ViaLite Alarm Concentrator User Manual (LAC-HB-5)
Contents
1. Position 8 The remote data stream is forwarded together with local alarm information in an RS232 electrical format to external equipment e g a PC or other system controller in response to a poll command on the serial data input via the D Sub connector at the rear of the 19 rack shelf The remote module status 15 also made available in parallel form via the D Sub connector This allows the system to be integrated into redundantly switched network The Alarm Concentrator modules are bi directional so that the status of remote modules can be determined at either end of cross site connection This greatly aids the commissioning and fault location during installation Alarm Concentrator Alarm Concentrator Transceiver LAC 1 Transceiver LAC 5 2 5 4 20 Lo 23 23 ae 28 aE TE 2 2 2 GE ne aL Parallel output of remote status Parallel output of remote status A Cross site Fibre Optic Cable Serial RS232 Rx Lei Serial RS232 data output S Se data output Alarm inputs from Alarm inputs from local modules H local modules 2 1 Module Operation 2 1 1 Installation The Alarm Concentrator module is available in plug in module form for use in PPM s ViaLite 19 Rack Case or in standalone configuration with Converter Sleeve
2. If the module is being used in conjunction with the 19 Rack Case the Alarm Concentrator must be inserted into position 8 immediately to the left of the power supplies This as shown in silkscreen on the backplane and engraved onto the rear panel The module is hot pluggable so can be inserted with power supplied to the rack case without affecting signal modules already installed Optical connections between local and remote modules are made at the rear of the module Using two clean FC APC cross site cables link the input ports I of each module to the output ports O of the mating module 2 2 Fibre Optic Cable amp Connectors 2 2 1 Care of fibre optic connectors Modern optical connectors offer very high levels of performance reliability and repeatability However they are more sensitive to damage and contamination than electrical connectors In order to maintain full performance from your fibre optic link system it is necessary to take care to protect the connectors from damage and to keep them clean The light carrying core of a singlemode optical fibre is 8 um in diameter and in a mating connector pair the two cores must be aligned to better than lum in order to minimise insertion loss The optical connectors used in PPM s systems maintain their performance even after hundreds of matings as long as they are kept clean Dirt or contamination may result in the core being obscured or misaligned and this in turn results in hi
3. Consult local PPM office Alarm Conc LED stays Remote module not powered Power up remote module RED Optical connectors absent dirty Connect two clean undamaged or damaged optical fibres between modules Optical loss between local and Consult optical budget section in remote location too high handbook Status LEDs lights up RED Remote module faulty or absent Remedy module fault at remote location appropriately The ViaLite range of equipment is precision engineered and calibrated for optimum performance and accuracy before dispatch However in the event of any problems or queries arising about the equipment please contact PPM or your local agent 18 6 Product Warranty The Company guarantees its products and will maintain them for period of three years from the date of shipment at no cost to the customer Extended warranty options are available at the time of purchase Please note that the customer is responsible for shipping costs to return the unit to PPM The Company or its agents will maintain its products in full working order and make all necessary adjustments and parts replacements during the Company s normal working hours provided that the Customer will pay at the rates currently charged by the Company for any replacements made necessary by accident misuse neglect wilful act or default or any cause other than normal use Claims must be made promptly and during the guarantee period IMPORTANT
4. Please contact both your selling agent and PPM prior to returning any goods for Warranty or Non Warranty repairs Goods will not be accepted without valid Goods Return Number GRN 19 ViaLite ALARM CONCENTRATOR HANDBOOK LAC HB ISSUE 5 CR2874 O PULSE POWER amp MEASUREMENT LTD 2011 PART OF THIS DOCUMENT MAY BE REPRODUCED OR TRANSMITTED IN ANY FORM WITHOUT PRIOR WRITTEN PERMISSION PPM LTD 65 SHRIVENHAM HUNDRED BUSINESS PARK SWINDON SN6 8TY UK TEL 44 1793 784389 FAX 44 1793 784391 EMAIL INFO PPM CO UK WEBSITE WWW PPM CO UK
5. for remote PSU failure If either the Main or the Reserve remote power supply modules fail the local Alarm Concentrator will register PSU alarm output It is possible to determine which PSU has failed by observation of the status LEDs on the local Alarm Concentrator or by polling either Alarm Concentrator module using the RS232 feature 13 3 4 Serial Communication The status of the Local and Remote modules as well as the Alarm Concentrator modules themselves can be ascertained by polling either Alarm Concentrator module in system pair This can be done using hyperterminal on a PC or by using any proprietary RS232 controller The connection to the RS232 port is made on rear panel 15way D Sub connector CONN8 immediately behind the Alarm Concentrator Module Pinout details are shown in section 3 3 The part number of the serial data lead required to interface with this port is 73635 This lead can be obtained from your local PPM representative 3 4 1 Protocol The protocol used for communication with the Alarm Concentrator is as follows Parity None Number of Stop Bits 1 Number of Data Bits 8 Data Rate 9600 baud 3 42 Command Set The Alarm Concentrator module can be polled for information using simple ASCII characters The table below lists valid commands Command Function Poll Status This will return an ASCII serial data stream in the following format LOC1 OK or FAIL LOC2 OK or FAIL LOC3 OK o
6. the connectors from damage and to keep them clean The cable connectors should always be cleaned before they are used even if they have been protected by dust caps When the fibre optic cables are not connected it is essential that the cable and module connectors are protected by the dust caps provided with the system Failure to do so may result in damage to the fibre ends which are critical to the system performance Please refer to section 2 2 for fibre optic cable handling and cleaning instructions 2 Setting up and Understanding the Product Please read fully document Lxx HB for information on installing your ViaLite equipment before commissioning your RF link system PPM s ViaLite Alarm Concentrator Transceiver module allows users to monitor the status of remotely located fibre optic link modules The status may be monitored e visually via front panel LEDs over a serial data output and e over a parallel data output The Alarm Concentrator Transceiver module occupies position 8 in the ViaLite 19 rack shelf It concentrates all alarms from neighbouring modules within the same rack and converts them into serial data stream for transmission over optical fibre to an identical Alarm Concentrator Transceiver module at the remote location Here the data stream is de multiplexed to provide visual indication of the status of remote modules via front panel LEDs
7. A ViaLite ViaLite Alarm Concentrator User Manual LAC HB 5 CR2874 14 04 11 C Pulse Power amp Measurement Ltd 65 Shrivenham Hundred Business Park Watchfield Swindon Wi ay UK DENE Tel 44 0 1793 784389 Fax 44 0 1793 784391 Email sales ppm co uk www vialite Instrument Care and Safety Information Please read the whole of this section before using your ViaLite product It contains important safety information and will enable you to get the most out of your link Electrical Safety The ViaLite 19 Rack Case power supply units are Safety Class 1 products having metal case that is directly connected to earth via the power supply cable When operating the equipment note the following e Hazardous voltages exist within the equipment There are no user serviceable parts inside and the covers should only be removed by suitably qualified personnel e The equipment does not have an isolating switch on the mains inlets Equipment must be installed within easy reach of a clearly labelled dual pole mains isolation switch e Make sure that only fuses of the required rated current and of the specified type anti surge quick blow etc are used for replacement Optical Safety The ViaLite RF Alarm Concentrator modules contain optical sources operating at 1300nm nominal These devices are rated at under IEC825 1 Safety of Laser Products Part 1 First Edition 1993 as CLASS 1 r
8. OR TECHNICAL DATA 15 AA Seiser 15 4 2 Optical Budget Caleulations mme 15 4 3 Dimensions EE 16 4 4 A SE 17 5 MAINTENANCE AND FAULT FINDING GUIDE ses 18 6 PRODUCT WARRANTY Luse 19 1 Introduction 1 1 ViaLite Alarm Concentrator PPM s ViaLite Alarm Concentrator provides a high reliability transparent cross site connection for the transport of system alarm information for ViaLite communications equipment Using optical fibre information about alarm status from remote location up to 20km away can be relayed to the local module whilst overcoming problems due to path loss and electro magnetic interference etc This enables PPM ViaLite equipment to be fully integrated into an Operations Maintenance and Control environment or redundantly switched network ViaLite ViaLite ViaLite ViaLite ViaLite ViaLite ViaLite T Band L Band L Band L Band L Band 950 2150MHz 950 2150MHz 950 2150MHz 950 2150MHz 950 2150MHz 950 2150MHz Optical Tx Optical Tx Optical Tx Optical Rx PPM s ViaLite Alarm Concentrator offers the following key advantages e Visual indication of remote module status e g laser fail low optical carrier etc e Parallel output of remote module status for integratio
9. adiation emitting devices When operating the equipment note the following e Never look into the end of an optical fibre directly or by reflection either with the naked eye or through an optical instrument e Never leave equipment with radiating bare fibres accessible always cap the connectors e Do not remove equipment covers when operating e Details of optical connections to the units compatible fibre types and care instructions can be found in the ViaLite system handbook Please read this section before using the link Adjustment maintenance and repair of the equipment should only be carried out by suitably qualified personnel For more information on the ViaLite range of products please refer to the ViaLite system handbook Lxx HB TABLE OF CONTENTS 1 INTRODUCTION sassanidene 5 1 1 ViaLite Alarm Concentrator meme 5 2 ses neo 6 1 3 Care of fibre optic Connectors sem 7 2 SETTING UP AND UNDERSTANDING THE 8 Zi Operations E 9 2 2 Fibre Optic Cable amp Connectors mure 10 3 USING THE ALARM CONCENTRATOR MODULE ss 13 3 1 Connecting the Module mme 13 3 2 Front Panel Indicators ereeeseserernsseseeesesesesnssereessesesesnsseseessesesesnsseseesseseseensesseessesssrensensesseesre 13 3 3 Parallel Alarm Outputs essseseernsseesseersssesstesessssesseessssesseesenssseesseesnsssessesnsessesseesssssessesnsese 13 3 4 Serial Communication EE 14 4 VIALITE ALARM CONCENTRAT
10. e Power Supply Module 2 Power and Voltage Consumption lt 4W at 12VDC 0 5VDC Operating Conditions Operating Temperature 0 C to 40 C Storage Temperature Optical Characteristics 40 C to 70 C Output Power 20dBm nominal Wavelength 1310 20nm Fibre Singlemode 9 125 Corning SMF28 or equivalent Optical Connector FC APC Narrow key gt 60dB return loss Suhner FCPC Z M A601 Optical Path Length Om to 20km for 1300nm single mode fibre Optical Power Budget 10dB Typical fibre losses Fibre 0 4dB km Connectors 0 5dB max 4 2 Optical Budget Calculations The maximum optical loss between local and remote modules to guarantee correct operation of the Alarm Concentrator link is 8dB The table below indicates typical losses for optical components that are CLEAN AND IN GOOD CONDITION The total loss of all the optical components in the system should not exceed 8dB Optical cable 0 4dB km FC APC Connectors 0 5dB per bulkhead connection 15 4 3 Module Dimensions Viatite A Modul 5 Alarm Concentrator en E TRANSCEIVER LAC 1 Figure 1 Plug in Module 16 EU 4 4 4 Alarm Connections The circuit below shows how the alarm output should be configured for all types of ViaLite signal module The switch to the left of t
11. gh insertion loss and poor link performance The following precautions should be taken to maintain the performance of your link e The cable connectors should always be cleaned before they are used even if they have been protected by dust caps e When the fibre optic cables are not connected it is essential that the cable and module connectors are protected by the dust caps provided with the system 2 2 2 Connector and Cable Types All ViaLite modules use singlemode 8um 125um fibre terminated with FC APC optical connectors Cross site cables are available in standard 3mm diameter and heavy duty 8mm diameter variants FC APC is an industry standard for angle polished optical connectors and must not be confused with standard FC PC connectors The two connector types are not interchangeable and mating one with the other will damage both the cross site interconnect and the module 2 2 3 Connecting and Disconnecting The cable connectors should be cleaned before each and every connection see 2 2 4 To connect FC APC optical connectors align the centre ferrule on the cable connector with the female receptacle in the module There is a lug on the side of the ferrule which must aligned to the gap in the receptacle When they are in alignment push the plug gently home and finger tighten the knurled collet onto the receptacle See Figure 1 below To disconnect FC APC connectors unscrew the knurled collet on the plug and gently withdra
12. he dotted line is internal to the module The circuitry to the right of the dotted line is provided by the system user In the presence of an alarm condition the module will act as high impedance node and will NOT sink current This is fail safe system in that an alarm condition will be raised when module is not present This is an important factor when commissioning link management systems as blank module positions will register module faults Internal to External to module module VEXT Pull Up Resistor Alarm Ground This circuitry is also provided by the Redundancy Switch module and the Alarm Concentrator module When either of these modules are used the alarm outputs can not be considered VOLT FREE This is because the Redundancy Switch module and the Alarm Concentrator modules use the same module alarm outputs to detect whether a unit has failed When these modules are used a voltage of between 5V and 12V may be present on the Alarm output line when the module is in the failed mode When the module is working correctly the voltage on the Alarm output line will be OV 1 0 0 If true VOLT FREE contacts are required please consult PPM Maximum current 50mA Maximum voltage 15V 17 5 Maintenance and Fault Finding Guide Refer to the following table that gives list of commonly encountered problems and suggested solutions Possible Causes Power LED lights up RED Internal fault
13. ion between the module and another remote Alarm Concentrator module 3 2 Front Panel Indicators The transmitter has 11 front panel LEDS to indicate status Power LED Alarm Conc LED Status LEDs 9 OFF Unit is Off Unit is Off Unit is Off or No valid ACM link GREEN Unit is OK ACM Link OK Remote Module OK RED Internal Fault No valid ACM link Remote Module Fault 3 3 Parallel Alarm Outputs With the Alarm Concentrator module fitted all REMOTE module alarms are available on 15way D Sub connector at module position 8 on the rear panel This connector can be used to take alarm information to the local units for remote end switching using the Vialite LRS n redundancy switch See LRS HB for details The open collector alarm outputs sink current in the absence of an alarm condition When an alarm occurs the output goes into a high impedance state Refer to section 4 4 for details of the alarm interface Backplane Alarm Concentrator Module 15way Connector 8 Pin Connections Pin Function Pin Function Number Number 1 Serial RS232 Data Output 9 Serial RS232 Data Input 2 Remote Module 1 Alarm 10 Remote Module 4 Alarm 3 Remote Module 2 Alarm 11 Remote Module 5 Alarm 4 Remote Module 3 Alarm 12 Remote Module 6 Alarm 5 Alarm Concentrator Alarm 13 Remote Module 7 Alarm 6 V 14 Remote PSU Alarm 7 Remote PSU Alarm 15 GND 8 GND There is only one alarm output
14. n into redundantly switched network e Serial output of local and remote module status for interface to PC etc via RS232 e Operation from 0m to gt 20km Complementary PPM ViaLite Products e Signal modules for RF GPS L Band 70 140MHz Broadband 2kHz 1500MHz and 10MHz 3GHz etc e 19 Rack Case e Redundancy Switch Module for fully automated 1 1 redundant operation e Dual redundant power supplies for maximum availability 1 2 Part Numbers This handbook covers the following modules Part Number Transceiver Plug In Shielded Module Refer to the ViaLite System Handbook for further details on the following ViaLite items Part Number Description LRKI1S Chassis for desktop or 19 rack installation Accommodates up to 8 plug in modules and 2 mains power supplies LRK2S Chassis for 19 rack installation Accommodates up to 8 plug in modules and 2 mains power supplies LPS M Main Power Supply plug in for LRK1S or LRK2S LPS R Reserve Power Supply plug in for LRK1S or LRK2S LRS 10 30 40 Redundancy Switch Module F6R1 x FC APC Patchlead 2 8mm jacket Length defined in metres by x Im 2m 5m 10m 1 3 Care of fibre optic connectors Fibre optic connectors are more sensitive to damage and contamination than electrical connectors In order to maintain full performance from your fibre optic link system it is necessary to take care to protect
15. r FAIL LOC4 OK or FAIL LOC5 OK or FAIL LOC6 OK or FAIL LOC7 OK or FAIL LOC PSU1 OK or FAIL LOC PSU2 OK or FAIL LAC OK or FAIL OK or FAIL REM2 OK or FAIL REM3 OK or FAIL OK or FAIL REMS OK or FAIL REM6 OK or FAIL REM7 OK or FAIL REM PSUI or FAIL REM PSU2 OK or FAIL W Software Issue 14 4 ViaLite Alarm 4 1 Specifications Parameter oncentrator Technical Data Value Serial Data Input Output 9600 Baud RS232 8N1 via 15 way D type Female on 19 Rack Case or Converter Sleeve Parallel Data Input Compatible with open collector alarm outputs via 19 Rack Case backplane PCB from local modules Parallel Data Status Outputs Remote 1 Remote 2 Remote 3 Remote 4 Remote 5 Remote 6 Remote 7 Remote PSU Alarm Concentrator Front Panel Indicator LEDs Power Alarm Concentrator local supply voltage Remote Status LEDs Alarm Concentrator Confirms that data is being received from remote Alarm Concentrator Module 1 Alarm status of remote module I Module 2 Alarm status of remote module 2 Module 3 Alarm status of remote module 3 Module 4 Alarm status of remote module 4 Module 5 Alarm status of remote module 5 Module 6 Alarm status of remote module 6 Module 7 Alarm status of remote module 7 PSU1 Alarm status of remote Power Supply Module 1 PSU2 Alarm status of remot
16. sidue from the receptacle 11 Important Notes is flammable Follow appropriate precautions and local guide lines when handling and storing IPA can be harmful if spilt on skin Use appropriate protection when handling e It should only be necessary to clean the female receptacles on the modules if problems are being experienced e Never inspect an optical fibre or connector with the naked eye or an instrument unless you are convinced that there is no optical radiation being emitted by the fibre Remove all power sources to all modules and completely disconnect the optical fibres 2 25 Minimum Bend Radius Because the optical fibre is made of glass it is important not to subject it to a tight bend radius For this reason the fibre has a minimum bend radius MBR specification beyond which the cable cannot be bent without excessive loss or damage occurring MBR specifications for PPM fibre are given in the ViaLite System Handbook Lxx HB 12 3 Using the Alarm Concentrator Module 3 1 Connecting the Module Install as described in section 2 1 Immediately after power up the module will perform self test during which the LEDs will illuminate in set pattern Assuming another Alarm Concentrator is connected via the rear panel optical connectors the module should be operational within 5 seconds If the Alarm Conc LED on the front panel is still illuminated red at this time then there is not a valid connect
17. w the plug Replace the dustcaps on both the receptacle and the cable connector 10 Figure 1 showing connector with dust cap removed b showing alignment of the lug on the side of the ferrule which must match the gap in the receptacle shroud before gently pushing the plug home and finger tighten the knurled collet nut onto the threaded receptacle a b 2 2 4 Care and Cleaning The cable optical connectors should be cleaned before each and every use even where they have been protected with dust caps It should only be necessary to clean the female receptacles on the modules if problems are being experienced Cleaning items required e Lint free fibre cleaning tissues normal cosmetic tissues produce dust and are not acceptable Reagent grade Iso Propyl Alcohol e duster or FILTERED compressed air line Cable Connector Cleaning e Dampen a patch of cleaning tissue with IPA and clean all surfaces of the plug ferrule e Using a dry cleaning tissue dry the ferrule and polish the end face e Using the air duster blow away all residue from the end of the connector Module Female Receptacle Cleaning only recommended if problems are being experienced e Twist a cleaning tissue to form a stiff probe and moisten with IPA Gently push the probe into the receptacle and twist around several times to dislodge any dirt e Repeat the above process with a dry tissue Using the air duster blow away all re
Download Pdf Manuals
Related Search
Related Contents
Roller Dock - Presentes.pt APPENDIX - Index of Atlantis Land A02-WRA2-11B User's Manual POWERMAX - Visonic 取扱説明書 EQUIPO PURIFICADOR DE AGUA NT-2W DE USO GENEVA - Thuasne Deutschland GmbH 586ITOX Revision B+ Samsung E2230 Korisničko uputstvo NBF...Q - ALLWEILER Service Portal Copyright © All rights reserved.