connected Based on the required steam quantity the microprocessor sets either one or both cylinders at work This way we obtain a rather precise regulation curve The humidifier is immersed electrodes box type Its structure guarantees low costs for routine cylinder maintenance The functioning of the humidifier is fully controlled by the microprocessor Depending on the relative humidity set point the control software controls the steam production and conductivity of the feeding water to the humidifier itself The microprocessor also discharges automatically the cylinder for water renewal The average life of a cylinder can vary from 500 to 1500
103. re the plant itself The total capacities of the circuits in litres are the following OH 62 138 36 litres OH 152 208 48 litres OH 242 308 67 litres r gt Handbook code 75802206A 0204 TECNAIR LB Sheet 40 of 82 CONTROL ERS 3 15 INSTALLING THE DIFFERENTIAL PRESSURE SWITCH THE ENVIRONMENT The differential pressure switch to install in the air conditioned environment is fundamental as it sends microprocessor the continuous reading of the ambient pressure and therefore it enable the microprocessor to execute the operations needed to maintain the right overpressure or depression in the controlled room The pressure switch used by Tecnair LB is DPT50 type has two air hydraulic inlets and a 5 pole terminal board To be connect by a schelded cable 3x0 35 AWG22 to the dedicat4ed terminal on the electri panel The connection cable is not provided by Tecnair The pressure difference between the room and the reference environment is measured through two small plastic transparent tubes with diameter 4 7 These two tubes are of standard length 2m the first one represents the positive pressure reference and must always be fixed to the air conditioned room by the free end the other one represents the negative transducer reference and must be positioned in an environment surrounding the room with natural pressure for example a passageway Aati piika Paqaliva i casi siia Ene ea
104. ready have an internal siphon and are two one for the condensate drainage and the other for humidifier outlet 3 6 HYDRAULIC CONNECTIONS WATER COOLED CONDENSERS As for the units fitted with frigorific circuit and water cooled condensers il W as the third character you shall also need to connect the feeding lines with the condensers The tubes diameter is indicated in the technical documentation the inlet in the right lower part of the condenser and outlet in the higher right part Anyhow the connections are shown on the following drawing r gt Handbook code 75802206A 0204 TECNAIR LB Sheet 32 of 82 CICE CONTROL ERS valvola condensatore piastre water cooled condenser ingresso refrigerante refrigerant inlet uscifa acqua water outlet lato refrigerante lato acqua refrigerant side waler side r ess C uscita refrigerante ngress acqua refrigerant outlet water inlet ngresso acqua waler inlet assostatica accessorio EER IN pressostatic valve laccessoryl If the feeding water comes from a well or a river two filters shall be installed in parallel one of them as backup with features conforming to the type of water used to prevent the condenser from getting clogged due to impurities in the water
105. roethylene etc or with powers or abrasive creams which might damage it If the unit is installed in the surgical room the cloths used for the cleaning shall be put into hermetically sealed containers and then be disposed of together with the septic waste of the hospital Connect the electricity again by turning the main shutter blocking switch on At this point the unit is ready to be set at work again gt Handbook code 75802206A 0204 TE CNAIR LB Sheet 59 of 82 CICAE CATRO ERS 6 MAINTENANCE 61 FILTER MAINTENANCE The filters must be replaced whenever the relevant alarm asks for cleaning The filter clogging can be foreseen by checking the frequency of the request for cleaning This way this operation can be executed during the normal unit stops so avoiding interrupting the unit functioning in vain It is important to remember that before carrying out this intervention the air conditioner must be cut off and a notice must be put on it saying that the unit is under maintenance To execute the cleaning the filters must be removed from the unit after cutting it off and after opening the back shutters Only the shutters indicated in the drawing enclosed to the unit shall be opened using the appropriate key During the designing of the air conditioners special care has been taken in eliminating all the sharp edges or surfaces inside the units themselves especially by those spots where the user needs to accede for routi
106. s longer than 15 mt are definitely not to be used 3 13 COMPLETING THE REFRIGERANT CHARGE The direct expansion air conditioners are shipped with only the necessary pressurization charge The condensers are shipped without charge The additional total charge of an air conditioning plant with direct expansion units to be matched with a remote condensing unit letter A third position in the coding is the sum of four factors Internal unit Discharge line Liquid line Condenser Conversely with direct expansion units to be matched to a remote condensing unit letter third position in the coding the addends are the following Corresponding pipeline inside the air conditioner Suction pipeline 7 Handbook code 75802206A 0204 TECNAIR LB Sheet 39 of 82 CATRO OTC ERS Liquid line Remote condensing unit not supplied by Tecnair please address to the related technical documentation In both cases the replenishment due to the corresponding pipeline inside the air conditioner is null as this is usually pre charged during the testing To know the quantity of refrigerant to replenish for the condenser model you just need to draw the volume from the relevant Tecnair documentation and multiply it by 0 3 Then multiply the outcome by the specific weight of the refrigerant 1 02 kgp m thus approximable to one Concerning the cooling pipelines the replenishment is determined based on the diameter of t
107. ssible to guaranty a raise in the temperature of at least four degrees so to reduce the humidity and avoid the risk of freezing the humidity which accumulates in the pre filter We suggest that this system is made with plain tubes because the possible fins are dirtied too quickly by the fresh air which in that point is not yet filtered We empathise that for temperatures lower than 20 C the possibility to install the air conditioner outdoor is excluded Version L units low air flow temperature minimum 22 C maximum 38 C humidity lower 10 maximum 100 Version H units high air flow temperature minimum 14 C maximum 30 C humidity lower 10 maximum 100 r gt Handbook code 75802206A 0204 TECNAIR LB Sheet 9 of 82 CICAE CATRO ERS 1 6 2 2 Operating limits for air cooled condensers 1 6 2 2 1 Minimum operating limit minimum outdoor air temperature Axial or radial air condenser with switch and speed variator minimum external air temperature 20 Axial or radial air condenser with switch and without speed variator The speed variator can be installed in the internal electric panel of the unit minimum external air temperature 25 Axial or radial air condenser without switch and without speed variator This solution is not in conformity with the safety standards since the operator is not certain that the condenser is not remotely switched on whilst he is doing main
108. stop so damaging it at the start up and or preventing the regular start up and causing a high pressure block Of course the valves shall be mounted vertically so as to respect the flow direction of the refrigerant The second one shall be installed on the liquid refrigerant outlet from the condenser as close as possible to this one and in vertical position this valve forbides the refrigerant migration back to the condenser when the installation is switched off and the ambient temperature is very low r gt Handbook code 75802206A 0204 TE CNAIR LB Sheet 35 of 82 CICAE CATRO ERS 3 10 2 Lines connecting unit with a remote condensing unit RETURN SUCTION LINE It runs from the valve on the direct expansion coil output and therefore from the unit output to the remote condensing unit Its working temperature is approx 5 it needs to be insulated to prevent condensation LIQUID LINE It runs from the output valve on the remote condensing unit to the input valve of the air conditioner Its working temperature is approx 40 and does not require any thermal insulation barring the units that must work in winter too with temperatures below zero 3 11 LINES LAYOUT FOR FRIGORIFIC CONNECTIONS The correct route of the lines is fundamental to the good functioning of the units and particular care shall be taken in choosing and laying down the compressor s supply pipeline especially with long lines In particular Q The dis
109. t is indispensable to execute the following instructions before opening the unit and carrying out any cleaning operation Make sure that the electricity has been disconnected Make sure that all live parts compressor in the driving compartment expulsion air fan and supply air fan have come to a complete stop that is have ceased moving All the electric feeding circuits of the equipment have been opened These instructions refer exclusively to the cleaning of the air conditioner Therefore we take for granted that maintenance cleaning and or disinfections of the other parts of the plant inside of the ducts vents and or air diffusers to the environment grille for air return from the room germinal lamps humidifier feeding water treatment system condensate discharge system etc have been carried out within the deadlines and following the procedures indicated by the relevant constructors and by the installer that has executed the system In fact the execution of the only cleaning washing and disinfections operations even if executed observing the instructions contained in this handbook is not enough to guarantee the necessary sterilisation of the whole system Even if they are equipped with internal filters Tecnair LB s air conditioners series have been designed to guarantee the environment air conditioning not its sterilisation In fact to obtain the required sterilisation in the environment the installer shall mount at its
110. t is oil free 6 5 ELECTRIC HEATER MAINTENANCE It is enough to check it for cleanliness and regular Ampere absorption according to the provisions indicated in the relevant data sheet If the electric heater is modulating type check occasionally the modulator for good functioning which can be made by verifying the proper behaviour of the unit during the heating by visualising the 0 10V tension outgoing to the modulator from the microprocessor on the related window See Use handbook r gt Handbook code 75802206A 0204 TECNAIR LB Sheet 61 of 82 CONTROL ERS 7 160 55 The air conditioner of the series produced Tecnair come standard equipped with an inverter on the supply fan and on the expulsion for the control of the air capacity necessary to guaranty the necessary air change in the environment and for the control of the overpressure depression in the room in regards to a reference environment Also a compressor is provided with inverter for the modulation of the frigorific capacity The inverters mounted on the air conditioner of the H series are essentially the two described underneath The main difference being that the supportable capacity of the connected charge 7 1 SERVICE INSTRUCTIONS INVERTER 160 SSC 7 1 1 NOTE This document does not substitute the user manual supplied by the manufacturer of the inverter delivered with the air conditioner TECNAIR LB recommends
111. ted to select an air cooled condenser with the following deltaT between fresh air entering project forecasted external temperature and condensing temperature For maximum outdoor temperatures up to 30 deltaT 17 For maximum outdoor temperatures up to 35 C deltaT 15 For maximum outdoor temperatures up to 40 deltaT 13 For maximum outdoor temperatures up to 46 DeltaT 10 For maximum outdoor temperatures over 46 Ask our offices to select a unit with another refrigerant R134 r gt Handbook code 75802206A 0204 TECNAIR LB Sheet 8 of 82 CICAE CATRO ERS 1 6 1 3 Operating limits for internal air conditioners with built in water cooled condenser Water condensers without pressostatic valve Entering water temperature between 25 and 40 Water condensers with pressostatic valve Entering water temperature between 7 and 40 C 1 6 1 4 Air conditioners with chilled water coils The temperature and humidity limits of the air to be treated external air mixture plus re circulation entering into the unit are valid for operating after the first transitory span with a nominal air flow and prevalence of 800 Pa and for entering water temperatures to the coil of 7 C We empathise that for external winter temperatures regularly lower than 5 it is necessary to install the fresh air duct a system for the preheating of the fresh air controlled
112. tem serves a second room with a lot of endogenous airflow and maybe even not simultaneously to the first room where the feeler is installed i e a surgical room and a sterilization room The temperature and humidity feeler must be positioned at a specific height min 1 7 m so not to be damaged accidentally by shocks and it is necessary to care for it during the sterilization process of the room r gt Handbook code 75802206A 0204 TECNAIR LB Sheet 45 of 82 CONTROL ERS feeler must be connected to the uP of the unit by a cable which must travel through ducts 3 17 1 4 Temperature and humidity feeler standard provided and installed in the re suction duct of the room The characteristics of this installation are the same as those in paragraph 2 15 1 3 The advantage is that the feeler is protected form shocks The disadvantage is that it becomes difficult to control and clean In this case it becomes necessary to request duct type feelers 3 17 2 Clean room air conditioners OW series The temperature and humidity feeler can be installed inside the unit only in case of total re circulation or total fresh air since the possible mix doesn t allow to measure the conditions of the room and therefore the relative control Otherwise they must be installed by the installer on the wall of the room or in the re suction ducts 3 18 D LJ D oO D DISASSEMBLE AND DISPOSAL Tecnair LB air conditi
113. temperature Check for blocked or non operating fan drive is over heating Reduce motor load current 32 EEPROM Fault The EEPROM has invalid data Reset using P56 Set tol and cycle power 33 Max Retries Fault Max Retries Fault The drive failed to reset within the Repair the system fault number of retries set in P50 36 Incompatible Fault Incompatible communication module installed Verify compatibility of communication module e Check the wiring between the drive and the motor 38 Phase U Fault A phase fault has Been deteeted between Check the motor for a grounded phase Check that the drive and the motor in phase U ground is not connected to U c 2 TECNAIR ue Handbook code 75802206A 0204 Sheet 70 of 82 phase to ground fault has been detected between Check the wiring between the drive and the motor 39 Phase V Fault 5 the drive and the motor in phase V Check the motor for a grounded phase A phase to ground fault has been detected between Check the wiring between the drive and the motor 40 Phase W Fault 5 the drive and the motor in phase W Check the motor for a grounded phase Excessive current has been detected between these Check the motor and external wiring to the drive 41 UV Short Fault gt two drive output terminals output terminals for a shorted condition 42 UW Short Fault Excessive curre
114. tenance work is therefore mandatory that the switch installed away from the condenser and inside the building is of lockable type minimum outdoor air temperature 40 1 6 2 2 2 Maximum operating limit maximum outdoor air temperature It is suggested to select an air cooled condenser with the following deltaT between fresh air entering project forecasted external temperature and condensing temperature For maximum outdoor temperatures up to 30 deltaT 17 For maximum outdoor temperatures up to 35 C deltaT 15 For maximum outdoor temperatures up to 40 deltaT 13 For maximum outdoor temperatures up to 46 DeltaT 10 For maximum outdoor temperatures over 46 Ask our offices to select a unit with another refrigerant R134 1 6 2 3 Operating limits for internal air conditioners with built in water cooled condenser Water condensers without pressostatic valve Entering water temperature between 25 and 40 Water condensers with pressostatic valve Entering water temperature between 7 and 40 C 1 6 2 4 Air conditioners with chilled water coils The temperature and humidity limits of the air to be treated external air mixture plus re circulation entering into the unit are valid for operating after the first transitory span with a nominal air flow and prevalence of 800 Pa and for entering water temperatures to the coil of 7 C r gt Handbook code 7
115. tervention on the unit shall be carried out only by competent skilled personnel We recommend not executing any kind of operation if you have not enough knowledge of the unit working principle Before executing any operation cut the tension out Legend of the failure diagram FAILURE FUNCTION CAUSE REMEDY r gt Handbook code 75802206A 0204 TECNAIR LB Sheet 72 of 82 CAURE ABE OF METH ERS 8 1 E AIR CONDITIONERS COOLING CIRCUIT PROBLEMS HIGH PRESSURE BLOCK AIR COND TOO LOW TOOHIGHINLET FUNCTIONING EXCESS AIRFLOW TO i i AIR i i CHARGED CONDENSER TEMPERATURE i COOLING CIRCUIT CHECK FOR TAKE THE WATER ELIMINATE CHECK CHECK THERMAL CHECK AND POSSIBLE TEMPERATURE POSSIBLE CONDENSATION PROTECTIONS AND BRING IT WITHIN CLOGGING ON EXPULS AIR CONTROL SYSTEM ABSORPTION THE DUE LIMITS THE COIL RECIRCUL FOR GOOD WORKING CLEAN CONDENSING COIL DEFECTUOUS PRESSOSTATIC VALVE EXCESS CHARGED COOLING CIRCUIT DIRTY i i TOO HIGH INLET CONDENSER ii WATER i TEMPERATURE LACK OF WATER CHECK HYDRAULIC CHECK GOOD CHECK AND BRING CHECK AND CIRCUIT PUMPS FUNCTIONING AND WITHIN THE DUE RESTORE THE AND joints ADJUSTMENT LIMITS ORIGINAL CONDITIONS r gt Handbook code 75802206A 0204 TECNAIR LB Sheet 73 of 82 TRC ATE CIIMEHTI CHN ERS LOW PRESSURE BLOCK LACK OF COMPRESSION
116. tomatically cancelled if the materials are repaired or modified or anyhow completed e g air conditioners supplied without electrical board or the like The above warranty and supply conditions shall be valid provided that the Customer has fulfilled all of his contract obligations with main reference to the payment terms It is understood that no employee or representative of TECNAIR LB or sales representative or service centre or the like is authorized to grant any derogations to the above mentioned warranty terms WARNING Before operating any unit the contents of this handbook shall be carefully read and fully understood 1 4 APPLICATION OF THE PRESENT MANUAL The two series OH and OW have much in common The most obvious difference is that the OH series is provided with the supply fan and the suction and exhaust one and therefore can control both the over and under pressure in reference to the surrounding areas where It can therefore be used even in areas where toxic substances are present therefore re circulation in room is not acceptable and where all the air supplied must be then sucked and expelled outside Contrarily the OW clean room series which can control only areas where toxic substances are not present and therefore can work with re circulation is provided only with the supply fans Another important difference is that the OH surgical room air conditioners are standard complete with all thermodynamic controls for the mo
117. tructions provided by the installer that has laid the system Mount the new filters on the unit Clean the washer of the operating compartment shutters Make sure that all the internal parts are completely dry Mount the operating compartment shutters back taking care not to damage the washers Connect the electricity by turning the main shutter blocking switch on Now the unit is ready to be set at work again 5 4 3 Procedure for cleanind the external framework of the air conditioners If the unit is installed inside the surgical room or in a communicating room anaesthesia room recovery room post operation monitoring room etc its external framework shall be cleaned whenever the operating compartments are washed and disinfected unless otherwise instructed by the Physician in charge of the Ward Conversely if the unit is installed a technical not communicating with the surgical room it may be cleaned every time the framework presents any trace of dust and or grease mark The framework shall be cleaned as described below Disconnect the electricity by turning the main shutter blocking switch off Put a notice on the switch saying that the unit is under maintenance Clean the framework with an alcoholic solution or equivalent commercial one by sprinkling it on the surface and then remove it with a clean cloth by wiping firmly For no reason the framework shall be cleaned with solvents acetone benzene petrol trichlo
118. uid gauge If bubbles are not present it means that the charge is correct pay attention that this control is not excluding that the charge is abundant if there are bubbles it means that the charge is not complete or there is a leakage in this case identify the leak and repair it Under normal conditions the indicator with chromatic change must be in green color if humidity is present in the circuit the indicator tends to become yellow in this case it means that humidity has been entered in the circuit during operations and therefore the refrigerant and the filter drier must be changed 4 2 2 Evaporating pressure control To make this control a manometer with scale end 8bar must be connected with the relevant service valve 74 on the suction valve of the compressor check that the compressor valve is open Tecnair units are studied to have very large heat exchangers and therefore very high evaporating pressures about 3 6 with input air temperature to the evaporator of 24 evaporating pressure higher than the indicated cannot be caused by a blink on the frigorific circuit but only by a too high condensing pressure A too low evaporating pressure can be generated by several different causes see diagnosis and failure repair low pressure switch intervention 4 2 3 Condensing pressure control Connect a manometer with scale end 30 bar with the relevant service valve 74 on the discharge valve of the compressor chec
119. upply and suction ducts towards and from the controlled room The necessity of sound absorbers on the air expulsion and fresh air suction ducts must be studied according to the urban context of the installation Noise absorbers are selected according to the following parameters Air flow quantity LWS in octave band of the fans declared by Tecnair in the offer or in the Order conformation in relationship to the exact projected working conditions LPS sound pressure level which must be guaranteed in the controlled environment normally 35 dB A Maximum pressure drop caused by the absorber normally 80 Pa The sound absorbers must have the noise absorbent panels un inflammable veloglass coverings or anyway a non destructible material and damped against humidity and superficial protection in drilled galvanised or stainless panels As a pure indication we hypotised the use of straight sound dampers with length of 2000 mm c 2 TECNAIR LB Handbook code 75802206A 0204 Sheet 30 of 82 3 INSTALLATION 3 1 TRANSPORT During site handling the unit shall be lifted and transported by a lift truck The forks shall be inserted as shown in the appropriate drawing handed over to the forwarder failing the lift truck pass two ropes under the pallet on which the air conditioner rests Moreover use rigid spacing bars for the lifting to make sure that these ropes cannot tread on the framework This oper
120. z 30 0 Hz 30 0 64 0 0 240 0 2 Preset Frequency 3 The programmed value sets the frequency that the drive outputs when elected Hz 40 0 Hz 40 0 0 0 240 0 65 Preset Frequency 4 The programmed value sets the frequency that the drive outputs when selected Hz 45 0 Hz 45 0 0 0 240 0 66 Preset Frequency 5 The programmed value sets the frequency that the drive outputs when selected Hz 50 0 Hz 50 0 67 0 0 240 0 2 Preset Frequency 6 The programmed value sets the frequency that the drive outputs when selected Hz 55 0 Hz 55 0 68 0 0 240 0 2 Preset Frequency 7 The programmed value sets the frequency that the drive outputs when selected Hz 60 0 Hz 60 0 69 Accel Time 2 Time for the drive to ramp from 0 0 Hz to P33 Maximum Frequency 0 0 600 0s 20s 20 0 Time for the drive to ramp from P33 Max Frequency to 0 0 Hz The rate is 70 Decel Time 2 linear for any decrease in command frequency unless P53 to a value other than 0 0 600 0 208 20 0 0 Minimum deceleration time must be set based on the applied motor size 71 IR Compensation The programmed value adds a voltage to the output based on the torque 0 150 50 50 current This parameter compensates for the inherent slip in an induction motor ATTENTION Hazard of personal injury or equipment damage exists due to 72 Slip Compensation unpredictable changes in motor speed Do not use P72 and P83 to disable PI 0 0 5 0 Hz 2 0 Hz 2 0 control while the drive is running Disable PI contr

Download Pdf Manuals

image

Related Search

Related Contents

Kollmann - RIDGID Professional Tools  基本ガイド - Panasonic  Samsung GT-P7310/M32 Brugervejledning  Pure Guardian H1510 Use and Care Manual  Cables Direct EX-103  Bintec-elmeg CAB-N-20m    Safety Curtains  Service Manual - Genie Industries  Self Directed Learning User Guide for the FOODcents for Aboriginal  